Distribution :             Controlled    X        Uncontrolled              Available on computer   X
Document status :                                            TO :
   F.I                 ( Information )
   F.C                 ( Comments )
   F.E                 ( Execution )
   F.A         X       ( Application )
   Title :                         CURRENT LINE DIFFERENTIAL PROTECTION
                                                        MICOM P 543
                                                 150 kV OHL Cilegon Baru
                                                        F87L - EF1007
   Type :      FIELD TEST REPORT
   Contract :
                                                             PEKERJAAN
                                                                          GI ASHAIMAS CHEMICAL
   Contract specific number                                                    Name
   by
   on
   by
  on
B by
  on
A by                                                                                                       9
   on        08.11.2017        08.11.2017       08.11.2017
Ind Rev      Prepared          Checked          Approved                   Modification                Sheets
                                                                         PT. ENERGI DIAN RAYA
                                                                               FA Section
PT. ENERGI DIAN RAYA                                    LINE DIFFERENTIAL              Ref.
FA Section                                                   PROTECTION                Chapt.
                                                       OHL CILEGON BARU                Sheet :           2
                                                                                       Rev.              A
                                 SUMMARY                                       SHEET          REVISION
     1       LIST OF EQUIPMENT USED                                               2                  A
     2       CHARACTERISTICS                                                      3                  A
     3       PRODUCT CHECKS                                                       3                  A
     4       MEASUREMENT CHECKS                                                   4                  A
     5       SETTING CHECKS                                                       5                  A
     6       FUNCTION TEST                                                        6                  A
     7       DISTANCE PROTECTION ZONE REACH                                       7                  B
     8       ON LOAD TEST                                                        10                  A
     8       ON LOAD TEST                                                        11                  A
   1 - LIST OF TEST EQUIPMENT USED
     Identification                                                    Test corresponding to paragr.
                                     Designation
        Number                                                     4        5     6    7      8      9
                        Secondary Current Injector OMICRON         X       X      X     X        X
                              Digital multimeter Fluke 179         X
PT. ENERGI DIAN RAYA                                            LINE DIFFERENTIAL        Ref.
FA Section                                                           PROTECTION          Chapt.
                                                               OHL CILEGON BARU          Sheet :   3
                                                                                         Rev.      A
   2      CHARACTERISTICS
       - Circuit :   EF1004 - 150KV PROTECTION OHL CILEGON BARU
       - Nominal Network Freq. :      50 Hz
       - Protection Relay :           MiCOM P543
       - Model number :               P543317C3M0520K
       - Serial Number :               3 1 4 8 4 2 4 2               /   0 9   /   1 0
       - Nominal voltage Vn :         100 - 120 V
       - Auxiliary supply Vaux :      110 - 250 V DC
       - Communication Protocol :     IEC 61850
   3      PRODUCT CHECK
              Visual Inspection
                 Rating information            ( Alarm Loop Link Internal )
                 Case earth                           OK
              External wiring
                 External wiring conformity              OK
                 Auxiliary Voltage to device             OK
              Date and Time
                 Clock set to local time                        OK
                 Info stored with aux. supply cut-off           OK
              Date and Time
                 Healthy LED status                      OK
                 All LEDs illumination checks            OK
PT. ENERGI DIAN RAYA                                                LINE DIFFERENTIAL          Ref.
FA Section                                                            PROTECTION               Chapt.
                                                                    OHL CILEGON BARU           Sheet :   4
                                                                                               Rev.      A
   4      MEASUREMENT CHECK
  Current Inputs Check
       Setting :        Displayed current :        X Primary               Secondary
                        Phase CT ratio :          2000 / 1 A               Mutual CT ratio :   -
                        Earth Fault CT ratio :       -
                                Injected          Displayed         Expected           Error
               Phase           Current (A)         Current           Display            [%]
                                   0,1              199.5              200             -0.25
                   IA              0,5              998.9             1000             -0.11
                                   1.0              2001              2000              0.05
                                   0,1              199.3              200             -0.35
                   IB              0,5              998.6             1000             -0.14
                                   1.0              2001              2000              0.05
                                   0,1              200.0              200              0.00
                   IC              0,5              999.7             1000             -0.03
                                   1.0              2000              2000              0.00
                                    -                 -                 -                 -
                   IM               -                 -                 -                 -
                                    -                 -                 -                 -
  Voltage Inputs Check
       Setting :        Displayed current :        X Primary               Secondary
                        Main VT ratio :           150 kV / 100 V
                        C/S VT ratio :                  -
                                Injected          Displayed         Expected           Error
               Phase
                               Voltage (V)       Voltage (KV)      Display (KV)         [%]
                                   10               14.93               15             -0.47
                   Va              30               44.98               45             -0.04
                                  57,7              86.55              86.7            -0.17
                                   10               14.93               15             -0.47
                   Vb              30               44.99               45             -0.02
                                  57,7              86.61              86.7            -0.10
                                   10               14.93               15             -0.47
                   Vc              30               44.97               45             -0.07
                                  57,7              86.58              86.7            -0.14
                                    -                  -                 -               -
                C/S                 -                  -                 -               -
               Voltage
                                    -                  -                 -               -
PT. ENERGI DIAN RAYA                                            LINE DIFFERENTIAL                Ref.
FA Section                                                        PROTECTION                     Chapt.
                                                                OHL CILEGON BARU                 Sheet :   5
                                                                                                 Rev.      A
  4.1 Measurement
     Test 1                  Injected values         Displayed Values
                     Phase     Magnitude    Angle   Magnitude    Angle
                      IA         0,2 A        0      399.6          0
        Currents      IB         0,4 A      -120     797.4       -121.2
                      IC         0,8 A      120       1598       118.3
                     VAN         30 V         0     44.99 KV     -1.851
        Voltages     VBN         40 V       -120    59.98 KV     -121.7
                     VCN         50 V       120     75.01 KV     118.2
    Test 2                   Injected values         Displayed Values
                     Phase     Magnitude    Angle   Magnitude    Angle
                      IA         1A          20      2003 A         0
        Currents      IB         1A         -100     2002 A       -120
                      IC         1A         140      2003 A       120
                     VAN       57,75 V        0     86.57 kV        0
        Voltages     VBN       57,75 V      -120    86.59 kV     -119.9
                     VCN       57,75 V      120     86.62 kV     120.1
   5     SETTING CHECK
  5.1    DIFFERENTIAL ELEMENT CHECK
         Setting : Is1 = 200 mA          k1 = 30 %
                    Is2 = 2 A            k2 = 150%
          Phase       Pick Up   Drop Off                    Note : Test with Internal Loopback
         Injection       (A)       (A)
             R         0.120     0.091
             S        0.120         0.091
             T        0.120         0.091
  5.2    TIMING CHECK
         Setting : Phase Time delay : 0 Second
          Phase      Current          Timing
         Injection Inject (A)          (ms)
                       0.2            39.10
             R         0.4            31.40
                       0.2            39.10
             S         0.4            31.40
                       0.2            39.10
             T         0.4            31.40
         Acceptance Criteria :
         Timing for 1 * I.sett = 1,05 x Sett ± 5%
         Timing for 2 * I.sett = 50% x (1,05 x Sett ± 5)
PT. ENERGI DIAN RAYA                       LINE DIFFERENTIAL       Ref.
FA Section                                   PROTECTION            Chapt.
                                                                   Sheet : 6
                                       OHL CILEGON BARU
                                                                   Rev.    A
  6. FUNCTION TEST
                 Phase
       Relay                Auto Reclose     CB Status    Result
               Simulation
                  R-N           OFF             Trip       OK
                  S-N           OFF             Trip       OK
                  T-N           OFF             Trip       OK
                  R-N           OFF             Trip       OK
                  S-N           OFF             Trip       OK
       P543
                  T-N           OFF             Trip       OK
                  R-S           OFF             Trip       OK
                  S-T           OFF             Trip       OK
                  R-T           OFF             Trip       OK
                 R-S-T          OFF             Trip       OK
PT. ENERGI DIAN RAYA                                 DIFFERENTIAL PROTECTION Ref.
FA Section                                                    RELAY                      Chapt.
                                                        OHL CILEGON BARU                 Sheet :         7
                                                                                         Rev.            B
  7. Distance Protection Zone Reach
  Phase-Ground
   Fault                           Impedance Z (Ohm)           Operating
           Zone Phase                                                         Indication           Remarks
    type                     Z        θ°       R         X     time (msec)
                            2.74      81     0.42       2.70      456.9      Start Phase - AN
                            2.74      60     1.37       2.37      450.6      Trip Phase - AN
                    A       33.0      0      33.00      0.00      456.3      Distance Trip Z2
                            2.74      81     0.42       2.70      455.7      Start Phase - BN
                            2.74      60     1.37       2.37      449.5      Trip Phase - BN
             2      B       33.0      0      33.00      0.00      458.8      Distance Trip Z2
   Ph-Grd
                            2.74      81     0.42       2.70      455.1      Start Phase - CN
                            2.74      60     1.37       2.37      450.8      Trip Phase - CN
                    C       33.0      0      33.00      0.00      454.6      Distance Trip Z2
                           7.390      81     1.15       7.29      1644       Start Phase - AN
                           7.390      60     3.69       6.40      1653       Trip Phase - AN
                    A      37.0       0      37.00      0.00      1660       Distance Trip Z3
                           7.390      81     1.15       7.29      1657       Start Phase - BN
                           7.390      60     3.69       6.40      1654       Trip Phase - BN
             3      B      37.0       0      37.00      0.00      1656       Distance Trip Z3
                           7.390      81     1.15       7.29      1646       Start Phase - CN
                           7.390      60     3.69       6.40      1655       Trip Phase - CN
                    C      37.0       0      37.00      0.00      1655       Distance Trip Z3
PT. ENERGI DIAN RAYA                               DISTANCE PROTECTION                Ref.
FA Section                                                RELAY                       Chapt.
                                                    OHL CILEGON BARU                  Sheet :         8
                                                                                      Rev.            B
  Phase-Phase
   Fault                       Impedance Z (Ohm)            Operating
          Zone Phase                                                       Indication           Remarks
    type                Z         θ°        R        X      time (msec)
                       2.120      81      0.33      2.09       437.8      Start Phase - AB
                       2.450      81      0.38      2.42       433.6      Trip Phase - AB
                 A-B   2.740      81      0.42      2.70       439.3      Distance Trip Z2
                       2.120      81      0.33      2.09       422.3      Start Phase - BC
                       2.450      81      0.38      2.42       433.7      Trip Phase - BC
             2   B-C   2.740      81      0.42      2.70       445.0      Distance Trip Z2
   Ph-Ph
                       2.120      81      0.33      2.09       441.8      Start Phase - AC
                       2.450      81      0.38      2.42       449.1      Trip Phase - AC
                 C-A   2.740      81      0.42      2.70       450.4      Distance Trip Z2
                       6.120      81     0.950      6.04       1631       Start Phase - AB
                       6.740      81     1.050      6.65       1645       Trip Phase - AB
                 A-B   7.390      81     1.150      7.29       1647       Distance Trip Z3
                       4.210      81     0.580      4.160      1634       Start Phase - BC
                       4.720      81     0.650      4.67       1646       Trip Phase - BC
             3   B-C   5.160      81     0.710      5.11       1653       Distance Trip Z3
                       4.210      81     0.580      4.160      1644       Start Phase - AC
                       4.720      81     0.650      4.67       1634       Trip Phase - AC
                 C-A   5.160      81     0.710      5.11       1646       Distance Trip Z3
PT. ENERGI DIAN RAYA                                DISTANCE PROTECTION                  Ref.
FA Section                                                    RELAY                      Chapt.
                                                        OHL CILEGON BARU                 Sheet :         9
                                                                                         Rev.            B
  Tiga Phase
    Fault                         Impedance Z (Ohm)             Operating
           Zone Phase                                                          Indication          Remarks
    type              Z            θ°      R        X          time (msec)
                          2.120      81      0.33       2.09      418.6      Start Phase - ABC
                          2.450      81      0.38       2.42      432.3      Trip Phase - ABC
             2    A-B-C   2.740      81      0.42       2.70      440.9       Distance Trip Z2
   3Phase                 6.120      81     0.950       6.04      1631       Start Phase - ABC
                          6.740      81     1.050       6.65      1637       Trip Phase - ABC
             3    A-B-C   7.390      81     1.150       7.29      1644        Distance Trip Z3
    Tested by :              Witnessed by :                           Approved by:               Date
PT. ALSTOM GRID            PT. PLN UPK JJB 3                       PT. PLN PUSERTIF
PT. ENERGI DIAN RAYA                                                      LINE DIFFERENTIAL                          Ref.
FA Section                                                                     PROTECTION                            Chapt.
                                                                          OHL CILEGON BARU                           Sheet : 10
                                                                                                                     Rev.       A
   9.       ON LOAD TEST
   Scheme :
                         A                                                                                    B
                         543                                                                              543
   CHECK MEASUREMENT
     No                   ITEM CHECK                              LOCAL                    REMOTE                 REMARKS
        1                    IA <degree
        2                    IB<degree
        3                    IC<degree
        4                    VA<degree
        5
                             VB<degree
        6
                             VC<degree
        7
                               Idiff A
        8
                               Idiff B
        9                      Idiff C
            Tested by :                                     Witnessed by :                                        Approved by :
   PT.ALSTOM GRID                          PT. PELINDO II               PT. PLN ENJINIRING             PT. ANDALAN MUTU ENERGY
This document is the property of PT. AG and cannot be used, reproduced or transmitted to thirds without prior written permission.
PT. ENERGI DIAN RAYA                                                      LINE DIFFERENTIAL                          Ref.
FA Section                                                                     PROTECTION                            Chapt.
                                                                          OHL CILEGON BARU                           Sheet : 11
                                                                                                                     Rev.       A
   8.         THROUGH FAULT TEST ( NOT TESTED )
   Scheme :
                         A                                                                                    B
                         543                                                                              543
   STABLE CONDITION
                Side A                                 Side B
   Phase                                                                                Remarks
          Current injected (A)                   Current injected (A)
   UNSTABLE CONDITION
                Side A                                 Side B
   Phase                                                                                Remarks
          Current injected (A)                   Current injected (A)
              Tested by :                                   Witnessed by :                                        Approved by :
            PT.ALSTOM GRID                  PT. PELINDO II               PT. PLN ENJINIRING            PT. ANDALAN MUTU ENERGI
This document is the property of PT. AG and cannot be used, reproduced or transmitted to thirds without prior written permission.