Operating Manual
MULTIS Lm55, Lm56
Operating Manual
MULTIS Lm55, Lm56
Programmable Multi-function Digital Panel Meter
Installation & Operating Instructions
Section
1.
2.
3.
Contents
Introduction
Measurement Reading Screens
Programming
3.1 Password Protection
3.2 Menu selection
3.2.1 System Parameter selection screen
3.2.1.1 System type
3.2.1.2 Potential transformer Primary value
3.2.1.3 Potential transformer secondary value
3.2.1.4 Current transformer Primary value
3.2.1.5 Current transformer Secondary value
3.2.1.6 Demand integration time
3.2.1.7 Auto Scrolling
3.2.1.8 Low current noise cutoff
3.2.1.9 Energy Display on modbus
3.2.1.10 Energy Digit reset count.
3.2.2 Communication Parameter selection screen
3.2.2.1 Address Setting
3.2.2.2 RS 485 Baud rate
3.2.2.3 RS 485 Parity selection
4.
5.
6.
7.
8.
9.
3.2.3 Reset Parameter selection screen
3.2.3.1 Resetting Parameter
3.2.4 Output Option selection screen (menu)
3.2.4.1 Configuration of Output
3.2.4.1.1 Relay 1 output selection menu
3.2.4.1.1.1 Pulse output
3.2.4.1.1.1.1 Assignment of Energy to Pulse (Relay 1)
3.2.4.1.1.1.2 Pulse Duration Selection
3.2.4.1.1.1.3 Pulse Rate
3.2.4.1.1.2 Limit output
3.2.4.1.1.2.1 Assignment of Limit Output1 to Parameter
3.2.4.1.1.2.2 Limit Configuration
3.2.4.1.1.2.3 Trip point selection
3.2.4.1.1.2.4 Hysteresis selection
3.2.4.1.1.2.5 Energizing delay time
3.2.4.1.1.2.6 De-energizing delay time
3.2.4.1.2 Relay 2 output selection menu
3.2.4.1.3 Analog output
3.2.4.1.3.1 Parameter setting for Analog Output-1
3.2.4.1.3.2 Parameter setting for Analog Output-2
3.2.5 Quit screen
Phase Rotation Error screen.
Run - Hour.
On - Hour.
Number of Interruption
Analog Output
Relay Output
9.1 Pulse output
9.2 Limit Switch
10.
11.
12.
13.
14.
15.
RS 485 ( ModBus )
10.1 User Assignable Modbus Register
Phaser Diagram
Installation
12.1 EMC Installation Requirements
12.2 Case Dimensions and Panel Cut-out
12.3 Wiring
12.4 Auxiliary Supply
12.5 Fusing
12.6 Earth / Ground Connections
Connection Diagrams
Specification
Connection for Optional Pulse output / RS 485 /Analog Ouput
1. Introduction
The MULTIS Lm5x is a panel mounted 96 x 96mm DIN Quadratic Digital metering system for the
measurement important electrical parameters like AC voltage, AC Current, Frequency, Power,
Energy(Active / Reactive / Apparent) . The instrument integrates accurate measurement
technology (All Voltages & Current measurements are True RMS upto 15th Harmonic) with
3 line 4 digits Ultra high brightness LED display.
MULTIS Lm can be configured and programmed at site for the
following :
PT Primary, PT Secondary, CT Primary, CT Secondary
(5A or1A) and 3 phase 3W or 3 Phase 4W system.
The front panel has two push buttons through which the
user may scroll through the available measurement readings,
reset the energy (Import/Export) Min/Max (System Voltage
and System Current) and configure the product.
Down Key
UpKey
TABLE 1:
Units of measurement
Measured Parameters
System Voltage
System Current
Voltage VL1-N(4wire only)
Voltage VL2-N(4wire only)
Voltage VL3-N(4wire only)
Voltage VL1-L2
Voltage VL2-L3
Voltage VL3-L1
Current L1
Current L2
Current L3
Neutral Current ( 4 wire only )
Frequency
Active Power (System / Phase (4 wire only) )
Reactive Power (System / Phase (4 wire only))
Apparent Power (System / Phase (4 wire only))
Power Factor (System / Phase (4 wire only))
Phase Angle ( Phase(4 wire only))
Active Import Energy (8 Digit resolution)
Active Export Energy (8 Digit resolution)
Reactive Import Energy (8 Digit resolution)
Reactive Export Energy (8 Digit resolution)
Apparent Energy (8 Digit resolution)
Volts
Amps
Volts
Volts
Volts
Volts
Volts
Volts
Amps
Amps
Amps
Amps
Hz
Kwatts
KVAr
KVA
Degree
kWh
kWh
kVArh
kVArh
kVAh
Units of measurement
Measured Parameters
Ampere Hour (8 Digit resolution)
Current Demand
KVA Demand
KW Import Demand
KW Export Demand
Max Current Demand
Max kVA Demand
Max KW Import Demand
Max KW Export Demand
Run Hour
On Hour
Number of Interruptions
Phase Reversal Indication
V1 THD
V2 THD
V3 THD
I1 THD
I2 THD
I3 THD
System Voltage THD
System Current THD
KAh
Amps
KVA
KW
KW
Amps
KVA
KW
KW
Hours
Hours
Counts
%
%
%
%
%
%
%
%
2. Measurement Reading Screens
In normal operation the user is presented with one of the measurement reading screens
out of several screens. These screens may be scrolled through one at a time in incremental
order by pressing the  Up key and in decremental order by pressing  Down key.
Screen 1 : System screen
(System Voltage, System Current,
System Active Power)
Screen 4 : Line Currents
Screen 2 : Line to
Neutral Voltages
(for 4 wire only)
Screen 5 : Neutral current
( for 4W only ) , Frequency
Sys. Power Factor
Screen 3 : Line to
Line Voltages
Screen 6 : System Power
( Reactive, Apparent, Active)
Screen 7 : Active Energy(Import)
Screen 8 : Active Energy (Export)
Screen 9 : Reactive Energy(Import)
Screen 10 : Reactive Energy(Export)
Screen 11 : Apparent Energy
Screen 12 : Ampere Hour
Screen 13 : Min System Voltage
& Current
Screen 14 : Max System Voltage
& Current
Screen 15 : Phase Power (R)
Reactive/ Apparent /Active ( for 4W only )
Screen 16 : Phase Power (Y)
Reactive/ Apparent /Active (for 4W only)
Screen 17 : Phase Power (B)
Reactive/ Apparent /Active (for 4W only)
Screen 18: Phase Angle
(Phase R / Y / B) (for 4W only)
Screen 19 : Phase Power Factor
(Phase R / Y / B) ( for 4W only )
Screen 20 : Current Demand
Screen 21 : Max Current
Demand
Screen 22 : kVA Demand
Screen 23 : Max kVA
Demand
Screen 24 : Import kW
Demand
10
Screen 25 : Max
Import kWDemand
Screen 26 :Export
kW Demand
Screen 28 :Run Hour
Screen 29 : On Hour
Screen 30: Number
of Interruptions
Screen 31: Correct Phase
sequence
Phase sequence error
Screen 32 :Voltage %THD
(for 4 wire only)
11
Screen 27 :Max Export kW
Demand
(for 3 wire only)
Screen 33: Current %THD
12
Screen 34 : System Voltage &
System Current %THD
13
A
Addr
(Sec 3.2.1.10)
(Energy digit reset count)
Edrc
(Sec 3.2.1.9)
(Energy Output (Display) on
ModBUS)
En.OP
(Sec 3.2.1.8)
(Noise Current Cut-off)
nC
(Sec 3.2.1.7)
(Auto Scrolling)
Auto
(Sec 3.2.1.6)
(Demand Integ.Time )
dit
(Sec 3.2.1.5)
(CT Secondary)
AS
(Sec 3.2.1.4)
(CT Primary )
AP
(Sec 3.2.1.3)
(PT Secondary)
US
(Sec 3.2.1.2)
(PT Primary)
UP
(Sec 3.2.1.1)
SYS
br
(Sec 3.2.2.3)
Pr
(Parity Bits)
(Sec 3.2.2.2)
(Baud Rate)
(Sec 3.2.2.1)
(Modbus Address)
(Sec 3.2.2)
(System Type / Network)
Ser PArA
(Serial Comm.Parameter)
(Sec 3.2.1)
(System Parameter)
SYS PArA
rSEt
Down key .
Select any one option using
none (No Parameter),
ALL (All Parameter),
d (Demand),
E (Energy),
hi (Max values),
Lo (Min values),
hr (Run Hour & On Hour),
Intr (No. of Interrupts)
(Sec 3.2.3)
(Pulse Divisor Rate)
1, 10, 100, 1000
(Sec 3.2.4.1.1.1.3)
rAt
(Sec 3.2.4.1.1.1.2)
60,100,200
dur
(Pulse Duration)
(i-E, E-E, i-rE, E-rE,
A-E, A-H)
(Sec 3.2.4.1.1.1.1)
dE-d
(Sec 3.2.4.1.1.2.6)
(De-energizing Delay time) 1s
to 10s
1s to 10s
(Sec 3.2.4.1.1.2.5)
En-d
(Energizing Delay time)
0.5% to 50%
(Sec 3.2.4.1.1.2.4)
HYS (Hysterisy s)
trip (Trip Point)
10% to 100%
(Sec 3.2.4.1.1.2.3)
(Hi-E, Hi-d,
Lo-E, Lo-d)
(Sec 3.2.4.1.1.2.2)
Limit Config.
Selection
(Sec 3.2.4.1.1.2.1)
Para. Selection
(Acc. To Table)
(Sec 3.2.4.1.1.2)
Para. Selection
Lt
(Limit Output)
(Sec 3.2.4.1.1.1)
(Relay 1 & 2)
(Sec 3.2.4.1.1)
rL1 & rL2
(Sec 3.2.4)
Out PArA
(Output Parameter)
(Analog 2 parameter
selection)
(Acc. To Table )
(Sec 3.2.4.2.3.2)
AnL2
(Sec 3.2.4.1.3.1)
(Analog1 parameter
selection)
(Acc. To Table)
(Sec 3.2.4.1.3)
AnL1
quit
quit
: UP KEY
: DOWN KEY
(Exit Menu)
(Sec 3.2.4)
(Exit Menu)
(Sec 3.2.5)
(Analog Output)
AnL Out
Exit from setup Parameter to Main Display
PUL
(Pulse Output)
codE (PassWord)
(Reset Parameter)
SEL (Select)
MULTIS Lm Setup Parameter Screen
3. Programming
The following sections comprise step by step procedures for configuring the MULTIS for
individual user requirements.
To access the set-up screens press and hold the  Down and  Up Key simultaneously
for 5 seconds. This will take the User into the Password Protection Entry Stage (Section 3.1).
3.1. Password Protection
Password protection can be enabled to prevent unauthorised access to set-up screens,
by default password protection is not enabled.
Password protection is enabled by selecting a four digit number other than 0000, setting a
password of 0000 disables the password protection.
14
Enter Password, second digit entered, prompt for third
digit.
(* Denotes that decimal point will be flashing).
Use the  Down key to scroll the value of the third
digit from 0 through to 9, the value will wrap from 9
round to 0.
Press the  Up key to advance to next digit.
Enter Password, third digit entered, prompt for fourth digit.
(* Denotes that decimal point will be flashing).
Use the  Down key to scroll the value of the fourth
digit from 0 through to 9, the value will wrap from 9
round to 0.
Press the  Up key to advance to verification of the
password.
Enter Password, fourth digit entered, awaiting
verification of the password.
15
Password confirmed.
Pressing  Down key will advance to the New /
change Password entry stage.
Pressing the  Up key will advance to the Menu selection
screen. (See section 3.2).
Password Incorrect.
The unit has not accepted the Password entered.
Pressing the "
Down" key will return to the Enter
Password stage.
Pressing the  Up key exits the Password menu and
returns operation to the measurement reading mode.
New / Change Password
(*Decimal point indicates that this will be flashing).
Pressing the  Down key will scroll the value of the
first digit from 0 through to 9, the value will wrap from 9
round to 0.
Pressing the  Up key to advance the operation to
the next digit and sets the first digit, in this case to 2
16
New / Change Password, first digit entered, prompting for
second digit. (*Decimal point indicates that this will be
flashing).
Pressing the  Down key will scroll the value of the
second digit from 0 through to 9, the value will wrap from
9 round to 0.
Pressing the  Up key to advance the operation to the
next digit and sets the second digit, in this case to 1
New / Change Password, second digit entered,
prompting for third digit. (*decimal point indicates that
this will be flashing).
Pressing the  Down key will scroll the value of the
third digit from 0 through to 9, the value will wrap from 9
Pressing the  Up key to advance the operation to
the next digit and sets the third digit, in this case to 5
New / Change Password, third digit entered, prompting
for fourth digit. (* denotes that decimal point will be
flashing).
Pressing the  Down key will scroll the value of the
fourth digit from 0 through to 9, the value will wrap from
9 round to 0.
Pressing the  Up key to advance the operation to
the New Password Confirmed and sets the fourth digit,
in this case to 3.
17
New Password confirmed.
Pressing the  Down key will return to the New/Change
Password.
Pressing the  Up key will advances to the Menu
selection screen.(see section 3.2).
3.2 Menu selection.
3.2.1 System Parameter selection screen.
This screen is used to select the different system
Parameter like system type,CT Ratio,PT Ratio,
Pressing the  Up key allows the user to set
Different system parameters.
(see section 3.2.1.1 to 3.2.1.8)
Pressing the  down key will advance to
Communication selection screen (see section 3.2.2)
3.2.2 Communication Parameter selection screen.
This screen is used to select the different communication
parameters like Address selection,RS485 Parity selection,
Rs485 baud rate
Pressing the  Up key allows the user to set different
Communication parameters
(see section 3.2.2.1 to 3.2.2.3)
Pressing the  down key will advance to Reset parameter
Screen. (see section 3.2.3)
18
3.2.3 Reset Parameter selection screen.
This screen is used to Reset the different parameters .
Pressing the  Up key allows the user to Reset different
system parameters (see section 3.2.3.1)
Pressing the 
down key  will advance to Output
Option selection screen (see section 3.2.4).
3.2.4 Output Option selection screen.
This screen will allow the user to select different
Output options Like Relay1,Relay2,Analog Output.
Pressing the  Up key allows the user to select &
Configuare the output option (see section 3.2.4.1)
Pressing the  down key will advance to Quit screen.
(see section 3.2.5)
3.2.5 Quit screen.
Pressing the  Up key will allow the user to Quit from menu
& return to measurement screen.
19
3.2.1 System parameters Selection
3.2.1.1 System Type
This screen is used to set the system type .
System type 3 for 3 phase 3 wire & 4 for 3 phase 4 wire system.
Pressing the 
Up key accepts the present
value and advances to the Potential transformer
primary value Edit menu (see section 3.2.1.2)
Pressing the  Down key will enter the system type
edit mode and scroll the values through values available .
Pressing the  Up key advances to the system
type confirmation menu.
System Type Confirmation
This screen will only appear following the edit of
system type. If system type is to be Downed again,
Pressing the 
Up key sets the displayed value and
will advance to Potential Transformer Primary Value
Edit menu. (See section 3.2.1.2)
Pressing the  Down key will return to the system type
edit stage by blanking the bottom line of the display
3.2.1.2 Potential Transformer Primary Value
The nominal full scale voltage which will be displayed as the Line to Line voltages for all
system types. The values displayed represent the voltage in kilovolts
(note the x1000 enunciator).
20
Pressing the  Up key accepts the present value
and advances to the potential Transformer secondary
Value edit menu. (See Section 3.2.1.3)
Pressing the  Down key will enter the Potential
Transformer Primary Value Edit mode.
Initially the multiplier must be selected, pressing the 
Down key will move the decimal point position to the
right until it reaches # # # .# after which it will return to #. # # #.
Pressing the  Up key accepts the present multiplier (decimal point position) and
advances to the potential Transformer primary Digit Edit mode.
Potential Transformer primary Digit Edit
Pressing the  Down key will scroll the value of the most
significant digit from 0 through to 9 unless the presently
displayed Potential Transformer Primary value together with
the Current Transformer Primary Value, previously set,
would result in a maximum power of greater than 666.6
MVA per phase in which case the digit range will be restricted.
Pressing the  Up key accepts the present value at the
cursor position and advances the cursor to the next less significant digit.
The PT Primary value can be set from 100V L-L to 692.8 kV L-L.
Note : the flashing decimal point indicates the cursor position, a steady decimal point will
be present to identify the scaling of the number until the cursor position coincides with the
steady decimal point position. At this stage the decimal point will flash.
When the least significant digit has been set pressing the 
Potential Transformer Primary Value Confirmation stage.
Up key will advance to the
Screen showing display of 0.120 kV i.e. 120 Volts indicating steady decimal point and cursor
flashing at the hundreds of volts position.
21
Potential Transformer Primary Value Confirmation
This screen will only appear following an edit of the
Potential Transformer Primary Value.
If the scaling is not correct, pressing the 
Down key
will return to the Potential Transformer Primary Value Edit
stage.
Note : 0.120 kV i.e. 120 VL-L
Pressing the  Up key sets the displayed value and
will advance to the Potential Transformer secondary value
(See Section 3.2.1.3)
3.2.1.3 Potential Transformer secondary Value
The value must be set to the nominal full scale secondary voltage which will be obtained
from the Transformer when the potential transformer(PT)primary is supplied with the voltage
defined in 3.2.1.2 potential transformer primary voltage. The ratio of full scale primary to full
scale secondary is defined as the transformer ratio.
Pressing the  Up key accepts the present value and
advances to the Current Transformer Primary Value edit
menu. (See Section 3.2.1.4)
Note that the range of instrument is from 240 to 480V for
415 VL-L. Please refer the table below for different ranges.
Pressing the  Down key will enter the Potential
Transformer Secondary Value Edit mode.
Down key will scroll the value of the most significant digit
From available range of PT secondary value
Pressing the  Up key accepts the present value at the cursor position and advances
the cursor to the next less significant digit.
22
Potential Transformer secondary ranges for various Input Voltages
110V L-L (63.5V L-N)
230V L-L (133.0V L-N)
415V L-L (239.6V L-N)
100 - 120V L-L (57.73V - 69.28V L-N)
121 - 239V L-L (69.86V - 138V L-N)
240 - 480V L-L (138.56V - 277.12V L-N)
Note : the flashing decimal point indicates the cursor position, a steady decimal point will
be present to identify the scaling of the number until the cursor position coincides with the
steady decimal point position. At this stage the decimal point will flash.
When the least significant digit has been set pressing the  Up key will advance to the
Potential Transformer secondary Value Confirmation stage.
Potential Transformer Secondary Value Confirmation
This screen will only appear following an edit of the
Potential Transformer Secondary Value.
If the scaling is not correct, pressing the 
Down
key will return to the Potential Transformer Secondary
Value Edit
Pressing the 
Up key sets the displayed value
and will advance to the current Transformer Primary Value (See Section 3.2.1.4)
3.2.1.4 Current Transformer Primary Value
The nominal Full Scale Current that will be displayed as the Line currents. This screen
enables the user to display the Line currents inclusive of any transformer ratios, the values
displayed represent the Current in Amps.
Pressing the  Up key accepts the present value and advances to the Current Transformer
Secondary Value (See Section 3.2.1.5)
23
Pressing the 
Down key will enter the Current
Transformer Primary Value Edit mode. This will scroll the
value of the most significant digit from 0 through to 9,
unless the presently displayed Current Transformer
Primary Value together with the Potential Transformer
Primary Value results in a maximum power of greater
than 666.6 MVA in which case the digit range will be
restricted, the value will wrap. Example: If primary value
of PT is set as 692.8kV L-L (max value) then primary value of Current is restricted to 1157A.
Pressing the  Up key will advance to the next less significant digit. (* Denotes that
decimal point will be flashing).
The Maximum Power restriction of 666.6 MVA refers to 120% of nominal current and
120% of nominal voltage, i.e, 462.96 MVA nominal power per phase.
When the least significant digit had been set, pressing the 
Current Transformer Primary Value Confirmation stage.
Up key will advance to the
The minimum value allowed is 1, the value will be forced to 1 if the display contains zero
when the  Up key is pressed.
Current Transformer Primary Value Confirmation.
This screen will only appear following an edit of the Current
Transformer
Primary Value
.
If the scaling is not correct, Pressing the 
Down key
will return to the  Current Transformer Primary Value Edit
stage with the most significant digit highlighted (associated
decimal point flashing) and the bottom line of the display
will be blanked.
Pressing the  Up key sets the displayed value and will advance to the Current
Transformer Secondary Value Edit menu. (See Section 3.2.1.5)
24
3.2.1.5 Current Transformer Secondary Value
Pressing the 
This screen is used to set the secondary value for Current
Transformer. Secondary value 5 for 5A or 1 for 1A can
be selected. Pressing  Up key accepts the present
value and advances to the Demand integration Time
(See Section 3.2.1.6)
Pressing the 
Down key will enter the CT Secondary
value edit mode and scroll the value through the values
available.
Up key will advance to the CT Secondary value confirmation.
CT Secondary value confirmation
This screen will only appears following an edit of CT
secondary value .
If secondary value shown is not correct, pressing the
Down key will return to CT secondary edit stage by
blanking the bottom line of the display.
Pressing  Up key sets the displayed value and will
advance to Demand integration Time Edit menu.
(See Section 3.2.1.6)
3.2.1.6 Demand Integration Time
This screen is used to set the period over which current and
power readings are to be integrated The Unit of displayed
Readings is minutes.
Down key will scroll through the
.Pressing the 
Folliowing Options 8,15,20,30.
Pressing the 
Up key will advance to Demand
Integration confirmation screen.
25
Demand Integration Time value confirmation
Pressing  Up key sets the displayed value and will
advance to scroll screen.
(See Section 3.2.1.7)
3.2.1.7 Auto Scrolling :
This screen allows user to enable screen scrolling.
Auto scrolling Edit.
Pressing  Up key accepts the present status and
advance to the Low Current noise cutoff
(See Section 3.2.1.8).
Pressing the 
Down key will enter the Auto Screen
Scrolling Edit and toggle the status Yes and No.
Pressing the  Up key will select the status displayed
and advance to the Low Current noise cutoff
(See Section 3.2.1.8)
26
3.2.1.8 Low Current noise cutoff.
This screen allows the user to set Low noise current cutoff in mA.
Low current cutoff Edit.
.Pressing  Up key accepts the present value and
advance to Energy output Selection.
(See section 3.2.1.9)
Pressing the 
Down key will enter the Low current
noise cutoff Edit mode and scroll the Value through 0 & 30
and wrapping back to 0. Setting 30 will display measured
currents as 0 below 30 mA.
Low current noise cutoff Confirmation.
pressing the  Down key will re-enter the Low current
Noise cutoff Edit mode.
Pressing  Up key set displayed value and Advance to
the energy output selection
(See section 3.2.1.9)
3.2.1.9. Energy Display on modbus
This screen enable user to set energy in terms of Wh / KWh / MWh on RS 485 Output
depending as per the requirement .Same applicable for all types of energy.
Pressing  Up key accepts the presents value and
advances to the Energy digit reset countmenu
(See section 3.2.1.10).
Pressing the  Down key will enter the Energy Display
On Modbus Edit mode and scroll the value through the values
1,2 & 3 wrapping back to 1
1 : Energy In Wh 2 : Energy in KWh 3: Energy in MWh
Pressing the  Up key advances to the Energy Display
On Modbus Confirmation menu.
27
Energy Display On Modbus Confirmation.
This screen will only appear following an edit of the Energy
Display On Modbus.
Pressing the 
Down key will enter the Energy Display
On Modbus Edit Edit stage by blanking the bottom line of
the display.
Pressing  Up key sets the displayed value and will
advance to the Energy digit reset count menu.
(See section 3.2.1.10)
Note : Default value is set to 1 i.e. Energy on Modbus will be in terms of
Wh/VArh/VAh/Ah resp.
3.2.1.10 Energy Digit reset count :
This screen enables user for setting maximum energy
count after which energy will rollback to zero depends upon
setting of Wh,KWh, & MWh.
Pressing the  Up key sets the displayed value and will jump
back to the system parameter selection (See Section 3.2.1)
Pressing the 
Down key will enter the Energy digit
reset count edit mode. This will scroll the value of reset
count from 7 to 14 for Wh,from 7 to 12 for KWh & from
7 to 9 for MWh.
Ex. If energy display on modbus is set Wh & It will set Energy digit count to 10 then energy
will reset after 9,999,999,999 & then will rollback to zero.
Pressing  Up key  will advance to Energy digit reset count confirmation screen.
Pressing the 
Down key will re-enter Energy digit reset count edit mode.
Pressing the  Up key sets the displayed value and will jump back to the system
parameter selection (See Section 3.2.1)
28
Note : 1) Default value is set to 14 i.e if energy count crosses 14 digit it will rollback to zero.
2) Energy displays on modbus is set to (2) & energy digit reset count is set to 12.Energy
screen on display will show ------- i.e Energy overflow .when energy crosses the 11 digit count.
3) Energy displays on modbus is set to (3) & energy digit reset count is set to 9.Energy screen
on display will show ------- i.e Energy overflow .when energy crosses the 8 digit count.
3.2.2 Communication Parameter Selection :
3.2.2.1 Address Setting : This screen applies to the RS 485 output only. This screen
allows the user to set Rs485 parameter for instruments
The range of allowable address is 1 to 247 .
Enter Address, prompt for first digit.
(* Denotes that decimal point will be flashing).
Press the  Down key to scroll the value of the first digit
Press the 
Up key to advance to next digit.
Enter Address, first digit entered, prompt for second digit
(* Denotes that decimal point will be flashing).
Use the 
Press the 
Down key to scroll the value of the second digit
Up key to advance to next digit.
29
Enter Address, second digit entered, prompt for third digit
(* Denotes that decimal point will be flashing).
Use the 
Down key to scroll the value of the third digit
Address confirmation Screen.
This Screen confirms the Address set by user .
Press the  Up key to advance to next Screen
Rs485 Baud Rate (See Section 3.2.2.2)
Pressing the 
Edit mode.
Down key will reenter the Address
3.2.2.2 RS 485 Baud Rate :
This screen allows the user to set Baud Rate of RS 485 port.
The values displayed on screen are in kbaud ..
Pressing  Up key accepts the present value and
advance to the Parity Selection (See Section 3.2.2.3)
Pressing the 
Down key will enter the Baud Rate
Edit mode and scroll the value through 2.4, 4.8, 9.6 , 19.2
and back to 2.4
30
RS 485 Baud Rate confirmation :
Pressing 
Down key will be re-enter into the.
Baud Rate Edit mode
Pressing the  Up key will select the value and advances
to the Parity Selection (See Section 3.2.2.3).
3.2.2.3 RS 485 Parity Selection :
This screen allows the user to set Parity & number of stop bits of RS 485 port.
Pressing  Up key accepts the present value and
advance to Menu selection (see section 3.2).
Pressing the 
Down key will enter the Parity & stop bit
Edit mode and scroll the value through
odd : odd parity with one stop bit
no 1 : no parity with one stop bit
no 2 : no parity with two stop bit
E : even parity with one stop bit
RS 485 Parity confirmation :
Pressing 
Down key will be re-enter into Parity Edit mode .
Pressing the 
Up key will set the value.
Pressing the  Up key again will jump back to the
communication parameter selection menu
(see section 3.2.2).
31
3.2.3 Reset Parameter Selection :
3.2.3.1 Resetting Parameter
The following screens allow the users to reset the all Energy , Lo(Min), hi(Max),Demand,
Run hour, .On hour, No.of Interrupts
Reset (None)
Pressing  Up key advances to Reset Parameter
selection screen (see section 3.2.3)
Pressing the  Down key will enter the Reset option
mode and scroll through Parameter and wrapping back
to None.
Reset option select, (Resets ALL resettable parameter)
The user has scrolled through to the ALL .
Pressing  Up key will select the value and advance to
the Reset ALL Confirmation Mode &. Will reset all
resettable parameter.
Reset ALL Confirmation.
Pressing the 
Select mode.
Down key will re-enter the Reset option
Pressing  Up key will jump back to the Reset
Parameter selection screen (see section 3.2.3).
32
Reset option select, (Reset A Demand, KVA Demand
Parameters KW demand (Import/Export))
The user has scrolled through to the d .
Pressing  Up key will select the value and
advance to the Reset d Confirmation Mode & resets all
Demand parameters.
Reset Demand parameters Confirmation.
Pressing the 
Select mode.
Down key will re-enter the Reset option
Pressing  Up key will jump back to the Reset
Parameter selection screen (see section 3.2.3).
Reset option select, (Resets all Energies)
The user has scrolled through to the E Energy value.
Pressing  Up key will select the value and advance to
the Reset Energy Confirmation Mode.
& resets all Energies (Import Enegy, Export Energy Import
reactive, Export reactive, Apparent Energy Ampere Hour)
33
Reset Energy Confirmation.
Pressing the 
option mode.
Down key will re-enter the Reset
Pressing  Up key will jump back to the
Reset Parameter selection screen (see section 3.2.3).
Reset option select, (Reset Hi)
The user has scrolled through to the Hi (Max)
Pressing  Up key will select the value and advance to
the Reset Hi Confirmation Mode.
Will reset Maximum (Hi) values of Voltage & Current Avg.
appeared at input.
Reset hI (Max) Confirmation.
Pressing the 
Select mode.
Down key will re-enter the Reset option
Pressing  Up key will jump back to the Reset
Parameter selection screen (see section 3.2.3).
34
Reset option select, (Reset Lo)
The user has scrolled through to the Lo (Min)
Pressing  Up key will select the value and advance to
the Reset Lo Confirmation Mode & Will reset minimum
values of Voltage & Current Avg. appeared at Input.
Reset Lo Confirmation
Pressing the  Down key will re-enter the Reset option
Select mode.
Pressing  Up key will jump back to the
Reset Parameter selection screen (see section 3.2.3).
Reset option select, hr (ON Hour & Run Hour)
The user has scrolled through to the hr
Pressing  Up key will select the value and advance to
the Reset hr Confirmation Mode & Will reset On hour &
Run Hour both.
35
Reset hr Confirmation
Pressing the  Down key will re-enter the Reset option
Select mode.
Pressing  Up key will jump back to the Reset
Parameter selection screen (see section 3.2.3).
Reset option select, (Reset Number of Interrupt)
The user has scrolled through to the intr
Pressing  Up key will select the value and advance to
the reset Interrupt Confirmation Mode & Will reset number
of Auxiliary supply interruption count.
Reset Interrupt Confirmation
Pressing the  Down key will re-enter the Reset
parameter Selection(see section 3.2.3).
Pressing  Up key will jump back to the Reset
Parameter selection screen (see section 3.2.3).
36
3.2.4. Output Option selection menu
3.2.4.1 Configuration of Output
This screen applies to the Relay1 Output option Selection .
Pressing  Up key will select the
Relay1 output selection menu(See section 3.2.4.1.1)
pressing the  Down key will advance
Relay2 output option below.
This screen applies to the Relay2 Output option Selection .
Pressing  Up key will advance to the select
Relay 2 output selection menu. (See section 3.2.4.1.2)
pressing the  Down key will advance to
Analog output option below.
This screen applies to the Analog Output Selection.
Pressing  Up key will Select the Analog output
selection menu (See section 3.2.4.3)
Pressing the 
37
Down key will advance to Quit screen.
This screen allows the user to quit the output option
Pressing  Up key will advance to the
Output Parameter selection (See section 3.2.4)
Pressing the  Down key will go back to
Relay1 output option (See section 3.2.4.1).
3.2.4.1.1 Relay1 output Selection menu :
3.2.4.1.1.1 Pulse output :
This screen is used to assign Relay1 in Pulse output mode
Pressing  Up key will advance to the Pulse (for Relay1)
output configuration
(See section 3.2.4.1.1.1.1)
Pressing  Down key will show Limitoutput option
(See section 3.2.4.1.1.2)
3.2.4.1.1.2 Limit output :
This screen is used to assign Relay1 in limit output mode.
Pressing  Up key will assign
Limit (for Relay1) output mode.(See section 3.2.4.1.1.2.1)
Pressing  Down key wil go back to the pulse option
(For Relay 1) screen.(See section 3.2.4.1.1.1)
38
3.2.4.1.1.1.1 Assignment of Energy to pulse output (Relay 1) :
This screen allows the user to assign pulse output to energy (for Relay 1)
Pressing  Up key accepts the present setting
and advance to Pulse duration selection
(see section 3.2.4.1.1.1.2).
Pressing the 
Down key will enter into edit mode
and scroll through the energy setting
A - E : Apparent Energy
I - rE : Import Reactive Energy
I - E : Import Energy ( Active ) E - rE : Export Reactive Energy
E - E : Export Energy ( Active ) A - H : Ampere Hour
Pulse output (for Relay 1) confirmation :
Pressing 
Down key will be re-enter into edit mode .
Pressing the  Up key will set the value and advances
to the  Pulse duration selection (see section 3.2.4.1.1.1.2).
3.2.4.1.1.1.2 Pulse Duration Selection:
This screen applies only to the Pulsed output mode of both the relay. This screen allows
the user to set Relay energisation time in milliseconds.
Pulse Duration Edit.
Pressing  Up key accepts the present value and advance
to pulse rate selection menu (see section 3.2.4.1.1.1.3).
Pressing the 
Down key will enter the Pulse Duration
Edit mode and scroll the value through 60, 100, 200 and
wrapping back to 60.
Pressing the  Up key will select the value and advances
to Pulse Duration Confirmation.
39
Pulse Duration Confirmation.
This screen will only appear following an edit of the
Pulse duration.
pressing the  Down key will re-enter the Pulse
Duration Edit mode.
Pressing  Up key set displayed value and Will advance
to pulse rate selection menu
(See section 3.2.4.1.1.1.3)
3.2.4.1.1.1.3 Pulse Rate
This screen applies to the Relay Output option only. The screen allows user to set the energy
pulse rate divisor. Divisor values can be selected through 1,10,100,1000 in Wh.
Pressing  Up key accepts the presents value and
advances to the Configuration of Output
(See section 3.2.4.1).
Pressing the  Down key will enter the Pulse rate divisor
Edit mode and scroll the value through the values 1,10,100,
1000 wrapping back to 1 in Wh but in KWh & MWh pulse rate
divisor is only 1 ..
Pressing the  Up key advances to the Pulse rate
Divisor Confirmation menu. For setting divisior value refer table 3.
Pulse Rate Divisor Confirmation.
This screen will only appear following an edit of the Pulse
rate divisor.
If the Pulse rate shown is not correct, pressing the  Down
key will return to the Pulse rate divisor Edit stage by
blanking the bottom line of the Pressing  Up key sets
the displayed value and will advance to the Configuration
of output.(See section 3.2.4.1)
40
3.2.4.1.1.2.1 Assignment of Limit output (for Relay1) to parameter.
This screen is for Limit output mode selection. It allows the user to set Limit output corresponding
measured value . Refer Table 2 Parameter for Analog & Limit output  for assignment.
Pressing  Up key accepts the present value and
advance to the Limit1 configuration select screen.
(see section 3.2.4.1.1.2.2 ).
Pressing the 
Down key will enter the  Limit1 output
Edit mode and scroll the values, as per Table 2,
 Parameter for Analog & Limit Output
Pressing the  Up key advance to the Limit1 output
confirmation screen .
Limit1 output Confirmation :
Pressing the 
Down key will re-enter the  Limit1
output Edit
Pressing the  Up key sets the displayed value and will
advance to the Limit1 Configuration select screen
( see section 3.2.4.1.1.2.2 )
3.2.4.1.1.2.2 Limit1 Configuration select
This screen is used to set the Limit1 Configuration, four
different types of configuration can be selected
H i - E (High Alarm & Energized Relay)
H i - d (High Alarm & De-Energized Relay)
L o - E (Low Alarm & Energized Relay)
L o - d (Low Alarm & De-Energized Relay)
(For detail refer to section 9.2)
41
Pressing the  Up key accepts the present value and advances to the Trip point
selectionscreen (see section 3.2.4.1.1.2.3)
Pressing the  Down key will enter the Limit1 configuration edit mode and scroll through
the Modes available .
Pressing the  Up key advances to the Limit1 configuration type confirmation menu.
Limit1 Configuration Confirmation
This screen will only appear following the edit of system
type. If system type is to be changed again,
pressing the  Down key will return to the Limit1configuration
Type edit stage by blanking the bottom line of the display
Pressing the 
Up key sets the displayed value and
will advance to Trip point selection Screen
(See section 3.2.4.1.1.2.3 )
3.2.4.1.1.2.3 Trip point selection :
This screen applies to the Trip point selection.
This screen allows the user to set Trip point for instruments
The allowable range is 10% to 120% for High Alarm .
The allowable range is 10% to 100% for Low Alarm .
Enter value, prompt for first digit.
(* Denotes that decimal point will be flashing).
Press the 
Down key to scroll the values of the first digit
Press the 
Up key to advance to next digit.
42
The first digit entered, prompt for second digit
(* Denotes that decimal point will be flashing).
Use the 
Press the 
Down key to scroll the value of the second digit
Up key to advance to next digit.
The second digit entered, prompt for third digit
(* Denotes that decimal point will be flashing).
Use the 
Down key to scroll the value of the third digit
Entered the value for third digit .
Press the 
Screen.
Up key to advance to trip point confirmation
43
Value confirmation Screen.
This Screen confirms the value set by user .
Press the 
Up key to advance to next Screen
Hysteresis selection ( see section 3.2.4.1.1.2.4)
Pressing the 
Down key will return in edit mode
3.2.4.1.1.2.4 Hysteresis selection :
This screen applies to the Hysteresis selection.
This screen allows the user to set Hysteresis for relay1 output
The allowable range is 0.5% to 50 % of Trip point .
Enter value, prompt for first digit.
(* Denotes that decimal point will be flashing).
Press the 
Press the 
Down key to scroll the value of the first digit.
Up key to advance to next digit.
The first digit entered, prompt for second digit (* Denotes
that decimal point will be flashing).
Use the 
digit
Press the 
Down key to scroll the value of the second
Up key to advance to next digit.
44
The second digit entered, prompt for third digit
(* Denotes that decimal point will be flashing).
Use the 
Down key to scroll the value of the third digit
Entered value for third digit .
Press the  Up key to advance to Hysteresis
confirmation Screen.
Hysteresis confirmation Screen.
This Screen confirms the percentage value set by user .
& Screen will appear only after edit mode of Hysteresis.
Press the 
Up key to advance to next Screen
Energizing delay time ( 3.2.4.1.1.2.5 )
45
3.2.4.1.1.2.5 Energizing Delay time.
This screen allows the user to set Energizing Delay time for Relay 1 Limit Assigned Parameters .
Pressing  Up key accepts the present value and
advance to De-energizing delay screen
.
Pressing the 
Down key will enter the Energizing
Delay Edit mode and scroll the Value through 1 to10
Energizing delay time Confirmation.
This screen will appear only after edit mode of Energizing
delay time
pressing the  Down key will re-enter the Energizing
delay Edit mode.
Pressing  Up key set displayed value and
will advance to Assignment of De-energizing delay time.
(See section 3.2.4.1.1.2.6 )
3.2.4.1.1.2.6 De-Energizing Delay time.
This screen allows the user to set De-Energizing Delay time for Relay 1 Limit Assigned Parameters .
Pressing  Up key accepts the present value and
advance to Configuration of Output.
(See section 3.2.4.1 )
Pressing the 
Down key will enter the De-Energizing
Delay Edit mode and scroll the Value through 1 to10
46
De-Energizing delay time Confirmation.
This screen will appear only after edit mode of De-energizing
delay time.
pressing the  Down key will re-enter the De-energizing
delay Edit mode.
Pressing  Up key set displayed value and will advance
to Configuration of Output. (See section 3.2.4.1 )
3.2.4.1.2 Relay 2 Output Selection :
Configuration of Relay 2 for Pulse or Limit Output is same as Relay 1. If you Select the
Pulse output option for Relay 1 same setting will be applicable for Relay 2 except
assignment of energy to Pulse output (i.e. Energy assignment of both relay can be different.)
3.2.4.1.3 Analog Output
3.2.4.1.3.1 Parameter setting for Analog Output 1 ( Optional )
This screen is for analog output 1 only . It allows the user to set analog output 1 to
corresponding measured parameter . Refer table2  Parameter for Analog & Limit output .
Pressing  Up key accepts the present value and
advance to the Analog output 2 selection
(see section 3.2.4.1.3.2 ).
Pressing the 
Down key will enter the  Analog output
1 Edit mode and scroll the values, as per Table 2
 Parameter for Analog & Limit output
Pressing the  Up key advance to the Analog output 1
confirmation screen .
47
Analog output 1 Confirmation :
This Screen will appear only after edit mode of Analog
output 1 Parameter.
Pressing the 
Down key will re-enter the  Analog
output 1 Edit
Pressing the  Up key sets the displayed value and will
advance to the Analog output 2 selection screen
( see section 3.2.4.1.3.2 )
3.2.4.1.3.2 Parameter setting Analog Output 2 ( Optional )
This screen is for analog output 2 only . It allows the user to set analog output 2 to
corresponding measured parameter . Refer table2  Parameter for Analog & Limit output .
Pressing  Up key accepts the present value and
advance to Analog output selection screen
(see section 3.2.4.1 ).
Pressing the 
Down key will enter the  Analog output
2 Edit mode and scroll the values, as per Table 2.
 Parameter for Analog output
Pressing the  Up key advance to the Analog output 2
confirmation screen .
Analog output 2 Confirmation :
This Screen will appear only after edit mode of Analog
output 2 Parameter.
Pressing the 
Down key will re-enter the  Analog
output 2 Edit
Pressing the  Up key sets the displayed value and will
advance to the Analog output selection screen
(see section 3.2.4.1 ).
48
4.Phase Rotation Error screen :
Meter shows phase rotation error if the phase sequence R-Y-B (L1-L2-L3) is not maintained
This screen indicates that Phase sequence is incorrect.
User must check this screen in order to get correct readings
When meter is connected.
Correct Phase sequence :
This Screen indicates the phase sequence connected to
meter is correct. If phase sequence is wrong this screen is
useful to get correct phase sequence by interchanging
connection & verifying it with screen.
This Screen indicates that all three phases (Voltages)
are absent.
49
5. Run Hour
This Screen shows the total no. of hours the load is
connected Even if the Auxiliary supply is interrupted count
of Run hour will be maintained in internal memory &
displayed in the format hours. min. For example if
Displayed count is 105000.10 r-H it indicates 105000 hours
& 10 minutes. After 999999.59 run hours display will
restart from zero. To reset run hour manually see section
Resetting Parameter 3.2.3.1
6. On Hour
This Screen shows the total no. of hours the Axillary Supply
is ON. Even if the Auxiliary supply is interrupted count of
On hour will be maintained in internal memory & displayed
in the format hours. min. For example if Displayed count
is 005000.10 On-H it indicates 005000 hours & 10 minutes.
After 999999.59 On hours display will restart from zero.
To reset On hour manually see section Resetting
Parameter 3.2.3.1
7. Number of Interruption :
This Screen Displays the total no. of times the Axillary
Supply was Interrupted. Even if the Auxiliary supply is
interrupted count will be maintained in internal memory
To reset No of Interruption manually see section
Resetting Parameter 3.2.3.1
50
8. Analog Output ( optional ) :
This module provides two d.c. isolated outputs .There are two output options
1) Two 0 - 1mA outputs , internally powered .
2) Two 4 - 20mA outputs , internally powered .
The 0 -1mA output module has an 0V return on each end of the 4 way connector
( Please refer section 15 for connection details )
On both modules the output signals are present on pins A1(Anolog Output 1) &
A2 (Analog Output 2)
These outputs can be individually assigned to represent any one of the measured and
displayed Parameters.
All settlings are user configurable via the user interface screen. See Analog o/p selection
( section 3.2.4.1.3 ) for details .
* Note : Refer diagrams 1 & 2
Diagram 2 : ( 0 - 1 mA )
Diagram 1 : ( 4 -20 mA )
0
0 (12mA)
00 (0.5mA)
90 (16mA)
270 (8mA)
900 (8mA)
2700 (0.25mA)
1810 (1mA)
181 (4mA)
1800 (1mA)
180 (20mA)
51
8. Analog Output ( optional ) :
TABLE 2 : Parameter for Analog & Limit output
Parameter No.
Parameter
None
Volts 1
Volts 2
Volts 3
IL1
IL2
IL3
W1
W2
W3
10
VA1
11
VA2
12
VA3
13
VAr1
14
VAr2
15
VAr3
16
* PF1
17
* PF2
18
* PF3
19
* PA1
3P 4W
3P 3W
Range
0 - 100 %
0 - 100 %
0 - 100 %
0 - 100 %
0 - 100 %
0 - 100 %
0 - 120 %
X
0 - 120 %
X
0 - 120 %
X
0 - 120 %
X
0 - 120 %
X
0 - 120 %
X
0 - 120 %
X
0 - 120 %
X
0 - 120 %
X
X
180 / 0 / -180
X
180 / 0 / -180
X
180 / 0 / -180
X
180 / 0 / -180
52
Parameter No.
20
Parameter
3P 4W
21
* PA3
22
Volts Ave.
24
Current Ave.
27
Watts sum
29
VA sum
31
VAr sum
32
* PF Ave.
34
36
* PA Ave.
Freq.
43
Watt Demand Imp.
44
Watt Max Demand Imp.
45
Watt Demand Exp
46
Watt Demand Max Exp
51
VA Demand
52
VA Max Demand.
53
Current Demand.
54
Current Max Demand.
101
VRY
102
VYB
103
VBR
113
I Neutral
3P 3W
Range
X
180 / 0 / -180
X
180 / 0 / -180
0 - 100 %
0 - 100 %
0 - 120 %
0 - 120 %
0 - 120 %
180 / 0 / -180
180 / 0 / -180
45 to 66 Hz
0 - 120 %
0 - 120 %
0 - 120 %
0 - 120 %
0 - 120 %
0 - 120 %
0 - 100 %
0 - 100 %
0 - 100 %
X
0 - 100 %
X
0 - 100 %
X
0 - 100 %
X
* PA2
53
Note : Parameters 1,2,3 are L-N Voltage for 3P 4W & L-L Voltage for 3P 3W .
9. Relay output (Optional) :
MULTIS is provided with either 1 or 2 relay for pulse output as well as for limit switch
9.1 Pulse Output :
Pulse output is the potential free, very fast acting relay contact which can be used to drive
an external mechanical counter for energy measurement.
Multifunction Meter pulse output can be configured to any of the following parameter
through setup parameter screen
4) Reactive Energy (Export)
1) Active Energy (Import)
5) Apparent Energy
2) Active Energy (Export)
3) Reactive Energy (Import) 6) Ampere hour
TABLE 3 : Energy Pulse Rate Divisor
1.For Energy Output in Wh
Pulse rate
Pulse
System Power*
1per Whr
Up to 3600W
1per kWhr
Up to 3600kW
Above 3600kW
1per MWhr
1per 10Whr
Up to 3600W
1per 10kWhr Up to 3600kW
1per 10MWhr Above 3600kW
1per 100Whr
Up to 3600W
1per 100kWhr Up to 3600kW
1per 100MWhr Above 3600kW
1 per 1000Whr Up to 3600W
1 per 1000kWhr Up to 3600kW
1per 1000MWhr Above 3600kW
Divisor
1
10
100
1000
Pulse Duration 60 ms,100 ms or 200 ms
54
2. For Energy Output in KWh
3. For Energy Output in MWh
Pulse rate
Divisor Pulse
System Power*
1 per KWhr
1
Up to 3600W
1 per 1000KWhr Up to 3600kW
1per 1000MWhr Above 3600kW
Pulse rate
Divisor Pulse
System Power*
1per MWhr
1
Up to 3600W
1per 1000MWhr Up to 3600kW
1per 1000GWhr Above 3600kW
Above options are also applicable for Apparent and Reactive Energy.
* System power = 3 x CT(Primary) x PT(Primary)L-N for 3 Phase 4 Wire
System power = Root3 x CT(Primary) x PT(Primary)L-L for 3 Phase 3 Wire
Ampere Hour:
Divisor 1(Default)
CT secondary = 1A Max pulse rate 3600 pulses per Ah **
CT secondary = 5A Max pulse rate 720 pulses per Ah **
Divisors 10
CT secondary = 1A Max pulse rate 3600 pulses per 10Ah **
CT secondary = 5A Max pulse rate 720 pulses per 10Ah **
Divisors 100
CT secondary = 1A Max pulse rate 3600 pulses per 100Ah **
CT secondary = 5A Max pulse rate 720 pulses per 100Ah **
Divisors 1000
CT secondary = 1A Max pulse rate 3600 pulses per 1000Ah **
CT secondary = 5A Max pulse rate 720 pulses per 1000Ah **
Pulse duration 60 ms, 100 ms or 200 ms
**No. of Pulses per Ampere hour = Maximum Pulses / CT Ratio
Where, CT Ratio = (CT primary/ CT Secondary)
55
9.2 Limit Switch :
Limit switch can be used to monitor the measured parameter ( Ref.Table:2 )in relation
with to a set limit.
The limit switch can be configured in one of the four mode given below:1) Hi alarm & Relay Energized Relay..
2) Hi alarm & De-Energized Relay.
3) Lo alarm & Energized Relay.
4) Lo alarm & De-Energized Relay.
With User selectable Trip point, Hysteresis, Energizing Delay & De-Energizing delay.
Hi Alarm:
If Hi-Alarm Energized or Hi Alarm De-Energized option is selected then relay will get
energized or De-energized,if selected parameter is greater than or equal to trip point.
Lo Alarm:
If Lo-Alarm Energized or Lo Alarm De-Energized option is selected then relay will get
energized or De-energized,if selected parameter is less than or equal to trip point.
Trip point:
Trip point can be set in the range of 10% to 120 % of nominal value for Hi-Alarm & 10%
to 100 % of nominal value for Lo-Alarm.
Hysteresis:
Hysteresis can be set in the range of 0.05% to 50 % of set trip point .
If Hi-alarm Energized or Hi-alarm De-energized is selected then relay will get
De-energized or Energized respectively, if set parameter value is less than Hysteresis
Similarly if Lo-alarm Energized or Lo-alarm De-Energized.
Energizing Delay:
The energizing delay can be set in the range from1 to 10 sec.
De-Energizing Delay:
The De-energizing delay can be set in the range from1 to 10 sec.
Note : In case of lo alarm if trip point is set at 100% then maximum 20% Hysterisis can be set..
56
10. RS 485 ( ModBus ) Output :
MULTIS supports MODBUS (RS485) RTU protocol( 2-wire ) .
Connection should be made using twisted pair shielded cable. All "A" and "B" connections
are daisy chained together. The screens should also be connected to the Gnd terminal.
To avoid the possibility of loop currents, an Earth connection should be made at one point
57
on the network.Loop (ring) topology does not require any termination load. Line topology
may or may not require terminating loads depending on the type and length of cable used.
The impedance of the termination load should match the impedance of the cable and be at
both ends of the line. The cable should be terminated at each end with a 120 ohm
(1/4 Watt min.) resistor.
RS 485 network supports maximum length of 1.2km. Including the Master, a maximum
of 32 instruments can be connected in Rs485 network.The permissible address range for
MULTIS is between 1 and 247 for 32 instruments. Broadcast Mode (address 0) is not allowed.
The maximum latency time of an MULTIS is 200ms i.e. this is the amount of time that can
pass before the first response character is output.
After sending any query through software ( of the Meter) , it must allow 200ms of time to
elapse before assuming that the MULTIS is not going to respond. If slave does not respond
within 200 ms, Master can ignore the previous query and can issue fresh query to the slave.
The each byte in RTU mode has following format:
8-bit binary, hexadecimal 0-9, A-F
2 hexadecimal characters contained in each 8-bit field of
the message
Format of Data Bytes
4 bytes (32 bits) per parameter.
Floating point format ( to IEEE 754)
Most significant byte first (Alternative least significant byte first)
Error Checking Bytes
2 byte Cyclical Redundancy Check (CRC)
Byte format
1 start bit,
8 data bits, least significant bit sent first
1 bit for even/odd parity
1 stop bit if parity is used; 1 or 2 bits if no parity
Communication Baud Rate is user selectable from the front panel between
2400, 4800, 9600, 19200 bps.
58
Function code :
03
Read Holding Registers
Read content of read /write location ( 4X )
04
Read input Registers
Read content of read only location ( 3X )
16
Presets Multiple Registers
Set the content of read / write locations ( 4X )
Exception Cases : An exception code will be generated when MULTIS receives ModBus
query with valid parity & error check but which contains some other error ( e.g. Attempt to
set floating point variable to an invalid value ) The response generated will be Function
code ORed with HEX (80H ). The exception codes are listed below
01
Illegal function
The function code is not supported by MULTIS
02
Illegal Data
Address
Attempt to access an invalid address or an attempt to read
or write part of a floating point value
03
Illegal Data
Value
Attempt to set a floating point variable to an invalid value
Accessing 3 X register for reading measured values:
Two consecutive 16 bit registers represent one parameter. Refer table 4 for the addresses
of 3X registers (Parameters measured by the instruments).
Each parameter is held in the 3X registers. Modbus Code 04 is used to access all parameters.
Example :
To read parameter ,
Volts 3 : Start address= 04 (Hex)
Number of registers = 02
Note : Number of registers = Number of parameters x 2
Each Query for reading the data must be restricted to 20 parameters or less. Exceeding
the 20 parameterlimit will cause a ModBus exception code to be returned.
59
Query :
01 (Hex)
04 (Hex)
Device
Address
Function
Code
00 (Hex)
04(Hex)
00 (Hex)
02(Hex)
30 (Hex)
0A (Hex)
CRC
Low
CRC
High
Start Address Start Address Number of Number of
Registers Hi Registers Lo
High
Low
Start Address High : Most significant 8 bits of starting address of the parameter requested.
Start Address low :Least significant 8 bits of starting address of the parameter requested.
Number of register Hi : Most significant 8 bits of Number of registers requested.
Number of register Lo : Least significant 8 bits of Number of registers requested.
(Note : Two consecutive 16 bit register represent one parameter.)
Response: Volt3 (219.25V)
01 (Hex)
04 (Hex)
04 (Hex)
Device
Address
Function
Code
Byte
Count
43 (Hex)
5B (Hex)
41 (Hex)
21 (Hex)
Data Register1 Data Register1 Data Register2 Data Register2
Low Byte
Low Byte
High Byte
High Byte
6F (Hex)
CRC
Low
9B (Hex)
CRC
High
Byte Count : Total number of data bytes received.
Data register 1 High Byte : Most significant 8 bits of Data register 1 of the parameter requested.
Data register 1 Low Byte : Least significant 8 bits of Data register 1 of the parameter requested.
Data register 2 High Byte : Most significant 8 bits of Data register 2 of the parameter requested.
Data register 2 Low Byte : Least significant 8 bits of Data register 2 of the parameter requested.
(Note : Two consecutive 16 bit register represent one parameter.)
60
Table 4 : 3 X register addresses (measured parameters)
Address Parameter Parameter
(Register) No.
1
30001
Volts 1
2
30003
Volts 2
3
30005
Volts 3
4
30007
Current 1
5
30009
Current 2
30011
6
Current 3
30013
7
W1
30015
8
W2
30017
9
W3
30019
10
VA1
30021
11
VA2
30023
12
VA3
30025
13
VAR1
30027
14
VAR2
30029
15
VAR3
30031
16
PF1
30033
17
PF2
30035
18
PF3
30037
19
Phase Angle 1
30039
20
Phase Angle 2
30041
21
Phase Angle 3
30043
22
Volts Ave
30045
23
Volts Sum
30047
24
Current Ave
30049
25
Current Sum
Modbus Start Address Hex
3P 4W 3P 3W
High Byte
Low Byte
00
0
00
2
00
4
00
6
00
8
00
A
00
X
C
00
X
E
00
X
10
00
X
12
00
X
14
00
X
16
00
X
18
00
X
1A
00
X
1C
00
X
1E
00
X
20
00
X
22
00
X
24
00
X
26
00
X
28
00
2A
00
2C
00
2E
00
30
61
Address Parameter Parameter
Modbus Start Address Hex
3P 4W 3P 3W
High Byte
Low Byte
(Register) No.
30051
26
Watts Ave
00
32
30053
27
Watts Sum
00
34
30055
28
VA Ave
00
36
30057
29
VA Sum
00
38
30059
30
VAr Ave
00
3A
30061
31
VAr Sum
00
3C
30063
32
PF Ave
00
3E
30065
33
PF Sum
00
40
X
30067
34
Phase Angle Ave
00
42
30069
35
Phase Angle Sum
00
44
X
30071
36
Freq
00
46
30073
37
Wh Import
00
48
30075
38
Wh Export
00
4A
39
30077
VARh Import
00
4C
40
30079
VARh Export
00
4E
41
30081
VAh
00
50
42
30083
Ah
00
52
43
30085
W Demand (Import)
00
54
44
30087
W Max Demand (Import)
00
56
45
30089
W Demand (Export)
58
00
46
30091
W Max Demand (Export)
00
5A
47
30093
48
30095
49
30097
00
30099
50
51
VA Demand
00
64
30101
52
66
30103
VA Max Demand
00
62
Address Parameter Parameter
Modbus Start Address Hex
3P 4W 3P 3W
High Byte
Low Byte
(Register) No.
53
30105
A Demand
00
68
54
30107
A Max Demand
00
6A
67
30133
Volts Ave Max
00
84
68
30135
Volts Ave Min
00
86
71
30141
Current Ave Max
00
8C
72
30143
Current Ave Min
00
8E
101
30201
VL 1 - 2 ( Calculated )
X
00
C8
102
30203
VL 2 - 3 ( Calculated )
X
00
CA
103
30205
VL 3 - 1 ( Calculated )
X
00
CC
104
30207
V1 THD( % )
00
CE
105
30209
V2 THD( % )
00
D0
106
30211
V3 THD( % )
00
D2
107
30213
I1 THD( % )
00
D4
108
30215
I2 THD( % )
00
D6
109
30217
I3 THD( % )
00
D8
110
30219
System Voltage THD( % )
00
DA
111
30221
System Current THD( % )
00
DC
113
30225
I neutral
X
00
E0
114
30227
Run Hour
00
E2
115
30229
On Hour
00
E4
116
30231
No. Of Interrupts
00
E6
Note : Parameters 1,2,3 are L-N Voltage for 3P 4W & L-L Voltage for 3P 3W .
63
Accessing 4 X register for Reading & Writing :
Each setting is held in the 4X registers .ModBus code 03 is used to read the current setting
and code 16 is used to write/change the setting. Refer Table 5 for 4 X Register addresses.
Example : Reading System type
System type : Start address= 0A (Hex)
Number of registers = 02
Note :Number of registers = Number of Parameters x 2
Query :
Device Address
01 (Hex)
Function Code
03 (Hex)
Start Address High
00 (Hex)
Start Address Low
0A (Hex)
Number of Registers Hi
00 (Hex)
Number of Registers Lo
02 (Hex)
CRC Low
E4 (Hex)
CRC High
09 (Hex)
Start Address High : Most significant 8 bits of starting address of the parameter requested.
Start Address low :Least significant 8 bits of starting address of the parameter requested.
Number of register Hi : Most significant 8 bits of Number of registers requested.
Number of register Lo : Least significant 8 bits of Number of registers requested.
(Note : Two consecutive 16 bit register represent one parameter.)
64
Response: System Type ( 3phase 4 wire = 3 )
Device Address
01 (Hex)
Function Code
03 (Hex)
Byte Count
04 (Hex)
Data Register1 High Byte
40 (Hex)
Data Register1Low Byte
40 (Hex)
Data Register2 High Byte
00 (Hex)
Data Register2 Low Byte
00(Hex)
CRC Low
EE (Hex)
CRC High
27 (Hex)
Byte Count : Total number of data bytes received.
Data register 1 High Byte : Most significant 8 bits of Data register 1 of the parameter requested.
Data register 1 Low Byte : Least significant 8 bits of Data register 1 of the parameter requested.
Data register 2 High Byte : Most significant 8 bits of Data register 2 of the parameter requested.
Data register 2 Low Byte : Least significant 8 bits of Data register 2 of the parameter requested.
(Note : Two consecutive 16 bit register represent one parameter.)
Example : Writing System type
System type :
Start address= 0A (Hex)
Number of registers = 02
65
Query:( Change System type to 3phase 3wire = 2 )
Device Address
01 (Hex)
Function Code
10 (Hex)
Starting Address Hi
00 (Hex)
Starting Address Lo
0A(Hex)
Number of Registers Hi
00 (Hex)
Number of Registers Lo
02(Hex)
Byte Count
04 (Hex)
Data Register-1High Byte
40 (Hex)
Data Register-1 Low Byte
00(Hex)
Data Register-2 High Byte
00(Hex)
Data Register-2 Low Byte
00(Hex)
CRC Low
66 (Hex)
CRC High
10 (Hex)
Byte Count : Total number of data bytes received.
Data register 1 High Byte : Most significant 8 bits of Data register 1 of the parameter requested.
Data register 1 Low Byte : Least significant 8 bits of Data register 1 of the parameter requested.
Data register 2 High Byte : Most significant 8 bits of Data register 2 of the parameter requested.
Data register 2 Low Byte : Least significant 8 bits of Data register 2 of the parameter requested.
(Note : Two consecutive 16 bit register represent one parameter.)
66
Response:
Device Address
01 (Hex)
Function Code
10 (Hex)
Start Address High
00 (Hex)
Start Address Low
0A(Hex)
Number of Registers Hi
00 (Hex)
Number of Registers Lo
02(Hex)
CRC Low
61 (Hex)
CRC High
CA (Hex)
Start Address High : Most significant 8 bits of starting address of the parameter requested.
Start Address low :Least significant 8 bits of starting address of the parameter requested.
Number of register Hi : Most significant 8 bits of Number of registers requested.
Number of register Lo : Least significant 8 bits of Number of registers requested.
(Note : Two consecutive 16 bit register represent one parameter.)
Table 5 : 4 X register addresses
Address Parameter Parameter
(Register) No.
1
40001
Demand Time
40003
Demand Period
2
Energy display on Modbus
3
40005
4
40007
Sys Voltage
5
40009
Sys Current
6
40011
Sys Type
7
40013
Pulse Width
8
40015
Energy Reset
Read / Write Modbus Start Address Hex
High Byte
Low Byte
00
00
00
02
00
04
00
06
00
08
00
0A
00
0C
00
0E
R/Wp
R
R/Wp
R/Wp
R
R
R/Wp
R/Wp
Wp
W
67
Address Parameter Parameter
(Register) No.
Run/On Hour & Interruption Reset
9
40017
RS 485 Set-up Code
40019
10
11
40021
.Node Address.
12
40023
Pulse Divisor
13
40025
Min Reset
14
40027
Max Reset
15
40029
Analog Out 1- Para Sel
16
40031
Analog Out 2- Para Sel
17
40033
PT Primary
18
40035
CT Primary
19
40037
System Power
20
Energy digit reset count
40039
21
40041
Register Order/Word Order
22
CT Secondary
40043
23
40045
PT Secondary
24
40047
Relay1 output select
25
40049
Pulse1/Limit1 Parameter select
26
40051
Limit1 Trip point
27
40053
Hysteresis(Limit1)
28
40055
Limit1 delay(On)
29
40057
Limit1 delay(Off)
30
40059
Relay2 output select
Pulse2/Limit2 Parameter select
31
40061
32
40063
Limit2 Trip point
33
40065
Hysteresis(Limit2)
34
Limit2 Delay(On)
40067
35
40069
Limit2 Delay(Off)
36
40071
Password
37
40073
Limit1 Configuration select
38
40075
Limit2 Configuration select
39
40077
Auto scroll
30mA Noise Current Elimination
40
40079
68
Read / Write Modbus Start Address Hex
High Byte
Low Byte
00
Wp
10
12
R/Wp
00
R/Wp
00
14
R/Wp
00
16
Wp
00
18
Wp
00
1A
R/Wp
00
1C
R/Wp
00
1E
R/Wp
00
20
R/Wp
00
22
00
R
24
R/Wp
00
26
R/Wp
00
28
R/Wp
00
2A
R/Wp
00
2C
R/Wp
00
2E
R/Wp
00
30
R/Wp
00
32
R/Wp
00
34
R/Wp
00
36
R/Wp
00
38
R/Wp
00
3A
R/Wp
00
3C
R/Wp
00
3E
R/Wp
00
40
R/Wp
00
42
R/Wp
00
44
R/W
00
46
R/Wp
00
48
R/Wp
00
4A
R/Wp
00
4C
R/Wp
00
4E
Explanation for 4 X register :
Address
Description
Parameter
40001
Demand Reset Demand Reset is used to reset the Demand parameter.
A value of zero must be Written to this register to reset
the Demand period. Writing any other value will return
an error.
40003
Demand
Period
Demand period represents demand time in minutes.
The applicable values are 8,15,20 or 30. Writing any
other value will return an error.
40005
Energy display
on Modbus
This address is used to set energy display on modbus in
Wh,KWh & MWh.Write one of the following value to this
address.
1 = Energy in Wh.
2 = Energy in KWh.
3 = Energy in MWh.
40007
System Voltage This address is read only and displays System Voltage
40009
System Current This address is read only and displays System Current
40011
System Type
40013
Pulse Width
of Relay
This address is used to set the System type.
Write one of the following value to this address.
2 = 3 Phase 3 Wire
3 = 3 Phase 4 Wire.
Writing any other value will return error .
This address is used to set pulse width of the Pulse
output. Write one of the following values to this address:
60 : 60 ms
100 : 100 ms
200 : 200 ms
Writing any other value will return error .
69
Address
40015
Parameter
Description
Reset Energy
Counter
This address is used to reset the Energy Counter.
Write zero value to this register to reset the energy
counter. Writing any other value will return an error.
40017
Run/On Hour & This address is used to reset the Run/On hour & number
Interruption
of Interruption . Write zero value to this register to reset
the Run/On hour & number of Interruption.
reset
Writing any other value will return an error.
40019
Rs485 Set-up
Code
This address is used to set the baud rate, Parity,
Number of stop bits. Refer to Table 6 for details.
40021
Node
Address
This register address is used to set Device address
between 1 to 247 .
40023
Pulse Divisor
This address is used to set pulse divisor of the Pulse
output. Write one of the following values to this address
for Wh:
1:
Divisor 1
10 : Divisor 10
100 : Divisor 100
1000 : Divisor 1000 & In KWH or MWh divisior will be
1 default. Writing any other value will return an error.
40025
Min - Reset
This address is used to reset the Min parameters value.
Write Zero value to this register to reset the Min
parameters. Writing any other value will return an error.
40027
Max - Reset
This address is used to reset the Max parameters value.
Write Zero value to this register to reset the Max
parameters. Writing any other value will return an error.
70
Address
Description
Parameter
40029
Analog Out 1Para Set
This address is used to set the parameter for Analog
Output 1.Write one of the parameter no. As per the
options given in Table 2 for Analog & Limit Output
Parameters. Writing any other value will return an error.
40031
Analog Out 2Para Set
This address is used to set the parameter for Analog
Output 2. Write one of the parameter no. As per the
options given in Table 2 for Analog & Limit Output
Parameters. Writing any other value will return an error.
40033
PT Primary
This address allows the user to set PT Primary value.
The maximum settable value is 692.8kV L-L
depends on the per phase 666.6MVA Restriction of
power combined with CT primary
40035
CT Pimary
This address allows the user to set CT Primary value.
The maximum settable value is 9999 & also depends on
the per phase 666.6MVA Restriction of power combined
with PT primary
40037
Sys Power
System Power (Read Only) is the Nominal system
power based on the values of Nominal system volts
and Nominal system current.
40039
Energy digit
Reset Count
This address is used to setting maximum energy count
after which energy will rollback to zero depends upon
setting of Wh,KWh, & MWh.If Energy display on modbus
in Wh count will be set in between 7 to 14 or In KWh set
in between 7 to 12 & In MWh set in between 7 to 9.
71
Address
Description
Parameter
40041
Word Order
40043
CT secondary
40045
PT secondary
This address is used to read and write the PT secondary
value. Ref Table for the range of PT secondary settable
values in Section 3.2.1.3
40047
Relay1 output
select
This address is used to select the Relay 1 operation as
pulse or Limit.
write one of the following values to this address.
0 = Pulse output on Relay 1
128 (Decimal) = Limit output on Relay 1
writing any other value will return an error.
40049
Pulse 1 /Limit 1 This address is used to assign the Parameter to Relay1
If Limit option is selected refer table 2 for parameter
parameter
number & if Pulse option is selected then refer table 7.
select
Word Order controls the order in which MULTIS Lm5x
receives or sends floating - point numbers:- normal or
reversed register order . In normal mode, the two
registers that make up a floating point numbers are sent
most significant bytes first. In reversed register mode ,
the two registers that make up a floating point numbers
are sent least significant bytes first. To set the mode,
write the value 2141.0 into this register- the instrument
will detect the order used to send this value and set
that order for all ModBus transaction involving floating
point numbers.
This address is used to read and write the CT
secondary value write one of the following values to this
address.
1=1A CT secondary
5=5A CT secondary
writing any other value will return an error.
72
Description
Address
40051
Parameter
Limit1
Trip Point
40053
Hysteresis
(Limit 1)
40055
Limit1
Energizing
Delay
This address is used to set the Energizing delay between
1 to 10 . Writting any other value will return an error.
40057
Limit1
de-energizing
Delay
Relay 2
output select
This address is used to set the De-Energizing delay
between 1 to 10 . Writting any other value will return
an error.
This address is used to select the Relay 2 operation as
pulse or Limit.
write one of the following values to this address.
0 = Pulse output on Relay 2
128 (decimal) = Limit output on Relay 2
writing any other value will return an error.
40061
Pulse 2/Limit 2
Parameter
select
This address is used to assign the Parameter to Relay2
If Limit option is selected refer table 2 for parameter
number & if Pulse option is selected then refer table 7.
40063
Limit 2
Trip point
This address is used to set the trip point in %. Any
value between 10 to 100 for Lo- alarm & 10 to120 for
Hi-alarm can be written to this address. Writing any
other value will return an error.
40065
Hysteresis
(Limit 2)
This address is used to set the hysteresis between
0.5 to 50 . Writting any other value will return an error.
40059
This address is used to set the trip point in %. Any value
between 10 to 100 for Lo- alarm & 10 to120 for Hi-alarm
can be written to this address. Writing any other value
will return an error.
This address is used to set the hysteresis between
0.5 to 50 . Writting any other value will return an error.
73
Address
Description
Parameter
40067
Limit 2
Energizing
delay
This address is used to set the Energizing delay
between 1 to 10 . Writting any other value will return
an error.
40069
Limit 2
De-Energizing
delay
This address is used to set the De-Energizing delay
between 1 to 10 . Writting any other value will return
an error.
40071
Password
This address is used to set & reset the password.
Valid Range of Password can be set is 0000 - 9999 .
1) If password lock is present & if this location is read it
will return zero.
2) If Password lock is absent & if this location is read it
will return One.
3) If password lock is present & to disable this lock
first send valid password to this location then write
0000 to this location
4) If password lock is present & to modify 4X parameter
first send valid password to this location so that 4X
parameter will be accessible for modification.
5) If for in any of the above case invalid password is
send then meter will return exceptional error 2.
40073
Limit1
Configuration
Select
This address is used to set the Configuration for relay 1
see table 8 . Writting any other value will return an error.
40075
Limit2
Configuration
Select
This address is used to set the Configuration for relay 2
see table 8 . Writting any other value will return an error.
74
Address
Description
Parameter
40077
Auto scroll
This address is used to activate or de-activatethe auto
scrolling write 0-Deactivate
1-Activate
Writing any other value will return an error.
40079
30mA Noise
current
Elimination
This address is used to activate or de-activatethe 30 mA
noise current elimination write
0-Deactivate
30 (Decimal)-Activate
Writing any other value will return an error.
Table 6 : RS 485 Set-up Code
Baud Rate
Parity
Stop Bit
Decimal value
19200
19200
19200
19200
9600
9600
9600
9600
4800
4800
4800
4800
2400
2400
2400
2400
NONE
NONE
EVEN
ODD
NONE
NONE
EVEN
ODD
NONE
NONE
EVEN
ODD
NONE
NONE
EVEN
ODD
01
02
01
01
01
02
01
01
01
02
01
01
01
02
01
01
12
75
13
14
15
08
09
10
11
04
05
06
07
00
01
02
03
NOTE :
Codes not listed in the table above may give rise to unpredictable results including loss of
communication. Excise caution when attempting to change mode via direct Modbus writes.
Table 7 : Pulse1 & Pulse2 Configuration select
Code
0
1
2
3
4
Configuration
Import Active Energy
Export Active Energy
Import Reactive Energy
Export Reactive Energy
Apparent Energy
Table 8 :Limit1 & Limit2 Configuration select
Code
0
1
2
3
Configuration
Hi- alarm & Energized relay
Hi- alarm & De-energized relay
Lo- alarm & Energized relay
Lo- alarm & De-energized relay
10.1 User Assignable Modbus Registers:
The MULTIS contains the 20 user assignable registers in the address range of 0x200
(30513) to 0x226 (30551) (see Table 9).
Any of the parameter addresses ( 3X register addresses Table 4)) accessible in the
instrument can be mapped to these 20 user assignable registers.
Parameters (3X registers addresses ) that resides in different locations may be accessed
by the single request by re-mapping them to adjacent address in the user assignable
registers area.
The actual address of the parameters ( 3X registers addresses) which are to be assessed
via address 0x200 to 0x226 are specified in 4x Register 0x200 to 0x213 (see Table 10).
76
Table 9 : User Assignable 3X Data Registers
Address
(Register)
30513
30515
30517
30519
30521
30523
30525
30527
30529
30531
30533
30535
30537
30539
30541
30543
30545
30547
30549
30551
Parameter
Number.
257
258
259
260
261
262
263
264
265
266
267
268
269
270
271
272
273
274
275
276
Assignable Register
Assignable Reg 1
Assignable Reg 2
Assignable Reg 3
Assignable Reg 4
Assignable Reg 5
Assignable Reg 6
Assignable Reg 7
Assignable Reg 8
Assignable Reg 9
Assignable Reg 10
Assignable Reg 11
Assignable Reg 12
Assignable Reg 13
Assignable Reg 14
Assignable Reg 15
Assignable Reg 16
Assignable Reg 17
Assignable Reg 18
Assignable Reg 19
Assignable Reg 20
77
Modbus Start Address (Hex)
High Byte
02
02
02
02
02
02
02
02
02
02
02
02
02
02
02
02
02
02
02
02
Low Byte
00
02
04
06
08
0A
0C
0E
10
12
14
16
18
1A
1C
1E
20
22
24
26
Table 10 : User Assignable mapping register ( 4X registers)
Address
(Register)
40513
40514
40515
40516
40517
40518
40519
40520
40521
40522
40523
40524
40527
40528
40529
40530
40531
40532
40533
40534
Parameter
Number.
257
258
259
260
261
262
263
264
265
266
267
268
269
270
271
272
273
274
275
276
Mapping Register
Mapped Add for register #0x0200
Mapped Add for register #0x0202
Mapped Add for register #0x0204
Mapped Add for register #0x0206
Mapped Add for register #0x0208
Mapped Add for register #0x020A
Mapped Add for register #0x020C
Mapped Add for register #0x020E
Mapped Add for register #0x0210
Mapped Add for register #0x0212
Mapped Add for register #0x0214
Mapped Add for register #0x0216
Mapped Add for register #0x0218
Mapped Add for register #0x021A
Mapped Add for register #0x021C
Mapped Add for register #0x021E
Mapped Add for register #0x0220
Mapped Add for register #0x0222
Mapped Add for register #0x0224
Mapped Add for register #0x0226
Modbus Start Address (Hex)
High Byte
02
02
02
02
02
02
02
02
02
02
02
02
02
02
02
02
02
02
02
02
Low Byte
00
01
02
03
04
05
06
07
08
09
0A
0B
0C
0D
0E
0F
10
11
12
13
Example :
Assigning parameter to user assignable registers
To access the voltage2 (3X address 0x0002) and Power Factor1 (3X address 0x001E)
through user assignable register assign these addresses to 4x register (Table 10 ) 0x0200
and 0x0201 respectively .
78
Assigning Query:
Device Address
Function Code
Starting Address Hi
Starting Address Lo
Number of Registers Hi
Number of Registers Lo
Byte Count
Data Register-1High Byte
Data Register-1 Low Byte
Data Register-2 High Byte
Data Register-2 Low Byte
CRC Low
CRC High
01 (Hex)
10 (Hex)
02 (Hex)
00 (Hex)
00 (Hex)*
02(Hex)*
04 (Hex)
00 (Hex)
02 (Hex)
00 (Hex)
1E (Hex)
CB (Hex)
07 (Hex)
Voltage 2 *
}(3X Address 0x0002)
Power Factor 1 *
}(3X
Address 0x001E)
* Note : Parameters should be assigned in Multiple of two i.e. 2,4,6,8.......20.
Response :
Device Address
Function Code
Start Address High
Start Address Low
Number of Registers Hi
Number of Registers Lo
CRC Low
CRC High
01 (Hex)
10 (Hex)
02 (Hex)
00 (Hex)
00 (Hex)
02 (Hex)
40 (Hex)
70 (Hex)
Reading Parameter data through User Assignable Registers:
In assigning query Voltage2 and Power Factor1 parameters were assigned to 0x 200 and
0x201(Table10) which will point to user assignable 3xregisters 0x200 and 0x202
(table9). So to read Voltage2 and PowerFactor1 data reading query should be as below.
79
Query:
01 (Hex)
04 (Hex)
02 (Hex)
00 (Hex)
00 (Hex)
04 (Hex) **
F0 (Hex)
71 (Hex)
Device Address
Function Code
Start Address High
Start Address Low
Number of Registers Hi
Number of Registers Lo
CRC Low
CRC High
Start Address High : Most significant 8 bits of starting address of User assignable register.
Start Address low :Least significant 8 bits of starting address of User assignable register.
Number of register Hi : Most significant 8 bits of Number of registers requested.
Number of register Lo : Least significant 8 bits of Number of registers requested.
**Note : Two consecutive 16 bit register represent one parameter.
Since two parameters are requested four registers are required
Response : (Volt2 = 219.30 / Power Factor1 = 1.0)
Device Address
Function Code
Byte count
Data Register-1High Byte
Data Register-1 Low Byte
Data Register-2 High Byte
Data Register-2 Low Byte
Data Register-3 High Byte
Data Register-3 Low Byte
Data Register-4 High Byte
Data Register-4 Low Byte
CRC Low
CRC High
01 (Hex)
04 (Hex)
08 (Hex)
43 (Hex)
5B (Hex)
4E (Hex)
04 (Hex)
3F (Hex)
80 (Hex)
00 (Hex)
00 (Hex)
79 (Hex)
3F (Hex)
80
}
}
Voltage 2 Data
Power Factor 1Data
(Starting Address)
User Assignable mapping Registers
User Assignable Data Registers
( 4X Registers Table10 )
(Starting Address) ( 3X Registers Table 9 )
0x200
Voltage 2 (0x0002)
0x200
0x200
(16 bit)
(16 bit)
0x201
Power Factor 1 (0x001E)
0x202
0x202
0x203
(16 bit)
(16 bit)
0x202
Wh Import (0x0048)
0x204
0x204
0x205
(16 bit)
(16 bit)
0x203
Frequency (0x0046)
0x206
0x206
0x207
0x212
Current 1 (0x0006)
0x224
0x224
(16 bit)
(16 bit)
0x213
VAh (0x0050)
0x226
0x226
0x227
(16 bit)
(16 bit)
(16 bit)
0x201
(16 bit)
0x225
To get the data through User assignable Register use following steps:
1) Assign starting addresses(Table3) of parameters of interest to a User assignable
mapping registers in a sequence in which they are to be accessed (see section
Assigning parameter to user assignable registers)
2) Once the parameters are mapped data can be acquired by using User assignable data
register  Starting address . i.e to access data of Voltage2, Power factor1,Wh import,
Frequency send query with starting address 0x200 with number of register 8 or
individually parameters can be accessed for example if current1 to be accessed use
starting address 0x212. (See section Reading Parameter data through User
Assignable Registers)
81
11. Phaser Diagram :
Capacitive
Inductive
Capacitive
Inductive
Connections Quadrant
Sign of
Active
Power ( P )
Sign of
Sign of
Inductive /
Reactive
Power
Capacitive
Power ( Q ) Factor ( PF )
Import
+P
+Q
Import
+P
-Q
Export
-P
+Q
Export
-P
-Q
Inductive means Current lags Voltage
Capacitive means Current leads Voltage
82
When MULTIS displays Active power ( P )with  +  ( positive signthe
) , connection is  Import  .
When MULTIS displays Active power ( P )with  -  ( negative signthe
) , connection is  Export  .
12. Installation
Mounting is by four side clamps, slide the side clamps through side slot till side clamp gets
firmly locked in a groove (Refer fig.) Consideration should be given to the space required
behind the instrument to allow for bends in the connection cables.
PANEL
SLIDE IN THIS DIRECTION AND LOCK
MULTIS Lm
As the front of the enclosure conforms to IP54 it is protected from water spray from all
directions, additional protection to the panel may be obtained by the use of an optional panel
gasket. The terminals at the rear of the product should be protected from liquids.
The MULTIS should be mounted in a reasonably stable ambient temperature and
0
where the operating temperature is within the range -10 to 55 C . Vibration should be kept
to a minimum and the product should not be mounted where it will be subjected to
excessive direct sunlight.
83
Caution
1.
2.
3.
In the interest of safety and functionality this product must be installed by
a qualified engineer, abiding by any local regulations.
Voltages dangerous to human life are present at some of the terminal
connections of this unit. Ensure that all supplies are de-energised before
attempting any connection or disconnection.
These products do not have internal fuses therefore external fuses must
be used to ensure safety under fault conditions.
12.1 EMC Installation Requirements
This product has been designed to meet the certification of the EU directives when installed
to a good code of practice for EMC in industrial environments, e.g.
1. Screened output and low signal input leads or have provision for fitting RF suppression
components, such as ferrite absorbers, line filters etc., in the event that RF fields
cause problems.
Note: It is good practice to install sensitive electronic instruments that are performing
critical functions, in EMC enclosures that protect against electrical interference which could
cause a disturbance in function.
2. Avoid routing leads alongside cables and products that are, or could be, a source of
interference.
3. To protect the product against permanent damage, surge transients must be limited to
2kV pk. It is good EMC practice to suppress differential surges to 2kV at the source.
The unit has been designed to automatically recover in the event of a high level of
transients. In extreme circumstances it may be necessary to temporarily disconnect the
auxiliary supply for a period of greater than 5 seconds to restore correct operation.
The Current inputs of these products are designed for connection in to systems via
Current Transformers only, where one side is grounded.
4. ESD precautions must be taken at all times when handling this product.
84
12.2 Case Dimension and Panel Cut Out
3.78
3.15
3.62
96mm
80mm
92mm
3.62
3.78
96mm
FRONT DISPLAY
AREA
PANEL CUTOUT
92mm
MAX PANEL THICKNESS 0.18,5mm
12.3 Wiring
Input connections are made directly to screw-type terminals with indirect wire pressure.
Numbering is clearly marked in the plastic moulding. Choice of cable should meet local
2
regulations. Terminal for both Current and Voltage inputs will accept upto 3mm x 2
diameter cables.
Note : It is recommended to use wire with lug for connection with meter.
12.4 Auxiliary Supply
MULTIS should ideally be powered from a dedicated supply, however it may be powered
from the signal source, provided the source remains within the limits of the chosen auxiliary
voltage.
12.5 Fusing
It is recommended that all voltage lines are fitted with 1 amp HRC fuses.
12.6 Earth/Ground Connections
For safety reasons, CT secondary connections should be grounded in accordance with
local regulations.
85
13. Connection Diagrams
3-PHASE 4-WIRE UNBALANCED LOAD
DIGITAL METERING SYSTEM
3-PHASE 3-WIRE UNBALANCED LOAD
DIGITAL METERING SYSTEM
2 5 8
2 5 8 11 1 3 4 6 7 9 13 14
3 4 6 7 9
L N
AUX
SUPPLY
L N
AUX
SUPPLY
L1
L2
L3
N
P1 S1
P1 S1
L
O
A
D
L1
L2
L3
N
P1 S1
P1 S1
P1 S1
L
O
A
D
14. Specification :
System
3 Phase 3 Wire / 4 Wire programmable at site
Inputs
Nominal input voltage
(Three wire and Four wire)
57.7VL-N to 277VL-N (100VL-L to 480 VL-L)
Max continuous input voltage
120% of Rated Value
Max short duration input voltage
Normal input voltage burden
2 x Raged Value
(1s application repeated 10 times at 10s intervals)
0.2VA apprax. per phase
Nominal input current
Max continuous input current
Nominal input current burden
1A / 5A AC rms programmable at site
120% of Rated Value
0.6VA approx. per phase
86
Max short duration current input
System CT primary values
20 x Rated Value (1s application repeated
5 times at 5 min. intervals)
Std. Values from 1 to 9999A
(1 or 5 Amp secondaries)
Auxiliary
Standard nominal Auxiliary
Supply voltages & Frequency
a.c. supply voltage tolerance
a.c. supply frequency range
a.c. supply burden
d.c. supply burden
110V AC/50 Hz , 230V AC/50 Hz ,380V AC/50 Hz ,
100 - 250V AC- DC (45-66Hz),
12 - 48V DC
+20 % / -15 % of Rated Value
45 to 66 Hz
4.5VA
3W
Operating Measuring Ranges
Voltage
Current
Frequency
Power Factor
5 .. 120 % of Rated Value
5 .. 120 % of Rated Value
40 .. 70 Hz
0.5 Lag ... 1 ... 0.8 Lead
Accuracy
Accuracy 1:
Voltage
Current
Frequency
Active Power
Re- Active Power
 0.5 % of range
 0.5 % of range
0.15% of mid frequency
 0.5 % of range
 0.5 % of range
87
Apparent Power
Active Energy
Re - Active Energy
 0.5 % of range
 1.0 % of range
 1.0 % of range
Apparant Energy
Power Factor
Angle
Analog Output
Total Harmonic Distortion
Neutral Current
 1.0 % of range
 1 % of Unity
 1 % of range
 1 % of Output end value
 4 % of range.
Accuracy 0.5:
Voltage
 0.5 % of range
Current
Frequency
Active Power
Re- Active Power
Apparent Power
Active Energy
 0.5 % of range
0.15% of mid frequency
 0.5 % of range
 0.5 % of range
 0.5 % of range
 0.5 % of range
Re - Active Energy
Apparant Energy
 0.5 % of range
 0.5 % of range
Power Factor
Angle
 1 % of Unity
 1 % of range
Analog Output
 1 % of Output end value
Total Harmonic Distortion
Neutral Current
1%
 4 % of range
88
Accuracy 0.2:
Voltage
 0.2 % of range
Current
Frequency
 0.2 % of range
0.15% of mid frequency
 0.2 % of range
 0.2 % of range
 0.2 % of range
 0.2 % of range
 0.2 % of range
 0.2 % of range
 1 % of Unity
 1 % of range
 1 % of Output end value
Active Power
Re- Active Power
Apparent Power
Active Energy
Re - Active Energy
Apparant Energy
Power Factor
Angle
Analog Output
Total Harmonic Distortion
Neutral Current
 4 % of range
Reference conditions for Accuracy :
Reference temperature
Input frequency
Input waveform
Auxiliary supply voltage
0
23 0C  2 C
50 or 60Hz  2%
Sinusoidal (distortion factor 0.005)
Rated Value  1 %
Auxiliary supply frequency
Voltage Range
Rated Value  1 %
50... 100% of Nominal Value.
60... 100% of Nominal Value for THD.
Current Range
10... 100% of Nominal Value.
20... 100% of Nominal Value for THD.
89
Power
cos / sin = 1
For Active / Reactive Power & Energy
10... 100% of Nominal Current &
50... 100% of Nominal Voltage.
Power Factor / Phase Angle
40... 100% of Nominal Current &
50... 100% of Nominal Voltage.
Nominal range of use of influence quantities for measurands
Voltage
Current
Input frequency
Temperature
Auxiliary supply voltage
Auxiliary supply frequency
Temperature Coefficient
(For Rated value range of use
0... 50 0C )
Error change due to variation of an
influence quantity
50 .. 120 % of Rated Value
10 .. 120 % of Rated Value
Rated Value  10 %
0 to 50 0C
Rated Value  10 %
Rated Value  10 %
0
0.025% / C for Voltage (50..120% of Rated Value)
0.05% / 0C for Current ( 10..120% of Rated Value )
2 * Error allowed for the reference
condition applied in the test.
Display
LED
Update
3 line 4 digits . Digit height 11mm
Approx. 1 seconds
Controls
User Interface
Two push buttons
90
Standards
EMC Immunity
IEC 61326
10V/m min-Level 3 industrial low level
electromagnetic radiation environment
IEC 61000-4-3.
Safety
IP for water & dust
IEC 61010-1 , Year 2001
IEC 60529
Isolation
Dielectric voltage withstand
test between circuits and
accessible surfaces
2.2 kV RMS 50 Hz for 1 minute
between all electrical circuits
Environmental
Operating temperature
Storage temperature
Relative humidity
Altitude
Warm up time
Shock
Vibration
Enclosure ( front only )
-10 to 55 0C
-20 to +65 0C
0 .. 90 % RH
2000m Max
3 minute (minimum)
15g in 3 planes
10 .. 55 Hz, 0.15mm amplitude
IP 54 as per IEC 60529
Enclosure
Style
96mm x 96mm DIN Quadratic
Material
Polycarbonate Housing ,
Self extinguish & non dripping as per UL 94 V-0
Screw-type terminals
< 80 mm
0.620 kg Approx.
Terminals
Depth
Weight
91
Pulse output Option ( 1 or 2 Relay ) :
Relay
Switching Voltage & Current
1NO + 1NC
240VDC , 5Amp.
Default Pulse rate Divisor
1 per Wh (up to 3600W),
1 per kWh (up to 3600kW),
1 per MWh (above 3600 kW)
Programmable on site
Pulse rate Divisors
10
1 per 10Wh (up to 3600W),
1 per 10kWh (up to 3600kW),
1 per 10MWh (above 3600 kW)
100
1 per 100Wh (up to 3600W),
1 per 100kWh (up to 3600kW),
1 per 100MWh (above 3600 kW)
1000
1 per 1000Wh (up to 3600W),
1 per 1000kWh (up to 3600kW),
1 per 1000MWh (above 3600 kW)
Pulse Duration
60ms , 100ms or 200ms
Note : Above conditions are also applicable for Reactive & Apparent Energy .
ModBus ( RS 485 ) Option :
Protocol
ModBus ( RS 485 )
Baud Rate
19200 , 9600 , 4800 or 2400
( Programmable )
Parity
Odd or Even, with 1 stop bit,
Or None with 1 or 2 stop bits
92
Analog Output Option :
Linear
0 ... 1mA dc into 0 - 2 kohm
Uni-directional, internally powered .
4 ... 20mA dc into 0 - 500 ohm
Uni-directional, internally powered.
15. Connection for Optional Pulse Output / RS 485
/ Analog Output ( rear view of MULTIS ) :
1. One Pulse Output (One Limit Output)
N/O N/C COM
Relay 1
2. Two Pulse Output ( Two Limit Output)
N/O N/C COM
Relay 1
N/O N/C COM
Relay 2
93
3. RS 485 Output
A Gnd
RS 485
A Gnd
RS 485
4. Two Analog Output
Gnd A1 A2 Gnd
4 -20 mA
5. One Pulse (One Limit) + RS 485 Output
N/O N/C COM
Relay 2
94
6. One Pulse (One Limit) + Two Analog Output
Gnd A1 A2 Gnd
0 - 1mA
N/O N/C COM
Relay 2
7. RS 485 + Two Analog Output
Gnd A1 A2 Gnd
4 -20 mA
A Gnd
RS 485
8. RS 485 Output + One Pulse (One Limit) + Two Analog Output
Gnd A1 A2 Gnd
0 - 1mA
N/O N/C COM
Relay 2
95
A Gnd
RS 485
9. Two Pulse (Two Limit) + RS 485 Output
N/O N/C COM
Relay 1
N/O N/C COM
Relay 2
A Gnd
RS 485
!
CAUTION!
Read & Understand this manual Before using the Instruments
Installation Instructions:
Multifunction Meter is ready to fit on the Panel by using fixing clamp provided with instruments.
Before Installation please make proper cut out on the panel as per sizes given in the
INSTALLATION CUT OUT. Please refer MOUNTING POSITION & CONNECTION DIA.
The connection at rear of the case should be free from liquids. Consideration should be given
to the space required behind the unit to allow the bends in the connecting cable.
Note: Ensure proper grounding of panel before installtion.
Indoor Use:
The unit should not be mounted where it can be subjected to excessive direct sunlight and
vibration should be kept minimum. Connection wires should be sized to comply with local
regulations and should be terminated on to tags suitable for screw connection.
Measurement Category: CAT III 300V. Pollution Degree 2.
Ventilation Requirement: This product is designed to use on Panel, no need to provide
extra ventilation for the same.
96
Wiring:
Input Connections are made directly to screw -type terminals with indirect wire pressure.
Numbering is clearly marked in the plastic moulding. Choice of cable should meet local
regulations. Terminals for both voltage and current inputs will accept upto 3mm2x2
diameter cables.
Note:
1)It is recommended to use wire with lug for connection with meter.
2)The instrument is not equipped with an integrated circuit breaker. During installation
check that a labeled switch is installed and that it can be easily be reached by operator.
3)The instruments must be taken out of service if safe operation is no longer possible
(eg. visible damage) in this case all the connection must be switched off.
Specification:
Disconnecting device used must meet the relevant requirements of IEC-60947-1 &
IEC-60947-3.
For Aux.: At least 1.5 times of applied Power supply.
For Measuring Input: At least 1.5 times of measuring inputs.
(Switching time of the device should be <0.1sec. for Aux. & I/P both.)
Cleaning & Maintenance:
No Cleaning and Maintenance is required beyond periodically checking of terminal area &
ensuring the connection remain tight.
Marking & Rating: Side Label Shows function, electrical rating & connection diagram.
Explanation of Symbols :
CAT III
CE Conformity mark
Caution! General Hazard Point.
Read the operating instructions
Attention Danger to life! Ensure that all leads
are free of potential when Connecting them
97
Measurement category Cat III for current
and voltage Inputs and Power Supply
Three phase alternating current
Note:
98
Note:
99
Item No:2-60-006-00-00507_Rev A_4/14
The Information contained in these installation instructions is for use only by installers trained to make electrical power
installations and is intended to describe the correct method of installation for this product.
It is the user's responsibility to determine the suitability of the installation method in the user's field conditions.
Socomec India Private Limited
756, Pace City II, Sector-37,
Gurgaon  122001 (Haryana) India
Tel. 0124-4562700
100