Substation Automation
Substation Automation
by TIKARAM
Date: 2009.11.20
17:59:55
GMT+05:30
Reason: CAT I
Location:
NTPCEOC
Functional Design Specification – Substation Automation System
!
" # $%& ' % !( %(
& )* & *
+ , - * & , .,
REVISION TABLE
NTECL
NTECL DOC.No. : 0260-573-PVE-M-093
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties
without express authority is strictly forbidden. Copyright © by ABB Limited
Document
Functional Design Specification - SAS Sale Order :
Prepared
Divya S 4200057645
Checked
M.V.Girish
Dept
PS SAS Created 2009-06-24 Revision 02 Yr 09 Wk 26 Lang En
YN1M301338
1338--ZAA
YN1M301338 1 (45)
Functional Design Specification – Substation Automation System
Table of Contents:
2 Introduction ......................................................................................................... 8
4.1.1 GOOSE............................................................................................... 14
4.1.3 Tripping logic and Trip Matrix Logic (PTRC, 94) ................................. 16
Document
Functional Design Specification - SAS Sale Order :
Prepared
Divya S 4200057645
Checked
M.V.Girish
Dept
PS SAS Created 2009-06-24 Revision 02 Yr 09 Wk 26 Lang En
YN1M301338
1338--ZAA
YN1M301338 2 (45)
Functional Design Specification – Substation Automation System
4.3.2 Logout................................................................................................. 23
YN1M301338
1338--ZAA
YN1M301338 3 (45)
Functional Design Specification – Substation Automation System
Table of Figures:
Figure 1: Goose (Peer to peer) Communication....................................................... 15
Document
Functional Design Specification - SAS Sale Order :
Prepared
Divya S 4200057645
Checked
M.V.Girish
Dept
PS SAS Created 2009-06-24 Revision 02 Yr 09 Wk 26 Lang En
YN1M301338
1338--ZAA
YN1M301338 4 (45)
Functional Design Specification – Substation Automation System
Document
Functional Design Specification - SAS Sale Order :
Prepared
Divya S 4200057645
Checked
M.V.Girish
Dept
PS SAS Created 2009-06-24 Revision 02 Yr 09 Wk 26 Lang En
YN1M301338
1338--ZAA
YN1M301338 5 (45)
Functional Design Specification – Substation Automation System
1.1 General
This document details the Substation automation system (SAS) functionality for NTECL
400kV GIS Switchyard & Unit Protection.
The SAS is designed considering the functional requirements of Technical Specification E11,
SAS Configuration diagram, Control& protection Schemes as applicable for the project and
brochures of ABB equipment & IED’s.
The SAS provides facility to monitor the complete 400kV GIS Protections, Control &
Synchronization of the Bay equipments & Metering (Via interfacing from the Energy metering
Master Station) from Switchyard Control Room as well as from Central control room. Main
Plant Operator workstation will be interfaced to the LAN at the Main plant control end. In
addition the SAS system also provide Gateways on IEC 60870-5-101 (Slave) protocol for
interfacing to Load Dispatch Centre and OPC connectivity for interfacing to Main plant
SCADA (DCS) respectively. Gateway for NTPC OS is also envisaged. SAS also uses an
Engineering work station for configuration, parameterization and disturbance evaluation of
IED’s.
The software or hardware described in this document is furnished under a license and may be
used, copied or disclosed only in accordance with the terms of such license.
1.3 Abbreviations
Document
Functional Design Specification - SAS Sale Order :
Prepared
Divya S 4200057645
Checked
M.V.Girish
Dept
PS SAS Created 2009-06-24 Revision 02 Yr 09 Wk 26 Lang En
YN1M301338
1338--ZAA
YN1M301338 6 (45)
Functional Design Specification – Substation Automation System
Document
Functional Design Specification - SAS Sale Order :
Prepared
Divya S 4200057645
Checked
M.V.Girish
Dept
PS SAS Created 2009-06-24 Revision 02 Yr 09 Wk 26 Lang En
YN1M301338
1338--ZAA
YN1M301338 7 (45)
Functional Design Specification – Substation Automation System
2 Introduction
The SAS is based on ABB make MicroSCADA Pro software running in a redundant
hot standby mode on two industrial PCs(network controllers) with Microsoft Windows
2003 Server Operating System.
One Metering Master Station to which all the energy meters are networked on
MODBUS
Intelligent Electronic Devices (IED’s) for bay and station protection (SCR& CCR)
GPS Receiver
Rear Projection mimic display unit (Located at the 400kV switchyard Control room)
Engineering and Disturbance Recorder Station (one in CCR and one each for
Common engineering rooms CER-1,2,3)
Document
Functional Design Specification - SAS Sale Order :
Prepared
Divya S 4200057645
Checked
M.V.Girish
Dept
PS SAS Created 2009-06-24 Revision 02 Yr 09 Wk 26 Lang En
YN1M301338
1338--ZAA
YN1M301338 8 (45)
Functional Design Specification – Substation Automation System
GPS Receiver
At each Common
Common Engineering Room:
GPS Receiver to time synchronize the SAS components including the IEDs
The SAS provides an extensive range of Supervisory Control and Data Acquisition (SCADA)
functions.
3 System Design
Chapter –E11 - Substation Automation System (SAS) for 400kV Switchyard at Vallur
TPP
The SAS is suitable for operation and monitoring of the complete substation including future
extensions as given in technical specification chapter E11.
The control hierarchy and control levels of the SAS shall be based on the logical structure of
the SAS, shown below
Document
Functional Design Specification - SAS Sale Order :
Prepared
Divya S 4200057645
Checked
M.V.Girish
Dept
PS SAS Created 2009-06-24 Revision 02 Yr 09 Wk 26 Lang En
YN1M301338
1338--ZAA
YN1M301338 9 (45)
Functional Design Specification – Substation Automation System
The SAS supports remote monitoring of the Substation from two Remote Control Centres
(One for RLDC, one for OS control room – Communication between Control Llevel 3 and
Control Level 2) .The interface ports for communication with RLDC shall be with V24/V28
standard using IEC 60870-5-101(Slave) protocol and for NTPC OS control room on OPC
connectivity. The lower control level has the highest priority.
The SAS also supports remote control and monitoring from the Main Plant SCADA
(Communication between Control level 2 and Main Plant SCADA) on OPC protocol. In
addition, the offered system envisages integration of status and analog signals (MW, MVAR,
Generator voltage, GTCB and associated Isolator /Earth switch status) from Owner’s OPC
compliant DCS to SAS.
The data exchange between Control level 2 (Station level HMI) and the Control level 1 (Bay
Control and Protection units) shall be based on IEC 61850-communication standard.
Data exchange between Control level 1 (Bay control and Protection units) and control level 0
(Switchgear equipment and Plant) will be through hardwired connections.
The SAS comprises full station and bay protection as well as control, monitoring and
communication functions and provides all functions required for the safe and reliable
operation of the 400 kV GIS at Vallur TPP.
For safety and availability reasons the SAS is based on a decentralized architecture and on a
concept of bay-oriented, distributed intelligence. Functions are decentralized, object-oriented
and located as close to the process as possible.
Bay Level.
A redundant PC based HMI (Main/standby / Operator work station) enables local station
control through the software package MicroSCADA Pro, which contains an extensive range of
SCADA functions.
The operator workstation HMI depicts the complete 400kV GIS real time graphic mimic
diagram.
Within the SAS it is possible to work from both Operator workstations at any point of time and
with the failure of Main controller the operations can be monitored from the Standby
Controller.
Document
Functional Design Specification - SAS Sale Order :
Prepared
Divya S 4200057645
Checked
M.V.Girish
Dept
PS SAS Created 2009-06-24 Revision 02 Yr 09 Wk 26 Lang En
YN1M301338
1338--ZAA
YN1M301338 10
(45)
Functional Design Specification – Substation Automation System
At the station level the SAS provide communication gateways for remote interface to RLDC
and NTPC OS. This gateway for RLDC will be through interface ports using V24/V28
communication standard (ITU-T standard, formerly CCITT standard) and will interface with
the Modem (ABB make NSK5 modem) suitable for use with the PLCC.
The Substation LAN is extended to the Central control room through fibre optic
communication equipment. The SAS also provides gateway on OPC Connectivity for Main
plant DCS interface.
Within the SAS, inter bay bus provides independent station-to-bay and bay-to-bay data
exchange.
The system can be extended both physically and functionally without affecting the original
application. It has a unique user-friendly definition language (SCIL) that facilitates integration
of the system by the users themselves, without detailed knowledge of real-time systems.
All alarm and event logs will be printed out on the DMP printer. The reports and graphics will
be printed on the Colour Laser printer connected to the system over the Ethernet LAN.
A dedicated GPS master clock is provided for the synchronization of the entire system in SCR
and CCR. This master clock is independent of the station computers and gateways, and it
synchronizes all devices via inter bay bus using SNTP protocol as defined by the IEC 61850
standards.
The Bay Level Control, Monitoring and Protection functions are achieved by a suite
of advanced range of IED670 series fully compliant to the IEC61850 standard. The
IEDs used for various applications are as under:
As per specification requirement, main – II protection relays for line are offered of a
different make and hardware platform in relay type 7SA522 of Siemens make. For
Document
Functional Design Specification - SAS Sale Order :
Prepared
Divya S 4200057645
Checked
M.V.Girish
Dept
PS SAS Created 2009-06-24 Revision 02 Yr 09 Wk 26 Lang En
YN1M301338
1338--ZAA
YN1M301338 11
(45)
Functional Design Specification – Substation Automation System
The offered IEDs are of single closed casing with sizes of ½, ¾, 1/1 of 19” and with
flush mounting arrangement. The basic hardware comprises of a built-in graphical
MIMIC display (HMI and basic modules comprising of main processing module
(CPU), analog digital conversion module (ADM), power supply module (PSM) and
application specific modules viz. transformer input modules (TRM) for acquisition of
the field current and voltage inputs in combination of 6I+6U, 9I+3U,6I or 12I as per
the scheme requirement, binary input/output modules (IOM) as per scheme
requirement. The IEDs are built-in with large monochrome graphical LCD MIMIC
display for controllers and small display units for protection relays. The HMI on the
BCU has the ability to show graphical switchgear arrangement, status information,
measurements, and disturbances (last 100 reports with scrolling function)
… Up/Down arrow keys Navigate between objects on same page and digits
YN1M301338
1338--ZAA
YN1M301338 12
(45)
Functional Design Specification – Substation Automation System
The IEDs are equipped with three status LEDs situated above the LCD screen with the
following indications.
The IEDs are also equipped with 15 freely configurable indication LEDs (6 red and 9
yellow). Both status and indication LEDs can be acknowledged / reset. The
configuration of the indication LEDs are indicated in the respective schematic
drawings.
The local HMI has a menu structure in the order of measurements, events,
disturbance records, settings, configuration, diagnostics, test and language. These
menus are accessible by pressing the menu key and then the navigation keys.
Screens are accessible by operating the respective keys on the IED for menu, help
and reset. The control screen is set as default in the IEDs. The details about the
navigation and handling the control, indication, disturbances and events from the HMI
is specified in detail in the operation and maintenance manual.
For the station-wide interlocking, the IEDs communicate via the system-wide
interbay bus (IEC 61850-8-1) or by using hard wired binary inputs/outputs.
The interlocking conditions depend on the circuit configuration and apparatus
Document
Functional Design Specification - SAS Sale Order :
Prepared
Divya S 4200057645
Checked
M.V.Girish
Dept
PS SAS Created 2009-06-24 Revision 02 Yr 09 Wk 26 Lang En
YN1M301338
1338--ZAA
YN1M301338 13
(45)
Functional Design Specification – Substation Automation System
position status at any given time. For instance to realize the Bus Earth switch
interlock, the status of Bus isolators information are passed on GOOSE.
4 System Description
The bay level functions provided for the 400kV system is as shown in the relevant control &
protection schematic drawings (trip logics)
Bay Ethernet switches are provided in each BCU panel, each Bay BPU panel and Generator
protection panels of each unit. The connection from each IED to the switch is by a single fibre
optic link. The switches are connected in a fault tolerant ring topology. At the station level, to
provide communication redundancy, Ethernet switches are used to connect the redundant
HMI and other station level equipment.
A process bus is not used and the connections from the bay level to the process are
hardwired. The details of the functions provided for the individual bays and at the station level
are described below.
The bay level functions for each of the feeders and the protection function distribution within
the IEDs are detailed in the protection single line diagram/trip logics.
4.1.1 GOOSE
GOOSE is an acronym for Generic Object Orientated System-wide Events. It aims to replace
the conventional hardwired logic necessary for intra-IED coordination with station bus
communications
It is a mechanism for the fast transmission of substation events, such as commands, alarms,
indications, as messages.
A GOOSE message sent by one IED can be received and used by several other IEDs
Document
Functional Design Specification - SAS Sale Order :
Prepared
Divya S 4200057645
Checked
M.V.Girish
Dept
PS SAS Created 2009-06-24 Revision 02 Yr 09 Wk 26 Lang En
YN1M301338
1338--ZAA
YN1M301338 14
(45)
Functional Design Specification – Substation Automation System
4.1.2 Bay
Ba y level human machine interface (IHMI or LHMI)
LHMI)
The local human machine interface or integrated human machine interface is equipped with
an LCD that can display the single line diagram with up to 9 objects. The local human-
machine interface is simple and easy to understand – the whole front plate is divided into
zones, each of them with a well-defined functionality:
Alarm indication LEDs consisting of 6 red LEDs and 9 yellow LEDs with user printable
sticker. All LEDs are configurable from the PCM600 tool.
Keypad with push buttons for control and navigation purposes, switch for selection
between local and remote control, reset and an isolated RJ-45 communication port
Document
Functional Design Specification - SAS Sale Order :
Prepared
Divya S 4200057645
Checked
M.V.Girish
Dept
PS SAS Created 2009-06-24 Revision 02 Yr 09 Wk 26 Lang En
YN1M301338
1338--ZAA
YN1M301338 15
(45)
Functional Design Specification – Substation Automation System
A function block for protection tripping is provided for each circuit breaker involved in the
tripping of the fault. It provides the pulse prolongation to ensure a trip pulse of sufficient
length, as well as all functionality necessary for correct co-operation with auto reclosing
functions. The trip function block includes functionality for evolving faults and breaker lock-
out.
The output pulse from the protection function block may be short which may not be sufficient
enough for the trip coil to energise. Hence, all the protection outputs are connected to the
PTRC block thereby extending the pulse duration ensuring correct operation of all functions.
Document
Functional Design Specification - SAS Sale Order :
Prepared
Divya S 4200057645
Checked
M.V.Girish
Dept
PS SAS Created 2009-06-24 Revision 02 Yr 09 Wk 26 Lang En
YN1M301338
1338--ZAA
YN1M301338 16
(45)
Functional Design Specification – Substation Automation System
Twelve trip matrix logic blocks are included in the IED. The function blocks are used in the
configuration of the IED to route trip signals and/or other logical output signals to the different
output relays. The matrix and the physical outputs will be seen in the PCM600 engineering
tool and this allows the user to adapt the signals to the physical tripping outputs according to
the specific application needs.
A high number of logic blocks and timers are available to adapt the configuration to the
specific application needs.
Protection and Control IED Manager PCM 600 is an easy-to-handle tool providing versatile
functionalities required throughout the life cycle of ABB's protection and control IEDs in
transmission and distribution applications. Its Microsoft Windows based user interface with
many familiar and easy-to-use functions adds to operating comfort. PCM 600 features fast
and reliable downloading and uploading of configuration and settings as well as uploading of
disturbance files both locally and remotely. It utilizes TCP/IP via corporate LAN or WAN, or
alternatively directly through the communication port at the front of the IED.
Disturbance Handling
Time Scheduler
Document
Functional Design Specification - SAS Sale Order :
Prepared
Divya S 4200057645
Checked
M.V.Girish
Dept
PS SAS Created 2009-06-24 Revision 02 Yr 09 Wk 26 Lang En
YN1M301338
1338--ZAA
YN1M301338 17
(45)
Functional Design Specification – Substation Automation System
Signal Monitoring
Event Viewer
Document
Functional Design Specification - SAS Sale Order :
Prepared
Divya S 4200057645
Checked
M.V.Girish
Dept
PS SAS Created 2009-06-24 Revision 02 Yr 09 Wk 26 Lang En
YN1M301338
1338--ZAA
YN1M301338 18
(45)
Functional Design Specification – Substation Automation System
The main purpose of the function is to measure and process signals from different measuring
transducers. Many devices used in process control represent various parameters such as
frequency, temperature and DC battery voltage as low current values, usually in the range 4-
20 mA. Alarm limits can be set and used as triggers, e.g. to generate trip or alarm signals.
The function requires that the IED is equipped with the mA input module.
The hardware of the station level system provided for the 400kV control room consists of the
following:
The SAS conforms to IEC 61850 standards and has a decentralized architecture consisting of
the main functional parts explained in the introduction part.
The SAS is based on ABB make MicroSCADA Pro software running in a redundant hot
standby mode on two industrial PCs with Microsoft Windows 2003 Server Operating System
supported by MicroSCADA software. The windows firewall will be envisaged in the system.
The SAS provides an extensive range of Supervisory Control and Data Acquisition (SCADA)
functions
YN1M301338
1338--ZAA
YN1M301338 19
(45)
Functional Design Specification – Substation Automation System
Full station level HMI include 2 No OWS, one LVS for special user functions such as station
single line diagram, overviews, control of circuit breakers and isolators, alarm lists and event
lists, logging of historical data for trends and reports.
The system will be controlled with the help of a mouse and keyboard. If required, system
engineering can also be done from the Station HMI. All alarm and event logs will be printed
out on the DMP printer. The reports and graphics will be printed on the Colour Laser printer.
The communication to the remote load dispatch centers uses IEC 60870-5-101 (slave)
protocol, with the remote centre as the master and the local gateway as the slave. It is
possible to control and monitor the local station from remote control centers; however remote
control centre will decide the default control point.
In addition to the above the gateway interface to Main Plant SCADA (DCS) uses OPC
connectivity.
4.2.1 Redundant Application server (Main/standby controllers) and Station HMI (Operating work
stations)
The redundant Application servers (Two numbers in SCR, Two numbers in CCR) consist of
industrial PCs with INTEL XEON microprocessor, running Windows 2003 Server operating
system. Monitoring and controlling of the station is through Operator workstations (Station
HMI) by the use of project specific pictures. A mouse is used to move the cursor and thus
navigate on and between picture pages. The PCs work on 230 V AC power supply.
The operator interface is based upon a hierarchical set of menu pages, which provide access
to overview, alarm list, event list and other pages. An authorization mechanism prevents
system access of unauthorized users and also allows assignment of a number of
authorization levels. This makes certain functions accessible only to users who have been
granted the required level of authorization.
Document
Functional Design Specification - SAS Sale Order :
Prepared
Divya S 4200057645
Checked
M.V.Girish
Dept
PS SAS Created 2009-06-24 Revision 02 Yr 09 Wk 26 Lang En
YN1M301338
1338--ZAA
YN1M301338 20
(45)
Functional Design Specification – Substation Automation System
The communication infrastructure consists of a fibre optic, managed, switched Ethernet LAN
in a redundant fault tolerant ring configuration. This LAN is used for both station level and
inter bay communications. The communication protocol conforms to IEC 61850-8-1 standard.
Bay Ethernet switches are provided in all the panels (BCU &BPU panels) wherever an IED is
mounted. By this the requirement of locating Ethernet switches as close to the IEDs is
assured and further it is assured that no FO cables runs between IEDs and bay Ethernet
switches through cable trenches. The IEDs are connected to the switch using fibre optic
cables. At the station level the Ethernet switches Provide dual LAN output for further interface
to Operators work stations. The main features of the Ethernet switches used are listed below:
Designed for harsh environment – exceeds IEC 61850-3 requirements for use in
electrical substations
Full compliance with IEEE 802.3 and IEEE 802.3u Ethernet standards for universal
interoperability
Enhanced Rapid Spanning Tree (IEEE 802.1w) for fault tolerance with fast recovery
times (<5ms)
Quality of service / Class of service (IEEE 802.1p) for prioritization of traffic (real time
traffic for software interlocks)
The time master is a GPS receiver provided in the SAS. The GPS receiver is connected to
the Ethernet LAN and it synchronizes all the IEDs, the redundant HMIs and the remote
communication gateways directly. In conformance with the IEC 61850 standards, SNTP
protocol is used for time synchronization function.
A desktop PC running Windows XP operating system along with the disturbance evaluation
software acts as the DR workstation. The application server automatically downloads the DR
Document
Functional Design Specification - SAS Sale Order :
Prepared
Divya S 4200057645
Checked
M.V.Girish
Dept
PS SAS Created 2009-06-24 Revision 02 Yr 09 Wk 26 Lang En
YN1M301338
1338--ZAA
YN1M301338 21
(45)
Functional Design Specification – Substation Automation System
data from the IEDs in the pre-defined time intervals. The downloading of DR data can also be
done manually on operator’s request.
The operator or protection engineer can access these DR files and analyze them using the
DR evaluation software. The disturbance waveforms are printed on the colour laser printer. In
addition to Disturbance data evaluation, the same work station facilitates Parameterisation
and configuration of the IEDs
Gateways (Two numbers each) are provided in SCR and CCR) for remote connectivity. The
gateway in SCR has serial port for communication to the RLDC on IEC 60870-5-101 (Slave)
and RJ45 port for communication to the OS Control Room on OPC connectivity. Further
connectivity to Owner’s OS Control room is not in ABB scope. The port for RLDC has
V.24/V28 Communication standard (ITU-T, formerly CCITT standard) interfaces for
connection to the communication channels being provided by NTPC. The communication
speed is selectable independently for each port and can be set to a maximum of 9600 bauds;
however the use of PLCC will restrict the communication speed to a maximum of 1200 bauds.
ABB make NSK5 modems shall also be supplied for interfacing with RLDC.
The Substation LAN is extended to the Main Plant control room through fibre optic
communication equipment. The SAS also provides gateway on OPC connectivity for Main
plant interface (DCS) in CCR.
The operator interface is based on MicroSCADA Pro (SYS600) software that runs on
Windows operating system. SYS 600 software consists of the basic functions needed to
monitor and control substations.
Application pictures are used to visualize the supervised processes. There are many different
types of application pictures: single line diagrams, process pictures, system supervision, lists,
application tools, measurement reports and trend reports. Generally, only one application
picture is presented within one monitor (Monitor Pro). The opening of another function closes
or hides the previous one. However, several monitors can be opened to the same application.
Each user can modify the layout of Monitor Pro. The user specific layout is saved when the
user logs out and it is loaded when the user logs into the application.
The system specific start picture is the first picture displayed when Monitor Pro is started.
When Monitor Pro starts, it requires login before the session can continue.The Close button in
the login dialog closes the login dialog but not Monitor Pro.
Document
Functional Design Specification - SAS Sale Order :
Prepared
Divya S 4200057645
Checked
M.V.Girish
Dept
PS SAS Created 2009-06-24 Revision 02 Yr 09 Wk 26 Lang En
YN1M301338
1338--ZAA
YN1M301338 22
(45)
Functional Design Specification – Substation Automation System
In the login dialog, there is a combo box, in which the current "HOT" applications are shown.
The start picture requests a user name and password. Each user is associated with a certain
user profile defined by the system manager.
The password is not displayed on the screen. If the user name and the password do not
match, or the user name does not exist, the login dialog reappears and you can make a new
attempt. Each attempt to log in is registered by the system, even those that are failed.
If the login succeeds, the substation overview picture is produced on the screen. All
operations subsequently performed on the Monitor Pro, are related to the authority profile
associated with the user name. The user name is also included in as an identifier in the event
register when certain manual operations are performed.
4.3.2 Logout
In Monitor Pro, logout means that the user name and user authority are cleared. The user is
logged out when:
Monitor Pro is closed down by using the Close button or the Main/Exit menu item
Document
Functional Design Specification - SAS Sale Order :
Prepared
Divya S 4200057645
Checked
M.V.Girish
Dept
PS SAS Created 2009-06-24 Revision 02 Yr 09 Wk 26 Lang En
YN1M301338
1338--ZAA
YN1M301338 23
(45)
Functional Design Specification – Substation Automation System
After a certain predefined time, e.g. 8 hours, an automatic logout is done. The logout duration
is defined in the Application Settings, i.e. the setting is user specific. The user has to login
again via the Login dialog.
An Application Settings picture can be given new settings by selecting Options-Settings in the
main menu bar. Only a user with rights on system management level (system manager) can
change the application settings. It is used to create some application specific settings such
as:
Application owner: the name of the customer to whom this product is licensed (in this
case – NTPC). The name of the application owner cannot be changed in the
Application settings picture.
First picture shown after login: defines the first picture that pops up after a user logs
in.
Lockout duration: this sets the session length. When the lockout duration time
expires, the authorization level is reset to View (0). The lockout duration time is given
in hours (from 1 to 254). The session duration can be activated or deactivated.
Show object ID: this defines the parts of the Object Identity attributes that are to be
shown in Alarm lists, Event lists and dialogs.
HD space alarm: Hard Disk Supervision function supervises the free Hard Disk
space. This function gives the operator an early warning if there is a risk of running
out of space on the hard disk. The supervision function is stopped when the limit is
set to zero.
Report Settings: this is used to define, among others, the base period for the reports
(15, 30 or 60 minutes) and the history length (1 year to 5 years). These settings are
valid for the entire application and changing these later will erase the existing history
data.
Document
Functional Design Specification - SAS Sale Order :
Prepared
Divya S 4200057645
Checked
M.V.Girish
Dept
PS SAS Created 2009-06-24 Revision 02 Yr 09 Wk 26 Lang En
YN1M301338
1338--ZAA
YN1M301338 24
(45)
Functional Design Specification – Substation Automation System
The user with rights on system management level (system manager) can make changes in
the User Management function. In the LIB 500 applications the standard functions in the
process pictures can be freely grouped into authorization groups. This means that a user can
have different authorization levels for different apparatus. Users can also be defined to have
different authorization levels for different tools, substations etc. (see Figure 12).
Document
Functional Design Specification - SAS Sale Order :
Prepared
Divya S 4200057645
Checked
M.V.Girish
Dept
PS SAS Created 2009-06-24 Revision 02 Yr 09 Wk 26 Lang En
YN1M301338
1338--ZAA
YN1M301338 25
(45)
Functional Design Specification – Substation Automation System
View (0) level: The user is allowed to view the substation status, but is not authorized
to make any control operations, or to use the programming and system configuration
tools.
Control (1) level: The user is allowed to make control operations, but he has no
access to the engineering and system configuration tools.
Engineering (2) level: The user is granted all rights for control, engineering and
system configuration, except system management.
System management (3) level: The user is granted all rights including the rights to
add and remove users. Only one user can be granted this authorization level.
The number of users and their authorization levels will be decided during the detailed
engineering stage. The system manager can add and remove users and user groups as well
as change the authorization levels. All users can change their own passwords.
The Process Display is a view, which is displayed when the user is logged into an application.
The process displays appear on the MicroSCADA Pro Monitor. They contain information on
the status of the process in the form of Single Line Diagrams (SLD) having graphical objects
with dynamic behaviour. Process displays in the MicroSCADA Pro Monitor contain the
functionality for zooming, panning and de-cluttering of displays.
The user interacts with the MicroSCADA system through the control dialogs accessed from
the process display. Only those users, who belong to certain user groups, are allowed to
execute control operations towards the process devices of the MicroSCADA system.
The SAS will have the 400kV substation SLD as the main process display. The substation
SLD will have the following information.
Document
Functional Design Specification - SAS Sale Order :
Prepared
Divya S 4200057645
Checked
M.V.Girish
Dept
PS SAS Created 2009-06-24 Revision 02 Yr 09 Wk 26 Lang En
YN1M301338
1338--ZAA
YN1M301338 26
(45)
Functional Design Specification – Substation Automation System
Line current, voltage, active power, reactive power and power factor
Bus bar colouring to identify powered, non powered and earthed segments of the
SLD
It is also possible to control the switchgears from this picture. Further, it provides access to
other pictures like event list, alarm list, trends and reports.
In addition to the above process displays, a ‘soft LED’ is also provided for indicating
‘synchronising in limit’ conditions. Further for doing a check while synchronising, both
Incoming and Running voltages and frequency will be displayed near to each breaker picture.
YN1M301338
1338--ZAA
YN1M301338 27
(45)
Functional Design Specification – Substation Automation System
Display Builder is the picture editor in MicroSCADA that is used to create complete graphical
interfaces. You can define the graphical appearance of objects in your interface, describe the
data they will display, and specify their dynamic behavior. The drawing process requires no
programming. Drawings are easy to create and edit directly in the drawing area, and dialogs
let you control all aspects of the editing process, including assigning display characteristics
and specifying how your data is stored. Display Builder provides default values for every
dynamic element of a drawing so you can quickly construct a complete dynamic drawing that
can monitor and control substations as well as electrical power transmission and distribution
systems.
The control dialogs provide fast and easy access to a device in a substation. The control
dialog combines different kind of information, depending on the object. Control dialogs
interact with standard objects created with Object Navigator by using standard library
functions.
Control dialogs are generic and they have same user-interface appearance, independent of
the IED and the communication protocol defined in standard object configuration. Only one
control dialog can be open at a time for each Monitor Pro window.
The station local/remote control shows whether the control is authorized from the station
locally or from an external control centre.
Document
Functional Design Specification - SAS Sale Order :
Prepared
Divya S 4200057645
Checked
M.V.Girish
Dept
PS SAS Created 2009-06-24 Revision 02 Yr 09 Wk 26 Lang En
YN1M301338
1338--ZAA
YN1M301338 28
(45)
Functional Design Specification – Substation Automation System
This control dialog has three tabs; Main tab, Message tab and Blocking tab. Main tab lets you
select the Local/Remote option. The options available depend on object configuration.
Unavailable options are dimmed. In Messages tab, different messages concerning the object
are shown. In Blocking tab, different blockings concerning the process object are shown and
controlled.
The Bay L/R control shows the whether the control of the bay is authorized from the bay unit
locally or remotely over a communication link. If the Bay L/R switch is remotely controllable, it
is possible to change the switch state from the control dialog.
Document
Functional Design Specification - SAS Sale Order :
Prepared
Divya S 4200057645
Checked
M.V.Girish
Dept
PS SAS Created 2009-06-24 Revision 02 Yr 09 Wk 26 Lang En
YN1M301338
1338--ZAA
YN1M301338 29
(45)
Functional Design Specification – Substation Automation System
This control dialog has three tabs; Main tab, Message tab and Blocking tab. Main tab lets you
select the Local/Remote option. The options available depend on object configuration.
Unavailable options are dimmed. In Messages tab, different messages concerning the object
are shown. In Blocking tab, different blockings concerning the process object are shown and
controlled.
Switch control dialogs can be used to show current state and status of a switch device object.
It is also used for operating the switch device. The same dialog is used for circuit breakers
and isolators. There are several tabs on this dialog. Navigate between the tabs navigation by
using the arrow buttons on the upper-right corner of the dialog.
Document
Functional Design Specification - SAS Sale Order :
Prepared
Divya S 4200057645
Checked
M.V.Girish
Dept
PS SAS Created 2009-06-24 Revision 02 Yr 09 Wk 26 Lang En
YN1M301338
1338--ZAA
YN1M301338 30
(45)
Functional Design Specification – Substation Automation System
The upper field of the main tab shows the object identification: station, bay and the object. The lower
field of the tab shows the object status. If control is not blocked, the Close button or Open button is
active. If, based on the interlock conditions, the selection of the control command is successful, the
Execute or Cancel symbol buttons become active. Confirm the control operation by clicking the
Execute button. Cancel the selection by clicking the Cancel symbol button. Possible errors during
operation appear in the Object status field of the Switch state tab. Close the dialog by clicking Exit or
click the icon on the upper-right corner of the dialog. If, based on the interlock conditions, the selection
of the control command is unsuccessful; the operator can view the object, which is blocking the
permissive in the SLD picture where that object will be shown in a flashing mode.
Incase of Breaker switch control dialog, if synchrocheck conditions are not met, the operator can view
a dialogue ‘ Device not synchronised’ in the switch control dialog. If in case Interlock conditions are
not met a dialogue ‘Device’ s Open/Close Interlocked’ appears in the switch control dialogue. The
latter is applicable for switch control dialogues of Isolators and Earth switches also.
Document
Functional Design Specification - SAS Sale Order :
Prepared
Divya S 4200057645
Checked
M.V.Girish
Dept
PS SAS Created 2009-06-24 Revision 02 Yr 09 Wk 26 Lang En
YN1M301338
1338--ZAA
YN1M301338 31
(45)
Functional Design Specification – Substation Automation System
Blocking tab
In the Blocking tab of the Switch control dialog, different blockings concerning the process
objects are displayed.
In the Forced operation tab, the internal blockings and control blockings can be bypassed.
After this, the Open and Close buttons are enabled. However, this does not disable any
interlockings or other IED measures, that is, no special bypass messages are sent to the
IEDs.
Event is a wide term that also comprises alarms. The event activation and consequential
actions are defined in the process database separately for each individual object.
Document
Functional Design Specification - SAS Sale Order :
Prepared
Divya S 4200057645
Checked
M.V.Girish
Dept
PS SAS Created 2009-06-24 Revision 02 Yr 09 Wk 26 Lang En
YN1M301338
1338--ZAA
YN1M301338 32
(45)
Functional Design Specification – Substation Automation System
The purpose of the Event List is to provide the user with information about events occurring in
the system. It is also provides information about activities carried out by other users,
operations of objects, acknowledging of alarms, editing of limit values, logging in and so on.
The Event List presents the data in a structured way for the user’s convenience. Each event
is presented by displaying an event text line, which consists of a time stamp, object
identification, a signal text and a text indicating the status.
Fast navigation using the scroll bar: jump to the last page, one page back or forward
and so on.
Possibility to navigate to the previous day or next day or to a day typed into the input
dialog
YN1M301338
1338--ZAA
YN1M301338 33
(45)
Functional Design Specification – Substation Automation System
Additional comments can be given to the events (up to 250 characters per event)
Color settings
Find
Column sort
If the Event List is in the updating mode, the list will be updated when a new event occurs in
the system. When the list is in the frozen mode (non-updating), a message will be displayed
informing the user to change the mode to the updating mode and view the latest events.
When the Event List is in the updating mode, half a page will be shown when the list is
presented on the screen. All the new events are presented on the remaining half a page until
the page is full. When the page is full, it scrolls up a half page and new events begin to fill the
page again.
When the Event List is in the updating mode, the events are sorted in the order which they
were written into history database, i.e. logging order. The order defined in the Settings dialog
is applied in the frozen mode.
It is possible to configure certain events to use different colors in the Event List. This improves
the possibility to locate certain system events. E.g. important events, which cause alarms in
the system, can be defined to use the red color in the Event List.
Document
Functional Design Specification - SAS Sale Order :
Prepared
Divya S 4200057645
Checked
M.V.Girish
Dept
PS SAS Created 2009-06-24 Revision 02 Yr 09 Wk 26 Lang En
YN1M301338
1338--ZAA
YN1M301338 34
(45)
Functional Design Specification – Substation Automation System
Filters are used when the user wants to display or concentrate on specific information. It is
possible to change the existing filters or add new filters that can be stored and reused by
other operators.
By clicking the left mouse button on a column header in the event list, the event list is sorted
on the column clicked. If the same column is clicked twice, the sorting is descending. After the
data is sorted, the list is set to Frozen mode. Column sort is reset when the list mode is
changed back to Update.
The Find tool allows the user to search for text within the current event list view. The Find tool
searches the list from the start to the end. If an event line contains the desired text, it is
selected. A message box appears when find has reached the end point of the search or when
searched text is not found.
The Alarm List displays a summary of the present alarm situation of the supervised process.
Each alarm is presented as an alarm text line, which has a time stamp, an object id, an object
text, a text indicating the alarm status, as well as a number ranging from 1-7 indicating the
alarm class.
Document
Functional Design Specification - SAS Sale Order :
Prepared
Divya S 4200057645
Checked
M.V.Girish
Dept
PS SAS Created 2009-06-24 Revision 02 Yr 09 Wk 26 Lang En
YN1M301338
1338--ZAA
YN1M301338 35
(45)
Functional Design Specification – Substation Automation System
Figure
Figure 16 : Alarm List (Template 2)*
The process alarms are alarms that are related to the supervised process, for example,
measurement values exceeding or going below the preset alarm limits, breakers tripping or
getting into a faulty position and so on.
The internal alarms are alarms caused by the network control system itself. Reasons for
these alarms include communication problems between a communication unit and substation,
printer device errors, substation getting suspended, etc.
User-friendly filters
YN1M301338
1338--ZAA
YN1M301338 36
(45)
Functional Design Specification – Substation Automation System
Alarm acknowledgement
Locate Object
Column sort
Find
An acknowledgement of an alarm is a way to show that the operator has registered and
identified the alarm. Generally, acknowledging an alarm does not affect the alarm state. An
unacknowledged alarm remains in the alarm buffer until it is acknowledged, even if the alarm
state has passed.
Alarm blocking blocks a signal in such a way that it cannot generate an alarm. (The same
implies for history blocking, printout blocking and reprocessing blocking.) Since the alarm is
blocked, it is not registered in the process database when the process object gets into an
alarm generating state.
Document
Functional Design Specification - SAS Sale Order :
Prepared
Divya S 4200057645
Checked
M.V.Girish
Dept
PS SAS Created 2009-06-24 Revision 02 Yr 09 Wk 26 Lang En
YN1M301338
1338--ZAA
YN1M301338 37
(45)
Functional Design Specification – Substation Automation System
The alarms can be grouped into seven equally significant alarm classes. This feature can be
used when the user wants to group alarms caused by process objects with common
properties. From the system point of view there is no internal priority between the different
alarm classes. The alarm classes can also be used when searching alarms from the alarm
buffer. By setting the alarm class to 0, the alarm function of a process object is set off.
Filters are used when the user wants to concentrate on certain information in the alarm buffer.
This is done by defining criteria to filter out unwanted information. A single criterion or multiple
criteria can be used for filtering. The alarm list filter settings are identical to the event list filter
settings (Figure 14 : Event list filter settings*
The alarm buffer is updated every time the alarm state of a process object changes. Basically,
the Alarm List should be updated at each update of the alarm buffer to give correct and up-to-
date information. However, if the list is updated frequently, it is almost impossible to
concentrate on a single alarm line. This is the reason why the Alarm List has two presentation
modes: frozen and updating. When the list is in the frozen mode, it is not updated, and the
alarm information can be read easily. If the alarm buffer is updated while the Alarm List is in
the frozen mode, the operator is notified with an informative text on the status bar. When in
the updating mode, the Alarm List is updated at every update of the alarm buffer. The frozen
mode is automatically selected when the list is scrolled or when a tool affecting the alarm
buffer is used. The current mode is always indicated.
By clicking the left mouse button on a list column header, the alarm list is sorted. The column
that is used for sorting is the column that was clicked. If the same column is clicked twice, the
sorting is in descending order. After the data is sorted, the list is set to the Frozen mode. The
column sort is reset when the list mode is changed back to Update.
The Find function allows you to search for text within the current alarm list view. Find
searches through the list from the beginning point down. The alarm line that contains
searched text is set selected. A message box appears when Find has reached the end point
of the search or when searched text does not exist.
Acknowledgement of a single alarm is done by selecting the alarm text line of the desired
alarm on the list. If the selected alarm is unacknowledged, selecting Acknowledge from the
pop-up menu can open the Acknowledgement dialog. At the same time the Alarm List is set to
the frozen mode to prevent unwanted scrolling.
The Blocking List summarizes the present blocking situation of the signals of the supervised
process. Each signal is presented as a signal text line, which describes the signal in the
process. The signal text line normally consists of a signal text and a group of check boxes
indicating the blocking state.
Document
Functional Design Specification - SAS Sale Order :
Prepared
Divya S 4200057645
Checked
M.V.Girish
Dept
PS SAS Created 2009-06-24 Revision 02 Yr 09 Wk 26 Lang En
YN1M301338
1338--ZAA
YN1M301338 38
(45)
Functional Design Specification – Substation Automation System
Alarm blocking: alarms are not raised, regardless of the object state.
Event blocking: event registrations are not made, events are not shown in the Event
List.
Document
Functional Design Specification - SAS Sale Order :
Prepared
Divya S 4200057645
Checked
M.V.Girish
Dept
PS SAS Created 2009-06-24 Revision 02 Yr 09 Wk 26 Lang En
YN1M301338
1338--ZAA
YN1M301338 39
(45)
Functional Design Specification – Substation Automation System
The available time ranges for the reports are listed below:
• Hourly report (time resolution: 3 minutes)
• Daily report (time resolution: 15 minutes)
• Daily report (time resolution: 30 minutes)
• Daily report (time resolution: 60 minutes)
• Weekly report (time resolution: 1 day)
• Monthly report (time resolution: 1 day)
• Yearly report (time resolution: 1 month)
The storage period for the reports can be up to 5 years. Longer storage periods can be
custom built or achieved by exporting data to an external reporting database.
Figure 19:
19: Measurement Reports (Tabular Form)
Document
Functional Design Specification - SAS Sale Order :
Prepared
Divya S 4200057645
Checked
M.V.Girish
Dept
PS SAS Created 2009-06-24 Revision 02 Yr 09 Wk 26 Lang En
YN1M301338
1338--ZAA
YN1M301338 40
(45)
Functional Design Specification – Substation Automation System
Figure 20:
20: Measurement Reports (Graphical form)
MicroSCADA Monitor Pro includes the new Trend Application. Trend Application is used for
trend analyses and for showing measured values in the form of a curve or a table.
Document
Functional Design Specification - SAS Sale Order :
Prepared
Divya S 4200057645
Checked
M.V.Girish
Dept
PS SAS Created 2009-06-24 Revision 02 Yr 09 Wk 26 Lang En
YN1M301338
1338--ZAA
YN1M301338 41
(45)
Functional Design Specification – Substation Automation System
Document
Functional Design Specification - SAS Sale Order :
Prepared
Divya S 4200057645
Checked
M.V.Girish
Dept
PS SAS Created 2009-06-24 Revision 02 Yr 09 Wk 26 Lang En
YN1M301338
1338--ZAA
YN1M301338 42
(45)
Functional Design Specification – Substation Automation System
Hairline function
• Using legend
Document
Functional Design Specification - SAS Sale Order :
Prepared
Divya S 4200057645
Checked
M.V.Girish
Dept
PS SAS Created 2009-06-24 Revision 02 Yr 09 Wk 26 Lang En
YN1M301338
1338--ZAA
YN1M301338 43
(45)
Functional Design Specification – Substation Automation System
• Printout option
• Update/Frozen modes
A trend is a time-related follow-up of process data. All types of process objects, e.g. analogue
and digital data can be illustrated as trends.
When the trend picture is shown, the user can select the data from the trend basket. When
the trend basket is closed, the selected trends are brought to the trend picture. Trend view
configuration includes a set of parameters such as colors, fonts, etc., which are called trend
preconfigurations. Users can create, delete or apply existing preconfiguration to the trend
picture.
The SYS 600 System Self Supervision (SSS) is used with the MicroSCADA systems for
supervising and monitoring the system. It provides status information of hardware and
software, as well as picture functions for the supervision of system objects.
Document
Functional Design Specification - SAS Sale Order :
Prepared
Divya S 4200057645
Checked
M.V.Girish
Dept
PS SAS Created 2009-06-24 Revision 02 Yr 09 Wk 26 Lang En
YN1M301338
1338--ZAA
YN1M301338 44
(45)
Functional Design Specification – Substation Automation System
Figure 24 : Example
Example of System Supervision picture*
Document
Functional Design Specification - SAS Sale Order :
Prepared
Divya S 4200057645
Checked
M.V.Girish
Dept
PS SAS Created 2009-06-24 Revision 02 Yr 09 Wk 26 Lang En
YN1M301338
1338--ZAA
YN1M301338 45
(45)
Annexure–
Annexure– Bay Functions
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties
without express authority is strictly forbidden. Copyright © by ABB Limited
Document
Annexure –Bay Functions Sale Order :
Prepared
Neetha MD 4200057645
Checked
M.V.Girish
Dept
PS SAS Created 2009-10-22 Revision 01 Yr 09 Wk 42 Lang En
YN1M301338
1338--ZAB
YN1M301338 ZAB 1 (24)
Annexure–
Annexure– Bay Functions
Table of Contents:
1 General ............................................................................................................... 5
2 Bay...................................................................................................................... 5
YN1M301338
1338--ZAB
YN1M301338 ZAB 2 (24)
Annexure–
Annexure– Bay Functions
Table of Figures:
Figure 1: Configuration of 400 kV Line bay IEDs .............................................. 12
Document
Annexure –Bay Functions Sale Order :
Prepared
Neetha MD 4200057645
Checked
M.V.Girish
Dept
PS SAS Created 2009-10-22 Revision 01 Yr 09 Wk 42 Lang En
YN1M301338
1338--ZAB
YN1M301338 ZAB 3 (24)
Annexure–
Annexure– Bay Functions
Document
Annexure –Bay Functions Sale Order :
Prepared
Neetha MD 4200057645
Checked
M.V.Girish
Dept
PS SAS Created 2009-10-22 Revision 01 Yr 09 Wk 42 Lang En
YN1M301338
1338--ZAB
YN1M301338 ZAB 4 (24)
Annexure–
Annexure– Bay Functions
1 General
This document explains briefly about the bay level IED’s hardware and
functionality. It also includes bay level protection details along with IED
features as enabled for each bay for both Main-I and Main-II.
2 Bay
A bay comprises of one circuit breaker and associated disconnectors, earth
switches and instrument transformers.
Each bay control IED is independent of the others and its functioning is not
affected by any fault occurring in any of the other bay control units of the
station.
The data exchange among bay level IEDs and between bay level and station
level takes place via the fibre-optic inter bay bus according to IEC 61850-8-1
standard. The use of fibre-optic LAN guarantees disturbance-free
communication.
Though, at station level, the entire station is controlled and supervised from
the station HMI, it is possible to control and monitor the bay from the bay level
equipment, whenever required. The decentralized architecture ensures that
station wide interlocking is available even when the station computer fails.
Separate IEDs are provided for bay control function and bay protection
function. For line bays, Auto reclose function is configured in the respective
bay control units. A backup autorecloser function is configured in a BPU
(Main-1 distance relay, REL670 for lines that will be enabled in case of failure
of BCU).
Document
Annexure –Bay Functions Sale Order :
Prepared
Neetha MD 4200057645
Checked
M.V.Girish
Dept
PS SAS Created 2009-10-22 Revision 01 Yr 09 Wk 42 Lang En
YN1M301338
1338--ZAB
YN1M301338 ZAB 5 (24)
Annexure–
Annexure– Bay Functions
Note The bay level functionalities shall be as per the approved Scheme.
Note:
Single shot auto reclose function (RREC, 79), with single phase or
three phase reclosing facility.
Document
Annexure –Bay Functions Sale Order :
Prepared
Neetha MD 4200057645
Checked
M.V.Girish
Dept
PS SAS Created 2009-10-22 Revision 01 Yr 09 Wk 42 Lang En
YN1M301338
1338--ZAB
YN1M301338 ZAB 6 (24)
Annexure–
Annexure– Bay Functions
As per IEC 61850, the primary equipments are also represented as LNs, and
the ones used in this bay are:
Isolators (XSWI)
Since process bus (IEC 61850-9-2) is not used, these LNs are hardwired
inputs and outputs of the control and protection IEDs. XCBR and XSWI
represent the status inputs from, and command outputs to the breaker and
isolators. TCTR and TVTR are the current and voltage inputs respectively
from the instrument transformers.
The function has a built in algorithm for load encroachment, which increases
the possibility to detect high resistive faults on heavily loaded lines. The
independent measurement of impedance for each fault loop together with a
sensitive and reliable built in phase selection makes the function suitable in
applications with single phase auto reclosing.
Document
Annexure –Bay Functions Sale Order :
Prepared
Neetha MD 4200057645
Checked
M.V.Girish
Dept
PS SAS Created 2009-10-22 Revision 01 Yr 09 Wk 42 Lang En
YN1M301338
1338--ZAB
YN1M301338 ZAB 7 (24)
Annexure–
Annexure– Bay Functions
Automatic switch onto fault logic is a function that gives an instantaneous trip
at closing of breaker onto a fault. A dead line detection check is provided to
activate the function when the line is dead.
Document
Annexure –Bay Functions Sale Order :
Prepared
Neetha MD 4200057645
Checked
M.V.Girish
Dept
PS SAS Created 2009-10-22 Revision 01 Yr 09 Wk 42 Lang En
YN1M301338
1338--ZAB
YN1M301338 ZAB 8 (24)
Annexure–
Annexure– Bay Functions
The weak-end infeed logic is used in cases where the apparent power behind
the protection can be too low to activate the distance protection function.
When activated, received carrier signal together with local under voltage
criteria and no reverse zone operation gives an instantaneous trip. The
received signal is also echoed back to accelerate the sending end.
The method based on detection of zero sequence voltage without any zero
sequence current. This is a useful principle in a directly earthed system and
can detect one or two phase fuse failures.
YN1M301338
1338--ZAB
YN1M301338 ZAB 9 (24)
Annexure–
Annexure– Bay Functions
that closing can be done safely. The function includes a built-in voltage
selection scheme for double bus and one- and a half or ring busbar
arrangements. Manual closing as well as automatic reclosing can be checked
by the function and can have different settings, e.g. the allowed frequency
difference can be set to allow wider limits for the auto-reclose attempt than for
the manual closing. A synchronizing function providing closing of the breaker
at the correct instance when network parts are running asynchronous is also
provided.
Document
Annexure –Bay Functions Sale Order :
Prepared
Neetha MD 4200057645
Checked
M.V.Girish
Dept
PS SAS Created 2009-10-22 Revision 01 Yr 09 Wk 42 Lang En
YN1M301338
1338--ZAB
YN1M301338 ZAB 10
(24)
Annexure–
Annexure– Bay Functions
For the station-wide interlocking, the IEDs communicate via the system-wide
interbay bus (IEC 61850-8-1) or by using hard wired binary inputs/outputs.
The interlocking conditions depend on the circuit configuration and apparatus
position status at any given time.
The IED for Main 1 distance protection is ABB make REL 670 (with
communication module), while for Main 2 we have used Siemens make
7SA522 relay. The bay control IED is ABB make REC 670, with built in mimic.
The bay control IED is designed to control (switch ON / OFF), along with all
necessary interlocks. It also measures voltages (R-Y, Y-B, and B-R), currents
(R, Y and B) and active and reactive power for each line.
The Auto Reclose (RREC) function of 400 kV line bays is integrated in the
respective Bay control IED REC 670. Check synchronizing functions required
for auto reclose function is also integrated within the same IED for easy
coordination. A backup autorecloser function is configured in a BPU (Main-1
Document
Annexure –Bay Functions Sale Order :
Prepared
Neetha MD 4200057645
Checked
M.V.Girish
Dept
PS SAS Created 2009-10-22 Revision 01 Yr 09 Wk 42 Lang En
YN1M301338
1338--ZAB
YN1M301338 ZAB 11
(24)
Annexure–
Annexure– Bay Functions
distance relay, REL 670 for lines and that will be enabled in case of failure of
BCU.
All intra-bay interlocks are software based and performed by the BCU. The
complete bay can be monitored and controlled from the local HMI on the
BCU.
Station wide interlocks are software based; the data for the interlocks are
transmitted using GOOSE messages by the individual IEDs. To provide
backup for these GOOSE messages, GOOSE messages will be duplicated.
i.e., a BCU requiring status of one equipment in another bay will receive that
status as GOOSE message from two BCUs simultaneously .In case of failure
of one of those two BCUs, still status will be available from the other BCU.
This ensures that failure of one Bay does not affect the operation of another.
However no duplication is envisaged for GOOSE signals used for DR triggerin
Document
Annexure –Bay Functions Sale Order :
Prepared
Neetha MD 4200057645
Checked
M.V.Girish
Dept
PS SAS Created 2009-10-22 Revision 01 Yr 09 Wk 42 Lang En
YN1M301338
1338--ZAB
YN1M301338 ZAB 12
(24)
Annexure–
Annexure– Bay Functions
Isolators (XSWI)
Reactor (ZREA)
As in the case of line bays, these LNs are hardwired inputs and outputs of the
control and protection IEDs.
Document
Annexure –Bay Functions Sale Order :
Prepared
Neetha MD 4200057645
Checked
M.V.Girish
Dept
PS SAS Created 2009-10-22 Revision 01 Yr 09 Wk 42 Lang En
YN1M301338
1338--ZAB
YN1M301338 ZAB 13
(24)
Annexure–
Annexure– Bay Functions
All intra-bay interlocks are software based and performed by the BCU. The
complete bay can be monitored and controlled from the local HMI on the
BCU. Station wide interlocks are software based; the data for the interlocks
are transmitted using GOOSE messages by the individual IEDs. To provide
backup for these GOOSE messages, GOOSE messages will be duplicated.
I.e., a BCU requiring status of one equipment in another bay will receive that
status as GOOSE message from two BCUs simultaneously .In case of failure
of one of those two BCUs, still status will be available from the other BCU.
This ensures that failure of one Bay does not affect the operation of another.
Document
Annexure –Bay Functions Sale Order :
Prepared
Neetha MD 4200057645
Checked
M.V.Girish
Dept
PS SAS Created 2009-10-22 Revision 01 Yr 09 Wk 42 Lang En
YN1M301338
1338--ZAB
YN1M301338 ZAB 14
(24)
Annexure–
Annexure– Bay Functions
REC 670
RET 670-
670-1 RET670-
RET670-2
CSWI RSYN
PDIF PDIF
CSWI
CILO IHMI
XCBR
XCBR TCTR XCBR TCTR
XSWI TCTR
ZREA TVTR ZREA TVTR
XSWI TVTR
Fault function.
Restricted earth fault protection (PDIF, 64R) for HV, LV1 & LV2
Standby earth fault protection (PTEF, 51N) for LV1 & LV2
Document
Annexure –Bay Functions Sale Order :
Prepared
Neetha MD 4200057645
Checked
M.V.Girish
Dept
PS SAS Created 2009-10-22 Revision 01 Yr 09 Wk 42 Lang En
YN1M301338
1338--ZAB
YN1M301338 ZAB 15
(24)
Annexure–
Annexure– Bay Functions
Isolators (XSWI)
As in the case of line bays, these LNs are hardwired inputs and outputs of the
control and protection IEDs.
All current inputs are provided with percentage bias restraint features, making
RET670 suitable for two or three winding transformers in multi-breaker station
arrangements.
Document
Annexure –Bay Functions Sale Order :
Prepared
Neetha MD 4200057645
Checked
M.V.Girish
Dept
PS SAS Created 2009-10-22 Revision 01 Yr 09 Wk 42 Lang En
YN1M301338
1338--ZAB
YN1M301338 ZAB 16
(24)
Annexure–
Annexure– Bay Functions
The setting facilities cover applications of the differential protection to all types
of power transformers and autotransformers with or without onload tap-
changer. An adaptive stabilizing feature is included for heavy through-faults.
All intra-bay interlocks are software based and performed by the BCU. The
complete bay can be monitored and controlled from the local HMI on the
BCU. Additionally, hardwired switches are provided to operate the breaker
during emergencies. During such emergency operations all interlocks are
bypassed. Station wide interlocks are software based; the data for the
interlocks are transmitted using GOOSE messages by the individual IEDs.
Document
Annexure –Bay Functions Sale Order :
Prepared
Neetha MD 4200057645
Checked
M.V.Girish
Dept
PS SAS Created 2009-10-22 Revision 01 Yr 09 Wk 42 Lang En
YN1M301338
1338--ZAB
YN1M301338 ZAB 17
(24)
Annexure–
Annexure– Bay Functions
CSWI MMXU
RDRE RDRE
CILO IHMI
XCBR
TCTR XCBR TCTR XCBR TCTR
XSWI
YPTR TVTR YPTR TVTR
XSWI TVTR
RET 670-
670-3
PDIF PVPH
RDRE RBRF
XCBR TCTR
YPTR TVTR
Document
Annexure –Bay Functions Sale Order :
Prepared
Neetha MD 4200057645
Checked
M.V.Girish
Dept
PS SAS Created 2009-10-22 Revision 01 Yr 09 Wk 42 Lang En
YN1M301338
1338--ZAB
YN1M301338 ZAB 18
(24)
Annexure–
Annexure– Bay Functions
YN1M301338
1338--ZAB
YN1M301338 ZAB 19
(24)
Annexure–
Annexure– Bay Functions
Isolators (XSWI)
As in the case of line bays, these LNs are hardwired inputs and outputs of the
control and protection IEDs.
All current inputs are provided with percentage bias restraint features, making
RET670 suitable for two or three winding transformers in multi-breaker station
arrangements.
Document
Annexure –Bay Functions Sale Order :
Prepared
Neetha MD 4200057645
Checked
M.V.Girish
Dept
PS SAS Created 2009-10-22 Revision 01 Yr 09 Wk 42 Lang En
YN1M301338
1338--ZAB
YN1M301338 ZAB 20
(24)
Annexure–
Annexure– Bay Functions
The setting facilities cover applications of the differential protection to all types
of power transformers and autotransformers with or without onload tap-
changer. An adaptive stabilizing feature is included for heavy through-faults.
YN1M301338
1338--ZAB
YN1M301338 ZAB 21
(24)
Annexure–
Annexure– Bay Functions
the load current voltage drop is compensated for to get a fully true flux
measurement. The over excitation function measures the U/f ratio which gives
a measure of the magnetic flux in transformers and generators.
REG670
REG670/7UM622
670/7UM622 RET 670-
670-1 RET 670
670-2
PDIS RFUF
PDOP PDUP
TCTR
XCBR TCTR
XCBR TCTR
XCBR TVTR YPTR TVTR
YPTR TVTR
Document
Annexure –Bay Functions Sale Order :
Prepared
Neetha MD 4200057645
Checked
M.V.Girish
Dept
PS SAS Created 2009-10-22 Revision 01 Yr 09 Wk 42 Lang En
YN1M301338
1338--ZAB
YN1M301338 ZAB 22
(24)
Annexure–
Annexure– Bay Functions
RET 670-
670-3 RET 670-
670-4 RET 670-
670-5
The REB 670 IED (Intelligent Electronic Device) is designed for the protection
and monitoring of busbars, T-connections and meshed corners from medium
to extra high voltage levels. Due to its extensive I/O capability, REB 670
protects single and double busbars with or without transfer bus, double circuit
breaker or one-and-half circuit breaker arrangements.
It provides selective, reliable and fast fault clearance for all types of internal
phase-to-phase and phase-to-earth faults in solidly earthed or low-impedance
earthed power systems. This IED features extremely short operate time,
typically 12 ms, for most internal faults regardless of number of connected
feeders. At the same time, it maintains complete stability for external faults,
even when heavy CT saturation occurs. It can also handle all internal multi-
phase faults in isolated or high-impedance earthed power systems.
YN1M301338
1338--ZAB
YN1M301338 ZAB 23
(24)
Annexure–
Annexure– Bay Functions
REB 670
PBDF RBRF
XCBR TCTR
XSWI RDRE
XSWI
Figure
Figure 5: Configuration of 400 kV REB 670
Document
Annexure –Bay Functions Sale Order :
Prepared
Neetha MD 4200057645
Checked
M.V.Girish
Dept
PS SAS Created 2009-10-22 Revision 01 Yr 09 Wk 42 Lang En
YN1M301338
1338--ZAB
YN1M301338 ZAB 24
(24)
PCM600 Project Aspects
PCM600 STARTUP
REVISION TABLE
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties
without express authority is strictly forbidden. Copyright © by ABB Limited
Document
PCM600 Project Aspects Sale Order :
Prepared
Deepa Lakshmi S
Approved
M V Girish
Dept Lang En
PS-SAS Created 2008.05.04 Revision 0 Yr 07 Wk 01
Page
ABB Ltd, India. 1 (17)
1MYN900031-001
PCM600 Project Aspects
Table of Contents:
1 About This Document.......................................................................................... 4
4 CAP 531............................................................................................................ 13
Table of Figures:
Figure 1: PCM 600 Display ........................................................................................ 4
Document
PCM600 Project Aspects Sale Order :
Prepared
Deepa Lakshmi S
Approved
M V Girish
Dept Lang En
PS-SAS Created 2008.05.04 Revision 0 Yr 07 Wk 01
Page
ABB Ltd, India. 2 (17)
1MYN900031-001
PCM600 Project Aspects
Document
PCM600 Project Aspects Sale Order :
Prepared
Deepa Lakshmi S
Approved
M V Girish
Dept Lang En
PS-SAS Created 2008.05.04 Revision 0 Yr 07 Wk 01
Page
ABB Ltd, India. 3 (17)
1MYN900031-001
PCM600 Project Aspects
Document
PCM600 Project Aspects Sale Order :
Prepared
Deepa Lakshmi S
Approved
M V Girish
Dept Lang En
PS-SAS Created 2008.05.04 Revision 0 Yr 07 Wk 01
Page
ABB Ltd, India. 4 (17)
1MYN900031-001
PCM600 Project Aspects
2 Engineering Workflow
The step-by-step procedure for creating a new project is shown below.
Document
PCM600 Project Aspects Sale Order :
Prepared
Deepa Lakshmi S
Approved
M V Girish
Dept Lang En
PS-SAS Created 2008.05.04 Revision 0 Yr 07 Wk 01
Page
ABB Ltd, India. 5 (17)
1MYN900031-001
PCM600 Project Aspects
Step 4: Create a new Substation. In the Object Properties edit the caption as AA1.
Document
PCM600 Project Aspects Sale Order :
Prepared
Deepa Lakshmi S
Approved
M V Girish
Dept Lang En
PS-SAS Created 2008.05.04 Revision 0 Yr 07 Wk 01
Page
ABB Ltd, India. 6 (17)
1MYN900031-001
PCM600 Project Aspects
Step 5: Create the voltage level. Choose the voltage level from the Voltage Range in the
Object properties. For example, the voltage level selected here is 220kV. The technical
Key is AA1D1.
Step 6: Create a new bay. Change the caption to corresponding bay name. For example,
The bay name here is Q01.
Document
PCM600 Project Aspects Sale Order :
Prepared
Deepa Lakshmi S
Approved
M V Girish
Dept Lang En
PS-SAS Created 2008.05.04 Revision 0 Yr 07 Wk 01
Page
ABB Ltd, India. 7 (17)
1MYN900031-001
PCM600 Project Aspects
Step 7: The appropriate IEDs are taken. For Example, here REC 670 IEC Version 1.1 is
chosen.
NOTE: The IED type will be Generic IED initially. Once the IED is configured using
configuration wizard, it will change to IED670.
Document
PCM600 Project Aspects Sale Order :
Prepared
Deepa Lakshmi S
Approved
M V Girish
Dept Lang En
PS-SAS Created 2008.05.04 Revision 0 Yr 07 Wk 01
Page
ABB Ltd, India. 8 (17)
1MYN900031-001
PCM600 Project Aspects
Step 9: Right click on the IED. Go to Configuration Wizard.
Document
PCM600 Project Aspects Sale Order :
Prepared
Deepa Lakshmi S
Approved
M V Girish
Dept Lang En
PS-SAS Created 2008.05.04 Revision 0 Yr 07 Wk 01
Page
ABB Ltd, India. 9 (17)
1MYN900031-001
PCM600 Project Aspects
Step 11: Then, IED Protocol should be selected.
Document
PCM600 Project Aspects Sale Order :
Prepared
Deepa Lakshmi S
Approved
M V Girish
Dept Lang En
PS-SAS Created 2008.05.04 Revision 0 Yr 07 Wk 01
Page
ABB Ltd, India. 10
1MYN900031-001
(17)
PCM600 Project Aspects
3 Communication Settings
Each IED is provided with a communication interface, enabling it to connect to one or many
substation level systems or equipment, either on the Substation Automation (SA) bus or
Substation Monitoring (SM) bus. Establishing the communication between the relays is very
vital in the substation automation system for horizontal and vertical communication. Single or
double optical Ethernet ports for the new substation communication standard IEC61850-8-1
for the station bus are provided and one RJ 45 port is available for programming and setting
of the relays.
3. Make sure the relay IP address matches with that of in the configuration before establishing
communication.
4. Ensure that the system IP address should match with relay subnet masking.
5. Go to network settings and set the TCP/IP properties as shown below. The IP address is
obtained from the architectural drawing made in visio using IET.
Document
PCM600 Project Aspects Sale Order :
Prepared
Deepa Lakshmi S
Approved
M V Girish
Dept Lang En
PS-SAS Created 2008.05.04 Revision 0 Yr 07 Wk 01
Page
ABB Ltd, India. 11
1MYN900031-001
(17)
PCM600 Project Aspects
Rear OEM-port AB. IEC61850-8-1 operation is made ON. This can be made directly from the
HMI or right click on the IED Parameter Settings. Change the PC value and can be loaded
to the IED.
Document
PCM600 Project Aspects Sale Order :
Prepared
Deepa Lakshmi S
Approved
M V Girish
Dept Lang En
PS-SAS Created 2008.05.04 Revision 0 Yr 07 Wk 01
Page
ABB Ltd, India. 12
1MYN900031-001
(17)
PCM600 Project Aspects
4 CAP 531
The IED is configured using CAP531 (Configuration and Programming tool).
Step 2: This screen will appear. Type the password as “abb”. It is not case-sensitive.
Document
PCM600 Project Aspects Sale Order :
Prepared
Deepa Lakshmi S
Approved
M V Girish
Dept Lang En
PS-SAS Created 2008.05.04 Revision 0 Yr 07 Wk 01
Page
ABB Ltd, India. 13
1MYN900031-001
(17)
PCM600 Project Aspects
Step 3: Click on the IED. Go to Edit Insert. This is to insert a new worksheet. Give a name
to the worksheet.
Document
PCM600 Project Aspects Sale Order :
Prepared
Deepa Lakshmi S
Approved
M V Girish
Dept Lang En
PS-SAS Created 2008.05.04 Revision 0 Yr 07 Wk 01
Page
ABB Ltd, India. 14
1MYN900031-001
(17)
PCM600 Project Aspects
Step 5: To enter a text on the worksheet, click on the “T” symbol shown. Double click on the
sheet. The font properties can be edited.
Document
PCM600 Project Aspects Sale Order :
Prepared
Deepa Lakshmi S
Approved
M V Girish
Dept Lang En
PS-SAS Created 2008.05.04 Revision 0 Yr 07 Wk 01
Page
ABB Ltd, India. 15
1MYN900031-001
(17)
PCM600 Project Aspects
Step 6: To add a function block into the worksheet, press “ F” on the worksheet or click on the
symbol that is shown in the toolbar. Choose the required function block from the list.
Document
PCM600 Project Aspects Sale Order :
Prepared
Deepa Lakshmi S
Approved
M V Girish
Dept Lang En
PS-SAS Created 2008.05.04 Revision 0 Yr 07 Wk 01
Page
ABB Ltd, India. 16
1MYN900031-001
(17)
PCM600 Project Aspects
Document
PCM600 Project Aspects Sale Order :
Prepared
Deepa Lakshmi S
Approved
M V Girish
Dept Lang En
PS-SAS Created 2008.05.04 Revision 0 Yr 07 Wk 01
Page
ABB Ltd, India. 17
1MYN900031-001
(17)
LARSEN & TOUBRO LIMITED
ECC DIVISION, EDRC – Electrical
Project 400/220kV GIS SWITCHYARD PACKAGE FOR VALLUR THERMAL POWER PROJECT (2x500MW + 1x500MW)
Client NTPC TAMILNADU ENERGY COMPANY LIMITED (NTECL)
Consultant -
Title COMPLIANCE REPORT FOR FUNCTIONAL DESIGN SPECIFICATION OF SAS. Date: 18.11.09
Ref. As per NTPC comments Dt: 04.11.09
Please provide details for each bay IED here also. Provide this details
6. bay wise. Please refer approved FDS for Jhajjar for this.
Complied.
Include details for interlocking function of the IEDs along with the
7. required functions for this. Please refer approved FDS for Jhajjar for Complied.
this.
Page 1 of 5
LARSEN & TOUBRO LIMITED
ECC DIVISION, EDRC – Electrical
Project 400/220kV GIS SWITCHYARD PACKAGE FOR VALLUR THERMAL POWER PROJECT (2x500MW + 1x500MW)
Client NTPC TAMILNADU ENERGY COMPANY LIMITED (NTECL)
Consultant -
Title COMPLIANCE REPORT FOR FUNCTIONAL DESIGN SPECIFICATION OF SAS. Date: 18.11.09
Ref. As per NTPC comments Dt: 04.11.09
For information on the frame and interpretation of the same, the standard
(61850-1) may be referred to. Same can be explained during FAT.
W.r.t the time taken for traverse of GOOSE messages: Latency of the
Please describe in detail with respect to the speed and the limit on Ethernet communication network is the time taken to traverse the message
number of goose messages sent/receive by any IED. Please clarify if form the transmitter to the receiver. The prominent sources of latency in an
there is any limit with respect to information storage with respect to this. Ethernet switched communication network are:
8. Also include the details regarding, how each device identify and
interprets the information, its source and meaning. Please ensure that (a) Store and Forward Latency L(SF) which is directly proportional to the size
each detail shall provide discrete example for the communication of the frame being transmitted and inversely proportional to the baud rate.
between the devices. L(SF) = FS/BR. It is approx 0.120ms for baud rate of 100MPBS and the
maximum frame size.
(b) Switch Fabric Latency L(SW) which is switch dependent and internal to
the switch. It is approx 0.0052ms for RuggedCOM make switch.
(c) Wireline Latency L(WL). Predominant in long distances of networks of
approx 100KM. In the present case it is insignificant as the distance is less
than a KM.
(d) Queuing Latency L(Q). Depends upon the traffic patterns of the network.
L(Q) = Network Load x L(SF). Most of the cases the no of IEDs connected
are in such a way that the network load is less than about 25% on an
average. The basis for bus loading calculation is as per IEC61850-5
Page 2 of 5
LARSEN & TOUBRO LIMITED
ECC DIVISION, EDRC – Electrical
Project 400/220kV GIS SWITCHYARD PACKAGE FOR VALLUR THERMAL POWER PROJECT (2x500MW + 1x500MW)
Client NTPC TAMILNADU ENERGY COMPANY LIMITED (NTECL)
Consultant -
Title COMPLIANCE REPORT FOR FUNCTIONAL DESIGN SPECIFICATION OF SAS. Date: 18.11.09
Ref. As per NTPC comments Dt: 04.11.09
The first three latency values are deterministic while queuing latency is non-
deterministic. Based on the above, L(TOTAL) = [L(SF)+L(SW)+L(WL)+L(Q)] x
No of switches in the network.
L(Q) can be calculated as {[(FS) x No of Ports] / BR (MBPS)}. For a 8 port
switch L(Q) is {[(12288) x 7] / 100} = 0.86ms.
Calculating the latency per switch for the given application for the worst case
conditions with the largest frame size L(TOTAL) = [0.120 + 0.0052 + 0 + 0.86]
= 0.9852ms. For a ring of 21 switches, the worst case latency would be
approx 20.6ms for the longest route and the highest frame size and fully
loaded bus. Which means the switch latency for one subnet in the present
application is less than 4ms considering 25% bus load on an average.
The output pulse from the protection function block may be short which may
not be sufficient enough for the trip coil to energise. Hence, all the protection
Tripping Logic & Trip Matrix Logic (PTRC, 94):
11. Please provide detailed description outputs are connected to the PTRC block thereby extending the pulse
duration ensuring correct operation of all functions.
Same is included & explained in clause no 4.1.3 of the FDS.
Please provide details about PCM 600. Also highlight if soft logic
12. preparation is also through PCM600, if yes, please provide the steps Kindly refer the attached Annexure-PCM.
and difference with reference to PST.
Process display for processes with dynamic behaviour shall be
13. included. Display in the form of SLD shall also be included. Please refer Complied.
approved FDS for Jhajjar for this.
Page 3 of 5
LARSEN & TOUBRO LIMITED
ECC DIVISION, EDRC – Electrical
Project 400/220kV GIS SWITCHYARD PACKAGE FOR VALLUR THERMAL POWER PROJECT (2x500MW + 1x500MW)
Client NTPC TAMILNADU ENERGY COMPANY LIMITED (NTECL)
Consultant -
Title COMPLIANCE REPORT FOR FUNCTIONAL DESIGN SPECIFICATION OF SAS. Date: 18.11.09
Ref. As per NTPC comments Dt: 04.11.09
Please confirm with the manufacturers limit on the number of metering
14. inputs to the converter? i.e. how many meters can be connected to the 32 meters can be connected.
converter?
On the capacity please provide the number of inputs able to connect
There are 20 ports available in the Ethernet switch. All the ports can be
15. through one Ethernet switch. Also if possible one diagram with terminal
used.
detail for the Ethernet switch can be provided here.
Please confirm if history for the changes made in the previous login is
also available in the SYS600 software. If yes, please specify how many
16. and through which login the data has been changed? Is this all also
Yes. The same thing can be viewed in the Event list
configured through the software?
"HOT" -The application is running. Its databases are stored
in the primary memory.
"WARM" -The application is not running, but the databases
17. Define HOT ,WARM & COLD state. are loaded and accessible.
"COLD" -The application is not running and not accessible,
but it may receive file shadow input from another
Application.
Please clarify if this (Display builder) operation is active even after the
18. users have been assigned view level? No. That option will be freezed for View level user.
Please provide brief description of these (update, control alarm..etc) Please refer the Clause 4.3.9 of FDS for the same and hence these are set in
19. blocking operations. What will each of these actions react as? the blocking Tab submenu.
These are not interlocks. Forced operation option will force the objects to
operate on your command even if another user is connected to them or the
Please describe these two interlockings?
20. (Internal Blockings & Control Blockings) function is normally not permitted. However, this does not disable any
interlockings or other IED measures, that is, no special bypass messages are
sent to the IEDs.
Forced operation does not disable any interlockings or other IED measures,
Please ensure/confirm that the Forced Operation does not bypass the
21. interlock as built within the IED. that is, no special bypass messages are sent to the IEDs.
Page 4 of 5
LARSEN & TOUBRO LIMITED
ECC DIVISION, EDRC – Electrical
Project 400/220kV GIS SWITCHYARD PACKAGE FOR VALLUR THERMAL POWER PROJECT (2x500MW + 1x500MW)
Client NTPC TAMILNADU ENERGY COMPANY LIMITED (NTECL)
Consultant -
Title COMPLIANCE REPORT FOR FUNCTIONAL DESIGN SPECIFICATION OF SAS. Date: 18.11.09
Ref. As per NTPC comments Dt: 04.11.09
Based on the functions the Alarms can be prioritised into different alarm
classes.
The base system software does not make any distinction between the
classes, but applications may use alarm classes to categorise alarms,
The application engineer can choose how to group the objects in alarm
22. Can the priority be defined among different alarm classes? classes. They can, for example, be grouped based on the location of the
process objects or alarm
severity. An object with alarm class 0 has no alarm function.
Changing AC from 0 to another value or vice versa does not affect the alarm
state of the object.
23. Are these commands set from blocking tab sub-menu? Yes.
Please clarify that trends are to be defined by the user or shall these be
24. defined by the system by default/ could these be configurable? The trend are to be defined by the user and the same is configurable.
Please ensure that bay level details shall be as per the protection
25. scheme for each bay. This shall be ensure for all the bays. Complied.
26. Clearly highlight that this is only for line bays. Complied.
Please ensure that all this descriptions for all the bays shall confirm
28. with the protection scheme with each bay. Complied.
Page 5 of 5