TRPPTRC1 - Tripping Logic

1. The document discusses the Tripping Main Application sheets which can be used for inserting tripping function blocks called TRPPTRC. 2. It provides an example of how to properly parameterize and check the activation logic of the TRPPTRC tripping logic block. 3. The TRPPTRC block is used to provide tripping signals to various protection functions like overcurrent, undervoltage, etc. based on configured logic and timing settings.

Uploaded by

square17.gopi
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
469 views7 pages

TRPPTRC1 - Tripping Logic

1. The document discusses the Tripping Main Application sheets which can be used for inserting tripping function blocks called TRPPTRC. 2. It provides an example of how to properly parameterize and check the activation logic of the TRPPTRC tripping logic block. 3. The TRPPTRC block is used to provide tripping signals to various protection functions like overcurrent, undervoltage, etc. based on configured logic and timing settings.

Uploaded by

square17.gopi
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 7

1 2 3 4 5 6 7 8

TRPPTRC1 - Tripping logic


A Check activation logic of TRPPTRC logic . A
The Tripping Main Application sheets can be used for inserting tripping function
Parametrize TRPPTRC properly
blocks (TRPPTRC).

86
TRPPTRC1
OR6
BLOCK TRIP 86_LOCKOUT_TRIP
PROT_TRIP+LOCKOUT B1 O OPERATE CL_LKOUT
B2 RESET_SIGNAL RST_LKOUT
B3 O:48|T:2.5|I:1
B4
B5
B6
O:43|T:2.5|I:3 NOT
B B
IN OUT 86_LOCKOUT_OK
O:54|T:2.5|I:15

50BF
CCBRBRF1
F_TRIG OR6
BLOCK CB_FAULT_AL
START TRBU 50BF_TRBU_TR CLK Q B1 O RESET_SIGNAL
CB_CLOSED_&_SERV POSCLOSE TRRET O:65|T:2.5|I:0 B2
CB_FAULT B3
O:84|T:2.5|I:1 B4
B5
RESET_ALARMS_CMD B6
O:75|T:2.5|I:5

C C

OR6
OC_PROT_TR B1 O PROT_TRIP+LOCKOUT
EF_PROT_TR B2
B3
87L_LNPLDF1_TR B4
D 49T_T1PTTR1_TR B5 D
46_NSPTOC1_TR B6
O:36|T:2.5|I:7

OR6
B1 O PROT_TRIP
27T_TR B2
B3
B4
B5
B6
O:77|T:2.5|I:4

E E

Main Application: Protection, Page: 1


1 2 3 4 5 6 7 8
Project Responsible department Technical reference Document kind Doc. designation
19-1049-EGPC CRUDE OIL TANK_CEAR ABB Ltd. Graphical Application Configuration pippo
Replacing Created by Title Document id.
RED615
19-1049-EGPC CRUDE OIL TANK_CEAR.Substation.0,4kV.Y- Approved by RED615 Rev. Rel. date Lang.
Rev. Modification Rel. date Created by Based on 787 0 5/30/2021 en
1/7
1 2 3 4 5 6 7 8

General start and general operate page


A
The Start/Operate Main Application sheets contain start and operate A
signals from protection functions blocks.

Remember if you add a new protection function block to the


configuration. Check the activation logic. Add also connections
to this place also.

LEDPTRC1
RESET_SIGNAL RESET OUT_START LEDPTRC1[1]_OUT_START
B OUT_OPERATE LEDPTRC1[1]_OUT_OPERATE B
OUT_ST_A
OUT_OPR_A
OUT_ST_B
OUT_OPR_B
OUT_ST_C
OUT_OPR_C
OUT_ST_NEUT
OUT_OPR_NEUT
O:106|T:2.5|I:1

C C

D D

E E

Main Application: Protection, Page: 2


1 2 3 4 5 6 7 8
Project Responsible department Technical reference Document kind Doc. designation
19-1049-EGPC CRUDE OIL TANK_CEAR ABB Ltd. Graphical Application Configuration pippo
Replacing Created by Title Document id.
RED615
19-1049-EGPC CRUDE OIL TANK_CEAR.Substation.0,4kV.Y- Approved by RED615 Rev. Rel. date Lang.
Rev. Modification Rel. date Created by Based on 787 0 5/30/2021 en
2/7
1 2 3 4 5 6 7 8

A The Protection Main Application sheets contain protection function blocks with predefined variables. A

If you want to enable ANSI names of protection functions set parameter in Tool->Options->
System Settings-> Naming Style.
If protection function is not used, delete relevant function blocks and the variables.
After that, check the application configuration.

Overcurrent protection function

50_I>>>
PHIPTOC1
B B
BLOCK OPERATE 50_I>>>_TR
68_INRUSH_BLK ENA_MULT START 50_I>>>_ST
O:18|T:2.5|I:1

50t_I>>
DPHHPDOC1
BLOCK OPERATE 50t_I>>_TR
ENA_MULT START 50t_I>>_ST
NON_DIR
O:19|T:5|I:1

51_I>
C DPHLPDOC1 C
BLOCK OPERATE 51_I>_TR
ENA_MULT START 51_I>_ST
NON_DIR
O:20|T:5|I:1

Grouped function operate


D D
OR6
50_I>>>_TR B1 O OC_PROT_TR
50t_I>>_TR B2
51_I>_TR B3
B4
B5
B6
O:30|T:2.5|I:38

E E

Main Application: Protection, Page: 3


1 2 3 4 5 6 7 8
Project Responsible department Technical reference Document kind Doc. designation
19-1049-EGPC CRUDE OIL TANK_CEAR ABB Ltd. Graphical Application Configuration pippo
Replacing Created by Title Document id.
RED615
19-1049-EGPC CRUDE OIL TANK_CEAR.Substation.0,4kV.Y- Approved by RED615 Rev. Rel. date Lang.
Rev. Modification Rel. date Created by Based on 787 0 5/30/2021 en
3/7
1 2 3 4 5 6 7 8

A The Protection Main Application sheets contain protection function blocks with predefined variables. A

If you want to enable ANSI names of protection functions set parameter in Tool->Options->
System Settings-> Naming Style.
If protection function is not used, delete relevant function blocks and the variables.
After that, check the application configuration.

Earth-fault protection function


Directional earthfault protection function

B 50N_Io>>>_TR B
50N_Io>>>_ST

50N_Io>>
EFHPTOC1
BLOCK OPERATE 50N_Io>>_TR
68_INRUSH_BLK ENA_MULT START 50N_Io>>_ST
O:21|T:5|I:1

C C
51N_Io>
DEFLPDEF1
BLOCK OPERATE 51N_Io>_TR
ENA_MULT START 51N_Io>_ST
RCA_CTL
O:22|T:5|I:1

Grouped function operate


D D
OR6
50N_Io>>>_TR B1 O EF_PROT_TR
50N_Io>>_TR B2
51N_Io>_TR B3
B4
B5
B6
O:29|T:2.5|I:0

E E

Main Application: Protection, Page: 4


1 2 3 4 5 6 7 8
Project Responsible department Technical reference Document kind Doc. designation
19-1049-EGPC CRUDE OIL TANK_CEAR ABB Ltd. Graphical Application Configuration pippo
Replacing Created by Title Document id.
RED615
19-1049-EGPC CRUDE OIL TANK_CEAR.Substation.0,4kV.Y- Approved by RED615 Rev. Rel. date Lang.
Rev. Modification Rel. date Created by Based on 787 0 5/30/2021 en
4/7
1 2 3 4 5 6 7 8

A The Protection Main Application sheets contain protection function blocks with predefined variables. A

If you want to enable ANSI names of protection functions set parameter in Tool->Options->
System Settings-> Naming Style.
If protection function is not used, delete relevant function blocks and the variables.
After that, check the application configuration.

Negative sequence overcurrent protection function Phase discontinuity protection function


46
NSPTOC1
B B
BLOCK OPERATE 46_NSPTOC1_TR
ENA_MULT START 46_NSPTOC1_ST
O:26|T:5|I:1

Inrush detector function

68
C INRPHAR1 C
BLOCK BLK2H 68_INRUSH_BLK
O:14|T:2.5|I:1

Thermal overload protection function


49T
T1PTTR1
BLK_OPR OPERATE 49T_T1PTTR1_TR
ENA_MULT START 49T_T1PTTR1_ST
AMB_TEMP ALARM 49T_T1PTTR1_ALARM
D BLK_CLOSE 49T_T1PTTR1_BLK_CLOSE D
O:28|T:5|I:1

E E

Main Application: Protection, Page: 5


1 2 3 4 5 6 7 8
Project Responsible department Technical reference Document kind Doc. designation
19-1049-EGPC CRUDE OIL TANK_CEAR ABB Ltd. Graphical Application Configuration pippo
Replacing Created by Title Document id.
RED615
19-1049-EGPC CRUDE OIL TANK_CEAR.Substation.0,4kV.Y- Approved by RED615 Rev. Rel. date Lang.
Rev. Modification Rel. date Created by Based on 787 0 5/30/2021 en
5/7
1 2 3 4 5 6 7 8

A The Protection Main Application sheets contain protection function blocks with predefined variables. A

If you want to enable ANSI names of protection functions set parameter in Tool->Options->
System Settings-> Naming Style.
If protection function is not used, delete relevant function blocks and the variables.
After that, check the application configuration.

Undervoltage protection function

27T
PHPTUV1
B B
VOLT PROT BLOCK BLOCK OPERATE 27T_TR
START 27T_ST OR
O:35|T:5|I:1
27T_TR B1 O
27R_TR B2
O:39|T:2.5|I:6

AND
B1 O 27_CUM_TRIP
X110_BI7_VT_MCB_CLOSED B2
O:45|T:2.5|I:7

27P
PHPTUV2
VOLT PROT BLOCK BLOCK OPERATE 27R_TR
START 27R_ST
C O:34|T:5|I:2 C

D D
Grouped function operate

OR6
OR
27T_TR B1 O PHPTUV_OPERATE
B2 X110_BI7_VT_MCB_CLOSED B1 O VOLT PROT BLOCK
B3 B2
B4 O:25|T:2.5|I:11
B5
B6
O:96|T:2.5|I:1

E E

Main Application: Protection, Page: 6


1 2 3 4 5 6 7 8
Project Responsible department Technical reference Document kind Doc. designation
19-1049-EGPC CRUDE OIL TANK_CEAR ABB Ltd. Graphical Application Configuration pippo
Replacing Created by Title Document id.
RED615
19-1049-EGPC CRUDE OIL TANK_CEAR.Substation.0,4kV.Y- Approved by RED615 Rev. Rel. date Lang.
Rev. Modification Rel. date Created by Based on 787 0 5/30/2021 en
6/7
1 2 3 4 5 6 7 8

A The Protection Main Application sheets contain protection function blocks with predefined variables. A

If you want to enable ANSI names of protection functions set parameter in Tool->Options->
System Settings-> Naming Style.
If protection function is not used, delete relevant function blocks and the variables.
After that, check the application configuration.

Binary signal transfer function Line differential protection function

BSTGGIO1
X130_BI2_POWER_TRAFO_ALARM SEND_SIG_1 RECV_SIG_1 REMOTE_CLOSE_PERMIT_FROM_UPSTREAM 87L
B X130_BI3_POWER_TRAFO_TRIP SEND_SIG_2 RECV_SIG_2 REMOTE_INTERTRIP_FROM_UPSTREAM B
INTERTRIP_TO_UPSTREAM SEND_SIG_3 RECV_SIG_3 LNPLDF1
SEND_SIG_4 RECV_SIG_4 OR
SEND_SIG_5 RECV_SIG_5 BLOCK OPERATE 87L_LNPLDF1_TR
LOCAL_LV_INCOMER_READY SEND_SIG_6 RECV_SIG_6 REMOTE_MV_FEEDER_READY CCSPVC1_FAIL B1 O BLOCK_LS START 87L_LNPLDF1_ST
CBXCBR1_OPENPOS SEND_SIG_7 RECV_SIG_7 REMOTE_MV_CB_OPEN REMOTE_CCSPVC_FAIL B2 ENA_MULT_HS STR_LS_LOC
CCSPVC1_FAIL SEND_SIG_8 RECV_SIG_8 REMOTE_CCSPVC_FAIL O:16|T:2.5|I:8 STR_LS_REM
SEND_SIG_A BSTGGIO1_SEND_SIG_A OPR_LS_LOC
RECV_SIG_A BSTGGIO1_RECV_SIG_A OPR_LS_REM
O:13|T:2.5|I:1 OPR_HS_LOC
OR OPR_HS_REM
BLKD2H_LOC
REMOTE_MV_FEEDER_READY B1 O BLKD2H_REM
REMOTE_MV_CB_OPEN B2 PRO_ACTIVE 87L_LNPLDF1_PROT_ACTIVE
O:17|T:2.5|I:10 O:27|T:2.5|I:1

C C

NOT
87L_LNPLDF1_PROT_ACTIVE IN OUT LNPLDF1_PROT_NOT_ACTIVE
O:101|T:2.5|I:7

D D

E E

Main Application: Protection, Page: 7


1 2 3 4 5 6 7 8
Project Responsible department Technical reference Document kind Doc. designation
19-1049-EGPC CRUDE OIL TANK_CEAR ABB Ltd. Graphical Application Configuration pippo
Replacing Created by Title Document id.
RED615
19-1049-EGPC CRUDE OIL TANK_CEAR.Substation.0,4kV.Y- Approved by RED615 Rev. Rel. date Lang.
Rev. Modification Rel. date Created by Based on 787 0 5/30/2021 en
7/7