MC2-30M                                  Doc.
N°   MO-0495-ING
                    MICROPROCESSOR
                   MOTOR PROTECTION
                         RELAY
                         TYPE
                  “MC2-30M”
                 OPERATION MANUAL
Copyright 2018                     Date   17.03.2022   Rev.   2         Pag.   1   of   64
                                                     MC2-30M                                      Doc. N°   MO-0495-ING
1. General Utilization and Commissioning Directions _________________________________________________________ 4
   1.1 - Storage and Transportation _____________________________________________________________________ 4
   1.2 - Installation __________________________________________________________________________________ 4
   1.3 - Electrical Connection___________________________________________________________________________ 4
   1.4 - Measuring Inputs and Power Supply _______________________________________________________________ 4
   1.5 - Outputs Loading ______________________________________________________________________________ 4
   1.6 - Protection Earthing ____________________________________________________________________________ 4
   1.7 - Setting and Calibration _________________________________________________________________________ 4
   1.8 - Safety Protection _____________________________________________________________________________ 4
   1.9 - Handling ____________________________________________________________________________________ 4
   1.10 - Maintenance ________________________________________________________________________________ 4
   1.11 - Waste Disposal of Electrical & Electronic Equipment __________________________________________________ 4
   1.12 - Fault Detection and Repair _____________________________________________________________________ 4
2. General _________________________________________________________________________________________ 5
   2.1 - Power Supply ________________________________________________________________________________ 5
3. Front Panel ______________________________________________________________________________________ 5
4. Keyboard and Display ______________________________________________________________________________ 6
   4.1 - Display _____________________________________________________________________________________ 6
5. Icons of Display ___________________________________________________________________________________ 7
6. Signalization _____________________________________________________________________________________ 8
   6.1 - Leds Manual Reset ____________________________________________________________________________ 8
   6.2 – Display of the last trip _________________________________________________________________________ 8
7. Leds Configuration_________________________________________________________________________________ 9
   7.1 - Name _____________________________________________________________________________________ 10
   7.2 - Link enable _________________________________________________________________________________ 10
   7.3 - Status _____________________________________________________________________________________ 10
   7.4 - Light Prog. _________________________________________________________________________________ 10
   7.5 - Funct. Mode ________________________________________________________________________________ 10
   7.6 - Functions __________________________________________________________________________________ 10
   7.7 - Table 1 ____________________________________________________________________________________ 11
   7.8 - Example: Change settings for “Led1” _____________________________________________________________ 12
      7.8.1 - “Link Enable” ____________________________________________________________________________ 12
      7.8.2 - “Flashing” ______________________________________________________________________________ 12
      7.8.3 - “Funct.Mode” ____________________________________________________________________________ 13
      7.8.4 -“Functions” _____________________________________________________________________________ 13
8. User Variables ___________________________________________________________________________________ 14
   8.1 - Name _____________________________________________________________________________________ 14
   8.2 - User Descr. _________________________________________________________________________________ 14
   8.3 - Linked functions _____________________________________________________________________________ 14
   8.4 - OpLogic ____________________________________________________________________________________ 14
   8.5 - Timer _____________________________________________________________________________________ 14
   8.6 - Timer type _________________________________________________________________________________ 14
   8.7 – Extra _____________________________________________________________________________________ 14
   8.8 - Logical status _______________________________________________________________________________ 14
   8.9 - Example: Setting “User Variable” ________________________________________________________________ 14
      8.9.1 - “User description” (User descr.) _____________________________________________________________ 15
      8.9.2 - “Linked Functions” ________________________________________________________________________ 15
      8.9.3 - “Operation Logic” (Oplogic) _________________________________________________________________ 16
      8.9.4 - “Timer” ________________________________________________________________________________ 16
      8.9.5 - “Timer type” ____________________________________________________________________________ 17
      8.9.6 - “Extra” _________________________________________________________________________________ 17
9. Local Commands _________________________________________________________________________________ 18
10. Measure _______________________________________________________________________________________ 19
11. Maximum Values ________________________________________________________________________________ 20
12. Trip Recording __________________________________________________________________________________ 21
13. Partial Counters _________________________________________________________________________________ 23
14. Total Counters __________________________________________________________________________________ 24
15. Events ________________________________________________________________________________________ 25
   15.1 – Events on display ___________________________________________________________________________ 26
16. System (System parameters) ______________________________________________________________________ 27
17. Settings _______________________________________________________________________________________ 28
   17.1 - Modifying the setting of variables _______________________________________________________________ 29
   17.2 - Password _________________________________________________________________________________ 30
   17.3 – Menu: Communic. (Communication) ___________________________________________________________ 31
      17.3.1 – Description of variables___________________________________________________________________ 31
      17.3.2 – Front Panel USB serial communication port (RS232) ____________________________________________ 31
      17.3.3 – Cable for connection from Relay to Personal Computer __________________________________________ 31
      17.3.4 – Main serial communication port (RS485) _____________________________________________________ 31
   17.4 - Menu: Customize (Human Machine Interface) ____________________________________________________ 32
      17.4.1 – Description of variables___________________________________________________________________ 32
   17.5 - Function: FileSys (File system and Disk management) ______________________________________________ 33
      17.5.1 - Description of variables ___________________________________________________________________ 33
      17.5.2 – Download file informations ________________________________________________________________ 33
   17.6 - Function: T> (Thermal Image F49) _____________________________________________________________ 34
Copyright 2018                                                     Date   17.03.2022   Rev.   2         Pag.   2   of   64
                                                       MC2-30M                                      Doc. N°   MO-0495-ING
      17.6.1 - Description of variables ___________________________________________________________________ 34
      17.6.2 - Trip and Alarm__________________________________________________________________________ 34
  17.7 - Function: 1I> (First Overcurrent Element F50/51) _________________________________________________ 36
      17.7.1 - Description of variables ___________________________________________________________________ 36
      17.7.2 – Blocking Logic (BO-BI) ___________________________________________________________________ 37
      17.7.3 - Automatic doubling of Overcurrent thresholds on current inrush ___________________________________ 37
  17.8 – Function: 2I> (Second Overcurrent Element F50/51) _______________________________________________ 38
      17.8.1 - Description of variables ___________________________________________________________________ 38
  17.9 - Function: 3I> (Third Overcurrent Element F50/51) _________________________________________________ 38
      17.9.1 - Description of variables ___________________________________________________________________ 38
  17.10 - Function: 1Io> (First Earth Fault Element 50N/51N) _______________________________________________ 39
      17.10.1 - Description of variables __________________________________________________________________ 39
  17.11 - Function: 2Io> (Second Earth Fault Element 50N/51N) ____________________________________________ 39
      17.11.1 - Description of variables __________________________________________________________________ 39
  17.12 - Function: 3Io> (Third Earth Fault Element 50N/51N) ______________________________________________ 40
      17.12.1 - Description of variables __________________________________________________________________ 40
  17.13 - Function: 1Is> (First Negative Sequence Element F46)_____________________________________________ 41
      17.13.1 - Description of variables __________________________________________________________________ 41
      17.13.2 – Time/Current operation of the first Current Unbalance element “f(t)” ______________________________ 41
  17.14 - Function:2Is> (Second Negative Sequence Element F46) ___________________________________________ 41
      17.14.1 - Description of variables __________________________________________________________________ 41
  17.15 - Function: MotSt (Motor Start) ________________________________________________________________ 42
      17.15.1 - Description of variables __________________________________________________________________ 42
  17.16 - Function: LR (Locked Rotor – Rotor jam) ________________________________________________________ 42
      17.16.1 - Description of variables __________________________________________________________________ 42
  17.17 - Function: StNo (Limitation Start Number) _______________________________________________________ 42
      17.17.1 - Description of variables __________________________________________________________________ 42
  17.18 - Function: StSeq (starting Sequence Control) _____________________________________________________ 43
      17.18.1 - Description of variables __________________________________________________________________ 43
      17.18.2 - Operation ____________________________________________________________________________ 43
  17.19 - Function: I< (No load running) _______________________________________________________________ 43
      17.19.1 - Description of variables __________________________________________________________________ 43
      17.19.2 - Operation ____________________________________________________________________________ 43
  17.20 - Function: TCS (Trip Circuit Supervision)_________________________________________________________ 44
      18.20.1 - Description of variables __________________________________________________________________ 44
      17.20.2 - Operation ____________________________________________________________________________ 44
  17.21 - Function: IRF (Internal Relay Fault)____________________________________________________________ 45
      17.21.1 - Description of variables __________________________________________________________________ 45
      17.21.2 - Operation ____________________________________________________________________________ 45
  17.22 - Function: BrkFail (Breaker Failure) ____________________________________________________________ 45
      17.22.1 - Description of variables __________________________________________________________________ 45
      17.22.2 - Operation ____________________________________________________________________________ 45
  17.23 - Function: Oscillo (Oscillographic Recording) _____________________________________________________ 46
      17.23.1 - Description of variables __________________________________________________________________ 46
      17.23.2 - Operation ____________________________________________________________________________ 46
      17.23.3 – Available on software ___________________________________________________________________ 47
      17.23.4 – Setting “User Trigger Oscillo” _____________________________________________________________ 48
      17.24.5 – Example: Setting “Oscillo Trigger Logic” _____________________________________________________ 49
  17.24 - Function: CB Mngn (Control C/B) _____________________________________________________________ 52
      17.24.1 - Description of variables __________________________________________________________________ 52
      17.24.2 – Push-Buttons (Programmable only via software) ______________________________________________ 52
  17.25 - Function: ExtResCfg (External Reset Configuration) _______________________________________________ 54
      17.25.1 - Description of variables __________________________________________________________________ 54
18. Input – Output (via software)______________________________________________________________________ 54
  18.1 – Digital Input _______________________________________________________________________________ 54
  18.2 – “DI” Configuration (via software) _______________________________________________________________ 54
      18.2.1 – Example ______________________________________________________________________________ 55
  18.3 – Physical Outputs____________________________________________________________________________ 56
  18.4 - “DO” Configuration __________________________________________________________________________ 56
      18.4.1 - Example configuration ____________________________________________________________________ 56
      18.4.2 - Functions - Operation Mode ________________________________________________________________ 57
19. InfoStatus _____________________________________________________________________________________ 59
20. Date and Time __________________________________________________________________________________ 60
      20.1- Clock synchronization ______________________________________________________________________ 61
21. Healthy (Diagnostic Information) ___________________________________________________________________ 62
22. Dev.Info (Relay Version) __________________________________________________________________________ 62
23. Maintenance ___________________________________________________________________________________ 62
24. Wiring Diagram _________________________________________________________________________________ 63
25. Overall Dimensions ______________________________________________________________________________ 63
26. Electrical Characteristics __________________________________________________________________________ 64
Copyright 2018                                                       Date   17.03.2022   Rev.   2         Pag.   3   of   64
                                                      MC2-30M                                     Doc. N°   MO-0495-ING
 1. General Utilization and Commissioning Directions
Always make reference to the specific description of the product and to the Manufacturer's instruction.
Carefully observe the following warnings.
  1.1 - Storage and Transportation
  Must comply with the environmental conditions stated in the product's specification or by the applicable IEC
  standards.
  1.2 - Installation
  Must be properly made and in compliance with the operational ambient conditions stated by the Manufacturer.
  1.3 - Electrical Connection
  Must be made strictly according to the wiring diagram supplied with the Product, to its electrical
  characteristics and in compliance with the applicable standards particularly with reference to human safety.
  1.4 - Measuring Inputs and Power Supply
  Carefully check that the value of input quantities and power supply voltage are proper and within the
  permissible variation limits.
  1.5 - Outputs Loading
  Must be compatible with their declared performance.
  1.6 - Protection Earthing
  When earthing is required, carefully check its effectiveness.
  1.7 - Setting and Calibration
  Carefully check the proper setting of the different functions according to the configuration of the protected
  system, the safety regulations and the co-ordination with other equipment.
  1.8 - Safety Protection
  Carefully check that all safety means are correctly mounted, apply proper seals where required and
  periodically check their integrity.
  1.9 - Handling
  Notwithstanding the highest practicable protection means used in designing electronic circuits, the electronic
  components and semiconductor devices mounted on the modules can be seriously damaged by electrostatic
  voltage discharge which can be experienced when handling the modules.
  The damage caused by electrostatic discharge may not be immediately apparent, but the design reliability and
  the long life of the product will have been reduced. The electronic circuits are completely safe from
  electrostatic discharge (8 KV IEC 255.22.2) when housed in their case; withdrawing the modules without
  proper cautions expose them to the risk of damage.
  1.10 - Maintenance
  Make reference to the instruction manual of the Manufacturer; maintenance must be carried-out by specially
  trained people and in strict conformity with the safety regulations.
  1.11 - Waste Disposal of Electrical & Electronic Equipment
  (Applicable throughout the European Union and other European countries with separate collection program).
  This product should not be treated as household waste when you wish dispose of it. Instead, it should be
  handed over to an applicable collection point for the recycling of electrical and electronic equipment.
  By ensuring this product is disposed of correctly, you will help prevent potential negative consequence to the
  environment and human health, which could otherwise be caused by inappropriate disposal of this product.
  The recycling of materials will help to conserve natural resource.
  1.12 - Fault Detection and Repair
  Internal calibrations and components should not be altered or replaced.
  For repair please ask the Manufacturer or its authorized Dealers.
Misapplication of the above warnings and instruction relieves the Manufacturer of any liability.
Copyright 2018                                                     Date   17.03.2022   Rev.   2         Pag.   4   of   64
                                                      MC2-30M                                      Doc. N°   MO-0495-ING
2. General
The main features of the relays are:
User friendly front face with hi-resolution graphic display (240x128), 10 programmable signal Leds, 6 push-
buttons (configurable) and four push-button for complete local managemen, USB for local communication.
Eight user programmable Output Relays.
Eight opto-isolated, self powered Digital Inputs.
Additional RS485 communication port
Input currents are supplied to 3 current transformers: measuring phase currents.
An additional internal CT directly measures the residual (Zero Sequence) current of the three inputs.
Current inputs can be 1 or 5A: selection between 1A or 5A is made by movable jumpers provided inside the
Relay.
  2.1 - Power Supply
  The relay can be fitted with two different types of power supply:
   Type 1        24V(-20%) / 110V(+15%) a.c.                   24V(-20%) / 125V(+20%) d.c.
   Type 2        80V(-20%) / 220V(+15%) a.c.                   90V(-20%) / 250V(+20%) d.c.
  Before energizing the unit check that supply voltage is within the allowed limits.
3. Front Panel
Copyright 2018                                                      Date   17.03.2022   Rev.   2         Pag.   5   of   64
                                                     MC2-30M                                     Doc. N°   MO-0495-ING
4. Keyboard and Display
                                            ↓     Pushbuttons     Programmable
                                                   Navigation     By these buttons the options showed in
                                                     menu         correspondence on the display are selected.
                                                    Increase
                                                                  These buttons are used to scroll the items of
                                                                  the different menus (Local Control,
                                                                  Measurements, Energy metering etc).
                                                    Decrease
  4.1 - Display
    The 240x128 pixel hi-resolution LCD display the available information (menu, etc.).
Copyright 2018                                                    Date   17.03.2022   Rev.   2         Pag.   6   of   64
                                                   MC2-30M                                       Doc. N°   MO-0495-ING
5. Icons of Display
             LocalCmd     Local Commands
             Measure      Actual Measurements
             MaxVal       Maximum Values
             TripRec.     Trip Recording
             Counter      Partial Counters (Resettable Counter)
             ROCnt        Total Counter (Read Only Counter)
             Events       Event Recording
             Setting      Function Settings
             System       System Settings
             InfoStatus   Information Status
             TimeDate     Time And Date
             Healthy      Diagnostic Information
             Dev.Info     Relay Version
Copyright 2018                                                    Date   17.03.2022   Rev.   2         Pag.   7   of   64
                                                               MC2-30M                                     Doc. N°   MO-0495-ING
6. Signalization
Eleven signal leds are provided:
     1      Led Power Supply             Not programmable                                      Green
     10     Leds                         Programmable (via software)
    N°     Colours
    1      Green
    2      Green
    3      Green
    4      Yellow
    5      Red
    6      Red
    7      Red
    8      Yellow
    9      Red
    10     Green
    6.1 - Leds Manual Reset
For Leds manual reset operate as follows:
1                                    •    Press “Menu” for        3                                        • Select
                                          access to the main                                                 “LedClear”
                                          menu with icons.                                                 • Press “Select” to
                                                                                                             execute the
                                                                                                             command.
2                                    •    Select icon             4                                        • When command has
                                          “LocalCmd” .                                                       been executed the
                                                                                                             display shows
                                                                                                             “Command Done”;
                                     •    Press “Select”,
    6.2 – Display of the last trip
    Beside the signalization of the led “Trip”, indicating a generic function trip, the display shows a window
    indicating the latest function that was tripped and the number of events that are stored in the memory.
    The display will show this window until the reset button or external reset are operated.
1                                    •    Press “Menu” to access to the main menu with icons.
                                          Press “Home” to erase trip visualization.
                                          Ex. “tTCS” (flashing) is the last trip.
Copyright 2018                                                             Date   17.03.2022    Rev.   2         Pag.   8   of   64
                                                     MC2-30M                                    Doc. N°   MO-0495-ING
7. Leds Configuration (only via software)
The relay manage up to 10 signal leds (Programmable), 1 led “Power” (green).
For Leds programming (only via software) operate as follows:
     -    Open the software program and connect to the relay.
     -    Select “Change Windows” from “Menu” button (options)
     -    Select “Led Setting”
Copyright 2018                                                   Date   17.03.2022   Rev.   2         Pag.   9   of   64
                                                     MC2-30M                                     Doc. N°   MO-0495-ING
The window for leds configuration will show:
  7.1 - Name
  Led name – for leds position see picture
  7.2 - Link enable
   Linked             =     Enable to operate
   Not Linked         =     Disable
  7.3 - Status
   Light-off          =   Normal condition
   Light-on           =   When cause appear led is illuminated
                                                                        See “Light Prog”
   Flashing           =   When cause appear led is flashing
  7.4 - Light Prog.
   Light-on           =   When cause appear led is illuminated
   Flashing           =   When cause appear led is flashing
  7.5 - Funct. Mode
   Volatile           =   When cause disappear led turn-off (Not memorized)
   Latched            =   When cause disappear led remain illuminated (memorized)
  7.6 - Functions
  Select the function assigned to specific led (see table 1).
  It’s possible to configure only one function for each led.
  For configuration multiple functions use “UserVar” function.
Copyright 2018                                                   Date    17.03.2022   Rev.   2         Pag.   10   of   64
                                                                   MC2-30M                                      Doc. N°   MO-0495-ING
  7.7 - Table 1
   Tal                  Alarm          Thermal Image T>
   T>                   Trip
   1I>                  Start          First overcurrent element
   t1I>                 Trip
   2I>                  Start          Second overcurrent element
   t2I>                 Trip
   3I>                  Start          Third overcurrent element
   t3I>                 Trip
   1Io>                 Start          First earth fault element
   t1Io>                Trip
   2Io>                 Start          Second earth fault element
   t2Io>                Trip
   3Io>                 Start          Third earth fault element
   t3Io>                Trip
   1Is>                 Start
                                       First negative sequence current element
   t1Is>                Trip
   2Is>                 Start
                                       Second negative sequence current element
   t2Is>                Trip
   I<                   Start          No Load Running element
   tI<                  Trip
   ILR                  Start          Locked Rotor element
   tILR                 Trip
   IRF                  Start          Internal Relay Failure
   tIRF                 Trip
   BF                                  BF (Breaker Failure)
   tTCS                                Trip coil supervision
   MotOn                               Motor On
   LimStNum                            Limitation Startings Number
   StSeqSucc                           Start Sequence
   Itr                                 Switch-over current
   DskClean                            Disk near Full clean operation is required
   DskFull                             Disk Full Write should be lock
   DskWR                               Disk write in progress
   DskFRMT                             Disk Format in progress
   DskCHK                              Check disk in progress
   rDskAttach                          Removable disk usb attach
   rDskDetach                          Removable disk usb detach
   rDskDtchable                        Removable disk usb now detachable
                            Not used
   rDskClean                           Removable disk usb near to full clean operation is required
   rDskFull                            Removable disk usb full, write locked
   rDskWR                              Removable disk usb write in progress
   rDskFRMT                            Removable disk usb format in progress
   rDskCHK                             Removable disk usb check in progress
   manOpCmd                            Manual Open Command
   L/Rdisc                             Local/Remote signal Discrepancy
   CL-Cmd                              Close Command
   C/Bfail                             Circuit Breaker failure
   UserTriggerOscillo                  User Variable for Oscillographic Recording
   UserVar<0>
   to                                  User Variable
   UserVar<24>
   Vcc                                 “One” logic
   Gnd                                 “Zero” logic
   Reset                               Reset signal logic
   P1                                  Push-button 1
   P2                                  Push-button 2
   P3                                  Push-button 3
   P4                                  Push-button 4
   P5                                  Push-button 5
   P6                                  Push-button 6
   Gen.Start            Start
                                       Generic
   Gen.Trip             Trip
   0.D1                                Digital Inputs
   0.D1Not
   to
   0.D8
   0.D8Not
   0.R1                                Output relays
   to
   0.R8
Copyright 2018                                                                   Date   17.03.2022   Rev.   2         Pag.   11   of   64
                                                       MC2-30M                                   Doc. N°   MO-0495-ING
  7.8 - Example: Change settings for “Led1”
  Change settings for “Led1” : “Enable”, “Flashing”, “Latched”, “1I>”.
  Main Windows:
     7.8.1 - “Link Enable”
    Select “Link enable” related to “Led 1” and press right button on mouse, select
    “Value change”:
    Select “Linked” and press “OK” (if Password is
    request, see § Password):
     7.8.2 - “Flashing”
    Select “Light prog” related to Led 1 and press right button on mouse, select “Value
    change”:
    Select “Flashing” and press “OK” (if Password is
    request, see § Password):
Copyright 2018                                                    Date   17.03.2022   Rev.   2         Pag.   12   of   64
                                                    MC2-30M                                     Doc. N°   MO-0495-ING
     7.8.3 - “Funct.Mode”
    Select “Funct.Mode” related to Led 1 and press right button on mouse, select
    “Value change”:
    Select “Latched” and press “OK”
    (if Password is request, see § Password):
     7.8.4 -“Functions”
    Select “Functions” related to Led 1 and press right button on mouse,
    select “Value change”:
    Select “1I>” and press “OK”
    (if Password is request, see § Password):
Copyright 2018                                                   Date   17.03.2022   Rev.   2         Pag.   13   of   64
                                                      MC2-30M                                     Doc. N°   MO-0495-ING
8. User Variables
The “User Variable” is a result of a logical operation (Or, AND, ecc...), it can be used like other logical output.
This operation is possible only via software.
  8.1 - Name
  Internal progressive name
  8.2 - User Descr.
  Custom identification label for user variable
  8.3 - Linked functions
  Selection functions
  8.4 - OpLogic
   Operation Logic         =   [None, OR, AND, XOR, NOR, NAND, NOT, Ff-SR, Counter, Rise-UP, Fall-Down]
  8.5 - Timer
  Time delay (0-600)s, step 0.01s
  8.6 - Timer type
   Delay                   =   Add a delay on output activation. The “Timer” is edge triggered on rise edge.
   Monostable P            =   Activated the output for the time “Timer”
   Monostable N            =   Disactivated the output for the time "Timer".
   Blinking                =   The output switches periodically at the frequency defined by "Timer".
   Delay-Fall-Down         =   Delay-Fall-Down
  8.7 – Extra
  Extra Time (0 - 65000)s, step 1s
  8.8 - Logical status
   “User Variable” Logical status
  8.9 - Example: Setting “User Variable”
  Open software program and connect to the relay.
  Select “Change Windows” from “Menu” button
  Select “User Variable”
  Setting for “UserVar<0>” : “Current Trip”, “1I>,2I>,3I>”, “OR”, “1”, “Monostable P”, “10”.
Copyright 2018                                                     Date   17.03.2022   Rev.   2         Pag.   14   of   64
                                                   MC2-30M                                     Doc. N°   MO-0495-ING
     8.9.1 - “User description” (User descr.)
    Select “User descr” related to “UserVar<0>” and press right button on mouse,
    select “Value change”:
    Insert “Current Trip” into box and press
    “OK”:
     8.9.2 - “Linked Functions”
    Select “Linked Functions” related to “UserVar<0>” and press right button on
    mouse, select “Value change”:
    Select “1I>, 2I>, 3I>” from “Available” box via push-button “<Add”, and press “OK”.
    For remove functions, use push-button “>Remove”.
Copyright 2018                                                  Date   17.03.2022   Rev.   2         Pag.   15   of   64
                                                    MC2-30M                                    Doc. N°   MO-0495-ING
     8.9.3 - “Operation Logic” (Oplogic)
    Select “Oper Logic” related to “UserVar<0>” and press right button on mouse,
    select “Value change”:
    Insert “OR” into box and press “OK”:
     8.9.4 - “Timer”
    Select “Timer” related to “UserVar<0>” and press right button on mouse, select
    “Value change”:
    Select “1” into box and press “OK”:
Copyright 2018                                                  Date   17.03.2022   Rev.   2         Pag.   16   of   64
                                                    MC2-30M                                    Doc. N°   MO-0495-ING
     8.9.5 - “Timer type”
    Select “Timer” related to “UserVar<0>” and press right button on mouse, select
    “Value change”:
    Select “Monostable P” into box and
    press “OK”:
     8.9.6 - “Extra”
    Select “Extra” related to “UserVar<0>” and press right button on mouse,
    Select “10” into box and press “OK”:
Copyright 2018                                                  Date   17.03.2022   Rev.   2         Pag.   17   of   64
                                                   MC2-30M                                     Doc. N°   MO-0495-ING
9. Local Commands
“Local Commands” allow to operate from relay front face controls like Thermal Memory reset, Leds reset, etc.
          Menu                                            Description                                       Password
 Led          Clear      Reset of signal Leds                                                                  No
 Relays       Clear      Manual reset of output relays                                                         No
 main C/B     Cl.        Manual C/B closing (conditioned by Password)                                          Yes
 main C/B     Op.        Manual C/B opening (conditioned by Password)                                          Yes
 Event        Clear      Reset Events                                                                          Yes
 LTrip        Clear      Reset Last Trip                                                                       Yes
 Counter      Clear      Reset Counters                                                                        Yes
 HistFail     Clear      Reset of Internal Failure Historic records                                            Yes
 Reset        StNo       Reset of the Starts Number                                                            Yes
 Reset        Term       Reset to zero of the accumulations relevant to Thermal Image and                      Yes
                         Interruption Energy (only if T> is enable)
 Leds            Test    Signal Leds test                                                                        No
 Force           Osc     Force Oscillo Recording                                                                 Yes
 Format          iDisk   Format internal disk                                                                    Yes
 Check           iDisk   Check internal disk                                                                     Yes
To operate one command by the Front Face Keyboard, proceed as follows (Led Clear in the present example).
1                              • Press “Menu” for access to the main menu with icons.
2                              • Select “LocalCmd” icon with pushbutton “Increase” or “Decrease”.
                               • Press “Select” for access.
3                              • Select with pushbutton “Increase” or “Decrease” the menu “LedClear”.
                               • Press “Select” to execute the command.
                                 (if Password is request, see § Password).
4                              • When command has been executed the display shows
                                 “Command Done”; go to “3”.
Copyright 2018                                                  Date   17.03.2022   Rev.   2         Pag.   18   of    64
                                                           MC2-30M                                     Doc. N°   MO-0495-ING
10. Measure
Real time values as measured during the normal operation.
1                                       • Press “Menu” for access to the main menu with icons.
2                                       • Select “Measure” icon with pushbutton “Increase” or “Decrease”.
                                        • Press “Select” for access.
3                                       • Scroll the menu “Measure” with pushbutton “Increase” or
                                        “Decrease” to display
                                          the measurement.
                                        • Press “Exit” to go to the main menu.
 Imx             (0   ÷   99999)   A     Largest of the 3 phase-currents (Ia,Ib,Ic)
 Ia              (0   ÷   99999)   A     RMS value phase A current
 Ib              (0   ÷   99999)   A     RMS value phase B current
 Ic              (0   ÷   99999)   A     RMS value phase C current
 Io              (0   ÷   99999)   A     RMS value of Zero Sequence Current
 I1              (0   ÷   99999)   In    Positive sequence current
 I2              (0   ÷   99999)   In    Negative Sequence current
 Tem             (0   ÷   99999)   %T    Thermal status as % of the full load continuous operation temperature Tn
 tst             (0   ÷   99999)    s    Motor starting time
 Ist             (0   ÷   99999)   A     Max current during motor starting
Copyright 2018                                                          Date   17.03.2022   Rev.   2         Pag.   19   of   64
                                                           MC2-30M                                     Doc. N°   MO-0495-ING
11. Maximum Values
Maximum demand values recorded starting from 100ms after closing of main Circuit Breaker (updated any time
the breaker closes).
1                                       • Press “Menu” for access to the main menu with icons.
2                                       • Select “MaxVal” icon with pushbutton “Increase” or “Decrease”.
                                        • Press “Select” for access.
3                                       • Scroll the menu “Measure” with pushbutton “Increase” or
                                        “Decrease” to display
                                          the measurement.
                                        • Press “Exit” to go to the main menu.
 Imx             (0   ÷   99999)   A     Largest of the 3 phase-currents (Ia,Ib,Ic)
 Ia              (0   ÷   99999)   A     RMS value phase A current
 Ib              (0   ÷   99999)   A     RMS value phase B current
 Ic              (0   ÷   99999)   A     RMS value phase C current
 Io              (0   ÷   99999)   A     RMS value of Zero Sequence Current
 I1              (0   ÷   99999)   In    Positive sequence current
 I2              (0   ÷   99999)   In    Negative Sequence current
 Tem             (0   ÷   99999)   %T    Thermal status as % of the full load continuous operation temperature Tn
Copyright 2018                                                          Date   17.03.2022   Rev.   2         Pag.   20   of   64
                                                    MC2-30M                                      Doc. N°   MO-0495-ING
12. Trip Recording
Display of the function which caused the tripping of the relay plus values of the measurement at the moment of
tripping. The last 30 events are recorded.
The memory buffer is refreshed at each new relay tripping (FIFO logic).
 Display                   →      Reading of recorded Trips.
 Erase                     →      Clear all Trips recorded.
1                              • Press “Menu” for access to the main menu with icons.
2                              • Select “TripRec.” icon with pushbutton “Increase” or “Decrease”.
                               • Press “Select” for access.
3                              • Select “Display” with pushbutton “Increase” or “Decrease”.
                               • Press “Select” for access.
                               • For “Erase” go to “8”
4                              • If no trip is recorded the display shows “No Trips”.
5                              • If any trip was recorded, select “View” to display the chronological list of the
                                  records.
                               • By the keys “Increase” or “Decrease” select the date of the record to be
                                  checked.
6                              • Will be shown:
                                 “Descr” the function that caused the event (Example: t1I> = Rise)
                                 “Edge” if the function was tripped (Rise) or reset (Fall)
                                 “Date”, date of trip, year/month/day, hour:minutes:seconds:milliseconds
                               • Press “Value”, for reading the value of input quantities on tripping.
Copyright 2018                                                    Date   17.03.2022   Rev.   2         Pag.   21   of   64
                                                             MC2-30M                                      Doc. N°   MO-0495-ING
7                                       • Scroll with pushbuttons “Increase” or “Decrease” the available
                                        measurements.
                                        • Select “Exit” to go back to “5” for another selection, or “2” go back to the
                                        main menu.
8                                       • Select “Erase” with button “Decrease”.
                                        • Press “Select” to execute the commands; All Trips recorded are erased.
                                          (if Password is request, see § Password).
9                                       • When command has been executed the display shows “Command Done”;
                                        • Press “Exit” to go back to the main menu.
 Imx             (0   ÷   99999)   A     Largest of the 3 phase-currents (Ia,Ib,Ic)
 Ia              (0   ÷   99999)   A     RMS value phase A current
 Ib              (0   ÷   99999)   A     RMS value phase B current
 Ic              (0   ÷   99999)   A     RMS value phase C current
 Io              (0   ÷   99999)   A     RMS value of Zero Sequence Current (RMS Secondary Amps)
 I2              (0   ÷   99999)   In    Negative Sequence current
 Tem             (0   ÷   99999)   %T    Thermal status as % of the full load continuous operation temperature Tn
Copyright 2018                                                             Date   17.03.2022   Rev.   2         Pag.   22   of   64
                                                           MC2-30M                                   Doc. N°   MO-0495-ING
13. Partial Counters
Partial counters of the number of operations for each of the relay functions.
 Display         → T>      0       Operations   counters     Thermal Image
                   1I>     0       Operations   counters     First overcurrent element
                   2I>     0       Operations   counters     Second overcurrent element
                   3I>     0       Operations   counters     Third overcurrent element
                   1Io>    0       Operations   counters     First earth fault element
                   2Io>    0       Operations   counters     Second earth fault element
                   3Io>    0       Operations   counters     Third earth fault element
                   1Is>    0       Operations   counters     First negative sequence current element
                   2Is>    0       Operations   counters     Second negative sequence current element
                   motST   0       Operations   counters     Motor Start
                   mStOV   0       Operations   counters     Motor Start Overall counter
                   LR      0       Operations   counters     Locked Rotor trip
                   StNo    0       Operations   counters     Start number limitation trip
                   StSeq   0       Operations   counters     Start Sequence trip
                   I<      0       Operations   counters     No Load running trip
                   TCS     0       Operations   counters     Trip Circuit Supervision
                   IRF     0       Operations   counters     Internal Relay Fault
                   BrkF    0       Operations   counters     Breaker failure
                   AutOp   0       Operations   counters     Automatic C/B Opening
                   AutCL   0       Operations   counters     Automatic C/B Closing
                   ManOp   0       Operations   counters     Manual C/B Opening
                   ManCL   0       Operations   counters     Manual C/B Closing
                   OvrOp   0       Operations   counters     Overall C/B Opening (Automatic + Manual)
                   OvrCL   0       Operations   counters     Overall C/B Closing (Automatic + Manual)
 Erase           →             Reset all Counters
                               (By the interface program software it is possible to individually reset the counters
                               and set an initial starting number)
1                                   • Press “Menu” for access to the main menu with icons.
2                                   • Select “Counter” icon with pushbutton “Increase” or “Decrease”.
                                    • Press “Select” for access.
3                                   • Select “Display” with pushbutton “Increase” or “Decrease”.
                                    • Press “Select” for access.
                                    • For “Erase” to go to “5”
4                                   • Display of the number of operations of each individual function.
                                    • With pushbuttons “Increase” or “Decrease” scroll the parameters
                                    • Press “Exit” go back to “3”.
Copyright 2018                                                        Date   17.03.2022   Rev.   2         Pag.   23   of   64
                                                       MC2-30M                                   Doc. N°   MO-0495-ING
5                               • Select “Erase” with pushbutton “Decrease”.
                                • Press “Select” .
                                  (if Password is request, see § Password).
6                               • When command has been executed the display shows “Command Done”;
                                  and return to “5”.
                                • With pushbutton “Exit” to go back to the main menu.
14. Total Counters
Counters of the total number of operation of each individual function.
These counters cannot be reset
 Display         → T>      0   Operations   counters     Thermal Image
                   1I>     0   Operations   counters     First overcurrent element
                   2I>     0   Operations   counters     Second overcurrent element
                   3I>     0   Operations   counters     Third overcurrent element
                   1Io>    0   Operations   counters     First earth fault element
                   2Io>    0   Operations   counters     Second earth fault element
                   3Io>    0   Operations   counters     Third earth fault element
                   1Is>    0   Operations   counters     First negative sequence current element
                   2Is>    0   Operations   counters     Second negative sequence current element
                   motST   0   Operations   counters     Motor Start
                   mStOV   0   Operations   counters     Motor Start Overall counter
                   LR      0   Operations   counters     Locked Rotor trip
                   StNo    0   Operations   counters     Start number limitation trip
                   StSeq   0   Operations   counters     Start Sequence trip
                   I<      0   Operations   counters     No Load running trip
                   TCS     0   Operations   counters     Trip Circuit Supervision
                   IRF     0   Operations   counters     Internal Relay Fault
                   BrkF    0   Operations   counters     Breaker failure
                   AutOp   0   Operations   counters     Automatic C/B Opening
                   AutCL   0   Operations   counters     Automatic C/B Closing
                   ManOp   0   Operations   counters     Manual C/B Opening
                   ManCL   0   Operations   counters     Manual C/B Closing
                   OvrOp   0   Operations   counters     Overall C/B Opening (Automatic + Manual)
                   OvrCL   0   Operations   counters     Overall C/B Closing (Automatic + Manual)
1                               • Press “Menu” for access to the main menu with icons.
2                               • Select “ROCnt” icon with pushbutton “Increase” or “Decrease”.
                                • Press “Select” for access.
3                               • With pushbuttons “Increase” or “Decrease” scroll the parameters.
                                • With pushbutton “Exit” to go back to the main menu.
Copyright 2018                                                    Date   17.03.2022   Rev.   2         Pag.   24   of   64
                                                     MC2-30M                                     Doc. N°   MO-0495-ING
15. Events
Display of the function which caused any of the following events: - Status change of digital Inputs/Outputs. -
Start of protection functions – Trip of protection function – Function reset.
The last 500 events are recorded at pick-up (rise) or drop-out (fall).
The memory buffer is updated at each new event.
 Display                    →      Reading events recorded.
 Erase                      →      Clear all events recorded.
 1                              • Press “Menu” for access to the main menu with icons.
 2                              • Select “Events” icon with pushbutton “Increase” or “Decrease”.
                                • Press “Select” for access.
 3                              • Select “Display” with pushbutton “Increase” or “Decrease”.
                                • Press “Select” for access.
                                • For “Erase” go to “7”
 4                              • If no event is recorded the display shows message “No Events”.
 5                              • If any event was recorded, select “View” to display the chronological list of
                                   the records.
                                • By the keys “Increase” or “Decrease” select the date of the record to be
                                   checked.
 6                              • Will be shown:
                                  “Descr” the function that caused the event
                                  (Example: 1I> = Start, t1I> = Trip)
                                  “Edge” if the function was tripped (Rise) or reset (Fall)
                                  “Date”, date of trip, year/month/day, hour:minutes:seconds:milliseconds
 7                              • Select “Erase” with button “Decrease”.
                                • Press “Select” to execute the commands; All Events recorded are erased.
                                  (if Password is request, see § Password).
 8                              • When command has been execute the display shows “Command Done”;
                                • Press “Exit” to go back to the main menu.
Copyright 2018                                                    Date   17.03.2022   Rev.   2         Pag.   25   of   64
                                                        MC2-30M                                          Doc. N°   MO-0495-ING
  15.1 – Events on display
    Functions         Events                              Events Description                                           Status
                     Displayed
                 Tal             Tal     Alarm                                                                     Rise
        T>                                       Thermal Image
                 T>              T>      Trip                                                                      Rise         Fall
                 1I>             1I>     Start                                                                     Rise
        1I>                                      Fist overcurrent element
                 t1I>            t1I>    Trip                                                                      Rise         Fall
                 2I>             2I>     Start                                                                     Rise
        2I>                                      Second overcurrent element
                 t2I>            t2I>    Trip                                                                      Rise         Fall
                 3I>             3I>     Start                                                                     Rise
        3I>                                      Third overcurrent element
                 t3I>            t3I>    Trip                                                                      Rise         Fall
                 1Io>            1Io>    Start                                                                     Rise
       1Io>                                      Fist earth fault element
                 t1Io>           t1Io>   Trip                                                                      Rise         Fall
                 2Io>            2Io>    Start                                                                     Rise
       2Io>                                      Second earth fault element
                 t2Io>           t2Io>   Trip                                                                      Rise         Fall
                 3Io>            3Io>    Start                                                                     Rise
       3Io>                                      Third earth fault element
                 t3Io>           t3Io>   Trip                                                                      Rise         Fall
                 1Is>            1Is>    Start                                                                     Rise
       1Is>                                      First negative sequence current
                 t1Is>           t1Is>   Trip                                                                      Rise         Fall
                 2Is>            2Is>    Start                                                                     Rise
       2Is>                                      Second negative sequence current
                 t2Is>           t2Is>   Trip                                                                      Rise         Fall
                 TCS             TCS     Start                                                                     Rise
        TCS                                      Trip Coil Supervision
                 tTCS            tTCS    Trip                                                                      Rise         Fall
                 IRF             IRF     Start                                                                     Rise
        IRF                                      Internal Relay Failure
                 tIRF            tIRF    Trip                                                                      Rise
         BF      BF              BF      Trip    Breacker Failure                                                  Rise         Fall
                 ILR             ILR     Start   Start Locked rotor                                                Rise
         LR
                 tILR            tILR    Trip    Trip Locked rotor                                                 Rise
       StNo      LimStNum                Trip    Limitation of start number                                        Rise
                 StSeqSucc               Start   Start sequence successful                                         Rise
       StSeq
                 Itr                     Start   Start sequence trip/switch over failure                           Rise
                 I<                      Start   Start No load running protection                                  Rise         Fall
         I<
                 tI<                     Trip    Trip No load running protection                                   Rise         Fall
                 MotON                   Trip    Motor On                                                          Rise         Fall
                 Time Sincro             Trip    Time Sincronization                                               Rise
                 DskClean                        Disk near to full clean operation is required                     Rise
                 DskFull                         Disk full write should be lock                                    Rise
                 DskFRMT                         Disk format in progress                                           Rise         Fall
                 rDskAttach      Not     Used    removable disk usb attach                                         Rise
        Disk
                 rDskDetach      Not     Used    removable disk usb detach                                         Rise
                 rDskDtchable    Not     Used    removable disk usb now detachable                                 Rise
                 rDskClean       Not     Used    Removable USB disk near to full clean oper. is required           Rise
                 rDskFull        Not     Used    Removable disk USB full, write locked                             Rise
                 L/R disc                        Local/Remote signal Discrepancy                                   Rise
                 manOpKey                        Circuit Breaker intentional open by key                           Rise
                 manOpLocC                       Circuit Breaker intentional open by local command                 Rise
                 manOpRemC                       Circuit Breaker intentional open by remote command                Rise
                 manOpExtIn                      Circuit Breaker intentional open by external input                Rise
                 ExterManOp                      Circuit Breaker intentional external open                         Rise
        C/B      manClKey                        Circuit Breaker intentional close by key                          Rise
                 manClLocC                       Circuit Breaker intentional close by local command                Rise
                 manClRemC                       Circuit Breaker intentional close by remote command               Rise
                 manClExtIn                      Circuit Breaker intentional close by external input               Rise
                 ExterManCh                      Circuit Breaker intentional external close                        Rise
                 CB-Fail                         Circuit Breaker (C/B Failure)                                     Rise         Fall
                 Gen.Trip                        General Trip                                                      Rise
                 Gen.Start                       General Start                                                     Rise
                 0.D1                            Digital Input D1                                                  Rise         Fall
      Digital
                 to                                                                                                Rise         Fall
      Inputs
                 0.D8                            Digital Input D8                                                  Rise         Fall
                 0.R1                            Output relays R1                                                  Rise         Fall
      Output
                 to                                                                                                Rise         Fall
      Relays
                 0.R8                            Output relays R8                                                  Rise         Fall
Copyright 2018                                                            Date   17.03.2022   Rev.   2         Pag.   26   of   64
                                                        MC2-30M                                       Doc. N°   MO-0495-ING
16. System (System parameters)
 Setting of system parameters.
 CTs&PTs         Phase CT      Primary   Prim.      →          1000    A       (1 ÷ 9999)              step        1    A
                               Secondary Sec.       →           1      A       (1 / 5)
                 Neutral CT    Primary   Prim.      →          1000    A       (1 ÷ 9999)              step        1    A
                               Secondary Sec.       →           1      A       (1 / 5)
                 Sys.Ratings                Fn     →           50      Hz      (50 / 60)
                                            Nominal Frequency
                                            In     →          100      A       (1 ÷ 9999)              step        1    A
                                            Nominal Current
 Setting Group                             Group →             1             (1 / 2)
 1                                • Press “Menu” for access to the main menu with icons.
 2                                • Select “System” icon with pushbuttons “Increase” or “Decrease”.
                                  • Press “Select” for access.
 3                                • Select “CTs&PTs”.
                                  • Press “Select” for access.
 4                                • Select “Phase CT”.
                                  • Press “Select” for access.
 5                                • Select “Primary” to modify the value, or press “Decrease”
                                  • Press “Modify” to modify the parameter.
                                    (if Password is request, see § Password).
 6
                                  • Appear    icon.
                                  • Use pushbuttons “Increase” or “Decrease” to set the value.
                                  • Press “Write” to confirm the value
 7                                • The value is now set.
                                  • To set a new value return to the point “4”.
                                  • Press “Exit”.
 8                                •   The display show “Confirm the change?”.
                                  •   Choose “Yes ” to confirm the changes.
                                  •   Choose “No ” to not confirm the changes.
                                  •   After set confirmation (or non-confirmation) the display goes back to
                                      point “3”.
Copyright 2018                                                        Date    17.03.2022   Rev.   2         Pag.   27   of   64
                                                   MC2-30M                                     Doc. N°   MO-0495-ING
17. Settings
 Two complete banks of settings of the programmable variables are available in the “SETTING” menu.
 Both “Group #1” and “Group #2” include the hereunder listed variables.
 1                                   Indicates the Setting Group that is actually being modified.
                                     This symbol indicates that the function aside is enabled; symbol missing
                                     indicates that the function is disabled.
 Group#1         Group#2       Descriptions
 Communic.       Communic.     Serial communication parameters
 Customise       Customise     Visualization parameters
 FileSys         FileSys       File Systems and disks management
 T>              T>            Thermal Image
 1I>             1I>           First       Overcurrent Element
 2I>             2I>           Second      Overcurrent Element
 3I>             3I>           Third       Overcurrent Element
 1Io>            1Io>          First       Earth Fault Element
 2Io>            2Io>          Second      Earth Fault Element
 3Io>            3Io>          Third       Earth Fault Element
 1Is>            1Is>          First       Negative Sequence Current Element
 2Is>            2Is>          Second      Negative Sequence Current Element
 MotSt           MotSt         Motor Start
 LR              LR            Locked rotor protection
 StNo            StNo          StartNumber limitation tripping
 StSeq           StSeq         Starting sequence Control
 I<              I<            No Load running protection
 TCS             TCS           Setting variables for Trip Circuit Supervision
 IRF             IRF           Internal Relay Fault
 BrkFail         BrkFail       Setting variables for Breaker Failure detection
 Oscillo         Oscillo       Setting variables for Oscillographic recording
 CB-Mngn         CB-Mngn       C/B command Local / Remote setting
 ExtReset        ExtReset      Configuration for external reset input
Copyright 2018                                                  Date   17.03.2022   Rev.   2         Pag.   28   of   64
                                                           MC2-30M                                  Doc. N°   MO-0495-ING
    17.1 - Modifying the setting of variables
    To modify any variable setting by the keyboard proceed as follows:
    (example: change setting of element “1I>”, from “Is 1.000 In” to “Is 3.500 In”)
1                                 •   Press “Menu” for          7                                   •
                                      access to the main                                                Appear         icon.
                                      menu with icons.
2                                 •   Select icon “Setting”     8                                   • Set new values
                                      by pushbuttons                                                  pushbuttons
                                      “Increase” or                                                   “Increase” or
                                      “Decrease”.                                                     “Decrease” buttons
                                  •   Press “Select”.                                               • Press “Write”.
3                                 •   Select by pushbuttons     9                                   • If the change of
                                      “Group#1”                                                       parameters is
                                                                                                      completed, press
                                  •   Press “Select”.                                                 “Exit”.
4                                 •   Select by pushbuttons     1                                   • “Yes” confirm all
                                      “Increase” or             0                                     changes.
                                      “Decrease” the
                                      parameter “1I>”.
                                  •   Press “Select”.                                               • “No” voids all the
                                                                                                      changes.
5                                 •   Select by buttons         1                                   • The relay returns to
                                      “Increase” or             1                                     point “4”.
                                      “Decrease” the menu
                                      “Oper.Levels”.
                                  •   Press “Select”.
6                                 •   The arrow aside “Is”
                                      shows the parameter
                                      selected for changing
                                  •   Press “Modify”.
                                  •   If Password is request,
                                      see § Password
Copyright 2018                                                       Date   17.03.2022   Rev.   2          Pag.   29     of    64
                                                             MC2-30M                                  Doc. N°   MO-0495-ING
    17.2 - Password
    The password is requested any time the user wishes to modify any password protected parameter
    (example “1I>” menu “Setting”).
    The factory default password is “1111”.
    The password is only modifiable with the software.
    When password is requested, proceed as follows:
1                                   Use the key “Increase” and     5                              Use the key “Increase” or
                                    “Decrease” and set the                                        “Decrease” to set the
                                    first digit of password.                                      third digit.
2                                   Press “Next”                   6                              Press “Next”
                                    to validate and go to the                                     to validate and go to the
                                    next digit.                                                   next digit.
3                                   Use the key “Increase” or      7                              Use the key “Increase” or
                                    “Decrease” to set second                                      “Decrease” to set the
                                    digit.                                                        fourth digit.
4                                   Press “Next”                   8                              Press “Next”
                                    to validate and go to the                                     to validate and go to
                                    next digit.                                                   modify the next
                                                                                                  parameter.
           By key “Prev” go back to previous digit.
           The password validity expires 60 sec after the last
           setting modification or as soon as you go back to the
           main menu
1                                   If set the incorrect password 2                               The display will repeat the
                                    the display shows                                             initial interrogation
                                    “Wrong code”.
Copyright 2018                                                         Date   17.03.2022   Rev.   2         Pag.   30   of   64
                                                     MC2-30M                                      Doc. N°   MO-0495-ING
  17.3 – Menu: Communic. (Communication)
   Options                   →   BRRem        19200               [9600 / 19200 / 38400]
                             →   PRRem       MODBUS               [MODBUS / IEC103]
   Node Address             →    Addr.          1                 [1 ÷ 250]
     17.3.1 – Description of variables
     BRRem        :   USB (Front Panel) serial communication speed
     PRRem        :   Remote Protocol
     Addr.        :   Identification number for the connection on serial communication bus
     17.3.2 – Front Panel USB serial communication port (RS232)
    A Mini-USB socket is available on Relay’s front face for connection.
    Through this port - and by the interface program for Windows XP Pro (SP3)/7/10 – it is possible connect a
    Personal Computer to download all available information, operate any control and program the relay; the
    protocol used is “Modbus RTU”.
     17.3.3 – Cable for connection from Relay to Personal Computer
      The connection cable is a standard
      USB-A/mini USB-B
     17.3.4 – Main serial communication port (RS485)
      From the Relay’s back terminal board, a RS485 ports is available for communication with SCADA system
      with Protocol Modbus RTU or IEC60870-5-103 (selectable).
      The communication interface allows to program all settings, operate all commands and download all
      information and records.
      The physical connection can be via a normal pair of wires (RS485).
Copyright 2018                                                     Date   17.03.2022   Rev.   2         Pag.   31   of   64
                                                          MC2-30M                                         Doc. N°   MO-0495-ING
    17.4 - Menu: Customize (Human Machine Interface)
    Options                  →   Lang           English              [English / Loc.Lang]
                             →   Light            On                 [Auto / On]
    Timers                   →   tBckL               20      s             (5 ÷ 120)                  step          1        s
     17.4.1 – Description of variables
     Lang               :   Set Language
     Light              :   Set Display backlight
     tBckL              :   Set Display backlight time
     This menu allows to customize the Language and the Display.
     The Display backlight can be programmed always on “ON” or switched-on “Automatically” for a few second
     (set parameter “tBckL”) at any operation of the keyboard.
     Example: set Local Language.
1                                •   Press “Menu” for            5                                        • Select “Loc.Lang”.
                                     access to the main
                                     menu with icons.                                                     • Press “Write”
                                                                                                          • If Password is
                                                                                                            requested, see §
                                                                                                            Password
2                                •   Select icon “Setting”       6                                        • Press “Exit”
                                     by pushbuttons
                                     “Increase” or
                                     “Decrease”.
                                 •   Press “Select”.
3                                •   Select “Group 1” or         7                                        • “Yes” confirms all
                                     “Group 2”                                                              changes.
                                 •   Select “Customize”
                                 •   Select “Options”.                                                    • “No” void all
                                 •   Press “Select”.                                                        changes.
4                                •   Select “Lang”               8                                        • After set confirmation
                                                                                                            the display shows
                                                                                                            “Please Wait”
                                 •   Press “Modify”.
Copyright 2018                                                             Date   17.03.2022   Rev.   2         Pag.    32   of   64
                                                                MC2-30M                                        Doc. N°   MO-0495-ING
  17.5 - Function: FileSys (File system and Disk management)
     Options                     →    log                 disable             [disable / int.disk]
                                 →    OniDF              StopWrite            [StopWrite / DelOldFiles]
     17.5.1 - Description of variables
     log                  :   Internal Disk write
                              Enable         : Protection log file write enabled
                              Disable        : Protection log file write disabled
     OniDF                :   Write policy on internal full disk condition
                              StopWrite      : Write disable
                              DelOldFiles    : Delete older folder and write
     17.5.2 – Download file informations
    Files related to "Journal" - "Fault log" - "Oscillo" are available in the relay internal memory.
    Connect the USB cable to the relay and wait a few moments.
    Through the "Computer            " icon on your desktop to access disk management, select the relay hard drive
    on recording equipment "                        ".
       17.5.2.1 – Journal file
        Example:
           Directory                                                                        Descriptions
           DATALOG               2018                                                       Year
                                              Jul                                           Month
                                                           08                               Day
                                                                     Jrnl_08.07.2018.txt    Journal File
           Jrnl_08.07.2018.txt
           Date           Time             Event
           2018/07/03     18:42:07:100     Vcc                       Rise
           2018/07/03     18:42:07:100     L/Rdisc                   Rise
           2018/07/03     18:42:07:110     IPU boot                  Rise
       17.5.2.2 – Faults log file
        Example:
           Directory                                                                         Descriptions
           TRIPS                 2018                                                        Year
                                              Jul                                            Month
                                                           15                                Day
                                                                     Trips_15.06.2018.txt    Trips log File
           Trips_15.06.2018.txt
           Date          Time                 Event        Values
           2018/06/15    08:17:27:200         tTCS         Imx=0.0; Ia=0.0; Ib=0.0; Ic=0.0; Io=0.0; I2=0.00; Tem=0
           2018/06/15    10:31:03:901         tTCS         Imx=0.0; Ia=0.0; Ib=0.0; Ic=0.0; Io=0.0; I2=0.00; Tem=0
        17.5.2.3 – Oscillographic file
        Example:
           Directory                                                                                       Descriptions
           OSCILLO               2018                                                                      Year
                                              Jul                                                          Month
                                                           18                                              Day
                                                                     fault1_2016.05.08.15.56.45.cfg        Oscillographic Comtrade
                                                                     fault1_2016.05.08.15.56.45.dat        File
Copyright 2018                                                                Date   17.03.2022   Rev.     2         Pag.   33   of   64
                                                        MC2-30M                                    Doc. N°   MO-0495-ING
  17.6 - Function: T> (Thermal Image F49)
     Status                    →   Enab.           No               [No / Yes]
     Options                   →   OPMOD          I1.I2              [I1.I2 / I.Max]
     Livelli                   →   Tal             50        %Tb     [10 ÷ 100]                step          1           %Tb
                               →   Is               1        In      [0.5 ÷ 1.5]               step          0.01        In
                               →   Tres            50        %Tb     [10 ÷ 100]                step          1           %Tb
                               →   To               1        nkt     [1 ÷ 10]                  step          1           nkt
     17.6.1 - Description of variables
     Abil.       : Function enabling (No = Disable / Yes = Enable)
     OPMOD       : I1.I2 = Direct/Inverse current
                   I.Max = Phase current
     Tal         : Temperature pre-alarm level
     Is          : Continuous admissible current
     Tres        : Temperature reset
     To          : Warming-up Time Constant of the load
     17.6.2 - Trip and Alarm
    The algorithm compares the amount of heat accumulated “T” (≡ i2•t) to the steady state amount of heat “Ts”
    corresponding to continuous operation at the continuously admissible current “Is”.
    When the ratio “T/Ts” reaches the level set for Thermal Alarm “Tal” of the max allowed heating, the relay
    trips accordingly
       17.6.2.1 – Trip time of the Thermal Image Element
        The trip time of the Thermal Image Element is a function of the current “I” flowing into the load and
        depends on its warming-up Time Constant “Kt”, on the previous thermal status “Ip” and on the maximum
        admissible continuous current “Is” according to the equation:
         t       =   Time to relay tripping
         Kt      =   Load thermal time constant                                                    2            2
         I       =   Actual load current                                                       I   Ip 
                                                                                                − 
                                                                                                In     In
                                                                                 t = Kt ⋅  n   2   2
         In      =   Load rated current
         Is      =   Continuous admissible current
         Ip      =   Steady state current before the overload                                  I   Is 
                                                                                                − 
         n      =   Natural Logarithm                                                         In   In 
        When the heating exceeds the set alarm level “Tal” or the max. allowed level (“I” > “Is” for the time “t”)
        the output relays programmed for these function will be operated. Reset will take place when the thermal
        status will drop below 95% of the trip level.
Copyright 2018                                                      Date   17.03.2022   Rev.   2         Pag.       34   of   64
                                                  MC2-30M                                  Doc. N°   MO-0495-ING
       17.6.2.2 – Thermal Image Curves (TU1024 Rev.1)
Copyright 2018                                              Date   17.03.2022   Rev.   2         Pag.   35   of   64
                                                        MC2-30M                                   Doc. N°   MO-0495-ING
  17.7 - Function: 1I> (First Overcurrent Element F50/51)
     Status                  →   Enab.            No               [No / Yes]
     Options                 →   f(t)          Type - D            [D / A / B / C / I / VI / EI / MI / SI ]
                             →   tBI             Off               [Off / 2tBO]
     Oper. Levels            →   Is                1         In    (0.1 ÷ 4)                  step          0.01    In
     Timers                  →   ts              100         s     (0.02 ÷ 100)               step          0.01    s
                             →   tBO             0.75        s     (0.05 ÷ 0.75)              step          0.01    s
     17.7.1 - Description of variables
       Enab.                 :   Function enabling (No = Disable / Yes = Enable)
       f(t)                  :   Operation characteristic (Time/Current curve):
                                 (D)        = Independent definite time
                                 (A)        = IEC Inverse Curve type A
                                 (B)        = IEC Very Inverse Curve type B
                                 (C)        = IEC Extremely Inverse Curve type C
                                 (I)        = IEEE Inverse Curve
                                 (VI)       = IEEE Very Inverse Curve
                                 (EI)       = IEEE Extremely Inverse Curve
                                 (MI)       = IEEE Moderate Inverse Curve
                                 (SI)       = IEEE Short Inverse Curve
       tBI                   :   Blocking input reset time
                                 Off        = Permanent block
                                 2tBO       = Set 2xtBO.
       Is                    :   Minimum operation level
       ts                    :   Trip time delay
       tBO                   :   Time to reset of the Blocking Output after expiring of the Trip time delay. “tBO”
                                 is also the trip time delay of the Breaker Failure function.
Copyright 2018                                                     Date   17.03.2022   Rev.   2         Pag.   36   of   64
                                                        MC2-30M                                      Doc. N°   MO-0495-ING
     17.7.2 – Blocking Logic (BO-BI)
      For each Protection Function it is possible to activate a Blocking Logic allowing for inhibiting their operation
      by external signals supplied to the Digital Input.
       17.7.2.1 – Output Blocking signal “BO”
        All the protection functions that can be programmed to operate in the blocking logic mode, element, have
        an instantaneous element (beside the time delayed) which is operated as soon as the controlled quantity
        exceeds the set trip level (I > [Is] for current, etc..) and is instantaneously reset when the input quantity
        drops below the reset level (normally 0.95Is).
        The instantaneous element can control one of the user programmable output relays that, by its contacts,
        makes the signal available for blocking an external element (BO = Blocking Output).
        In case, “tBO” sec after the set trip time “ts” has expired, the Protection function is still in operation
        (current above trip level), the Blocking Output relay (instantaneous element) is anyhow reset to
        eventually remove the Blocking signal from a back-up protection.
       17.7.2.2 – Blocking Input “BI”
        For all the functions controllable by the Blocking Logic, it is possible to inhibit the time delayed tripping
        by an external signal that activates a Digital Input programmed for this functionality.
        The programmed Digital Input gets activated by an external cold contact closing across its terminals.
        With the variable “tBI” set to “OFF” (tBI=OFF), the tripping of the delayed function is blocked as long as
        the Blocking Input signal is present at the terminals of the Digital Input.
        With the variable “tBI” set to “2xtBI” (tBI=2xtBI), 2xtBI seconds after the set trip time delay of the
        function has expired the blocking input is anyhow ignored and the function enabled to trip.
     17.7.3 - Automatic doubling of Overcurrent thresholds on current inrush
      For some of the phase Overcurrent functions it is possible to have the set trip level [Is] automatically
      doubled when strong inrush current is detected.
      If at circuit Breaker switch-on (i.e. when the input current rises from zero to a minimum measurable value)
      the current increases from 0 to 1.5 times the rated value [In] in less than 60ms, the set minimum pick-up
      level [Is] is dynamically doubled ([Is]→[2Is]) and keeps this value until the input current drops below
      1.25xIn or the set time [t2xI] has elapsed.
      This functionality is very useful to avoid spurious tripping of the instantaneous, or short-time delayed
      Overcurrent elements, that could be experienced at switch-on when energizing the feeder.
Copyright 2018                                                        Date   17.03.2022   Rev.   2         Pag.   37   of   64
                                                         MC2-30M                                    Doc. N°   MO-0495-ING
  17.8 – Function: 2I> (Second Overcurrent Element F50/51)
     Status                  →   Enab.             Yes               [No / Yes]
     Options                 →   tBI               Off               [Off / 2tBO]
                             →   2xI             Disable             [Disable / Enable]
     Oper. Levels            →   Is                 1         In     (0.1 ÷ 40)                 step          0.01    In
     Timers                  →   ts               100         s     (0.02 ÷ 100)                step          0.01    s
                             →   tBO              0.75        s     (0.05 ÷ 0.75)               step          0.01    s
                             →   t2xI              2          s     (0.02 ÷ 100)                step          0.01    s
     17.8.1 - Description of variables
       Enab.           :   Function enabling (No = Disable / Yes = Enable)
       tBI             :   Blocking input reset time
                           Off       = Permanent block
                           2tBO      = Set 2xtBO.
       2xI             :   Automatic doubling of trip level on inrush
       Is              :   Minimum operation level
       ts              :   Trip time delay
       tBO             :   Time to reset of the Blocking Output after expiring of the Trip time delay. “tBO” is
                           also the trip time delay of the Breaker Failure function.
       t2xI            :   Maximum time of automatic threshold doubling on inrush
  17.9 - Function: 3I> (Third Overcurrent Element F50/51)
     Status                  →   Enab.             Yes               [No / Yes]
     Options                 →   tBI               Off               [Off / 2tBO]
                             →   2xI             Disable             [Disable / Enable]
     Oper. Levels            →   Is                 1         In     (0.1÷40)                   step          0.01    In
     Timers                  →   ts                5          s     (0.02÷100)                  step          0.01    s
                             →   tBO              0.75        s     (0.05÷0.75)                 step          0.01    s
                             →   t2xI              2          s     (0.02÷100)                  step          0.01    s
     17.9.1 - Description of variables
       Enab.           :   Function enabling (No = Disable / Yes = Enable)
       tBI             :   Blocking input reset time
                           Off       = Permanent block
                           2tBO      = Set 2xtBO.
       2xI             :   Automatic doubling of trip level on inrush
       Is              :   Minimum operation level
       ts              :   Trip time delay
       tBO             :   Time to reset of the Blocking Output after expiring of the Trip time delay. “tBO” is
                           also the trip time delay of the Breaker Failure function.
       t2xI            :   Maximum time of automatic threshold doubling on inrush
Copyright 2018                                                       Date   17.03.2022   Rev.   2         Pag.   38   of   64
                                                         MC2-30M                                   Doc. N°   MO-0495-ING
  17.10 - Function: 1Io> (First Earth Fault Element 50N/51N)
     Status                  →   Enab.             Yes              [No / Yes]
     Options                 → f(t)             Type - D            [D / A / B / C / I / VI / EI / MI / SI]
                             → tBI                Off               [Off / 2tBO]
     Oper.Levels             →   Is               0.01        On    (0.01 ÷ 4)                 step          0.01    On
     Timers                  → ts                 100         s     (0.02 ÷ 100)               step          0.01    s
                             → tBO                0.75        s     (0.05 ÷ 0.75)              step          0.01    s
    On = Rated primary current of CTs or of the current Tore CT.
     17.10.1 - Description of variables
       Enab.          :    Function enabling (No = Disable / Yes = Enable)
       f(t)           :    Operation characteristic (Time/Current curve):
                           (D)       = Independent definite time
                           (A)       = IEC Inverse Curve type A
                           (B)       = IEC Very Inverse Curve type B
                           (C)       = IEC Extremely Inverse Curve type C
                           (I)       = IEEE Inverse Curve
                           (VI)      = IEEE Very Inverse Curve
                           (EI)      = IEEE Extremely Inverse Curve
                           (MI)      = IEEE Moderate Inverse Curve
                           (SI)      = IEEE Short Inverse Curve
       tBI            :    Blocking Input reset time
                           Off       = Permanent block
                           2tBO      = Set 2xtBO.
       Is             :    Minimum operation level
       ts             :    Trip time delay
       tBO            :    Time to reset of the Blocking Output after expiring of the Trip time delay. “tBO” is
                           also the trip time delay of the Breaker Failure function.
  17.11 - Function: 2Io> (Second Earth Fault Element 50N/51N)
     Status                  →   Enab.             Yes                [No / Yes]
     Options                 →   tBI               Off                [Off / 2tBO]
     Oper.Levels             →   Is               0.01        On      (0.01 ÷ 9.99)            step          0.01    On
     Timers                  →   ts               100         s       (0.02 ÷ 100)             step          0.01    s
                             →   tBO              0.75        s       (0.05 ÷ 0.75)            step          0.01    s
    On = Rated primary current of CTs or of the current Tore CT.
     17.11.1 - Description of variables
       Enab.           :   Function enabling (No = Disable / Yes = Enable)
       tBI             :   Blocking Input reset time
                           Off       = Permanent block
                           2tBO      = Set 2xtBO.
       Is              :   Minimum operation level
       ts              :   Trip time delay
       tBO             :   Time to reset of the Blocking Output after expiring of the Trip time delay. “tBO” is
                           also the trip time delay of the Breaker Failure function.
Copyright 2018                                                      Date   17.03.2022   Rev.   2         Pag.   39   of   64
                                                         MC2-30M                                   Doc. N°   MO-0495-ING
  17.12 - Function: 3Io> (Third Earth Fault Element 50N/51N)
     Status                  →   Enab.             Yes                [No / Yes]
     Options                 →   tBI               Off                [Off / 2tBO]
     Oper.Levels             →   Is               0.01        On      (0.01÷9.99)              step          0.01    On
     Timers                  →   ts               100         s       (0.02÷100)               step          0.01    s
                             →   tBO              0.75        s       (0.05÷0.75)              step          0.01    s
    On = Rated primary current of CTs or of the current Tore CT.
     17.12.1 - Description of variables
       Enab.           :   Function enabling (No = Disable / Yes = Enable)
       tBI             :   Blocking Input reset time
                           Off       = Permanent block
                           2tBO      = Set 2xtBO.
       Is              :   Minimum operation level
       ts              :   Trip time delay
       tBO             :   Time to reset of the Blocking Output after expiring of the Trip time delay. “tBO” is
                           also the trip time delay of the Breaker Failure function.
Copyright 2018                                                      Date   17.03.2022   Rev.   2         Pag.   40   of   64
                                                           MC2-30M                                    Doc. N°   MO-0495-ING
  17.13 - Function: 1Is> (First Negative Sequence Element F46)
     Status                    →    Enab.            Yes               [No / Yes]
     Options                   →    t(t)           Type-D              [D / A / B / C / I / VI / EI / MI / SI]
                               →    tBI              Off               [Off / 2tBO]
     Oper.Levels               →    Is                4         In     (0.1 ÷ 4)                  step          0.01    In
     Timers                    →    ts              100         s      (0.02 ÷ 100)               step          0.01    s
                               →    tBO             0.75        s      (0.05 ÷ 0.75)              step          0.01    s
     17.13.1 - Description of variables
       Enab.                    :   Function enabling (No = Disable / Yes = Enable)
       f(t)                     :   Operation characteristic (Time/Current curve):
                                    (D)         = Independent definite time
                                    (A)         = IEC Inverse Curve type A
                                    (B)         = IEC Very Inverse Curve type B
                                    (C)         = IEC Extremely Inverse Curve type C
                                    (I)         = IEEE Inverse Curve
                                    (VI)        = IEEE Very Inverse Curve
                                    (EI)        = IEEE Extremely Inverse Curve
                                    (MI)        = IEEE Moderate Inverse Curve
                                    (SI)        = IEEE Short Inverse Curve
       tBI                      :   Blocking Input reset time
                                    Off         = Permanent block
                                    2tBO        = Set 2xtBO.
       Is                       :   Minimum operation level
       ts                       :   Trip time delay
       tBO                      :   Time to reset of the Blocking Output after expiring of the Trip time delay. “tBO”
                                    is also the trip time delay of the Breaker Failure function.
     17.13.2 – Time/Current operation of the first Current Unbalance element “f(t)”
    The relay measures the Negative Sequence component “I2” of the input current.
    The Time/Current curves can be selected by programming the variable “f(t)”:
       f(t) = D                              Independent definite time operation.
       f(t) = I, VI, EI, MI, SI, A, B, C     Dependent Inverse time operation
  17.14 - Function:2Is> (Second Negative Sequence Element F46)
     Status                    →    Enab.            Yes               [No / Yes]
     Options                   →    tBI              Off               [Off / 2tBO]
     Oper.Levels               →    Is                4         In     (0.1 ÷ 4)                  step          0.01    In
     Timers                    →    ts              100         s      (0.02 ÷ 100)               step          0.01    s
                               →    tBO             0.75        s      (0.05 ÷ 0.75)              step          0.01    s
     17.14.1 - Description of variables
       Enab.                    :   Function enabling (No = Disable / Yes = Enable)
       tBI                      :   Blocking Input reset time
                                    Off         = Permanent block
                                    2tBO        = Set 2xtBO.
       Is                       :   Minimum operation level
       ts                       :   Trip time delay
       tBO                      :   Time to reset of the Blocking Output after expiring of the Trip time delay. “tBO”
                                    is also the trip time delay of the Breaker Failure function.
Copyright 2018                                                         Date   17.03.2022   Rev.   2         Pag.   41   of   64
                                                         MC2-30M                                   Doc. N°   MO-0495-ING
  17.15 - Function: MotSt (Motor Start)
     Oper.Levels             →   Im                0.1        In    (0.05 ÷ 1)                 step          0.01      In
     Timers                  →   tfst             0.1         s     (0.02 ÷ 1)                 step          0.01      s
                             →   tst              120         s     (10 ÷ 120)                 step          0.01      s
     17.15.1 - Description of variables
       Im              :   Minimum operation level
       tfst            :   Motor start filter time
       tst             :   Motor starting time; 2xtst Inhibition time of the locked rotor function
  17.16 - Function: LR (Locked Rotor – Rotor jam)
     Status                  →   Enab.            Yes               [No / Yes]
     Oper.Levels             →   ILR                1         In    (1 ÷ 5)                    step          0.01      In
     Timers                  →   tLR              120         s     (1 ÷ 120)                  step          0.01      s
     17.16.1 - Description of variables
       Enab.           :   Function enabling (No = Disable / Yes = Enable)
       ILR             :   Minimum operation level
       tLR             :   Trip time delay
  17.17 - Function: StNo (Limitation Start Number)
     Status                  →   Enab.            Yes               [No / Yes]
     Oper.Levels             →   StNo              10         In    (1 ÷ 60)                   step          1
     Timers                  →   tstNo            600         s     (60 ÷ 3600)                step          60        s
                             →   tBst             600         s     (60 ÷ 3600)                step          60        s
     17.17.1 - Description of variables
       Enab.           :   Function enabling (No = Disable / Yes = Enable)
       StNo            :   Maximum number of starting allowed within te time tStNo
       tstNo           :   Time in to which the StNo is counted
       tBst            :   Restart inhibition time after tripping StNo
Copyright 2018                                                      Date   17.03.2022   Rev.   2         Pag.     42   of   64
                                                         MC2-30M                                   Doc. N°   MO-0495-ING
  17.18 - Function: StSeq (starting Sequence Control)
     Status                    →   Enab.           Yes              [No / Yes]
     Oper.Levels               →   ITr              10        In    (0.1 ÷ 1)                  step          0.1        In
     Timers                   →    tTr             20         s     (0.5 ÷ 50)                 step          0.1        s
     17.18.1 - Description of variables
       Enab.             :   Function enabling (No = Disable / Yes = Enable)
       Itr               :   Switch-over current of motor starter
       tstNo             :   Trip time delay of LR during run
     17.18.2 - Operation
    During start-up of the motor, the unit can control an output relay used to operate the switch-over of motor
    starter (star-delta, resistance or impedance, autotransformer, etc...) thus allowing to automatically manage
    the starting transition by controlling the parameters “ITr”, “tTr”.
    At motor start counting of “tTr” begins. If during “tTr” the motor current drops below “lTr”, switching-over is
    operated; if motor current stays above “lTr” longer than “tTr”, the Locked Rotor element is activated.
  17.19 - Function: I< (No load running)
     Status                    →   Enab.           No               [No / Yes]
     Oper.Levels               →   I<              0.5        In    (0.15 ÷ 1)                 step          0.01       In
     Timers                    →   tI<             30         s     (0.1 ÷ 90)                 step          0.01       s
     17.19.1 - Description of variables
     Enab.         :   Function enabling (No = Disable / Yes = Enable)
     I<            :   Operation level
     tI<           :   Trip time delay
     17.19.2 - Operation
    This function performs the protection against no-load running: it is activated by motor under current.
Copyright 2018                                                      Date   17.03.2022   Rev.   2         Pag.      43   of   64
                                                        MC2-30M                                      Doc. N°   MO-0495-ING
  17.20 - Function: TCS (Trip Circuit Supervision)
     Status                    →   Enab.           No                 [No / Yes]
     Timers                    →   ts             0.1        s        (0.1 ÷ 100)                step          0.01    s
     18.20.1 - Description of variables
       Enab.            :   Function enabling (No = Disable / Yes = Enable)
       ts               :   Trip time delay
     17.20.2 - Operation
      The relay includes a complete Circuit Breaker Trip Circuit Supervision unit that is associated to the Contact
      “9-10” of the “R1” Output Relay.
      The contact of “R1” is used to trip the C/B as reported in the drawing here below.
      The supervision works when the C/B is closed and recognizes the Trip Circuit as sound as far as the current
      flowing exceeds “1mA”.
      In case of Trip Circuit Fault detection, the diagnostic relay is operated and the Led starts flashing (see §
      Signalization).
      To have Supervision also with the C/B open one N/C contact (52b) from the C/B and an external resistor
      “R” are needed.
                    V
        R[kΩ] ≤        − R52       where   R52= Trip Coil internal resistance [kΩ]
                   1mA
                                           V = Trip Circuit Voltage
                    2
                   V
        PR ≥ 2 ⋅     [W ]   Designed power of external resistance “R”
                   R
    Tripping of the function operates a user programmable output relay.
Copyright 2018                                                        Date   17.03.2022   Rev.   2         Pag.   44   of   64
                                                         MC2-30M                                   Doc. N°   MO-0495-ING
  17.21 - Function: IRF (Internal Relay Fault)
     In this menu it is possible to configurate the operation of the Relay Internal Fault detection element
     Status                  →   Enab.             No               [No / Yes]
     Timers                  →   tIRF               5         s     (5 ÷ 200)                  step          0.01    s
     17.21.1 - Description of variables
       Enab.           :   Function enabling (No = Disable / Yes = Enable)
       tIRF            :   Trip time delay
     17.21.2 - Operation
    Tripping of the function operates a user programmable output relay.
  17.22 - Function: BrkFail (Breaker Failure)
     Status                  →   Enab.             No               [No / Yes]
     Timers                  →   tBF              0.75        s     (0.05 ÷ 0.75)              step          0.01    s
     17.22.1 - Description of variables
       Enab.           :   Function enabling (No = Disable / Yes = Enable)
       tBF             :   Trip time delay
     17.22.2 - Operation
      The Breaker Failure detection is started by the operation of the output relay “R1”, (programmed to be
      controlled by the Protection Functions that trip the C/B).
      If after [tBF] seconds from operation of the relay “R1”, any input current flow is still detected (>10% In),
      the function “BF” trips and operate one user programmable output relay,
Copyright 2018                                                      Date   17.03.2022   Rev.   2         Pag.   45   of   64
                                                                  MC2-30M                                   Doc. N°   MO-0495-ING
  17.23 - Function: Oscillo (Oscillographic Recording)
     Status                         →    Enab.             No               [No / Yes]
     Options                        →    Trig              Trip             [Start / Trip / OnCmd / REUserLg / FEUserLg]
     Timers                         →    tPre              0.5         s    (0.01 ÷ 2)                  step          0.01    s
                                    →    tPost             0.5         s    (0.01 ÷ 8)                  step          0.01    s
     17.23.1 - Description of variables
       Enab.                :   Function enabling (No = Disable / Yes = Enable)
       Trig                 :   Selection of the Trigger command source (start recording):
                                Start      = Trigger on time start of protection functions
                                Trip       = Trigger on trip (time delay end) of protection functions
                                OnCmd      = On Asynchronous Force trigger command
                                REUserLg = On rising edge of “User Logic”          (see § “User Trigger Oscillo”)
                                FEUserLg = On falling edge of “User Logic”
       tPre                 :   Recording time before Trigger
       tPost                :   Recording time after Trigger
     17.23.2 - Operation
    In the options: “Trig = Start” and “Trig = Trip”, the oscillographic recording starts respectively when any
    protection function starts operating or trip.
    The “Oscillo” Function includes the oscillographic recorder of input quantities able to store up to 10 seconds
    for each record.
    The number of events recorded depends on the duration of each individual recording (tPre + tPost).
    In any case the number of event stored can not exceed 40 (40 x 1 sec).
    Any new event exciting the memory capability, cancels and overwrites the former records.
    Example:
     tPre        =   0.5s
                                =       1s      →   40   Oscillographic recording
     tPost       =   0.5s
     tPre        =   2s
                                =   10s         →   4    Oscillographic recording
     tPost       =   8s
Copyright 2018                                                              Date    17.03.2022   Rev.   2         Pag.   46   of   64
                                                                                MC2-30M                                          Doc. N°   MO-0495-ING
     17.23.3 – Available on software
                           DskClean                     Disk near Full clean operation is required
       Internal
                           DskFull                      Disk Full Write should be lock
         Disk
                           DskWR                        Disk write in progress
                           DskFRMT                      Disk Format in progress
                           DskCHK                       Check disk in progress
                           rDskAttach                   Removable disk usb attach
         Removable Disk
                           rDskDetach                   Removable disk usb detach
                           rDskDtchable                 Removable disk usb now detachable
                           rDskClean                    Removable disk usb near to full clean operation is required
                           rDskFull                     Removable disk usb full, write locked
                           rDskWR                       Removable disk usb write in progress
                           rDskFRMT                     Removable disk usb format in progress
                           rDskCHK                      Removable disk usb check in progress
                           Tal                  Alarm
        T>                                              Thermal Image T>
                           T>                   Trip
                           1I>                  Start
       1I>                                              First overcurrent element F50-51
                           t1I>                 Trip
                           2I>                  Start
       2I>                                              Second overcurrent element F50-51
                           t2I>                 Trip
                           3I>                  Start
       3I>                                              Third overcurrent element F50-51
                           t3I>                 Trip
                           1Io>                 Start
      1Io>                                              First earth fault element F50N-51N
                           t1Io>                Trip
                           2Io>                 Start
      2Io>                                              Second earth fault element F50N-51N
                           t2Io>                Trip
                           3Io>                 Start
      3Io>                                              Third earth fault element F50N-51N
                           t3Io>                Trip
                           1Is>                 Start
       1Is>                                             First negative sequence current element F46
                           t1Is>                Trip
                           2Is>                 Start
       2Is>                                             Second negative sequence current element F46
                           t2Is>                Trip
                           Mot On                       Motor Start
                           ILR                  Start   Start Locked rotor
        LR
                           tILR                 Trip    Trip Locked rotor
                           LimStNum             Trip    Limitation of start number
                           StSeqSucc            Start   Start sequence successful
        Itr                Itr                  Trip    Switch-over current
                           I<                   Trip
        I<                                              No Load Running protection
                           tI<                  Start
        BF                 BF                   Trip    Breaker Failure
                           TCS                  Start
       TCS                                              trip coil supervision
                           tTCS                 Trip
                           IRF                  Start
       IRF                                              Internal Relay Failure
                           tIRF                 Trip
                          manOpCmd                      Manual Open Command
                          CL-Cmd                        Close Command
       C/B
                          C/Bfail                       Circuit Breaker failure
                          L/Rdisc                       Local/Remote signal Discrepancy
                          Gen.Start                     Start Generic
                          Gen.Trip                      Trip Generic
                          OscilloTriggerLogic           User Variable for Oscillographic Recording
                          UserVar<0>
                          to                            User Variable
                          UserVar<24>
                          Vcc                           Reserved
                          Gnd                           Reserved
                          ResLog                        Reset signal logic
                          P1
                          to                            Push-button
                          P6
                          0.D1                          Digital Input “0.D1”            activated
                          0.D1Not                       Digital Input “0.D1”            deactivated
                          to                                                                               Digital Inputs
                          0.D8                          Digital Input “0.D8”            activated
                          0.D8Not                       Digital Input “0.D8”            deactivated
Copyright 2018                                                                                Date    17.03.2022      Rev.   2         Pag.   47   of   64
                                                            MC2-30M                                     Doc. N°   MO-0495-ING
     17.23.4 – Setting “User Trigger Oscillo”
    The “User trigger Oscillo” is a result of a logical operation (Or, AND, ecc...), it can be used like other logical
    output. This operation is possible only via software.
       17.23.4.1 - Name
        Internal name
       17.23.4.2 - User descr.
        Fixed
       17.23.4.3 - Linked functions
        Selection functions
       17.23.4.4 - OpLogic
          Operation Logic     =       [None, OR, AND, XOR, NOR, NAND, NOT, Ff-SR, Counter, Rise-UP, Fall-Down]
       17.23.4.5 - Timer
        Time delay (0 ÷ 600)s, step 0.01s
       17.23.4.6 - Timer type
          Delay                   =   Add a delay on output activation. The “Timer” is edge triggered on rise edge.
          Monostable P            =   Activated the output for the time “Timer”
          Monostable N            =   Disactivated the output for the time "Timer".
          Blinking                =   The output switches periodically at the frequency defined by "Timer".
          Delay-Fall-Down         =   Delay-Fall-Down
       17.23.4.7 – Extra
        Extra Time (0 ÷ 65000)s, step 1s
       17.23.4.8 - Logical status
          “User Trigger Oscillo” Logical status
Copyright 2018                                                           Date   17.03.2022   Rev.   2         Pag.   48   of   64
                                                      MC2-30M                                     Doc. N°   MO-0495-ING
     17.24.5 – Example: Setting “Oscillo Trigger Logic”
      Open software program and connect to the relay.
      Select “Change Windows” from “Menu” button
      Select “User Variable”
      Setting for “User Trigger Oscillo” : “1I>/2I>/3I>”, “AND”, “1”, “Monostable”, “10”.
       17.25.5.1 – “Linked Functions”
        Select “Linked Functions” related to “User Trigger Oscillo” and press right
        button on mouse, select “Value change”:
        Select “1I>, 2I>, 3I>” from “Available” box via push-button “<Add”, and press “OK”.
        For remove functions, use push-button “>Remove”.
Copyright 2018                                                     Date   17.03.2022   Rev.   2         Pag.   49   of   64
                                                      MC2-30M                                      Doc. N°   MO-0495-ING
       17.20.5.2 – “Operation Logic” (Oplogic)
        Select “Oper Logic” related to “User Trigger Oscillo” and press right button on
        mouse, select “Value change”:
        Insert “AND” into box and press “OK”:
       17.20.5.3 – “Timer”
        Select “Timer” related to “User Trigger Oscillo” and press right button on mouse,
        select “Value change”:
        Select “1” into box and press “OK”:
Copyright 2018                                                      Date   17.03.2022   Rev.   2         Pag.   50   of   64
                                                      MC2-30M                                      Doc. N°   MO-0495-ING
       17.20.5.4 – “Timer type”
        Select “Timer” related to “User Trigger Oscillo” and press right button on mouse,
        select “Value change”:
        Select “Monostable P” into box and
        press “OK”:
       17.20.5.5 – “Extra”
        Select “Extra” related to “User Trigger Oscillo” and press right button on mouse,
        Select “10” into box and press
        “OK”:
Copyright 2018                                                      Date   17.03.2022   Rev.   2         Pag.   51   of   64
                                                            MC2-30M                                   Doc. N°   MO-0495-ING
  17.24 - Function: CB Mngn (Control C/B)
     This menu allows to configurate the command for C/B operation.
     Options                 →     L/R             Ignored             [Ignored / Active]
                             →     Key              Enable             [Disable / Enable]
                             →     Key0              None              [None / P1 / P2 / P3 / P4 / P5 / P6]
                             →     KeyC              None              [None / P1 / P2 / P3 / P4 / P5 / P6]
     Timers                  →     tL/R              0.05         s    (0.05 ÷ 1)                 step          0.05    s
                             →     tC/Bs             0.5          s    (0.05 ÷ 1)                 step          0.05    s
     17.24.1 - Description of variables
       L/R       : Selection of Local/Remote C/B operation mode Ignored or Active
       Key       : Disable    = The pushbuttons on Front Panel are disabled;
                   Enable     = The pushbuttons on Front Panel are Enable
       Key0      : Configure a Key as C/B Open
       KeyC      : Configure a Key as C/B Close
       tL/R      : Admissible time before detection of the Local/Remote discrepancy alarm.
       tC/Bs     : Maximum admissible delay for detection of status signal after C/B operation.
     17.24.2 – Push-Buttons (Programmable only via software)
    It is possible to program up to six buttons on front of the relay, assigning any action / function.
    Example: “            ” to “    ” and “              ” to “   ”.
       17.24.2.1 – “DI Configurations” (Digital Inputs)
    Select “DI configuration”:
    Assign to:
     Type                    Functions
     Main C/B CloseSts       0.D1             digital input
     Local State             0.D3             digital input
     Remote State            0.D4             digital input
Copyright 2018                                                         Date   17.03.2022   Rev.   2         Pag.   52   of   64
                                                 MC2-30M                                        Doc. N°   MO-0495-ING
       17.24.2.2 – “User Variables”
    Select “User Variable”:
    Assign to:
     Type           User descr.   Linked Functions
     UserVar<0>     UserVar<0>    manOpCmd,Gen.Trip      Manual Open Command, Generic Trip
     UserVar<1>     UserVar<1>    CL-Cmd                 Close Command
       17.24.2.3 – “DO Configuration”
    Select “DO Configuration”:
    Assign to:
     Type                     Linked Functions
     0.R1                     UserVar<0>
     0.R2                     UserVar<1>
       17.24.2.4 – “Function Setting”
    Select “Function Setting”:
    Assign to “CB Manage”:
     Type                                             Settings
     Enable Local/remote                              Active
     Enable Local Keys                                Enable
     KeyO                                             P1
     KeyC                                             P2
Copyright 2018                                                   Date   17.03.2022   Rev.   2         Pag.   53   of   64
                                                            MC2-30M                                      Doc. N°   MO-0495-ING
  17.25 - Function: ExtResCfg (External Reset Configuration)
     This menu allows to select the edge polarity of the signal on the digital input configured to reset the relay
     after a trip (see 17.2 input ExtReset).
     The reset input will reset all the output relays configured as manual reset (latched), the signalisation of the
     trip on the display and the indication of the LED are cleared also.
     Options                    →      ActOn         RiseEdge             [RiseEdge / FallEdge]
     17.25.1 - Description of variables
       ActOn             :   RiseEdge          Active on Rise Edge (Digital Input close).
                             FallEdge          Active on Fall Edge (Digital Input open).
18. Input – Output (via software)
The firmware can manage up to 8 digital inputs and 8 output relays.
The interfacing software also allows to program the operation of the output relays (Physical Output), and Digital
Inputs.
  18.1 – Digital Input
   0.D1          Programmable   (D1)
   0.D2          Programmable   (D2)
   0.D3          Programmable   (D3)
                                                                     Any digital input is active
   0.D4          Programmable   (D4)
                                                                    when the relevant terminals
   0.D5          Programmable   (D5)
                                                                 (see wiring diagram) are shorted.
   0.D6          Programmable   (D6)
   0.D7          Programmable   (D7)
   0.D8          Programmable   (D8)
  18.2 – “DI” Configuration (via software)
  Any of the Digital Inputs can be programmed to control one or more of the following functions.
   Bi1I>                                        Blocking input    First overcurrent element
   Bi2I>                                        Blocking input    Second overcurrent element
   Bi3I>                                        Blocking input    Third overcurrent element
   Bi1Io>                                       Blocking input    First earth fault element
   Bi2Io>                                       Blocking input    Second earth fault element
   Bi3Io>                                       Blocking input    Third earth fault element
   Bi1Is>                                       Blocking input    First negative sequence current element
   Bi2Is>                                       Blocking input    Second negative sequence current element
   Group 1-2                                    Selection of the setting Group 1 or 2.
   Main C/B CloseSts                            Main Circuit Breaker CLOSE position status
   ExtR                                         External Reset input
   Local state                                  Locate state
   Remote state                                 Remote state
   C/B open command                             Open C/B Command
   C/B close command                            Close C/B Command
Copyright 2018                                                            Date   17.03.2022   Rev.   2         Pag.   54   of   64
                                                      MC2-30M                                     Doc. N°   MO-0495-ING
     18.2.1 – Example
       18.2.1.1 – Name
        Logical Input name
       18.2.1.2 – Status
        Logical Input status
       18.2.1.3 – Functions
        Selection function
       18.2.1.4 – Example: Setting “Digital Input”
        Open software program and connect to the relay.
        Select “Change Windows” from “Menu”
        Select “DI configuration”
        Setting for “Bi1I>” : “1I>”.
       18.2.1.5 – “Functions”
        Select “Functions” related to “Bi1I>” and press right button on mouse, select
        “Value change”:
        From box “Available”, select “1I>” and press “Add”.
        Press “OK” for confirmation. (if Password is request, see § Password)
Copyright 2018                                                     Date   17.03.2022   Rev.   2         Pag.   55   of   64
                                                        MC2-30M                                      Doc. N°   MO-0495-ING
  18.3 – Physical Outputs
   The output relay are fully user programmable and controlled by any protection functions and by any digital
   inputs.
   0.R1      Programmable   (R1)
   0.R2      Programmable   (R2)
   0.R3      Programmable   (R3)
   0.R4      Programmable   (R4)
                                                                      Available in the relay
   0.R5      Programmable   (R5)
   0.R6      Programmable   (R6)
   0.R7      Programmable   (R7)
   0.R8      Programmable   (R8)
  18.4 - “DO” Configuration
  Any Output Relay can be programmed to be controlled (energized) by one or more of the following functions
  or Digital Inputs:
     18.4.1 - Example configuration
       18.4.1.1 - Relay
        Relay internal name
       18.4.1.2 - Linked function
        It’s available only 1 link, select the function for tripping the output relay (for multiple association use
        “User Variable”)
       18.4.1.3 - Operation Logic
        Not Used
       18.4.1.4 - Logical Status
        Relay Logical status
       18.4.1.5 - Output Configuration
          Normally Denergized       The output relay is denergized in normal conditions and gets energized on
                                    activation of the controlling Functional Output; reset means denergizing.
          Normally Energized        The output relay is energized in normal conditions and gets denergized on
                                    activation of the controlling Functional Output; reset means energizing.
       18.4.1.6 - tON (Operation Time)
        This timer controls the duration of the activation of the output relay.
          tON         :        0    (0.01-10)s, step 0.01s
       18.4.1.7 - Relay Status
        Relay – Physical status
Copyright 2018                                                        Date   17.03.2022   Rev.   2         Pag.   56   of   64
                                                    MC2-30M                                      Doc. N°   MO-0495-ING
     18.4.2 - Functions - Operation Mode
      Automatic     : In this mode the output relay is “operated” (energized if “N.D.”, denergized if “N.E.”)
                      when the controlling Functional Output is activated and it is reset to the “non operated”
                      condition when the Functional Output gets disactivated but, anyhow, not before the time
                      “tON” has elapsed (minimum duration of the operation time)
      Manual        : In this mode the output relay is “operated” when the controlling Functional Output is
                      activated and remains in the operated condition until a manual reset command is issued
                      by the relay keyboard (local commands menu) or via the serial communication. In this
                      mode the timer “tON” has no effect.
      Impulsive     : In this mode the output relay is “operated” when the controlling Functional Output is
                      activated and it remains in the “operated” condition (energized if “N.D.”, denergized if
                      “N.E.”) for the set time “tON” independently from the status of the controlling Functional
                      Output.
      Open software program and connect to the relay.
      Select “Change Windows” from “Menu”
      Select “DO Configuration”
Copyright 2018                                                    Date   17.03.2022   Rev.   2         Pag.   57   of   64
                                                       MC2-30M                                    Doc. N°   MO-0495-ING
       18.4.2.1 - Example: Change settings for “0.R1”
        Change settings for “0.R1” : “1I>”, “Normally Deenergized”, “Automatic reset”, “0.5”.
       18.4.2.2 - “Linked Functions”
        Select “Linked Functions” related to 0.R1 and press right button on mouse,
        select “Value change”:
        From box “Available”, select “1I>” and press
        “Add”.
        Press “OK” for confirmation. (if Password is
        request, see § Password)
       18.4.2.3 - “Output Config”
        Select “Output Config” related to “0.R1” and press right button on mouse, select
        “Value change”:
        Select “Normally Deenergized” from
        combo box and press “OK”
        (if Password is request, see § Password)
Copyright 2018                                                     Date   17.03.2022   Rev.   2         Pag.   58   of   64
                                                        MC2-30M                                       Doc. N°   MO-0495-ING
       18.4.2.4 - “Function”
        Select “Function” related to “0.R1” and press right button on mouse, select “Value
        change”:
        Select “Manual reset” from combo box
        and press “OK”
        (if Password is request, see § Password)
       18.4.2.5 - “tON”
        Select “tON” related to “0.R1” and press right button on mouse, select “Value
        change”:
        Set “0.5” and press “OK”
        (if Password is request, see § Password)
19. InfoStatus
In this menu is showed the status of relay
     Options                   →   LocR            Disable
       LocR               :   Local and Remote Status
                                                             Disable
                                                             Local
                                                             Remote
                                                             Discrepancy Status
Copyright 2018                                                         Date   17.03.2022   Rev.   2         Pag.   59   of   64
                                                         MC2-30M                                        Doc. N°   MO-0495-ING
20. Date and Time
 In this menu it is possible to configurate the Date and Time
 Date:                     20YY      / MM      / DD     (2000/01/01 ÷ 2099/12/31)
                                                        YY = Year / MM = Month / DD = Day
 Time:                     HH        : MM      : 00     HH = hour / MM = Minutes / 00
 DofW:                     Day                          Es: Wednesday
1                                 • Press “Menu” for access to the main menu with icons.
2                                 • Select icon “TimeDate” by pushbuttons “Increase” or “Decrease”.
                                  • Press “Select”.
3                                 • Press “Modify”.
4                                 • The last two figures of the Year will appear in bold character; by pushbuttons
                                    “Increase” or “Decrease” set the new figures.
                                  • Press “Next” to go to the next setting.
5                                 • As above for changing the “Month”
                                  • Press “Next” to go to the next setting.
6                                 • As above for changing the “Day”
                                  • Press “Next” to go to the next setting.
Copyright 2018                                                          Date    17.03.2022   Rev.   2         Pag.   60   of   64
                                                        MC2-30M                                        Doc. N°   MO-0495-ING
7                                  • As above for changing the “Hours”
                                   • Press “Next” to go to the next setting.
8                                  • As above for changing the “Minutes”
                                   • Press “Next” to go to the next setting.
9                                  • The Day of the Week is calculated and displayed automatically.
                                   • Press “Exit” to go back to the main menu.
                                   • Press “Modify” to go back to the step “3”
          Press the button “Next” to go back to the previous display.
     20.1- Clock synchronization
      The internal clock has 1ms resolution and a stability of ±35ppm in the operational temperature range.
      It can be synchronized with an external time reference in the following ways:
            Using the standard “Time Synchronization” procedure of the “IEC870-5-103” protocol.
            Using the software or from the DCS with the Modbus RTU protocol.
Copyright 2018                                                       Date      17.03.2022   Rev.   2         Pag.   61   of   64
                                                       MC2-30M                                        Doc. N°   MO-0495-ING
21. Healthy (Diagnostic Information)
The relay operates a continuous checking of the vital functionalities and in case an internal failure is detected,
the I.R.F. function (see § I.R.F.) is activated and the Power/IRF led is set to flashing.
 Device           →               No Fail                 →     No Fail
                                  Fail                    →     Fail present
                                  MinorFail               →     Minor Fail
                                  HistoricalFail          →     Cleared Fail
                                  IAU FW notC             →     Firmware MPUs not compatible
 Boards           →               Int.Ram                 →     Internal RAM fault
                                  SCI 1                   →     Serial comm. Controller 1
                                  SCI 2                   →     Serial comm. Controller 2
                                  SDRAM                   →     SDRAM fault
                                  Keys                    →     Keyboard failure
                                  TK stop/fail            →     Time Keeper to sync or stopped/failure
                                  E2pCorrupt              →     E2P Corrupt
                                  SRAM                    →     SRAM Corrupt
                                  Code Corrupt            →     Code Corrupt
                                  Data Corrupt            →     Data Corrupt
                                  SPI                     →     Serial peripheral interface
                                  IIC                     →     I2C bus failure
If an internal self-clearing (transient) fault is detected, it is recorded into an historical file without any other
action.
22. Dev.Info (Relay Version)
In this menu it is possible to read the information relevant to relay unit.
 SW Version         IPU-R            →   ####.##.##.#              Firmware version
 Protect.Model                       →   xxxxxx                    Protection Type
 Serial Number                       →   ###/##/##/####            Relay Serial Number
 User Tag                            →   xxxxxxx                   Relay identification label.
                                                                   This information can only be modified by the
                                                                   interface program software and allows the
                                                                   user to give to the relay any suitable
                                                                   denomination.
 Build                               →   ############              Build identification label.
 Line                                →   ############              Line identification label.
23. Maintenance
No maintenance is required. In case of malfunctioning please contact Service or the local Authorized Dealer
mentioning the relay's Serial No reported in the label on relays enclosure.
Copyright 2018                                                       Date     17.03.2022   Rev.   2         Pag.   62   of   64
                         MC2-30M                                  Doc. N°   MO-0495-ING
24. Wiring Diagram
25. Overall Dimensions
Copyright 2018                     Date   17.03.2022   Rev.   2         Pag.   63   of   64
                                                                               MC2-30M                                                   Doc. N°   MO-0495-ING
26. Electrical Characteristics
Approval: CE
Reference Standards                 IEC 60255 - CE Directive - EN/IEC61000 - IEEE C37
Dielectric test voltage                                            IEC 60255-5    2kV, 50/60Hz, 1 min.
Impulse test voltage                                               IEC 60255-5    5kV (c.m.), 2kV (d.m.) – 1,2/50µs
Insulation resistance                                              > 100MΩ
Environmental Std. Ref. (IEC 60068)
Operation ambient temperature                                                     -10°C / +55°C
Storage temperature                                                               -25°C / +70°C
Environmental testing           (Cold)                                            IEC60068-2-1
                                (Dry heat)                                        IEC60068-2-2
                                (Change of temperature)                           IEC60068-2-14
                                (Damp heat, steady state)                         IEC60068-2-78           RH 93% Without Condensing AT 40°C
CE EMC Compatibility (EN61000-6-2 - EN61000-6-4 - EN50263)
Electromagnetic emission                              EN55011        industrial environment
Radiated electromagnetic field immunity test          IEC61000-4-3   level 3      80-2000MHz         10V/m
                                                      ENV50204                    900MHz/200Hz       10V/m
Conducted disturbances immunity test                  IEC61000-4-6   level 3      0.15-80MHz         10V
Electrostatic discharge test                          IEC61000-4-2   level 3      6kV contact / 8kV air
Power frequency magnetic test                         IEC61000-4-8                1000A/m            50/60Hz
Pulse magnetic field                                  IEC61000-4-9                1000A/m, 8/20µs
Damped oscillatory magnetic field                     IEC61000-4-10               100A/m, 0.1-1MHz
Immunity to conducted common mode                     IEC61000-4-16 level 4
disturbance 0Hz-150KHz
Electrical fast transient/burst                       IEC61000-4-4   level 3      2kV, 5kHz
HF disturbance test with damped oscillatory wave      IEC60255-22-1 class 3       400pps, 2,5kV (m.c.), 1kV (d.m.)
(1MHz burst test)
Oscillatory waves (Ring waves)                        IEC61000-4-12 level 4       4kV(c.m.), 2kV(d.m.)
Surge immunity test                                   IEC61000-4-5   level 4      2kV(c.m.), 1kV(d.m.)
Voltage interruptions                                 IEC60255-4-11
Resistance to vibration and shocks                    IEC60255-21-1 - IEC60255-21-2 10-500Hz 1g
Caracteristics
Accuracy at reference value of influencing factors                                1% In                             for measure
                                                                                  2% + to (to=20÷30ms @ 2xIs) for times
Rated Current                                                                     In = 1 or 5A - On = 1 or 5A
Current Overload                                                                  100 In for 1 sec; 4 In continuous
Burden on current inputs                                                          Phase : 0.01VA at In = 1A; 0.2VA at In = 5A
                                                                                  Neutral : 0.01VA at In = 1A ; 0.2VA at In = 5A
Average power supply consumption                                                  < 10 VA
Output relays                                                                     rating 5 A; Vn = 380 V
                                                                                  A.C. resistive switching = 1100W (380V max)
                                                                                  make = 30 A (peak) 0,5 sec.
                                                                                  break = 0.3 A, 110 Vcc,
                                                                                  L/R = 40 ms (100.000 op.)
Communication Parameter
Rear serial port (Terminal Blocks)                                       RS485 – 9600 to 38400 bps – 8,n,1 – Modbus RTU – IEC60870-5-103
Front serial port (USB)                                                  RS232(virtual) – 9600 to 57600 bps – 8,n,1 – Modbus RTU
This publication may be subject to alteration without prior notice. Therefore, a printed copy of this document may not be the latest revision. Please contact your local
representative for the latest update. The trademarks MS Microelettrica Scientifica, Knorr and Knorr-Bremse as well as the figurative mark “K” are registered. Copyright
© Knorr-Bremse AG and Microelettrica Scientifica SpA - all rights reserved, including industrial property rights application. Knorr-Bremse AG and Microelettrica