Brosur LV Cable - New
Brosur LV Cable - New
FRC 1 CORE
(Copper Conductor, Mica Glass Tape, XLPE Insulated, Low Smoke Free Halogen Sheathed)
Standard Specification : SS 299, BS 6387 & IEC 60331
Construction Data
Copper conductor Special Features on Request:
• UV Resistance Nom Overall Cable
Cross Section Diameter Weight
• Flame Retardant Cat. A, B, C
Mica Glass Tape
• Flame Retardant Non Category Area approx. approx.
XLPE Insulation
• Heat Resistance
mm² mm kg/km
• Anti Termite
Orange LSFH Outer sheath • Anti Rodent 1.5 6.9 59
• Low Smoke Zero Halagen 2.5 7.5 75
4 7.9 93
Note: 6 8.1 110
Conductor Shape 10 9.0 155
1.5 - 10 sqmm supplied in solid (re) or non 16 10.0 215
compacted circular stranded (rm) conductor
shape 25 11.7 315
16 sqmm supplied in non compacted circular 35 12.8 405
stranded (rm) conductor shape 50 14.5 535
25 - 800 sqmm supplied in non compacted
70 16.5 745
circular stranded (rm) or compacted circular
Application: stranded (cm) conductor shape 95 18.5 1,005
For wiring of fire resistance safety circuits, Standard Packing 120 20.5 1,245
such as fire alarm system, emergency 1.5 - 10 sqmm supplied in coil @ 100 meters 150 22.5 1,530
lighting and power, public address and 16 - 400 sqmm supplied in wooden drum @ 185 25.0 1,895
emergency voice communication systems in 1000 meters 240 28.0 2,465
500 - 800 sqmm supplied in wooden drum
highrise building, control and instrumenta- 300 31.0 3,075
on available length
tion services in industrial, commercial and Length Tolerance per drum ± 2% 400 35.0 3,935
residential complexes. 500 39.5 5,025
630 43.0 6,375
800 49.0 8,185
Electrical Data
Conductor Inductance Current - Carrying Capacity at 30 °C *
Short
Nom DC AC Circuit current
Cross Resistance Resistance in air in ground at 1 second
Section at 20 °C at 90 °C (mH/km) Max. Max. Max.
Area Max. Max. (A) (A) (kA)
mm² (Ω/km) (Ω/km)
1.5 12.1 15.429 0.478 35 43 0.22
2.5 7.41 9.449 0.441 43 58 0.37
4 4.61 5.787 0.409 57 76 0.59
6 3.08 3.927 0.387 72 95 0.89
10 1.83 2.334 0.356 98 128 1.49
16 1.15 1.466 0.333 132 169 2.38
25 0.727 0.927 0.317 187 220 3.71
35 0.524 0.668 0.303 217 265 5.20
50 0.387 0.494 0.290 263 316 7.43
70 0.268 0.342 0.280 331 385 10.40
95 0.193 0.347 0.272 408 465 14.11
120 0.153 0.196 0.268 474 531 17.83
150 0.124 0.160 0.267 550 597 22.29
185 0.0991 0.128 0.265 633 680 27.49
240 0.0754 0.099 0.260 750 790 35.66
300 0.0601 0.080 0.255 871 901 44.57
400 0.0470 0.064 0.254 1019 1032 59.43
500 0.0366 0.052 0.251 1182 1180 74.29
630 0.0283 0.043 0.247 1241 1233 93.60
800 0.0221 0.036 0.244 1295 1287 118.86
* Further information about rating factor for certain cable arrangement can be found on supplementary technical information
FIRE RESISTANCE CABLES FIRE RESISTANCE CABLES
N2XY 2 x (1.5 - 300) mm2 0.6/1 kV N2XY 3 x (1.5 - 300) mm2 0.6/1 kV
Cu / MGT / XLPE / LSFH Cu / MGT / XLPE / LSFH
FRC 3 CORE
FRC 2 CORE
(Copper Conductor, Mica Glass Tape, XLPE Insulated, Low Smoke Free Halogen Sheathed) (Copper Conductor, Mica Glass Tape, XLPE Insulated, Low Smoke Free Halogen Sheathed)
Standard Specification : SS 299, BS 6387 & IEC 60331 Standard Specification : SS 299, BS 6387 & IEC 60331
* Further information about rating factor for certain cable arrangement can be found on supplementary technical information * Further information about rating factor for certain cable arrangement can be found on supplementary technical information
FIRE RESISTANCE CABLES N2XY 1 x (1.5 - 500) mm2 0.6/1 kV
N2XY 4 x (1.5 - 300) mm2 0.6/1 kV Cu / XLPE / PVC
Cu / MGT / XLPE / LSFH (Copper Conductor, XLPE Insulated, PVC Sheathed)
FRC 4 CORE
N2XY 1 CORE
Standard Specification : SPLN 43 - 6 & IEC 60502 - 1
(Copper Conductor, Mica Glass Tape, XLPE Insulated, Low Smoke Free Halogen Sheathed)
Standard Specification : SS 299, BS 6387 & IEC 60331
Construction Data
Copper conductor
Special Features on Request:
Construction Data • Fire Resistance Nom Overall Cable
Cross Section Diameter Weight
Special Features on Request: XLPE Insulation • Oil Resistance
• UV Resistance Nom Overall Cable • UV Resistance Area approx. approx.
Cross Section Diameter Weight Black PVC Outer sheath • Flame Retardant Cat. A, B, C
• Flame Retardant Cat. A, B, C mm² mm kg/km
• Flame Retardant Non Category • Flame Retardant Non Category
Area approx. approx. 1.5 5.8 47
Copper conductor • Heat Resistance • Heat Resistance
mm² mm kg/km • Anti Termite 2.5 6.2 59
• Anti Termite
Mica Glass Tape • Anti Rodent 1.5 16.5 325 • Anti Rodent 4 6.8 77
XLPE Insulation • Low Smoke Zero Halagen • Low Smoke Zero Halagen
2.5 17.5 390 6 7.3 98
LSFH Inner sheath
4 19.0 485 Note: 10 8.2 145
Orange LSFH Outer sheath Note:
6 20.5 605 16 9.3 205
Conductor Shape
Conductor Shape
10 23.0 840 1.5 - 10 sqmm supplied in solid (re) or non 25 11.0 305
1.5 - 10 sqmm supplied in solid (re) or non
compacted circular stranded (rm) conductor 35 12.1 405
compacted circular stranded (rm) conductor 16 25.5 1,125 shape
shape 50 14.0 525
25 29.0 1,605 16 sqmm supplied in non compacted circular
16 sqmm supplied in non compacted circular 70 16.0 730
stranded (rm) conductor shape
stranded (rm) conductor shape 35 32.0 2,075
Application: 95 18.0 1,005
25 - 300 sqmm supplied in non compacted 25 - 500 sqmm supplied in non compacted
50 36.0 2,630
circular stranded (rm) or compacted circular Power cable : Indoors, cable trunking, out- circular stranded (rm) or compacted circular 120 20.0 1,250
70 41.0 3,585 stranded (cm) conductor shape 150 22.0 1,525
Application: stranded (cm) conductor shape doors and buried in the ground, for power
For wiring of fire resistance safety circuits, Standard Packing 95 44.5 4,700 stations, industry and switchgear as well Standard Packing 185 24.0 1,885
such as fire alarm system, emergency 1.5 - 70 sqmm supplied in wooden drum @ 120 50.0 5,850 as for urban supply networks, if mechanical 1.5 - 10 sqmm supplied in coil @ 100 meters 240 27.5 2,475
lighting and power, public address and 1000 meters damage is unlikely. 16 - 300 sqmm supplied in wooden drum @
150 55.5 7,145 300 30.0 3,045
95 - 300 sqmm supplied in wooden drum 1000 meters
emergency voice communication systems in 185 61.0 8,850 400 34.0 3,930
on available length 400 - 500 sqmm supplied in wooden drum
highrise building, control and instrumenta- on available length 500 38.0 4,960
Length Tolerance per drum ± 2% 240 67.5 11,315
tion services in industrial, commercial and Length Tolerance per drum ± 2%
300 74.0 13,870
residential complexes.
Electrical Data
Conductor Inductance
Electrical Data Current - Carrying Capacity at 30 °C *
Short
Nom DC AC Circuit current
Conductor Inductance Current - Carrying Cross Resistance Resistance at 1 second
Capacity at Short Section at 20 °C at 90 °C (mH/km) in air in ground Max.
Nom DC AC Circuit curent Area Max. Max.
30 °C * Max. Max. (kA)
Cross Resistance Resistance at 1 second mm² (Ω/km) (Ω/km) (A) (A)
Section at 20 °C at 90 °C (mH/km) in air in ground Max.
Area Max. Max. Max. Max. 1.5 12.1 15.429 0.452 35 43 0.22
(kA)
mm² (Ω/km) (Ω/km) (A) (A) 2.5 7.41 9.449 0.417 43 58 0.37
1.5 12.1 15.429 0.315 23 29 0.22 4 4.61 5.787 0.387 57 76 0.59
2.5 7.41 9.449 0.293 32 38 0.37 6 3.08 3.927 0.364 72 95 0.89
4 4.61 5.878 0.275 41 49 0.59 10 1.83 2.334 0.336 98 128 1.49
6 3.08 3.927 0.263 52 60 0.89 16 1.15 1.466 0.315 132 169 2.38
10 1.83 2.334 0.248 71 97 1.49 25 0.727 0.927 0.302 187 220 3.71
16 1.15 1.467 0.238 96 108 2.38 35 0.524 0.668 0.289 217 265 5.20
25 0.727 0.927 0.240 130 141 3.71 50 0.387 0.494 0.279 263 316 7.43
35 0.524 0.669 0.233 159 170 5.20 70 0.268 0.342 0.270 331 385 10.40
50 0.387 0.494 0.232 193 201 7.43 95 0.193 0.347 0.263 408 465 14.11
70 0.268 0.342 0.229 245 249 10.40 120 0.153 0.196 0.259 474 531 17.83
95 0.193 0.247 0.224 302 299 14.11 150 0.124 0.160 0.259 550 597 22.29
120 0.153 0.196 0.223 349 340 17.83 185 0.0991 0.128 0.258 633 680 27.49
150 0.124 0.160 0.224 400 381 22.29 240 0.0754 0.099 0.253 750 790 35.66
185 0.0991 0.128 0.225 464 434 27.49 300 0.0601 0.080 0.249 871 901 44.57
240 0.0754 0.099 0.223 552 506 35.66 400 0.0470 0.064 0.249 1019 1032 59.43
300 0.0601 0.080 0.221 640 586 44.57 500 0.0366 0.052 0.246 1188 1180 74.29
* Further information about rating factor for certain cable arrangement can be found on supplementary technical information * Further information about rating factor for certain cable arrangement can be found on supplementary technical information
N2XY 2 x (1.5 - 300) mm2 0.6/1 kV N2XY 3 x (1.5 - 300) mm2 0.6/1 kV
Cu / XLPE / PVC Cu / XLPE / PVC
(Copper Conductor, XLPE Insulated, PVC Sheathed) (Copper Conductor, XLPE Insulated, PVC Sheathed)
N2XY 3 CORE
N2XY 2 CORE
Standard Specification : SPLN 43 - 6 & IEC 60502 - 1 Standard Specification : SPLN 43 - 6 & IEC 60502 - 1
Special Features on Request: Construction Data Special Features on Request: Construction Data
• Fire Resistance • Fire Resistance
• Oil Resistance Nom Overall Cable • Oil Resistance Nom Overall Cable
Copper conductor
• UV Resistance Cross Section Diameter Weight Copper conductor
• UV Resistance Cross Section Diameter Weight
• Flame Retardant Cat. A, B, C • Flame Retardant Cat. A, B, C
XLPE Insulation Area approx. approx. Area approx. approx.
• Flame Retardant Non Category • Flame Retardant Non Category
PVC Inner sheath XLPE Insulation
• Heat Resistance mm² mm kg/km • Heat Resistance mm² mm kg/km
PVC Inner sheath
Black PVC Outer sheath • Anti Termite 1.5 11.5 170 • Anti Termite 1.5 12.0 190
• Anti Rodent Black PVC Outer sheath • Anti Rodent
• Low Smoke Zero Halagen 2.5 12.5 205 • Low Smoke Zero Halagen 2.5 13.0 235
4 14.0 260 4 14.5 305
Note: 6 15.0 320 Note: 6 15.5 380
Conductor Shape 10 17.0 445 Conductor Shape 10 17.5 545
1.5 - 10 sqmm supplied in solid (re) or non 1.5 - 10 sqmm supplied in solid (re) or non
compacted circular stranded (rm) conductor 16 19.0 605 compacted circular stranded (rm) conductor 16 20.0 755
shape 25 22.0 885 shape 25 23.5 1,120
16 sqmm supplied in non compacted circular 16 sqmm supplied in non compacted circular
35 24.5 1,145 35 26.0 1,465
stranded (rm) conductor shape stranded (rm) conductor shape
Application: 25 - 300 sqmm supplied in non compacted 50 27.5 1,480 Application: 25 - 300 sqmm supplied in non compacted 50 29.0 1,905
Power cable : Indoors, cable trunking, out- circular stranded (rm) or compacted circular 70 31.5 2,025 Power cable : Indoors, cable trunking, out- circular stranded (rm) or compacted circular 70 34.0 2,670
stranded (cm) conductor shape stranded (cm) conductor shape
doors and buried in the ground, for power 95 36.0 2,745 doors and buried in the ground, for power 95 38.5 3,580
Standard Packing Standard Packing
stations, industry and switchgear as well 120 40.0 3,415 stations, industry and switchgear as well 120 42.5 4,465
1.5 - 150 sqmm supplied in coil @ 100 1.5 - 120 sqmm supplied in coil @ 100
as for urban supply networks, if mechanical as for urban supply networks, if mechanical
meters 150 44.0 4,180 meters 150 47.5 5,535
damage is unlikely. 185 - 300 sqmm supplied in wooden drum damage is unlikely. 150 - 300 sqmm supplied in wooden drum
185 49.0 5,210 185 53.0 6,840
@ 1000 meters @ 1000 meters
Length Tolerance per drum ± 2% 240 55.0 6,730 Length Tolerance per drum ± 2% 240 59.0 8,865
300 61.0 8,335 300 66.0 10,995
* Further information about rating factor for certain cable arrangement can be found on supplementary technical information * Further information about rating factor for certain cable arrangement can be found on supplementary technical information
N2XY 4 x (1.5 - 300) mm2 0.6/1 kV NA2XY 1 x (10 - 800) mm2 0.6/1 kV
Cu / XLPE / PVC AL / XLPE / PVC
(Copper Conductor, XLPE Insulated, PVC Sheathed) (Aluminium Conductor, XLPE Insulated, PVC Sheathed)
NA2XY 1 CORE
N2XY 4 CORE
Standard Specification : SPLN 43 - 6 & IEC 60502 - 1 Standard Specification : SPLN 43 - 6 & IEC 60502 - 1
Aluminium conductor
Special Features on Request: Construction Data
Special Features on Request: Construction Data • Oil Resistance
• Fire Resistance XLPE Insulation • UV Resistance Nom Overall Cable
• Oil Resistance Nom Overall Cable • Flame Retardant Cat. A, B, C Cross Section Diameter Weight
• UV Resistance Cross Section Diameter Weight Black PVC Outer sheath • Flame Retardant Non Category
Copper conductor • Flame Retardant Cat. A, B, C • Heat Resistance Area approx. approx.
Area approx. approx.
• Flame Retardant Non Category • Anti Termite mm² mm kg/km
XLPE Insulation • Heat Resistance mm² mm kg/km • Anti Rodent
10 8.3 83
PVC Inner sheath • Anti Termite 1.5 13.0 220 • Low Smoke Zero Halagen
• Anti Rodent 16 9.4 111
Black PVC Outer sheath
• Low Smoke Zero Halagen 2.5 14.0 275
25 11.1 155
4 15.5 360 Note:
35 12.2 195
Note: 6 17.0 460 Conductor Shape
50 14.0 255
Conductor Shape 10 19.0 665 10 - 16 sqmm supplied in solid (re) or non
1.5 - 10 sqmm supplied in solid (re) or non compacted circular stranded (rm) conductor 70 16.0 335
compacted circular stranded (rm) conductor 16 21.5 935 shape 95 18.5 440
shape 25 25.5 1,395 25 - 800 sqmm supplied in non compacted
120 20.0 530
16 sqmm supplied in non compacted circular circular stranded (rm) or compacted circular
35 28.5 1,840
stranded (rm) conductor shape Application: stranded (cm) conductor shape 150 22.0 640
Application: 25 - 35 sqmm supplied in non compacted 50 29.5 2,240
Power cable : Indoors, cable trunking, out- Standard Packing 185 24.5 785
Power cable : Indoors, cable trunking, out- circular stranded (rm) or compacted circular 70 34.5 3,125 doors and buried in the ground, for power 10 - 800 sqmm supplied in wooden drum @ 240 28.0 1,015
stranded (cm) conductor shape
doors and buried in the ground, for power 95 39.0 4,205 1000 meters
50 - 400 sqmm supplied in non compacted stations, industry and switchgear as well 300 30.0 1,230
stations, industry and switchgear as well Length Tolerance per drum ± 2%
circular stranded (rm) or compacted circular 120 43.0 5,305 as for urban supply networks, if mechanical
stranded (cm) or sector shaped stranded
400 34.5 1,600
as for urban supply networks, if mechanical damage is unlikely.
(sm) conductor
150 48.0 6,445
damage is unlikely. 500 38.0 1,940
185 53.5 8,045
Standard Packing 630 43.0 2,480
1.5 - 70 sqmm supplied in wooden drum @ 240 59.5 10,430
800 47.0 3,050
1000 meters 300 65.0 12,945
95 - 300 sqmm supplied in wooden drum
on available length
Length Tolerance per drum ± 2%
Electrical Data
Conductor Inductance
Electrical Data Current - Carrying Capacity at 30 °C *
Short
Nom DC AC Circuit current
Conductor Inductance Current - Carrying Cross Resistance Resistance at 1 second
Capacity at Short Section at 20 °C at 90 °C (mH/km) in air in ground Max.
Nom DC AC Circuit current Area Max. Max. Max. Max. (kA)
30 °C *
Cross Resistance Resistance at 1 second mm² (Ω/km) (Ω/km) (A) (A)
Section at 20 °C at 90 °C in air in ground Max.
Area Max. Max. Max. Max. 10 3.08 3.949 0.336 72 95 0.98
(mH/km) (kA)
mm² (Ω/km) (Ω/km) (A) (A) 16 1.91 2.449 0.311 102 131 1.57
1.5 12.1 15.429 0.315 23 29 0.22 25 1.20 1.539 0.302 137 170 2.45
2.5 7.41 9.449 0.293 32 38 0.37 35 0.868 1.113 0.289 168 205 3.43
4 4.61 5.878 0.275 41 49 0.59 50 0.641 0.822 0.279 204 242 4.91
6 3.08 3.927 0.263 52 60 0.89 70 0.443 0.568 0.269 257 301 6.87
10 1.83 2.334 0.248 71 97 1.49 95 0.320 0.411 0.263 316 360 9.32
16 1.15 1.467 0.238 96 108 2.38 120 0.253 0.325 0.260 368 421 11.77
25 0.727 0.927 0.240 130 141 3.71 150 0.206 0.265 0.258 421 463 14.72
35 0.524 0.669 0.233 159 170 5.20 185 0.164 0.212 0.258 488 525 18.15
50 0.387 0.494 0.232 193 201 7.43 240 0.125 0.162 0.253 583 615 23.55
70 0.268 0.342 0.229 245 249 10.40 300 0.100 0.130 0.249 675 700 29.44
95 0.193 0.247 0.224 302 299 14.11 400 0.0778 0.103 0.245 790 800 39.25
120 0.153 0.196 0.223 349 340 17.83 500 0.0605 0.081 0.245 921 915 49.06
150 0.124 0.160 0.224 400 381 22.29 630 0.0469 0.065 0.243 942 936 61.82
185 0.0991 0.128 0.225 464 434 27.49 800 0.0367 0.053 0.241 1074 1068 78.50
240 0.0754 0.099 0.223 552 506 35.66
* Further information about rating factor for certain cable arrangement can be found on supplementary technical information
300 0.0601 0.080 0.221 640 585 44.57
* Further information about rating factor for certain cable arrangement can be found on supplementary technical information
NA2XY 2 x (10 - 300) mm2 0.6/1 kV NA2XY 3 x (10 - 300) mm2 0.6/1 kV
AL / XLPE / PVC AL / XLPE / PVC
(Aluminium Conductor, XLPE Insulated, PVC Sheathed) (Aluminium Conductor, XLPE Insulated, PVC Sheathed)
NA2XY 2 CORE
NA2XY 3 CORE
Standard Specification : SPLN 43 - 6 & IEC 60502 - 1 Standard Specification : SPLN 43 - 6 & IEC 60502 - 1
Special Features on Request: Construction Data Special Features on Request: Construction Data
• Oil Resistance • Oil Resistance
• UV Resistance Nom Overall Cable • UV Resistance Nom Overall Cable
Aluminium conductor
• Flame Retardant Cat. A, B, C Cross Section Diameter Weight • Flame Retardant Cat. A, B, C Cross Section Diameter Weight
Aluminium conductor
• Flame Retardant Non Category • Flame Retardant Non Category
XLPE Insulation • Heat Resistance Area approx. approx. • Heat Resistance Area approx. approx.
PVC Inner sheath XLPE Insulation
• Anti Termite mm² mm kg/km • Anti Termite mm² mm kg/km
• Anti Rodent PVC Inner sheath • Anti Rodent
Black PVC Outer sheath 10 17.0 325 10 17.5 365
• Low Smoke Zero Halagen • Low Smoke Zero Halagen
Black PVC Outer sheath
16 19.0 425 16 20.0 480
25 22.5 595 25 24.0 680
Note: Note:
35 25.0 735 35 26.0 845
Conductor Shape Conductor Shape
50 28.5 965 50 30.0 1,110
10 - 16 sqmm supplied in solid (re) or non 10 - 16 sqmm supplied in solid (re) or non
compacted circular stranded (rm) conductor 70 32.0 1,255 compacted circular stranded (rm) conductor 70 35.0 1,500
shape 95 36.5 1,635 shape 95 39.0 1,895
25 - 300 sqmm supplied in non compacted 25 - 300 sqmm supplied in non compacted
circular stranded (rm) or compacted circular
120 40.0 1,985 circular stranded (rm) or compacted circular
120 43.0 2,305
Application: stranded (cm) conductor shape 150 44.5 2,415 Application: stranded (cm) conductor shape 150 48.0 2,870
Power cable : Indoors, cable trunking, out- Standard Packing 185 50.0 3,015 Power cable : Indoors, cable trunking, out- Standard Packing 185 53.0 3,530
doors and buried in the ground, for power 10 - 185 sqmm supplied in wooden drum @ doors and buried in the ground, for power 10 - 185 sqmm supplied in wooden drum @
240 56.0 3,815 240 60.0 4,525
1000 meters 1000 meters
stations, industry and switchgear as well 300 62.0 4,715 stations, industry and switchgear as well 300 66.0 5,525
240 - 300 sqmm supplied in wooden drum on 240 - 300 sqmm supplied in wooden drum on
as for urban supply networks, if mechanical available length as for urban supply networks, if mechanical available length
damage is unlikely. Length Tolerance per drum ± 2% damage is unlikely. Length Tolerance per drum ± 2%
* Further information about rating factor for certain cable arrangement can be found on supplementary technical information * Further information about rating factor for certain cable arrangement can be found on supplementary technical information
NA2XY 4 x (10 - 300) mm2 0.6/1 kV NAYA 10 - 400 mm2 450 /750 V
AL / XLPE / PVC AL / PVC
(Aluminium Conductor, XLPE Insulated, PVC Sheathed) (Aluminium Conductor, PVC Insulated)
NA2XY 4 CORE
NAYA
Standard Specification : SPLN 43 - 6 & IEC 60502 - 1 Standard Specification : IEC 60227 - 1
Special Features on Request: Construction Data Special Features on Request: Construction Data
• Oil Resistance • Oil Resistance
• UV Resistance Nom Overall Cable Aluminium conductor
• Flame Retardant Cat. A, B, C Nom Overall Cable
• Flame Retardant Cat. A, B, C Cross Section Diameter Weight • Flame Retardant Non Category Cross Section Diameter Weight
Aluminium conductor
• Flame Retardant Non Category
• Heat Resistance Area approx. approx. Area approx. approx.
XLPE Insulation PVC Insulation
• Anti Termite mm² mm kg/km mm² mm kg/km
PVC Inner sheath
• Anti Rodent Note:
10 19.0 425 10 6.1 55
Black PVC Outer sheath
• Low Smoke Zero Halagen Conductor Shape
16 22.0 565 16 7.2 79
10 - 400 sqmm supplied in non compacted
25 26.0 810 circular stranded (rm) conductor shape 25 8.9 120
Note:
35 28.5 1,015 Standard Packing 35 10.0 155
Conductor Shape 10 - 400 sqmm supplied in wooden drum @
50 29.5 1,055 50 12.0 215
10 - 16 sqmm supplied in solid (re) or non 1000 meters
compacted circular stranded (rm) conductor 70 34.5 1,435 Length Tolerance per drum ± 2%
70 14.0 290
shape 95 39.0 1,820 95 16.0 385
25 - 35 sqmm supplied in non compacted
circular stranded (rm) or compacted circular
120 43.0 2,240 120 17.5 465
Application: stranded (cm) conductor shape 150 48.0 2,725 Application: 150 20.0 575
50 - 400 sqmm supplied in non compacted
Power cable : Indoors, cable trunking, out- 185 53.5 3,365 For building wire installed in donduit in dry 185 22.0 725
circular stranded (rm) or compacted circular
doors and buried in the ground, for power stranded (cm) or sector shaped stranded 240 59.5 4,280 location, sometimes can be used as ground- 240 25.0 935
stations, industry and switchgear as well (sm) conductor ing conductor, inherently flame retardant in
300 65.0 5,205 300 28.0 1,160
as for urban supply networks, if mechanical Standard Packing compliance with IEC 60332 - 1
400 32.0 1,505
damage is unlikely. 10 - 120 sqmm supplied in wooden drum @
1000 meters
150 - 300 sqmm supplied in wooden drum on
available length
Length Tolerance per drum ± 2%
Electrical Data
Conductor Insulation Inductance Current - Carrying
Electrical Data Capacity at Short
Nom DC AC Insulation Circuit current
30 °C *
Conductor Inductance Current - Carrying Cross Resistance Resistance Resistance at 1 second
Capacity at Short Section at 20 °C at 70 °C at 20 °C in pipe in air Max.
Nom DC AC Circuit current Area Max. Max. Min. Max. Max. (kA)
30 °C * (mH/km)
Cross Resistance Resistance at 1 second mm² (Ω/km) (Ω/km) (M.Ω.km) (A) (A)
Section at 20 °C at 90 °C in air in ground Max.
Area Max. Max. Max. Max. 10 3.08 3.701 0.0065 0.274 35 57 1.08
(mH/km) (kA)
mm² (Ω/km) (Ω/km) (A) (A) 16 1.91 2.295 0.0050 0.258 48 77 1.72
10 3.08 3.949 0.248 52 60 0.98 25 1.20 1.442 0.0050 0.257 65 101 2.69
16 1.91 2.449 0.236 75 84 1.57 35 0.868 1.043 0.0040 0.249 80 123 3.77
25 1.20 1.539 0.242 110 110 2.45
50 0.641 0.771 0.0045 0.248 103 154 5.39
35 0.868 1.113 0.234 123 132 3.43
70 0.443 0.533 0.0035 0.239 129 191 7.54
50 0.641 0.822 0.232 149 156 4.91
95 0.320 0.385 0.0035 0.239 162 226 10.24
70 0.443 0.568 0.229 189 193 6.87
120 0.253 0.305 0.0032 0.235 184 269 12.93
95 0.320 0.411 0.224 233 232 9.32
150 0.206 0.249 0.0032 0.235 - 305 16.16
120 0.253 0.325 0.223 271 268 11.77
185 0.1640 0.199 0.0032 0.235 - 348 19.93
150 0.206 0.265 0.225 310 296 14.72
240 0.1250 0.152 0.0032 0.233 - 410 25.86
185 0.164 0.212 0.225 359 336 18.15
300 0.100 0.123 0.0030 0.232 - 473 32.33
240 0.125 0.162 0.223 429 393 23.55
400 0.0778 0.097 0.0028 0.229 - 566 43.10
300 0.100 0.130 0.222 496 447 29.44
* Further information about rating factor for certain cable arrangement can be found on supplementary technical information
* Further information about rating factor for certain cable arrangement can be found on supplementary technical information
NAYY 1 x (10 - 800) mm2 0.6/1 kV NAYY 2 x (10 - 300) mm2 0.6/1 kV
AL / PVC / PVC AL / PVC / PVC
(Aluminium Conductor, PVC Insulated, PVC Sheathed) (Aluminium Conductor, PVC Insulated, PVC Sheathed)
NAYY 1 CORE
NAYY 2 CORE
Standard Specification : SPLN 43 - 1 & IEC 60502 - 1 Standard Specification : SPLN 43 - 1 & IEC 60502 - 1
Special Features on Request: Construction Data Special Features on Request: Construction Data
Aluminium conductor • Oil Resistance • Oil Resistance
• UV Resistance Nom Overall Cable Aluminium conductor • UV Resistance Nom Overall Cable
PVC Insulation • Flame Retardant Cat. A, B, C Cross Section Diameter Weight • Flame Retardant Cat. A, B, C Cross Section Diameter Weight
• Flame Retardant Non Category • Flame Retardant Non Category
PVC Insulation
Black PVC Outer sheath • Heat Resistance Area approx. approx. • Heat Resistance Area approx. approx.
PVC Inner sheath
• Anti Termite mm² mm kg/km • Anti Termite mm² mm kg/km
• Anti Rodent • Anti Rodent
10 9.0 105 Black PVC Outer sheath 10 18.0 390
• Low Smoke Zero Halagen • Low Smoke Zero Halagen
16 10.0 135 16 20.0 495
25 12.0 190 25 23.5 690
Note: Note:
35 13.0 230 35 26.0 845
Conductor Shape Conductor Shape
50 15.0 305 50 30.0 1,115
10 - 16 sqmm supplied in solid (re) or non 10 - 16 sqmm supplied in solid (re) or non
compacted circular stranded (rm) conductor 70 17.0 395 compacted circular stranded (rm) conductor 70 33.5 1,420
shape 95 19.5 515 shape 95 38.0 1,840
25 - 800 sqmm supplied in non compacted 25 - 300 sqmm supplied in non compacted
120 21.0 610 120 41.5 2,180
circular stranded (rm) or compacted circular circular stranded (rm) or compacted circular
Application: stranded (cm) conductor shape 150 23.0 740 Application: stranded (cm) conductor shape 150 45.5 2,640
Power cable : Indoors, cable trunking, out- Standard Packing 185 25.5 915 Power cable : Indoors, cable trunking, out- Standard Packing 185 51.5 3,355
doors and buried in the ground, for power 10 - 800 sqmm supplied in wooden drum @ 240 29.0 1,160 doors and buried in the ground, for power 10 - 150 sqmm supplied in wooden drum @
240 58.0 4,255
1000 meters 1000 meters
stations, industry and switchgear as well 300 32.0 1,425 stations, industry and switchgear as well
Length Tolerance per drum ± 2% 185 - 300 sqmm supplied in wooden drum on 300 64.0 5,245
as for urban supply networks, if mechanical as for urban supply networks, if mechanical available length
400 36.0 1,825
damage is unlikely. damage is unlikely. Length Tolerance per drum ± 2%
500 39.5 2,200
630 44.0 2,760
800 48.0 3,335
NAYY 4 CORE
Standard Specification : SPLN 43 - 1 & IEC 60502 - 1 Standard Specification : SPLN 43 - 1 & IEC 60502 - 1
Special Features on Request: Construction Data Special Features on Request: Construction Data
• Oil Resistance • Oil Resistance
• UV Resistance Nom Overall Cable • UV Resistance Nom Overall Cable
• Flame Retardant Cat. A, B, C Cross Section Diameter Weight Aluminium conductor • Flame Retardant Cat. A, B, C Cross Section Diameter Weight
Aluminium conductor
• Flame Retardant Non Category • Flame Retardant Non Category
• Heat Resistance Area approx. approx. • Heat Resistance Area approx. approx.
PVC Insulation
PVC Insulation
• Anti Termite mm² mm kg/km PVC Inner sheath
• Anti Termite mm² mm kg/km
PVC Inner sheath
• Anti Rodent • Anti Rodent
10 19.0 445 10 21.0 520
Black PVC Outer sheath • Low Smoke Zero Halagen Black PVC Outer sheath • Low Smoke Zero Halagen
16 21.5 570 16 23.0 680
25 25.0 795 25 27.5 960
Note: Note:
35 27.5 980 35 30.0 1,185
Conductor Shape Conductor Shape
50 32.0 1,300 50 32.0 1,325
10 - 16 sqmm supplied in solid (re) or non 10 - 16 sqmm supplied in solid (re) or non
compacted circular stranded (rm) conductor 70 36.5 1,710 compacted circular stranded (rm) conductor 70 36.0 1,710
shape 95 41.0 2,215 shape 95 42.0 2,225
25 - 400 sqmm supplied in non compacted 25 - 35 sqmm supplied in non compacted
circular stranded (rm) or compacted circular 120 45.0 2,615 circular stranded (rm) or compacted circular 120 45.0 2,640
Application: stranded (cm) conductor shape 150 50.0 3,215 Application: stranded (cm) conductor shape 150 50.5 3,225
Power cable : Indoors, cable trunking, out- Standard Packing Power cable : Indoors, cable trunking, out- 50 - 400 sqmm supplied in non compacted
185 55.0 3,960 185 56.0 3,965
circular stranded (rm) or compacted circular
doors and buried in the ground, for power 10 - 150 sqmm supplied in wooden drum @ doors and buried in the ground, for power
240 62.5 5,080 stranded (cm) or sector shaped stranded 240 62.5 5,055
1000 meters
stations, industry and switchgear as well stations, industry and switchgear as well (sm) conductor
185 - 400 sqmm supplied in wooden drum on 300 69.0 6,230 300 68.5 6,175
as for urban supply networks, if mechanical available length
as for urban supply networks, if mechanical Standard Packing
400 78.0 7,980 400 78.0 7,945
damage is unlikely. Length Tolerance per drum ± 2% damage is unlikely. 10 - 120 sqmm supplied in wooden drum @
1000 meters
150 - 400 sqmm supplied in wooden drum on
available length
Length Tolerance per drum ± 2%
* Further information about rating factor for certain cable arrangement can be found on supplementary technical information * Further information about rating factor for certain cable arrangement can be found on supplementary technical information
NYA 1.5 - 400 mm2 450 / 750 V NYB(AL)Y 1 x (16 - 500) mm2 0.6/1 kV
Cu / PVC Cu / PVC / DATA / PVC
(Copper Conductor, PVC Insulated) (Copper Conductor, PVC Insulated, Double Aluminium Tape Armor, PVC Sheathed)
NAYA
NYBY 1 CORE
Standard Specification : SPLN 42 - 1, SNI 04 - 6629.3 & IEC 60227 - 1 Standard Specification : IEC 60502 - 1 & SPLN 43 - 3
Electrical Data
Electrical Data
Conductor Insulation Inductance Current - Carrying
Capacity at Short
Conductor Insulation Inductance Current - Carrying Nom DC AC Insulation
Short 30 °C * Circuit current
Capacity at Cross Resistance Resistance Resistance
Nom DC AC Insulation Circuit current at 1 second
30 °C * Section at 20 °C at 70 °C at 20 °C in air in ground
Cross Resistance Resistance Resistance at 1 second Max.
Section at 20 °C at 70 °C at 70 °C in pipe in air Area Max. Max. Min. Max. Max. (kA)
Max. (mH/km)
Area Max. Max. Min. Max. Max. mm² (Ω/km) (Ω/km) (M.Ω.km) (A) (A)
(mH/km) (kA)
mm² (Ω/km) (Ω/km) (M.Ω.km) (A) (A) 16 1.15 1.376 40 0.412 105 129 1.81
1.5 12.1 14.478 0.0100 0.320 15 24 0.17 25 0.727 0.870 40 0.374 140 169 2.82
2.5 7.41 8.866 0.0900 0.309 19 32 0.28 35 0.524 0.627 40 0.356 175 210 3.95
4 4.61 5.516 0.0077 0.290 25 42 0.45 50 0.387 0.463 30 0.341 215 250 5.65
6 3.08 3.685 0.0065 0.276 33 54 0.68 70 0.268 0.321 30 0.324 270 310 7.91
10 1.83 2.190 0.0065 0.274 45 73 1.13 95 0.193 0.232 30 0.313 335 375 10.7
16 1.15 1.376 0.0050 0.260 61 98 1.81 120 0.153 0.184 30 0.303 390 425 13.56
25 0.727 0.870 0.0050 0.257 83 129 2.82 150 0.124 0.150 20 0.298 445 480 16.94
35 0.524 0.627 0.0040 0.249 103 158 3.45 185 0.0991 0.120 20 0.291 510 550 20.90
50 0.387 0.464 0.0045 0.248 132 197 5.65 240 0.0754 0.093 20 0.285 620 640 27.11
70 0.268 0.321 0.0035 0.240 165 245 7.91 300 0.0601 0.075 20 0.279 710 730 33.89
95 0.193 0.232 0.0032 0.239 207 290 10.73 400 0.0470 0.060 20 0.278 850 855 40.06
120 0.153 0.184 0.0032 0.235 235 345 13.56 500 0.0366 0.049 20 0.272 1000 990 50.08
150 0.124 0.150 0.0032 0.235 - 390 16.94
* Further information about rating factor for certain cable arrangement can be found on supplementary technical information
185 0.0991 0.121 0.0032 0.235 - 445 20.90
240 0.0754 0.093 0.0032 0.233 - 525 27.11
300 0.0601 0.075 0.0030 0.232 - 605 33.89
400 0.0470 0.060 0.0028 0.231 - 725 40.06
* Further information about rating factor for certain cable arrangement can be found on supplementary technical information
NYBY 2 x (1.5 - 300) mm2 0.6/1 kV NYBY 3 x (1.5 - 300) mm2 0.6/1 kV
Cu / PVC / DSTA / PVC Cu / PVC / DSTA / PVC
(Copper Conductor, PVC Insulated, Double Steel Tape Armor, PVC Sheathed) (Copper Conductor, PVC Insulated, Double Steel Tape Armor, PVC Sheathed)
NYBY 2 CORE
NYBY 3 CORE
Standard Specification : IEC 60502 - 1 & SPLN 43 - 3 Standard Specification : IEC 60502 - 1 & SPLN 43 - 3
Special Features on Request: Construction Data Special Features on Request: Construction Data
• Fire Resistance • Fire Resistance
• Oil Resistance Nom Overall Cable • Oil Resistance Nom Overall Cable
Copper conductor Copper conductor
• UV Resistance Cross Section Diameter Weight • UV Resistance Cross Section Diameter Weight
• Flame Retardant Cat. A, B, C • Flame Retardant Cat. A, B, C
PVC Insulation • Flame Retardant Non Category Area approx. approx. PVC Insulation • Flame Retardant Non Category Area approx. approx.
PVC Inner sheath PVC Inner sheath
• Heat Resistance mm² mm kg/km • Heat Resistance mm² mm kg/km
Double Steel Tape Armor Double Steel Tape Armor
• Anti Termite • Anti Termite
Black PVC Outer sheath 1.5 13.0 260 1.5 13.5 285
• Anti Rodent Black PVC Outer sheath • Anti Rodent
• Low Smoke Zero Halagen 2.5 14.0 305 • Low Smoke Zero Halagen 2.5 14.5 345
4 15.5 405 4 16.5 465
Note: 6 16.5 480 Note: 6 18.0 555
Conductor Shape 10 18.5 630 Conductor Shape 10 20.0 745
1.5 - 10 sqmm supplied in solid (re) or non 16 21.0 825 1.5 - 10 sqmm supplied in solid (re) or non 16 22.0 990
compacted circular stranded (rm) conductor compacted circular stranded (rm) conductor
shape 25 24.0 1,160 shape 25 25.5 1,420
16 sqmm supplied in non compacted circular 35 26.5 1,455 16 sqmm supplied in non compacted circular 35 28.0 1,805
stranded (rm) conductor shape stranded (rm) conductor shape
Application: 50 30.0 1,880 Application: 50 32.0 2,350
25 - 300 sqmm supplied in non compacted 25 - 300 sqmm supplied in non compacted
For installation indoors, cable channels and circular stranded (rm) or compacted circular 70 34.0 2,480 For installation indoors, cable channels and circular stranded (rm) or compacted circular 70 38.0 3,485
in ground, for industry installations, switch- stranded (cm) conductor shape in ground, for industry installations, switch- stranded (cm) conductor shape
95 40.5 3,710 95 43.0 4,635
gear, and power station, if there is a risk Standard Packing gear, and power station, if there is a risk Standard Packing
120 44.0 4,445 120 47.0 5,890
that low mechanical damage may occur. 1.5 - 120 sqmm supplied in wooden drum @ that low mechanical damage may occur. 1.5 - 95 sqmm supplied in wooden drum @
1000 meters 150 48.0 5,370 1000 meters 150 52.0 6,830
150 - 300 sqmm supplied in wooden drum on 185 53.0 6,580 120 - 300 sqmm supplied in wooden drum on 185 57.0 8,320
available length available length
240 59.5 8,375 240 64.0 10,710
Length Tolerance per drum ± 2% Length Tolerance per drum ± 2%
300 66.0 10,280 300 71.0 13,085
1.5 12.1 14.478 50 0.328 21 27 0.17 1.5 12.1 14.478 50 0.328 18 23 0.17
2.5 7.41 8.866 50 0.304 29 36 0.28 2.5 7.41 8.866 50 0.304 25 31 0.28
25 0.727 0.870 40 0.255 120 134 2.82 25 0.727 0.870 40 0.255 105 116 2.82
35 0.524 0.627 40 0.246 150 160 3.95 35 0.524 0.627 40 0.246 130 138 3.95
50 0.387 0.464 30 0.247 180 187 5.65 50 0.387 0.464 30 0.247 160 165 5.65
70 0.268 0.321 30 0.238 230 230 7.91 70 0.268 0.321 30 0.238 200 205 7.91
95 0.193 0.232 30 0.238 275 280 10.7 95 0.193 0.232 30 0.238 245 245 10.7
120 0.153 0.184 30 0.233 320 320 13.56 120 0.153 0.184 30 0.233 285 285 13.56
150 0.124 0.150 20 0.233 375 355 16.94 150 0.124 0.150 20 0.233 325 315 16.94
185 0.0991 0.121 20 0.233 430 409 20.9 185 0.0991 0.121 20 0.233 370 355 20.9
240 0.0754 0.093 20 0.232 510 472 27.11 240 0.0754 0.093 20 0.232 435 415 27.11
300 0.0601 0.075 20 0.231 590 525 33.89 300 0.0601 0.075 20 0.231 500 465 33.89
* Further information about rating factor for certain cable arrangement can be found on supplementary technical information * Further information about rating factor for certain cable arrangement can be found on supplementary technical information
NYBY 4 x (1.5 - 300) mm2 0.6/1 kV NYCY 1 x (1.5 - 500) mm2 0.6/1 kV
Cu / PVC / DSTA / PVC Cu / PVC / CWS / PVC
(Copper Conductor, PVC Insulated, Double Steel Tape Armor, PVC Sheathed) (Copper Conductor, PVC Insulated, Copper Wire Screen, PVC Sheathed)
NYBY 4 CORE
NYCY 1 CORE
Standard Specification : IEC 60502 - 1 & SPLN 43 - 3 Standard Specification : SPLN 43 - 4 & IEC 60502 - 1
Special Features on Request: Construction Data Special Features on Request: Construction Data
• Fire Resistance • Fire Resistance
• Oil Resistance Nom Overall Cable Copper conductor • Oil Resistance Nom Overall Cable
• UV Resistance Cross Section Diameter Weight • UV Resistance Cross Section Diameter Weight
Copper conductor
• Flame Retardant Cat. A, B, C • Flame Retardant Cat. A, B, C
Area approx. approx. PVC Insulation Area approx. approx.
• Flame Retardant Non Category • Flame Retardant Non Category
PVC Inner Sheath
PVC Insulation • Heat Resistance • Heat Resistance
mm² mm kg/km Copper Wire Screen mm² mm kg/km
PVC Inner sheath • Anti Termite • Anti Termite
Double Steel Tape Armor 1.5 14.5 325 Black PVC Outer sheath 1.5 / 1.5 10.0 130
• Anti Rodent • Anti Rodent
Black PVC Outer sheath • Low Smoke Zero Halagen 2.5 15.5 395 • Low Smoke Zero Halagen 2.5 / 2.5 11.0 155
4 18.0 540 4/4 12.0 200
Note: 6 19.0 660 Note: 6/6 13.0 245
Conductor Shape 10 21.5 895 Conductor Shape 10 / 10 13.5 335
1.5 - 10 sqmm supplied in solid (re) or non 16 24.0 1,205 1.5 - 10 sqmm supplied in solid (re) or non 16 / 16 15.0 465
compacted circular stranded (rm) conductor compacted circular stranded (rm) conductor
shape 25 28.0 1,750 shape 25 / 16 16.5 585
16 sqmm supplied in non compacted circular 35 30.5 2,235 16 sqmm supplied in non compacted circular 35 / 16 17.5 695
stranded (rm) conductor shape stranded (rm) conductor shape
50 33.0 2,670 Application: 50 / 25 20.0 935
25 - 35 sqmm supplied in non compacted 25 - 500 sqmm supplied in non compacted
Application: circular stranded (rm) or compacted circular 70 38.5 3,890 For installation in the ground, indoors, circular stranded (rm) or compacted circular 70 / 35 22.0 1,245
For installation indoors, cable channels and stranded (cm) conductor shape cable trunking and outdoors if subsequent stranded (cm) conductor shape
95 44.0 6,195 95 / 50 24.0 1,675
in ground, for industry installations, switch- 50 - 400 sqmm supplied in non compacted mechanical damage is likely, for urban net- Standard Packing
circular stranded (rm) or compacted circular 120 47.5 6,330 120 / 70 26.0 2,110
gear, and power station, if there is a risk works, household feeder and street lighting. 1.5 - 240 sqmm supplied in wooden drum @
stranded (cm) or sector shaped stranded 150 52.5 7,610 150 / 70 28.0 2,415
that low mechanical damage may occur. 1000 meters
(sm) conductor
185 58.0 9,425 300 - 500 sqmm supplied in wooden drum 185 / 95 31.0 3,030
Standard Packing on available length
240 64.5 11,985 240 / 120 34.0 3,885
1.5 - 70 sqmm supplied in wooden drum @ Length Tolerance per drum ± 2%
1000 meters 300 70.5 14,745 300 / 150 38.0 4,815
95 - 300 sqmm supplied in wooden drum on 400 / 185 42.0 6,095
available length
500 / 240 47.0 7,725
Length Tolerance per drum ± 2%
Electrical Data
Electrical Data Conductor Insulation Inductance Current - Carrying
Capacity at Short
Conductor Insulation Inductance Current - Carrying Nom DC AC Insulation Circuit current
Capacity at Short 30 °C *
Cross Resistance Resistance Resistance at 1 second
Nom DC AC Insulation Circuit current
30 °C * Section at 20 °C at 70 °C at 20 °C in air in ground
Cross Resistance Resistance Resistance at 1 second Max.
Section at 20 °C at 70 °C at 20 °C in air in ground Area Max. Max. Min. Max. Max. (kA)
Max. (mH/km)
Area Max. Max. Min. Max. Max. mm² (Ω/km) (Ω/km) (M.Ω.km) (A) (A)
(mH/km) (kA)
mm² (Ω/km) (Ω/km) (M.Ω.km) (A) (A) 1.5 / 1.5 12.1 14.478 50 0.455 26 33 0.17
1.5 12.1 14.478 50 0.328 18 24 0.17 2.5 / 2.5 7.41 8.866 50 0.514 35 45 0.28
2.5 7.41 8.866 50 0.304 25 32 0.28 4/4 4.61 5.516 50 0.485 46 58 0.45
4 4.61 5.516 50 0.303 34 41 0.45 6/6 3.08 3.685 50 0.457 58 74 0.68
6 3.08 3.685 50 0.288 44 52 0.68 10 / 10 1.83 2.190 50 0.420 80 98 1.13
10 1.83 2.190 50 0.269 60 69 1.13 16 / 16 1.15 1.376 40 0.399 105 129 1.81
16 1.15 1.376 40 0.255 80 89 1.81 25 / 16 0.727 0.870 40 0.373 140 169 2.82
25 0.727 0.870 40 0.255 105 116 2.82 35 / 16 0.524 0.627 40 0.355 175 210 3.95
35 0.524 0.627 40 0.246 130 138 3.95 50 / 25 0.387 0.463 30 0.345 215 250 5.65
50 0.387 0.464 30 0.247 160 165 5.65 70 / 35 0.268 0.321 30 0.329 270 310 7.91
70 0.268 0.321 30 0.238 200 205 7.91 95 / 50 0.193 0.232 30 0.322 335 375 10.7
95 0.193 0.232 30 0.238 245 245 10.7 120 / 70 0.153 0.184 30 0.316 390 425 13.56
120 0.153 0.184 30 0.233 285 280 13.56 150 / 70 0.124 0.150 20 0.310 445 480 16.94
150 0.124 0.150 20 0.233 325 315 16.94 185 / 95 0.0991 0.121 20 0.305 510 550 20.9
185 0.0991 0.121 20 0.233 370 355 20.9 240 / 120 0.0754 0.093 20 0.298 620 640 27.11
240 0.0754 0.093 20 0.232 435 415 27.11 300 / 150 0.0601 0.075 20 0.294 710 730 33.89
300 0.0601 0.075 20 0.231 500 465 33.89 400 / 185 0.0470 0.061 20 0.293 850 855 40.06
* Further information about rating factor for certain cable arrangement can be found on supplementary technical information 500 / 240 0.0366 0.049 20 0.289 1000 990 50.08
* Further information about rating factor for certain cable arrangement can be found on supplementary technical information
NYCY 2 x (1.5 - 300) mm2 0.6/1 kV NYCY 3 x (1.5 - 300) mm2 0.6/1 kV
Cu / PVC / CWS / PVC Cu / PVC / CWS / PVC
(Copper Conductor, PVC Insulated, Copper Wire Screen, PVC Sheathed) (Copper Conductor, PVC Insulated, Copper Wire Screen, PVC Sheathed)
NYCY 2 CORE
NYCY 3 CORE
Standard Specification : SPLN 43 - 4 & IEC 60502 - 1 Standard Specification : SPLN 43 - 4 & IEC 60502 - 1
Copper conductor
Special Features on Request: Construction Data Special Features on Request: Construction Data
• Fire Resistance • Fire Resistance
• Oil Resistance Nom Overall Cable • Oil Resistance Nom Overall Cable
PVC Insulation • UV Resistance Cross Section Diameter Weight Copper conductor • UV Resistance Cross Section Diameter Weight
• Flame Retardant Cat. A, B, C • Flame Retardant Cat. A, B, C
PVC Inner sheath
• Flame Retardant Non Category Area approx. approx. PVC Insulation • Flame Retardant Non Category Area approx. approx.
Copper Wire Screen
• Heat Resistance mm² mm kg/km PVC Inner sheath • Heat Resistance mm² mm kg/km
Copper Wire Screen
• Anti Termite • Anti Termite
1.5 / 1.5 13.5 220 1.5 / 1.5 14.0 245
• Anti Rodent • Anti Rodent
Black PVC Outer sheath 2.5 / 2.5 14.5 265 2.5 / 2.5 15.0 305
• Low Smoke Zero Halagen Black PVC Outer sheath • Low Smoke Zero Halagen
4/4 16.5 365 4/4 17.0 420
Note: 6/6 17.5 445 Note: 6/6 18.5 520
Conductor Shape 10 / 10 19.5 615 Conductor Shape 10 / 10 20.5 735
1.5 - 10 sqmm supplied in solid (re) or non 16 / 16 22.0 845 1.5 - 10 sqmm supplied in solid (re) or non 16 / 16 23.0 1,015
compacted circular stranded (rm) conductor compacted circular stranded (rm) conductor
shape 25 / 16 25.0 1,150 shape 25 / 16 27.0 1,405
16 sqmm supplied in non compacted circular 35 / 16 27.5 1,425 16 sqmm supplied in non compacted circular 35 / 16 29.0 1,775
stranded (rm) conductor shape stranded (rm) conductor shape
50 / 25 31.5 1,895 Application: 50 / 25 33.5 2,370
25 - 300 sqmm supplied in non compacted 25 - 300 sqmm supplied in non compacted
circular stranded (rm) or compacted circular 70 / 35 35.5 2,565 For installation in the ground, indoors, circular stranded (rm) or compacted circular 70 / 35 38.0 3,240
Application: stranded (cm) conductor shape cable trunking and outdoors if subsequent stranded (cm) conductor shape
95 / 50 41.0 3,505 95 / 50 44.0 4,425
For installation in the ground, indoors, Standard Packing
120 / 70 44.5 4,350 mechanical damage is likely, for urban net- Standard Packing
120 / 70 47.5 5,480
cable trunking and outdoors if subsequent 1.5 - 120 sqmm supplied in wooden drum @ works, household feeder and street lighting. 1.5 - 95 sqmm supplied in wooden drum @
1000 meters 150 / 70 48.5 5,155 1000 meters 150 / 70 52.5 6,590
mechanical damage is likely, for urban net-
150 - 300 sqmm supplied in wooden drum on 185 / 95 54.5 6,490 120 - 300 sqmm supplied in wooden drum on 185 / 95 58.0 8,225
works, household feeder and street lighting. available length available length
240 / 120 61.0 8,355 240 / 120 65.5 10,675
Length Tolerance per drum ± 2% Length Tolerance per drum ± 2%
300 / 150 67.5 10,345 300 / 150 73.0 13,255
NYFGbY 2 CORE
Standard Specification : SPLN 43 - 4 & IEC 60502 - 1 Standard Specification : IEC 60502 - 1, SPLN 43 - 2 & SNI IEC 60502 - 1
Special Features on Request: Construction Data Special Features on Request: Construction Data
• Fire Resistance • Fire Resistance
• Oil Resistance Nom Overall Cable • Oil Resistance Nom Overall Cable
• UV Resistance Cross Section Diameter Weight Copper conductor • UV Resistance Cross Section Diameter Weight
• Flame Retardant Cat. A, B, C • Flame Retardant Cat. A, B, C
• Flame Retardant Non Category Area approx. approx. • Flame Retardant Non Category Area approx. approx.
Copper conductor
PVC Insulation
• Heat Resistance mm² mm kg/km • Heat Resistance mm² mm kg/km
• Anti Termite PVC Inner sheath • Anti Termite
PVC Insulation 1.5 / 1.5 15.0 290 Galvanized Steel Flat 25 25.5 1,500
PVC Inner sheath
• Anti Rodent • Anti Rodent
Galvanized Steel tape
Copper Wire Screen • Low Smoke Zero Halagen 2.5 / 2.5 16.0 365 • Low Smoke Zero Halagen 35 28.0 1,830
Black PVC Outer sheath
4/4 18.5 510 50 32.0 2,345
Black PVC Outer sheath
Note: 6/6 19.5 635 Note: 70 36.0 3,060
Conductor Shape 10 / 10 22.0 900 Conductor Shape 95 40.5 3,975
1.5 - 10 sqmm supplied in solid (re) or non 16 / 16 25.0 1,255 25 - 300 sqmm supplied in non compacted 120 44.0 4,730
compacted circular stranded (rm) conductor circular stranded (rm) or compacted circular
shape 25 / 16 29.0 1,770 stranded (cm) conductor shape 150 48.5 5,720
16 sqmm supplied in non compacted circular 35 / 16 31.5 2,245 Standard Packing 185 53.5 6,930
stranded (rm) conductor shape
50 / 25 34.5 2,760 Application: 25 - 95 sqmm supplied in wooden drum @ 240 60.0 8,790
25 - 35 sqmm supplied in non compacted 1000 meters
Application: circular stranded (rm) or compacted circular 70 / 35 38.5 3,725 For installation in ground, indoors, cable 300 66.0 10,705
120 - 300 sqmm supplied in wooden drum on
For installation in the ground, indoors, stranded (cm) conductor shape
95 / 50 44.5 5,085 trunking and outdoors if increased mechani- available length
cable trunking and outdoors if subsequent 50 - 300 sqmm supplied in non compacted cal protection is required or where high-
120 / 70 48.0 6,330 Length Tolerance per drum ± 2%
circular stranded (rm) or compacted circular
mechanical damage is likely, for urban net- pulling stress may occur during installation
stranded (cm) or sector shaped stranded 150 / 70 53.5 7,585
works, household feeder and street lighting. (sm) conductor or operation.
185 / 95 59.0 9,500
Standard Packing
240 / 120 66.0 12,260
1.5 - 70 sqmm supplied in wooden drum @
1000 meters 300 / 150 73.0 15,230
95 - 300 sqmm supplied in wooden drum on
available length
Length Tolerance per drum ± 2%
Electrical Data
Electrical Data
Conductor Insulation Inductance Current - Carrying
Conductor Insulation Inductance Current - Carrying Capacity at Short
Capacity at Short Nom DC AC Insulation Circuit current
30 °C *
Nom DC AC Insulation Circuit current Cross Resistance Resistance Resistance at 1 second
30 °C *
Cross Resistance Resistance Resistance at 1 second Section at 20 °C at 70 °C at 20 °C in air in ground Max.
Section at 20 °C at 70 °C at 20 °C in air in ground Max. Area Max. Max. Min. Max. Max. (kA)
(mH/km)
Area Max. Max. Min. Max. Max. (kA) mm² (Ω/km) (Ω/km) (M.Ω.km) (A) (A)
(mH/km)
mm² (Ω/km) (Ω/km) (M.Ω.km) (A) (A)
25 0.727 0.870 40 0.255 120 134 2.82
1.5 / 1.5 12.1 14.478 50 0.328 18 24 0.17
35 0.524 0.627 40 0.246 150 160 3.95
2.5 / 2.5 7.41 8.866 50 0.304 25 32 0.28
50 0.387 0.464 30 0.247 180 187 5.65
4/4 4.61 5.516 50 0.303 34 41 0.45
70 0.268 0.321 30 0.238 230 230 7.91
6/6 3.08 3.685 50 0.288 44 52 0.68
95 0.193 0.232 30 0.238 275 280 10.7
10 / 10 1.83 2.190 50 0.269 60 69 1.13
120 0.153 0.184 30 0.233 320 320 13.56
16 / 16 1.15 1.376 40 0.255 80 89 1.81
150 0.124 0.150 20 0.233 375 355 16.94
25 / 16 0.727 0.870 40 0.255 105 116 2.82
185 0.0991 0.121 20 0.233 430 409 20.9
35 / 16 0.524 0.627 40 0.246 130 138 3.95
240 0.0754 0.093 20 0.232 510 472 27.11
50 / 25 0.387 0.464 30 0.247 160 165 5.65
300 0.0601 0.075 20 0.231 590 525 33.89
70 / 35 0.268 0.321 30 0.238 200 205 7.91
* Further information about rating factor for certain cable arrangement can be found on supplementary technical information
95 / 50 0.193 0.232 30 0.238 245 245 10.7
120 / 70 0.153 0.184 30 0.233 285 285 13.56
150 / 70 0.124 0.150 20 0.233 325 315 16.94
185 / 95 0.0991 0.121 20 0.233 370 355 20.9
240 / 120 0.0754 0.093 20 0.232 435 415 27.11
300 / 150 0.0601 0.075 20 0.231 500 465 33.89
* Further information about rating factor for certain cable arrangement can be found on supplementary technical information
NYFGbY 3 x (25 - 400) mm2 0.6/1 kV NYFGbY 4 x (16 - 400) mm2 0.6/1 kV
Cu / PVC / SFA / PVC Cu / PVC / SFA / PVC
(Copper Conductor, PVC Insulated, Galvanized Steel Flat Armor, PVC Sheathed) (Copper Conductor, PVC Insulated, Galvanized Steel Flat Armor, PVC Sheathed)
NYFGbY 3 CORE
NYFGbY 4 CORE
Standard Specification : IEC 60502 - 1, SPLN 43 - 2 & SNI IEC 60502 - 1 Standard Specification : IEC 60502 - 1, SPLN 43 - 2 & SNI IEC 60502 - 1
Special Features on Request: Construction Data Special Features on Request: Construction Data
• Fire Resistance • Fire Resistance
• Oil Resistance Nom Overall Cable • Oil Resistance Nom Overall Cable
• UV Resistance Cross Section Diameter Weight Copper conductor • UV Resistance Cross Section Diameter Weight
Copper conductor
• Flame Retardant Cat. A, B, C • Flame Retardant Cat. A, B, C
• Flame Retardant Non Category Area approx. approx. • Flame Retardant Non Category Area approx. approx.
PVC Insulation PVC Insulation
PVC Inner sheath
• Heat Resistance mm² mm kg/km • Heat Resistance mm² mm kg/km
PVC Inner sheath
Galvanized Steel Flat • Anti Termite Galvanized Steel Flat • Anti Termite
Galvanized Steel Tape 25 27.0 1,800 16 25.0 1,585
• Anti Rodent Galvanized Steel Tape • Anti Rodent
• Low Smoke Zero Halagen 35 29.5 2,235 • Low Smoke Zero Halagen 25 29.0 2,150
Black PVC Outer sheath Black PVC Outer sheath
50 34.0 2,830 35 32.0 2,704
Note: 70 38.0 3,725 Note: 50 34.5 3,175
Conductor Shape 95 43.0 4,925 Conductor Shape 70 38.5 4,135
25 - 300 sqmm supplied in non compacted 120 47.0 5,895 16 sqmm supplied in non compacted circular 95 44.0 5,455
circular stranded (rm) or compacted circular stranded (rm) conductor shape
stranded (cm) conductor shape 150 52.0 7,145 25 - 35 sqmm supplied in non compacted 120 48.0 6,610
Standard Packing 185 57.0 8,705 circular stranded (rm) or compacted circular 150 53.0 7,965
stranded (cm) conductor shape
Application: 25 - 70 sqmm supplied in wooden drum @ 240 64.0 11,155 Application: 185 58.5 9,830
1000 meters 50 - 400 sqmm supplied in non compacted
For installation in ground, indoors, cable 300 71.0 13,575 For installation in ground, indoors, cable circular stranded (rm) or compacted circular 240 65.0 12,435
95 - 400 sqmm supplied in wooden drum on
trunking and outdoors if increased mechani- trunking and outdoors if increased mechani- stranded (cm) or sector shaped stranded
available length 400 79.0 17,315 300 71.0 15,240
(sm) conductor
cal protection is required or where high- Length Tolerance per drum ± 2% cal protection is required or where high- 400 80.0 19,310
Standard Packing
pulling stress may occur during installation pulling stress may occur during installation
16 - 50 sqmm supplied in wooden drum @
or operation. or operation.
1000 meters
70 - 400 sqmm supplied in wooden drum on
available length
Length Tolerance per drum ± 2%
* Further information about rating factor for certain cable arrangement can be found on supplementary technical information 400 0.0470 0.060 20 0.229 600 535 40.06
* Further information about rating factor for certain cable arrangement can be found on supplementary technical information
NYFGbY 5 x (16 - 50) mm2 0.6/1 kV NYM 2 x (1.5 - 35) mm2 300 /500 V
Cu / PVC / SFA / PVC Cu / PVC / PVC
(Copper Conductor, PVC Insulated, Galvanized Steel Flat Armor, PVC Sheathed) (Copper Conductor, PVC Insulated, PVC Sheathed)
NYFGbY 5 CORE
NYM 2 CORE
Standard Specification : IEC 60502 - 1, SPLN 43 - 2 & SNI IEC 60502 - 1 Standard Specification : SPLN 42 - 2, SNI 04 - 6629.4 & IEC 60227 - 3
Special Features on Request: Construction Data Special Features on Request: Construction Data
• Fire Resistance • Fire Resistance
• Oil Resistance Nom Overall Cable Copper conductor • Oil Resistance Nom Overall Cable
Copper conductor • UV Resistance Cross Section Diameter Weight PVC Insulation • Flame Retardant Cat. A, B, C Cross Section Diameter Weight
• Flame Retardant Cat. A, B, C PVC filler extruded • Flame Retardant Non Category
PVC Insulation • Flame Retardant Non Category Area approx. approx. White PVC Outer sheath Area approx. approx.
PVC Inner Sheath • Heat Resistance mm² mm kg/km Note: mm² mm kg/km
Galvanized Steel Flat • Anti Termite
16 27.0 1,835 Conductor Shape 1.5 9.0 116
Galvanized Steel Tape • Anti Rodent
• Low Smoke Zero Halagen 25 32.0 2,585 1.5 - 10 sqmm supplied in solid (re) or non 2.5 10.5 157
Black PVC Outer sheath compacted circular stranded (rm) conductor
35 35.5 3,285 4 11.5 205
shape
Note: 50 40.5 4,250 16 - 35 sqmm supplied in non compacted 6 12.5 265
Conductor Shape circular stranded (rm) conductor shape 10 16.0 425
16 sqmm supplied in non compacted circular Standard Packing 16 19.0 640
stranded (rm) conductor shape 1.5 - 4 sqmm supplied in coil @ 100 meters or
25 - 50 sqmm supplied in non compacted Application: in wooden drum @ 1000/2000 meters
25 23.0 965
circular stranded (rm) or compacted circular For building wire installed in donduit in dry 6 - 35 sqmm supplied in wooden drum @ 35 25.5 1,290
stranded (cm) conductor shape 1000 meters
Application: location and interwiring in swich board and
Standard Packing Length Tolerance per drum ± 2%
For installation in ground, indoors, cable control panel, inherently flame retardant in
16 - 50 sqmm supplied in wooden drum @
trunking and outdoors if increased mechani- 1000 meters
compliance with IEC 60332 - 1.
cal protection is required or where high- Length Tolerance per drum ± 2%
pulling stress may occur during installation
or operation.
* Further information about rating factor for certain cable arrangement can be found on supplementary technical information 10 1.83 2.190 0.0065 0.278 61 1.13
16 1.15 1.376 0.0052 0.255 82 1.81
25 0.727 0.870 0.0050 0.252 108 2.82
35 0.524 0.627 0.0044 0.244 134 3.45
* Further information about rating factor for certain cable arrangement can be found on supplementary technical information
NYM 3 x (1.5 - 35) mm2 300 /500 V NYM 4 x (1.5 - 35) mm2 300 /500 V
Cu / PVC / PVC Cu / PVC / PVC
(Copper Conductor, PVC Insulated, PVC Sheathed) (Copper Conductor, PVC Insulated, PVC Sheathed)
NYM 3 CORE
NYM 4 CORE
Standard Specification : SPLN 42 - 2, SNI 04 - 6629.4 & IEC 60227 - 3 Standard Specification : SPLN 42 - 2, SNI 04 - 6629.4 & IEC 60227 - 3
Special Features on Request: Construction Data Special Features on Request: Construction Data
Copper conductor • Fire Resistance • Fire Resistance
• Oil Resistance Nom Overall Cable • Oil Resistance Nom Overall Cable
PVC Insulation Copper conductor
• Flame Retardant Cat. A, B, C Cross Section Diameter Weight • Flame Retardant Cat. A, B, C Cross Section Diameter Weight
PVC filler extruded PVC Insulation
• Flame Retardant Non Category • Flame Retardant Non Category
White PVC Outer sheath Area approx. approx. PVC filler extruded
Area approx. approx.
Conductor Shape 1.5 9.5 135 Conductor Shape 1.5 10.5 165
1.5 - 10 sqmm supplied in solid (re) or non 2.5 11.0 185 1.5 - 10 sqmm supplied in solid (re) or non 2.5 11.5 225
compacted circular stranded (rm) conductor compacted circular stranded (rm) conductor
4 12.0 250 4 13.0 315
shape shape
16 - 35 sqmm supplied in non compacted 6 13.5 335 16 - 35 sqmm supplied in non compacted 6 14.5 410
circular stranded (rm) conductor shape 10 16.5 530 circular stranded (rm) conductor shap 10 18.0 655
Standard Packing 16 20.0 820 Standard Packing 16 22.0 1,020
1.5 - 4 sqmm supplied in coil @ 100 meters or 1.5 - 2.5 sqmm supplied in coil @ 100 meters
in wooden drum @ 1000/2000 meters
25 24.0 1,235 or in wooden drum @ 1000/2000 meters
25 27.0 1,570
6 - 35 sqmm supplied in wooden drum @ 35 27.0 1,630 4 - 35 sqmm supplied in wooden drum @ 35 29.5 2,045
1000 meters 1000 meters
Application: Application:
Length Tolerance per drum ± 2% Length Tolerance per drum ± 2%
For building wire installed in donduit in dry For building wire installed in donduit in dry
location and interwiring in swich board and location and interwiring in swich board and
control panel, inherently flame retardant in control panel, inherently flame retardant in
compliance with IEC 60332 - 1. compliance with IEC 60332 - 1.
NYR(AL)Y 1 CORE
Standard Specification : SPLN 42 - 2, SNI 04 - 6629.4 & IEC 60227 - 3 Standard Specification : IEC 60502 - 1 & SPLN 43 - 2
Special Features on Request: Construction Data Special Features on Request: Construction Data
Copper conductor • Fire Resistance • Fire Resistance
• Oil Resistance Copper conductor • Oil Resistance
PVC Insulation Nom Overall Cable Nom Overall Cable
• Flame Retardant Cat. A, B, C Cross Section Diameter Weight • UV Resistance Cross Section Diameter Weight
PVC filler extruded
• Flame Retardant Non Category PVC Insulation • Flame Retardant Cat. A, B, C
Area approx. approx. • Flame Retardant Non Category Area approx. approx.
White PVC Outer sheath PVC Inner Sheath
Aluminium Wire Armor • Heat Resistance
Note: mm² mm kg/km mm² mm kg/km
Polyester Binder Tape
• Anti Termite
Conductor Shape 1.5 11.0 195 Black PVC Outer sheath 10 13.5 285
• Anti Rodent
1.5 - 10 sqmm supplied in solid (re) or non 2.5 12.5 275 • Low Smoke Zero Halagen 16 14.5 365
compacted circular stranded (rm) conductor
4 15.0 395 25 16.5 495
shape
16 - 35 sqmm supplied in non compacted 6 16.0 515 Note: 35 17.5 610
circular stranded (rm) conductor shap 10 19.5 800 Conductor Shape 50 19.0 765
Standard Packing 16 24.5 1,270 10 - 16 sqmm supplied in non compacted 70 21.0 995
1.5 - 2.5 sqmm supplied in coil @ 100 meters circular stranded (rm) conductor shape
or in wooden drum @ 1000/2000 meters
25 29.5 1,930 25 - 500 sqmm supplied in non compacted 95 23.5 1,300
4 - 35 sqmm supplied in wooden drum @ 35 33.0 2,550 circular stranded (rm) or compacted circular 120 26.5 1,680
1000 meters stranded (cm) conductor shape
Application: Application: 150 28.5 2,000
Length Tolerance per drum ± 2% Standard Packing
For building wire installed in donduit in dry For installation in ground, indoors, cable 185 31.0 2,415
10 - 300 sqmm supplied in wooden drum @
location and interwiring in swich board and trunking and outdoors if increased mechani- 1000 meters 240 34.0 3,070
control panel, inherently flame retardant in cal protection is required or where high- 400 - 500 sqmm supplied in wooden drum 300 37.0 3,745
compliance with IEC 60332 - 1. pulling stress may occur during installation on available length
400 42.0 4,835
or operation. Length Tolerance per drum ± 2%
500 46.0 5,970
* Further information about rating factor for certain cable arrangement can be found on supplementary technical information
NYRGbY 2 x (10 - 300) mm2 0.6/1 kV NYRGbY 3 x (10 - 400) mm2 0.6/1 kV
Cu / PVC / SWA / PVC Cu / PVC / SWA / PVC
(Copper Conductor, PVC Insulated, Galvanized Steel Wire Armor, PVC Sheathed) (Copper Conductor, PVC Insulated, Galvanized Steel Wire Armor, PVC Sheathed)
NYRGbY 2 CORE
NYRGbY 3 CORE
Standard Specification : IEC 60502 - 1 & SPLN 43 - 2 Standard Specification : IEC 60502 - 1 & SPLN 43 - 2
Copper conductor Special Features on Request: Construction Data Special Features on Request: Construction Data
• Fire Resistance • Fire Resistance
• Oil Resistance Nom Overall Cable • Oil Resistance Nom Overall Cable
Copper conductor
• UV Resistance Cross Section Diameter Weight • UV Resistance Cross Section Diameter Weight
PVC Insulation
• Flame Retardant Cat. A, B, C • Flame Retardant Cat. A, B, C
• Flame Retardant Non Category Area approx. approx. PVC Insulation
• Flame Retardant Non Category Area approx. approx.
PVC Inner Sheath
• Heat Resistance mm² mm kg/km PVC Inner Sheath • Heat Resistance mm² mm kg/km
Galvanized Steel Wire Armor • Anti Termite Galvanized Steel Wire Armor
• Anti Termite
10 20.0 850 10 21.0 975
• Anti Rodent Galvanized Steel Tape • Anti Rodent
Galvanized Steel Tape • Low Smoke Zero Halagen 16 22.0 1,070 • Low Smoke Zero Halagen 16 23.5 1,255
25 27.0 1,775 Black PVC Outer sheath 25 28.5 2,065
Electrical Data
Electrical Data
Conductor Insulation Inductance Current - Carrying
Capacity at Short
Conductor Insulation Inductance Current - Carrying Nom DC AC Insulation Circuit current
Short 30 °C *
Capacity at Cross Resistance Resistance Resistance at 1 second
Nom DC AC Insulation Circuit current
30 °C * Section at 20 °C at 70 °C at 20 °C in air in ground Max.
Cross Resistance Resistance Resistance at 1 second Area Max. Max. Min. Max. Max. (kA)
Section at 20 °C at 70 °C at 20 °C in air in ground Max. (mH/km)
mm² (Ω/km) (Ω/km) (M.Ω.km) (A) (A)
Area Max. Max. Min. Max. Max. (kA)
(mH/km)
mm² (Ω/km) (Ω/km) (M.Ω.km) (A) (A) 10 1.83 2.190 50 0.269 60 69 1.13
10 1.83 2.190 50 0.269 66 78 1.13 16 1.15 1.376 40 0.255 80 89 1.81
16 1.15 1.376 40 0.255 90 102 1.81 25 0.727 0.870 40 0.255 105 116 2.82
25 0.727 0.870 40 0.255 120 134 2.82 35 0.524 0.627 40 0.246 130 138 3.95
35 0.524 0.627 40 0.246 150 160 3.95 50 0.387 0.464 30 0.247 160 165 5.65
50 0.387 0.464 30 0.247 180 187 5.65 70 0.268 0.321 30 0.238 200 205 7.91
70 0.268 0.321 30 0.238 230 230 7.91 95 0.193 0.232 30 0.238 245 245 10.7
95 0.193 0.232 30 0.238 275 280 10.7 120 0.153 0.184 30 0.233 285 285 13.56
120 0.153 0.184 30 0.233 320 320 13.56 150 0.124 0.150 20 0.233 325 315 16.94
150 0.124 0.150 20 0.233 375 355 16.94 185 0.0991 0.121 20 0.233 370 355 20.9
185 0.0991 0.121 20 0.233 430 409 20.9 240 0.0754 0.093 20 0.232 435 415 27.11
240 0.0754 0.093 20 0.232 510 472 27.11 300 0.0601 0.075 20 0.231 500 465 33.89
300 0.0601 0.075 20 0.231 590 525 33.89 400 0.0470 0.060 20 0.229 600 535 40.06
* Further information about rating factor for certain cable arrangement can be found on supplementary technical information
* Further information about rating factor for certain cable arrangement can be found on supplementary technical information
NYRGbY 4 x (10 - 400) mm2 0.6/1 kV NYSY 1 x (1.5 - 500) mm2 0.6/1 kV
Cu / PVC / SWA / PVC Cu / PVC / CTS / PVC
(Copper Conductor, PVC Insulated, Galvanized Steel Wire Armor, PVC Sheathed) (Copper Conductor, PVC Insulated, Copper Tape Screen, PVC Sheathed)
NYRGbY 4 CORE
NYSY 1 CORE
Standard Specification : IEC 60502 - 1 & SPLN 43 - 2 Standard Specification : IEC 60502 - 1
Special Features on Request: Construction Data Special Features on Request: Construction Data
• Fire Resistance Copper conductor • Fire Resistance
• Oil Resistance Nom Overall Cable • Oil Resistance Nom Overall Cable
• UV Resistance Cross Section Diameter Weight PVC Insulation
• UV Resistance Cross Section Diameter Weight
Copper conductor
• Flame Retardant Cat. A, B, C • Flame Retardant Cat. A, B, C
PVC Inner Sheath
• Flame Retardant Non Category Area approx. approx. • Flame Retardant Non Category Area approx. approx.
Copper Tape Screen
PVC Insulation • Heat Resistance mm² mm kg/km Non-hygroscopic tape • Heat Resistance mm² mm kg/km
PVC Inner Sheath • Anti Termite • Anti Termite
10 23.0 1,150 Black PVC Outer sheath 1.5 9.0 120
Galvanized Steel Wire Armor
• Anti Rodent • Anti Rodent
• Low Smoke Zero Halagen 16 27.0 1,805 • Low Smoke Zero Halagen 2.5 9.5 140
Galvanized Steel Tape
25 31.0 2,455 4 10.5 175
Black PVC Outer sheath Note: 35 34.0 3,055 Note: 6 11.0 205
Conductor Shape 50 37.0 3,765 Conductor Shape 10 12.0 260
10 sqmm supplied in solid (re) or non 70 41.0 4,790 1.5 - 10 sqmm supplied in solid (re) or non 16 13.0 335
compacted circular stranded (rm) conductor compacted circular stranded (rm) conductor
shape 95 48.0 6,605 shape 25 15.0 460
16 sqmm supplied in non compacted circular 120 51.0 7,855 16 sqmm supplied in non compacted circular 35 16.0 575
stranded (rm) conductor shape stranded (rm) conductor shape
150 57.0 9,345 Application: 50 17.5 725
25 - 35 sqmm supplied in non compacted 25 - 500 sqmm supplied in non compacted
circular stranded (rm) or compacted circular 185 62.0 11,255 For power plants and switchgear as well as circular stranded (rm) or compacted circular 70 19.5 950
stranded (cm) conductor shape for installation of sub-station; for installa- stranded (cm) conductor shape
Application: 240 70.0 14,840 95 22.0 1,260
50 - 400 sqmm supplied in non compacted tion indoors in confinned spaces and cable Standard Packing
For installation in ground, indoors, cable circular stranded (rm) or compacted circular 300 76.0 17,885 120 23.5 1,520
channels because of small bending radius. 1.5 - 300 sqmm supplied in wooden drum @
trunking and outdoors if increased mechani- stranded (cm) or sector shaped stranded 400 85.0 22,325 150 25.5 1,830
1000 meters
cal protection is required or where high- (sm) conductor As buried cable, because of its light weight
400 - 500 sqmm supplied in wooden drum 185 28.0 2,235
pulling stress may occur during installation Standard Packing prefered in where installation is difficult. on available length
240 31.0 2,865
or operation. 10 - 50 sqmm supplied in wooden drum @ Length Tolerance per drum ± 2%
1000 meters 300 34.5 3,550
70 - 400 sqmm supplied in wooden drum on 400 38.0 4,490
available length
500 42.0 5,605
Length Tolerance per drum ± 2%
Electrical Data
Conductor Insulation Inductance Current - Carrying
Electrical Data Nom DC AC Insulation
Capacity at Short
30 °C * Circuit current
Cross Resistance Resistance Resistance at 1 second
Conductor Insulation Inductance Current - Carrying
Short Section at 20 °C at 70 °C at 20 °C in air in ground Max.
Capacity at
Nom DC AC Insulation Circuit current Area Max. Max. Min. Max. Max. (kA)
30 °C * (mH/km)
Cross Resistance Resistance Resistance at 1 second mm² (Ω/km) (Ω/km) (M.Ω.km) (A) (A)
Section at 20 °C at 70 °C at 20 °C in air in ground Max. 1.5 12.1 14.478 50 0.531 26 33 0.17
Area Max. Max. Min. Max. Max. (kA)
(mH/km)
mm² (Ω/km) (Ω/km) (M.Ω.km) (A) (A) 2.5 7.41 8.866 50 0.491 35 45 0.28
10 1.83 2.190 50 0.269 60 69 1.13 4 4.61 5.516 50 0.464 46 58 0.45
16 1.15 1.376 40 0.255 80 89 1.81 6 3.08 3.685 50 0.436 58 74 0.68
25 0.727 0.870 40 0.255 105 116 2.82 10 1.83 2.190 50 0.401 80 98 1.13
35 0.524 0.627 40 0.246 130 138 3.95 16 1.15 1.376 40 0.374 105 129 1.81
50 0.387 0.464 30 0.247 160 165 5.65 25 0.727 0.870 40 0.352 140 169 2.82
70 0.268 0.321 30 0.238 200 205 7.91 35 0.524 0.627 40 0.336 175 210 3.95
95 0.193 0.232 30 0.238 245 245 10.7 50 0.387 0.463 30 0.323 215 250 5.65
120 0.153 0.184 30 0.233 285 285 13.56 70 0.268 0.321 30 0.307 270 310 7.91
150 0.124 0.150 20 0.233 325 315 16.94 95 0.193 0.232 30 0.298 335 375 10.7
185 0.0991 0.121 20 0.233 370 355 20.9 120 0.153 0.184 30 0.289 390 425 13.56
240 0.0754 0.093 20 0.232 435 415 27.11 150 0.124 0.150 20 0.285 445 480 16.94
300 0.0601 0.075 20 0.231 500 465 33.89 185 0.0991 0.12 20 0.280 510 550 20.9
400 0.0470 0.060 20 0.229 600 535 40.06 240 0.0754 0.093 20 0.273 620 640 27.11
* Further information about rating factor for certain cable arrangement can be found on supplementary technical information 300 0.0601 0.075 20 0.270 710 730 33.89
400 0.0470 0.060 20 0.268 850 855 40.06
500 0.0366 0.049 20 0.263 1000 990 50.08
* Further information about rating factor for certain cable arrangement can be found on supplementary technical information
NYSY 2 x (1.5 - 300) mm2 0.6/1 kV NYSY 3 x (1.5 - 300) mm2 0.6/1 kV
Cu / PVC / CTS / PVC Cu / PVC / CTS / PVC
(Copper Conductor, PVC Insulated, Copper Tape Screen, PVC Sheathed) (Copper Conductor, PVC Insulated, Copper Tape Screen, PVC Sheathed)
NYSY 2 CORE
NYSY 3 CORE
Standard Specification : IEC 60502 - 1 Standard Specification : IEC 60502 - 1
Copper conductor
Special Features on Request: Construction Data Special Features on Request: Construction Data
• Fire Resistance • Fire Resistance
• Oil Resistance Nom Overall Cable • Oil Resistance Nom Overall Cable
• UV Resistance Cross Section Diameter Weight • UV Resistance Cross Section Diameter Weight
PVC Insulation
• Flame Retardant Cat. A, B, C • Flame Retardant Cat. A, B, C
PVC Inner Sheath Area approx. approx. Copper conductor
• Flame Retardant Non Category • Flame Retardant Non Category Area approx. approx.
Copper Tape Screen • Heat Resistance mm² mm kg/km • Heat Resistance mm² mm kg/km
Non-hygroscopic tape • Anti Termite PVC Insulation
• Anti Termite
1.5 12.5 235 1.5 13.0 260
• Anti Rodent PVC Inner Sheath • Anti Rodent
Black PVC Outer sheath • Low Smoke Zero Halagen 2.5 13.0 280 Copper Tape Screen • Low Smoke Zero Halagen 2.5 14.0 315
Non-hygroscopic tape
4 15.0 375 4 16.0 430
Black PVC Outer sheath
Note: 6 16.0 445 Note: 6 17.0 520
Conductor Shape 10 18.0 590 Conductor Shape 10 19.0 705
1.5 - 10 sqmm supplied in solid (re) or non 16 20.0 780 1.5 - 10 sqmm supplied in solid (re) or non 16 21.5 945
compacted circular stranded (rm) conductor compacted circular stranded (rm) conductor
shape 25 23.5 1,115 shape 25 25.0 1,365
16 sqmm supplied in non compacted circular 35 26.0 1,405 16 sqmm supplied in non compacted circular 35 27.5 1,750
stranded (rm) conductor shape stranded (rm) conductor shape
50 30.0 1,830 50 32.0 2,330
25 - 300 sqmm supplied in non compacted 25 - 300 sqmm supplied in non compacted
Application:
Application: circular stranded (rm) or compacted circular 70 34.0 2,465 circular stranded (rm) or compacted circular 70 36.0 3,115
stranded (cm) conductor shape For power plants and switchgear as well as stranded (cm) conductor shape
For power plants and switchgear as well as 95 38.5 3,310 95 41.5 4,205
Standard Packing
for installation of sub-station; for installa-
for installation of sub-station; for installa- 120 42.5 4,015 Standard Packing
120 45.5 5,180
1.5 - 120 sqmm supplied in wooden drum @ tion indoors in confinned spaces and cable 1.5 - 95 sqmm supplied in wooden drum @
tion indoors in confinned spaces and cable 150 47.0 4,935 150 50.0 6,305
1000 meters channels because of small bending radius. 1000 meters
channels because of small bending radius.
150 - 300 sqmm supplied in wooden drum on 185 52.0 6,055 As buried cable, because of its light weight 120 - 300 sqmm supplied in wooden drum on 185 56.0 7,825
As buried cable, because of its light weight available length available length
240 58.5 7,855 prefered in where installation is difficult. 240 63.0 10,090
prefered in where installation is difficult. Length Tolerance per drum ± 2% Length Tolerance per drum ± 2%
300 64.5 9,625 300 69.0 12,400
NYY 1 CORE
Standard Specification : IEC 60502 - 1 Standard Specification : SPLN 43 - 1 : 1994 & SNI IEC 60502 - 1 : 2009
Special Features on Request: Construction Data Special Features on Request: Construction Data
• Fire Resistance Copper conductor • Fire Resistance
• Oil Resistance Nom Overall Cable • Oil Resistance Nom Overall Cable
Copper conductor • UV Resistance Cross Section Diameter Weight PVC Insulation • UV Resistance Cross Section Diameter Weight
• Flame Retardant Cat. A, B, C • Flame Retardant Cat. A, B, C
• Flame Retardant Non Category Area approx. approx. • Flame Retardant Non Category Area approx. approx.
PVC Insulation Black PVC Outer sheath
• Heat Resistance mm² mm kg/km • Heat Resistance mm² mm kg/km
PVC Inner Sheath
• Anti Termite • Anti Termite
Copper Tape Screen 1.5 13.5 300 1.5 6.0 53
• Anti Rodent • Anti Rodent
Non-hygroscopic tape
• Low Smoke Zero Halagen 2.5 15.0 365 • Low Smoke Zero Halagen 2.5 6.5 65
Black PVC Outer sheath 4 17.0 505 4 7.5 91
Note: 6 18.5 620 Note: 6 8.0 114
Conductor Shape 10 21.0 855 Conductor Shape 10 9.0 162
1.5 - 10 sqmm supplied in solid (re) or non 16 23.5 1,160 1.5 - 10 sqmm supplied in solid (re) or non 16 10.0 225
compacted circular stranded (rm) conductor compacted circular stranded (rm) conductor
shape 25 27.5 1,690 shape 25 12.0 334
16 sqmm supplied in non compacted circular 35 30.5 2,190 16 sqmm supplied in non compacted circular 35 13.0 437
stranded (rm) conductor shape stranded (rm) conductor shape
50 32.0 2,780 50 14.5 571
25 - 35 sqmm supplied in non compacted 25 - 500 sqmm supplied in non compacted
circular stranded (rm) or compacted circular 70 36.5 3,725 Application: circular stranded (rm) or compacted circular 70 16.5 779
Application: stranded (cm) conductor shape stranded (cm) conductor shape
95 42.0 5,060 Power cable : Indoors, cable trunking, out- 95 19.0 1,069
For power plants and switchgear as well as 50 - 400 sqmm supplied in non compacted
120 45.5 6,215
doors and buried in the ground, for power Standard Packing
120 20.5 1,315
for installation of sub-station; for installa- circular stranded (rm) or compacted circular
stranded (cm) or sector shaped stranded stations, industry and switchgear as well 1.5 - 10 sqmm supplied in coil @ 100 meters
tion indoors in confinned spaces and cable 150 51.0 7,570 150 23.0 1,615
(sm) conductor as for urban supply networks, if mechanical 16 - 300 sqmm supplied in wooden drum @
channels because of small bending radius. 185 56.0 9,445 1000 meters 185 25.0 2,005
Standard Packing damage is unlikely.
As buried cable, because of its light weight 240 62.5 12,105 400 - 500 sqmm supplied in wooden drum 240 28.5 2,610
1.5 - 70 sqmm supplied in wooden drum @ on available length
prefered in where installation is difficult. 1000 meters 300 68.5 14,990 300 31.5 3,230
Length Tolerance per drum ± 2%
95 - 300 sqmm supplied in wooden drum on 400 35.0 4,130
available length
500 39.0 5,200
Length Tolerance per drum ± 2% Electrical Data
Conductor Insulation Inductance Current - Carrying
Electrical Data Capacity at Short
Nom DC AC Insulation Circuit current
30 °C *
Conductor Insulation Inductance Current - Carrying Cross Resistance Resistance Resistance at 1 second
Capacity at Short Section at 20 °C at 70 °C at 20 °C in air in ground Max.
Nom DC AC Insulation Circuit current
30 °C * Area Max. Max. Min. Max. Max. (kA)
Cross Resistance Resistance Resistance at 1 second (mH/km)
mm² (Ω/km) (Ω/km) (M.Ω.km) (A) (A)
Section at 20 °C at 70 °C at 20 °C in air in ground Max.
Area Max. Max. Min. Max. Max. (kA) 1.5 12.1 14.478 50 0.459 26 33 0.17
(mH/km)
mm² (Ω/km) (Ω/km) (M.Ω.km) (A) (A)
2.5 7.41 8.866 50 0.423 35 45 0.28
1.5 12.1 14.478 50 0.328 18 24 0.17
4 4.61 5.516 50 0.404 46 58 0.45
2.5 7.41 8.866 50 0.304 25 32 0.28
6 3.08 3.685 50 0.380 58 74 0.68
4 4.61 5.516 50 0.303 34 41 0.45
10 1.83 2.190 50 0.350 80 98 1.13
6 3.08 3.685 50 0.288 44 52 0.68
16 1.15 1.376 40 0.327 105 129 1.81
10 1.83 2.190 50 0.269 60 69 1.13
25 0.727 0.870 40 0.312 140 169 2.82
16 1.15 1.376 40 0.255 80 89 1.81
35 0.524 0.627 40 0.299 175 210 3.95
25 0.727 0.870 40 0.255 105 116 2.82
50 0.387 0.464 30 0.290 215 250 5.65
35 0.524 0.627 40 0.246 130 138 3.95
70 0.268 0.321 30 0.278 270 310 7.91
50 0.387 0.464 30 0.247 160 165 5.65
95 0.193 0.232 30 0.274 335 375 10.7
70 0.268 0.321 30 0.238 200 205 7.91
120 0.153 0.184 30 0.267 390 425 13.56
95 0.193 0.232 30 0.238 245 245 10.7
150 0.124 0.150 20 0.266 445 480 16.94
120 0.153 0.184 30 0.233 285 285 13.56
185 0.0991 0.121 20 0.264 510 550 20.9
150 0.124 0.150 20 0.233 325 315 16.94
240 0.0754 0.093 20 0.261 620 640 27.11
185 0.0991 0.121 20 0.233 370 355 20.9
300 0.0601 0.075 20 0.258 710 730 33.89
240 0.0754 0.093 20 0.232 425 415 27.11
400 0.0470 0.061 20 0.256 850 855 40.06
300 0.0601 0.075 20 0.231 500 465 33.89
500 0.0366 0.049 20 0.252 1000 990 50.08
* Further information about rating factor for certain cable arrangement can be found on supplementary technical information
* Further information about rating factor for certain cable arrangement can be found on supplementary technical information
NYY 2 x (1.5 - 400) mm2 0.6/1 kV NYY 3 x (1.5 - 400) mm2 0.6/1 kV
Cu / PVC / PVC Cu / PVC / PVC
(Copper Conductor, PVC Insulated, PVC Sheathed) (Copper Conductor, PVC Insulated, PVC Sheathed)
NYY 2 CORE
NYY 3 CORE
Standard Specification : SPLN 43 - 1, SNI IEC 60502 - 1 & IEC 60502 - 1 Standard Specification : SPLN 43 - 1, SNI IEC 60502 - 1 & IEC 60502 - 1
Special Features on Request: Construction Data Special Features on Request: Construction Data
• Fire Resistance • Fire Resistance
• Oil Resistance Nom Overall Cable • Oil Resistance Nom Overall Cable
Copper conductor
• UV Resistance Cross Section Diameter Weight • UV Resistance Cross Section Diameter Weight
Copper conductor
• Flame Retardant Cat. A, B, C • Flame Retardant Cat. A, B, C
PVC Insulation • Flame Retardant Non Category Area approx. approx. • Flame Retardant Non Category Area approx. approx.
PVC Inner sheath • Heat Resistance mm² mm kg/km PVC Insulation • Heat Resistance mm² mm kg/km
• Anti Termite PVC Inner sheath • Anti Termite
Black PVC Outer sheath 1.5 12.5 200 1.5 13.0 224
• Anti Rodent • Anti Rodent
• Low Smoke Zero Halagen 2.5 13.0 240 Black PVC Outer sheath
• Low Smoke Zero Halagen 2.5 14.0 274
4 15.0 330 4 16.0 380
Note: 6 16.0 397 Note: 6 17.0 465
Conductor Shape 10 18.0 535 Conductor Shape 10 19.0 645
1.5 - 10 sqmm supplied in solid (re) or non 16 20.0 715 1.5 - 10 sqmm supplied in solid (re) or non 16 21.0 875
compacted circular stranded (rm) conductor compacted circular stranded (rm) conductor
shape 25 23.5 1,032 shape 25 25.0 1,280
16 sqmm supplied in non compacted circular 35 26.0 1,315 16 sqmm supplied in non compacted circular 35 27.0 1,650
stranded (rm) conductor shape stranded (rm) conductor shape
Application: 50 29.0 1,715 Application: 50 31.0 2,160
25 - 500 sqmm supplied in non compacted 25 - 400 sqmm supplied in non compacted
Power cable : Indoors, cable trunking, out- circular stranded (rm) or compacted circular 70 33.0 2,295 Power cable : Indoors, cable trunking, out- circular stranded (rm) or compacted circular 70 35.5 2,970
doors and buried in the ground, for power stranded (cm) conductor shape doors and buried in the ground, for power stranded (cm) conductor shape
95 38.0 3,140 95 41.0 4,025
stations, industry and switchgear as well Standard Packing stations, industry and switchgear as well Standard Packing
120 41.5 3,825 120 44.5 4,925
as for urban supply networks, if mechanical 1.5 - 120 sqmm supplied in wooden drum @ as for urban supply networks, if mechanical 1.5 - 95 sqmm supplied in wooden drum @
1000 meters 150 45.5 4,665 1000 meters 150 49.5 6,065
damage is unlikely. damage is unlikely.
150 - 300 sqmm supplied in wooden drum on 185 51.0 5,820 120 - 400 sqmm supplied in wooden drum on 185 54.5 7,500
available length available length
240 57.5 7,520 240 62.0 9,785
Length Tolerance per drum ± 2% Length Tolerance per drum ± 2%
300 63.5 9,295 300 69.0 12,200
400 76.5 15,415
Electrical Data
Conductor Insulation Inductance Current - Carrying
Capacity at Short
Nom DC AC Insulation Circuit current
30 °C *
Cross Resistance Resistance Resistance at 1 second
Section at 20 °C at 70 °C at 20 °C in air in ground Max.
Area Max. Max. Min. Max. Max. (kA)
(mH/km)
mm² (Ω/km) (Ω/km) (M.Ω.km) (A) (A)
1.5 12.1 14.478 50 0.328 18 24 0.17
2.5 7.41 8.866 50 0.304 25 32 0.28
4 4.61 5.516 50 0.303 34 41 0.45
6 3.08 3.685 50 0.288 44 52 0.68
10 1.83 2.190 50 0.269 60 69 1.13
16 1.15 1.376 40 0.255 80 89 1.81
25 0.727 0.870 40 0.255 105 116 2.82
35 0.524 0.627 40 0.246 130 138 3.95
50 0.387 0.464 30 0.247 160 165 5.65
70 0.268 0.321 30 0.238 200 205 7.91
95 0.193 0.232 30 0.238 245 245 10.7
120 0.153 0.184 30 0.233 285 280 13.56
150 0.124 0.150 20 0.233 325 315 16.94
185 0.0991 0.121 20 0.233 370 355 20.9
240 0.0754 0.093 20 0.232 435 415 27.11
300 0.0601 0.075 20 0.231 500 465 33.89
400 0.0470 0.060 20 0.229 600 535 40.06
* Further information about rating factor for certain cable arrangement can be found on supplementary technical information