SITE TEST REPORT FOR POWER METER
PROJECT 132 / 13.8 KV S/S ( JIZAN UNIVERSITY )
CUSTOMER NGSA CONTRACT # PTS#09SN150
LOCATION JIZAN PANEL NO : W606
TECHNICAL DATA:
Tag No. Multifunction Meter Designation
Panel No. Serial No.
Manufacturer Celsa Model No. UMG96RM
Dwg & Sh No. CT Ratio 2000/1
VT RATIO 132/√3 KV: 110/√3 V
Mechanical Check and Visual Inspection
Item No. Description Checked
1 Inspect for Physical Damages/ Defects
2 Verify Connection As Per Approved Drawing
3 Check Tightness of all connection
ELECTRICAL TESTS
1. Calibrate all meters in accordance with manufacturer's instructions. Verify
meter deflection and accuracy at 1/2, and 100% full scale values. Provide
calibration data.
2. Verify all meter multipliers.
Siemens Consultant Client (NGSA-CSD)
Name: Mohamed Abdel Gaber Name: Name: S. JAFFER ALI
Signature: Signature: Signature:
Date: Date: Date:
SIEMENS Ltd. Saudi Arabia
1
SITE TEST REPORT FOR POWER METER
PROJECT 132 / 13.8 KV S/S ( JIZAN UNIVERSITY )
CUSTOMER NGSA CONTRACT # PTS#09SN150
LOCATION JIZAN PANEL NO : W606
VOLTAMMETER READING 132 /√3 KV: 110/√3V
QUANTIT INJECTED EXPECTED MEASURED VALUE ACCURAC
RESULT
Y VOLTAGE VALUE(KV) R Y B Y%
25% 19.05 18.9 18.9 18.8
PHASE 50% 38.1 37.7 37.8 37.7
VOLTAGE 1
(KV) 100% 76.21 75.5 75.5 75.5
120% 91.45 90.6 90.7 90.6
QUANTIT INJECTED EXPECTED MEASURED VALUE ACCURAC
RESULT
Y VOLTAGE VALUE(KV) RY YB BR Y%
25% 33 32.7 32.7 32.8
LINE 50% 66 65.3 65.4 65.5
VOLTAGE 2
(KV) 100% 132 130 130 131
120% 158.4 156 156 157
Siemens Consultant Client (NGSA-CSD)
Name: Mohamed Abdel Gaber Name: Name: S. JAFFER ALI
Signature: Signature: Signature:
Date: Date: Date:
SIEMENS Ltd. Saudi Arabia
2
SITE TEST REPORT FOR POWER METER
PROJECT 132 / 13.8 KV S/S ( JIZAN UNIVERSITY )
CUSTOMER NGSA CONTRACT # PTS#09SN150
LOCATION JIZAN PANEL NO : W606
AMMETER READING CT RATIO = 2000/1 A
QUANTIT INJECTED EXPECTED MEASURED VALUE ACCURAC
RESULT
Y CURRENT VALUE R Y B Y%
25% 500 499 497 496
PHASE 50% 1000 998 995 993
CURRENT 1
(A) 100% 2000 1990 1990 1980
120% 2400 2.39 2.39 2.38
FREQUENCY:
INJECTED EXPECTED ACTUAL
QUANTITY Result ACCURACY%
VALUE VALUE VALUE
65 65 65
60 60 60
FREQUENCY(HZ) 55 55 55 1.5
50 50 50
45 45 45
TEST EQUIPMENT : FREJA 300 TAG NO : 1455
CAL DATE : 3 / 4 / 2013
DUE DATE : 3 / 4 / 2014
Siemens Consultant Client (NGSA-CSD)
Name: Mohamed Abdel Gaber Name: Name: S. JAFFER ALI
Signature: Signature: Signature:
Date: Date: Date:
SIEMENS Ltd. Saudi Arabia
3