TRPPTRC1 - Tripping Logic
TRPPTRC1 - Tripping Logic
86
TRPPTRC1
OR6
BLOCK TRIP 86_LOCKOUT_TRIP
PROT_TRIP+LOCKOUT B1 O OPERATE CL_LKOUT
B2 RESET_SIGNAL RST_LKOUT
B3 O:48|T:2.5|I:1
B4
B5
B6
O:43|T:2.5|I:3 NOT
B B
IN OUT 86_LOCKOUT_OK
O:54|T:2.5|I:15
50BF
CCBRBRF1
F_TRIG OR6
BLOCK CB_FAULT_AL
START TRBU 50BF_TRBU_TR CLK Q B1 O RESET_SIGNAL
CB_CLOSED_&_SERV POSCLOSE TRRET O:65|T:2.5|I:0 B2
CB_FAULT B3
O:84|T:2.5|I:1 B4
B5
RESET_ALARMS_CMD B6
O:75|T:2.5|I:5
C C
OR6
OC_PROT_TR B1 O PROT_TRIP+LOCKOUT
EF_PROT_TR B2
B3
87L_LNPLDF1_TR B4
D 49T_T1PTTR1_TR B5 D
46_NSPTOC1_TR B6
O:36|T:2.5|I:7
OR6
B1 O PROT_TRIP
27T_TR B2
B3
B4
B5
B6
O:77|T:2.5|I:4
E E
LEDPTRC1
RESET_SIGNAL RESET OUT_START LEDPTRC1[1]_OUT_START
B OUT_OPERATE LEDPTRC1[1]_OUT_OPERATE B
OUT_ST_A
OUT_OPR_A
OUT_ST_B
OUT_OPR_B
OUT_ST_C
OUT_OPR_C
OUT_ST_NEUT
OUT_OPR_NEUT
O:106|T:2.5|I:1
C C
D D
E E
A The Protection Main Application sheets contain protection function blocks with predefined variables. A
If you want to enable ANSI names of protection functions set parameter in Tool->Options->
System Settings-> Naming Style.
If protection function is not used, delete relevant function blocks and the variables.
After that, check the application configuration.
50_I>>>
PHIPTOC1
B B
BLOCK OPERATE 50_I>>>_TR
68_INRUSH_BLK ENA_MULT START 50_I>>>_ST
O:18|T:2.5|I:1
50t_I>>
DPHHPDOC1
BLOCK OPERATE 50t_I>>_TR
ENA_MULT START 50t_I>>_ST
NON_DIR
O:19|T:5|I:1
51_I>
C DPHLPDOC1 C
BLOCK OPERATE 51_I>_TR
ENA_MULT START 51_I>_ST
NON_DIR
O:20|T:5|I:1
E E
A The Protection Main Application sheets contain protection function blocks with predefined variables. A
If you want to enable ANSI names of protection functions set parameter in Tool->Options->
System Settings-> Naming Style.
If protection function is not used, delete relevant function blocks and the variables.
After that, check the application configuration.
B 50N_Io>>>_TR B
50N_Io>>>_ST
50N_Io>>
EFHPTOC1
BLOCK OPERATE 50N_Io>>_TR
68_INRUSH_BLK ENA_MULT START 50N_Io>>_ST
O:21|T:5|I:1
C C
51N_Io>
DEFLPDEF1
BLOCK OPERATE 51N_Io>_TR
ENA_MULT START 51N_Io>_ST
RCA_CTL
O:22|T:5|I:1
E E
A The Protection Main Application sheets contain protection function blocks with predefined variables. A
If you want to enable ANSI names of protection functions set parameter in Tool->Options->
System Settings-> Naming Style.
If protection function is not used, delete relevant function blocks and the variables.
After that, check the application configuration.
68
C INRPHAR1 C
BLOCK BLK2H 68_INRUSH_BLK
O:14|T:2.5|I:1
E E
A The Protection Main Application sheets contain protection function blocks with predefined variables. A
If you want to enable ANSI names of protection functions set parameter in Tool->Options->
System Settings-> Naming Style.
If protection function is not used, delete relevant function blocks and the variables.
After that, check the application configuration.
27T
PHPTUV1
B B
VOLT PROT BLOCK BLOCK OPERATE 27T_TR
START 27T_ST OR
O:35|T:5|I:1
27T_TR B1 O
27R_TR B2
O:39|T:2.5|I:6
AND
B1 O 27_CUM_TRIP
X110_BI7_VT_MCB_CLOSED B2
O:45|T:2.5|I:7
27P
PHPTUV2
VOLT PROT BLOCK BLOCK OPERATE 27R_TR
START 27R_ST
C O:34|T:5|I:2 C
D D
Grouped function operate
OR6
OR
27T_TR B1 O PHPTUV_OPERATE
B2 X110_BI7_VT_MCB_CLOSED B1 O VOLT PROT BLOCK
B3 B2
B4 O:25|T:2.5|I:11
B5
B6
O:96|T:2.5|I:1
E E
A The Protection Main Application sheets contain protection function blocks with predefined variables. A
If you want to enable ANSI names of protection functions set parameter in Tool->Options->
System Settings-> Naming Style.
If protection function is not used, delete relevant function blocks and the variables.
After that, check the application configuration.
BSTGGIO1
X130_BI2_POWER_TRAFO_ALARM SEND_SIG_1 RECV_SIG_1 REMOTE_CLOSE_PERMIT_FROM_UPSTREAM 87L
B X130_BI3_POWER_TRAFO_TRIP SEND_SIG_2 RECV_SIG_2 REMOTE_INTERTRIP_FROM_UPSTREAM B
INTERTRIP_TO_UPSTREAM SEND_SIG_3 RECV_SIG_3 LNPLDF1
SEND_SIG_4 RECV_SIG_4 OR
SEND_SIG_5 RECV_SIG_5 BLOCK OPERATE 87L_LNPLDF1_TR
LOCAL_LV_INCOMER_READY SEND_SIG_6 RECV_SIG_6 REMOTE_MV_FEEDER_READY CCSPVC1_FAIL B1 O BLOCK_LS START 87L_LNPLDF1_ST
CBXCBR1_OPENPOS SEND_SIG_7 RECV_SIG_7 REMOTE_MV_CB_OPEN REMOTE_CCSPVC_FAIL B2 ENA_MULT_HS STR_LS_LOC
CCSPVC1_FAIL SEND_SIG_8 RECV_SIG_8 REMOTE_CCSPVC_FAIL O:16|T:2.5|I:8 STR_LS_REM
SEND_SIG_A BSTGGIO1_SEND_SIG_A OPR_LS_LOC
RECV_SIG_A BSTGGIO1_RECV_SIG_A OPR_LS_REM
O:13|T:2.5|I:1 OPR_HS_LOC
OR OPR_HS_REM
BLKD2H_LOC
REMOTE_MV_FEEDER_READY B1 O BLKD2H_REM
REMOTE_MV_CB_OPEN B2 PRO_ACTIVE 87L_LNPLDF1_PROT_ACTIVE
O:17|T:2.5|I:10 O:27|T:2.5|I:1
C C
NOT
87L_LNPLDF1_PROT_ACTIVE IN OUT LNPLDF1_PROT_NOT_ACTIVE
O:101|T:2.5|I:7
D D
E E