DIGITAL INDICATOR WITH RELAY OUTPUTS
MODEL:                  AK-62
DESCRIPTION
                                                                            The Controller has one display windows on the front panel for
The AK-62 is a fully configurable microcontroller based Digital             indication of Process value and the set-point values. Two LED
Indicating controller in a compact, rugged & reliable execution. The        indications show the status of the two control Relays.
instrument has a four-digit red LED seven-segment digital display on
the front panel to continuously indicate the real time process value
and other menu options.                                                     CONTROL KEYS
The Process value display can indicate any scale range between -999         The instrument has three keys on the front panel, the functions of
to +9999 units The instrument has non-volatile memory (i.e., in case        which are described below:
of power failure, the set points and other settings are retained in
memory and the indication and control actions resume after power is                         The PROGRAM key is the central co-ordinating key for
restored).                                                                    PROG          accessing the settings of the instrument. Pressing this Key, one
                                                                                            can sequentially view, change and save the parameters such
The instrument accepts a 4 to 20 mA DC current loop signal at the                           as Zero & Span settings, Decimal Points, Relay Set-points for
input. An auxillary power supply output of 24 V DC is available at the                      control action, Hysterisis, etc.
terminals. The instrument may therefore be used in either two-wire or
four-wire configuration. [The instrument is calibrated as specified. This                   The INC or Incrementing key allows the operator to select the
calibration may be changed by the end-user by following the                                 numeral in the digit being set. The digit will sequentially display
instructions under the “CONFIGURATION / CALIBRATION” section].              INC             0, 1, 2….9 on each pressing of the INC key. This may be used
The AK-62 provides two Relay outputs, the set points of which may                           to set the Zero/Span and Set-points of the displays.
be set through the Membrane Keypad on the front panel [see
CONFIGURATION – INITIAL SETTINGS section]. The instrument also                              The DEC or Decrementing key allows the operator to select the
provides an RS-485 communication signal on MODBUS RTU                                       numeral in the digit being set. The digit will sequentially display
(optional). It operates on universal AC power supply (90 to 270 V AC,       DEC             9, 8, 7….0 on each pressing of the DEC key. This may be used
50/60 Hz) and is offered in standard 1/8 DIN panel-mount execution.                         to set the Zero/Span and Set-points of the displays.
INSTALLATION
The instrument should be mounted in the cutout (44 x 92 mm) on the          TERMINAL DIAGRAM
panel using the mounting clamps provided. All inter-connections to
the instrument should be made with strong multi-strand wire of the
order of 2.5 sq.mm. The ends of the wires should be properly ferruled                          UPPER TERMINAL BLOCK
and suitably terminated.                                                               1       2      3       4       5       6      7         8
The cables carrying the Input Signal should be properly isolated from                  L      N       E       +       -       +      -
the Power Line cables, to prevent any electromagnetic interference or                 90–270 VAC, 50 hz                      4 to 20mA          X
                                                                                                             24 V DC
noise-related malfunctions from the Mains Power Line. Use of                          Universal AC power                         I/P
shielded twisted pair cable is recommended for the input signal. It is
essential that the instrument be earthed to a proper grounding point
                                                                                               LOWER TERMINAL BLOCK
before connecting the power supply. The voltage between the Earth
and Neutral terminals should be negligible (Approx. 1 V AC).                           9      10      11      12      13      14       15      16
                                                                                       +       -      NO       C      NC      NO       C       NC
After connecting the input signal to a suitable source, the power may                 4 to 20 mA
be switched ON. The instrument must first be configured and then                                           RELAY–2                 RELAY–1
                                                                                          O/P
calibrated (see sections below).
                                                                                                 TERMINAL DETAILS
OPERATION & SETTINGS
                                                                            TERMINAL         TERMINAL
The front panel of the AK-62 Digital Indicating Controller is as shown                                             NOTATION                 DETAILS
                                                                             BLOCK              NO.
below :                                                                                          1                  L (Line)             90 to 270 VAC,
                                                                                                 2                 N (Neutral)             50 / 60 Hz
                                                                                                 3                  E (Earth)           AC POWER SUPPLY
                                                                                                 4                      +
                                                                              UPPER                                                          24 V DC
                                                                                                 5                      -
                                                                                                 6                      +               4 to 20 mA DC
                                                                                                 7                      -                     I/P
                                                                                                 8                      X                  No Conn
                                                                                                 9                      +               4 to 20 mA DC
                                                                                                10                      -                     O/P
                                                                                                11                     NO
                                                                                                12                      C                   RELAY – 2
                                                                              LOWER
                                                                                                13                     NC
                                                                                                14                     NO
                                                                                                15                      C                   RELAY – 1
                                                                                                16                     NC
CONFIGURATION (INITIAL SETTINGS)
After the instrument is properly connected to the mains power supply and input signal, the Initial Settings of the Digital Indicating Controller must
first be done. Only after the Initial Settings are completed, the instrument can be calibrated. An external current source is NOT REQUIRED for
calibration. During Calibration, the Display will “Time-Out” after 5 seconds (i.e., if no key is pressed for 5 seconds, the displays will return to their
“normal” states). The following is the sequence of settings to be carried out on the Controller before first use :
All settings to be done using Increment () and Decrement () keys.
             KEY                                ALTERNATING
                              DISPLAY                                                                FUNCTION
          PRESSED                                 DISPLAY
            Press
         Decrement
           () key
         together for
          2 seconds
                                                                        Enter the number of Relays actually being used in the
                                                                        application. [Options are 0/1/2].
            PROG
                                  Pt                  0002              This feature may be used to temporarily disable the use of
             P
                                                                        one or more Relays in the instrument. e.g., if the User needs
                                                                        to use both Relays, select 2.
                                                                        This indicates an Analog Input signal (4 to 20 mA DC in this case).
            PROG
                                SEn                   U – I             The input signal is fixed for this application and hence no selection is
             P
                                                                        available.
            PROG                                                        Set the Decimal Position. [Applicable for Current Input
                                 dP                    0000
             P                                                          only]..
                                                                        The desired Zero (lower) range setting for the process
             PROG
                               RngL                   0000              being measured may be set using INC and DEC keys.
              P
                                                                        The minimum Zero level possible is –999.
                                                                        The desired Span (upper) range setting for the process
            PROG
                               RngH                   5000              being measured / controlled may be set using INC and
             P
                                                                        DEC keys. The maximum Span level possible is 9999.
            PROG                                                        On/Off or PID control action selection
                                Con                      On
             P                                                          (“On” to be selected for your application).
            PROG
                                S – Id                0001              Slave Identity number (range is from 0001 to 0255)
             P
            PROG
                              ASHE              (process value)         Normal process value
             P
            PROG                                 Default factory        Adjust the desired Set-Point for Relay-1 using INC and
                                Set1
             P                                      setting             DEC keys. [Range is –999 to 9999].
                                                                        Process Value Hysterisis : Adjust the desired Hysterisis
            PROG
                                HY1                   0001              for Relay-1 using INC and DEC keys
             P
                                                                        [e.g. 0010 for a hysterisis of 10 degrees].
            PROG                                                        Adjust the desired Control Logic for Relay-1 using INC
                               LOG1                     h I
             P                                                          and DEC keys. [Options are HI / LO].
            PROG                                 Default factory        Adjust the desired Set-Point for Relay-2 using INC and
                                Set2
             P                                      setting             DEC keys. [Range is –999 to 9999].
                                                                        Process Value Hysterisis : Adjust the desired Hysterisis
            PROG
                                hY2                   0001              for Relay-2 using INC and DEC keys
             P
                                                                        [e.g. 0010 for a hysterisis of 10 degrees].
            PROG                                                        Adjust the desired Control Logic for Relay-2 using INC
                               LOG2                     h I
             P                                                          and DEC keys. [Options are HI / LO].
            PROG
                              ASHE              (process value)         (if Input Signal is connected)
             P