PACiS
C264 Expert Utilisation
1 > L2 4A C264 Expert utilisation 02 1
C264 Expert
1 ) Hardware installation & Commissioning
2 ) Computer’s basic settings
3 ) Software Installation
4 ) Download DataBase and Switch
5 ) Communication Testing
2 > L2 4A C264 Expert utilisation 02 2
C264 Expert
Installation / Commissioning
1) Requirement
2) Checks Power Off Hardware configuration (CORTEC)
3) Checks/install only Power Software Version
Ethernet/Front port
Database Version
Hardware Self tests
4) Checks with I/O IED Communication
DB
3 > L2 4A C264 Expert utilisation 02 3
1.1) Set-up Requirements
1) Adapted DC Power supply (protected)
2) Personal Computer (WINDOWS 2000 administrator)
3) RS232C Null Modem Cable
4) Ethernet cable (cross if not hub/switch)
5) Screw-driver (Torque 10, POZ 1) extractor
19200 bauds
No parity
8 bit
1 stop
No flow control
4 > L2 4A C264 Expert utilisation 02 4
1.2 ) C264 Requirement
MANDATORY
From Business Ordering
1) C264 Delivery Form
2) C264 Hardware Version (kind of CPU, Power Supply)
3) C264 Software Version + System Release Note
4) C264 Business IP, Net name
5) C264 Business Board Configuration
CORTEC
Kind by Slot, Voltage, BIU port
6) C264 Business Data Bag
5 > L2 4A C264 Expert utilisation 02 5
2 ) Checks Power OFF
2 ) Power Off Hardware Checks
2.1) C264 Package Reception
2.2) Front panel Removal Check Hardware configuration
Boards location and Voltage
2.3) Optional Bus removal Check BIU ports jumpers
2.4) Mechanical Mounting
2.5) Wiring installation Shield
6 > L2 4A C264 Expert utilisation 02 6
2.1 ) Delivery reception
1) Packing inspection and opening
2) Delivery Form checking / acceptance
3) Delivery Form Storage in Business Hardware Binder
4) Checking Front Panel Sticker
5) Opening Record Sheet
7 > L2 4A C264 Expert utilisation 02 7
2.2) Front Panel Removing
Rack mounting
Front Panel removal POZ 1
8 > L2 4A C264 Expert utilisation 02 8
2.2 ) Checking Boards Slot / Voltage
Remove front panel and check boards location / Slot
Board Number Board Name
BIU
CPU
DIU DOU CCU AIU
9 > L2 4A C264 Expert utilisation 02 9
2.2 ) Checking Boards Slot / Voltage
Remove front panel and check Voltages
BIU / DIU / CCU
A01 24 V
A02 48V
Sticker A03 110/125V
A04 220V
10 > L2 4A C264 Expert utilisation 02 10
2.3 ) BIU Port Setting
0) Check no power on BIU, get anti-static Brace
1) Get HW chapter (hardware)
2) Remove BUS with finger starting from left
3) Remove Torque Screw (Board + ruler)
4) Extract board with dedicated extractor tool
5) Checking PORT 1/2 setting via jumpers
6) Put Back Board / screws / Bus
11 > L2 4A C264 Expert utilisation 02 11
2.4 ) Mechanical Mounting
Front Panel Reinstall
C264 mechanical fixation (19” rack or other)
12 > L2 4A C264 Expert utilisation 02 12
2.5 ) Wiring Check (still no power)
1) Shield wiring
2) Power supply wiring (BIU + neutral policy)
3) I/O board wiring
4) Ethernet Networks wiring
5) Serial TBUS/LBUS network wiring
Refer to “CONNECTIONS” chapter
(“C264_EN CO” documentation)
Good Practices Shield Scheme
wire color/diameter policy
naming e.g. DIU200_2_D
Write name on connector
13 > L2 4A C264 Expert utilisation 02 13
3 ) Checks Power ON on BIU only
3 ) Checks on Computer’s basic settings
3.1) Run-time Requirements
3.2) C264 power up sequence
3.3) Setting commands
2.3) Checking default settings
2.4 ) Input new settings
14 > L2 4A C264 Expert utilisation 02 14
3.1) Run-time Requirement
1) Connection IP, Serial link
2) Launch HyperTerminal on the PC
3) Launch CMT and WFTP
4) Power up delivered MiCOM C264
>p CR
The following information should be displayed:
“boot device : tffs=0,0
“processor number :0
“host name : <factory host PC name>
“file name : /flash/bin/vxWorks
“inet on ethernet : <factory C264 IP addres xxx.xxx.xxx.xxx>
“inet on backplane : CR
“host inet : <factory host IP adresse xxx.xxx.xxx.xxx>
“gateway inet : 0.0.0.0
“user : <user name>
“ftp password : <password>
“flags : 0x0
“target name : <factory target name>
“startup script :
ALSTOM
“other : motfec
Serial link
RS232
15 > L2 4A C264 Expert utilisation 02 15
3.2 ) C264 Starting
1) Pre boot
First Count Down [VxWorks]
2) Booting Software(network, flash)
Second Count Down ->
3) Starting Software
4) Loading Data Base
16 > L2 4A C264 Expert utilisation 02 16
3.3 ) settings commands
BASIC COMMANDS
Default settings visualization :
VxWorks level > use “p” command
application level > use “bootChange” command
Default settings setup :
VxWorks level > use “c” command
application level > use “bootChange” command
Reboot the computer :
VxWorks level > use “^X” “@” command
application level > use “reboot” command
power off - power on
17 > L2 4A C264 Expert utilisation 02 17
3.3 ) Checking default settings
>p CR or bootChange (CR) Tffs=0,0 boot from flash
The following information should be displayed: motfec=0 boot from PC
“boot device : tffs=0,0
“processor number :0
“host name : <factory host PC name>
“file name : /flash/bin/vxWorks
“inet on ethernet : <factory C264 IP addres xxx.xxx.xxx.xxx>
“inet on backplane : CR
“host inet : <factory host IP adresse xxx.xxx.xxx.xxx>
“gateway inet : 0.0.0.0
c264_cpu0 cpu 8mega flash-old LCD
“user : <c264_cpu2>
“ftp password : <password> c264_cpu1 cpu 16mega flash-old LCD
“flags : 0x0 c264_cpu2 cpu 16mega flash-new LCD
“target name : <factory target name>
“startup script :
“other : motfec
18 > L2 4A C264 Expert utilisation 02 18
4 ) Computer’s Software Installation
3 ) Computer’s Software Installation on PC
3.1 ) Computer’s Software Installation Requirements
3.2 ) Install computer’s software on the PC
3 ) Computer’s Software Installation on C264
3.3 ) Transfer computer’s software on the C264
3.4 ) Input settings for Software Installation
3.5 ) Transfer computer’s software on the C264
3.6 ) Change settings after Software Installation
19 > L2 4A C264 Expert utilisation 02 19
4.1 ) Computer’s Software Installation
Requirements
Requirements for new software installation
Ethernet link
COM1
or
COM2
9600/19200
8 bit
no parity TTY
mode
Serial link cable for “HyperTerminal” application
Ethernet Connection may be direct or via Ethernet switch
Use a crossed Ethernet cable for direct connection
20 > L2 4A C264 Expert utilisation 02 20
4.2 ) Install computer’s software on the PC
Step 1 : agreement acceptance
21 > L2 4A C264 Expert utilisation 02 21
Install computer’s software on the PC (next)
Step 2 : choose default directories “recommended
recommended”
recommended
CAUTION : Computer’s software and FTP server are configured to be
installed to the default directories. If you don’t choose default directories
« FTP server » must be reconfigured.
22 > L2 4A C264 Expert utilisation 02 22
Install computer’s software on the PC(next)
Step 3 : Don’t choose “FTP server” if is not the first
installation via the Personal Computer
23 > L2 4A C264 Expert utilisation 02 23
4.3 ) Transfer computer’s software on the C264
0) if already loaded CLEAN_DB
1) Change to motfec, start wftp, reboot
loading software from network to RAM
2) cleaning flash by eraseFlash + reboot
3) stop 2nd count down Stop Computer with CMT
4) bootInstall
copy from RAM to flash
5) change to tffs=0,0, stop wftp, reboot
loading software from flash
6) Check Software version LCD, VERSION with front link
24 > L2 4A C264 Expert utilisation 02 24
4.4 ) Input settings for Software Installation
Change settings for new software installation
->c CR (or bootChange CR)
“boot device : tffs=0,0 enter <motfec0> CR
“processor number :0 CR
“host name : <Enter host PC name> CR
“file name : /flash/bin/vxWorks enter <vxworks> CR
“inet on ethernet : xxx.xxx.xxx.xxx> CR (@IP change if needed)
“inet on backplane : CR
“host inet : xxx.xxx.xxx.xxx> CR (@IP change if needed)
“gateway inet : 0.0.0.0 CR
“user : c264_cpu2(or c264_cpu1) CR
“ftp password : vxworks CR
“flags : 0x0 CR
“target name : <target name> CR
“startup script : CR
“other : motfec CR
->@ CR (or reboot CR)
25 > L2 4A C264 Expert utilisation 02 25
computer’’s software on the C264
4.5 ) Transfer computer
1) Launch FTP server on your PC
2) Reboot the computer
3 ) hit “CR” on the “HyperTerminal” after loading C264 software
4 ) enter “eraseFlash”+ “CR”
5 ) Reboot the computer
6 ) enter “bootInstall” + “CR” after loading C264 software (can
take some minutes)
If the computer can’t loading C264 software check
Ethernet link and verify settings with “p” or
“bootChange” command
26 > L2 4A C264 Expert utilisation 02 26
Transfer computer’s software on the C264(next)
1) At the end of software installation reboot the
computer
2 ) select the “service panel” and check the version of
the new software
3 ) The computer must be in “maintenance mode”
4 ) Check software installed version
27 > L2 4A C264 Expert utilisation 02 27
4.6 ) Change settings after Software Installation
Change settings for taking in account the new software
-> c CR (or bootChange CR)
“boot device : motfec0 enter < tffs=0,0 > CR
“processor number :0 CR
“host name : <Enter host PC name> CR
“file name : vxworks enter </flash/bin/vxWorks > CR
“inet on ethernet : xxx.xxx.xxx.xxx> CR
“inet on backplane : CR
“host inet : xxx.xxx.xxx.xxx> CR
“gateway inet : 0.0.0.0 CR
“user : <user name> CR
“ftp password : <password> CR
“flags : 0x0 CR
“target name : <target name> CR
“startup script : CR
“other : motfec CR
->@ CR (or reboot CR)
28 > L2 4A C264 Expert utilisation 02 28
4.7) Checking Software version
➘ Check software version via the service panel
S E R V . I N F O
Purchased version
C O M P U T E R S E R I A L N B :
S O F T W A R E V E R S I O N :
D A T A B A S E 1 V E RS & S T A T E : No data base
D A T A B A S E 2 V E RS & S T A T E :
O P E R A T I N G H O UR S :
O P E R A T I N G M O DE :
R E D U N D A N C Y M O DE :
29 > L2 4A C264 Expert utilisation 02 29
4.8) Database Downloading
Checking connection
Loading DB under SMT
Download DB unto C264
Switch to downloaded data base
30 > L2 4A C264 Expert utilisation 02 30
5 ) Communications Testing
5 ) Communications Testing
5.1 ) Communications Testing Requirements
5.2 ) Debug port testing
5.3 ) IED communication testing
5.4 ) IED communication Debug commands
5.5 ) Printer communication testing
5.6 ) Ethernet Communication testing
31 > L2 4A C264 Expert utilisation 02 31
5.1 ) Communications ports
Debug port (serial link)
Scc1 port (serial link RS232 or RS485)
Scc2 port (serial link RS232 or RS485)
Scc3 port (serial link RS232)
Scc4 port (serial link RS232)
Ethernet port
32 > L2 4A C264 Expert utilisation 02 32
5.2) Communications Testing Requirements
Computer must be in operational mode (SCE DB loaded)
Ethernet link
Printer cable
Serial link cable for “HyperTerminal” application
Ethernet Connection may be direct or via Ethernet Hub
Use a crossed Ethernet cable for direct connection
33 > L2 4A C264 Expert utilisation 02 33
5.3 ) Debug port testing
>p CR
The following information should be displayed:
“boot device : tffs=0,0
“processor number :0
“host name : <factory host PC name>
“file name : /flash/bin/vxWorks
“inet on ethernet : <factory C264 IP addres xxx.xxx.xxx.xxx>
“inet on backplane : CR
“host inet : <factory host IP adresse xxx.xxx.xxx.xxx>
“gateway inet : 0.0.0.0
“user : <user name>
“ftp password : <password>
“flags : 0x0
“target name : <factory target name>
“startup script :
“other : motfec
COM1
or
COM2
9600 / 19200
8 bit
no parity
TTY mode
Serial link cable for “HyperTerminal” application
No Communication check :
> serial cable
> check PC COMx settings
34 > L2 4A C264 Expert utilisation 02 34
5.4 ) Ethernet Communication testing
Ethernet link
Ethernet Connection may be direct or via Ethernet switch
Use a crossed Ethernet cable for direct connection
If no communication :
•check IP addresses settings/Mask/Negotiation of both equipment
•use “ping” command via MS-DOS window
•Launch the CMT
35 > L2 4A C264 Expert utilisation 02 35
5.4 ) Serial communication testing
Use the “TEST_COM”
TEST_COM” debug command to send a frame
from one port to the other
<TEST_COM ( port_E,Port_R,type,”text”,1)>
Transmitter port Always=1
Receiver port 0=RS232,1=RS485 ASCII string
Use the “S_APICOM_ShowConfig”
S_APICOM_ShowConfig” debug command to
verify the business DB port setting (and if initialized)
<S_APICOM_ShowConfig N°port>
36 > L2 4A C264 Expert utilisation 02 36
5.4 ) IED communication testing
1 ) Link together scc1 and Scc2 as follow
2 )Via the HyperTerminal launch the TEST_COM
command
1
2 BIU 200
3
4
5
connector
6
7
8
9
10
11
12 Scc2 T-
13 GND
14 Scc2 T+
15 GND
16
17
Scc1 T+
18 Scc1 T-
19
20
21
22
23
24
example “ TEST_COM (1,2,1,”test port 1 to 2”,1)
example “ TEST_COM (2,1,1,”test port 2 to 1”,1)
37 > L2 4A C264 Expert utilisation 02 37
5.4 ) IED communication testing
1 ) Link together scc3 and Scc4 as follow
2 )Via the HyperTerminal launch the command
“test_com” to send frame from one port to another
example “ TEST_COM (3,4,0,”test port 3 to 4”,1)
example “ TEST_COM (4,3,0,”test port 4 to 3”,1)
1 1
2 2
3 3
4 4
5 5
6 6
7 7
8 8
9 9
Scc3 Scc4
38 > L2 4A C264 Expert utilisation 02 38
5.5 ) IED communication Debug commands
>p CR
The following information should be displayed:
Debug Commands
“boot device : tffs=0,0
“processor number :0
“host name : <factory host PC name>
“file name : /flash/bin/vxWorks
“inet on ethernet : <factory C264 IP addres xxx.xxx.xxx.xxx>
“inet on backplane : CR
Traces_scc1=16
“host inet : <factory host IP adresse xxx.xxx.xxx.xxx>
“gateway inet : 0.0.0.0
“user : <user name>
“ftp password : <password>
“flags : 0x0
“target name : <factory target name>
“startup script :
Traces_scc2=16
“other : motfec
RS485 RS232
-> traces_scc1=16 Frame : C264 to IED
traces_scc1 = 0x516fd8: value = 16 = 0x10
0x1274568 (T35IECM20): 0065ms -->P=1 L=5 :10 5B 02 5D 16
0x1274568 (T35IECM20): 0015ms <<<P=1 L=5 :10 09 02 0B 16 Frame : IED response
No Communication with the IED : check C264 configuration
and IED settings, check wiring with the IED
39 > L2 4A C264 Expert utilisation 02 39
IED communication - frames IEC
IEC 60870-5-103 Frames
->
-> traces_scc1=16
traces_scc1 = 0x516fd8: value = 16 = 0x10
0x1274568 (T35IECM20): 0065ms -->P=1 L=5 :10 5B 02 5D 16
0x1274568 (T35IECM20): 0015ms <<<P=1 L=5 :10 09 02 0B 16
0x1274568 (T35IECM20): 0065ms -->P=1 L=5 :10 7B 02 7D 16
0x1274568 (T35IECM20): 0015ms <<<P=1 L=5 :10 09 02 0B 16
0x1274568 (T35IECM20): 0070ms -->P=1 L=5 :10 5B 02 5D 16
0x1274568 (T35IECM20): 0015ms <<<P=1 L=5 :10 09 02 0B 16
0x1274568 (T35IECM20): 0070ms -->P=1 L=5 :10 7B 02 7D 16
1 IEC 103 Device
Device’s Address =2
40 > L2 4A C264 Expert utilisation 02 40
IED communication frames
ModBus
ModBus Frames
-> traces_scc2=16
traces_scc2 = 0x516fdc: value = 16 = 0x10
0x129d068 (T42MBM21): 0025ms -->P=2 L=8 :02 02 00 00 00 10 79 F5
0x129d068 (T42MBM21): 0020ms <<<P=2 L=7 :02 02 02 00 00 FD B8
0x129d068 (T42MBM21): 0240ms -->P=2 L=4 :01 07 41 E2
0x129d068 (T42MBM21): 0015ms <<<P=2 L=5 :01 07 01 E3 F0
0x129d068 (T42MBM21): 0025ms -->P=2 L=8 :02 02 00 00 00 10 79 F5
0x129d068 (T42MBM21): 0020ms <<<P=2 L=7 :02 02 02 00 00 FD B8
0x129d068 (T42MBM21): 0245ms -->P=2 L=4 :01 07 41 E2
0x129d068 (T42MBM21): 0010ms <<<P=2 L=5 :01 07 01 E3 F0
0x129d068 (T42MBM21): 0025ms -->P=2 L=8 :02 02 00 00 00 10 79 F5
0x129d068 (T42MBM21): 0020ms <<<P=2 L=7 :02 02 02 00 00 FD B8
2 ModBus IED devices
Address 1 and 2
41 > L2 4A C264 Expert utilisation 02 41
5.6 ) Printer communication testing
Central CPU260
Scc1 & Scc2 port (serial link RS232 or RS485) Processing Unit
board
PIN
12 3 4 5 6 7 8
10/100 BaseT
Ethernet-based link
RJ-45
(female)
OPTIONNAL LINKS:
DCD
1 RS232/
RXD / T-
2 RS485
P2 3
TXD / T+
1 2 3 45 6 7 8
Serial
Scc3, Scc4 used (usually) for printer or 5 GND link 2
SCADA link (protocols ModBus, IEC RJ-45
(female)
7
8
RTS
CTS
#
60870-5-101) P3
1 2 3 45 6 7 8
1
2
DCD
RXD / T-
RS232/
RS485
TXD / T+
3
Serial
5
GND link 1
RJ-45
RTS
(female) 7
8 CTS
#
42 > L2 4A C264 Expert utilisation 02 42
Printer’s communication
SS WESPEELAR CAS 36 - C264WESP 02/01/88
09:07:37.890
* 02/01/88 09:07:37.890 C264 WESPELAART3 REENCL ES NON BL
Set
* 02/01/88 09:07:37.890 WESPELAAR /DV SPS REENCL EN NB
Set
* 02/01/88 09:07:37.890 WESPELAAR /DV AR BLOCKING
Reset
* 02/01/88 09:07:38.079 WESPELAAR /IN FROM COM TRAN UHT< ET UMT<
Reset
* 02/01/88 09:07:38.094 WESPELAAR /IN FROM COM TRAN UHT >
Set
* 02/01/88 09:07:38.094 WESPELAAR /IN FROM COM TRAN UMT>
Set
* 02/01/88 09:07:40.521 WESPELAAR /P142 TPR GenStart
Reset
* 02/01/88 09:07:40.798 WESPELAAR /INP FROM SYN RTU ENCL/DECL MAN DV
Open
* 02/01/88 09:07:40.924 WESPELAAR /sd SPS DEVERROUILLA
Reset
* 02/01/88 09:07:40.924 WESPELAAR TC EN COURS
Set
* 02/01/88 09:07:40.940 WESPELAAR /DV+ SPS DECL PH C
Set
If no printing check : printers settings and C264 DB
settings
43 > L2 4A C264 Expert utilisation 02 43