Operating Manual
RISH Eine+
           2-60-006-00-00510_Rev_E 3/2018
       1
2
           PROGRAMMABLE DC DPM
                DC Voltmeter : Eine+ Voltage
                DC Ammeter : Eine+ Current
          Installation & Operating Instructions
Section   Contents
  1.      Introduction
  2.      Measurement Reading Screens
  3.      Programming
           3.1 Setup Screens
                   3.1.1 Meter Type Selection
                   3.1.2 Normal Meter
                         3.1.2.1 Input start value
                         3.1.2.2 Display end value
                         3.1.2.3 Display start value
                         3.1.2.4 Bent function selection
                         3.1.2.5 Input bent value
                         3.1.2.6 Display bent value
                   3.1.3 Power Factor Meter
                         3.1.3.1 Input start value
                         3.1.3.2 PF end value
                         3.1.3.3 PF start value
           3.2 Other Display Indications
  4.      Installation
           4.1 EMC Installation Requirements
           4.2 Case Dimensions and Panel Cut-out
           4.3 Wiring
           4.4 Auxiliary Supply
           4.5 Fusing
           4.6 Earth / Ground Connections
  5.      Connection Diagrams
  6.      Specifications
                             3
Available Models :
 1. Eine+ mV            2. Eine+ mA             3. Eine+ V        4. Eine+ A
               mV                      mA                     V                     A
                         1. Introduction
                         The Eine+ is a series of panel mounted 96 x 96mm and
                         48x96 Digital Panel Meters for the measurement of
                         DC Voltage and Current.
                    A
                         The instrument integrates accurate measurement technology.
                         The parameters are displayed with Ultra high bright LED
                         display with 14mm Digit height. Programmable DPM can be
                         configured and programmed on site for the following:
                         Input start and bent values, Display start, end and bent values.
  UP DOWN                The front panel has two push buttons through which the user
                         can enter into programming mode and can configure the
                         meter.
                                            4
2. Measurement Reading Screen
In normal operation the user is presented with the measurement reading screens.
These screens may be scrolled through keys one at a time in incremental order by
pressing the      key and in decrementing order by pressing      key.
 Screens of Eine+
 Screen 1 : Current                        Screen 1 : Voltage
                      mA                                        mV
 Screen 2 : Ambient Temperature (°C)       Screen 3 : Ambient Temperature (°F)
                      mV                                        mV
                                          A flashing message of “°F” will be shown
                                          at intervals of 1.5 sec.
 Note: All the screen shown in manual is for reference(Screens are applicable for
       both models i.e., 48x96 & 96x96)
                                       5
Eine+ Setup Parameter Screen
    Press both keys to enter Setup                  Exit from setup Parameter to Main Display
                                                                            A
                                        tYPE
                                     (Meter Type)
                                      (Sec 3.1.1)
                    PF                                      nor
                (PF display)                           (normal display)
                  (Sec 3.1.3)                              (Sec 3.1.2)
                    inP.S                                    inP.S
                 (Input start)                            (Input start)
                 (Sec 3.1.3.1)                            (Sec 3.1.2.1)
                    PF-E                                    dSP.E
                (PF end value)                        (Display end value)
                 (Sec 3.1.3.2)                            (Sec 3.1.2.2)
                    PF-S                                     dSP.S
                                                      (Display start value)
               (PF start value)                           (Sec 3.1.2.3)
                 (Sec 3.1.3.3)
                                                             bEnt           OFF
                       A                             (Bent function on/off)
                                                          (Sec 3.1.2.4)
                                                                   ON
                                                              inP.b
                                                       (Input bent value)
                                                          (Sec 3.1.2.5)
                                                             dSP.b
                                                      (Display bent value)          A
                                                         (Sec 3.1.2.6)
                                             6
3. Programming
The following sections comprise step by step procedures for configuring the meter
for individual user requirements. To access the set-up screens press and hold the
“ ” and “ ” keys simultaneously.
This will take the User into the Meter Type Screen. (section 3.1.1)
3.1 Setup Screens
3.1.1 Meter type
                         This screen is used to set the meter type. The user can
                         scroll between the following options using the “ up” key
                         nor: normal operation
                         PF: operate as Power Factor DPM
                         Pressing the “    down” key will accept the present type
                         and advance to Input Start value selection(section 3.1.2.1).
                         Pressing the “ up” key again will enter the meter type
                         edit mode and user can scroll through the types available.
                         Pressing the “ down” key advances to the meter type
                         confirmation menu.
Meter Type Confirmation
                         This screen will only appear following the edit of meter type.
                         Pressing the “     down” key sets the displayed type and
                         will advance to Input Start value selection (section 3.1.2.1).
                                        7
3.1.2 Normal Meter
3.1.2.1 Input Start Value (inP.S)
This screen allows the user to set the Start value of Input.
The Start value can be set from -100% to 20% of Input End value for all models,
except for 500 & 1000V models in which Start value range is from 0 to 20% of Input
End value, where Input End value is the Nominal Input value of the meter.
NOTE: Decimal point will be fixed depending upon the Nominal Input value of meter.
Eg. For 20mA model, decimal pt. will be fixed after second digit. Hence, Input start
value of 04.00 will correspond to 4mA.
                           Initially, ‘inP.S’ message is displayed on screen following
                           which user can start editing Input Start value by pressing
                           the “ ” key.
                           After entering the edit mode, by pressing the “ ”key user
                           can turn the ‘-’ symbol On or Off. If ‘-’ symbol is On then
                           Input Start value will be set as negative.
                           Pressing the “ ” key will set the ‘-’ symbol and editing of
                           first digit will start. By pressing the “ ”key user can scroll
                           the value from 0 to 9 or it will get restricted by Input End
                           value.
Pressing the “ ” key will set the first digit and advance the operation to next digit.
Similarly, user can edit the remaining three digits.
After all four digits have been set, pressing the “ ” key will advance to the Input
Start value confirmation mode.
Pressing the “ ” key will re-enter into the Start value edit mode.
Pressing the “ ” key will confirm the set value. If meter type had been earlier
selected as ‘nor’ then operation will advance to Display End value selection
(section 3.1.2.2) , otherwise if ‘PF’ had been selected then it will advance to PF end
value selection (section 3.1.3.2).
                                          8
3.1.2.2 Display End Value (dSP.E)
This screen allows the user to set the Display End value which will correspond to the
Input End value.
The End value can be set from -9999 to -10 or +10 to +9999 counts.
Initially,‘dSP.E’ message is displayed on screen following which user can start editing
Display End value by pressing the “ ” key.
Instead on pressing the “ ” key will confirm the present value and advance to
Display Start value selection (section 3.1.2.3).
                             After entering the edit mode, by pressing the “ ” key
                             user can turn the ‘-’ symbol On or Off. If ‘-’ symbol is On
                             then Display End value will be set as negative else it will
                             be positive.
                             Pressing the “ ” key once will set the ‘-’ symbol.
                             Next, on pressing “ ” key editing of Decimal point will
                             start. With each press of the same key, the Decimal point
                             will shift towards right by one digit.
                             Pressing the “ ” key will set the decimal point position
                             and advance to digit editing.
By pressing the “ ” key user can scroll the value from 0 to 9.
Pressing the “ ” key will set the first digit and advance the operation to next digit.
Similarly, user can edit the remaining three digits.
After all four digits have been set, pressing the “ ” key will advance to the Display
End value confirmation mode.
Pressing the “ ” key will re-enter into the End value edit mode.
Pressing the “ ” key will confirm the set value and advance to Display Start value
selection (section 3.1.2.3).
NOTE: The decimal point position can only be set in the Display End value screen
and the same will reflect in the measurement screen.
                                          9
3.1.2.3 Display Start Value (dSP.S)
This screen allows the user to set the Display Start value which will correspond to the
Input Start value.
If the Display End value is negative then Start value can be set from 90% of End
value to +9999 counts, otherwise if the End value is positive then Start value can be
set from -9999 to 90% of End value.
Initially, ‘dSP.S’ message is displayed on screen following which user can start editing
Display Start value by pressing the “ ” key.
Instead on pressing the “ ” key will confirm the present value and advance to
Bent Function Selection menu (section 3.1.2.4).
                           After entering the edit mode, by pressing the “ ” key
                           user can turn the ‘-’ symbol On or Off. If ‘-’ symbol is On
                           then Display Start value will be set as negative else it will
                           be positive.
                           Pressing the “ ” key will set the ‘-’ symbol and editing
                           of first digit will start.
                           By pressing the “ ” key user can scroll the value from
                           0 to 9.
Pressing the “ ” key will set the first digit and advance the operation to next digit.
Similarly, user can edit the remaining three digits.
After all four digits have been set, pressing the “ ” key will advance to the Display
Start value confirmation mode.
Pressing the “ ” key will re-enter into the Start value edit mode.
Pressing the “ ” key will confirm the set value and advance to Bent Function
Selection menu (section 3.1.2.4).
                                          10
3.1.2.4 Bent Function Selection
This screen allows the user to enable or disable the bent characteristics function.
This is applicable only to Normal meter type, and not to PF meter.
                           Initially, ‘bEnt’ message is displayed on screen.
                           On pressing the “ ” key, the meter will enter the Bent
                           function edit mode and user can scroll between yes and no.
                           YES: Bent function is enabled
                           no: Bent function is disabled
                           Pressing the “ ” key will accept the displayed condition.
                           If Bent function is enabled, then the meter will advance to
                           Input Bent value selection (section 3.1.2.5) otherwise will
                           exit the Setup menu and return to measurement mode.
3.1.2.5 Input Bent Value (inP.b)
This screen appears only when Bent Function has been enabled. This screen allows
the user to set the Input Bent value. The Bent value can be set in-between
(Input Start value + (1.5% of Input End value)) and 98.5% of Input End value.
                           Initially, ‘inP.b’ message is displayed on screen following
                           which user can start editing Input Bent value by pressing
                           the “ ” key.
                           Instead on pressing the “ ” key will confirm the present
                           value and advance to Display Bent value selection
                           (section 3.1.2.6).
                           After entering the edit mode, by pressing the “ ” key user
                           can turn the ‘-’ symbol On or Off. If ‘-’ symbol is On then
                           Input Bent value will be set as negative.
                           Pressing the “ ” key will set the ‘-’ symbol and editing of
                           first digit will start. By pressing the “ ” key user can scroll
                           the value from 0 to 9 or it will get restricted depending upon
                           Input Start and End value.
                                           11
Pressing the “ ” key will set the first digit and advance the operation to next digit.
Similarly, user can edit the remaining three digits.
After all four digits have been set, pressing the “ ” key will advance to the Input
Bent value confirmation mode.
Pressing the “ ” key will re-enter into the Bent value edit mode.
Pressing the “ ” key will confirm the set value and advance to Display Bent value
selection (section 3.1.2.6).
3.1.2.6 Display Bent Value (dSP.b)
This screen appears only when Bent Function has been enabled. This screen allows
the user to set the Display Bent value. The Bent value can be set in-between
(Display Start value + (1.5% of Display End value)) and 98.5% of Display End
value.
                            Initially, ‘dSP.b’ message is displayed on screen following
                            which user can start editing Display Bent value by pressing
                            the “ ” key.
                            Instead on pressing the “ ” key will confirm the present
                            value and exit the Setup menu to return to measurement
                            mode.
                            After entering the edit mode, by pressing the “ ” key user
                            can turn the ‘-’ symbol On or Off. If ‘-’ symbol is On then
                            Display Bent value will be set as negative.
                            Pressing the “ ” key will set the ‘-’ symbol and editing of
                            first digit will start. By pressing the “ ” key user can scroll
                            the value from 0 to 9 or it will get restricted depending upon
                            Display Start and End value.
Pressing the “ ” key will set the first digit and advance the operation to next digit.
Similarly, user can edit the remaining three digits.
After all four digits have been set, pressing the “ ” key will advance to the Display
Bent value confirmation mode.
Pressing the “ ” key will re-enter into the Bent value edit mode.
Pressing the “ ” key will confirm the set value and exit the Setup menu to return to
measurement mode.
                                           12
3.1.3 Power Factor Meter
            Capacitive                                                     Inductive
                                       Phasor
                                       Diagram
        Inductive                                                          Capacitive
                                PHASOR DIAGRAM
3.1.3.1 Input Start Value (inP.S)
Refer section 3.1.2.1.
3.1.3.2 PF End Value (PF-E)
This screen allows the user to set the PF End value which will correspond to the
Input End value.
The End value can be set from -1 to +1 (quadrants 1 & 2).
Initially, ‘PF-E’ message is displayed on screen following which user can start editing
PF End value by pressing the “ ” key.
Instead on pressing the “ ” key will confirm the present value and advance to
PF Start value selection (section 3.1.3.3).
                                         13
                           After entering the edit mode, by pressing the “ ” key
                           user can turn the ‘-’ symbol On or Off. If ‘-’ symbol is On
                           then PF End value will be set as negative else it will be
                           positive. ‘L’ (inductive) or ‘C’ (capacitive) are automatically
                           displayed depending on the quadrant in which value is
                           being set.
                           Pressing the “ ” key will set the ‘-’ symbol and digit
                           editing will start.
By pressing the “ ” key user can scroll the value between 0 and 1.
Pressing the “ ” key will set the first digit and advance the operation to next digit.
Similarly, user can edit the remaining two digits from 0 to 9 if first digit is 0.
After all three digits have been set, pressing the “ ” key will advance to the PF
End value confirmation mode.
Pressing the “ ” key will re-enter into the End value edit mode.
Pressing the “ ” key will confirm the set value and advance to PF Start value
selection (section 3.1.3.3).
NOTE: The decimal point position will remain fixed after the first digit, both in setup
and in the measurement screen.
3.1.3.3 PF Start Value (PF-S)
This screen allows the user to set the PF Start value which will correspond to the
Input Start value.
The Start value can be set from -1 to +1 (quadrants 3 & 4). Refer the Phasor diagram.
If the End value is -1 or +1, then the Start value will get restricted to -0.98 or +0.98
respectively.
Initially, ‘PF-S’ message is displayed on screen following which user can start editing
Display Start value by pressing the “ ” key.
Instead on pressing the “ ” key will confirm the present value and exit the Setup
menu to return to measurement mode.
                                          14
                          After entering the edit mode, by pressing the “ ” key
                          user can turn the ‘-’ symbol On or Off. If ‘-’ symbol is On
                          then PF Start value will be set as negative else it will be
                          positive. ‘L’ (inductive) or ‘C’ (capacitive) are automatically
                          displayed depending on the quadrant in which value is
                          being set.
                          Pressing the “ ” key will set the ‘-’ symbol and digit
                          editing will start.
By pressing the “ ” key user can scroll the value between 0 and 1.
Pressing the “ ” key will set the first digit and advance the operation to next digit.
Similarly, user can edit the remaining two digits from 0 to 9 if first digit is 0.
After all three digits have been set, pressing the “ ” key will advance to the PF
Start value confirmation mode.
Pressing the “ ” key will re-enter into the Start value edit mode.
Pressing the “ ” key will confirm the set value and exit the Setup menu to return to
measurement mode.
3.2 Other Display Indications
         Indication                             Description
            -oL-              Overload indication above 125% input
           ––––               When display count exceeds 9999
          0 reading             If negative input is given to 500/1000 V meter (for eg. due
                                to wrong connection) , it will display value same as that
                                displayed for no input value(according to input start,
                                display start and display end values set by user).
        –ve reading            For 4-20mA range, if meter setting is as follows:
                               input start value = 04.00, display end value = 20.00 &
                               display start value = 00.00, then if input falls below 4mA
                               or input gets disconnected, then meter will show
                               negative reading
                                          15
4. Installation
Mounting of EINE+ is featured with easy “Clip- in” mounting. Push the meter in panel
slot (size 92 x92 mm), it will click fit into panel with the four integral retention clips on
two sides of meter.
If required Additional support is provided with swivel screws (optional) as shown in
figure.
                                                As the front of the enclosure conforms to
                                                IP 50. additional protection to the panel
                                                may be obtained by the use of an optional
                                                panel gasket. The terminals at the rear
                                                of the product should be protected from
                                                liquids.
 Easy Clip - in
   mounting                                     The meter should be mounted in a
                                                reasonably stable ambient temperature
                                                and where the operating temperature
                                                                           0
                                                                                       is
                                Swivel screw    within the range -10 to 55 C . Vibration
                                                should be kept to a minimum and the
                                                product should not be mounted where it
                                                will be subjected to excessive direct
                                                sunlight.
                                               16
                                            For 48 x 96mm-Mounting of Rish
                                            Eine+ DC DPM 48 x 96 is featured with
                66.6mm                      easy “Clip- in” mounting. Push the meter
                                            in panel slot (size 48.5 x 96 mm), it will
                                            click fit into panel with the four integral
                                            retention clips on two sides of meter.
                                            The front of the enclosure conforms to
                                        5mm IP54. Additional protection to the panel
                    58.1mm
                                            may be obtained by the use of an
                                            optional panel gasket. The terminals at
                                            the rear of the product should be
                                            protected from liquids.
The Rish Eine+ DC DPM should be mounted in a reasonably stable ambient
temperature and where the operating temperature is within the range -10°C to 55°C
. Vibration should be kept to a minimum and the product should not be mounted
where it will be subjected to excessive direct sunlight.
   Caution
 1. In the interest of safety and functionality this product must be installed by a qualified
    engineer, abiding by any local regulations.
 2. Voltages dangerous to human life are present at some of the terminal connections of
    this unit. Ensure that all supplies are de-energised before attempting any connection
    disconnection.
 3. These products do not have internal fuses therefore external fuses must be used to
    ensure safety under fault conditions.
                                             17
4.1 EMC Installation Requirements
This product has been designed to meet the certification of the EU directives when
installed to a good code of practice for EMC in industrial environments, e.g.
1. Screened output and low signal input leads or have provision for fitting RF
   suppression components, such as ferrite absorbers, line filters etc., in the event
   that RF fields cause problems.
NOTE: It is good practice to install sensitive electronic instruments that are
        performing critical functions, in EMC enclosures that protect against electrical
        interference which could cause a disturbance in function.
2. Avoid routing leads alongside cables and products that are, or could be, a source
   of interference.
3. To protect the product against permanent damage, surge transients must be
   limited to 2kV pk. It is good EMC practice to suppress differential surges to 2kV at
   the source. The unit has been designed to automatically recover in the event of a
   high level of transients. In extreme circumstances it may be necessary to
   temporarily disconnect the auxiliary supply for a period of greater than 5 seconds
   to restore correct operation.
4. ESD precautions must be taken at all times when handling this product.
                                          18
4.2 Case Dimensions and Panel Cut Out
                                                  27 mm                    92mm+0.8
                  96 mm
                                                                                                    92mm+0.8
                                96mm
              Front Display
                Area
                                       6 mm                           Panel Cutout
                                                    35 mm         MAX PANEL THICKNESS 0.18”,5mm
                                          For 96 x 96 mm
                                                 66.6mm                                      92mm+0.8
               96.0mm
                                                                            45mm+0.8
48.0mm       Display Area
                                                                  5mm
                                                    58.1mm
                                              Mounting Position                        Installation Cutout
                                          For 48 x 96 mm
4.3 Wiring
Input connections are made directly to screw-type terminals with indirect wire
pressure. Numbering is clearly marked on the connector. Choice of cable should meet
local regulations. Terminal for inputs will accept up to 4mm2(12 AWG) or
2.5mm2 (12AWG) Standard.
Note : 1) It is recommended to use wire with lug for connection with meter.
        2) For disconnecting the device a switch or circuit-breaker shall be included
           at the site and shall be within easy reach of the operator. The specification
           are as below.
           For Aux. = At least 1.5 times of applied Power supply.
           For Measuring Input = At least 1.5 times of applied measuring inputs.
                                                  19
4.4 Auxiliary Supply
Eine+ should ideally be powered from a dedicated supply.
4.5 Fusing
It is recommended that all voltage lines are fitted with 1 amp HRC fuse.
4.6 Earth/Ground Connections
For safety reasons, panels and accesoriess should be grounded in accordance
5. Connection Diagrams
                                                                     1
                                                                 +
                                     +                                       0...500V
                                               -10...10mA                    0...1000V
    96x96 model                      -         -20...20mA        -3
                                               -1...1A
                                               -5...5A
                        1 2 3
                                               -75...75mV
                                               -150...150mV
                                               -5...5V
                                               -10...10V
                                                        -   +
      13 14
    L N                             -    +   1 2 3 4   5 6 7 8       B   A
  Aux Supply                                                                   L N
                                 0...500V
                                 0...1000V                                   Aux Supply
                                             48x96 model
                                         20
6. Specifications :
Measuring Range (Eine+ Voltage) :
Nominal Input Voltage Ranges     -75...0...75 mV, -150...0...150 mV,
                                 -5...0...5 V, -10...0...10 V
                                  0...500 V, 0...1000 V
Max continuous input voltage    120% of nominal value
Input Current                   < 300 uA
Measuring Range (Eine+ Current) :
Nominal Input Current Ranges    -10...0...10 mA, -20...0...20 mA, 4...20 mA,
                                -1...0...1 V, -5...0...5 V
Max continuous input current    120% of nominal value
Voltage Drop                    < 600 mV
Overload Indication :               “-oL-”
                                    (If input is greater than 125% of nominal
                                     value)
Auxiliary Supply :
AC-DC Auxiliary Supply              40V to 300V AC/DC (+/- 5%)
                                    20-60V DC / 20-40V AC (+/- 5%)
AC Auxiliary Supply                 80V to 300V AC [For 96x96 Model]
Frequency Range                     45 to 65 Hz
VA Burden                           < 4.5 VA at 240V, 50Hz
Overload Withstand :
Voltage                         2 X Rated Value for 1 Second, repeated
                                10 times at 10 second interval.
Current                         4 X Rated Value for 1 Second, repeated
                                5 times at 5 min interval.
                               21
Reference conditions for Accuracy :
                                         0     0
Reference temperature                 23 C + 2 C
Auxiliary Supply Voltage              Rated value ±1%
Auxiliary Supply Frequency            Rated value ±1%
Accuracy :
Voltage (mV / V)                      <0.5% of Display End value ± 1 digit
Current (mA / A)                      <0.5% of Display End value ± 1 digit
Ambient Temperature                   ±3 °C
Influence of Variations :
Temperature Coefficient               0.05% / °C, plus
Zero point drift                      0.025% / °C
Display :
Type                                  1 line 4-digits 7 segment LED display
Digit height                          14mm
Annunciator LED                       For Displaying Negative sign
Display Range                         -9999...+9999
Controls :
User Interface                        2 Keys
Applicable Standards :
EMC                                   IEC 61326-1: 2005
                                      10V/m min-Level 3 industrial low level
                                      Electromagnetic radiation environment
Safety                                IEC 61010-1: 2010, Permantly Connected
                                      use.
IP for water & dust                   IEC 60529
                                 22
Safety :
Pollution Degree              2
Installation Category         III
High Voltage Test             2.2 kV AC, 50 Hz for 1 minute
Environmental conditions :
                                       0
Operating temperature         -10 to 55 C
                                        0
Storage temperature           -25 to 70 C
Relative humidity             0 .. 90 % (Non condensing)
Warm up time                  Minimum 3 minute
Shock                         15g in 3 planes
Vibration                     10 .. 55 Hz, 0.15mm amplitude
Enclosure :
Front                         IP50(For 96x96 model)
                              IP54(For 48x96 model)
Back                          IP20
Material                      Polycarbonate Housing
Terminals                     Screw-type terminals
Dimension and weight :
For 96 x 96mm
Bezel Size (DIN 43718)        96mm X 96mm
Panel Cut-Out                 92 + 0.8mm X 92 + 0.8mm
Overall Depth                 40mm
Weight                        310g Approx.
                             23
For 48 x 96mm
Bezel Size (DIN 43718)                           48mm X 96mm
Panel Cut-Out                                    45 + 0.8mm X 92 + 0.8mm
Overall Depth                                    <75mm
Weight                                           250 grams Approx.
The Information contained in these installation instructions is for use only by installers trained
to make electrical power installations and is intended to describe the correct method of
installation for this product. However, Manufacturer has no control over the field condition
which influence product installation.
It is the user's responsibility to determine the suitability of the installation method in the
user's field conditions. Manufacturer only obligations are those in Manufacturer standard
Conditions of Sale for this product and in no case will Manufacturer be liable for any other
Incidental, indirect or consequential damages arising from the use or misuse of the products.
                                               24