The document describes an NX1000A combined overcurrent and earth fault relay. It has microprocessor-based numerical relaying with current measurement based on fundamental frequency. It provides three-phase, low-set and high-set overcurrent protection as well as low-set and high-set earth fault protection. It has local display of measured and set values, programmable relay outputs, and complies with IEC 60255 standards. It has ratings for 5A rated current at 50 or 60Hz and settings ranges for overcurrent and earth fault elements.

Uploaded by

AhmadAfiq
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
480 views2 pages

NX1000A

The document describes an NX1000A combined overcurrent and earth fault relay. It has microprocessor-based numerical relaying with current measurement based on fundamental frequency. It provides three-phase, low-set and high-set overcurrent protection as well as low-set and high-set earth fault protection. It has local display of measured and set values, programmable relay outputs, and complies with IEC 60255 standards. It has ratings for 5A rated current at 50 or 60Hz and settings ranges for overcurrent and earth fault elements.

Uploaded by

AhmadAfiq
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

Combined Overcurrent & Earth Fault Relay

www.itmikro.com

NX1000A
Features
• Microprocessor based numerical relay
• Current measurement based on fundamental
frequency
• Three-phase, low-set overcurrent
• Three-phase, high-set overcurrent
• Low-set earth-fault
• High-set earth-fault


• Local display of measured and set values
• Programmable relay outputs


• Complies with IEC 60255 standard
• ANSI Code : 50P, 50N, 51P, 51N

Technical Data
RATINGS SETTING RANGES INDICATORS
Rated current ( In ) :5 A I RCURRENT ELEMENT Auxiliary supply : Green indicator
Rated frequency : 50 or 60 Hz Low-set ( I> ) : 0.1 A to 10.0 A Pick-up : Red indicator
Burden : < 0.3 VA at In (2% to 200%) Trip : 7-segment display
Themal withstand : 4 x In : 0.01 to 1.0 and Red indicators
AUXILIARY SUPPLY : 0.00 sec to 100 sec
Model NX1000A-240A : 198 ~ 265 V AC High-set ( I>> ) : 0.5 A to 100 A
Model NX1000A-240AD : 85 ~ 265 V AC (10% to 2000%) ENVIRONMENTAL CONDITIONS
110 ~ 340 V DC or disable Temperature : -10˚C to +55˚C
Model MK1000A-150D : 24 ~ 150 V DC : 0.00 sec to 100 sec Humidity : 5% to 95%,
Supply frequency : 50 or 60 Hz non-condensing
: 3 VA typical
II EART FAULT ELEMENT
ACCURACY Low-set ( Io> ) : 0.10 A to 5.0 A,
: ± 5% (2% to 100%) MECHANICAL
Time delay : ± 5% with a o>) : 0.01 to 1.0 :
minimum of 50 ms o> ) : 0.00 sec to 100 sec Dimension (mm) : 96(w) x 96(h) x 110(d)
High-set ( Io>> ) : 0.10 A to 50 A : IP54 at the panel
OUTPUT CONTACTS (2% to 1000%) Approximate weight : 0.8 kg
Trip Contacts ( R1 & R2 ) or disable
Rated voltage : 250V AC / DC o>> ) : 0.00 sec to 100 sec
:5A
Expected electrical life (0.00 to 1.00, step 0.01; 1.00 to 10.0, step 0.10;
at rated current 10.0 to 100, step 0.5)
Expected mechanical life : 5 x 106
NX 1000A
Combined Overcurrent & Earth Fault Relay

www.itmikro.com

Normal Inverse Very Inverse Long Time Inverse Extremely Inverse

Normal Inverse 1.3/10 Typical Application Diagram Case Dimensions


96 mm
NX1000A

96 mm
Front

110 mm
100 mm

Side

91.0 ± 0.5 mm

91.0 ± 0.5 mm

Panel Cutout

Ordering Information
MODEL DESCRIPTION
NX1000A-240A For 50/60 Hz system, auxiliary voltage 198 ~ 265 V AC
NX1000A-240AD For 50/60 Hz system, auxiliary voltage 85 ~ 265 V AC or 110~340 V DC
NX1000A-150D For 50/60Hz system, auxiliary voltage 24 ~ 150 V DC