0% found this document useful (0 votes)
297 views27 pages

AS 1668.1-2052 - Z - Presentation

This document summarizes a presentation about revisions made to AS/NZS 1668.1:2015, which provides requirements for ventilation and air conditioning systems in buildings. The presentation discusses the purpose of the revision, including clarifying interpretations, addressing gaps, and incorporating new technologies. It provides an overview of changes made to each section, such as expanded scopes, additional diagrams, clarified definitions, and improved documentation and testing requirements. The goal of the revisions is to improve safety, usability and compliance for mechanical smoke control systems in buildings.

Uploaded by

Sean Rose
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
297 views27 pages

AS 1668.1-2052 - Z - Presentation

This document summarizes a presentation about revisions made to AS/NZS 1668.1:2015, which provides requirements for ventilation and air conditioning systems in buildings. The presentation discusses the purpose of the revision, including clarifying interpretations, addressing gaps, and incorporating new technologies. It provides an overview of changes made to each section, such as expanded scopes, additional diagrams, clarified definitions, and improved documentation and testing requirements. The goal of the revisions is to improve safety, usability and compliance for mechanical smoke control systems in buildings.

Uploaded by

Sean Rose
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 27

AS/NZS 1668.

1:2015
The use of ventilation and air conditioning in buildings

Fire and smoke control in buildings

Presented by:
BRETT FAIRWEATHER

+INTEGRITY +INFORMED +INNOVATION


Presentation Content
• PURPOSE OF REVISION

• BRIEF SCOPE OF EACH SECTION

• IMPORTANT CHANGES IN EACH SECTION


PURPOSE OF REVISION
• Clarification for known misinterpretations
• Black holes between NCC & 1998 edition
• New technology
• Better supporting information
• Improved diagrams
• 17 year old Standard
SECTION 1
GENERAL

• Scope:
– Minimum requirements for the design,
construction, installation and commissioning of
mechanical smoke control systems in Class 2 to
Class 9 buildings.
– Now includes multi-compartment & large, single-
compartment buildings
– Requirements for the maintenance of smoke
control systems are not included.
SECTION 2
AIR-HANDLING SYSTEMS

• Scope:
– General requirements for air-handling systems
and pressurization systems
– Properties & installation requirements for
components
SECTION 2
AIR-HANDLING SYSTEMS

• Changes:
– Interaction between smoke control systems
– Damper definitions
– Concessions for combustibility & temp of fusion
– Electrical reference to AS/NZS 3000
– Reminder about seismic conditions
SECTION 3
FIRE PROTECTION OF OPENINGS

• Scope:
– To maintain the fire integrity of building elements
compromised by mechanical ventilation
– Protection of ducts, openings & equipment
SECTION 3
FIRE PROTECTION OF OPENINGS

• Changes:
– Clarification around FRL components
– Openings in Walls & Floors now “Method of
Protection”
– Exemptions & Exclusions
– Fire-resistant enclosing construction
– “Smoke-spill” is now “Smoke exhaust”
– Subduct clarifications
SECTION 4
SMOKE CONTROL SYSTEMS

• Scope:
– general requirements for air-handling systems
used for smoke control
– Location of inlets, outlets & direction of airflow
– Noise & door force limits
– Fan construction
– Electrical requirements
– Control & Indication
– T&C requirements and Records
SECTION 4
SMOKE CONTROL SYSTEMS

• Changes:
– Transfer of content to AS1670.1 Smoke Control
– Wiring exceptions:
• within fire rated plantroom (previous clash with
authorities)
• no adverse affect on operation
– VSD Labelling
– Can’t use BMS
– Table 4.1
SECTION 4
SMOKE CONTROL SYSTEMS

• More changes:
– Baseline data, test results & documentation shall
be readily available at the site
– Improved documentation requirements:
• Design documentation
• O&M instructions & equipment schedules
• Concise essential instructions
• Schematic diagram
– Improved testing requirements
SECTION 5
MISCELLANEOUS SYSTEMS

• Scope:
– requirements for miscellaneous air-handling
systems that do not form part of a smoke control
system.
SECTION 5
MISCELLANEOUS SYSTEMS

• Changes:
– “Small systems” now “Single enclosures”. 1000L/s
– Improved minor system (<0.1m²) requirements
– Carparks:
• NOT A SMOKE EXHAUST SYSTEM
• Dedicated (non-essential) main switch required
• Jet fans shut down (and are not in series)
• Ventilation (incl. supply) operate at FVR
• Fire dampers often OK
• Stair pressurisation relief = Smoke exhaust system
SECTION 6
KITCHEN EXHAUST HOOD SYSTEMS

• Scope:
– requirements for exhaust systems serving kitchen
hoods and kitchen appliances with proprietary
exhaust provisions installed as required by AS
1668.2
SECTION 6
KITCHEN EXHAUST HOOD SYSTEMS

• Changes:
– “it shall not shut down” (with switch labelling)
– Other ventilation systems may share the shaft
– Flame and spark arrestance required
SECTION 7
SHUTDOWN SYSTEMS

• Scope:
– requirements for the shutdown of air-handling
systems that do not form part of a smoke control
system.

• Changes:
– Improved requirements for smoke dampers
SECTION 8
ZONE PRESSURIZATION SYSTEMS

• Scope:
– requirements for systems that are required to
provide zone smoke control utilizing a
pressurization system
– central plant and individual plant air-handling
systems
SECTION 8
ZONE PRESSURIZATION SYSTEMS

• Changes:
– Now 20 to 80 Pa below other compartments
– Clearer diagrams
SECTION 9
HOT LAYER SMOKE CONTROL SYSTEMS

• Scope:
– Exhaust smoke from the hot smoke layer to
maintain the smoke layer above egress paths.
– Based on a single axisymmetric plume, which is
confined to one reservoir.
– Smoke plumes spilling across multiple reservoirs
are not considered.
SECTION 9
HOT LAYER SMOKE CONTROL SYSTEMS

• Changes:
– Entirely new section
– Transfer of content from AS1668.3
– Omission of “Fire Engineering-ness”
– Exhaust air capacity (as per BCA)
– Describes intakes, reservoirs, plenums, curtains,
make-up & operation
– Single fan permitted for multiple compartments
SECTION 10
PROTECTION OF FIRE-ISOLATED EXITS

• Scope:
– Protection of fire-isolated exits by pressurization
– Pressurization creates airflow across open doors
– Relief, relief, relief
SECTION 10
PROTECTION OF FIRE-ISOLATED EXITS

• Changes:
– More reminders about relief
– Dedicated vs Zone pressurisation (leakage)
– VSD’s: encourages location within the exit
– Vertical & horizontal combined
– Reworked performance criteria
– …and don’t forget about relief
SECTION 11
AIR PURGE SYSTEMS

• Scope:
– Legacy item
– Operation of HVAC smoke control to “purge” smoke
from building
– Smoke out. Outdoor air in.
– Only applies to central plant systems serving multiple
compartments

• Changes:
– Not much.
SECTION 12
LIFT SHAFT PRESSURIZATION SYSTEM

• Scope:
– lift shaft pressurization system when required to
aid in smoke control

• Changes:
– Not much.
APPENDICES
• A: Health & Aged Care (Informative)
• B: Subduct Principles (NEW) (Informative)
• C: Reliability (Informative)
• D: Wiring Systems Fire Resistance (Normative)
• E: Commissioning Tests (Informative)
• F: Hot Layer Application (NEW) (Informative)
• G: Building Geometry (NEW) (Informative)
• H: Hot Layer Inlet Requirements (NEW) (Normative)
• I: General Design Information (NEW) (Informative)
• J: Open Access Ramps & Balconies (NEW) (Informative)
• K: Exit Pressurization Tips (NEW) (Informative)
Thank you

Presentation prepared by
BRETT FAIRWEATHER
Member AS/NZS 1668.1 sub-committee
for more information, please contact Brett at It’s Engineered
+INTEGRITY +INFORMED +INNOVATION www.itsengineered.com.au

You might also like