S2-334W DIGITAL WATT METER (PROGRAMMABLE) S2 SERIES
FEATURES
4 digits display : 9999 Accuracy : 0.25%
Programmable process rate monitor
Easy-to-wire, screw-type terminals
Precision measurement even for unbalance system
Outside dimension is DIN standard (96 x48mm)
SPECIFICATION
Input Display . . . . . . . . . . . . . . . . . . . . . . . . . .14.2mm ( 0.56") H, red LED
Max. input over capability . . . . . . . . . . . . .Amp. 3 x rated continuous
AC Input
Circuit Basic Watt 10 x rated 30 seconds
Voltage Ampere
50 x rated 1 seconds
110V 0.5 KW Volt. 750V continuous
Single Phase
220V 1 KW Accuracy . . . . . . . . . . . . . . . . . . . 0.25% F.S. 3 digits, PF 0.5
3-Phase, 110V 5A 1 KW
(Option : Depending on actual measuring)
3-Wire 220V 2 KW
Measuring mode . . . . . . . . . . . . . . . . . . . . . . . . . . . .Transducer type
3 110V/110V 1.5 KW
3-Phase, Input burden . . . . . . . . . . . . . . . . . . . . . . . .Volt. input 0.5VA/Phase
4-Wire 3 220V/220V 3 KW
Amp. input 0.1VA/Phase
Display (Programmable process) Input frequency range . . . . . . . . . . . . . . . . . . . . . . .45~65HZ, 400HZ
Effect of frequency variation . . . . . . . . . . . . . . . . . . . . . . 0.03%
Per frequency change
Sampling time . . . . . . . . . . . . . . . . . . . . . . . . . . .Abt. 0.8 sec typically
Over input indication . . . . . . . . . . . . . . . . . . . . . . . . . . ." 0000 " Flash
Polarity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Only " " display
Aux. power source . . . . . . . . . . . . . .AC 110V/220V 10%, 50/60Hz
Display P I N Power consumption . . . . . . . . . . . . . . . . . . . . . . . . . . . . AC 4.5 VA
STAGE
(Full Scale)
1 2 3 4 5 6 7 8 9 Operating temperature range . . . . . . . . . . . . . . . . . . . . . . . . .0~60
1 5120 Storage temperature range . . . . . . . . . . . . . . . . . . . . . . . . .-10~70
2 2560 Temperature coefficient . . . . . . . . . . . . . . . . . . . . . . . . 150PPM/
3 1280 Max. relative humidity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .95%
4 640 Dielectric strength (IEC 688) . . . . . . . . . . . . . . . . . .AC 2KV/1 minute
5 320
Input to power terminals
6 160
AC 3KV/1 minute
7 80
8 40 All terminals to case
9 20 Impulse (IEC 255-4) . . . . . . . . . . . .Common mode 1.2 x 50 s 4 KV
DIP Switch is , Off, Three mode, don't set Off
EXAMPLE : Input : AC 11KV/110V, 100A/5A, 3 3W
Full Scale : 1KW x 100 x 20 = 2000KW
Display : 2000KW 2000-(1280)-(640)-(80) = 0
Stage of DIP switches :
D. P Jumper : None
ORDERING INFORMATION
S2-334W-
Circuit Input Voltage Input Current Input Frequency Aux. Power Source
12: single phase, 2-wire 1: AC 110V A: AC 5A
5: 50HZ 1: AC 110V/220V
33: 3-phase, 3-wire 2: AC 220V O: Option
6: 60HZ 0: Option
34: 3-phase, 4-wire 3: AC 3 110V/110V
7: 400HZ
4: AC 3 220V/220V
0: Option
0: Option
TAIK Electric Co., Ltd. www.taik.com.tw TEL:886-2-2242-6825 FAX:886-2-2242-6827
S2-334W DIGITAL WATT METER (PROGRAMMABLE) S2 SERIES
CONNECTION DIAGRAM
DIMENSION (UNIT : mm)