UPS Technical Specification
Manufacturer’s declaration in accordance with IEC 62040-3
Subclause Characteristic of Equipment Manufacturer's Declared Values
CONSTRUCTION
Model catalogue reference Eaton Power Xpert 9395P
Output:
Model rating
600 kVA pf 0.9 (540 kW) @ 400 Volts
VFI-SS-111
Classification
1880 x 880 x 1880 mm (UPS)
Dimensions length x depth x height
Weight without batteries 1350kg (UPS)
ENVIRONMENTAL
4.1.4 Ambient storage temperature range -25 to +60ºC in the protective package
4.1.2 Ambient service temperature UPS power electronics: +0 to +40ºC
1000m. Max transit Altitude is 15000m. At
4.1.1 Maximum service altitude maximum operating temperature without
derating. Derated per IEC 62040-3 Edition 2
4.1.3 Relative humidity range 5 to 95%, no condensation allowed
EN 60529 Degree of protection IP20
7.3 Acoustic noise at 1 m 76 dBA (ISO7779)
ELECTRICAL CHARACTERISTICS – INPUT
Rectifier input: 3x230/400V nominal;
Tolerance: (-15%, +15%) at 100% load,
5.2.2 and 6.3.2.1 Rated input voltage and voltage tolerance (-30%, +15%) at 50% load.
Bypass input: 3x230/400V nominal;
Tolerance: (-10%, +10%)
5.2.2 and 6.3.2.2 Rated input frequency and frequency tolerance 50 or 60 Hz, tolerance ±3 Hz
5.2.2 and 6.3.10 Rated input current 3 x 862 A r.m.s
5.2.2 and 6.3.9.2 Maximum input current 3 x 1013 A r.m.s
5.2.2 Input current distortion at rated input current 3-5% THD (in nominal linear-load condition)
0.99 at 100...30% load condition
5.2.2 and 6.3.10 Input power factor
0.95 at 10% load condition
Rectifier input: 3 Phases
5.2.2 Number of input phases
Bypass input: 3 Phases + Neutral
OUTPUT WAVEFORM
5.3.1.2 Waveform – Normal mode Sine waveform
5.3.1.2 Waveform – Stored energy mode Sine waveform
Transfer – Normal mode / Stored energy No break
Break time / make time No break
Power Xpert 9395P 600kVA Tech Spec Page 1 of 4
UPS Technical Specification
Manufacturer’s declaration in accordance with IEC 62040-3
Subclause Characteristic of Equipment Manufacturer's Declared Values
ELECTRICAL OUTPUT CHARACTERISTICS - STATIC CHARACTERISTICS - NORMAL MODE
5.3.2 Rated output voltage 220/380, 230/400, 240/415 V r.m.s
Output voltage variation ± 3V (± 1.5%)
Crest factor 3:1
Rated output frequency (nominal) 50 (default) or 60 Hz
6.3.2.2 Unsynchronized frequency variation ±3 Hz of rated, < 0.1 Hz free running
6.3.2.3 Output frequency Phase Angle Displacement ±4 degrees
Rated output apparent power 600 kVA
Rated output active power across linear load 540 kW
6.3.4.2 Total voltage distortion across a linear load 2%
Total voltage distortion across a reference
6.3.8.1 5%
non-linear load
6.3.4.2 Individual harmonics voltage See separate declaration
5.3.2 and 6.3.5.3 Short circuit capability 1500 Arms, 300 ms
Without bypass:
10 min >100…110% load
30 sec >110…125% load
10 sec >125…150% load
5.3.2 and 6.3.5.1 Overload capability (40 ℃) With bypass:
Continuous >100…115% load
50 ms 600% load
20 ms 1000% load
Note! Bypass fuses may limit the overload
capability.
Range of load power factor permitted - linear
5.3.2 and 6.3.4 Normal: 0.7 lagging – 0.8 leading
load
Number of output phases 3 Phases + Neutral
Output voltage unbalance at reference
5.3.2 and 6.3.4.5 ±2.5%
unbalance load
5.3.2 and 6.3.4.5 Maximum phase angle variation ±2°
ELECTRICAL OUTPUT CHARACTERISTICS – DYNAMIC CHARACTERISTICS - NORMAL MODE
Output voltage dynamic variation during
5.3.2 and 6.3.6.1 and
transfer normal/stored energy mode of 1%
6.3.6.2
operation and vice versa
Output voltage dynamic variation due to load ± 5% with 100 ms recovery
6.3.7.1 and 6.3.8.4
changes (Complies with IEC 62040-3, clause 5.3.1)
Maximum rate of change of output frequency 0.7 Hz/s
Power Xpert 9395P 600kVA Tech Spec Page 2 of 4
UPS Technical Specification
Manufacturer’s declaration in accordance with IEC 62040-3
ELECTRICAL OUTPUT CHARACTERISTICS - STATIC CHARACTERISTICS - STORED ENERGY
5.3.1 Rated output voltage 220/380, 230/400, 240/415 V r.m.s
6.3.4.4 Output voltage variation ±1%
Crest factor 3:1
5.3.2 Output frequency 50 Hz (default) or 60 Hz
5.3.2 Output frequency variation < 0.1 Hz
5.3.2 Rated output apparent power 600 kVA
5.3.2 Rated output active power 540 kW
Rated output active power non-linear (0.9 pf)
5.3.2 540 kW
load
2% THD (linear load condition)
6.3.4.4 Total output voltage distortion
5% THD (non-linear load condition)
Individual harmonic voltages
6.3.4.4 -
- linear load
Individual harmonic voltages
6.3.2 and 6.3.8.2 -
- non-linear load
5.3.2 and 6.3.5.4 Short circuit capability 1500 Arms. 300 ms
Depends on battery voltage, DC current above
700A /UPM max 2 seconds. Below 700A DC
5.3.2 and 6.3.5.2 Overload capability
/UPM, overload capability as stated on normal
mode.
5.3.2 Range of load power factors permitted Normal: 0.7 lagging – 0.8 leading
5.3.2 Number of output phase 3 Phases + Neutral
ELECTRICAL OUTPUT CHARACTERISTICS - DYNAMIC CHARACTERISTICS - STORED ENERGY
Output voltage dynamic variation during
6.3.6.1 transfer from stored energy mode to normal 1%
mode
Output voltage dynamic variation due to load ± 5% with 100 ms recovery
6.3.7.1
changes (Complies with IEC 62040-3, clause 5.3.1)
EFFICIENCY
95.8% at 100% Maximum Rated Active Power
96% at 75% Maximum Rated Active Power
6.6.11 Efficiency Input / Output
96% at 50% Maximum Rated Active Power
95.2% at 25% Maximum Rated Active Power
Power Xpert 9395P 600kVA Tech Spec Page 3 of 4
UPS Technical Specification
Manufacturer’s declaration in accordance with IEC 62040-3
STORED ENERGY MODE OF OPERATION
Duration of maximum permitted stored energy
No limit.
time at rated load
6.3.9.1 Stored energy time at rated load See separate declaration
Max. 10 h recommended
Restored energy time to 90% charge
240 cells (VRLA), max. battery voltage
6.3.9.2 Battery rating and quantity
240*2.35V = 564V
Battery recharge profile
ABM = 90% resting, 10% float charging
1.75 VPC with 2 min shutdown timer;
6.3.9.1 Battery cut-off voltage
1.67 VPC absolute value
CONTROL AND MONITORING SIGNALS
See separate declaration for complete list of
5.8 indications and remote alarm/monitoring or See User’s Manual
interface devices
BYPASS CHARACTERISTICS
5.5.2 Type of bypass Manual and Automatic (standard)
5.5.2 Mechanical/static No / Yes
5.5.2 No break transfer / break transfer No break transfer
5.5.2 Break time / make time no break / no break
5.5.2 Maintenance bypass No (optional, external)
Recommended Bypass protection fuse or
5.5.2 1000 A
circuit-breaker rating
5.5.2 Galvanic isolation fitted No (optional, external)
5.7 ELECTROMAGNETIC COMPATIBILITY
Immunity, see IEC/EN 62040-2 Yes (Class A: restricted sales distribution)
Emission, see IEC/EN 62040-2 Yes (Class A: restricted sales distribution)
Earth leakage currents
Earth leakage currents:
- Touch current, charger off: NA mA
- Touch current, charger on: NA mA
- Protective conductor current, charger off: NA A
- Protective conductor current, charger on NA A
Power Xpert 9395P 600kVA Tech Spec Page 4 of 4