Horizon Headwall
Horizon Headwall
Horizon®
Headwall
System
From Hill-Rom
man043ra
Second Edition
Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 - 10
Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 - 11
Line Voltage Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 - 12
Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 - 12
Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 - 13
Ground Jack Receptacle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 - 14
Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 - 14
Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 - 15
Telephone Receptacle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 - 16
Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 - 16
Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 - 17
Night Light or Chart Light Bulb . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 - 18
Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 - 18
Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 - 19
Chart Light Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 - 20
Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 - 20
Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 - 21
Circuit Breaker (Standard/Emergency Power) . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 - 22
Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 - 22
Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 - 23
Low Voltage Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 - 24
Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 - 24
Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 - 25
Timed Light Switch and Toggle Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 - 27
Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 - 27
Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 - 28
In-Warranty Exchanges . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 - 6
Out-of-Warranty Exchanges . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 - 6
Recommended Spare Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 - 7
Chase Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 - 8
Chase Assembly (Isolated Power) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 - 10
Chase Panels and Trim . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 - 12
Light Raceway . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 - 14
Gas Raceway. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 - 16
Bottom Raceway. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 - 18
Raceway Fascia and Gas Excluder . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 - 22
Chase Breaker Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 - 24
Timed Light Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 - 28
Specialite Patient Light Provision (Standard/Emergency) . . . . . . . . . . . . . . . . . . 5 - 30
Nurse Call Backbox . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 - 32
Chaseless Raceway—Standard and Isolated Power . . . . . . . . . . . . . . . . . . . . . . . 5 - 34
TeleMate/Phone Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 - 36
Duplex Outlet Receptacles . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 - 38
Single Outlet Receptacles . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 - 40
Line Voltage Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 - 42
Ground Receptacles . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 - 44
Night and Chart Lights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 - 46
Hose Panels. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 - 48
Manifold Tree . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 - 52
Low Voltage Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 - 54
SideCom Communication System Receptacle . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 - 56
Low Voltage Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 - 58
Disinfection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 - 3
Preventive Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 - 4
Preventive Maintenance Schedule . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 - 4
Preventive Maintenance Checklist . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 - 6
Tool and Supply Requirements. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 - 7
Line Isolation Monitor Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 - 7
Installation and Post Installation Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 - 7
Chapter 7: Accessories
NOTES:
Chapter Contents
NOTES:
Chapter 1. Introduction
You are currently reading chapter 1. Chapter 1 is an introduction to this manual
and to the features and capabilities of the Horizon Headwall System. The
operational specifications for the unit, label location, and safety tips are also
included.
1 Chapter 1: Introduction
Chapter 7. Accessories
This revision of the Horizon Headwall System Service Manual does not
contain any additional information for accessories.
1 Chapter 1: Introduction
General Information
Ceiling line
Vertical
chase
Light raceway
Gas raceway
Movable
gas
Gas outlet
hose
panel
Bottom raceway
Floor line
m043a027
For over 30 years, Hill-Rom has been producing products that aid in the
efficient care of patients and reduce nursing burdens for many facets of
healthcare. Today, with improvements in technology and changes in the way
healthcare is delivered, Hill-Rom is designing products to continuously meet
the changing needs of the healthcare industry.
System Features
The Horizon Headwall System maintains flexibility in hospital room services,
quickly and at a low cost. The system offers:
• Low voltage power service
• Normal power service
• Emergency power service
• Multiple variable gas outlets
• Flexible storage cabinetry
• Reduced clutter around the bed and placement of equipment at convenient
working levels for staff
• Variable total length to meet requirements of larger open areas
• Flexibility for the hospital room to be upgraded to a more sophisticated
level of care
• Adaptability for new services without the need to break into walls or
reconstruct the room
1 Chapter 1: Introduction
Specifications
The following tables contain specifications of the Horizon Headwall System.
Feature Dimension
Depth 4 1/2" (114 mm)
Width 13" (330 mm)
Height Adjustable from ceiling to 10"
(254 mm) above floor
Feature Dimension
Depth 2 9/16" (65 mm)
Width 36", 48", 60", 84", 96", and
108", variable up to 336"
(914 mm, 1219 mm, 1524 mm,
2133 mm, 2438 mm,
2743 mm, and 8534 mm)
Height 6 1/2" (165 mm)
Panel depth 3/4" (19.1 mm)
Description Specification
Hospital grade receptacle Three pole
Three wire grounded
Hospital grade is indicated by
green dot on the face of the
receptacle.
Single phase 2 wires plus ground
Three phase 3 wires plus ground
Voltage 125V AC
Amperage 20 amp
Receptacle color Ivory = standard power duplex
Red = emergency power
duplex (critical branch)
Black = locking single
Orange = isolated ground
1 Chapter 1: Introduction
Description Specification
Check valves DISS indexed
Copper tubing ASTM-B-88
Inner diameter–oxygen and air tubing 1/2" (12.7 mm)
Inner diameter–vacuum tubing 3/4" (19.1 mm)
Brazing Silver alloy
o o
Minimum melting point–brazing 1000 F (538 C)
Pressure test 150 psi (1034.2 kPa)
Pressure test certification MFPA-56F and or contractual
documents
UL Classification
1 Chapter 1: Introduction
Model Identification
SHOCK HAZARD:
Locate the involved power supply circuit breaker panel. Set the involved
circuit breaker (A) to OFF (see figure 2-1 on page 2-11). Failure to
follow this procedure could cause serious injury and damage to the
equipment.
SHOCK HAZARD:
Locate the involved building standard/emergency circuit breaker panel.
Set the involved circuit breaker (A) to OFF (see figure 2-1 on page
2-11). Lock out and tag out the breaker. Failure to follow this procedure
could cause serious injury and damage to the equipment.
SHOCK HAZARD:
Use care when checking live voltages. Do not touch live terminals,
wires, and ground. Failure to use caution will cause serious electrical
shock injury.
WARNING:
Only facility authorized maintenance personnel should troubleshoot the
Horizon Headwall System.
WARNING:
When following these procedures you must adhere to the “Infection
Control Policies and Procedures” outlined in the Exposure Control Plan.
Not following these procedures could cause the spread of infection.
CAUTION:
Do not use harsh cleaners, solvents, or detergents.
1 Chapter 1: Introduction
m043a042
m043a048
m043a047
m043a049
1 Chapter 1: Introduction
NOTES:
Getting Started . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 - 3
Initial Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 - 3
Function Checks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 - 4
Final Actions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 - 5
Bed Receptacle or Indicator Is Inoperative. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 - 6
Chart Light Does Not Come On . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 - 7
Night Light Does Not Come On . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 - 8
Dimmer Switch Will Not Operate The Light . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 - 9
Line Voltage Switch Will Not Operate Attached Device. . . . . . . . . . . . . . . . . . . 2 - 10
Duplex Electrical Receptacle—Standard/Emergency Is Inoperative . . . . . . . . . . 2 - 12
Indirect/Read Light (Low Voltage Controller) Will Not Function. . . . . . . . . . . . 2 - 13
Timed Light Switch and Toggle Switch Do Not Operate Properly . . . . . . . . . . . 2 - 15
Circuit Breaker Is Inoperative. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 - 16
Specialite Patient Light Provision (Standard Power) Does Not Come On. . . . . . 2 - 17
NOTES:
Getting Started
Begin each procedure in this chapter with step 1. Follow the sequence outlined
(each step assumes the previous steps are correct). Each step is the normal
operational event of the product and can be confirmed by answering Y (yes) or
N (no) to the statement. Your response will lead to another step in the
procedure, a repair analysis procedure (RAP), or a component replacement. If
more than one component is listed, replace them in the order given.
2
Start with Initial Actions to begin gathering information about the problem.
Perform the Final Actions after the Function Checks to verify the repair.
WARNING:
Only facility authorized maintenance personnel should troubleshoot the
Horizon Headwall System.
Initial Actions
Initial Actions are used to gather information from the operators concerning
problems with the Horizon Headwall System. Note symptoms or other
information concerning the problem that the operator identifies. This
information helps identify the probable cause.
2. Ask that person to demonstrate or explain the problem. The problem can be
duplicated.
Yes No
↓ → Go to “Function Checks” on page 2-4.
Function Checks
1. Initial actions have been performed.
Yes No
↓ → Go to “Initial Actions” on page 2-3.
2. The hospital unit is plugged into an appropriate power source, and the
switch is turned on.
Yes No
↓ → Plug the unit into an appropriate power source, and turn on the
switch.
Final Actions
1. Complete the required preventive maintenance procedures. See
“Preventive Maintenance Schedule” on page 6-4.
3. The Specialite fixture moves freely when lifted from the bottom.
Yes No
↓ → Go to step 6.
5. The voltage reads good, on a low impedance voltage tester, between the
short slot and the ground terminal of the receptacle.
Yes No
↓ → Go to step 8.
8. The voltage reads good, on a low impedance voltage tester, between the
short slot and the long slot in the receptacle.
Yes No
↓ → Go to step 9.
5. Replace the night light bulb. See “Night Light or Chart Light Bulb” on
page 4-18.
SHOCK HAZARD:
Use care when checking live voltages. Do not touch live terminals,
wires, and ground. Failure to use caution will cause serious electrical
shock injury.
7. Continuity is present in the wires between the circuit breaker and the night
light.
Yes No
↓ → Repair or replace the wiring.
SHOCK HAZARD:
Use care when checking for live voltages. Do not touch live terminals,
wires, and ground. Failure to use caution will cause serious electrical
shock injury.
7. Continuity is present in the wires between the circuit breaker and the
dimmer switch.
Yes No
↓ → Repair or replace the wires.
SHOCK HAZARD:
Use care when checking live voltages. Do not touch live terminals,
wires, and ground. Failure to use caution will cause serious electrical
2 shock injury.
SHOCK HAZARD:
Locate the involved building standard/emergency circuit breaker panel.
Set the involved circuit breaker (A) to OFF (see figure 2-1 on page
2-11). Lock out and tag out the breaker. Failure to follow this procedure
could cause serious injury and damage to the equipment.
a. Set the Horizon Headwall System circuit breaker (lower panel) to the
OFF position.
b. Remove the wires from the switch terminals.
c. Place the removed switch in the ON position.
3. The line voltage switch has continuity between the power terminals.
Yes No
↓ → Replace the switch with a new switch. See “Line Voltage
Switch” on page 4-12.
5. Reset the applicable Horizon Headwall System circuit breaker back to the
ON position.
SHOCK HAZARD:
Use care when checking live voltages. Do not touch live terminals,
wires, and ground. Failure to use caution will cause serious electrical
shock injury.
7. Voltage is present between the lug and terminal of the circuit breaker.
2
Yes No
↓ → Go to “Circuit Breaker Is Inoperative” on page 2-16.
8. Continuity is present in the wires between the circuit breaker and the line
voltage switch.
Yes No
↓ → Repair or replace the wiring.
m043a028
SHOCK HAZARD:
Use care when checking live voltages. Do not touch live terminals,
2 wires, and ground. Failure to use caution will cause serious electrical
shock injury.
5. The voltage reads good, on a low impedance voltage tester, between the
short slot and the ground terminal. Also, the voltage reads good between
the short slot and long slot.
Yes No
↓ → Go to step 7.
3. Press the indirect/read light switch momentarily, and release it. The
indirect light turns ON.
Yes No
↓ → Go to step 6.
4. Press the indirect/read light switch momentarily, and release it. The read
light turns ON, and the indirect light turns OFF.
Yes No
↓ → Go to step 10.
6. The voltmeter reads good, on a low impedance voltage tester, from the
yellow wire to the ground (see figure 2-2 on page 2-14).
Yes No
↓ → Go to step 8.
8. The voltmeter reads 11V DC from the red wire to the ground.
Yes No
↓ → Replace the low voltage controller. See “Low Voltage
Controller” on page 4-24.
10. The voltmeter reads good, on a low impedance voltage tester, from the
white wire to the ground.
Yes No
↓ → Go to step 12.
12. The voltmeter reads 11V DC from the blue wire to the ground.
Yes No
↓ → Replace the low voltage controller (see figure 4-12 on page
4-25).
13. The problem is in the indirect/read light switch. Refer to the Specialite
2 Patient Light Service Manual.
m043a040
3. Place the toggle switch in the ON position. The lights turn ON.
Yes No
↓ → Replace the toggle switch. See “Timed Light Switch and Toggle
Switch” on page 4-27.
4. Place the toggle switch in the OFF position. The lights turn OFF at the
setting of the timer (0–15 minutes).
Yes No
↓ → Replace the timed light switch. See “Timed Light Switch and
Toggle Switch” on page 4-27.
SHOCK HAZARD:
Locate the involved building standard/emergency circuit breaker panel.
Set the involved circuit breaker (A) to OFF (see figure 2-1 on page
2-11). Lock out and tag out the breaker. Failure to follow this procedure
could cause serious injury and damage to the equipment.
d. Continuity exists in the wires from the circuit breaker to the equipment.
Yes No
↓ → Replace or repair the wires from the circuit breaker to the
equipment.
SHOCK HAZARD:
Locate the involved power supply circuit breaker panel. Set the involved
circuit breaker (A) to OFF (see figure 2-1 on page 2-11). Failure to
follow this procedure could cause serious injury and damage to the
equipment.
7. Refer to the Specialite Service Manual to diagnose and repair the Specialite
Patient Light.
NOTES:
Chapter Contents
Voltage Distribution . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 - 3
Electrical Switches . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 - 5
Specialite Patient Light . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 - 8
Low Voltage Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 - 9
3
Chase Theory . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 - 10
Chase. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 - 10
Medical Gases. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 - 10
Standard Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 - 10
Emergency Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 - 10
Communications/Low Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 - 10
NOTES:
Voltage Distribution
Communication compartment
Standard/emergency power
compartment
Emergency/standard power
compartment
Emergency/standard
power breaker panel
Gas raceway
Bottom raceway
Vertical chase
Ground bar
10 AWG ground
m043a025
Communication
Standard/emergency power
Raceway ground terminal Emergency/standard power
10 AWG ground Reference ground
Junction box
Standard power
Emergency/standard
power breaker panel
Gas raceway
Standard/emergency
power breaker panel
6 AWG reference ground
Bottom raceway
Ground bar
m043a026
Electrical Switches
m043a021
m043a022
m043a023
m043a024
m043a040
Chase Theory
Chase
The vertical service chase carries medical gases, standard power, emergency
power, and communications cabling from the ceiling to multiple wall-mounted
raceways. The vertical chase consists of three modules: a power distribution
wireway, an expansion module to accommodate varying ceiling heights, and a
main junction box module for incoming electrical services.
The vertical chase will normally have an upper and a lower circuit breaker box
attached. The upper circuit breaker box supplies emergency power. The lower
circuit breaker supplies standard power.
3 Medical Gases
One-half inch (12.7 mm) inside diameter copper tubing carries the oxygen and
air. Three-quarter inch (190 mm) inside diameter copper tubing carries the
vacuum.
Standard Power
Standard power is available through the lower circuit breaker box and into all
three raceways. Ivory receptacles are used for the standard power outlets.
Emergency Power
Emergency power is available through the upper circuit breaker box and into
all of the raceways. Red receptacles are used for the emergency power outlets.
Communications/Low Voltage
Communications are carried by low voltage.
Chapter Contents
Duplex Receptacle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 - 3
Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 - 3
Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 - 4
Bed Receptacle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 - 6
Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 - 6
Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 - 7
Single Receptacle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 - 8 4
Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 - 8
Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 - 9
Dimmer Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 - 10
Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 - 10
Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 - 11
Line Voltage Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 - 12
Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 - 12
Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 - 13
Ground Jack Receptacle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 - 14
Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 - 14
Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 - 15
Telephone Receptacle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 - 16
Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 - 16
Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 - 17
Removal
SHOCK HAZARD:
Locate the involved power supply circuit breaker panel. Set the involved
circuit breaker (A) to OFF (see figure 4-1 on page 4-3). Failure to follow
this procedure could cause serious injury and damage to the
equipment.
4
A
m043a028
1. Turn off power at the appropriate circuit breaker (A) (lower breaker box
for the ivory receptacle or upper breaker box for the red receptacle), and
tag the breaker box out-of-service.
2. Remove the screws (B) from the duplex receptacle faceplate (C) (see figure
4-2 on page 4-4).
5. Pull the receptacle (A) out of the opening in the device plate.
Raceway
4
A
m043a029
Replacement
1. Replace the color coded wires at their original terminals (see figure 4-2 on
page 4-4).
6. Install the faceplate (C) onto the device plate, and tighten the screws (B).
7. Remove the out-of-service tags, and turn the circuit breaker on.
Removal
SHOCK HAZARD:
Locate the involved power supply circuit breaker panel. Set the involved
circuit breaker (A) to OFF (see figure 4-1 on page 4-3). Failure to follow
this procedure could cause serious injury and damage to the
equipment.
1. Locate the bed receptacle circuit breaker panel. Reset the circuit breaker
(A) to the OFF position, and tag the breaker box out-of-service.
NOTE:
Find the standard breaker box just above the lower raceway (A). The standard
breaker box mounts on the vertical chase.
2. Remove the faceplate screws and the faceplate (D) (see figure 4-3 on page
4-7).
5. Loosen the receptacle screws (C) until the receptacles (B) can be lifted
away from the device plate.
8. Remove the power supply and indicator wires from the receptacle (B).
B
C
D
m043a030
Replacement 4
1. Place the indicator and power supply wires onto the receptacle terminal
screws.
3. Align the receptacle (B) with the retaining holes in the device plate.
4. Install and tighten the two receptacle-retaining fasteners into the device
plate.
5. Insert the faceplate (D) and indicator (E) onto the device plate.
6. Install and tighten the two faceplate screws to secure the faceplate (D) on
the device plate.
7. Set the circuit breaker to the ON position, test the receptacle (B) for power,
and remove the out-of-tag service tags.
Removal
SHOCK HAZARD:
Locate the involved power supply circuit breaker panel. Set the involved
circuit breaker (A) to OFF (see figure 4-1 on page 4-3). Failure to follow
this procedure could cause serious injury and damage to the
equipment.
1. Locate the circuit breaker (A), set the involved breaker to the OFF position,
and tag the breaker box out-of-service.
2. Remove the screws (B) and the faceplate (C) from the single receptacle
device plate (see figure 4-4 on page 4-9).
3. Loosen the receptacle screws (D) until the receptacle (A) will lift away
from the device plate.
4 5. Unscrew the wire terminal screws just enough to remove the wires from
the receptacle (A).
Raceway
B
m043a031
Replacement
1. Install the color coded wires to the proper terminals on the new receptacle
4
(A).
3. Align the receptacle screws (D) with the holes in the device plate, and
install the receptacle (A) on the device plate.
4. Install the faceplate (C) and the screws (B) on the device plate.
5. Set the circuit breaker to the ON position, and remove the out-of-service
tags.
6. Test the receptacle (A) for power. See “Duplex Electrical Receptacle—
Standard/Emergency Is Inoperative” on page 2-12.
Removal
SHOCK HAZARD:
Locate the involved power supply circuit breaker panel. Set the involved
circuit breaker (A) to OFF (see figure 4-1 on page 4-3). Failure to follow
this procedure could cause serious injury and damage to the
equipment.
1. Locate the dimmer switch circuit breaker (A) in the standard power (lower
panel) breaker panel box, set it to the OFF position, and tag the breaker box
out-of-service.
3. Remove the faceplate screws (D) and the faceplate (B) (see figure 4-5 on
page 4-11).
4. Take out the switch device plate retaining screws (E), and remove the
switch (A).
4 5. Record the positions of the color coded wires on the switch terminals.
6. Loosen the terminal screws on the switch, and remove the wires from the
switch (A).
Raceway
C (Supplied with
E dimmer switch)
Replacement
m043a032
4
1. Place the color coded wires in their original positions on the switch.
3. Install the switch (A) on the device plate, and tighten the retaining screws
(E).
4. Place the faceplate (B) on the device plate, and install the retaining screws
(D).
6. Set the switch circuit breaker to the ON position, and test to see if the
switch (A) is working. See “Dimmer Switch Will Not Operate The Light”
on page 2-9.
Removal
SHOCK HAZARD:
Locate the involved power supply circuit breaker panel. Set the involved
circuit breaker (A) to OFF (see figure 4-1 on page 4-3). Failure to follow
this procedure could cause serious injury and damage to the
equipment.
1. Locate the line voltage switch circuit breaker (A) in the standard power
breaker panel (lower panel), set it to the OFF position, and tag the breaker
box out-of-service.
2. Remove the faceplate screws (C) and the faceplate (B) (see figure 4-6 on
page 4-13).
3. Take out the switch device plate retaining screws (D), and remove the
switch (A).
4. Record the positions of the color coded wires on the switch terminals.
4 5. Loosen the terminal screws on the switch (A) and remove the wires from
the switch (A).
Raceway
C
D
m043a033
Replacement 4
1. Place the color coded wires in their original positions on the switch (A).
3. Install the switch (A) on the device plate. Install and tighten the retaining
screws (D).
4. Place the faceplate (B) on the device plate, and install the retaining screws
(C).
5. Set the circuit breaker to the ON position, remove the out-of-service tags,
and test the operation of the switch (A). See “Line Voltage Switch Will Not
Operate Attached Device” on page 2-10.
Removal
1. Remove the screws (C) and the faceplate (B) from the ground jack
receptacle device plate (see figure 4-7 on page 4-14).
2. Loosen the ground mounting plate screws (D) until the mounting plate (E)
will lift away from the device plate.
3. Unscrew the ground wire fastener just enough to remove the ground wire
from the receptacle (A).
4. Remove the attaching screws (D) and lift the ground receptacle (A) from
the ground mounting plate.
Raceway
4
E
A
C B
m043a034
Replacement
1. Install the ground receptacle (A) into the ground mounting plate. Place the
ground wire on the terminal, and tighten the fastener to hold it in place.
2. Align the ground plate screws with the holes in the device plate, and install
the ground plate on the device plate.
3. Install the faceplate (B) and screws (C) on the device plate.
Removal
1. Remove the screws (B) and the telemate faceplate (C) from the device
plate (see figure 4-8 on page 4-16).
2. Loosen the phone plate screws (A) until the phone plate will lift away from
the device plate.
3. Remove the telephone interface connector from the back of the modular
phone receptacle (D).
4. Remove the attaching screws (A) and lift the modular phone receptacle
from the phone plate.
Raceway
4
A
C
D
m043a035
Replacement
1. Install a modular phone receptacle (D) into the phone plate.
2. Place the phone wire interface into the back of the modular phone
receptacle (D).
3. Align the phone plate screws (A) with the holes in the device plate, and
install the phone plate on the device plate.
4. Install the TeleMate faceplate (C) and screws (B) on the device plate.
5. Check the modular phone receptacle (D) for correct phone function.
Removal
SHOCK HAZARD:
Locate the involved power supply circuit breaker panel. Set the involved
circuit breaker (A) to OFF (see figure 4-1 on page 4-3). Failure to follow
this procedure could cause serious injury and damage to the
equipment.
1. Locate the standard power circuit breaker (lower panel), and set the
involved breaker to the OFF position.
2. Remove the screws (D) and the chart or night light faceplate (E) from the
device plate (see figure 4-9 on page 4-19).
3. Remove the lock screws (C) and lock plates (F) from the night light
housing (I).
4. Take the device plate attaching screws (G) from the backbox, and remove
the device plate (H) from the raceway (K).
4 5. Remove the light bulb (A) from the fixture (B).
J C
I
D
H
G
F
E
m043a036 4
Replacement
1. Install the new light bulb (A) in the fixture (B).
2. Insert the device plate attaching screws (G) and the device plate (H) on the
backbox.
3. Install the lock plate (F), device plate (H), and attaching screws (C) on the
chart or night light housing (I).
4. Install the screws (D) and faceplate (E) on the device plate (H).
Removal
SHOCK HAZARD:
Locate the involved power supply circuit breaker panel. Set the involved
circuit breaker (A) to OFF (see figure 4-1 on page 4-3). Failure to follow
this procedure could cause serious injury and damage to the
equipment.
1. Locate the standard power circuit breaker (lower panel), set the involved
breaker to the OFF position, and tag the breaker box out-of-service.
2. Remove the screws (F) and the chart light faceplate (G) from the device
plate (J) (see figure 4-10 on page 4-21).
3. Take off the hex nut (K) from the base of the switch (C).
4. Remove the two retaining screws from the chart light switch (C).
5. Lift the switch (C) away from the device plate (J).
4 6. Remove the switch (C) wires from the power supply connectors.
A
B
C
D
K
F
J
I Screw
H
G
Replacement
m043a043
4
1. Install the power wires on the switch (C).
2. Insert the switch (C) into the device plate (J) and install the attaching
screws (I).
3. Install the hex nut (K) on the base of the switch shaft.
4. Install the screws (F) and faceplate (G) on the device plate (J).
5. Set the circuit breaker to the ON position, and remove the out-of-service
tags.
Removal
NOTE:
The emergency power circuit breaker is similar.
SHOCK HAZARD:
Locate the involved building standard/emergency circuit breaker panel.
Set the involved circuit breaker (A) to OFF (see figure 4-1 on page 4-3).
Lockout and tagout the breaker. Failure to follow this procedure could
cause serious injury and damage to the equipment.
1. Make note of the position of the Horizon Headwall System circuit breaker
to be replaced (see figure 4-11 on page 4-23).
2. Remove the breaker cover assembly (B) and the dead front panel (A).
3. Remove the retaining screw and kit (F) for the malfunctioning circuit
breaker (E) (for main breaker only).
5. Note the color coding and placement of the wires in the circuit breaker (E).
6. Remove one, two, or three wires from the one pole, two pole, or three pole
breaker (E).
E F
Interior load
center
D
A
B
m043a037
4
Replacement
1. Install the color coded wires in the circuit breaker (E) in their original
places.
2. Align the breaker (E) and the retaining kit (F) (if equipped) to install the
screw that holds the breaker (E) in place.
3. Install the dead front panel (A) and breaker cover assembly (B).
4. Remove the lockout and tagout from the building circuit breaker, and set
the building circuit breaker back to the ON position.
Removal
SHOCK HAZARD:
Locate the involved power supply circuit breaker panel. Set the involved
circuit breaker(A) to OFF (see figure 4-1 on page 4-3). Failure to follow
this procedure could cause serious injury and damage to the
equipment.
1. Remove the three wire nuts (E) from the wire joints leading to the raceway
and bed switches (see figure 4-12 on page 4-25).
3. Remove the four wire nuts (A) from the wires on the high voltage side of
the controller.
5. Loosen the two screws from the reference ground (C), and remove the two
4 ground wires.
6. Remove the controller mounting screws and the controller (B) from the
barrier (D).
Replacement
NOTE:
Before replacing the low voltage controller, check the following resistances
between the output leads:
• 120V AC 500 Ohms, plus or minus 100 Ohms
• 240V AC 1800 Ohms, plus or minus 100 Ohms
• 277V AC 2500 Ohms, plus or minus 100 Ohms
1. Align the low voltage controller (B) with mounting screw holes on the
barrier (D).
3. Insert the two ground wires in the reference ground (C), and tighten the
screws.
4. Connect the four wires to the high voltage side of the controller (A).
6. Connect the three wires to the wires leading to the raceway and bed
switches (E).
8. Remove the lockout and tagout from the building circuit breaker, and set
the building circuit breaker back to the ON position.
Removal
SHOCK HAZARD:
Locate the involved power supply circuit breaker panel. Set the involved
circuit breaker (A) to OFF (see figure 4-1 on page 4-3). Failure to follow
this procedure could cause serious injury and damage to the
equipment.
1. Turn power OFF at the standard power circuit breaker (lower breaker
panel), and tag the breaker box out-of-service.
3. Pull the timed light switch (C) away from the device plate.
4. Remove the wire nut (B) from the timed light switch ground wire.
6. Pull the toggle switch (E) away from the device plate.
7. Loosen the screws holding the power supply wires and timed light switch
4
wire.
A B
E
A
4 D
m043a016
Replacement
1. Connect the power supply wires to the toggle switch screws.
3. Connect the timed light switch ground wire to the toggle switch screw.
5. Insert the toggle switch (E) in the device plate, and align the screw holes.
7. Connect the timed light switch ground wire with the wire nut (B).
10. Remove the out-of-service tags from the standard circuit breaker, and set
the circuit breaker back to the ON position.
11. Test the timed light switch and toggle switch for power availability.
Adjustment
NOTE:
The timed light switch is adjustable to either 0 to 15 minutes or 0 to 30
minutes. Adjustments may be set from 0 to 30 minutes.
4. Replace the cover and check for the proper delay after switching the light
off.
4
NOTES:
Chapter Contents
Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 - 3
Ordering Service Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 - 5
Exchange Policy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 - 6
In-Warranty Exchanges . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 - 6
Out-of-Warranty Exchanges . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 - 6
Recommended Spare Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 - 7
Chase Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 - 8
Chase Assembly (Isolated Power) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 - 10
Chase Panels and Trim . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 - 12
Light Raceway . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 - 14
Gas Raceway. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 - 16
Bottom Raceway. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 - 18
Raceway Fascia and Gas Excluder . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 - 22
Chase Breaker Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 - 24
Timed Light Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 - 28
5
Specialite Patient Light Provision (Standard/Emergency) . . . . . . . . . . . . . . . . . . 5 - 30
Nurse Call Backbox . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 - 32
Chaseless Raceway—Standard and Isolated Power . . . . . . . . . . . . . . . . . . . . . . . 5 - 34
TeleMate/Phone Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 - 36
Duplex Outlet Receptacles . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 - 38
Single Outlet Receptacles . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 - 40
Line Voltage Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 - 42
Ground Receptacles . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 - 44
Warranty
Hill-Rom ,
A Hillenbrand Industry
LIMITED WARRANTY
Hill-Rom has a long tradition of providing superior quality products and service to our customer. Our goal is “Total Customer
Satisfaction.” In that spirit, Hill-Rom is proud to offer the following warranty.
GENERAL WARRANTY:
Hill-Rom warrants to the original purchaser that its products shall be free from defects in material and workmanship for a
period of one (1) year after date of delivery. Hill-Rom’s obligation under this warranty is expressly limited to supplying
replacement parts and/or service for, or replacing, at its option, any product which is, in the sole discretion of Hill-Rom,
found to be defective. In addition to the foregoing one year warranty, Hill-Rom warrants to the original purchaser that the
frame and welds on its beds will be free from structural defects for the life of the bed. THE FOREGOING WARRANTIES
ARE EXCLUSIVE AND IN LIEU OF ALL OTHER EXPRESS WARRANTIES AND IMPLIED WARRANTIES,
INCLUDING BUT NOT LIMITED TO, THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS OF
PURPOSE. HILL-ROM’S OBLIGATION UNDER THESE WARRANTIES SHALL NOT INCLUDE ANY LIABILITY
FOR LOSS OF PROFITS, DIRECT, INDIRECT OR CONSEQUENTIAL DAMAGES OR DELAYS. Some states do not
allow the exclusion or limitation of incidental or consequential damages, so the above exclusion or limitation may not apply.
If requested by Hill-Rom, products or parts for which a warranty claim is made shall be returned prepaid to Hill-Rom’s
factory. Any improper or negligent use, any alterations or repairs not in accordance with Hill-Rom’s manuals or performed by
others in such manner as in Hill-Rom’s judgment affects the product materially and adversely, shall void these warranties. No
employee or representative of Hill-Rom is authorized to change these warranties in any way or grant any other warranty.
These warranties shall not apply outside the United States. These warranties provide specific legal rights; however, there may
be other available rights, which vary from state to state.
5
PART AVAILABILITY POLICY: Hill-Rom will supply parts for new products for fifteen (15) years from date of last
manufacture, and on remanufactured products for ten (10) years from date of sale.
OUT OF WARRANTY EXCHANGE POLICY: After the expiration of the original warranty, upon request, Hill-Rom will
ship as a replacement, rebuilt electric motors, control boards, and air compressors for like units returned to Hill-Rom by the
original purchaser for forty percent (40%) of the then-current new price. The exchange price is a substantial savings to the
hospital as compared to the price of a new motor, control boards, and air compressors. The replacement motors, control
boards and air compressors will carry a new one (1) year parts warranty.
SPECIFIC WARRANTIES:
MATTRESS WARRANTIES:
DYNAMICAIRE™ SLEEP SURFACE: Hill-Rom warrants to the original purchaser that its product shall be free from
defects in material and workmanship for a period of two (2) years from date of delivery. After the expiration of this warranty,
the surface components may be purchased at 50% of the then-current price during the third, fourth and fifth years after date of
delivery. (Continued)
COMFORTLINE® MATTRESS: Hill-Rom warrants to the original purchaser that its product shall be free from defects in
material and workmanship for a period of two (2) years from date of delivery. After the expiration of this warranty, the
mattress components may be purchased at 50% of the then-current price during the third, fourth and fifth years after date of
delivery.
ZONEAIRE® SLEEP SURFACE: Hill-Rom warrants to the original purchaser that its product shall be free from defects in
material and workmanship for a period of two (2) years from date of delivery. After the expiration of this warranty, the
surface components may be purchased at 50% of the then-current price during the third, fourth and fifth years after date of
delivery. Electromechanical components (compressor, valves, printed circuit boards, hoses and couplers) are warranted to be
free from defects in material and workmanship for a period of one (1) year from date of delivery.
INNERSPRING MATTRESS: Hill-Rom warrants to the original purchaser that its product shall be free from defects in
material and workmanship for the following specified periods from date of delivery. SureRest® III: Twelve (12) year prorated
warranty; SureRest II: Ten (10) year prorated warranty; SureRest I: Five (5) year prorated warranty.
PERINATAL MATTRESS: Hill-Rom warrants to the original purchaser that its product shall be free from defects in
material and workmanship for a period of one (1) year, when used with proper draping practices, from date of delivery.
FOAM MATTRESS: Hill-Rom warrants to the original purchaser that its product shall be free from defects in material and
workmanship for a period of two (2) years from date of delivery.
COMPOSER™ COMMUNICATION SYSTEM WARRANTIES:
COMPOSER HARDWARE WARRANTIES: Hill-Rom warrants to the original purchaser that the hardware components
of the COMposer shall be free from defects in material and workmanship for a period of one (1) year after the date of system
certification. Hill-Rom’s obligation under this warranty is expressly limited to supplying replacement parts and/or service for,
or replacing, at its option, any product which is, in the sole discretion of Hill-Rom, found to be inoperable.
COMPOSER SOFTWARE WARRANTIES: Hill-Rom warrants to the original purchaser that the physical diskettes on
which COMposer system software is distributed shall be free from defects in material and workmanship for a period of sixty
(60) days from the date of delivery. The entire and exclusive remedy available to the purchaser under this warranty is limited
to replacement of inoperable diskettes and shall not extend to any claim for or right to recover any damages, including but not
limited to, loss of profit, data or use of the software, or special, incidental or consequential damages, or other similar claims.
COMPOSER EXPENDABLES WARRANTIES: Hill-Rom warrants for sixty (60) days the expendable parts such as
locator badge batteries and dome light incandescent bulbs.
OTHER WARRANTIES:
EXPENDABLES WARRANTIES: A sixty (60) day limited warranty applies to expendable parts such as overhead
fluorescent tubes, heating elements and temperature probes.
UPGRADE KIT WARRANTIES: Hill-Rom warrants to the original purchaser that its product shall be free from defects in
material and workmanship for a period of one (1) year from date of delivery. The warranty on existing product is not affected.
5 A Product Assurance and/or Preventive Maintenance contract will be offered at the time of installation for a pre-determined
fee. This will act to advise the customer of the condition of Hill-Rom products being upgraded along with specific parts and
PM recommendations.
FOR PARTS AND SERVICE UNDER THESE WARRANTIES: Call Hill-Rom Technical Support Department at
(800) 445-3720, Monday through Friday. In order to expedite service, we request you furnish the following information:
customer identification number, product model number, serial number, and description of problem. A qualified Specialist will
provide, via telephone, troubleshooting assistance for hospital personnel and provide necessary parts to make repairs. If
telephone troubleshooting determines the need for on-site technical service, a qualified Territory Service Representative will
be dispatched. Replacement of non-technical items will be the responsibility of the customer. These warranties do not cover
failures due to misuse, abuse, neglect or lack of routine maintenance, which are the responsibility of the owner.
Revised November 1, 1995
NOTE:
You will find the product number listed along with each part number in this
chapter.
We suggest a minimum of $40.00 when placing orders for service parts. This
will help prevent an increase in the cost of processing your service order.
Terms:
• Net 30 days.
• F.O.B. Batesville, Indiana.
• Shipping charges are prepaid and added to the invoice.
• All service orders are shipped UPS ground, unless you specifically request
an alternative method.
NOTE:
To eliminate possible delays or incorrect billings, do not return any items
without a Return Material Authorization (RMA) number. A Return Material
Authorization packet is included with each order when a return is requested.
This packet includes an RMA number, instructions, and a shipping label. If
misplaced, obtain an RMA number by phoning the Hill-Rom Technical
Support Department at (800) 445-3720.
Exchange Policy
The following are Hill-Rom’s policies for in-warranty and out-of-warranty
exchanges.
In-Warranty Exchanges
Hill-Rom will request that parts/products be returned for inspection in some
cases. When this occurs, you are expected to return parts/products within 30
days. If you fail to return the inoperative parts/products within the 30-day
period, Hill-Rom will invoice your facility for the full selling price of the
parts/products.
NOTE:
The preceding billing procedure only pertains to parts/products that Hill-Rom
requests to be returned.
In some cases, the invoice sent with the parts will show the full selling price of
the parts. This is for Hill-Rom’s internal use only and should not be confused
with the price you will actually pay.
5 Please do not return any parts without an RMA number. Hill-Rom will include
a Return Material Authorization packet with the parts/products shipment when
parts/products have been requested to be returned. If misplaced, obtain an
RMA number by phoning the Hill-Rom Technical Support Department at
(800) 445-3720.
Out-of-Warranty Exchanges
You are expected to return the inoperative parts/product to Hill-Rom within 30
days. Hill-Rom will include a Return Material Authorization packet with the
parts/products shipment. If misplaced, obtain an RMA number by phoning the
Hill-Rom Technical Support Department at (800) 445-3720. If you fail to
return the equipment within 30 days, Hill-Rom will invoice your facility for
the difference between the exchange price and the new price of the part.
Chase Assembly
m043a001
m043a002
m043a003
Light Raceway
m043a004
Gas Raceway
m043a005
Bottom Raceway
m043a006
NOTES:
m043a007
m043a008
NOTES:
m043a009
m043a010
m043a011
m043a012
TeleMate/Phone Options
m043a013
m043a014
m043a015
m043a016
Ground Receptacles
m043a017
m043a018
Hose Panels
m043a019
NOTES:
Manifold Tree
m043a020
m043a038
m043a039
m043a041
NOTES:
Chapter Contents
NOTES:
WARNING:
When following these procedures you must adhere to the “Infection
Control Policies and Procedures” outlined in the Exposure Control Plan.
Not following these procedures could cause the spread of infection.
SHOCK HAZARD:
Locate the involved power supply circuit breaker panel. Set the involved
circuit breaker (A) to OFF (see figure 4-1 on page 4-3). Failure to follow
this procedure could cause serious injury and damage to the
equipment.
General Cleaning
Do not use excessive water. Clean the unit with a lightly dampened cloth and
ordinary cleaners and disinfectants.
Use neutral soap suds and lukewarm water to remove soil or stains. Then, rinse
with clean water and dry.
CAUTION:
Do not use harsh cleaners, solvents, or detergents.
Steam Cleaning
Do not use any steam cleaning device on the Horizon Headwall System. The
excessive moisture can damage electrical components in the Horizon Headwall
System.
Disinfection
Dilute disinfectants and/or germicides as specified on the manufacturer’s label.
Preventive Maintenance
The Horizon Headwall System must have an effective maintenance program.
We recommend that you perform preventive maintenance and testing for Joint
Commission on Accreditation of Health care Organizations (JCAHO)
annually. This not only meets JCAHO requirements, but will help to ensure a
long and productive life for the Horizon Headwall System. This will help
minimize downtime due to excessive wear failures.
Pay particular attention to the safety features regarding the Horizon Headwall
System such as:
• Mounting configuration of the Horizon Headwall System
• Electrical receptacles
• Leaks in the gas delivery system
Function Procedure
Power cables Inspect all cables for good condition and possible cracking
6 Circuit breakers
or cuts or pinches in insulating coverings.
Turn the breaker off and on to check proper function.
Power indicator light Check that the Bed receptacle indicator is on. See “Bed
Receptacle or Indicator Is Inoperative” on page 2-6.
Electrical receptacles Check all receptacles for proper ground conductor extrac-
tive force. The extraction force should be four ounces with
a 0.184 (4.67 mm) diameter pin.
Function Procedure
Electrical connections Check all electrical connections for tightness and tighten as
needed.
Ceiling support Inspect the ceiling chase hanger bracket. Compare to the
installation drawings provided by the manufacturer.
Gas supply conduit Inspect all joints in the Horizon Headwall System for gas
and hoses leaks. Inspect hoses for cracking, wear, collapse, or
leakage.
Line isolation monitor Test the function of the line isolation monitor monthly. See
(if equipped) “Line Isolation Monitor Test” on page 6-7.
General appearance Check cleanliness. See “Cleaning and Care” on page 6-3 if
needed.
Manufacturer
Circuit breakers
Power indicator light
Electrical receptacles
Electrical connections
Ceiling support
Model Number
Labor Time:
for This Page
Total Charge
Repair Cost:
6 Inspected By:
Remarks
Applicable
O=Okay
R=Repair or
N=Not
Legend
Replace
A=Adjust
C=Clean
Chapter Contents
This revision of the Horizon Headwall System Service Manual does not
contain any additional information for accessories.
7
Horizon® Headwall System Service Manual Page 7 - 1
Chapter 7: Accessories
NOTES:
7
Page 7 - 2 Horizon® Headwall System Service Manual