Basement Ventilation Calculation
SR.NO. DESCRIPTION UNITS REMARKS
1 AREA, M2 2538
2 HEIGHT, M 4
3 VOLUME, M3 10152
4 AIR CHANGES PER HOUR 12 12 ACPH as per NBC2016
5 TOTAL AIR VOLUME (CMH) 121824
6 TOTAL AIR VOLUME (CFM) 71661
7 VELOCITY (FPM) 2000
8 AREA REQUIRED FOR EXHAUST DUCT 3.329
9 DUCT SIZE PROPOSED Jet fans with axial fan-no ducting
Fire Pump Room Ventilation Calculation
SR.NO. DESCRIPTION UNITS REMARKS
1 AREA, M2 66
2 HEIGHT, M 7.65
3 VOLUME, M3 504.9
4 AIR CHANGES PER HOUR 20 15-30 ACPH as per NBC2016
5 TOTAL AIR VOLUME (CMH) 10098
6 TOTAL AIR VOLUME (CFM) 5940
7 VELOCITY (FPM) 2000
8 AREA REQUIRED FOR EXHAUST DUCT 0.276
9 DUCT SIZE PROPOSED 525 525
Domestic Water Pump Room Ventilation Calculation
SR.NO. DESCRIPTION UNITS REMARKS
1 AREA, M2 64
2 HEIGHT, M 4.05
3 VOLUME, M3 259.2
4 AIR CHANGES PER HOUR 20 15-30 ACPH as per NBC2016
5 TOTAL AIR VOLUME (CMH) 5184
6 TOTAL AIR VOLUME (CFM) 3049
7 VELOCITY (FPM) 2000
8 AREA REQUIRED FOR EXHAUST DUCT 0.142
9 DUCT SIZE PROPOSED 376 376
Sewage Treatment Plant Room Ventilation Calculation
SR.NO. DESCRIPTION UNITS REMARKS
1 AREA, M2 66
2 HEIGHT, M 7.65
3 VOLUME, M3 504.9
4 AIR CHANGES PER HOUR 30 Min 30 ACPH as per NBC2016
5 TOTAL AIR VOLUME (CMH) 15147
6 TOTAL AIR VOLUME (CFM) 8910
7 VELOCITY (FPM) 1800
8 AREA REQUIRED FOR EXHAUST DUCT 0.460
9 DUCT SIZE PROPOSED 678 678