0% found this document useful (0 votes)
50 views383 pages

Vamp 11V en Manual 1.0

The document is a technical manual that provides safety instructions for a VAMP 11V voltage and frequency relay. It outlines important safety symbols and labels, proper installation and maintenance procedures, and technical specifications. Personnel should read the manual fully before working with the equipment to ensure safe operation and avoid exposure to hazardous voltages. Only qualified personnel should install, commission or service the relay.

Uploaded by

Achraf AEP
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
50 views383 pages

Vamp 11V en Manual 1.0

The document is a technical manual that provides safety instructions for a VAMP 11V voltage and frequency relay. It outlines important safety symbols and labels, proper installation and maintenance procedures, and technical specifications. Personnel should read the manual fully before working with the equipment to ensure safe operation and avoid exposure to hazardous voltages. Only qualified personnel should install, commission or service the relay.

Uploaded by

Achraf AEP
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 383

VOLTAGE AND FREQUENCY

RELAY

VAMP 11V

Technical Manual
(V11V/EN M v1.0)
(January 2016)
Note: The technical manual for this device gives instructions for its installation, commissioning, and operation.
However, the manual cannot cover all conceivable circumstances or include detailed information on all
topics. In the event of any questions or specific problems arising, do not take any action without proper
authorization. Contact the appropriate Schneider Electric Energy technical sales office and request the
necessary information.

Any agreements, commitments, and legal relationships and any obligations on the part of Schneider
Electric Energy including settlements of warranties, result solely from the applicable purchase contract,
which is not affected by the contents of the technical manual.

This device MUST NOT be modified. If any modification is made without the express permission of
Schneider Electric Energy, it will invalidate the warranty, and may render the product unsafe.

The SCHNEIDER ELECTRIC ENERGY logo and any alternative version thereof are trademarks and service marks of
SCHNEIDER ELECTRIC ENERGY.

VAMP is a registered trademark of SCHNEIDER ELECTRIC ENERGY. All trade names or trademarks mentioned herein
whether registered or not, are the sole property of their owners.

This manual is provided for informational use only and is subject to change without notice.

© 2015, SCHNEIDER ELECTRIC ENERGY. All rights reserved.


CONTENTS

Safety Section V11V/EN SS SS


Update Documentation
N/A
Section 1 Introduction V11V/EN IT IT
Section 2 Technical Data V11V/EN TD TD
Section 3 Getting Started V11V/EN GS GS
Section 4 Settings V11V/EN ST ST
Section 5 Operation V11V/EN OP OP
Section 6 Application Notes V11V/EN AP AP
Section 7 Measurements and Recording V11V/EN MR MR
Section 8 Commissioning V11V/EN CM CM
Section 9 Maintenance V11V/EN MT
MT
Section 10 Troubleshooting V11V/EN TS
TS
Section 11 Symbols and Glossary V11V/EN SG
SG
Section 12 Installation V11V/EN IN
IN
Section 13 Communication Database V11V/EN CT
CT
Firmware and Service Manual
Section 14 V11V/EN VH
Version History VH
Safety Section V11V/EN SS v1.0

SS

SAFETY SECTION
Safety Section V11V/EN SS v1.0

(SS) - 1

CONTENTS

1. INTRODUCTION 2
SS
2. HEALTH AND SAFETY 2
3. SYMBOLS AND LABELS ON THE EQUIPMENT 3
3.1 Symbols 3
3.2 Labels 3

4. INSTALLING, COMMISSIONING AND SERVICING 3


5. DE-COMMISSIONING AND DISPOSAL 6
6. TECHNICAL SPECIFICATIONS FOR SAFETY 6
6.1 Protective fuse rating 6
6.2 Protective class 6
6.3 Installation category 6
6.4 Environment 6
V11V/EN SS v1.0 Safety Section

(SS) - 2

STANDARD SAFETY STATEMENTS AND EXTERNAL LABEL INFORMATION


FOR SCHNEIDER ELECTRIC ENERGY EQUIPMENT

1. INTRODUCTION
SS This Safety Section and the relevant equipment documentation provide full information on
safe handling, commissioning and testing of this equipment. This Safety Section also
includes reference to typical equipment label markings.
The technical data in this Safety Section is typical only, see the technical data section of the
relevant equipment documentation for data specific to a particular item of equipment.

Before carrying out any work on the equipment the user should be familiar with
the contents of this Safety Section and the ratings on the equipment’s rating
label.

Reference should be made to the external connection diagram before the equipment is
installed, commissioned or serviced.
Language specific, self-adhesive User Interface labels are provided in a bag for some
equipment.

2. HEALTH AND SAFETY


The information in the Safety Section of the equipment documentation is intended to ensure
that equipment is properly installed and handled in order to maintain it in a safe condition.
It is assumed that everyone who will be involved with the equipment is familiar with the
contents of this Safety Section, or the Safety Guide (SFTY/4L M).
When electrical equipment is in operation, dangerous voltages are present in certain parts of
the equipment. Failure to observe warning notices, incorrect use, or improper use may
endanger personnel and equipment and also cause personal injury or physical damage.
Before working in the terminal strip area, the equipment must be isolated.
Proper and safe operation of the equipment depends on appropriate shipping and handling,
proper storage, installation and commissioning, and on careful operation, maintenance and
servicing. For this reason only qualified personnel may work on or operate the equipment.
Qualified personnel are individuals who:

• Are familiar with the installation, commissioning, and operation of the equipment and of
the system to which it is being connected;

• Are able to safely perform switching operations in accordance with accepted safety
engineering practices and are authorized to energize and de-energize equipment and to
isolate, ground, and label it;

• Are trained in the care and use of safety apparatus in accordance with safety
engineering practices;

• Are trained in emergency procedures (first aid).


The equipment documentation gives instructions for its installation, commissioning, and
operation. However, the manuals cannot cover all conceivable circumstances or include
detailed information on all topics. In the event of any questions or specific problems arising,
do not take any action without proper authorization. Contact the appropriate Schneider
Electric Energy technical sales office and request the necessary information.
Safety Section V11V/EN SS v1.0

(SS) - 3

3. SYMBOLS AND LABELS ON THE EQUIPMENT


For safety reasons the following symbols which may be used on the equipment or referred to
in the equipment documentation, should be understood before it is installed or
commissioned.
3.1 Symbols
SS

Caution: refer to equipment documentation Caution: risk of electric shock

Functional/Protective Conductor (*Earth)


Protective Conductor (*Earth) terminal
terminal

Note: This symbol may also be used for a Protective Conductor (Earth) Terminal if that
terminal is part of a terminal block or sub-assembly e.g. power supply.

*NOTE: THE TERM EARTH USED THROUGHOUT THIS TECHNICAL MANUAL IS THE
DIRECT EQUIVALENT OF THE NORTH AMERICAN TERM GROUND.

3.2 Labels
See Safety Guide (SFTY/4L M) for typical equipment labeling information.

4. INSTALLING, COMMISSIONING AND SERVICING


Equipment connections
Personnel undertaking installation, commissioning or servicing work on this
equipment should be aware of the correct working procedures to ensure safety.
The equipment documentation should be consulted before installing,
commissioning, or servicing the equipment.
Terminals exposed during installation, commissioning and maintenance may
present a hazardous voltage unless the equipment is electrically isolated.
Any disassembly of the equipment may expose parts at hazardous voltage, also
electronic parts may be damaged if suitable electrostatic voltage discharge (ESD)
precautions are not taken.
If there is unlocked access to the rear of the equipment, care should be taken by
all personnel to avoid electric shock or energy hazards.
Voltage connections should be made using insulated crimp terminations to ensure
that terminal block insulation requirements are maintained for safety.
Watchdog (self-monitoring) contacts are provided in numerical relays to indicate
the health of the device. Schneider Electric Energy strongly recommends that
these contacts are hardwired into the substation's automation system, for alarm
purposes.
To ensure that wires are correctly terminated the correct crimp terminal and tool
for the wire size should be used.
The equipment must be connected in accordance with the appropriate connection
diagram.

Protection Class I Equipment


- Before energizing the equipment it must be earthed using the protective
conductor terminal, if provided, or the appropriate termination of the
supply plug in the case of plug connected equipment.
V11V/EN SS v1.0 Safety Section

(SS) - 4

- The protective conductor (earth) connection must not be removed since


the protection against electric shock provided by the equipment would be
lost.
- When the protective (earth) conductor terminal (PCT) is also used to
terminate cable screens, etc., it is essential that the integrity of the
SS protective (earth) conductor be checked after the addition or removal of
such functional earth connections. For M4 stud PCTs the integrity of the
protective (earth) connections should be ensured by use of a locknut or
similar.
The recommended minimum protective conductor (earth) wire size is 2.5 mm²
(3.3 mm² for North America) unless otherwise stated in the technical data section
of the equipment documentation, or otherwise required by local or country wiring
regulations.
The protective conductor (earth) connection must be low-inductance and as short
as possible.
All connections to the equipment must have a defined potential. Connections that
are pre-wired, but not used, should preferably be grounded when binary inputs
and output relays are isolated. When binary inputs and output relays are
connected to common potential, the pre-wired but unused connections should be
connected to the common potential of the grouped connections.
Before energizing the equipment, the following should be checked:
- Voltage rating/polarity (rating label/equipment documentation);
- VT circuit rating (rating label) and integrity of connections;
- Protective fuse rating;
- Integrity of the protective conductor (earth) connection (where
applicable);
- Voltage rating of external wiring, applicable to the application.
Accidental touching of exposed terminals
If working in an area of restricted space, such as a cubicle, where there is a risk of
electric shock due to accidental touching of terminals which do not comply with
IP20 rating, then a suitable protective barrier should be provided.
Equipment use
If the equipment is used in a manner not specified by the manufacturer, the
protection provided by the equipment may be impaired.
Removal of the equipment front panel/cover
Removal of the equipment front panel/cover may expose hazardous live parts,
which must not be touched until the electrical power is removed.
UL and CSA listed or recognized equipment
To maintain UL and CSA approvals the equipment should be installed using UL
and/or CSA listed or recognized parts of the following type: connection cables,
protective fuses/fuse holders or circuit breakers, insulation crimp terminals, and
replacement internal battery, as specified in the equipment documentation.
Equipment operating conditions
The equipment should be operated within the specified electrical and
environmental limits.
External resistors, including voltage dependent resistors (VDRs)
Where external resistors, including voltage dependent resistors (VDRs), are fitted
to the equipment, these may present a risk of electric shock or burns, if touched.
Battery replacement
Where internal batteries are fitted they should be replaced with the recommended
type and be installed with the correct polarity to avoid possible damage to the
equipment, buildings and persons.
Insulation and dielectric strength testing
Insulation testing may leave capacitors charged up to a hazardous voltage. At the
end of each part of the test, the voltage should be gradually reduced to zero, to
Safety Section V11V/EN SS v1.0

(SS) - 5

discharge capacitors, before the test leads are disconnected.


Insertion of modules and pcb cards
Modules and PCB cards must not be inserted into or withdrawn from the
equipment whilst it is energized, since this may result in damage.
Insertion and withdrawal of extender cards SS
Extender cards are available for some equipment. If an extender card is used, this
should not be inserted or withdrawn from the equipment whilst it is energized.
This is to avoid possible shock or damage hazards. Hazardous live voltages may
be accessible on the extender card.
External test blocks and test plugs
Great care should be taken when using external test blocks and test plugs such
as the MMLG, MMLB and MiCOM P990 types, hazardous voltages may be
accessible when using these.
Fiber-optic communication
Where fiber-optic communication devices are fitted, these should not be viewed
directly. Optical power meters should be used to determine the operation or signal
level of the device.
Cleaning
The equipment may be cleaned using a lint free cloth dampened with clean water,
when no connections are energized. Contact fingers of test plugs are normally
protected by petroleum jelly, which should not be removed.
Maintenance and installation
For safety reason, no work must be carried out on the VAMP until all power
sources to the unit have been disconnected
V11V/EN SS v1.0 Safety Section

(SS) - 6

5. DE-COMMISSIONING AND DISPOSAL


De-commissioning
The supply input (auxiliary) for the equipment may include capacitors across the
SS supply or to earth. To avoid electric shock or energy hazards, after completely
isolating the supplies to the equipment (both poles of any dc supply), the
capacitors should be safely discharged via the external terminals prior to de-
commissioning.

Disposal
It is recommended that incineration and disposal to water courses is avoided.
The equipment should be disposed of in a safe manner. Batteries should be
removed from any equipment before its disposal, taking precautions to avoid
short circuits. Particular regulations within the country of operation, may apply to
the disposal of the equipment.

6. TECHNICAL SPECIFICATIONS FOR SAFETY


6.1 Protective fuse rating
Where UL Listing of the equipment is not required the recommended fuse type is a high
rupture capacity (HRC) type with a maximum current rating of 16 Amps and a minimum DC
rating of 250 Vdc, for example the Red Spot NIT or TIA type.
To maintain UL and CUL Listing of the equipment for North America a UL Listed fuse shall
be used. The UL Listed type shall be a Class J time delay fuse, with a maximum current
rating of 15 A and a minimum DC rating of 250 Vdc, for example type AJT15.
The protective fuse should be located as close to the unit as possible.

6.2 Protective class


IEC 60255-27: 2013 Class I (unless otherwise specified in the
equipment documentation).

6.3 Installation category


IEC 60255-27: 2013 Installation category III (Overvoltage Category III).
EN 60255-27: 2014 Distribution level, fixed installation.
Equipment in this category is qualification tested at
5kV peak, 1.2/50µs, 500Ω, 0.5J, between all
supply circuits and earth and also between
independent circuits.
6.4 Environment
The equipment is intended for indoor installation and use only. If it is required for use in an
outdoor environment then it must be housed in a specific cabinet which will enable it to meet
the requirements of IEC 60529 with the classification of degree of protection IP54 (dust and
splashing water protected).
Pollution Degree - Pollution Degree 2 Compliance is demonstrated by reference to safety
Altitude - Operation up to 2000m standards.
IEC 60255-27:2013
EN 60255-27: 2014
Introduction V11V/EN IT v1.0

VAMP 11V

IT

INTRODUCTION

Date: 1st December 2015


Software Version: 1A
Connection Diagrams: 10V11V01
Introduction V11V/EN IT v1.0

VAMP V11V (IT) 1-1

CONTENTS

1. VAMP DOCUMENTATION STRUCTURE 2


2. INTRODUCTION TO VAMP 4
3. PRODUCT SCOPE 5 IT
3.1 Key for the manual 5
3.2 Functional overview 5
3.3 Ordering options Information (Required with Order) 7
3.4 Catalogue numbers for international distribution center ordering 7

FIGURES

Figure 1: Functional diagram of the V11V 6


V11V/EN IT v1.0 Introduction

(IT) 1-2 VAMP 11V

1. VAMP documentation structure


The manual provides a functional and technical description of the VAMP protection relay and
a comprehensive set of instructions for the relay’s use and application.
The section contents are summarized below:
V11V/EN IT Introduction

IT A guide to the VAMP range of relays and the documentation structure. Also a general
functional overview of the relay and brief application summary are given.
V11V/EN TD Technical Data
Technical data including setting ranges, accuracy limits, recommended operating conditions,
ratings and performance data. Compliance with norms and international standards is quoted
where appropriate.
V11V/EN GS Getting Started
A guide to the different user interfaces of the protection relay describing how to start using it.
This section provides detailed information regarding the communication interfaces of the
relay, including a detailed description of how to access the settings database stored within
the relay.
V11V/EN ST Settings
List of all relay settings, including ranges, step sizes and defaults, together with a brief
explanation of each setting.
V11V/EN OP Operation
A comprehensive and detailed functional description of all protection and non-protection
functions.
V11V/EN AP Application Notes
This section includes a description of common power system applications of the relay,
calculation of suitable settings, some typical worked examples, and how to apply the settings
to the relay.
V11V/EN MR Measurements and Recording
Detailed description of the relays recording and measurements functions.
V11V/EN CM Commissioning
Instructions on how to commission the relay, comprising checks on the calibration and
functionality of the relay.
V11V/EN MT Maintenance
A general maintenance policy for the relay is outlined.
V11V/EN TS Troubleshooting
Advice on how to recognize failure modes and the recommended course of action. Includes
guidance on whom at Schneider Electric Energy to contact for advice.
V11V/EN SG Symbols and Glossary
List of common technical abbreviations found within the product documentation.
V11V/EN IN Installation
Recommendations on unpacking, handling, inspection and storage of the relay. A guide to
the mechanical and electrical installation of the relay is provided, incorporating earthing
recommendations. All external wiring connections to the relay are indicated.
Introduction V11V/EN IT v1.0

VAMP V11V (IT) 1-3

V11V/EN CM Communication Database


This section provides an overview regarding the SCADA/DCS communication interfaces of
the relay.
V11V/EN VH Firmware and Service Manual Version History
History of all hardware and software releases for the product.

IT
V11V/EN IT v1.0 Introduction

(IT) 1-4 VAMP 11V

2. INTRODUCTION TO VAMP
VAMP is a comprehensive solution capable of meeting all electricity supply requirements.
It comprises a range of components, systems and services from Schneider Electric Energy.
Central to the VAMP concept is flexibility.
VAMP provides the ability to define an application solution and, through extensive
communication capabilities, integrate it with your power supply control system.
IT
VAMP products include extensive facilities for recording information on the state and
behavior of the power system using disturbance and fault records. They can also provide
measurements of the system at regular intervals for a control center enabling remote
monitoring and control to take place.
For up-to-date information on any VAMP product, visit our website:
www.schneider-electric.com
Introduction V11V/EN IT v1.0

VAMP V11V (IT) 1-5

3. PRODUCT SCOPE
VAMP 11V is cost-effective over/under voltage and frequency protection relay for essential
protection functions. It is high-quality, easy to install and easy to set up (even manually by
using front panel HMI).
Thanks of very small case dimensions can be applied as replacement of all old technology
protection relays or installed in the modern low dimension MV or LV switchgear panels,
events and relay settings can be downloaded to a local PC (selected Models).
IT
Settings for the protection elements are entered using the front panel keyboard and can be
checked on the local display or using the MiCOM S1 Studio setting software (selected
Models). MiCOM S1 Studio must be at least 5.1.0 software version or higher. In case of
having older version of MiCOM S1 Studio than 5.1.0, please install the newest tool from
Schneider Electric Web Page.
3.1 Key for the manual
The V11V relays are available in several hardware versions offering different numbers of
outputs, inputs, communication ports etc. called “Models” (Model: A, N, L).
Please refer to the commercial publication for further information on the product features and
application arrangements.
3.2 Functional overview
The V11V relay offers a wide variety of protection functions.
The protection features are summarized below:

Function
PROTECTION FUNCTIONS OVERVIEW
available
Three undervoltage stages are provided with AND/OR logic. The
first (U<) and the second stage (U<<) may be set to Inverse
27/27S All models
Definite Minimum Time (IDMT) or Definite Time (DT); the third
stage (U<<<) may be set to DT only.
Three overvoltage stages are provided with AND/OR logic. The
first (U>) and the second stage (U>>) may be set to Inverse
59 All models
Definite Minimum Time (IDMT) or Definite Time (DT); the third
stage (U>>>) may be set to DT only.
Three earth fault stages operates from a measured or calculated
(from phase voltage) earth fault voltage value. The first earth All models
fault stage has time-delayed characteristics which are selectable Model L does
59N not have
between inverse definite minimum time (IDMT) and definite time
dedicated
(DT). The second and third stages have a definite time analog input
characteristic only.
Two negative sequence overvoltage stages are provided as
overvoltage protection with independent time-delay
47 characteristics. These characteristics are selectable between N, A
inverse definite minimum time (IDMT) and definite time (DT) for
first stage, second stage can operate only with DT characteristic.
The positive sequence undervoltage element included in the
V11V relays provides two stage non-directional undervoltage
protection with independent time-delay characteristics. These
27D A
characteristics are selectable between inverse definite minimum
time (IDMT) and definite time (DT) for first stage. Second stage
can operate only with DT characteristic.
The frequency element included in the V11V relay provides six
stages of non-directional overfrequency or underfrequency
81U/81O A
protection with independent time-delay characteristics. These
characteristics are only definite time (DT) characteristic.
USB port (in models: A with powering feature) N,A
L(optional),
Rear communication port (RS485)
N,A
V11V/EN IT v1.0 Introduction

(IT) 1-6 VAMP 11V

Function
PROTECTION FUNCTIONS OVERVIEW
available
CB Control via a rear communication port (RS485) or dedicated
NA
binary input
L(0), N(2),
Binary inputs
A(6)
L(4), N(6),
IT Output contacts (Watchdog included)
A(8)
3 timers (AUX) N, A
Comprehensive disturbance recording (waveform capture) A
Time synchronization via binary input A
Circuit breaker status & condition monitoring A

The V11V also offers the following relay management functions in addition to the functions
listed above.

• Up to 20 Fault Records, 5 Alarm Records, 200 Events (if ports are available) (when the
available space is exhausted, the oldest record is automatically overwritten by the new
one)

• Readout of actual settings available via the USB port or rear communication port
(RS485) (if ports are available)

• 2 alternative setting groups

• 3 phase voltage input

• Earth fault voltage input (model N, A)

• CB Control via the front panel menu

• Counters

• Programmable allocation of binary inputs and outputs

• Multi-level password protection

Application overview

Figure 1: Functional diagram of the V11V


Introduction V11V/EN IT v1.0

VAMP V11V (IT) 1-7

3.3 Ordering options Information (Required with Order)


Cortec number

Cortec type: V11V 1 N N N N N 1 1


Voltage Protection Relay.
Three Voltage Inputs (Ph or Ph-Ph)
Flush mounting case, 2x16 LCD display and 8 LEDs,
Close and Trip keys on the front panel
IT
Model
Model L (3 voltages, No Binary Inputs, 4 Binary Outputs) L
Model N (4 voltages, 2 Binary Inputs, 6 Binary Outputs) N
Model A (4 voltages, 6 Binary Inputs, 8 Binary Outputs,
Over/Under frequency protection, A
Back-lit LCD display, RTC back-up capacitor)

Earth Voltage input


Model L: without 0
Model N, A: Uon = 57 - 130Vac 1
Voltage inputs (Ph or Ph-Ph)
Un= 57 - 130Vac 1
Un= 220 - 480Vac 2
Vx Auxiliary Voltage Supply
Model N, A: 24 - 60 Vac/dc 1
Model L: 24-240Vac/dc, Model N, A: 90 - 240 Vac/dc; 2

Communication port / protocol


Model L: Without 0
Model N, A,: USB port and RS485 with settable switching between Modbus and IEC103 via HMI 1
Language
Language: English/ German/ French/ Spanish/ Russian/ Turkish/ Polish 1
Accessories
Without N

3.4 Catalogue numbers for international distribution center ordering


Model Catalogue no. Voltage inputs' range Aux. power supply Cortec code
Model L REL10070 Un = 57-130 Vac Vx = 24 - 240 Vac/250 Vdc V11VL10N1N2N0NN11N
Model L REL10071 Un = 220 - 480 Vac Vx = 24 - 240 Vac/250 Vdc V11VL10N2N2N0NN11N
Model N REL10090 Un = 57-130 Vac Vx = 24 - 60 Vac/dc V11VN11N1N1N1NN11N
Model N REL10091 Un = 220 - 480 Vac Vx = 24 - 60 Vac/dc V11VN11N2N1N1NN11N
Model N REL10092 Un = 57-130 Vac Vx = 90 - 240 Vac/250 Vdc V11VN11N1N2N1NN11N
Model N REL10093 Un = 220 - 480 Vac Vx = 90 - 240 Vac/250 Vdc V11VN11N2N2N1NN11N
Model A REL10080 Un = 57-130 Vac Vx = 24 - 60 Vac/dc V11VA11N1N1N1NN11N
Model A REL10081 Un = 220 - 480 Vac Vx = 24 - 60 Vac/dc V11VA11N2N1N1NN11N
Model A REL10082 Un = 57-130 Vac Vx = 90 - 240 Vac/250 Vdc V11VA11N1N2N1NN11N
Model A REL10083 Un = 220 - 480 Vac Vx = 90 - 240 Vac/250 Vdc V11VA11N2N2N1NN11N
REL10030 Adapter for V11 standard flush mounting case to allow mounting on the wall
REL10031 Front cover with sealing for V11 standard case preventing from unauthorised access
Technical Data V11V/EN TD v1.0

VAMP 11V

TD

TECHNICAL DATA

Date: 1st December 2015


Software Version: 1A
Connection Diagrams: 10V11V01
V11V/EN TD v1.0 Technical Data

VAMP 11V

TD
Technical Data V11V/EN TD v1.0

VAMP 11V (TD) 2-1

CONTENT

1. Mechanical specification 3
1.1 Case 3
1.2 Terminals 3

2. RATINGS 4
2.1 Power Supply 4
TD
2.2 Frequency (Voltage Inputs) 5
2.3 Voltage Inputs 5
2.4 Binary Inputs 6
2.5 Output Relay Characteristics 7

3. INSULATION 8
4. EMC TESTS 9
5. ENVIRONMENT 11
6. EU Directive 12
6.1 EMC Compliance 12
6.2 Product Safety 12

7. DEVIATIONS OF THE PROTECTION ELEMENTS 13


8. Deviations of Automation Functions Timers 15
9. DEVIATIONS OF MEASUREMENTS 15
10. PROTECTION SETTING RANGES 16
10.1 [27] Phase Undervoltage Protection (L, N, A) 16
10.1.1 Protection Setting Ranges 16
10.2 [59] Phase Overvoltage Protection (L, N, A) 17
10.2.1 Protection Setting Ranges 17
10.3 [59N] Residual Overvoltage Protection (L, N, A) 18
10.3.1 Protection Setting Ranges 18
10.4 [47] Negative Sequence Overvoltage Protection (N, A) 1
10.4.1 Protection Setting Ranges 1
10.5 [27D] Positive Sequence Undervoltage Protection (A) 1
10.5.1 Protection Setting Ranges 1
10.6 [81U/81O] Under/Over Frequency Protection (A) 2
10.6.1 Protection Setting Ranges 2

11. AUTOMATION CONTROL FUNCTIONS 3


11.1 Trip Commands 3
11.2 Blocking Logic (N, A) 3
V11V/EN TD v1.0 Technical Data

(TD) 2-2 VAMP V11V

11.3 Output Relays 3


11.4 Latch of the auxiliary Output Relays 3
11.5 Reverse Output Relay Logic 3
11.6 Inputs (N, A) 3
11.6.1 Input Assignation 3
11.6.2 Reverse Input Logic 4
11.7 LEDs 4
11.8 Latch of the LED’s 4
11.9 Auxiliary Timers (N, A) 5
TD
11.10 Circuit Breaker (L, N, A) 6
11.10.1 CB Time Setting Ranges 6
11.10.2 Time-delay for Faulty CB External Signal (A) 6
11.10.3 Remote Control Mode (N, A) 6
11.10.4 Circuit Breaker Control and Monitoring Setting Ranges (A) 6

12. RECORDING FUNCTIONS 7


12.1 Event Records 7
12.2 Fault Records 7
12.3 Disturbance Records (A) 8
12.3.1 Triggers, Data, Setting Ranges 8

13. COMMUNICATION (Model N, A) 9


14. CURVES 10
14.1 General 10
14.1.1 Inverse Time Curves 10
14.1.2 Reset Timer 11
Technical Data V11V/EN TD v1.0

VAMP 11V (TD) 2-3

1. Mechanical specification
1.1 Case

Design Flush mounting case


Weight approx. 0.65 kg

1.2 Terminals
AC Voltage Input Terminals
Threaded M3 screw-type plug-in terminals, with wire protection for conductor cross-section
2
(i) 0.2 - 6 mm single-core
TD
2
(ii) 0.2 - 4 mm finely stranded
General Input/Output Terminals
For power supply, binary and contact inputs, output contacts and COM for rear
communications.
Threaded M3 screw-type plug-in terminals, with wire protection for conductor cross-section
2
(i) 0.2 - 4 mm single-core
2
(ii) 0.2 - 2.5 mm finely stranded
Local communication
USB port
Cable Type: USB 2.0
Connectors:
PC: type A male
V11V: type mini B 5-pin male
USB Cable: minimum 1P*28AWG/2C*24AWG, max : 2m

Rear Communications Port


EIA(RS)485 signal levels, two wire
Connections located on general purpose block, M3 screw
For screened twisted pair cable, distance to be bridged: multi-endpoint link: max. 100 m
Isolation to SELV level.
V11V/EN TD v1.0 Technical Data

(TD) 2-4 VAMP V11V

2. RATINGS
2.1 Power Supply

Nominal auxiliary voltage Vx 24V – 60V dc/ac (50Hz/60Hz) (A and N)


(ordering options) 90V – 240V dc/ac (50Hz/60 Hz) (A and N)
24V – 240V dc/ac (50Hz/60 Hz) (L only)
Operating range 19V – 72V dc, 19V – 66V ac (A and N)
72V - 300V dc, 72V -265V ac (A and N)
19V – 300V dc, 19V – 265V ac (L only)

TD Tolerable AC ripple Up to 12% for a dc supply, per IEC 60255-11: 2008

Nominal Burden Auxiliary Power Supply Vx


Note: (i) Initial position: no output, no LED energized.
(ii) Active position: all outputs and LEDs energized.
For ac Vx voltage max. approx:

Vx S

Vx range VA
V
Initial position Active position

24 3.5 7.5
24V – 60V ac
60 4.5 8.0
110 6.0 10.0
90V – 240V ac
(L, N: 24V -240V ac) 230 10.0 14.5
240 10.2 15.0

For dc Vx voltage max. approx:

Vx range W

Initial position Active position

24V – 60V dc 2.5 5.0


90V – 240V dc
2.5 4.5
(L, N: 24V-240V dc)
Technical Data V11V/EN TD v1.0

VAMP 11V (TD) 2-5

Auxiliary Power EN 60255- Interruption of the ac/dc auxiliary supply without


Supply Voltage 26:2013 de-energizing (TOFF).
Interruption

Vx *TOFF
ac dc
24 V 20 ms 20 ms
48 V 50 ms 30 ms
60 V 90 ms 50 ms
90 V 200 ms 100 ms
TD
110 V 300 ms 150 ms
220 V 1,2 s 600 ms
230 V 1,3 s 700 ms
240 V 1,4 s 750 ms
250 V 1,5 s 800 ms
*4 energized output relays

2.2 Frequency (Voltage Inputs)

Nominal frequency 50 or 60 Hz (selectable in V11V menu)


Operating range (40 ÷ 60) Hz or (50 ÷ 70) Hz

2.3 Voltage Inputs


Phase voltage inputs:

Nominal voltage (Un) (57 ÷ 130) Vph-phac eff or (220 ÷ 480) Vph-phac eff
(dependent on CORTEC number)
Operating range (5 ÷ 200) Vph-phac eff or (20 ÷ 720) Vph-phac eff
Nominal Burden at Un < 0.22 VA at (57 ÷ 130) Vac;
< 0.3 VA at (220 ÷ 480) Vac;
Thermal withstand 10 s @ 300/1300 Vph-phac eff
continuous: 200/720 Vph-phac eff
Connection Refer to section 12 of V11V Installation chapter
(V11V/EN IN)

Earth voltage inputs:

Nominal voltage Uon (57 ÷ 130) Vac


Operating range (5 ÷ 135) Vac
Nominal burden at Uon < 0.43 VA
Thermal withstand 10 s @ 200 Vac
continuous: 135 Vac
Connection Refer to section 12 of V11V Installation chapter
(V11V/EN IN)
V11V/EN TD v1.0 Technical Data

(TD) 2-6 VAMP V11V

2.4 Binary Inputs


Binary inputs type: Optically isolated inputs

Binary Inputs
Filtering Minimum Maximum
time Nominal Voltage polarisation polarisation Maximum
approx. Voltage operating voltage current continuous
range range (Logic 1) withstand
approx. approx.
24 – 19.2 – 16 Vdc 12 mA 110 Vdc
1 40 ms
60 Vac/dc 66 Vac/dc 18 Vac (66V) 78 Vac
TD 2 40 ms
90 – 72 –
66 Vac/dc
2.5 mA 300 Vdc
240 Vac/dc 264 Vac/dc (264V) 264 Vac

Binary input energy consumption


Logic input burden for Vx ordering code 0 R input = approx. 6kOhm
Logic input burden for Vx ordering code 1 R input = approx. 109kOhm
Logic input recognition time As filtering time + 2 ms
Technical Data V11V/EN TD v1.0

VAMP 11V (TD) 2-7

2.5 Output Relay Characteristics

Contact ratings
Contact relay Dry contact, Ag Ni
Carry capability 5 A continuous
Rated Voltage 250 Vac
Breaking characteristics for RL1, RL2, RL3 and WD
Short-duration capacity 25 A for 3 s
Making capacity 150 A for 30 ms
AC breaking capacity 1250 VA resistive (cos φ = unity) TD
1250 VA inductive (cos φ = 0.7)
DC breaking capacity 250 Vdc;
50 W resistive
25 W inductive (L/R = 40 ms)
Operation time <10ms
Durability
Loaded contact 10 000 operations minimum
Unloaded contact 100 000 operations minimum
Breaking characteristics for RL4, RL5, RL6, RL7
Short-duration capacity 25 A for 3 s
Making capacity 150 A for 30 ms
AC breaking capacity 1250 VA resistive (cos φ = unity)
1250 VA inductive (cos φ = 0.7)
DC breaking capacity 250 Vdc;
50 W resistive
25 W inductive (L/R = 40 ms)
Operation time <10ms
Durability
Loaded contact 10 000 operations minimum
Unloaded contact 100 000 operations minimum
V11V/EN TD v1.0 Technical Data

(TD) 2-8 VAMP V11V

3. INSULATION
Insulation resistance EN 60255-27: 2014 > 100 MΩ at 500 Vdc
(Using only electronic/brushless insulation
tester).
High Voltage 2 kV RMS AC, 1 minute:
(Dielectric) Between all case terminals connected
Withstand together and the case earth.
Between all terminals of independent circuits
with terminals on each independent circuit
connected together (USB port excluded).
TD Impulse Voltage Front time: 1.2 µs, Time to half-value: 50 µs,
Withstand Test Peak value: 5 kV
Source Characteristics: 500 Ohm, 0.5 J.
Common and differential mode: power supply,
terminal block (excluding RS485), binary
inputs, relays
Creepage Distances Pollution degree 2,
and Clearances Overvoltage category III,
Impulse test voltage 5 kV.
Technical Data V11V/EN TD v1.0

VAMP 11V (TD) 2-9

4. EMC TESTS
1 MHz Burst High EN 60255 - 26: 2013 Common-mode test voltage: 2.5 kV,
Frequency EN61000-4-18: 2010 Differential test voltage: 1.0 kV,
Disturbance Test
Level 3 Test duration: 2 s,
Source impedance: 200 Ω
Immunity to EN61000-4-2: 2009 8 kV discharge in air to all communication
Electrostatic Level 3 ports.
Discharge 6 kV point contact discharge to any part of the
front of the product.
Electrical Fast EN61000-4-4: 2012 Amplitude: 2 kV, TD
Transient or Burst Level 3 Burst frequency 5 kHz (Class III)
Requirements
Surge Immunity Test EN61000-4-5: 2014 Time to half-value: 1.2/50 µs,
Level 3 Amplitude: 2 kV between all groups and case
earth,
Amplitude: 1 kV between terminals of each
group
Immunity to Radiated EN61000-4-3: 2010 Test field strength, frequency band:
Electromagnetic - 80 MHz to 1000 MHz: 10 V/m,
Energy
- 1.4 GHz to 2.7 GHz: 10 V/m
Test using AM: 1 kHz / 80% sinus
Spot frequencies:
80MHz, 160MHz, 380MHz, 450MHz, 900MHz,
1850MHz, 2150MHz
80 % AM, 1kHz, 100% (duty cycle)
Radiated Immunity 10 V/m, 900 MHz 100% AM, 200 Hz/50%
from Digital Radio square wave
Telephones
Immunity to EN61000-4-6: 2014 Disturbing test voltage: 10 V, 150 kHz to
Conducted 80 MHz, 80% AM, 1 kHz
Disturbances Induced Spot frequencies: 27 MHz, 68 MHz
by Radio Frequency
Fields
Power Frequency EN61000-4-8: 2010 50Hz, 30 A/m - 1 minute for each position
Magnetic Field Level 4 50Hz, 300 A/m - 3 seconds for each position
Immunity
Network frequency 50Hz, 1000A/m – 1 seconds for each position
(50Hz)
electromagnetic fields
immunity test
Pulse magnetic fields EN61000-4-9: 2010 6,4/16 µs magnetic pulse 1000A/m.
immunity test Applied to enclosure.
Level 5
Conducted Emissions EN55022: 2011 0.15 MHz - 0.5 MHz, 79 dBµV (quasi peak)
(CISPR 22) 66 dBµV (average);
Class A 0.5 MHz - 30 MHz, 73 dBµV (quasi peak)
60 dBµV (average)
Radiated Emissions EN55022: 2011 30 MHz - 230 MHz, 40 dBµV/m at 10 m
(CISPR 11) measurement distance;
Class A 230 MHz - 1 GHz, 47 dBµV/m at 10 m
measurement distance
1 - 2 GHz, 76 dBµV/m at 3 m
measurement distance
V11V/EN TD v1.0 Technical Data

(TD) 2-10 VAMP V11V

AC and DC voltage EN 60255 - 26: 2013 0%xUT residual voltage,


dips 10ms, 20ms, 50ms, 100ms, 200ms, 500ms
EN61000-4-29: 2000
(ac/dc)
EN61000-4-11: 2004
40%xUT residual voltage,
200ms (50Hz), 200 ms(60Hz)
200ms (dc)

70%xUT residual voltage,


500ms (50Hz), 500 ms(60Hz)
500ms (dc)
AC and DC voltage EN61000-4-29: 2000 0%xUT residual voltage,
5s (50Hz), 5s (60Hz)
TD interruptions EN61000-4-11: 2004
5s (dc)
AC component in DC EN61000-4-17: 2009 15% of rated DC value
(ripple) 100 Hz and 120 Hz / 600 s

Gradual shut- EN61000-4-29: 2000 Shut-down ramp 60s


down/start –up
power off 5min
(for DC power supply)
start-up ramp 60s
Technical Data V11V/EN TD v1.0

VAMP 11V (TD) 2-11

5. ENVIRONMENT
Ambient EN 60255-1: 2010 Operating temperature range: -20°C to +60°C
Temperature EN60068-2-2 Bd: (–4°F to +140°F),
Range 2007 Storage and transit: –25°C to +70°C
EN60068-2-1 Ad: (–13°F to +158°F).
2007
Ambient EN 60068-2-78: Cab: 56 days at 93% relative humidity and +40°C.
Humidity 2013
Range
EN 60068-2-30: Db: Damp heat cyclic, six (12 + 12) hour cycles,
2005 93% RH, +25 to +55°C
TD
Vibration Test EN 60255-21-1: 1995 Response Class 1
Endurance Class 1
Shock and EN 60255-21-2: 1995 Shock response Class 1
Bump Shock withstand Class 1
Bump Class 1
Seismic EN 60255-21-3:1995 Class 2
Enclosure EN 60529: 2000 IP 40 Protection for relay housing
Protection IP 20 Protection for terminals.
IP 54 Protection (front panel) against dust and
dripping water for flash mounted case.
V11V/EN TD v1.0 Technical Data

(TD) 2-12 VAMP V11V

6. EU Directive
6.1 EMC Compliance

2014/30/EU

Compliance with the European Commission's EMC Directive.


Product Specific Standards were used to establish conformity:

− EN 60255-26: 2013
TD − EN 60255-1: 2010
6.2 Product Safety

2014/35/EU

Compliance with the European Commission's Low Voltage Directive. Compliance is


demonstrated by reference to generic safety standards:

− EN60255-27:2014
Technical Data V11V/EN TD v1.0

VAMP 11V (TD) 2-13

7. DEVIATIONS OF THE PROTECTION ELEMENTS


Glossary
U1, U2, U3: measured value of AC Voltage Inputs U1, U2, U3
Umax : max (U1, U2, U3)
Vs : setting value for V>, V>>, V>>>, V<, V<<, V<<<
V1s : setting value for V1<, V1<<
V2s : setting value for V2>, V2>>
fs : setting value for f1, f2, f3, f4, f5, f6
Ves : setting value for VN>, VN>>, VN>>>
DT : Definite time TD
IDMT : Inverse definite minimum time

Reference voltage (Un):


Un = 57V – 130V
Un = 220V – 480V

PROTECTION FUNCTIONS TIME DETAILS


Retardation Drop off
Element 1
time time
V>, V>>, V>>>, V<, V<<,
Voltage protection
V<<<
Residual voltage protection VN>, VN>>, VN>>>
≤ 50ms ≤ 50ms
Positive sequence undervoltage V1<, V1<<
protection V2>, V2>>
Negative sequence overvoltage
protection
Frequency protection f1, f2, f3, f4, f5, f6 ≤ 50ms ≤ 80ms
1 - Retardation time – see V11V/EN SG chapter.
V11V/EN TD v1.0 Technical Data

(TD) 2-14 VAMP V11V

Functions Range Operate (Deviation) Reset (Deviation) Time deviation


1
Undervoltage DT: DT: DT :
protection (5÷200)V Vs (±2%Vs ±0.2V) ((settable) 1.00÷1.20) ±(2% + 60 ms)
(V<, V<<, V<<<) (20÷720)V Vs (±2%Vs ±2V) Vs (±3%)
2
IDMT: IDMT: IDMT :
0.9Vs (±2%Vs) 0.95Vs (±2%Vs) ±(4% + 40 ms)
1
Overvoltage DT: DT: DT :
protection (5÷200)V Vs (±2%Vs ±0.2V) ((settable) 0.80÷1.00) ±(2% + 60 ms)
(V>, V>>, V>>>) (20÷720)V Vs (±2%Vs ±2V) Vs (±3%)
2
IDMT: IDMT: IDMT :
1.1Vs (±2%Vs) 1.05Vs (±2%Vs) ±(4% + 40 ms)
1
Residual voltage (0.5÷130)V DT: DT: DT :
TD protection
(VN>, VN>>,
Direct
measurement
Ves (±2%Ves ±0.2V)
IDMT:
0.95Vs (±2%)
IDMT:
±(2% + 60 ms)
2
VN>>>) 1.1Ves (±2%Ves) 1.05Ves (±2%Ves) IDMT :
±(4% + 40 ms)
1
Residual voltage (0.5÷130)V DT :
protection Calculated for Un DT: DT: ±(3% + 60 ms)
(VN>, VN>>, (5÷200)V Ves (±3%Umax ±0.5V) 0.95Ves (±3%)
2
VN>>>) (20÷720)V Ves (±3%Umax ±4V) IDMT :
IDMT: IDMT: ±(7% + 60 ms)
1.1Ves (±3%Umax) 1.05Ves (±3%Umax)
1
Positive sequence DT: DT: DT :
undervoltage V1s (±3%Umax ±0.5V) 1.05V1s (±3%) ±(2% + 60 ms)
(5÷200)V
protection V1s (±3%Umax ±2V)
(20÷720)V 2
(V1<, V1<<) IDMT: IDMT: IDMT :
0.9V1s (±3%Umax) 0.95V1s (±3%Umax) ±(4% + 40 ms)
1
Negative sequence DT: DT: DT :
overvoltage V2s (±3%Umax ±0.5V) 0.95V2s (±3%) ±(2% + 60 ms)
(5÷200)V
protection V2s (±3%Umax ±2V)
(20÷720)V 2
(V2>, V2>>) IDMT: IDMT: IDMT :
1.1V2s (±3%Umax) 1.05V2s (±3%Umax) ±(4% + 40 ms)
Under/Over (40-70)Hz
fs (±10mHz)
frequency U≥ 0.5Un Fs+50mHz/-50mHz
±(2% + 25 ms)
(±10mHz)
fs (±50mHz)
0.1Un<U<0.5Un (±50mHz)
1. During investigation of operation time - injection value must be 2 times greater than setting value.
2. According to standard IEC 60255-151. For UK Rectifier (Rect) characteristic: ±(12% + 40 ms).
Technical Data V11V/EN TD v1.0

VAMP 11V (TD) 2-15

8. Deviations of Automation Functions Timers


Automation Function Timers
CB monitoring timers Greater of ± 2% or ± 30ms

Auxiliary timers tAUX1, tAUX2, tAUX3, tAUX4, tVTS Greater of 2% or (+35ms…+55ms)

9. DEVIATIONS OF MEASUREMENTS TD
Measurement Range Deviation
± (2% of rdg + 2 digits)
1
Voltage / Residual voltage (57 ÷ 130) Vac
(220 ÷ 480) Vac
Frequency (40 ÷ 60) Hz ±10 mHz
(50 ÷ 70) Hz
1. rdg: reading (the read-in value)
digit: the smallest value that can be displayed
V11V/EN TD v1.0 Technical Data

(TD) 2-16 VAMP V11V

10. PROTECTION SETTING RANGES


Note: (L, N, A) – available in Model L, N and A
10.1 [27] Phase Undervoltage Protection (L, N, A)

− Phase to Phase or Phase to neutral Voltage Fundamental


10.1.1 Protection Setting Ranges

Setting Range
[27] Undervoltage
Min. Max. Step

TD V< ? Disabled, OR Trip, OR Alarm, AND Trip, AND Alarm, OR


Trip/52a, OR Alarm/52a, AND Trip/52a, AND Alarm/52a
V< 5 V for range (57-130)V 130 V 0.1 V
20 V for range (220-480)V 480 V 0.5 V
Delay type DT or IDMT (IEC_SI, IEC_VI, IEC_EI, IEC_LTI, UK_STI,
C02_P20, US_ C08, IEEE_MI, IEEE_VI, IEEE_EI, RXIDG,
BPN EDF, RI, RECT, C02_P40 curve)
tV< 0.02 s 200 s 0.01 s
V< TMS 0.02 1.50 0.01
V< TD 0.02 100 0.01
V< Reset Delay Type DT or IDMT (refer to Operation chapter)
DMT V< tReset 0.00 s 600 s 0.01 s
K (RI) 0.1 10 0.1
V<< ? Disabled, OR Trip, OR Alarm, AND Trip, AND Alarm, OR
Trip/52a, OR Alarm/52a, AND Trip/52a, AND Alarm/52a
V<< 5 V for range (57-130)V 130 V 0.2 V
20 V for range (220-480)V 480 V 0.5 V
Delay type DT or IDMT (IEC_SI, IEC_VI, IEC_EI, IEC_LTI, UK_STI,
C02_P20, US_ C08, IEEE_MI, IEEE_VI, IEEE_EI, RXIDG,
BPN EDF, RI, RECT, C02_P40 curve)
tV<< 0.02 s 200 s 0.01 s
V<< TMS 0.02 1.50 0.01
V<< TD 0.02 100 0.01
V<< Reset Delay DT or IDMT (refer to Operation chapter)
Type
DMT V<< tReset 0.00 s 600 s 0.01 s
K (RI) 0.1 10 0.1
V<<< ? Disabled, OR Trip, OR Alarm, AND Trip, AND Alarm, OR
Trip/52a, OR Alarm/52a, AND Trip/52a, AND Alarm/52a
V<<< 5 V for range (57-130)V 130 V 0.2 V
20 V for range (220-480)V 480 V 0.5 V
tV<<< 0.02 s 200 s 0.01 s
Technical Data V11V/EN TD v1.0

VAMP 11V (TD) 2-17

10.2 [59] Phase Overvoltage Protection (L, N, A)

− Phase to Phase or Phase to neutral Voltage Fundamental


10.2.1 Protection Setting Ranges

Setting Range
[59] Overvoltage
Min. Max. Step
V> ? Disabled, OR Trip, OR Alarm, AND Trip, AND Alarm, OR
Trip/52a, OR Alarm/52a, AND Trip/52a, AND Alarm/52a
V> 5 V for range (57-130)V 200 V 0.1 V
20 V for range (220-480)V 720 V 0.5 V TD
Delay type DT or IDMT (IEC_SI, IEC_VI, IEC_EI, IEC_LTI, UK_STI,
C02_P20, US_ C08, IEEE_MI, IEEE_VI, IEEE_EI, RXIDG,
BPN EDF, RI, RECT, C02_P40 curve)
tV> 0.02 s 200 s 0.01 s
V> TMS 0.02 1.50 0.01
V> TD 0.02 100 0.01
V> Reset Delay Type DT or IDMT (refer to Operation chapter)
DMT V> tReset 0.00 s 600 s 0.01 s
K (RI) 0.1 10 0.1
V>> ? Disabled, OR Trip, OR Alarm, AND Trip, AND Alarm, OR
Trip/52a, OR Alarm/52a, AND Trip/52a, AND Alarm/52a
V> > 5 V for range (57-130)V 200 V 0.1 V
20 V for range (220-480)V 720 V 0.5 V
Delay type DT or IDMT (IEC_SI, IEC_VI, IEC_EI, IEC_LTI, UK_STI,
C02_P20, US_ C08, IEEE_MI, IEEE_VI, IEEE_EI, RXIDG,
BPN EDF, RI, RECT, C02_P40 curve)
tV> > 0.02 s 200 s 0.01 s
V>> TMS 0.02 1.50 0.01
V>> TD 0.02 100 0.01
V>> Reset Delay DT or IDMT (refer to Operation chapter)
Type
DMT V>> tReset 0.00 s 600 s 0.01 s
K (RI) 0.1 10 0.1
V>>> ? Disabled, OR Trip, OR Alarm, AND Trip, AND Alarm, OR
Trip/52a, OR Alarm/52a, AND Trip/52a, AND Alarm/52a
V>>> 5 V for range (57-130)V 200 V 0.1 V
20 V for range (220-480)V 720 V 0.5 V
tV>>> 0.02 s 200 s 0.01 s
V11V/EN TD v1.0 Technical Data

(TD) 2-18 VAMP V11V

10.3 [59N] Residual Overvoltage Protection (L, N, A)

− Earth fault voltage Fundamental

− Earth fault voltage ranges See following table

− Ua+Ub+Uc Derived voltage


10.3.1 Protection Setting Ranges

Setting Range
[59] Overvoltage
Min. Max. Step
VN> ? Disabled, Trip (measured), Alarm (measured), Trip
TD (Ua+Ub+Uc), Alarm (Ua+Ub+Uc)
VN> 0.5 V 130 V 0.1 V

Delay type DT or IDMT (IEC_SI, IEC_VI, IEC_EI, IEC_LTI,


UK_STI, C02_P20, US_ C08, IEEE_MI, IEEE_VI,
IEEE_EI, RXIDG, BPN EDF, RI, RECT, C02_P40
curve)
tVN> 0.02 s 200 s 0.01 s
VN> TMS 0.02 1.50 0.01
VN> TD 0.02 100 0.01
VN> Reset Delay DT or IDMT (refer to Operation chapter)
Type
DMT VN> tReset 0.00 s 600 s 0.1 s
K (RI) 0.1 10 0.1
VN>> ? Disabled, Trip (measured), Alarm (measured), Trip
(Ua+Ub+Uc), Alarm (Ua+Ub+Uc)
VN>> 0.5 V 130 V 0.1 V

tVN>> 0.02 s 200 s 0.01 s


VN>>> ? Disabled, Trip (measured), Alarm (measured), Trip
(Ua+Ub+Uc), Alarm (Ua+Ub+Uc)
VN>>> 0.5 V 130 V 0.1 V

tVN>>> 0.02 s 200 s 0.01 s


Technical Data V11V/EN TD v1.0

VAMP 11V (TD) 2-1

10.4 [47] Negative Sequence Overvoltage Protection (N, A)

− Phase Voltage: Fundamental


10.4.1 Protection Setting Ranges

[47] Negative Setting Range


Sequence OV Min. Max. Step
V2> ? Disabled, Trip, Alarm, Trip/52a, Alarm/52a
V2> 5 V for range (57-130)V 200 V 0.1 V
20 V for range (220-480)V 720 V 0.5 V
Delay type DT or IDMT (IEC_SI, IEC_VI, IEC_EI, IEC_LTI, UK_STI, TD
C02_P20, US_ C08, IEEE_MI, IEEE_VI, IEEE_EI, RXIDG,
BPN EDF, RI, RECT, C02_P40 curve)
tV2> 0.02 s 200 s 0.01 s
V2> TMS 0.02 1.50 0.01
V2> TD 0.02 100 0.01
V2> Reset Delay DT or IDMT (refer to Operation chapter)
Type
DMT U2> tReset 0.00 s 600 s 0.01 s
K (RI) 0.1 10 0.1
V2>> ? Disabled, Trip, Alarm, Trip/52a, Alarm/52a
V2>> 5 V for range (57-130)V 200 V 0.1 V
20 V for range (220-480)V 720 V 0.5 V
tV2>> 0.02 s 200 s 0.01 s
Technical Data V11V/EN TD v1.0

VAMP 11V (TD) 2-1

10.5 [27D] Positive Sequence Undervoltage Protection (A)

− Phase to Phase or Phase to neutral Voltage : Fundamental


10.5.1 Protection Setting Ranges

[27D] Positive Setting Range


Sequence UV Min. Max. Step
V1< ? Disabled, Trip, Alarm, Trip/52a, Alarm/52a
V1< 5 V for range (57-130)V 130 V 0.1 V
20 V for range (220-480)V 480 V 0.5 V
Delay type DT or IDMT (IEC_SI, IEC_VI, IEC_EI, IEC_LTI, UK_STI, TD
C02_P20, US_ C08, IEEE_MI, IEEE_VI, IEEE_EI, RXIDG,
BPN EDF, RI, RECT, C02_P40 curve)
tV1< 0.02 s 200 s 0.01 s
V1< TMS 0.02 1.50 0.01
V1< TD 0.02 100 0.01
V1< Reset Delay DT or IDMT (refer to Operation chapter)
Type
DMT V1< tReset 0.00 s 600 s 0.01 s
K (RI) 0.1 10 0.1
V1<<? Disabled, Trip, Alarm, Trip/52a, Alarm/52a
V1<< 5 V for range (57-130)V 130 V 0.1 V
20 V for range (220-480)V 480 V 0.5 V
tV1<< 0.02 s 200 s 0.01 s
V11V/EN TD v1.0 Technical Data

(TD) 2-2 VAMP V11V

10.6 [81U/81O] Under/Over Frequency Protection (A)


10.6.1 Protection Setting Ranges

Setting ranges
[81U/O] Frequency
Min. Max. Step
f1? Disabled, f> Trip, f> Alarm, f< Trip,
f< Alarm
f1 fn-10 Hz fn+10 Hz 0.01 Hz
tf1 0.1 s 600.00 s 0.01 s
TD f2? Disabled, f> Trip, f> Alarm, f< Trip,
f< Alarm
f2 fn-10 Hz fn+10 Hz 0.01 Hz
tf2 0.1 s 600.00 s 0.01 s
f3? Disabled, f> Trip, f> Alarm, f< Trip,
f< Alarm
f3 fn-10 Hz fn+10 Hz 0.01 Hz
tf3 0.1s 600.00 s 0.01 s
f4? Disabled, f> Trip, f> Alarm, f< Trip,
f< Alarm
f4 fn-10 Hz fn+10 Hz 0.01 Hz
tf4 0.1 s 600.00 s 0.01 s
f5? Disabled, f> Trip, f> Alarm, f< Trip,
f< Alarm
f5 fn-10 Hz fn+10 Hz 0.01 Hz
tf5 0.1 s 600.00 s 0.01 s
f6? Disabled, f> Trip, f> Alarm, f< Trip,
f< Alarm
f6 fn-10 Hz fn+10 Hz 0.01 Hz
tf6 0.1 s 600.00 s 0.01 s

Where fn is nominal frequency.


Technical Data V11V/EN TD v1.0

VAMP 11V (TD) 2-3

11. AUTOMATION CONTROL FUNCTIONS


Note: (L, N, A) – available in Model L, N and A

11.1 Trip Commands


The following protection elements may be set to 'Disabled', 'Trip' or 'Alarm’, for each option with
state control of the connector and possibility of work from fault in 3 phases (AND) or for fault in
any one phase (OR): tV>, tV>>, tV>>>, tV<, tV<<, tV<<<, tV1<(A), tV1<<(A), tV2>(N, A),
tV2>>(N, A).
The following protection elements may be set to 'Disabled', 'Trip' or 'Alarm’, for each option with
possibility of work from measured value or calculated : tVN>, tVN>>, tVN>>>.
TD
The following protection elements may be set to 'Disabled', 'Trip' or 'Alarm, for each option
under or over type: tf1(A), tf2(A), tf3(A), tf4(A), tf5(A), tf6(A).
The following protection elements may be set to 'Disabled', 'Trip' or 'Alarm: tAUX1, tAUX2,
tAUX3.
11.2 Blocking Logic (N, A)
In V11V, we have tree ways to block protections: by input, VTS or state control of connector.

The following time-delayed stages may be blocked by input:

− tV>, tV>>, tV>>>, tV<, tV<<, tV<<<, tV1<(A), tV1<<(A), tV2>, tV2>>, tVN>, tVN>>,
tVN>>>, tf1(A), tf2(A), tf3(A), tf4(A), tf5(A), tf6(A).
The following stages may be blocked by VTS:

− V>, V>>, V>>>, V<, V<<, V<<<, V1<(A), V1<<(A), V2>, V2>>, VN>, VN>>, VN>>>, f1(A),
f2(A), f3(A), f4(A), f5(A), f6(A).
The following stages may be blocked by state control of connector:

− VTS, V>, V>>, V>>>, V<, V<<, V<<<, V1<(A), V1<<(A), V2>, V2>>, VN>, VN>>, VN>>>.

11.3 Output Relays


Assignable functions: Protection Trip, Protection Trip (pulse), Trip CB Order, Close CB Order,
Alarm, Start V>, Start V>>, Start V>>>, Start V<, Start V<<, Start V<<<, Start V1<(A), Start
V1<<(A), Start V2>(N, A), Start V2>>(N, A), Start VN>, Start VN>>, Start VN>>>, Start f1(A),
Start f2(A), Start f3(A), Start f4(A), Start f5(A), Start f6(A), AUX1, AUX2, AUX3, AUX4, AUX5,
tV>, tV>>, tV>>>, tV<, tV<<, tV<<<, tV1<(A), tV1<<(A), tV2>(N, A), tV2>>(N, A), tVN>, tVN>>,
tVN>>>, tf1(A), tf2(A), tf3(A), tf4(A), tf5(A), tf6(A), tAUX1, tAUX2, tAUX3, CB Alarm, tCB Faulty
ext., Setting Group 1, tVTS, tfout.
11.4 Latch of the auxiliary Output Relays
All output relays (WD not included) can be latched.
11.5 Reverse Output Relay Logic
All logic of the output relays can be reversed.
Note: Reverse logic means that if a function assigned to outputs is disabled the
contact is closed. If the function is enabled the contact is opened.
11.6 Inputs (N, A)
11.6.1 Input Assignation
A single function or multiple automation functions can be assigned to 2(N) or 6(A) logic inputs:
None, Maintenance Mode, Reset Latched Signaling, Reset Latched Outputs, Blocking tV>,
Blocking tV>>, Blocking tV>>>, Blocking tV<, Blocking tV<<, Blocking tV<<<, Blocking tV1<(A),
Blocking tV1<<(A), Blocking tV2>, Blocking tV2>>, Blocking tVN>, Blocking tVN>>, Blocking
V11V/EN TD v1.0 Technical Data

(TD) 2-4 VAMP V11V

tVN>>>, Blocking tf1(A), Blocking tf2(A), Blocking tf3(A), Blocking tf4(A), Blocking tf5(A),
Blocking tf6(A), AUX1, AUX2, AUX3, AUX4, AUX5, CB Status 52a, CB Status 52b, CB FLT
External Signalling, Setting Group 2, Manual Close, Manual Trip, VTS, Start Disturber
Recorder, Local CTRL Mode, Time Synchronization.
11.6.2 Reverse Input Logic
The logic of the inputs can be reversed: Input L1 and L2 (N) or L1 to L6 (A)
Note: Reverse logic means that if an input is energized, the function assigned to this input is
disabled. If the input is not energized, the function is enabled.
11.7 LEDs

TD Assignable functions: Alarm, Start V>, Start V>>, Start V>>>, Start V<, Start V<<, Start V<<<,
Start V1<(A), Start V1<<(A), Start V2>(N, A), Start V2>>(N, A), Start VN>, Start VN>>, Start
VN>>>, Start f1(A), Start f2(A), Start f3(A), Start f4(A), Start f5(A), Start f6(A), AUX1, AUX2,
AUX3, AUX4, AUX5, tV>, tV>>, tV>>>, tV<, tV<<, tV<<<, tV1<(A), tV1<<(A), tV2>(N, A),
tV2>>(N, A), tVN>, tVN>>, tVN>>>, tf1(A), tf2(A), tf3(A), tf4(A), tf5(A), tf6(A), tAUX1, tAUX2,
tAUX3, Local CTRL mode, CB Alarm, Maintenance, tCB Faulty External Signalling, Setting
Group 2, tVTS, tfout.
11.8 Latch of the LED’s
All LED’s can be latched.
Technical Data V11V/EN TD v1.0

VAMP 11V (TD) 2-5

11.9 Auxiliary Timers (N, A)

Setting range
Auxiliary timers G1/G2
Min. Max. Step
Aux1 ? Disabled , Trip, Alarm
Time-delay tAux1 0 600 s 10 ms
Aux2 ? Disabled , Trip, Alarm
Time-delay tAux2 0 600 s 10 ms
Aux3? Disabled , Trip, Alarm
Time-delay tAux3 0 600 s 10 ms TD
V11V/EN TD v1.0 Technical Data

(TD) 2-6 VAMP V11V

11.10 Circuit Breaker (L, N, A)


11.10.1 CB Time Setting Ranges

Setting range
CB Control Time Model
Min. Max. Step
tOpen Pulse min All models 0.1 s 10 s 0.01 s
tClose Pulse All models 0.1 s 10 s 0.01 s
Time-delay for Close A 0.0 s 200 s 0.01 s

11.10.2 Time-delay for Faulty CB External Signal (A)


TD
CB Faulty External Setting range
Monitoring Min. Max. Step
tCB FLT ext 1s 200 s 1s

11.10.3 Remote Control Mode (A)

Remote Control Mode Setting range

Remote CTRL Mode Remote only


Remote + Local

11.10.4 Circuit Breaker Control and Monitoring Setting Ranges (A)

Setting range
CB Supervision
Min. Max. Step
CB Time Supervision? Yes or No
CB Open time 0.01 s 10 s 0.01 s
CB Close time 0.01 s 10 s 0.01 s
Technical Data V11V/EN TD v1.0

VAMP 11V (TD) 2-7

12. RECORDING FUNCTIONS


12.1 Event Records
(not available in model L)

Capacity 200 events


Time-tag 1 millisecond
Triggers Any selected protection alarm and threshold
Logic input change of state
Setting changes
Self test events
TD
12.2 Fault Records

Capacity 20 faults
Time-tag 1 millisecond
Triggers Any selected protection which trip CB
Data Fault date
Protection thresholds
Setting Group
AC inputs measurements (RMS)
Fault measurements
V11V/EN TD v1.0 Technical Data

(TD) 2-8 VAMP V11V

12.3 Disturbance Records (A)


12.3.1 Triggers, Data, Setting Ranges

Disturbance Records Total record: up to 4s, but not more than 5 records
Triggers Any selected protection alarm and threshold, logic input, remote
command
Data AC input channels 16 sample per cycle
digital input and output states
Default value Setting range
TD Min. Max. Step
Pre-fault Time 0.1 0.1 2 0.01
Post-fault Time 0.1 0.1 1 0.01
Max record time 1.5 0.10 4 0.01
Disturb record Trig on Inst on Trip or on Inst.
Trigger Protection selected for tripping, Logic input (Start Distur.R.)
Technical Data V11V/EN TD v1.0

VAMP 11V (TD) 2-9

13. COMMUNICATION (Model N, A)


Type Physical
Connectors Data Rate Comms. mode Protocol
Port Link
RS485 Screened Screws or 4.8 or 9.6 or 19.2 or Data Bit: 8 Modbus RTU,
twisted snap-on 38.4 or 57.6 or Stop bit: 1/ 2 IEC60870-5-103
pair 115.2 kbits/s (selectable in
Parity: None/Odd/Even
(default:19.2 kbit/s) menu)
Adress: 1 to 247 for
Modbus
Adress: 1 to 254 for
IEC60870-5-103 TD
USB USB2.0 PC: type A 115.2 kbits/s Data Bit:8 Modbus RTU
male (fixed) Stop bit: 1
V11V: type Parity: None
mini B male
Adress: 1
V11V/EN TD v1.0 Technical Data

(TD) 2-10 VAMP V11V

14. CURVES
14.1 General

Although the curves tend towards infinite when the voltage approaches Vs (general threshold),
the minimum guaranteed value of the operating voltage for all the curves with the inverse time
characteristic is 1.1 Vs (with a tolerance of ± 0.05 Vs).
14.1.1 Inverse Time Curves
Some stage of protection functions can be selected (refer to settings options) with an inverse
definite minimum time (IDMT) characteristic. The time-delay is calculated using a mathematical
formula.
TD In all, there are fifteen IDMT characteristics available.
The mathematical formula applicable to the first ten curves is:

 
 
 k 
t = TMS ×  α
+ c
  G  − P 
 Gs 
   
Where:
t Operation time
k, c, α, P Constant (see table)
G Value of measured voltage
Gs Value of the programmed threshold (pick-up value)
TMS Time multiplier setting (for IEC: TMS; IEEE: TD)

Type of curve
(according to IEC60255- Standard k c α P
151 std definition)
IEC Standard inverse (SI) IEC/A 0.14 0 0.02 1
IEC Very inverse (VI) IEC/B 13.5 0 1 1
IEC Extremely inverse (EI) IEC/C 80 0 2 1
Long time inverse (LTI) IEC 120 0 1 1
FR Short time inverse (STI) FR 0.05 0 0.04 1
US Short time inverse C02 P20 0.02394 0.01694 0.02 1
US Short time inverse C02 P40 0.16758 0.11858 0.02 1
Long time inverse C08 5.848 0.1654 2 1
IEEE Moderately Inverse IEEE 0.0515 0.114 0.02 1
IEEE Very inverse IEEE 19.61 0.491 2 1
IEEE Extremely inverse IEEE 28.2 0.1217 2 1
UK Rectifier protection RECT 45900 0 5.6 1
BNP (EDF) EDF 1000 0.655 2 1
RI -4.2373 0 -1 1.43644

Note: For RI curve the equation is valid for the range: 1.1 ≤ V/Vs ≤ 20
Technical Data V11V/EN TD v1.0

VAMP 11V (TD) 2-11

RXIDG Curves
The first earth thresholds can be selected with dedicated RXIDG curves.
The curves available follow the formula:
t = 5.8 – 1.35 * Un ( 1/ (k * Vs/V))
Where:
t = tripping time
k = coefficient (from 0.3 to 1, by steps of 0.01)
TD
Vs = value of the programmed threshold (Pick-up value)
V = value of measured voltage

14.1.2 Reset Timer


Some stage of protection functions are provided with a timer hold facility: "tReset".
The value that is set for this reset timer corresponds to the minimum time during which the
voltage value needs to be lower than 95% of the phase (or earth) threshold before the
corresponding phase (or earth) time-delay is reset.
Note: There is an exception to this rule when the protection triggers. In fact, in
that case, the time-delays are immediately reset.
The value of the Reset Timer depends on the type of timer associated with the pick-up of the
first phase (or earth) stage.

Type of timer Reset Timer

DMT Reset
IDMT characteristic
characteristic
DMT, Rectifier, LTI, STI, Settable from 0 to 600 ms Not available. If IDMT is
Rectifier, BNP EDF, RXIDG selected: reset timer is set to
0s (see table below: K=0)
IDMT IEC or RI Settable from 0 to 600 ms Based on RTMS value
(refer to Operation chapter)
IDMT IEEE or CO Settable from 0 to 600 ms Based on RTD value
(refer to Operation chapter)

Reset timer:
The first phase, earth and negative sequence overvoltage stages are provided with a timer hold
facility: "t Reset".
It may be set to a definite time value or to an inverse definite minimum time characteristic
(IEC/IEEE/ANSI curves only). This may be useful in certain applications, for example when
grading with upstream electromechanical overcurrent relays that have inherent reset time-
delays.
The second and third earth fault stages have only a definite time reset.
A possible situation where the reset timer may be used is to reduce fault clearance times where
intermittent faults occur.
An example may occur in a cable with plastic insulation. In this application it is possible that the
fault energy melts the cable insulation, which then reseals after clearance, thereby eliminating
the cause for the fault. This process repeats itself to give a succession of fault current pulses,
V11V/EN TD v1.0 Technical Data

(TD) 2-12 VAMP V11V

each of increasing duration with reducing intervals between the pulses, until the fault becomes
permanent.
When the reset time of the overvoltage relay is set to its minimum, the relay will be repeatedly
reset and will not be able to trip until the fault becomes permanent. By using the reset timer hold
function the relay will integrate the fault current pulses, thereby reducing the fault clearance
time.
The mathematical formula applicable to the five curves is:
 
 
 tr 
t = RT ×  p 

TD  1 −  G  
 
  Gs  
Where:
t Reset time
tr, p Constant (see table)

G Value of the measured voltage

Gs Value of the programmed threshold (pick-up value)


RT Reset time multiplier (RTMS for IEC or RTD for IEEE/US) setting between 0.025 and
1.5.

Type of curve Standard tr p


US Short time inverse C02_P40 2.261 2
US Short time inverse C02_P20 2.261 2
Long time inverse C08 5.95 2
IEEE Moderately inverse (MI) IEEE 4.9 2
IEEE Very inverse (VI) IEEE 21.6 2
IEEE Extremely Inverse (EI) IEEE 29.1 2
IEC Standard Inverse Time (SI) IEC/A 12.1 2
IEC Very Inverse Time (VI) IEC/B 43.2 2
IEC Extremely Inverse Time (EI) IEC/C 80 2
IEC Long Time Inverse (LTI) IEC 0 2
FR Short Time Inverse (STI) FR 0 2
UK Rectifier (Rect) UK 0 2
BNP EDF BNP EDF 0 2
RXIDG RXIDG 0 0
RI RI 0 2
Getting Started V11V/EN GS v1.0

VAMP 11V

GS

GETTING STARTED

Date: 1st December 2015


Software Version: 1A
Connection Diagrams: 10V11V01
V11V/EN GS v1.0 Getting Started

VAMP V11V

GS
Getting Started V11V/EN GS v1.0

VAMP 11V (GS) 3-1

CONTENTS

1. RELAY POWER UP 4
1.1 System Connections 4
1.2 Auxiliary Power Supply Connections 4
1.3 Powering up from the USB port is available in model A only (not available in model N,
model L no USB on the front panel) 4

2. USER INTERFACES AND MENU STRUCTURE 5


2.1 Introduction to the relay 5
2.1.1 Front panel 5
2.1.2 Special symbols on the LCD display 5
2.1.3 Indications 6
GS
2.2 Relay connection and power-up 9
2.2.1 Auxiliary Supply Voltage (Vaux) connection 9
2.2.2 Voltage inputs 9
2.2.3 Earthing 9
2.2.4 Output contacts 9
2.2.5 Binary inputs 10
2.3 Introduction to the user interfaces and setting options 10
2.4 Changing parameters via the front panel user interface (HMI) 10
2.4.1 SETTING CHANGE MODE 12
2.5 V11V Menu description 16
2.5.1 Headers 16
2.5.2 ALARM STATUS column 16
2.5.3 RECORDS column 17
2.5.4 SETTING GROUP columns 18
2.5.5 GLOBAL SETTINGS column 20
2.5.6 COMMISSIONING column 22
2.5.7 SETTING CHANGE MODE column 23
2.5.8 Menu Map 25

3. LOCAL CONNECTION VAMP 11V TO A PC 43


3.1 Configuration 43
3.2 USB Driver and virtual COM software installation 43
3.2.1 Remote connection 43
3.3 Products plugged into the same panel 44
3.4 MiCOM S1 Studio relay communications basics 44
3.5 MiCOM S1 Studio 5.1.0 45
3.5.1 MiCOM S1 Studio downloading 45
3.5.2 Data Model Management 47
V11V/EN GS v1.0 Getting Started

(GS) 3-2 VAMP 11V

3.5.3 “Quick Connection” to the relay using MiCOM S1 Studio 49


3.5.4 Create a system 57
3.5.5 Create a new substation 59
3.5.6 Create a new voltage level 60
3.5.7 Create a new bay 61
3.5.8 Create a new device 61
3.5.9 Open a Settings File 63
3.6 Troubleshooting USB connection 66
3.7 Presentation and analysis of disturbances 68

4. COMPANY CONTACT INFORMATION 70

GS
Getting Started V11V/EN GS v1.0

VAMP 11V (GS) 3-3

FIGURES

Figure 1: V11V Front Panel 8


Figure 2: Rear View of the V11V 8
Figure 3: Column headers 16
Figure 4: RECORDS column 17
Figure 5: SETTING GROUP 1 columns 19
Figure 6: GLOBAL SETTINGS column 21
Figure 7: COMMISSIONING column 23
Figure 8: SETTING CHANGE MODE column 24
Figure 9: V11V Model A Menu Map part 1 (Firmware 1A) 25
Figure 10: V11V Model A Menu Map part 2 (Firmware 1A) 26
GS
Figure 11: V11V Model A Menu Map part 3 (Firmware 1A) 27
Figure 12: V11V Model A Menu Map part 4 (Firmware 1A) 28
Figure 13: V11V Model A Menu Map part 5 (Firmware 1A) 29
Figure 14: V11V Model A Menu Map part 6 (Firmware 1A) 30
Figure 15: V11V Model A Menu Map part 7 (Firmware 1A) 31
Figure 16: V11V Model N Menu Map part 1 (Firmware 1A) 32
Figure 17: V11V Model N Menu Map part 2 (Firmware 1A) 33
Figure 18: V11V Model N Menu Map part 3 (Firmware 1A) 34
Figure 19: V11V Model N Menu Map part 4 (Firmware 1A) 35
Figure 20: V11V Model N Menu Map part 5 (Firmware 1A) 36
Figure 21: V11V Model N Menu Map part 6 (Firmware 1A) 38
Figure 22: V11V Model N Menu Map part 7 (Firmware 1A) 38
Figure 23: V11V Model L Menu Map part 1 (Firmware 1A) 39
Figure 25: V11V Model L Menu Map part 3 (Firmware 1A) 41
Figure 26: V11V Model L Menu Map part 4 (Firmware 1A) 42
Figure 27: Connection relay to the PC 43
Figure 28: Connection between relays in local network 44
V11V/EN GS v1.0 Getting Started

(GS) 3-4 VAMP 11V

BEFORE CARRYING OUT ANY WORK ON THE EQUIPMENT, THE


USER SHOULD BE FAMILIAR WITH THE CONTENTS OF THE SAFETY
GUIDE SFTY/4L M/E11 OR LATER ISSUE, OR THE SAFETY AND
TECHNICAL DATA SECTION OF THE TECHNICAL MANUAL AND ALSO
THE RATINGS ON THE EQUIPMENT RATING LABEL.

For safety reasons, no work must be carried out on the V11V until all
power sources to the unit have been disconnected.

1. RELAY POWER UP
Follow the following instructions carefully in order to correctly power up the relay.
GS 1.1 System Connections
Check the wiring scheme of your installation.
Check that the output relay contacts are included in your trip circuit.
1.2 Auxiliary Power Supply Connections
Connect a DC or AC (according to nominal supply rating VAUX) voltage power supply.

Positive VAUX to terminal A1


Negative VAUX to terminal A2

Turn on the auxiliary power supply and set to approximately the rated voltage as shown on
the relay's front panel.
The display should show:

1.00 kV 1.00 kV Displays:


- first line: phases A and B voltages,
1.00 kV 1.00 kVe - second line: phase C voltage and earth voltage,
taking into account the phase VT ratio
(CONFIGURATION/VT RATIO submenu).

The LEDs should be configured as follows:

− The green LED "Healthy" (watchdog) is illuminated.


The configuration of the remaining LEDs depends on the relay's history before powering
(if the LEDs are configured as latching their state is stored in memory, therefore after
repowering they are illuminated again until they are manually reset).
1.3 Powering up from the USB port is available in model A only (not available in model N,
model L no USB on the front panel)
Only some of the relay's electronic circuits, for the HMI and RS485 communications, are
supplied from the USB port.
Note: Since the I/O boards are not supplied from the USB port the inputs'
status is set to default value.
Additionally, output contacts are not operational therefore it is
impossible to execute any commands.
Getting Started V11V/EN GS v1.0

VAMP 11V (GS) 3-5

2. USER INTERFACES AND MENU STRUCTURE


The settings and functions of the VAMP protection relay can be accessed both from the front
panel keypad and LCD, and via the front and rear communication ports. Information on each
of these methods is given in this section to describe how to start using the relay.
Note:
“(NA)” means that function is available in model N and A only.
“(A)” means that function is available in model A, etc.
2.1 Introduction to the relay
2.1.1 Front panel
The front panel of the relay is shown in Figure 1.
The front panel of the relay includes:

− a 16-character by 2-line alphanumeric liquid crystal display (LCD),


GS
− a 9-key keypad comprising 4 arrow keys ( , , , ), an HMI key, a clear key
( ), a read key ( ), a trip command key ( ) and a close command key ( ).

− 8 LEDs,

− a USB port for local communications,


2.1.2 Special symbols on the LCD display
The following special symbols may appear on the LCD display:
- It is possible to move up by pressing this key,

- It is possible to move left by pressing this key,

- It is possible to move down by pressing this key,

- It is possible to move right by pressing this key,


- The last menu cell in the column. If the key is pressed here the cursor will
reach the first cell in the column,
- It is possible to edit the displayed values,
<0.1 40> - Setting range: from 0.1 to 40,

0.01 - Setting value step: 0.01,

- On the last line: Setting group 1 is displayed.


In the upper-right corner: Setting group 1 is active,

- On the last line: Setting group 2 is displayed,


In the upper-right corner: Setting group 2 is active,

- Edition of values on the display password-protected,

- Edition of setting value is possible (the level correct password has been
entered),

A - An alarm is still active (the cause of alarm is highlighted).


V11V/EN GS v1.0 Getting Started

(GS) 3-6 VAMP 11V

2.1.3 Indications
Note: “(NA)” means that function is available in model N and A only.
Fixed Function LEDS:
Healthy – Powering of microprocessor and no hardware problems detected (green LED)
Trip – Any trip caused by protection criteria
And 6 programmable LEDS for the following functions (OR logic):
Alarm – Alarm signal
U> – Start of the first overvoltage stage
U>> – Start of the second overvoltage stage
U>>>– Start of the third overvoltage stage
U< – Start of the first undervoltage stage
U<< –
GS Start of the second undervoltage stage
U<<<– Start of the third undervoltage stage
U1< – Start of the first positive sequence undervoltage stage (A)
U1<< – Start of the second positive sequence undervoltage stage (A)
U2>– Start of the first stage negative sequence overvoltage stage (NA)
U2>>– Start of the second stage negative sequence overvoltage stage (NA)
UN> – Start of the first earth fault overvoltage stage
UN>> – Start of the second earth fault overvoltage stage
UN>>>– Start of the third earth fault overvoltage stage
Start f1– Start of the first frequency stage (A)
Start f2– Start of the second frequency stage (A)
Start f3– Start of the third frequency stage (A)
Start f4– Start of the fourth frequency stage (A)
Start f5– Start of the fifth frequency stage (A)
Start f6– Start of the sixth frequency stage (A)
AUX1 – Trigger of AUX1 (via a binary input) (A)
AUX2 – Trigger of AUX2 (via a binary input) (A)
AUX3 – Trigger of AUX3 (via a binary input) (A)
tU> – Trip of the first overvoltage stage
tU>> – Trip of the second overvoltage stage
tU>>>– Trip of the third overvoltage stage
tU< – Trip of the first undervoltage stage
tU<< – Trip of the second undervoltage stage
tU<<<– Trip of the third undervoltage stage
tU1< – Trip of the first positive sequence undervoltage stage (A)
tU1<< – Trip of the second positive sequence undervoltage stage (A)
tU2>– Trip of the first stage negative sequence overvoltage stage (NA)
tU2>>– Trip of the second stage negative sequence overvoltage stage (NA)
tUN> – Trip of the first earth fault overvoltage stage
tUN>> – Trip of the second earth fault overvoltage stage
Getting Started V11V/EN GS v1.0

VAMP 11V (GS) 3-7

tUN>>>– Trip of the third earth fault overvoltage stage


tf1– Trip of the first frequency stage (A)
tf2– Trip of the second frequency stage (A)
tf3– Trip of the third frequency stage (A)
tf4– Trip of the fourth frequency stage (A)
tf5– Trip of the fifth frequency stage (A)
tf6– Trip of the sixth frequency stage (A)
tAUX1 – Trigger of AUX1 timer (via a binary input) (NA)
tAUX2 – Trigger of AUX2 timer (via a binary input) (NA)
tAUX3 – Trigger of AUX3 timer (via a binary input) (A)
Local CTRL Mode – Local Control Mode (NA)
CB Alarm – Circuit Breaker condition alarm signal (CB Open NB, Sum Amps(n),
CB Open Time and CB Close Time) (A) GS
Maintenance Mode – Maintenance Mode (outputs are disconnected from all functions) (A)
tCB FLT Ext.Sign. – An input mapped to this function detects CB problems that may
influence control possibilities (for example spring problem, insufficient
pressure, etc.). Signaling is active during a settable time (GLOBAL
SETTINGS/CIRCUIT BREAKER/ tCB FLT ext) (A)
Setting Group n – Setting Group n active (n= 1, 2)
tVTS – Trigger of VT supervision (A)
fout – frequency is out of range (A)
Every LED can be configured to be latched or self-resetting (SETTING GROUP 1/ LEDS
CONFIGURATION G1/ Latched LEDs).
If a LED is configured as latching, the manner in which it will be reset is selectable:
- Resetting of LEDs via manual reset (GLOBAL SETTINGS/LOC/Signaling Reset 0:
Manual only)
- Resetting of LEDs via any protection start (set for CB tripping) or via manual reset
(GLOBAL SETTINGS/LOC/Signaling Reset 1: Start protect.)
- Resetting of LEDs via manual close command (RS485, HMI or Input) or via manual reset
(GLOBAL SETTINGS/LOC/LEDs Reset 2: Close Command)
V11V/EN GS v1.0 Getting Started

(GS) 3-8 VAMP 11V

GS

1 – Red “Trip” LED: Protection trip


2 – Yellow “Alarm” LED: Alarm signaling
3,4, 5, 6, 7 – Red programmable LED
8 – Green “Healthy” LED: Watchdog
9 – 16-character by 2-line alphanumeric liquid crystal display (LCD)
10 – Clear key
11 – Read key
12 – 4 arrow keys, an enter key
14 – CB Close key
15 – CB Open Key
16 – USB port for local connection

Figure 1: V11V Front Panel

PJ103ENd

1 – Terminal block A: Auxiliary voltage Vaux, contact outputs (WD,RL1-RL3) and binary inputs (L1, L2) and
RS485
2 – Contact outputs (A): RL6, RL7 and binary inputs (A): L3, L4, L5, L6
3 – Terminal block C: voltage analogue inputs (phases and earth), (NA) output contacts: RL4, RL5
Refer to Installation chapter V11V/EN IN.

Figure 2: Rear View of the V11V


Getting Started V11V/EN GS v1.0

VAMP 11V (GS) 3-9

2.2 Relay connection and power-up


The relay can be powered from the following sources:
- Auxiliary voltage Vaux (terminals A1-A2)
! - USB port (only some electronic boards: to ensure HMI, USB and/or RS485
communications)
Note:
1. USB is not available in model L
2. USB not supply electronic of V11V in model N. The auxiliary voltage have to present on
A1-A2 terminals
2.2.1 Auxiliary Supply Voltage (Vaux) connection
Before applying the auxiliary supply voltage to the relay, check that the rated nominal ac or
dc voltage is appropriate for the application and that it will be connected to the correct
terminals (A1&A2). The relay's serial number, voltage rating, and power rating information
can be viewed on the upper side of the case. The ac or dc supply voltage must be within the GS
corresponding nominal range of the device, as indicated in the table below, for the
appropriate nominal rating of the equipment:

! Model Nominal ranges of auxiliary


Operative dc range Operative ac range
voltage Vaux
L 24 – 240 Vdc/Vac 19 to 300 Vdc 19 to 265 Vac
24 – 60 Vdc/Vac 19 to 72 Vdc 19 to 66 Vac
N
90 – 240 Vdc/Vac 72 to 300 Vdc 72 to 265 Vac
24 – 60 Vdc/Vac 19 to 72 Vdc 19 to 66 Vac
A
90 – 240 Vdc/Vac 72 to 300 Vdc 72 to 265 Vac

Once the ratings have been verified for the application, connect the equipment to an external
power source capable of delivering the requirements specified on the label, to perform the
relay familiarization procedures. Please refer to the wiring diagrams in the Installation section
for complete installation details, ensuring that the correct polarities are observed in the case
of dc supply.
Note: The label specifies the auxiliary voltage for the V11V supply input and
binary inputs (dependent on ordering options).
2.2.2 Voltage inputs
The measuring voltage inputs of the V11V should be connected to the secondary wires of
the power system VTs as shown in the connection diagrams in section 8 of V11V Installation
chapter V11V/EN IN.
The parameters of the VTs that can be connected to the V11V’s voltage input terminals are
detailed in section 3 of chapter V11V/EN AP - Applications.
2.2.3 Earthing
V11V have no the Protective (Earth) Conductor Terminal (because of the plastic case)
2.2.4 Output contacts
Depends on the model the V11V has:
- Model L: 3 output contacts + WD(RL0)
- Model N: 5 output contacts + WD(RL0)
- Model A: 7 output contacts + WD(RL0)
V11V/EN GS v1.0 Getting Started

(GS) 3-10 VAMP 11V

V11V is delivered with the following default factory settings for the outputs:
- Output RL0/WD (N/O: A3-A5, N/C: A4-A5) -watchdog is not configurable
- Output RL1 (N/O: A6-A8, N/C: A7-A8) is not configured
- Output RL2 (N/O: A9-A11, N/C: A10-A11) is not configured
- Output RL3 (N/O: A12-A13) is not configured
- Output RL4 (NA) (N/O: C1-C2) is not configured
- Output RL5 (NA) (N/O: C3-C4) is not configured
- Output RL6 (A) (N/O: B1-B2) is not configured
- Output RL7 (A) (N/O: B3-B4) is not configured
To modify the outputs configuration, refer to section 2.2 of chapter V11V/EN ST - Settings.
The output connection diagram is shown in section 8 of chapter V11V/EN IN - Installation.
GS 2.2.5 Binary inputs
Depends on the model the V11V has:
- Model L: no binary inputs
- Model N: 2 binary inputs
- Model A: 6 binary inputs
Binary inputs:
- Input L1 (NA): A14-A16 terminals (terminal block A)
- Input L2 (NA): A15-A16 terminals (terminal block A)
- Input L3 (A): B5-B7 terminals (terminal block B)
- Input L4 (A): B6-B7 terminals (terminal block B)
- Input L5 (A): B8-B10 terminals (terminal block B)
- Input L6 (A): B9-B10 terminals (terminal block B)
There operation range is the same as auxiliary voltage supply (A1-A2 terminals) see chapter
2.2.1 (ordering option).
To modify the inputs' configuration, refer to section 1.2.3 of chapter V11V/EN ST - Settings.
The input connection diagram is shown in section 8 of chapter V11V/EN IN - Installation.

2.3 Introduction to the user interfaces and setting options


The relay has a USB user interface for use with MiCOM S1 STUDIO 5.1.0 (or higher)
software.
With this interface it is possible to download the setting values, latest fault, alarm and event
records (NA) as well as disturbance records (A) and fully configure the V11V.
Note: After connection to the USB port the Healthy LED is lit. If the LED is not lit refer to
chapter V11V/EN TS - Troubleshooting.
The USB port integrates electronic boards only to allow communications with the V11V via
the HMI/RS485/USB interfaces.
2.4 Changing parameters via the front panel user interface (HMI)
Changing of all parameters is password-protected.
Getting Started V11V/EN GS v1.0

VAMP 11V (GS) 3-11

After restart or powering up, the V11V is in Protection Mode. This means that all settings
are the same as in the relay's operation system and are available on the front panel user
interface.
To change any parameters, it is necessary to switch the V11V to the SETTING CHANGE
MODE.
The SETTING CHANGE MODE, for entered password level which changes setting
parameters, is indicated by the sequential flashing of the programmable LEDs (from 4 up to
8 LEDs) on the front panel.
Until it is switched back from the SETTING CHANGE MODE to the PROTECTION MODE,
or restarted by disconnecting then reconnecting the power supply, the V11V uses the setting
parameters that were active before the SETTING CHANGE MODE was entered (previous
settings).
Press the OK navigation key, after changing a chosen parameter (confirmation of change).
The new value is saved in FRAM memory but the V11V still uses the setting value that was
active before the SETTING CHANGE MODE was entered (previous settings). The new
value will be available in the operation system only after the firmware has been reset. When
the firmware is reset, all the settings are loaded into the V11V system. GS
When switching from the SETTING CHANGE MODE to the PROTECTION MODE, a warm
reset is applied.
The V11V therefore applies the new parameters to the relay's operation system.
Afterwards, the settings available on the front panel and those used by the operation system
are consistent.
Note: While the LEDs (LED’s 3 - 7) are start flashing subsequently
(SETTING CHANGE MODE by entering Administrator or Protection
setting password) there can be a mismatch between the settings
displayed on the front panel and those used by the operating system.
When “Control only” rights password is entered then all LED’s (LED’s
3 - 7) start flashing in the same time. Administrator or Protection
setting password. Additionally all changes are executed and recorded
immediately (no need warm reset of firmware). Because this level is
not signaled so after 5 minutes V11V switches back automatically
from the SETTING CHANGE MODE to the PROTECTION MODE.
The password protection of the relay comprises three levels:

− Administrator (Without limits)

− Protection setting (Protection only)

− Control only (Test control) – this level is used for tests and/or control execution only (no
changing of setting parameters) so signaling of SETTING CHANGE MODE differs from
above. On this password level there is no the sequential flashing of the programmable
LEDs (from 3 up to 7 LEDs) but flashing in the same time. On the control windows is the
special sign: which informs that control is allowed.
Administrator rights: all the menu settings may be changed (violet color on Fig.9-25).
Protection setting rights: it is possible to change settings in the PROTECTION column;
CTRL Default Windows (CB status CTRL, L/R status CTRL) and COMMISSIONING/
Maintenance Mode windows are also possible (green color on Fig.9-25).
Control rights: CTRL Default Windows (CB status CTRL, L/R status CTRL) and
COMMISSIONING/Maintenance Mode windows from the front panel only (yellow color on
Fig.9-25).
For each level the password consists of 4 digits (0 to 9)
NOTE: The default password is 0000 for every password protection level.
V11V/EN GS v1.0 Getting Started

(GS) 3-12 VAMP 11V

It is recommended to change default password from 0000 to unique value for every
password level.
If the first password is different, this means that the Administrator password has been
changed.
The Protection setting password is still 0000. Therefore, to protect settings against
unauthorized access it is necessary to change the Protection setting password by first
entering 0000 then a new value.
The Control password is still 0000. Therefore, if it is necessary to change it, first enter 0000
then the new value (Control right) of the password.
Notes: 1. If the Protection setting rights have not been changed, or if it has
been set to the default value (0000), it is possible to change all the
settings in the PROTECTION column, reset the counters and control
the CB without entering a password, simply by pressing the OK
navigation key. This makes it possible to change a chosen parameter
by automatically switching the V11V to the SETTING CHANGE
MODE (the programmable LEDs are flashing).
GS This means that even after changing only one parameter it is
necessary to switch the V11V back to PROTECTION MODE in order
to activate the new settings (warm restart).
2. If the Control rights password has not been changed or if it has
been set to the default value (0000) it is possible to control the CB in
menu without password protection.
2.4.1 SETTING CHANGE MODE
The SETTING CHANGE MODE should be used to change settings.
Using the SETTING CHANGE MODE ensures that all changed parameters will be applied
simultaneously so as to avoid any problems caused by possible setting inconsistencies.
The SETTING CHANGE MODE makes it possible to change settings while the relay is
active without any risk (the V11V continues to use the previous settings).
After exiting the SETTING CHANGE MODE a warm reset of firmware is applied so that all
the protection counters are reset.
Note: Latched LEDs and outputs are not reset (stored values are not
cleared during a V11V reset)

To switch the V11V to the SETTING CHANGE MODE navigate to the SETTING CHANGE
MODE main header (see Figure 9), then press the key:

Edit settings?
Enter PSWD

Press the OK navigation key.

Edit settings?
Enter PSWD 0000

The 0 digit furthest to the right is flashing.


Enter the password:

1. If the digit is flashing, change the digit to the required value by pressing the key or
the key.

2. Change the flashing digit by pressing the key or key.


3. Continue as above to set the whole password (4 digits)
Getting Started V11V/EN GS v1.0

VAMP 11V (GS) 3-13

4. If the correct password is set, press the OK navigation key


The LCD displays 'OK' during approximately 1 second, then the new SETTING CHANGE
cell is displayed:
If the password entered is for:
- Administrator rights:

Setting change:
Without limits

To indicate that the V11V is in SETTING CHANGE MODE on the level: “Without limits”
the programmable LEDs are flashing

- Protection settings:

Setting change:
Protection only
GS
To indicate that the V11V is in SETTING CHANGE MODE on the level: “Protection only”
the programmable LEDs are flashing

- Control only:

Setting change:
Test control

There is no any indication that this level is entered. SETTING CHANGE MODE is active by 5
minutes only.

The screen displays the scope of the current modification rights..


At this time it is possible to start changing the setting parameters.

Note: The parallel pressing: and key it makes jump from any place
to:

Edit settings?
Enter PSWD

the menu cell in which the password can be entered (hot key).
If all settings are changed, it is necessary to return to PROTECTION MODE to apply a warm
reset.

Press the and keys simultaneously to jump to the following cell:

Edit settings?
Exit:press ENTER

Press the OK navigation key to apply a warm reset and display the following cell:

Setting change:
Protected

The programmable LEDs do not flash sequentially. The V11V is in PROTECTION MODE
Note: In SETTING CHANGE MODE all functions use the previously stored
settings (before the SETTING CHANGE MODE was entered).
V11V/EN GS v1.0 Getting Started

(GS) 3-14 VAMP 11V

Changing of a single setting parameter


Go to the required setting cell (see section 2.5.8).
Press the HMI OK key.

Edit settings?
Enter PSWD 000

Using the , , , keys, enter the password.


Press OK navigation key to confirm the password and switch to SETTING CHANGE MODE.
Press OK navigation key to enter the chosen setting parameter.

Using the , , , keys, set the required value.


Confirm the change by pressing the OK navigation key.
Switch from SETTING CHANGE MODE to PROTECTION MODE.
GS
For example, press the and keys simultaneously to display the following cell:

Edit settings?
Exit:press ENTER

Press the OK navigation key to switch from SETTING CHANGE MODE to PROTECTION
MODE.
The following cell should be displayed:

Setting change:
Protected

The above cell confirms that settings are password-protected, and that the V11V is in
PROTECTION MODE.
Additionally the programmable LEDs do not flash sequentially.
Changing the password
To change the password, first enter the existing password to obtain the appropriate
password protection rights.

Press the key to display the following cell:

Change Password

Press the OK navigation key, to display:

Change Password
0000

Using the , , , keys, enter the new password.


Press OK navigation key to confirm the new password and jump to the cell displaying
information on protection rights
For example:

Setting change:
Without limits

To exit the SETTING CHANGE MODE (apply a warm reset) press the and keys
simultaneously to display the following cell:
Getting Started V11V/EN GS v1.0

VAMP 11V (GS) 3-15

Edit settings?
Exit:press ENTER

Press the OK navigation key to confirm switching from SETTING CHANGE MODE to
PROTECTION MODE.
The following cell should be displayed:

Setting change:
Protected

The above cell confirms that the settings are password-protected and that the V11V is in
PROTECTION MODE. Additionally the programmable LEDs do not flash sequentially.

GS
V11V/EN GS v1.0 Getting Started

(GS) 3-16 VAMP 11V

2.5 V11V Menu description


2.5.1 Headers
The main headers are shown in Figure 3.

GS

Figure 3: Column headers


2.5.2 ALARM STATUS column
ALARM STATUS (see Figure 4) information is available if the cause of alarm has been
triggered. Therefore, if after pressing the key the new cell is displayed, it means that no
alarms have been detected.
Depending on the V11V configuration an alarm signal is self-resetting (no cause of alarm –
no alarm signal; GLOBAL SETTINGS/LOC/Alarm Display 0: Self-reset) or manually
resettable (alarm signal latched; GLOBAL SETTINGS/LOC/Alarm Display 1: Latching).
Default setting: 0: Self-Reset. This means that if an alarm signal has disappeared no
information is available in the ALARM STATUS column.
If set to Latching, this means that if an alarm signal has disappeared information is still
available in the ALARM STATUS column until it is reset in the ALARM STATUS/ Alarm
Reset window.
Alarm information is always available in the event recorder. However, the programmable
LEDs can be used to store causes of alarm if required.
Figure 4 shows all causes of alarms (if alarms have been enabled in the main configuration
column of the protection function).
2.5.3
VAMP 11V

the
Getting Started

RECORDS

Figure 4:

or
FAULT ALARM COUNTERS MAX MEAS.
RECORD RECORD VALUES
RECORDS column

Record Number Record Number CONTROL FAULT Max Va=


Fault 1 Alarm 1 COUNTER COUNTER 00.000Un
OK navigation key then the

Fault Type Alarm Type No.Trips No.Fault Trips Max Vb=


None None 00000 00000 00.000Un
software or via the RS485 link.

RECORDS column
or

Fault Time Alarm Time No.Close No.Faut Starts Max Vc=


to enter the Control rights password.

00:00:00.000 00:00:00.000 00000 00000 00.000Un

Fault Date Alarm Date Reset Counter No.Alarms Max Vab=


01/01/00 01/01/00 CTRL: Cancel 00000 00.000Un
Twenty fault records are available in the V11V.

Active Setting Active Setting No.HD Warnings Max Vbc=


Group 1 Group 1 00000 00.000Un

Fault Origin Alarm Origin Reset Counter Max Vca=


None None CTRL: Cancel 00.000Un

Va= 00000.0V Va= 00000.0V Max Values Reset


Vb= 00000.0V Vb= 00000.0V CTRL: Cancel
Access:

Read only
Vc= 00000.0V Vc= 00000.0V
VN= 00000.0V VN= 00000.0V
Write under the password protection:

Or (depends on the Or (depends on the Administrator password (Without limits)

scheme connection): scheme connection): Protection setting password (Protection only)

Vab= 00000.0V Vab= 00000.0V Control password (Test control)


Vbc= 00000.0V Vbc= 00000.0V
PJ913ENd
Vac= 00000.0V Vac= 00000.0V
VN= 00000.0V VN= 00000.0V

change. This operation requires entering a Administrator password (Without limits).


(GS) 3-17
V11V/EN GS v1.0

Counters can be reset in the Counter Reset cell of the menu, by pressing the OK key then
Records in the Fault Recorder can be reset using the MiCOM S1 Studio communication
key. Once the required record is selected, press the

key. Once the required record is selected, press the OK key to confirm the
HMI OK key to confirm the change. If the Control rights password has been set to the default
Changing a record in the menu is possible in the Record Number menu cell, by pressing the

value (0000), this operation does not require entering a password; otherwise it is necessary

GS
V11V/EN GS v1.0 Getting Started

(GS) 3-18 VAMP 11V

In addition, counters can be reset using the MiCOM S1 Studio communication software or
via the RS485 link.
2.5.4 SETTING GROUP columns
The V11V has two setting groups. The relay is delivered with one setting group active only
(factory default setting).
If two setting groups are to be used, the second setting group must be activated in the menu
cell:
GLOBAL SETTINGS/SETTING GROUP SELECT/Setting Group Select:

Nb of Groups
0: One Group

by changing its setting from 0: One Group to 1: Two Groups


Each setting group includes:
GS
- Protection settings
- Output relay configuration
- Binary input configuration
- Programmable LED configuration
Switching between setting groups is possible via:
- Configured binary inputs
- Menu (GLOBAL SETTINGS/SETTING GROUP SELECT/Setting Group Select cell)
- MiCOM S1 Studio setting software
- Remotely via RS485
VAMP 11V

SETTING GROUP 1
Getting Started

Figure 5:
PROTECTION G1

PHASE O/V G1 PHASE U/V G1 E/GND FAULT O/V NEGATIVE SEQ.O/V POSITIVE SEQ.U/V Frequency AUX TIMERS G1

Notes:
[59] [27] [59N] G1 [47] G1 [27D] G1 [81O/81U] G1

U>? U<? UN>?(measured) U2>? U1<? f1? AUX1?


1: Trip 1: Trip 2:Alarm 2: Alarm 1: Trip 4: f< Alarm 1: Trip

Active Set Group cell.


U> Threshold U< Threshold UN> Threshold U2> Threshold U1< Threshold f1 Threshold f5? tAUX1
120.0V 80.0V 20.0V 120.0V 80.0V 49.50Hz 2:f> Alarm 10.00s

Delay Type Delay Type Delay Type Delay Type Delay Type tf1 f5 Threshold AUX2?
U> 1: IEC SI U< 1: IEC SI UN> 1: IEC SI U2> 1: IEC SI U1< 1: IEC SI 1.00s 50.20Hz 2: Alarm

U> TMS U< TMS UN> TMS U2> TMS U1< TMS f2? tf5 tAUX2?
1.00 1.00 1.00 1.00 1.00 3: f< Trip 1.00s 10.00s

SETTING GROUP 1 columns


Reset Delay Type Reset Delay Type Reset Delay Type Reset Delay Type Reset Delay Type f2 Threshold f6? AUX3?
U> 1:IDMT U< 1:IDMT UN> 1:IDMT U2> 1:IDMT U1< 1:IDMT 48.50Hz 1:f> Trip 1: Trip

RTD/RTMS Reset RTD/RTMS Reset RTD/RTMS Reset RTD/RTMS Reset RTD/RTMS Reset tf2 f6 Threshold tAUX3
U> 0.00 U< 0.00 UN> 0.00 U2> 0.00 U1< 0.00 1.00s 50.50Hz 10.00s

Group 1 and Setting Group 2.


U>>? U<<? UN>>?(measured) U2>>? U1<<? f3? tf6
1: Trip 1: Trip 1: Trip 1: Trip 1: Trip 3: f< Trip 1.00s

U>> Threshold U<< Threshold UN>> Threshold U2>> Threshold U1<< Threshold f3 Threshold
140.0V 70.0V 30.0V 140.0V 70.0V 47.50Hz

tU>> tU<< tUN>> tU2>> tU1<< tf3


1.00s 1.00s 1.00s 1.00s 1.00s 1.00s

U>>>? U<<<? UN>>>?(Ua+Ub+Uc) f4?


2: Alarm 2: Alarm 3:Trip 3: f< Trip
Access:

U>>> Threshold U<<< Threshold UN>>> Threshold Read only


f4 Threshold
160.0V 60.0V 60.0V 46.50Hz
Write under the password protection:

configuring them to that function and via a special symbol on the LCD display.
Administrator password (Without limits)
tU>>> tU<<< tUN>>> tf4
Protection setting password (Protection only)
0.10s 0.10s 0.10s 1.00s
Control password (Test control)

PJ914ENd
(GS) 3-19
V11V/EN GS v1.0

binary input must be configured to setting group switch both in Setting


1. If setting groups are to be switched using a binary input (NA), this
Information about the active setting group is available in menu: OP PARAMETERS/

Information about the active setting group can be displayed via the programmable LEDs by
GS
V11V/EN GS v1.0 Getting Started

(GS) 3-20 VAMP 11V

2. It is possible to copy all the parameters from Setting Group 1 to


Setting Group 2 or vice versa (GLOBAL SETTINGS/SETTING
GROUP SELECT/Copy Settings cell). It will then only be necessary
to change the parameters' values.
2.5.5 GLOBAL SETTINGS column
Global Settings include all general settings, such as:
- Localization (LOC),
- Setting Group operation (SETTING GROUP SELECT),
- Voltage transformer parameters (VT RATIO),
- Time settings related to Circuit Breaker control or monitoring (CIRCUIT BREAKER),
- Voltage transformer supervision (VT SUPERVISION),
- Advanced settings for the froquency protection elements ([81] ADVANCED SETTINGS),

GS - Advanced settings for the voltage protection elements (VOLTAGE ADVANCED


CONFIGURATION),
- RS485 communication parameters (COMMUNICATION) (NA),
- Disturbance recorder parameters (DISTURBANCE RECORDER) (A),
Getting Started V11V/EN GS v1.0

VAMP 11V (GS) 3-21

GS

Figure 6: GLOBAL SETTINGS column


V11V/EN GS v1.0 Getting Started

(GS) 3-22 VAMP 11V

It is possible to Copy all parameters from Setting Group 1 to Setting Group 2 and inversely in
the Copy settings cell by pressing the OK navigation key. Choose the required operation by
pressing the or key (Copy G1 G2 or Copy G2 G1). Confirm the change by
pressing the OK navigation key.
Note: The setting group change's time-delay, from Setting Group 1 to Setting Group 2
(t Change Setting cell), applies to changes effected via a binary input only (NA).
2.5.6 COMMISSIONING column
The settings available in the the COMMISSIONING column are:

− Opto I/P status – which binary inputs are active (logic status) (NA),

− Relay O/P status – which binary outputs are active (physical status),

− Maintenance mode – allows the user to check the operation of the protection
functions without actually sending any external command (tripping or signaling) (A),

GS − Test Pattern – allows the user to set outputs contacts for tests (A),

− Contact Test Time – defines the output's pulse length during the tests (A),

− Test outputs – if set to 1: apply test, pressing the OK navigation key will execute the
test of the outputs (A),

− Functional Test – allows the user to set the protection criteria to be tested (A),

− Functional Test End – defines the end of the functional test: CB opened or Time
(A),

− Functional Test Time – defines the pulse length during the functional test (A),

− Functional Test – if set to Apply Test pressing the OK navigation key will execute
the functional test (A).
It is possible to set following Maintenance mode options (A):

• “No” - Maintenance mode is disabled. All window cells below are hidden
(Maintenance mode is the latest cell in COMMISIONING column)

• “Yes,outp.trips” - Maintenance mode is enabled. In this mode all test cells in


COMMISIONING column are available (see Fig.7 below). During tests outputs are
energized.

• “Yes,outp.block” - Maintenance mode is enabled and all test cells in


COMMISIONING column are available (see Fig.7 below). In this mode, the high
state of output functions are ignored (control of outputs are blocked).
This operation requires entering a Control rights password (Test control).
It is possible to set additional programmable LED for Maintenance Mode.
Note: The Maintenance Mode is active up to 10 minutes only. After this time V11V
automatically sets - Maintenance mode: “No”. It protects user against leaving the V11V
in this mode after tests.
Getting Started V11V/EN GS v1.0

VAMP 11V (GS) 3-23

GS

Figure 7: COMMISSIONING column

2.5.7 SETTING CHANGE MODE column


The SETTING CHANGE MODE column is used to:
- Allow changing of all parameters in the menu (SETTING CHANGE MODE).
- Set a new password or change the existing password (Change Password)
V11V/EN GS v1.0 Getting Started

(GS) 3-24 VAMP 11V

Figure 8: SETTING CHANGE MODE column


GS
Getting Started V11V/EN GS v1.0

VAMP 11V (GS) 3-25

2.5.8 Menu Map

GS

Figure 9: V11V Model A Menu Map part 1 (Firmware 1A)


V11V/EN GS v1.0 Getting Started

(GS) 3-26 VAMP 11V

GS

Figure 10: V11V Model A Menu Map part 2 (Firmware 1A)


Getting Started V11V/EN GS v1.0

VAMP 11V (GS) 3-27

GS

Figure 11: V11V Model A Menu Map part 3 (Firmware 1A)


V11V/EN GS v1.0 Getting Started

(GS) 3-28 VAMP 11V

GS

Figure 12: V11V Model A Menu Map part 4 (Firmware 1A)


LEDS
VAMP 11V

CONFIGURATION G1

Latched 765432 Start 765432 765432 765432 Setting 765432


Getting Started

LEDs 000000 VN>> 000000 tV> 000000 tf1 000000 Group 1 000000

765432 Start 765432 765432 765432 765432


Alarm 000000 VN>>> 000000 tV>> 000000 tf2 000000 tVTS 000000

Start 765432 Start 765432 765432 765432 765432


V> 000000 f1 000000 tV>>> 000000 tf3 000000 fout 000000

Start 765432 Start 765432 765432 765432


V>> 000000 f2 000000 tV< 000000 tf4 000000

Start 765432 Start 765432 765432 765432


V>>> 000000 f3 000000 tV<< 000000 tf5 000000

Start 765432 Start 765432 765432 765432


V< 000000 f4 000000 tV<<< 000000 tf6 000000

Start 765432 Start 765432 765432 765432


V<< 000000 f5 000000 tV1< 000000 tAUX1 000000

Access:
Start 765432 Start 765432 765432 765432
V<<< 000000 f6 000000 tV1<< 000000 tAUX2 000000 Read only

Write under the password protection:


Start 765432 765432 765432 765432
Administrator password (Without limits)
V1< 000000 AUX1 000000 tV2> 000000 tAUX3 000000

Figure 13: V11V Model A Menu Map part 5 (Firmware 1A)


Protection setting password (Protection only)

Control password (Test control)


Start 765432 765432 765432 Local 765432
V1<< 000000 AUX2 000000 tV2>> 000000 CTRL Mode 000000
PJ916ENd
Start 765432 765432 765432 CB 765432
V2> 000000 AUX3 000000 tVN> 000000 Alarm 000000

Start 765432 765432 765432 Mainten. 765432


V2>> 000000 AUX4 000000 tVN>> 000000 Mode 000000

Start 765432 765432 765432 tCB FLT 765432


VN> 000000 AUX5 000000 tVN>>> 000000 Ext.Sign. 000000
(GS) 3-29
V11V/EN GS v1.0

GS
V11V/EN GS v1.0 Getting Started

(GS) 3-30 VAMP 11V

GS

Figure 14: V11V Model A Menu Map part 6 (Firmware 1A)


Getting Started V11V/EN GS v1.0

VAMP 11V (GS) 3-31

GS

Figure 15: V11V Model A Menu Map part 7 (Firmware 1A)


V11V/EN GS v1.0 Getting Started

(GS) 3-32 VAMP 11V

GS

Figure 16: V11V Model N Menu Map part 1 (Firmware 1A)


Getting Started V11V/EN GS v1.0

VAMP 11V (GS) 3-33

GS

Figure 17: V11V Model N Menu Map part 2 (Firmware 1A)


V11V/EN GS v1.0 Getting Started

(GS) 3-34 VAMP 11V

GS

Figure 18: V11V Model N Menu Map part 3 (Firmware 1A)


Getting Started V11V/EN GS v1.0

VAMP 11V (GS) 3-35

GS

Figure 19: V11V Model N Menu Map part 4 (Firmware 1A)


GS
LEDS
(GS) 3-36

CONFIGURATION G1

Latched 765432 765432 765432


V11V/EN GS v1.0

LEDs 000000 AUX1 000000 tAUX1 000000

765432 765432 765432


Alarm 000000 AUX2 000000 tAUX2 000000

Start 765432 765432 Local 765432


V> 000000 tV> 000000 CTRL Mode 000000

Start 765432 765432 Setting 765432


V>> 000000 tV>> 000000 Group 1 000000

Start 765432 765432


V>>> 000000 tV>>> 000000

Start 765432 765432


V< 000000 tV< 000000

Start 765432 765432


V<< 000000 tV<< 000000

Access:
Start 765432 765432
V<<< 000000 tV<<< 000000 Read only

Write under the password protection:


Start 765432 765432
Administrator password (Without limits)
V2> 000000 tV2> 000000

Figure 20: V11V Model N Menu Map part 5 (Firmware 1A)


Protection setting password (Protection only)

Control password (Test control)


Start 765432 765432
V2>> 000000 tV2>> 000000
PJ923ENd
Start 765432 765432
VN> 000000 tVN> 000000

Start 765432 765432


VN>> 000000 tVN>> 000000

Start 765432 765432


VN>>> 000000 tVN>>> 000000
VAMP 11V
Getting Started
Getting Started V11V/EN GS v1.0

VAMP 11V (GS) 3-37

GS
V11V/EN GS v1.0 Getting Started

(GS) 3-38 VAMP 11V

Figure 21: V11V Model N Menu Map part 6 (Firmware 1A)

GS

Figure 22: V11V Model N Menu Map part 7 (Firmware 1A)


Getting Started V11V/EN GS v1.0

VAMP 11V (GS) 3-39

GS

Figure 23: V11V Model L Menu Map part 1 (Firmware 1A)


V11V/EN GS v1.0 Getting Started

(GS) 3-40 VAMP 11V

GS

Figure 24: V11V Model L Menu Map part 2 (Firmware 1A)


Getting Started V11V/EN GS v1.0

VAMP 11V (GS) 3-41

GS

Figure 24: V11V Model L Menu Map part 3 (Firmware 1A)


V11V/EN GS v1.0 Getting Started

(GS) 3-42 VAMP 11V

GS

Figure 25: V11V Model L Menu Map part 4 (Firmware 1A)


Getting Started V11V/EN GS v1.0

VAMP 11V (GS) 3-43

3. LOCAL CONNECTION VAMP 11V TO A PC


3.1 Configuration

GS

Figure 26: Connection relay to the PC


Local connection between a PC and the relay is made through a USB cable.
Before connection cable to USB socket it is necessary discharge static electricity
from the body by touching a metal grounded object (such as an unpainted metal
surface) to prevent against ESD damage.
Communications can be established between a PC and a device fitted with a USB port.
The MiCOM S1 STUDIO 5.1.0 (or higher) software has a built-in USB driver and virtual COM
software.
3.2 USB Driver and virtual COM software installation
Note: The MiCOM S1 STUDIO 5.1.0 (or higher) software includes all
drivers therefore no action is needed.
3.2.1 Remote connection
The Figure 27 shows the recommended way to connect an RS485 cable to the relay in order
to build a local network.
V11V/EN GS v1.0 Getting Started

(GS) 3-44 VAMP 11V

3.3 Products plugged into the same panel

A18 A19

GS
P0953ENa

Figure 27: Connection between relays in local network


3.4 MiCOM S1 Studio relay communications basics
MiCOM S1 Studio 5.1.0 (or higher) are the universal VAMP 11x and MiCOM IED Support Software
packages which provide users with a direct and convenient access to all data stored in any VAMP
11x using the USB front communication port.
MiCOM S1 Studio 5.1.0 provide full access to:

− VAMP 11x/MiCOM Px10 relays

− Px20, Px20, Px30, Px40 relays

− MiCOM Mx20 measurements units


The following sections give the main procedures to connect to and to use MiCOM S1 Studio
5.1.0.
Before starting, check that the USB serial cable is properly connected to the USB port on the
front panel of the relay. Please follow the instructions given in section 3.1 in order to ensure
proper connection between the PC and the relay before attempting to communicate with the
relay.
This section is intended as a quick start guide to using MiCOM S1 Studio 5.1.0, and
assumes that you have a copy of MiCOM S1 Studio 5.1.0 installed on your PC. Please refer
to the MiCOM S1 Studio User Manual for more detailed information.
Getting Started V11V/EN GS v1.0

VAMP 11V (GS) 3-45

3.5 MiCOM S1 Studio 5.1.0


3.5.1 MiCOM S1 Studio downloading
The MiCOM S1 Studio can be downloaded from WEB site: www.schneider-electric.com.
In the search field enter “Studio” (1)

During typing an advice will appear as above (type slowly), so select "MiCOM S1 Studio
- IED Support Software” (2)

The new window will appear (see below). Click on “MiCOM S1 Studio 5.1.0” (1)”
GS

The new window will appear (see below). Click on MiCOM S1 Studio Installer 5.1.0 (1)

Note: in case of any problems with finding windows as above, it is possible to go directly to
window below by typing in internet browser: “MiCOM-S1-Studio 5.1.0 Installer.exe”.

The new window will appear (see below). Click “Save file”, than run exe file for starting of
installation.
V11V/EN GS v1.0 Getting Started

(GS) 3-46 VAMP 11V

GS
Getting Started V11V/EN GS v1.0

VAMP 11V (GS) 3-47

3.5.2 Data Model Management

The settings and parameters of the protection relay can be extracted from the relay or
loaded using the Data Model manager. The Data Model Manager can load any model from a
local file, a external disks/drives or an Internet server (if connected).
The Data Model Manager is used to add and remove data models, as well as to export and
import data model files.
It is necessary to close MiCOM S1 Studio prior to launching the Data Model Manager.

To open the Data Model Manager, click on the icon: . Select "All
" programs" then
"Schneider Electric" and than "MiCOM S1 Studio".

GS

The following window is displayed:

Select the Add option to add the new data model then click on Next..
V11V/EN GS v1.0 Getting Started

(GS) 3-48 VAMP 11V

The next window is used to select the data model's source (external
(external drives, local folder or
Schneider Electric FTP server). Select the data model's source then click on Next.

GS

Note: The procedure below assumes connection to Schneider Electric FTP


server.

The Data Modell Manager loads the data models details then automatically displays the
language selection panel. Select the menu language then click on Next.

The data models panel is displayed.


displayed. Select the data model relevant to your product
prod (for
instance, to download V11
11V data models, expand the V11x/Px10/Px20/Px20C/M/Modulex
Px10/Px20/Px20C/M/Modulex
sub-menu (click on + then select the data model relevant to your product). Once the data
models are selected, the Data Model Manager window displays the file size of the download.
Getting Started V11V/EN GS v1.0

VAMP 11V (GS) 3-49

GS

Click on Install.. The data model files are downloaded and updated in your system.

Once installation is complete, close the Data Model Manager. The downloaded Data Model
will be used byy MiCOM S1 Studio when a system file is opened or created. For more
information on how to open this default setting file, refer to sub-chapter
chapter 3.5.99.
3.5.3 “Quick Connection” to the relay using MiCOM S1 Studio

To start MiCOM S1 Studio, click on the icon:

In the Programs menu, select Schneider Electric then MiCOM S1 Studio.


Studio
V11V/EN GS v1.0 Getting Started

(GS) 3-50 VAMP 11V

GS

The MiCOM S1 Studio launcher screen is displayed:

− Click on the Quick Connect button at the top left of the application's window.
Getting Started V11V/EN GS v1.0

VAMP 11V (GS) 3-51

− Select Px10/V11x Series from the presented options:

GS

− Select Front USB port:

− Enter Password: administrator level (without limits) - the same as in the V11V which is
connected via USB port. If the administrator password is not entered in the V11V – leave it
as default. Note: the password could be unique for every V11V so if the password is
forgotten – contact with SE service for help.
Select virtual COM (VCP) which was created by USB driver:
V11V/EN GS v1.0 Getting Started

(GS) 3-52 VAMP 11V

GS

The virtual COM can be read in WINDOWS’s “Device Manager” like below:

NOTE: If V11V is connected but no any USB Serial port is shown, it means that USB drivers
are not installed or VCP (Virtual COM Port) option of USB Serial Converter is not
selected. Check VCP option as below:
Getting Started V11V/EN GS v1.0

VAMP 11V (GS) 3-53

Right-click to open the contextual menu: Properties and Advanced:

GS
Unplug USB cable and plug in again. Restart MiCOM S1 Studio and repeat the procedure.

− Select Language. Enter Name and Comment:


V11V/EN GS v1.0 Getting Started

(GS) 3-54 VAMP 11V

− The new Device is created:

GS

− Select Settings. Right-click to open the contextual menu: Extract Settings:

− Wait for the end of the process:


Getting Started V11V/EN GS v1.0

VAMP 11V (GS) 3-55

− V11V settings were saved on PC. The name of SET file is 000.set:

GS

− Double Click on 000.set set file to see settings on the right window of MiCOM S1
Studio:

− Change settings. Save changes


Note: If the changed settings are not Saved on hard disk of PC, MiCOM S1 Studio send
setting file before changing. Be sure that Save icon was pressed:
V11V/EN GS v1.0 Getting Started

(GS) 3-56 VAMP 11V

GS
− Click on the name of Device and right-click to open the contextual menu: Send:

− Select setting (000.set) file for sending. Press Send:


Getting Started V11V/EN GS v1.0

VAMP 11V (GS) 3-57

− If 000.set file was saved on the PC disc, press Yes:

− Wait for the end of operation. Press Close:

GS

Settings were sent to V11V.

3.5.4 Create a system


In MiCOM S1 Studio, a System provides a root node in the Studio Explorer panel from which
all subsequent nodes are created.
Add substations, bays, voltage levels and devices to the system.
If a system is no longer needed, delete it using the delete command.
The use of Quick Connect will automatically create a default system, if one does not already
exist. Systems are not opened automatically, unless Reopen last System at start-up is
checked in the Preferences menu.
To create a new system:

− By default, the window displays the message “create new or open existing system”: click
on "New" to create a new system.

− If a system is loaded in the Studio Explorer window, right-click on the panel's


background and select "New System" or the corresponding icon on Studio Explorer's
toolbar.
V11V/EN GS v1.0 Getting Started

(GS) 3-58 VAMP 11V

GS
− The following window is displayed: Enter the name of the system, and the path to save
the system file. Click OK.

The new System is displayed in the Studio Explorer panel:

Note: If an item is selected in the Studio Explorer panel, its properties are
displayed in the Properties panel:
Getting Started V11V/EN GS v1.0

VAMP 11V (GS) 3-59

3.5.5 Create a new substation


Select the system: the menu bar is updated with the New device, New substation, Close,
Delete, Paste, Properties and Options icons.

GS

Click on the New substation icon (or right-click to open the contextual menu). The following
window is displayed:
V11V/EN GS v1.0 Getting Started

(GS) 3-60 VAMP 11V

The new substation is displayed and the menu bar is updated when a substation is selected:

GS

Click on the Import SCL button to import a Substation Configuration File.


To create a substation configuration, click on the New voltage level button.
3.5.6 Create a new voltage level
Select the substation and click on the New station level button (or right-click to open the
contextual menu).
In the Create a new voltage level, enter the voltage level of the station.
The New voltage level is displayed and the New bay icon is displayed.
Getting Started V11V/EN GS v1.0

VAMP 11V (GS) 3-61

3.5.7 Create a new bay


Select the substation and click on the New bay button (or right-click to open the contextual
menu).
In the Create new bay window, enter the bay indication,
The new bay is displayed.

GS

3.5.8 Create a new device


Click on the New device button (or right-click to open the contextual menu).
Select the device type:
V11V/EN GS v1.0 Getting Started

(GS) 3-62 VAMP 11V

Select the device type then click on Next, select the model then click on Next:

GS

Enter the name and add a description to the device:


Getting Started V11V/EN GS v1.0

VAMP 11V (GS) 3-63

The new device is created and displayed:

GS

3.5.9 Open a Settings File


To open an existing file:

− If the file is saved or if the relay is not connected: Click on the Settings and right-click to
open the contextual menu: Add Existing file
V11V/EN GS v1.0 Getting Started

(GS) 3-64 VAMP 11V

− If the relay is connected, extract its settings: Click on the Settings and right-click to open
the contextual menu: Extract Settings

GS

To open default settings:

− Click on the Settings and right-click to open the contextual menu: New File

− The new setting file 000.set is created:


Getting Started V11V/EN GS v1.0

VAMP 11V (GS) 3-65

GS

− Start working with VAMP 11V relay.


V11V/EN GS v1.0 Getting Started

(GS) 3-66 VAMP 11V

3.6 Troubleshooting USB connection


The virtual COM can be read in WINDOWS’s “Device Manager” like below:

GS
NOTE: If V11V is connected but no any USB Serial port is shown, it means that:

a) USB drivers are not installed


or
b) VCP (Virtual COM Port) option of USB Serial Converter is not selected.
USB drivers:

If you can’t see “USB Serial Converter” it means that USB divers are not installed.
Refer section “3.2 USB Driver and virtual COM software installation”
Getting Started V11V/EN GS v1.0

VAMP 11V (GS) 3-67

VCP (Virtual COM Port)


On the window as below:

GS
Check VCP option by right-click to open the contextual menu: Properties and Advanced:

Unplug USB cable and plug in again. Restart MiCOM S1 Studio and repeat the procedure.
V11V/EN GS v1.0 Getting Started

(GS) 3-68 VAMP 11V

3.7 Presentation and analysis of disturbances


Reading and analysis of disturbance records is done using Wavewin.
To open Wavewin with MiCOM S1 Studio:
In the Programs menu, select MiCOM S1 Studio then PX20, Px20C, M, Modulex Series
Tools then WaveWin

GS

Using MiCOM S1 Studio, open Wavewin using the Tools menu.

The Wavewin File Manager is displayed (refer to the Wavewin User’s guide to operate
Wavewin).
Getting Started V11V/EN GS v1.0

VAMP 11V (GS) 3-69

GS
V11V/EN GS v1.0 Getting Started

(GS) 3-70 VAMP 11V

4. COMPANY CONTACT INFORMATION


If you need information pertaining to the operation of the VAMP 11x product that you have
purchased, please contact your local Schneider Electric agent or the After Sales Service
Department of Schneider Electric. Do not forget to give the serial number and reference of
the VAMP 11x product.
The VAMP 11x product reference and serial numbers are documented under the upper
hinged cover on the front of the relay. For more precise information, refer to the section
"Relay Identification" in this chapter.
PLEASE PROVIDE THE FOLLOWING INFORMATION WHEN CONTACTING
SCHNEIDER ELECTRIC:

− CORTEC code of the VAMP 11x relay

− Serial number of the VAMP 11x relay

− Schneider Electric order reference


GS − Schneider Electric operator reference

Schneider Electric Worldwide Contact Centre:

− Website: http://www.schneider-electric.com/CCC
Settings V11V/EN ST v1.0

VAMP 11V

ST

SETTINGS

Date: 1st December 2015


Software Version: 1A
Connection Diagrams: 10V11V
Settings V11V/EN ST v1.0

VAMP 11V (ST) 4-1

CONTENTS

1. GENERAL INFORMATION 3
2. SETTINGS 5
2.1 Protection Settings 5
2.1.1 Phase O/V [59] 5
2.1.2 Phase U/V [27] 7
2.1.3 Positive sequence U/V [27D] (A) 9
2.1.4 Negative Sequence O/V [46] (NA) 11
2.1.5 E/GND FAULT O/V [59N] 13
2.1.6 FREQUENCY [81O/81U] (A) 15
ST
2.1.7 Auxiliary Timers (AN) 16
2.2 Input Configuration 17
2.3 Output Relay Configuration 21
2.4 LED Configuration 26

3. GLOBAL SETTINGS 30
3.1 LOC 30
3.2 Setting Group Select 31
3.3 VT’s Supervision (AN) 32
3.4 VT Ratio 34
3.5 Circuit Breaker 34
3.6 Voltage Advanced Configuration 35
3.7 [81] Advanced Settings (A) 36
3.8 Communication (AN) 37
3.9 Disturbance Recorder (A) 38

4. COMMISSIONING (AN) 39
5. SETTING CHANGE MODE 41
6. OP PARAMETERS 42
V11V/EN ST v1.0 Settings

(ST) 4-2 VAMP 11V

ST
Settings V11V/EN ST v1.0

VAMP 11V (ST) 4-3

1. GENERAL INFORMATION
The V11V must be configured to the system and application by means of the appropriate
settings. This section gives instructions for determining the settings, which are located in the
folder entitled, Schneider Electric Energy in the menu tree. The order in which the settings
are listed and described in this chapter is: the protection settings, control and configuration
settings (see section V11V/EN GS for the detailed relay menu map). The relay is supplied
with a factory-set configuration of default settings
All voltage settings are in secondary side voltage (transform by VT). The voltage can be
defined as phase to phase or phase to neutral measurements. We have four possibilities for
VT connections, like as:

− 3Upn – connected three voltage phase to neutral

− 3Upn + UN – connected three voltage phase to neutral and earth fault voltage (open
delta)

− 2Upp + UN – connected two voltage phase to phase and earth fault voltage (open
delta) ST
− 3Upp + UN – connected three voltage phase to phase and earth fault voltage (open
delta)
MiCOM S1 Studio 5.1.0 (or higher) can be used to download and upload protection and
configuration setting values via the relay's USB port.
The protection and I/O settings include all the following items that become active once
enabled in the configuration column of the relay menu database:

− Protection element settings,

− Output settings,

− Input settings,

− LED settings.
There are two groups of protection and I/O settings, with each group containing the same
setting cells. One group of protection and I/O settings is selected as the active group, and is
used by the protection elements. The settings for group 1 are shown. The settings are
discussed in the same order in which they are displayed in the menu.
The menu structure is as follows:
- DEFAULT WINDOW - Voltage phase to phase and phase to neutral in multiples of Vn, all
type voltage like above in Volts, CB Control window (A), Local/remote control window (NA),
status of frequency protection (A)
- ALARM STATUS
- RECORDS
- FAULT RECORD
- ALARM RECORD
- COUNTERS
- CONTROL COUNTER
- FAULT COUNTER
- MAXIMUM MEASURMENT VALUES
- SETTING GROUP 1
- PROTECTION G1
- PHASE O/V G1 [59]
V11V/EN ST v1.0 Settings

(ST) 4-4 VAMP 11V

- PHASE U/V G1 [27]


- E/GND FAULT O/V G1 [59N]
- NEGATIVE SEQUENCE O/V G1 [47] (NA)
- POSITIVE SEQUENCE U/V G1 [27D] (A)
- FREQUENCY G1 [81O/81U] (A)
- AUX TIMERS G1 (A)
- OUTPUT RELAY CONFIGURATION G1
- INPUTS CONFIGURATION G1
- LEDS CONFIGURATION G1
- SETTING GROUP 2
- PROTECTION G2
ST - PHASE O/V G2 [59]
- PHASE U/V G2 [27]
- E/GND FAULT O/V G2 [59N]
- NEGATIVE SEQUENCE O/V G2 [47] (NA)
- POSITIVE SEQUENCE U/V G2 [27D] (A)
- FREQUENCY G2 [81O/81U] (A)
- AUX TIMERS G2 (A)
- OUTPUT RELAY CONFIGURATION G2
- INPUTS CONFIGURATION G2
- LEDS CONFIGURATION G2
- GLOBAL SETTINGS
- LOC
- SETTING GROUP SELECT
- VT RATIO
- CIRCUIT BREAKER (A)
- VT SUPERVISION (A)
- [81] ADVANCED SETTINGS (A)
- VOLTAGE ADVANCED CONFIGURATION
- COMMUNICATION RS485 (NA)
- DISTURBANCE RECORDER (A)
- COMMISSIONING
- SETTING CHANGE MODE
- OP PARAMETERS
- MEASUREMENTS
Settings V11V/EN ST v1.0

VAMP 11V (ST) 4-5

2. SETTINGS
2.1 Protection Settings
2.1.1 Phase O/V [59]
The overvoltage protection included in the V11V relays provides three-stage overvoltage
protection with independent time-delay characteristics (DT or IDMT – dependent for stage),
which can be set to operate from phase to phase or phase to neutral voltage. All overvoltage
settings apply to all three phases but are independent for each of the three stages.
The first overvoltage stags have time-delayed characteristics which are selectable between
inverse definite minimum time (IDMT) and definite time (DMT). The second and third stage
has definite time characteristics (DMT) only.

Setting Range
Menu Text Default Setting Step Size
Min. Max.
Disabled, OR Trip, OR Alarm, AND Trip,
V> ? Disabled
AND Alarm, OR Trip/52a (NA), OR ST
Alarm/52a (NA), AND Trip/52a (NA), AND
Alarm/52a (NA)
Setting to disable or enable the protection element.
The protection element can be set to trip the CB (Enable Trip), only issue an Alarm signal
(Enable Alarm), option OR means that, protection will work when fault appears in any one
phase, for AND when fault appears in all three phases. Trip/52a and Alarm/52a means
that we have possibility to block this protection function from state CB – turn off position.
If the protection element is set to 'Trip' it means that it is linked to the Protection trip (see
LED and Output configuration) and Trip Command (see Output configuration) functions.
Additionally this protection element will trigger fault recording, disturbance recording, as
well as the Trip LED on the front panel.
If the protection element is set to 'Alarm' it means that it is linked to the Alarm function
(see LED and Output configuration) and 'ALARM STATUS' indication.
20 V 5V 200 V 0.1 V
V> Threshold
20 V 20 V 720 V 0.1 V
Pick-up setting for the first stage of the overvoltage element.
We have two ranges of settings, first is for 57 – 130 VAC, second is for 220 – 480 VAC.
DT, IEC_SI, IEC_VI, IEC_EI, IEC_LTI,
UK_STI, RECT, RI, IEEE_MI, IEEE_VI,
V> Delay Type DT
IEEE_EI, CO2_Px20, US_CO8, RXIDG,
BPN_EDF, CO2_Px40
Setting for the tripping characteristic for the first stage overvoltage element.
tV> /TMS/TD 0.02 s 0.02 s* 200 s* 0.01 s*
Setting for the time-delay for the definite time setting if selected for first stage element and
setting for the time multiplier setting to adjust the operating time of the all IDMT.
* Range and step size for DMT curve. Range and step size for IDMT curves are described
below:
1) TD: min=0.02 s; max=100 s, step size=0.01 s,
2) TMS: min=0.02 s; max=1.5 s, step size=0.01 s,
3) k: min=0.3 s; max=1 s, step size=0.01 s,
4) K: min=0.1 s; max=10 s, step size=0.1 s.
V> Reset Delay Type DT High State DT High State or IDMT N/A
Setting to determine the type of reset/release characteristic of the IEEE/US curves.
V> DMT tReset 0s 0s 600 s 0.01 s
Setting that determines the reset/release time for definite time reset characteristics.
V11V/EN ST v1.0 Settings

(ST) 4-6 VAMP 11V

Setting Range
Menu Text Default Setting Step Size
Min. Max.
Disabled, OR Trip, OR Alarm, AND Trip,
AND Alarm, OR Trip/52a (NA), OR
V>> ? Disabled
Alarm/52a (NA), AND Trip/52a (NA), AND
Alarm/52a (NA)
See V>
40 V 5V 200 V 0.1 V
V>> Threshold
40 V 20 V 720 V 0.1 V
Pick-up setting for the second stage of the overvoltage element.
We have two ranges of settings, first is for 57 – 130 VAC, second is for 220 – 480 VAC.
tV>> 0.02 s 0.02 s 200 s 0.01 s
Setting for the time-delay for the definite time setting for this stage element.

ST Disabled, OR Trip, OR Alarm, AND Trip,


AND Alarm, OR Trip/52a (NA), OR
V>>> ? Disabled
Alarm/52a (NA), AND Trip/52a (NA), AND
Alarm/52a (NA)
See V>
50 V 5V 200 V 0.1 V
V>>> Threshold
50 V 20 V 720 V 0.1 V
Pick-up setting for the third stage of the overvoltage element.
We have two ranges of settings, first is for 57 – 130 VAC, second is for 220 – 480 VAC.
tV>>> 0.02 s 0.02 s 200 s 0.01 s
Setting for the time-delay for the definite time setting for this stage element.

IDMT tripping can be blocked if any DMT stage is started, settings: IDMT interlock by DMT
(GLOBAL SETTINGS/O/V ADVANCED column). This settings is common for E/Gnd Fault
O/V [59N], Phase O/V [59] and Phase U/V [27]

Menu Text Default Setting Setting Range Step Size


IDMT interlock by
No No Yes n/a
DMT stage
[27] Hysteresis 1.05 1.00 1.20 0.01
Sets drop off of undervoltage protection
[59] Hysteresis 0.95 0.80 1.00 0.01
Sets drop off of overvoltage protection
Settings V11V/EN ST v1.0

VAMP 11V (ST) 4-7

2.1.2 Phase U/V [27]


The undervoltage protection included in the V11V relays provides three-stage undervoltage
protection with independent time-delay characteristics (DT or IDMT – dependent for stage),
which can be set to operate from phase to phase or phase to neutral voltage. All
undervoltage settings apply to all three phases but are independent for each of the three
stages.

Setting Range
Menu Text Default Setting Step Size
Min. Max.
Disabled, OR Trip, OR Alarm, AND Trip,
AND Alarm, OR Trip/52a (NA), OR
V< ? Disabled
Alarm/52a (NA), AND Trip/52a (NA), AND
Alarm/52a (NA)
Setting to disable or enable the protection element.
The protection element can be set to trip the CB (Enable Trip), only issue an Alarm signal
(Enable Alarm), option OR means that, protection will work when fault appears in any one
phase, for AND when fault appears in all three phases. Trip/52a and Alarm/52a means ST
that we have possibility to block this protection function from state CB – turn off position.
If the protection element is set to 'Trip' it means that it is linked to the Protection trip (see
LED and Output configuration) and Trip Command (see Output configuration) functions.
Additionally this protection element will trigger fault recording, disturbance recording, as
well as the Trip LED on the front panel.
If the protection element is set to 'Alarm' it means that it is linked to the Alarm function
(see LED and Output configuration) and 'ALARM STATUS' indication.
20 V 5V 130 V 0.1 V
V< Threshold
20 V 20 V 480 V 0.1 V
Pick-up setting for the first stage of the undervoltage element.
We have two ranges of settings, first is for 57 – 130 VAC, second is for 220 – 480 VAC.
DT, IEC_SI, IEC_VI, IEC_EI, IEC_LTI,
UK_STI, RECT, RI, IEEE_MI, IEEE_VI,
V< Delay Type DT
IEEE_EI, CO2_Px20, US_CO8, RXIDG,
BPN_EDF, CO2_Px40
Setting for the tripping characteristic for the first stage undervoltage element.
tV< /TMS/TD 0.02 s 0.02 s* 200 s* 0.01 s*
Setting for the time-delay for the definite time setting if selected for first stage element and
setting for the time multiplier setting to adjust the operating time of the all IDMT.
* Range and step size for DMT curve. Range and step size for IDMT curves are described
below:
1) TD: min=0.02 s; max=100 s, step size=0.01 s,
2) TMS: min=0.02 s; max=1.5 s, step size=0.01 s,
3) k: min=0.3 s; max=1 s, step size=0.01 s,
4) K: min=0.1 s; max=10 s, step size=0.1 s.
V< Reset Delay Type DT High State DT High State or IDMT N/A
Setting to determine the type of reset/release characteristic of the IEEE/US curves.
V< DMT tReset 0s 0s 600 s 0.01 s
Setting that determines the reset/release time for definite time reset characteristics.
Disabled, OR Trip, OR Alarm, AND Trip,
AND Alarm, OR Trip/52a (NA), OR
V<< ? Disabled
Alarm/52a (NA), AND Trip/52a (NA), AND
Alarm/52a (NA)
See V<
V11V/EN ST v1.0 Settings

(ST) 4-8 VAMP 11V

Setting Range
Menu Text Default Setting Step Size
Min. Max.
40 V 5V 130 V 0.1 V
V<< Threshold
40 V 20 V 480 V 0.1 V
Pick-up setting for the second stage of the undervoltage element.
We have two ranges of settings, first is for 57 – 130 VAC, second is for 220 – 480 VAC.
tV<< 0.02 s 0.02 s 200 s 0.01 s
Setting for the time-delay for the definite time setting for this stage element.
Disabled, OR Trip, OR Alarm, AND Trip,
AND Alarm, OR Trip/52a (NA), OR
V<<< ? Disabled
Alarm/52a (NA), AND Trip/52a (NA), AND
Alarm/52a (NA)
See V<

ST V<<< Threshold
50 V 5V 130 V 0.1 V
50 V 20 V 480 V 0.1 V
Pick-up setting for the third stage of the undervoltage element.
We have two ranges of settings, first is for 57 – 130 VAC, second is for 220 – 480 VAC.
tV<<< 0.02 s 0.02 s 200 s 0.01 s
Setting for the time-delay for the definite time setting for this stage element.
Settings V11V/EN ST v1.0

VAMP 11V (ST) 4-9

2.1.3 Positive sequence U/V [27D] (A)


This function is used to protect motors against faulty operation due to insufficient or
unbalanced network voltage, and detection of reverse rotation of motor.
The positive sequence undervoltage element included in the V11V relays provides two stage
non-directional undervoltage protection with independent time-delay characteristics. These
characteristics are selectable between inverse definite minimum time (IDMT) and definite
time (DT) for first stage. Second stage can operate only with DT characteristic.

Setting Range
Menu Text Default Setting Step Size
Min. Max.
V1 < ? Disabled Disabled, Trip, Alarm, Trip/52a, Alarm/52a
Setting to disable or enable the protection element.
The protection element can be set to trip the CB (Enable Trip), only issue an Alarm signal
(Enable Alarm).
If the protection element is set to 'Trip' it means that it is linked to the Protection trip (see
LED and Output configuration) and Trip Command (see Output configuration) functions.
Additionally this protection element will trigger fault recording, disturbance recording, as
ST
well as the Trip LED on the front panel.
If the protection element is set to 'Alarm' it means that it is linked to the Alarm function
(see LED and Output configuration) and 'ALARM STATUS' indication.
20 V 5V 130 V 0.1 V
V1< Threshold
20 V 20 V 480 V 0.1 V
Pick-up setting for the first stage positive sequence U/V element.
We have two ranges of settings, first is for 57 – 130 VAC, second is for 220 – 480 VAC.
DT, IEC_SI, IEC_VI, IEC_EI, IEC_LTI, UK_STI,
RECT, RI, IEEE_MI, IEEE_VI, IEEE_EI,
V1< Delay Type DT
CO2_Px20, US_CO8, RXIDG, BPN_EDF,
CO2_Px40
Setting for the tripping characteristic for the first stage positive sequence U/V element.
tV1</TMS/TD 0.02 s 0.02 s* 200 s* 0.01 s*
Setting for the time-delay for the definite time setting if selected for first stage element and
setting for the time multiplier setting to adjust the operating time of the all IDMT.
* Range and step size for DMT curve. Range and step size for IDMT curves are described
below:
1) TD: min=0.02 s; max=100 s, step size=0.01 s,
2) TMS: min=0.02 s; max=1.5 s, step size=0.01 s,
3) k: min=0.3 s; max=1 s, step size=0.01 s,
4) K: min=0.1 s; max=10 s, step size=0.1 s.
V1< Reset Delay
DT High State DT High State or IDMT N/A
Type
Setting to determine the type of reset/release characteristic of the IEEE/US curves.
V1< DMT tReset 0s 0s 600 s 0.01 s
Setting that determines the reset/release time for definite time reset characteristics.
V1 << ? Disabled Disabled, Trip, Alarm, Trip/52a, Alarm/52a
See V1<
40 V 5V 130 V 0.1 V
V1<< Threshold
40 V 20 V 480 V 0.1 V
Pick-up setting for the second stage positive sequence U/V element.
We have two ranges of settings, first is for 57 – 130 VAC, second is for 220 – 480 VAC.
V11V/EN ST v1.0 Settings

(ST) 4-10 VAMP 11V

Setting Range
Menu Text Default Setting Step Size
Min. Max.
tV1<< 0.02 s 0.02 s 200 s 0.01 s
Setting for the time-delay for the definite time setting for this stage element.

ST
Settings V11V/EN ST v1.0

VAMP 11V (ST) 4-11

2.1.4 Negative Sequence O/V [46] (NA)


This function is used to protect against unbalance resulting from phase inversion or
unbalanced supply.
The negative sequence overvoltage element included in the V11V relays provides two stage
non-directional overvoltage protection with independent time-delay characteristics. These
characteristics are selectable between inverse definite minimum time (IDMT) and definite
time (DT) for first stage, second stage can operate only with DT characteristic.

Setting Range
Menu Text Default Setting Step Size
Min. Max.
V2> ? Disabled Disabled, Trip, Alarm, Trip/52a, Alarm/52a
Setting to disable or enable the protection element.
The protection element can be set to trip the CB (Enable Trip), only issue an Alarm signal
(Enable Alarm.
If the protection element is set to 'Trip' it means that it is linked to the Protection trip (see
LED and Output configuration) and Trip Command (see Output configuration) functions.
ST
Additionally this protection element will trigger fault recording, disturbance recording, as
well as the Trip LED on the front panel.
If the protection element is set to 'Alarm' it means that it is linked to the Alarm function
(see LED and Output configuration) and 'ALARM STATUS' indication.
20 V 5V 200 V 0.1 V
V2> Threshold
20 V 20 V 720 V 0.1 V
Pick-up setting for the first stage negative sequence O/V element.
We have two ranges of settings, first is for 57 – 130 VAC, second is for 220 – 480 VAC.
DT, IEC_SI, IEC_VI, IEC_EI, IEC_LTI,
UK_STI, RECT, RI, IEEE_MI, IEEE_VI,
V2> Delay Type DT
IEEE_EI, CO2_Px20, US_CO8, RXIDG,
BPN_EDF, CO2_Px40
Setting for the tripping characteristic for the first stage negative sequence O/V element.
tV2>/TMS/TD 0.02 s 0.02 s* 200 s* 0.01 s*
Setting for the time-delay for the definite time setting if selected for first stage element and
setting for the time multiplier setting to adjust the operating time of the all IDMT.
* Range and step size for DMT curve. Range and step size for IDMT curves are described
below:
1) TD: min=0.02 s; max=100 s, step size=0.01 s,
2) TMS: min=0.02 s; max=1.5 s, step size=0.01 s,
3) k: min=0.3 s; max=1 s, step size=0.01 s,
4) K: min=0.1 s; max=10 s, step size=0.1 s.
V2> Reset Delay
DT High State DT High State or IDMT N/A
Type
Setting to determine the type of reset/release characteristic of the IEEE/US curves.
V2> DMT tReset 0s 0s 600 s 0.01 s
Setting that determines the reset/release time for definite time reset characteristics.
V2>> ? Disabled Disabled, Trip, Alarm, Trip/52a, Alarm/52a
See V2>>
40 V 5V 200 V 0.1 V
V2>> Threshold
40 V 20 V 720 V 0.1 V
Pick-up setting for the first stage negative sequence O/V element.
We have two ranges of settings, first is for 57 – 130 VAC, second is for 220 – 480 VAC.
V11V/EN ST v1.0 Settings

(ST) 4-12 VAMP 11V

Setting Range
Menu Text Default Setting Step Size
Min. Max.
tV2>> 0.02 s 0.02 s 200 s 0.01 s
Setting for the time-delay for the definite time setting for this stage element.

ST
Settings V11V/EN ST v1.0

VAMP 11V (ST) 4-13

2.1.5 E/GND FAULT O/V [59N]


The Earth fault element operates from a measured or calculated (from phase voltage) earth
fault voltage value.
The first earth fault stage has time-delayed characteristics which are selectable between
inverse definite minimum time (IDMT) and definite time (DT). The second and third stages
have a definite time characteristic only.

Setting Range
Menu Text Default Setting Step Size
Min. Max.
Disabled, Trip (measured), Alarm
(measured), Trip (Ua+Ub+Uc), Alarm
VN> ? Disabled (Ua+Ub+Uc)
Measured option is available in model N, A
only
Setting to disable or enable the protection element.
The protection element can be set to trip the CB (Enable Trip), only issue an Alarm signal ST
(Enable Alarm). Trip/Alarm (measured) earth fault voltage will be measured, when we
select Trip/Alarm (Ua+Ub+Uc) earth fault voltage will be calculated.
If the protection element is set to 'Trip' it means that it is linked to the Protection trip (see
LED and Output configuration) and Trip Command (see Output configuration) functions.
Additionally this protection element will trigger fault recording, disturbance recording, as
well as the Trip LED on the front panel.
If the protection element is set to 'Alarm' it means that it is linked to the Alarm function
(see LED and Output configuration) and 'ALARM STATUS' indication.
VN> Threshold 5V 0.5 V 130 V 0.1 V
Pick-up setting for the first stage of the overvoltage element.
DT, IEC_SI, IEC_VI, IEC_EI, IEC_LTI,
UK_STI, RECT, RI, IEEE_MI, IEEE_VI,
VN> Delay Type DT
IEEE_EI, CO2_Px20, US_CO8, RXIDG,
BPN_EDF, CO2_Px40
Setting for the tripping characteristic for the first stage E/F overvoltage element.
tVN> /TMS/TD 0.02 s 0.02 s* 200 s* 0.01 s*
Setting for the time-delay for the definite time setting if selected for first stage element and
setting for the time multiplier setting to adjust the operating time of the all IDMT.
* Range and step size for DMT curve. Range and step size for IDMT curves are described
below:
1) TD: min=0.02 s; max=100 s, step size=0.01 s,
2) TMS: min=0.02 s; max=1.5 s, step size=0.01 s,
3) k: min=0.3 s; max=1 s, step size=0.01 s,
4) K: min=0.1 s; max=10 s, step size=0.1 s.
VN> Reset Delay
DT High State DT High State or IDMT N/A
Type
Setting to determine the type of reset/release characteristic of the IEEE/US curves.
VN> DMT tReset 0s 0s 600 s 0.01 s
Setting that determines the reset/release time for definite time reset characteristics.
Disabled, Trip (measured), Alarm
(measured), Trip (Ua+Ub+Uc), Alarm
VN>> ? Disabled (Ua+Ub+Uc)
Measured option is available in model N, A
only
See VN>
V11V/EN ST v1.0 Settings

(ST) 4-14 VAMP 11V

Setting Range
Menu Text Default Setting Step Size
Min. Max.
VN>> Threshold 10 V 0.5 V 130 V 0.1 V
Pick-up setting for the second stage of the overvoltage element.
tVN>> 0.02 s 0.02 s 200 s 0.01 s
Setting for the time-delay for the definite time setting for this stage element.
Disabled, Trip (measured), Alarm
(measured), Trip (Ua+Ub+Uc), Alarm
VN>>> ? Disabled (Ua+Ub+Uc)
Measured option is available in model N, A
only
See VN>
VN>>> Threshold 15 V 0.5 V 130 V 0.1 V
ST Pick-up setting for the third stage of the E/F overvoltage element.
We have two ranges of settings, first is for 57 – 130 VAC, second is for 220 – 480 VAC.
tVN>>> 0.02 s 0.02 s 200 s 0.01 s
Setting for the time-delay for the definite time setting for this stage element.
Settings V11V/EN ST v1.0

VAMP 11V (ST) 4-15

2.1.6 FREQUENCY [81O/81U] (A)


This function has two possibility to work: underfrequency or overfrequency. Underfrequency
is used to detection of abnormally low frequency compared to the rated frequency, to monitor
power supply quality, overfrequency option can detect abnormally high frequency of power
supply.
The frequency element included in the V11V relay provides six stages of non-directional
overfrequency or underfrequency protection with independent time-delay characteristics.
These characteristics are only definite time (DT) characteristic.

Setting Range
Menu Text Default Setting Step Size
Min. Max.
Disabled, f> Trip, f> Alarm, f< Trip,
f1 ? Disabled
f< Alarm
Setting to disable or enable the protection element.
The protection element can be set to trip the CB (Enable Trip), only issue an Alarm signal ST
(Enable Alarm). We can select overfrequency (f>) type or underfrequency (f<).
If the protection element is set to 'Trip' it means that it is linked to the Protection trip (see
LED and Output configuration) and Trip Command (see Output configuration) functions.
Additionally this protection element will trigger fault recording, disturbance recording, as
well as the Trip LED on the front panel.
If the protection element is set to 'Alarm' it means that it is linked to the Alarm function
(see LED and Output configuration) and 'ALARM STATUS' indication.
f1 Threshold 50 Hz 40 Hz 60 Hz 0.01 Hz
Pick-up setting for the first stage frequency element, when in GLOBAL SETTINGS
/GENERAL SETTINGS/Nominal Frequency is set on 50Hz
f1 Threshold 50 Hz 50 Hz 70 Hz 0.01 Hz
Pick-up setting for the first stage frequency element, when in GLOBAL SETTINGS
/GENERAL SETTINGS/Nominal Frequency is set on 60Hz
tf1 0.1 s 0.1 s 600 s 0.01 s
Setting for the time-delay for the definite time setting for first stage element.
For f2 to f6 stages, settings are the same like for f1 stage
V11V/EN ST v1.0 Settings

(ST) 4-16 VAMP 11V

2.1.7 Auxiliary Timers (AN)

Setting Range
Menu Text Default Setting Step Size
Min. Max.
AUX1 ? Disabled Disabled , Trip, Alarm
Setting to disable or enable the AUX element.
The element can be set to:
- trip the CB (Enable Trip),
- signal only (Alarm).
tAUX1 0s 0s 600 s 0.01 s
Setting for the operating time-delay of the AUX1 function.
AUX2 ? Disabled See AUX1?
Same as AUX1

ST tAUX2 0s 0s 600 s 0.01 s


Setting for the operating time-delay of the AUX2 function.
AUX3 ? Disabled See AUX1?
Same as AUX1
tAUX3 0s 0s 600 s 0.01 s
Setting for the operating time-delay of the AUX3 function.
Settings V11V/EN ST v1.0

VAMP 11V (ST) 4-17

2.2 Input Configuration


Binary Input settings define which signals are mapped to the V11V opto-isolated inputs.
Matrix configuration allows free mapping of any one function to each input.
Note:
- Model L has no inputs
- Model N has 2 binary inputs (L1 to L2)
- Model A has 6 binary inputs (L1 to L6)

Step
Menu Text Default Setting Setting Range
Size

Description of bits: L: 6,5,4,3,2,1

Reverse Input Logic 000000 0-1 1


Reverse logic provides extra flexibility to the application. Reverse Input Logic means that
ST
the high state of a binary input causes the corresponding logic signal to be in low state.
Default Setting: “000000” means that:
L6: “0” – input L6 is without reverse logic. The state of L6 logic input is in line with the
state of L6 binary input
L5: “0” – see Input 6
L4: “0” – see Input 6
L3: “0” – see Input 6
L2: “0” – see Input 6
L1: “0” – see Input 6
Mainten. Mode (A) 000000 0-1 1
Maintenance Mode ON/OFF change.
The selection of the maintenance mode is possible via a logic input, using a control
command (rear or front port), or from the front panel interface. The termination of the
maintenance mode is done via a logic input, using a control command or by the front panel
interface timing out (10 minutes) or turning the power supply off.
This mode allows the user to verify the operation of the protection functions with or
without actually sending any external command (tripping or signaling). If without option is
selected, all the output contacts are blocked, and no command can be issued to these
contacts, even if a protection threshold associated with one of these output contacts has
been crossed.

Reset Latched Sign 000000 0-1 1


The high state of this logic input resets all latched LEDs, Alarm and Trip Information.
Reset Latched
000000 0-1 1
Outputs
The high state of this logic input resets all latched contact outputs
Blocking tV> (NA) 000000 0-1 1
The high state of this logic input enables the blocking logic function of the V> protection
element (resets its associated time-delay).
Blocking tV>> (NA) 000000 0-1 1
The high state of this logic input enables the blocking logic function of the V>> protection
element (resets its associated time-delay)
Blockinging tV>>>
000000 0-1 1
(NA)
The high state of this logic input enables the blocking logic function of the V>>> protection
element (resets its associated time-delay)
V11V/EN ST v1.0 Settings

(ST) 4-18 VAMP 11V

Step
Menu Text Default Setting Setting Range
Size

Blocking tV< (NA) 000000 0-1 1


The high state of this logic input enables the blocking logic function of the V< element
(resets its associated time-delay)
Blocking tV<< (NA) 000000 0-1 1
The high state of this logic input enables the blocking logic function of the V<< protection
element (resets its associated time-delay)
Blocking tV<<< (NA) 000000 0-1 1
The high state of this logic input enables the blocking logic function of the V<<< protection
element (resets its associated time-delay)
Blocking tV1< (A) 000000 0-1 1
The high state of this logic input enables the blocking logic function of the V1< protection
ST element (resets its associated time-delay)
Blocking tV1<< (A) 000000 0-1 1
The high state of this logic input enables the blocking logic function of the V1<< element
(resets its associated time-delay)
Blocking tV2> (NA) 000000 0-1 1
The high state of this logic input enables the blocking logic function of the V2> (resets its
associated time–delay)
Blocking tV2>> (NA) 000000 0-1 1
The high state of this logic input enables the blocking logic function of the V2>> (resets its
associated time–delay)
Blocking tVN> (NA) 000000 0-1 1
The high state of this logic input enables the blocking logic function of the VN> (resets its
associated time–delay)
Blocking tVN>> (NA) 000000 0-1 1
The high state of this logic input enables the blocking logic function of the VN>> (resets its
associated time–delay)
Blocking tVN>>>
000000 0-1 1
(NA)
The high state of this logic input enables the blocking logic function of the VN>>> (resets its
associated time–delay)
Blocking f1 (A) 000000 0-1 1
The high state of this logic input enables the blocking logic function of the f1 (resets its
associated time–delay)
Blocking f2 (A) 000000 0-1 1
The high state of this logic input enables the blocking logic function of the f2 (resets its
associated time–delay)
Blocking f3 (A) 000000 0-1 1
The high state of this logic input enables the blocking logic function of the f3 (resets its
associated time–delay)
Blocking f4 (A) 000000 0-1 1
The high state of this logic input enables the blocking logic function of the f4 (resets its
associated time–delay)
Blocking f5 (A) 000000 0-1 1
Settings V11V/EN ST v1.0

VAMP 11V (ST) 4-19

Step
Menu Text Default Setting Setting Range
Size

The high state of this logic input enables the blocking logic function of the f5 (resets its
associated time–delay)
Blocking f6 (A) 000000 0-1 1
The high state of this logic input enables the blocking logic function of the f6 (resets its
associated time–delay)
AUX1 (NA) 000000 0-1 1
This logic input energizes the AUX1 function
AUX2 (NA) 000000 0-1 1
This logic input energizes the AUX2 function
AUX3 (A) 000000 0-1 1
This logic input energizes the AUX3 function
ST
AUX4 (A) 000000 0-1 1
This logic input energizes the AUX4 function.
Note:
1. AUX4 has no timer therefore it is not included in the SETTING GROUP
x/PROTECTION Gx/AUX TIMERS submenu.
2. AUX4 cannot be assigned directly to Protection Trip or Alarm functions.
3. AUX4 is used as a simple bridge between an input and the LEDs or an input and the
outputs without any signaling (Alarm or Trip).
AUX5 (A) 000000 0-1 1
This logic input energizes the AUX5 function.
Note:
1. AUX5 has no timer therefore it is not included in the SETTING GROUP
x/PROTECTION Gx/AUX TIMERS submenu.
2. AUX5 cannot be assigned directly to Protection Trip or Alarm functions.
3. AUX5 is used as a simple bridge between an input and the LEDs or an input and the
outputs without any signaling (Alarm or Trip).
CB Status 52A (A) 000000 0-1 1
This logic input provides the V11V with information about the turn on state of the CB. This
information is used by the communication system and CB diagnostic function.
Note:
1. If inputs are assigned to both: CB Status 52A and CB Status 52B, the V11V uses a
two-bit CB status logic.
2. If inputs are assigned to either CB Status 52A or CB Status 52B only, the V11V uses
a one-bit CB status logic
V11V/EN ST v1.0 Settings

(ST) 4-20 VAMP 11V

Step
Menu Text Default Setting Setting Range
Size

CB Status 52B (A) 000000 0-1 1


This logic input provides the V11V with information about the turn off state of the CB. This
information is used by the communication system and the CB diagnostic function.
Note: see above.
CB FLT Ext.Sign (A) 000000 0-1 1
After switching the logic input’s state from low to high this function initiates the “tCB FLT
ext” time-delay and blocks a close command. When this time-delay has elapsed the Alarm
signal is issued.
The binary Input is used to indicate that there is sufficient energy in the CB operating
mechanism to close and trip the CB.
The tCB FLT ext. time-delay is set at GLOBAL SETTINGS/CIRCUIT BREAKER/ tCB FLT
ext.
The Alarm signal can be additionally assigned to output contacts using the CB FLT
ST Ext.Sign output (SETTING GROUP x/OUTPUTRELAYS CONFIGURATION Gx/ CB FLT
Ext.Sign).
Setting group 2 (NA) 000000 0-1 1
The high state of this logic input switches the active setting group to Setting Group 2.
Setting Group 1 is active from the low state of Logic Input.
Note: If two setting groups are switched via binary input, this input must be assigned to
this function in both setting groups: Setting Group 1 and Setting Group 2. If it is not done
there will be not changing of setting group via this input.
Manual Close (A) 000000 0-1 1
Mapping of a control close function to the input. When activated, it is possible to control
the output relays assigned to the Close CB function.
Note: Manual Close command is blocked if:
1. The front panel LEDs are lit (LED resetting is required)
2. An input is assigned to the CB FLT Ext.Sign function and the state of this function is
high
Manual Trip (A) 000000 0-1 1
Mapping of a control trip function to the input. When activated, it is possible to control the
output relay(s) assigned to the Trip CB function
VTS (A) 000000 0-1 1
VT supervision function works when input “VTS” is energising
Start Distur. R. (A) 000000 0-1 1
This logic input triggers the Disturbance Recorder.
Local CTRL Mode (A) 000000 0-1 1
Local mode condition (if enabled, any remote command to the output relays is forbidden).
Time Synchr. (A) 000000 0-1 1
Assigning of a time synchronization input (see Application chapter).
Settings V11V/EN ST v1.0

VAMP 11V (ST) 4-21

2.3 Output Relay Configuration


Output settings define which signals are mapped to the V11V outputs.
Matrix configuration allows free mapping of any one function to each output.
Note:
- Model L have RL1 to RL3 + WD outputs
- Model N have RL1 to RL5 + WD outputs
- Model A have RL1 to RL7 + WD outputs

Menu Text Default Setting Setting Range Step Size

Description of bits: RL: 7,6,5,4,3,2,1

Latched Outputs 0000000 0-1 1


Each output can be configured with or without latching.
Default Setting: “0000000” means that:
ST
RL7: “0” – output RL7 is not latched. The high state of the function mapped to the output
determines the high state of RL7. The low state of this function determines the
low state of RL7 (A).
RL6: “0” – see RL7 (A).
RL5: “0” – see RL7 (NA).
RL4: “0” – see RL7 (NA).
RL3: “0” – see RL7 (LNA).
RL2: “0” – see RL7 (LNA).
RL1: “0” – see RL7 (LNA).
The high state of the function mapped to the output determines the high state of
the output relay. The low state of this function does not change the state of the
output relay. For the low state of output relay, it is necessary to activate the
Reset of Latched Output function (via a binary input, from the front panel or via
a communication port)
Reverse outp.log. 0000000 0-1 1
Reverse outp. logic gives more application flexibility. If reverse logic is chosen for the
output, after the V11V is powered (auxiliary voltage) the output contacts close. Any high
state function connected with this output will open the contacts of the output relay.
Protection Trip 0000000 0-1 1
Protection Trip is high if any protection element configured to Trip is high (voltage-based
protection elements and external protection elements: AUX1, AUX2, AUX3 for model A
and for AUX1, AUX2 model N).
Prot.Trip pulse 0000000 0-1 1
Protection Trip pulse is energized via Protection Trip (see above). This command has
a pulse duration not less than tOpen time set at GLOBAL SETTINGS/CIRCUIT
BREAKER/tOpen pulse min.
Trip CB Order (A) 0000000 0-1 1
The Trip CB Order function is high during the set time if the manual trip command is
executed (communication port, front panel, binary inputs)
(the trip pulse is set at GLOBAL SETTINGS/CIRCUIT BREAKER/ tOpen pulse min)
Close CB Order (A) 0000000 0-1 1
The Close CB Order function is high during the set time if the manual close command or
Auto-reclose function are executed (Communication port, binary input, front panel). The
close pulse is set at GLOBAL SETTINGS/CIRCUIT BREAKER/ tClose Pulse.
V11V/EN ST v1.0 Settings

(ST) 4-22 VAMP 11V

Menu Text Default Setting Setting Range Step Size

Alarm 00000000 0-1 1


The Alarm function is high if any protection element configured to Alarm is high (voltage-
based protection element and external protection elements: AUX1, AUX2, AUX3).
Default Setting: “00000000” means that:
RL7: “0” –RL7 contact is not assigned to the Alarm function
RL6: “0” – see RL7 (A).
RL5: “0” – see RL7 (NA).
RL4: “0” – see RL7 (NA).
RL3: “0” – see RL7 (LNA).
RL2: “0” – see RL7 (LNA).
RL1: “0” – see RL7 (LNA).
Start V> 0000000 0-1 1
ST Start V> is high if the V> protection element has started (voltage above the set V>
threshold).
Start V>> 0000000 0-1 1
Start V>> is high if the V>> protection element has started (voltage above the set V>>
threshold).
Start V>>> 0000000 0-1 1
Start V>>> is high if the V>>> protection element has started (voltage above the set V>>>
threshold).
Start V< 0000000 0-1 1
Start V< is high if the V< protection element has started (voltage below the set V<
threshold).
Start V<< 0000000 0-1 1
Start V<< is high if the V<< protection element has started (voltage below the set V<<
threshold).
Start V<<< 0000000 0-1 1
Start V<<< is high if the V<<< protection element has started (voltage below the set V<
threshold).
Start V1< (A) 0000000 0-1 1
Start V1< is high if the V1< protection element has started (V1 below the set V1<
threshold).
Start V1<< (A) 0000000 0-1 1
Start V1<< is high if the V1<< protection element has started (V1 below the set V1<<
threshold).
Start V2> (NA) 0000000 0-1 1
Start V2> is high if the V2> protection element has started (V2 above the set V2>
threshold).
Start V2>> (NA) 0000000 0-1 1
Start V2>> is high if the V2>> protection element has started (V2 above the set V2>>
threshold).
Start VN> 0000000 0-1 1
Start VN> is high if the VN> protection element has started (VN above the set VN>
threshold).
Start VN>> 0000000 0-1 1
Settings V11V/EN ST v1.0

VAMP 11V (ST) 4-23

Menu Text Default Setting Setting Range Step Size

Start VN>> is high if the VN>> protection element has started (VN above the set VN>>
threshold).
Start VN>>> 0000000 0-1 1
Start VN>>> is high if the VN>>> protection element has started (VN above the set VN>>>
threshold).
Start f1 (A) 0000000 0-1 1
Start f1 is high if the f1 protection element has started (f above or below the set f1
threshold – is contingent on what we set).
Start f2 (A) 0000000 0-1 1
Start f2 is high if the f2 protection element has started (f above or below the set f2
threshold – is contingent on what we set).
Start f3 (A) 0000000 0-1 1 ST
Start f3 is high if the f3 protection element has started (f above or below the set f3
threshold – is contingent on what we set).
Start f4 (A) 0000000 0-1 1
Start f4 is high if the f4 protection element has started (f above or below the set f4
threshold – is contingent on what we set).
Start f5 (A) 0000000 0-1 1
Start f5 is high if the f5 protection element has started (f above or below the set f5
threshold – is contingent on what we set).
Start f6 (A) 0000000 0-1 1
Start f6 is high if the f6 protection element has started (f above or below the set f6
threshold – is contingent on what we set).
AUX1 (NA) 0000000 0-1 1
AUX1 is high if the input assigned to AUX1 is set high.
AUX2 (NA) 0000000 0-1 1
AUX2 is high if the input assigned to AUX2 is set high.
AUX3 (A) 0000000 0-1 1
AUX3 is high if the input assigned to AUX3 is set high.
AUX4 (A) 0000000 0-1 1
AUX4 is high if the input assigned to AUX4 is set high.
AUX5 (A) 0000000 0-1 1
AUX5 is high if the input assigned to AUX5 is set high.
tV> 0000000 0-1 1
tV> is high if the set time-delay for the V> element has elapsed
tV>> 0000000 0-1 1
tV>> is high if the set time-delay for the V>> element has elapsed
tV>>> 0000000 0-1 1
tV>>> is high if the set time-delay for the V>>> element has elapsed
tV< 0000000 0-1 1
tV< is high if the set time-delay for the V< element has elapsed
tV<< 0000000 0-1 1
V11V/EN ST v1.0 Settings

(ST) 4-24 VAMP 11V

Menu Text Default Setting Setting Range Step Size

tV<< is high if the set time-delay for the V<< element has elapsed
tV<<< 0000000 0-1 1
tV<<< is high if the set time-delay for the V<<< element has elapsed
tV1< (A) 0000000 0-1 1
tV1< is high if the set time-delay for the V1< element has elapsed
tV1<< (A) 0000000 0-1 1
tV1<< is high if the set time-delay for the V1<< element has elapsed
tV2> (NA) 0000000 0-1 1
tV2> is high if the set time-delay for the V2> element has elapsed
tV2>> (NA) 0000000 0-1 1
ST tV2>> is high if the set time-delay for the V2>> element has elapsed
tVN> 0000000 0-1 1
tVN> is high if the set time-delay for the VN> element has elapsed
tVN>> 0000000 0-1 1
tVN>> is high if the set time-delay for the VN>> element has elapsed
tVN>>> 0000000 0-1 1
tVN>>> is high if the set time-delay for the VN>>> element has elapsed
tf1 (A) 0000000 0-1 1
tf1 is high if the set time-delay for the f1 element has elapsed
tf2 (A) 0000000 0-1 1
tf2 is high if the set time-delay for the f2 element has elapsed
tf3 (A) 0000000 0-1 1
tf3 is high if the set time-delay for the f3 element has elapsed
tf4 (A) 0000000 0-1 1
tf4 is high if the set time-delay for the f4 element has elapsed
tf5 (A) 0000000 0-1 1
tf5 is high if the set time-delay for the f5 element has elapsed
tf6 (A) 0000000 0-1 1
tf6 is high if the set time-delay for the f6 element has elapsed
tAUX1 (NA) 0000000 0-1 1
tAUX1 is high if the set time-delay for the AUX1 element has elapsed
tAUX2 (NA) 0000000 0-1 1
tAUX2 is high if the set time-delay for the AUX2 element has elapsed
tAUX3 (A) 0000000 0-1 1
tAUX3 is high if the set time-delay for the AUX3 element has elapsed
CB Alarm (A) 0000000 0-1 1
CB Alarm : Circuit Breaker Alarm function signal
tCB FLT Ext.Sign (A) 0000000 0-1 1
Settings V11V/EN ST v1.0

VAMP 11V (ST) 4-25

Menu Text Default Setting Setting Range Step Size

tCB FLT Ext.Sign is high if the tCB FLT ext. time-delay has elapsed.
The counter is started if the function CB FLT Ext.Sign assigned to binary input is high.
Binary input is used to indicate that there is sufficient energy in the CB operating
mechanism to close and trip the CB.
The tCB FLT ext. time-delay is set at GLOBAL SETTINGS/CIRCUIT BREAKER/ tCB
FLT ext.
The binary input is set at SETTING GROUP x/INPUTS CONFIGURATION Gx/ CB FLT
Ext.Sign.
Setting Group 1 (NA) 0000000 0-1 1
Setting Group 1 is active (switched via a binary input, the front panel, RS485 comms).
tVTS (A) 0000000 0-1 1
tVTS is active (VT supervision fail).
fout (A) 0000000 0-1 1 ST
Frequency is out of range.
V11V/EN ST v1.0 Settings

(ST) 4-26 VAMP 11V

2.4 LED Configuration


LED configuration settings define which signals are mapped to the V11V LEDs.
Matrix configuration allows free mapping of any one function to each LED.

Step
Menu Text Default Setting Setting Range
Size

Description of bits: LED: 7,6,5,4,3,2 LED: 7,6,5,4,3,2

Latched LEDs 000000 0–1 1


Each LED can be configured with or without latching.
Default Setting: “000000” means that:
LED7: “0” – LED 7 is latched until the LEDs are reset (Binary Input, Front panel,
communication system)
LED6: “0” – see LED7
ST LED5: “0” – see LED7
LED4: “0” – see LED7
LED3: “0” – see LED7
LED2: “0” – see LED7
Alarm 000000 0–1 1
This LED is lit if any protection element set to “Alarm” is high (voltage-based protection
elements, external protection elements: AUX1, AUX2, AUX3, VT Supervision, CB FLT
ext).
Default Setting: “000000” means that:
LED7: “0” – LED 7 is not assigned to an Alarm
LED6: “0” – see LED7
LED5: “0” – see LED7
LED4: “0” – see LED7
LED3: “0” – see LED7
LED2: “0” – see LED7
Start V> 000000 0-1 1
This LED is lit if start V> is high.
Start V>> 000000 0-1 1
This LED is lit if Start V>> is high.
Start V>>> 000000 0-1 1
This LED is lit if Start V>>> is high.
Start V< 000000 0-1 1
This LED is lit if Start V< is high.
Start V<< 000000 0-1 1
This LED is lit if Start V<< is high.
Start V<<< 000000 0-1 1
This LED is lit if Start V<<< is high.
Start V1< (A) 000000 0-1 1
This LED is lit if Start V1< is high.
Start V1<< (A) 000000 0-1 1
This LED is lit if Start V1<< is.
Start V2> (NA) 000000 0-1 1
This LED is lit if Start V2> is high.
Settings V11V/EN ST v1.0

VAMP 11V (ST) 4-27

Step
Menu Text Default Setting Setting Range
Size

Start V2>> (NA) 000000 0-1 1


This LED is lit if Start V2>> is high.
Start VN> 000000 0-1 1
This LED is lit if Start VN> is high.
Start VN>> 000000 0-1 1
This LED is lit if Start VN>> is high.
Start VN>>> 000000 0-1 1
This LED is lit if Start VN>>> is high.
Start f1 (A) 000000 0-1 1
This LED is lit if Start f1 is high if the f1 protection element has started.
Start f2 (A) 00000 0-1 1
ST
This LED is lit if Start f2 is high if the f2 protection element has started.
Start f3 (A) 000000 0-1 1
This LED is lit if Start f3 is high if the f3 protection element has started.
Start f4 (A) 000000 0-1 1
This LED is lit if Start f4 is high if the f4 protection element has started.
Start f5 (A) 000000 0-1 1
This LED is lit if Start f5 is high if the f5 protection element has started.
Start f6 (A) 000000 0-1 1
This LED is lit if Start f6 is high if the f6 protection element has started.
AUX1 (NA) 000000 0-1 1
This LED is lit if AUX1 is high if the input assigned to AUX1 is set high.
AUX2 (NA) 000000 0-1 1
This LED is lit if AUX2 is high if the input assigned to AUX2 is set high.
AUX3 (A) 000000 0-1 1
This LED is lit if AUX3 is high if the input assigned to AUX3 is set high.
AUX4 (A) 000000 0-1 1
This LED is lit if AUX4 is high if the input assigned to AUX4 is set high.
AUX5 (A) 000000 0-1 1
This LED is lit if AUX5 is high if the input assigned to AUX5 is set high.
tV> 000000 0-1 1
This LED is lit if tV> is high.
tV>> 000000 0-1 1
This LED is lit if tV>> is high.
tV>>> 000000 0-1 1
This LED is lit if tV>>> is high.
tV< 000000 0-1 1
This LED is lit if tV< is high.
tV<< 000000 0-1 1
V11V/EN ST v1.0 Settings

(ST) 4-28 VAMP 11V

Step
Menu Text Default Setting Setting Range
Size

This LED is lit if tV<< is high.


tV<<< 000000 0-1 1
This LED is lit if tV<<< is high.
tV1< (A) 000000 0-1 1
This LED is lit if tV1< is high.
tV1<< (A) 000000 0-1 1
This LED is lit if tV1<< is high.
tV2> (NA) 000000 0-1 1
This LED is lit if tV2> is high.
tV2>> (NA) 000000 0-1 1
ST This LED is lit if tV2>> is high.
tVN> 000000 0-1 1
This LED is lit if tVN> is high.
tVN>> 000000 0-1 1
This LED is lit if tVN>> is high.
tVN>>> 000000 0-1 1
This LED is lit if tVN>>> is high.
tf1 (A) 000000 0-1 1
This LED is lit if tf1 is high.
tf2 (A) 000000 0-1 1
This LED is lit if tf2 is high.
tf3 (A) 000000 0-1 1
This LED is lit if tf3 is high.
tf4 (A) 000000 0-1 1
This LED is lit if tf4 is high.
tf5 (A) 000000 0-1 1
This LED is lit if tf5 is high.
tf6 (A) 000000 0-1 1
This LED is lit if tf6 is high.
tAUX1 (NA) 000000 0-1 1
This LED is lit if tAUX1 is high.
tAUX2 (NA) 000000 0-1 1
This LED is lit if tAUX2 is high.
tAUX3 (A) 000000 0-1 1
This LED is lit if tAUX3 is high.
Local CTRL Mode (A) 000000 0-1 1
This LED is lit if relay is local mode.
CB Alarm (A) 000000 0-1 1
This LED is lit if we have CB Alarm.
Settings V11V/EN ST v1.0

VAMP 11V (ST) 4-29

Step
Menu Text Default Setting Setting Range
Size

tCB FLT Ext.Sign (A) 000000 0-1 1


This LED is lit if tCB FLT Ext.Sign is high.
Setting Group 1 (NA) 000000 0-1 1
This LED is lit if Setting Group 1 is active.
tVTS (A) 000000 0-1 1
This LED is lit if tVTS is active (VT supervision fail).
fout (A) 000000 0-1 1
This LED is lit if Frequency is out of range.

ST
V11V/EN ST v1.0 Settings

(ST) 4-30 VAMP 11V

3. GLOBAL SETTINGS
3.1 LOC

Menu Text Default Setting Available Settings

English
German
French
Language English Spanish
Russian
Turkish
Regional
This cell is used to change the language of the menu.
The REGIONAL language is used if it is necessary to customize labels in the V11V menu.
For example: the CB Fail label instead of the AUX1 label. To change the labels in the
V11V menu, the Menu Creator Software is used. All available V11V language versions
ST can be used as a template for a Regional menu.
Meas. P – P [V]
Meas. P – P [Un]
Meas. P – N [V]
Default Display Measurements P – P [V]
Meas. P – N [Un]
CB Control (A)
L/R Mode (A)
This cell is used to change the default display window:
0: Measurements in phase to phase voltage
1: Measurements in phase to phase voltage refer to Un
2: Measurements in phase to neutral voltage
3: Measurements in phase to neutral voltage refer to Un
4: CB control window for CB control (close and trip command)
5: L/R Status Local/Remote and for presenting Control Mode state information
Manual only
LEDs Reset Manual only Protect.Start
Close Command (A)
This cell is used to change the resetting method of latched LEDs in the menu.
0: Manual only – Resetting of latched LEDs via manual reset only (C clear key, input,
USB,RS485)
1: Protect.Start – Resetting of latched LEDs upon any protection start (set for CB tripping)
or via manual reset
2: Close Command - Resetting of latched LEDs upon Close Command applied by V11V
Manual only
Latched Outputs
Manual only Protect.Start
Reset
Close Command (A)
This cell is used to change the resetting method of latched outputs in the menu.
0: Manual only – Resetting of latched outputs via manual reset only (C clear key, input,
USB,RS485)
1: Protect.Start – Resetting of latched outputs upon any protection start (set for CB
tripping) or via manual reset
2: Close Command - Resetting of latched outputs upon Close Command applied by V11V
Manual only
Trip Info Reset Manual only Protect.Start
Close Command (A)
Settings V11V/EN ST v1.0

VAMP 11V (ST) 4-31

Menu Text Default Setting Available Settings

This cell is used to change the resetting method of latched outputs in the menu.
0: Manual only – Resetting of trip info reset via manual reset only (C clear key, input,
USB, RS485)
1: Protect.Start – Resetting of trip info reset upon any protection start (set for CB tripping)
or via manual reset
2: Close Command - Resetting of trip info reset upon Close Command applied by V11V
Self Reset
Alarm Info Latching Self Reset
Manual Reset
This cell is used to change the resetting method of Alarm indication windows (ALARM
STATUS)
0: Self Reset – This option means that if an alarm signal has disappeared no information
is available in the ALARM STATUS column
1: Manual Reset – this option means that if an alarm signal has disappeared information is
still available in the ALARM STATUS column until it is reset in the ALARM STATUS/
Alarm Reset cell. ST
50Hz
Nominal Frequency 50Hz
60Hz
This cell is used to set the nominal frequency of the power system.
Control Keys No (Without)
No
Confirm Yes (With)
This cell is used to select the way of close/trip command execution from the front panel
(CB Close key/CB Open key).
No: after pressing CB Close key or CB Open key the command is executed
instantaneously
Yes: after pressing CB Close key or CB Open key the new window will be appeared to
confirm or cancel the control command (Close or Trip). After pressing OK key the control
command is executed or after pressing C clear key the control command is cancelled.

3.2 Setting Group Select

Menu Text Default Setting Available Settings

One
Number of Groups One
Two
This cell is used to choose the number of setting groups available in the V11V.
By choosing One Group all settings related to Group 2 are hidden in the menu.
Group 1
Setting Group Group 1
Group 2
This cell is used to change the current setting group.
t Change Settings 0.00 to 200 s, step
0.00 s
Group (G1 -> G2) 0.01 s
This cell is used to set the time-delay changing between the setting Group 1 and Group 2.
V11V/EN ST v1.0 Settings

(ST) 4-32 VAMP 11V

3.3 VT’s Supervision (AN)

Menu Text Default Setting Available Settings

Disabled
VT’s Supervision Disabled
Enabled
This cell is used to enabled voltage transformer supervision function.
VTS Input
Detection Mode VTS Input Delta Ur
Delta Ur or VTS Input
This cell is visible when GLOBAL SETTINGS/VT RATIO/VT Connection is set to:
3Upn+UN,
or 2Upp+UN,
or 3Upp+UN.
In other case (3Upn) is fixed VTS Input only.
ST This cell is used to change the detection mode of VT failure.
Ur – difference between: VN measured and VN calculated
2V to 130V
Delta Vr 15V
step 0,1V
This cell is visible when GLOBAL SETTINGS/VT SUPERVISION/Detection Mode is set
to:
Delta Ur,
or Delta Ur or VTS Input
0.00s to 100 s,
tVTS 5.00 s
step 0.01 s
This cell is used to change the operating time delay of the element upon detection of a
voltage transformer supervision.
No
Inhibit VTS / 52a No
Yes
This cell is used to enabled blocking logic of VTS supervision from state CB – turn off
position.
No
Block [27] U/V No
Yes
This cell is used to enabled blocking logic of V< protection from tVTS function.
No
Block [59] O/V No
Yes
This cell is used to enabled blocking logic of V> protection from tVTS function.
Block [59N] E/GND No
No
O/V Yes
This cell is used to enabled blocking logic of VN> protection from tVTS function.
Block [27D] POS. No
No
SEQ. U/V Yes
This cell is used to enabled blocking logic of V1< protection from tVTS function.
Block [47] NEG. No
No
SEQ. O/V Yes
This cell is used to enabled blocking logic of V2> protection from tVTS function.
Settings V11V/EN ST v1.0

VAMP 11V (ST) 4-33

Menu Text Default Setting Available Settings

No
Block [81] freq. No
Yes
This cell is used to enabled blocking logic of frequency protection from tVTS function.

ST
V11V/EN ST v1.0 Settings

(ST) 4-34 VAMP 11V

3.4 VT Ratio

Setting Range
Menu Text Default Setting Step Size
Min. Max.
0.1 kV
Line VT Primary 0.05 kV 65 kV 0.01 kV
0.22 kV
Sets the voltage transformer input's primary voltage rating.
Default value depends on Phase range (see: Line VT Sec)
Default setting 0.1 kV is set for Phase Range 50 - 130 V
Default setting 0.22 kV is set for Phase Range 220 - 480 V
Line VT Sec 100 V 57 V 130 V 0.1 V
Sets the voltage transformer input's secondary voltage rating. Set for 57-130VAC
measuring range.
Line VT Sec 220 V 220 V 480 V 0.1 V
ST Sets the voltage transformer input's secondary voltage rating. Set for 220-480VAC
measuring range.
E/Gnd VT Primary 0.1 kV 0.05 kV 65 kV 0.01 kV
Sets the earth fault transformer input's primary voltage rating.
E/Gnd VT Sec 100 V 57 V 130 V 0.1 V
Sets the earth fault transformer input's secondary voltage rating.
3Upn
3Upn+UN
VT Connection (AN) 3Upn+UN N/A N/A
2Upp+UN
3Upp+UN
Sets type of analog connection of VT
P-N
Prot. Config. V> P-P N/A N/A
P-P
Sets type of voltage which is use in protections
P-N
Prot. Config. V< P-P N/A N/A
P-P
Sets type of voltage which is use in protections

3.5 Circuit Breaker

Setting Range
Menu Text Default Setting Step Size
Min. Max.
tOpen Pulse min 0.1 s 0.1 s 10 s 0.01 s
Defines the duration of the trip pulse used by the Autoreclose, Trip Command and Trip
CB Order outputs.
tClose Pulse 0.1 s 0.1 s 10 s 0.01 s
Defines the duration of the close pulse used by the Close CB Order output.
Time Delay for Close 0s 0s 200 s 0.01 s
Defines the time-delay for Manual or Remote CB close commands.
tCB FLT ext (A) 16 s 1s 200 s 1s
Settings V11V/EN ST v1.0

VAMP 11V (ST) 4-35

Setting Range
Menu Text Default Setting Step Size
Min. Max.
A settable time-delay is included for manual closure with this circuit breaker check. If the
circuit breaker does not indicate a healthy condition in this time period following a close
command, then the relay will lockout and set off an alarm.
Remote only
Remote Mode (A) 0: Remote only
Remote+Local
This cell is used to define Remote CB control mode.
0: Remote only – If V11V is in Remote mode it is possible to apply a close and a trip
command via RS485 only.
1: Remote+Local – In Remote mode it is possible to close and trip CB via RS485 or
locally (Default window menu, Front panel keys, binary input).
CB Supervision (AN) No No Yes n/a
Selection of the time monitoring function of CB open and close operations.
If Yes is selected, the CB Open Time and CB Close Time menu are displayed. (ALARM
signalling).
ST
Max CB Open Time
0.1 s 0.1 s 10 s 0.01 s
(A)
Displays the Alarm time threshold for a CB open operation.
Max CB Close Time
0.5 s 0.1 s 10 s 0.01 s
(A)
Displays the Alarm time threshold for a CB close operation.

3.6 Voltage Advanced Configuration

Menu Text Default Setting Setting Range Step Size


IDMT interlock by
No No Yes n/a
DMT stage
IDMT tripping can be blocked if any DMT stage is started settings: IDMT interlock by DMT
(GLOBAL SETTINGS/O/V ADVANCED column).
U/V Hysteresis 1.05 1.00 1.20 0.01
Sets drop off of undervoltage protection. Applies function with DT curve. For IDMT curves
see V11V/EN TD v1.0 chapter, table in point 7.
O/V Hysteresis 0.95 0.80 1.00 0.01
Sets drop off of overvoltage protection. Applies function with DT curve. For IDMT curves
see V11V/EN TD v1.0 chapter, table in point 7.
V11V/EN ST v1.0 Settings

(ST) 4-36 VAMP 11V

3.7 [81] Advanced Settings (A)

Setting Range
Menu Text Default Setting Step Size
Min. Max.
Prot. Freq. Blocking 65 V 5V 100 V 1V
Sets threshold of voltage below [81] function is blocked
Meas. Valid. Nb of
4 1 10 1
halfcycles
Sets numbers of halfcycles which are need to confirm working [81] protection

ST
Settings V11V/EN ST v1.0

VAMP 11V (ST) 4-37

3.8 Communication (AN)

Setting Range
Menu Text Default Setting Step Size
Min. Max.
Relay Address 247 1 247 1
This cell sets the unique address for the relay so that only one relay is accessed by the
master station's software. This address is applied for RS485 port only.
Note: USB port has fixed address: 1.
Modbus
Protocol IEC103 IEC103
Modbus (DE)
This cell sets the type of protocol for RS485:
0: Modbus RTU protocol (used for MS1S)
1: IEC103 protocol
2: Modbus (DE) valid with Modbus Standard ST
This setting parameter is applied for RS485 port only.
Note: USB port has fixed protocol: Modbus.
4800 bits/s , 9600 bits/s, 19200 bits/s,
Baud Rate 19200 bits/s
38400 bits/s, 57600 bits/s, 115200 bits/s
This cell controls the communication speed between relay and master station. It is
important that both the relay and the master station have the same speed setting.
This setting parameter is applied for RS485 port only.
Note: USB port has fixed Baud Rate: 115.2 kbits/s.
Parity None None, Odd, Even
This cell controls the parity format used in the data frames. It is important that both the
relay and the master station have the same parity setting.
This setting parameter is applied for RS485 port only.
Note: USB port has fixed Parity: No parity.
Stop bits 1 stop bit 1 stop bit, 2 stop bits
This cell controls the stop bit format used in the data frames. It is important that both the
relay and the master station have the same stop bits setting.
This setting parameter is applied for RS485 port only.
Note: USB port has fixed Stop bits: 1 stop bit.

Note: The above parameters are relevant to the RS485 port only.
The USB port has the non-settable following parameters:
- Protocol: Modbus RTU
- Address: 1
- Baud Rate: 115.2 kbits/s
- Comms. Mode:
Data Bit: 8
Stop bit: 1
Parity: none
V11V/EN ST v1.0 Settings

(ST) 4-38 VAMP 11V

3.9 Disturbance Recorder (A)


The Disturb Record submenu makes it possible to set and read out disturbance records. Up
to 4 second's duration but not more than 5 disturbance records can be stored.
Total number of records available in disturbance recorder is:
o One - for set Max Record Time from in range: 2.01s – 4.00s
o Two – for set Max Record Time from in range: 1.34s – 2.00s
o Three – for set Max Record Time from in range: 1.01s – 1.33s
o Four – for set Max Record Time from in range: 0.81s – 1.00s
o Five - for set Max Record Time from in range: 0.10s – 0.80s
The beginning of the record can be adjusted with a selected pre-fault time. It is possible to
limit the duration of a record.

Setting Range
ST Menu Text Default Setting
Min. Max.
Step Size

Pre-Time 0.1 s 0.1 s 2s 0.01 s


Setting for the disturbance record pre-fault time. The pre-fault time sets the beginning of the
disturbance record. In this example, the record starts 100 ms before the disturbance. Its
length can be limited by setting.
Post-Trip Time 0.1 s 0.1 s 1s 0.01 s
Setting for the disturbance record post-fault time. The total disturbance recording time is:
pre-fault time + high state of triggering criteria (Start or Trip time) + post-fault time.
The above total recording time is limited by setting.
on Inst.
Disturbance Rec.Trig. on Inst.
on Trip
Setting for the trigger criteria:
0: on Inst. – the trigger is the disturbance indicated by the starting of a protection element
set to trip the CB. If this option is chosen the total recording time is: pre-fault time + duration
of protection start + post-fault time, but no longer than the value of Max Record Time.
When delay time of any protection function exceeds Max Record Time and after this delay
time TRIP signal occurs then TRIP is recorded in the next additional record.
1: on Trip. – the trigger is the disturbance indicated by a protection element trip. If this
option is chosen the total recording time is: pre-fault time + duration of protection trip+ post-
fault time, but no longer than the value of Max Record Time.
Max Record Time 1.5 s 0.1 s 4s 0.01 s
Setting for the maximum total recording time.
Settings V11V/EN ST v1.0

VAMP 11V (ST) 4-39

4. COMMISSIONING

This column contains menu cells which allow the status of the opto-isolated inputs, output
relay contacts to be monitored. Additionally there are cells to test the operation of the output
contacts, user-programmable LEDs.

Menu Text Default Setting Available Settings

Description of bits: L: 6,5,4,3,2,1

Input Status (AN) 000000


This menu cell displays the status of the relay’s opto-isolated inputs as a binary string, a
‘1’ indicating an energised opto-isolated input and a ‘0’ a de-energised one - for standard
input logic. If the inputs logic is reversed (for any input) than ‘1’ indicates a
de-energised and ‘0’ energised input.
ST
Description of bits: RL: 7,6,5,4,3,2,1

Output Status 0000000


This menu cell displays the status of the digital signals used to energize the output relays
as a binary string, a ‘1’ indicating an operated state and ‘0’ a non-operated state.
No
Maintenance Mode
No Yes, outp.trips
(A)
Yes, outp.block
Choose whether you want to activate the MAINTENANCE MODE of the relay.
MAINTENANCE MODE allows to test contact outputs and functional tests.
For changing this value Control password have to be entered.
If “No” is selected, all menu cells below are hidden.
If “Yes,outp.trips” or “Yes” – ALARM LED is lit and 10 minutes timer is started for
returning to “No” option. In this time V11V is in SETTING MODE. Changing of test values
and execution of command are allowed.
If “Yes,outp.block” is selected, output relays are disconnected from the protection and
automation functions.

Description of bits: RL: 7,6,5,4,3,2,1

Test Pattern (A) 0000000


This menu cell is used to set outputs for the test. The digit: 1 set in this cell means that this
output will be energized after the test command is applied.
If the test is applied (COMMISSIONING/Test outputs cell) outputs set in this cell will be
energized for the duration of Contact Test Time.
Contact Test Time
0.0 s 0s 200 s 0.01 s
(A)
Set the time pulse of contact closing during the tests.
no operation
Test outputs (A) no operation
Apply test
This menu cell is used to apply a test to the outputs set in the Test Pattern cell.
To apply the output test: Press OK, change a setting option from 0 to 1 (1: Apply test),
confirm this action by pressing the OK key. After this, outputs (set in Test Pattern cell) are
energized for the duration of Contact Test Time.
Note: If the Test control password is not equal to 0 before changing of option (from 0 to 1)
at least Test control password should be entered (as for every other V11V setting).
V11V/EN ST v1.0 Settings

(ST) 4-40 VAMP 11V

Menu Text Default Setting Available Settings


V>
V>>
V>>>
V<
V<<
V<<<
VN>
VN>>
VN>>>
Functional Test (A) V> V2>
V2>>
V1<
V1<<
f1
f2
f3
ST f4
f5
f6
This menu cell is used to set a protection element for Functional tests.
Functional Test End CB trip
Time
(A) Time
This menu cell is used to choose the method of ending the test procedure.
0: CB trip – the test is applied until Trip signal
1: Time – the test is ended after the Functional Test Time set value.
Functional Test Time
0.1 s 0.1 s 200 s 0.01 s
(A)
Setting for the time pulse of contact closing during Functional tests.
no operat.
Functional Test (A) no operat.
Apply Test
This menu cell is used to apply test of outputs which were set in Functional Test pattern
cell.
To apply output test: Press enter, change a setting option from no operat. to Operate,
confirm this action by pressing OK key. After that outputs (set in Functional Test pattern
cell) are energized via Functional Test Time.
Note: if Test control password is not equal 0 before changing of option (from no operat. to
Operat) at least Test control password should be entered (like for every V11V setting).
Settings V11V/EN ST v1.0

VAMP 11V (ST) 4-41

5. SETTING CHANGE MODE


This column contains menu cells which allow the settings and configuration to be changed.
Before any change to the settings it is necessary to set a V11V’s Edit Setting Mode to
Without limits or Protection only. If changing of parameters is allowed, the LEDs light up
one by one until the Setting Change status cell is in the Protected state.
In the Without limits state, it is possible to change all of the settings.
In the Protection only state, it is only possible to change protection settings (PROTECTION
columns)
In the Control state, it is possible to control the CB in the default window and apply
MAINTENANCE MODE for outputs and functional tests . If the password is set to 0, no
password is necessary to control the CB.
In the Protected state, settings are password-protected.

Menu Text Default Setting Available Settings ST


Edit Settings? Enter PSWD 0000 – 9999
This cell is used to switch the P111Enh to Edit Settings in order to allow changing the
settings.
Protected/Without
Setting Change Protected limits/Protection
only/Test Control
This cell displays the level of rights to change settings.
Change Password 0000 – 9999
This cell is displayed if the password is entered. To change the password it is necessary to
press the OK key and enter the new password. After that it is necessary to press enter to
save the new password.

To access the Edit Setting Menu window faster, press the left and up keys at the same
time.
This action makes the menu jump to the Edit Setting cell.
Then press the OK key, a password will be requested.
Enter the password (the default factory password is “0000” for every password level)

In the Without limits or the Protection only state, all the LEDs will then light up, in rapid
sequence. This indicates that the V11V is operating in Edit Mode: the parameters can be
changed in this state.
In the Control state there is no any LED signaling (no lighting up in rapid sequence as
above).

After having set all the required parameters, press simultaneously the 4 and 8 keys,
then press the OK key once
V11V/EN ST v1.0 Settings

(ST) 4-42 VAMP 11V

6. OP PARAMETERS
This column contains menu cells to show some of the V11V 's parameters.

Menu Text Default Setting Available Settings

Description V11V Read only


This cell is used to show the type of relay.
Serial Nb 000000 Read only
This cell is used to show the serial number of the relay.
Reference SE MiCOM Read only
This cell is used to show the relay's manufacturer.
Software Version 1.A Read only
This cell is used to show the software version (firmware)
ST Hardware Version Model A Read only
This cell is used to show the hardware version ordered
Active Set Group Group 1 Read only
This cell is used to show the active setting group

Date 01/01/08 00/00/00 – 99/99/99

This cell is used to set the date of the internal clock


Time 00:00:00 00:00:00 – 23/59/59
This cell is used to set the time of the internal clock
Note:
1. A back-up clock capacitor is charged from an auxiliary voltage supply (terminals 11-12)
only. The capacitor's energy allows storage of real time information for up to 2 days. When
the back-up capacitor is completely discharged, it takes less than 10 minutes to recharge it
completely
2. If the clock has no real time information (the back-up capacitor is recharged) and the
current exceeds the minimum current required for operation, the real time is set to
01/01/2008 00:00:00. Therefore events are dated with reference to this start time value.
Nominal Frequency: 50Hz or 60Hz Read only
This cell is used to show the nominal frequency setting.
Operation V11V/EN OP v1.0

VAMP 11V

OP

OPERATION

Date: 1st December 2015


Software Version: 1A
Connection Diagrams: 10V11V01
V11V/EN OP v1.0 Operation

VAMP 11V

OP
Operation V11V/EN OP v1.0

VAMP 11V (OP) 5-1

CONTENTS

1. OPERATION OF INDIVIDUAL PROTECTION FUNCTIONS 3


1.1 Overvoltage Protection 3
1.1.1 Operation Time-Delay 4
1.2 Undervoltage Protection 9
1.3 Earth Fault Overvoltage Protection 11
1.4 Negative Sequence Overvoltage Protection (Model N, A) 12
1.5 Positive Sequence Undervoltage Protection (Model A) 13
1.6 Frequency Protection (Model A) 14
1.7 Auxiliary Timers (Model NA) 15
1.8 Blocking Logic Function (Model A) 16 OP
2. OPERATION OF NON PROTECTION FUNCTIONS 17
2.1 VT Supervision (Model A) 17
2.2 Circuit Breaker State Monitoring (Model A) 17
2.3 Local / Remote Mode (Model A) 19
2.4 Setting Group Selection 20
2.5 Commissioning 23
2.5.1 Maintenance Mode (Model A) 23
2.5.2 Outputs test 23
2.5.3 Functional test 24
2.6 Circuit Breaker Control 25
2.7 Real Time Clock Synchronization via Opto-Inputs (Model A) 26
2.8 Resetting of Latched LEDs and Outputs 26
2.9 Records 28
2.9.1 Fault Recorder 28
2.9.2 Alarm Recorder 28
2.10 Disturbance Recorder (Model A) 29
2.11 Event Records (Model N, A) 29
V11V/EN OP v1.0 Operation

(OP) 5-2 VAMP 11V

FIGURES

Figure 1: Overvoltage protection logic diagram 3


Figure 2: Undervoltage protection logic diagram 10
Figure 3: Earth Fault protection logic diagram for UN>. For other two stages, the logic diagram
is the same but without the IDMT characteristics 11
Figure 4: Negative sequence overvoltage protection logic 12
Figure 5: Positive Sequence Undervoltage Protection logic 13
Figure 6: Frequency protection logic 14
Figure 7: AUX Timer Logic (AUX1-AUX3) 15
Figure 8: Remote Control of Circuit Breaker 25

OP
Operation V11V/EN OP v1.0

VAMP 11V (OP) 5-3

1. OPERATION OF INDIVIDUAL PROTECTION FUNCTIONS


The following sections detail the individual protection functions.
1.1 Overvoltage Protection
The overvoltage protection included in the V11V relays provides three-stage overvoltage
protection with independent time-delay characteristics (DT or IDMT – depending on stage),
which can be set to operate from phase to phase or phase to neutral voltage. All overvoltage
settings apply to all three phases but are independent for each of the three stages.
Each protection stage can be selected to Trip the CB (works when all three phases are faulty
– AND option, or if in any one phase fault appears – OR option) or to indicate a signal
(Alarm) only, there is possibility to chose trip and alarm with blocking option from state of CB
contacts (52a).
If an overvoltage protection stage (V>, V>> or V>>>) is set to Trip, it means that that stage
is linked to the Protect.Trip and Prot.Trip pulse functions (see LED and Output
configuration).
If an overvoltage protection stage (V>, V>> or V>>>) is set to Alarm, it means that that OP
stage is linked to the Alarm function (see LED and Output configuration).
If OR Trip is selected, the overvoltage stage will trip when any phase is faulty (works
similarly for alarm option).
If AND Trip is selected, the overvoltage stage will trip when all phases are faulty
(works similarly for alarm option).
If OR Trip/52a is selected, the overvoltage stage will trip when any phase is faulty and
there is confirmation of closed state of breaker (works similarly for alarm option).
If AND Trip/52a is selected, the overvoltage stage will trip when all phases are faulty
and there is confirmation of closed state of breaker (works similarly for alarm option).

Block tV> Input V> Alarm Alarm

VTS Block V>


& Alarm Recorder
0 T

&
V> Disabled TIMER

52a tV> Time delay

V> AND/52a & OR &


DT/IDMT
with DT or IDMT
reset
tV>

V> AND

Start V>A Threshold


&
OR
Start V>B Threshold
& Start V>

Start V>C Threshold

& Instantaneous
Recorder

OR
52a & Trip Protection

V> OR/52a & OR & Trip Pulse Protection

V> OR V> Trip Fault Recorder

Figure 1: Overvoltage protection logic diagram


V11V/EN OP v1.0 Operation

(OP) 5-4 VAMP 11V

1.1.1 Operation Time-Delay

The first (V>) and second (V>>) stages of overvoltage protection have time-delayed
characteristics which are selectable between inverse definite minimum time (IDMT) and
definite time (DT). The third (V>>>) stage has a definite time characteristic only.
The inverse time-delayed characteristics indicated above comply with the following formula:

k
IEC/UK/FR curves: t = TMS ⋅ ( + c) ;
G
( )α − P
Gs
k
IEEE/US curves: t = TD ⋅ ( + c) ;
G
( )α − P
Gs
where:
OP t = Operating time in [s],
k, P, c = Constant,
G = Measured voltage in [V],
TMS = Time multiplier setting for IEC curves,
TD = Time dial setting for IEEE curves,
Gs = Voltage threshold setting in [V],

α = Constant.

Type of Curve
according to IEC60255-151 Standard k c α P
std definition
IEC Standard Inverse Time (SI) IEC/A 0.14 0 0.02 1
IEC Very Inverse Time (VI) IEC/B 13.5 0 1 1
IEC Extremely Inverse Time (EI) IEC/C 80 0 2 1
IEC Long Time Inverse (LTI) IEC 120 0 1 1
FR Short Time Inverse (STI) FR 0.05 0 0.04 1
UK Rectifier (Rect) UK 45900 0 5.6 1
IEEE
IEEE Moderately Inverse Time (MI) 0.0515 0.114 0.02 1
(IEC/D)
IEEE
IEEE Very Inverse Time (VI) 19.61 0.491 2 1
(IEC/E)
IEEE
IEEE Extremely Inverse Time (EI) 28.2 0.1217 2 1
(IEC/F)
US Time Inverse (CO8) US 5.848 0.1654 2 1

US Short Time Inverse (CO2 P20) US 0.02394 0.01694 0.02 1

US Short Time Inverse (CO2 P40) US 0.16758 0.11858 0.02 1


BNP (EDF) EDF 1000 0.655 2 1
RI -4.2373 0 -1 1.43644

A time multiplier setting TMS is used to adjust the operating time of IEC & UK IDMT curves.
Operation V11V/EN OP v1.0

VAMP 11V (OP) 5-5

A time multiplier setting TD is used to adjust the operating time of IEEE or US IDMT curves.
Note:
1. For (CO2 P20), TD is defined like in MiCOM P20 series
2. For (CO2 P40), TD is defined like in MiCOM P40 series
The difference between above two characteristics is in definition of TD setting value only.

Standard Inverse IEC Very Inverse IEC

100 100

10

10 OP
Time [s] Time [s]
A A
1

B B

C
C
1
D
0.1
D

E 0.01
0.1
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
Multiples of pickup setting: G/Gs Multiples of pickup setting: G/Gs

E: TMS=0.05 D: TMS=0.2 C: TMS=0.5 E: TMS=0.05 D: TMS=0.2 C: TMS=0.5

B: TMS=1 A: TMS=2 B: TMS=1 A: TMS=2

Extremely Inverse IEC RI Inverse Time

100 100

10

10

Time [s] Time [s] A

1
B

A C
1
B
0.1 C D

E
0.01 E 0.1
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

Multiples of pickup setting: G/Gs Multiples of pickup setting: G/Gs

E: TMS=0.05 D: TMS=0.2 C: TMS=0.5 E: TMS=0.05 D: TMS=0.2 C: TMS=0.5


B: TMS=1 A: TMS=2 B: TMS=1 A: TMS=2
V11V/EN OP v1.0 Operation

(OP) 5-6 VAMP 11V

Long Time Inverse UK Short Time Inverse


100
1000

10
100

Time [s] Time [s]


A 1
10 A
B
B
C
C
D 0.1
1 D

E
E
OP 0.01
0.1
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 0 1 2 3 4 5 6 7 8 9 10 11 1213 14 1516 17 18 19 20

Multiples of pickup setting: G/Gs Multiples of pickup setting: G/Gs


E: TMS=0.05 D: TMS=0.2 C: TMS=0.5 E: TMS=0.05 D: TMS=0.2 C: TMS=0.5
B: TMS=1 A: TMS=2
B: TMS=1 A: TMS=2

Rectifier Moderately Inverse IEEE


100
100

10
10

Time [s] A
Time [s]
1 B
1
C

0.1
0.1
E

E D C B A 0.01
0.01
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
Multiples of pickup setting: G/Gs
Multiples of pickup setting: G/Gs
E: TMS=0.05 D: TMS=0.2 C: TMS=0.5 E: TD=0.05 D: TD=0.2 C: TD=0.5
B: TMS=1 A: TMS=2 B: TD=1 A: TD=2
Operation V11V/EN OP v1.0

VAMP 11V (OP) 5-7

Very Inverse IEEE Extremely Inverse IEEE


100
100

10
10

Time [s] Time [s]

1 A
1
B
A
C
B

0.1 D 0.1 C

D
E

0.01
0 1 2 3 4 5 6 7 8 9 1011121314151617 181920
0.01
0 1 2 3 4 5 6 7 8 9 1011121314151617 181920
E
OP
Multiples of pickup setting: G/Gs
Multiples of pickup setting: G/Gs
E: TD=0.05 D: TD=0.2 C: TD=0.5
E: TD=0.05 D: TD=0.2 C: TD=0.5 B: TD=1 A: TD=2
B: TD=1 A: TD=2

Short Time Inverse (CO2) US Inverse (CO8) US

100 100

10

10
Time [s]
Time [s] A
1
B
A
C
B
1
0.1 C
D
D

E 0.01 E
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
0.1
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 Multiples of pickup setting: G/Gs
Multiples of pickup setting: G/Gs E: TD=0.05 D: TD=0.2 C: TD=0.5
B: TD=1 A: TD=2
E: TD=0.05 D: TD=0.2 C: TD=0.5
B: TD=1 A: TD=2

RXIDG Curves
The curves available follow the formula:
t = 5.8 – 1.35 * Un ( 1/ (k * Us/U))
Where:
t = tripping time
k = coefficient (from 0.3 to 1, by steps of 0.01)
Us = value of the programmed threshold (Pick-up value)
U = value of measured voltage
V11V/EN OP v1.0 Operation

(OP) 5-8 VAMP 11V

Timer Hold Facility

First stage of overvoltage protection in the V11V relay are provided with a timer hold facility,
which may either be set to zero or to a definite time value. Setting of the timer to zero means
that the overvoltage timer for that stage will reset instantaneously once the voltage falls
below 95% of the threshold setting. Setting of the hold timer to a value other than zero,
delays the resetting of the protection element timers for this period. When the reset time of
the overvoltage relay is instantaneous, the relay will be repeatedly reset and not be able to
trip until the fault becomes permanent. By using the Timer Hold facility the relay will integrate
the fault pulses, thereby reducing fault clearance time.
The timer hold facility can be found for the first overvoltage stages as settings V> DMT
tRESET". Note that this cell is not visible for the IEC/IEEE/US curves if an inverse time reset
characteristic has been selected (SETTING GROUP x/PROTECTION Gx/ PHASE O/V
G1(G2)/ V>) Reset Delay Type 1:IDMT setting), as the reset time is then determined by the
programmed time dial setting.

Reset IDMT Characteristic


OP
IEEE/US /IEC

The IEEE/US/IEC curves may have an inverse time reset characteristic (V> Reset Delay
Type 1: IDMT setting) or instantaneous reset (V> Reset Delay Type 0:DMT setting). If
IDMT reset is selected (V> Reset Delay Type 1: IDMT setting) then the following menu will
be available: V> RTD/RTMS RESET. The following equation can be used to calculate the
inverse reset time for IEEE/IEC curves:

tr
IEC: reset time = RTMS ⋅
G
1 − ( )p
Gs
tr
IEEE: reset time = RTD ⋅
G
1 − ( )P
Gs
where:
RTD = Time dial setting for IEEE/US curves,
RTMS = A time multiplier setting for IEC curves,
tr = Constant (see table below),
P = Constant (see table below).
Note: To be in line with IEEE/IEC the RTMS (RTD) value should be equal to
the TMS (TD) value. The setting for RTMS or RTD is given to adjust
the reset characteristic to specific applications. Typically RTMS = TMS
and RTD = TD.

Type of Curve Standard tr P


IEC Standard Inverse Time (SI) IEC/A 12.1 2
IEC Very Inverse Time (VI) IEC/B 43.2 2
IEC Extremely Inverse Time (EI) IEC/C 80 2
IEC Long Time Inverse (LTI) IEC 0 2
FR Short Time Inverse (STI) FR 0 2
UK Rectifier (Rect) UK 0 2
IEEE Moderately Inverse Time (MI) IEEE (IEC/D) 4.9 2
Operation V11V/EN OP v1.0

VAMP 11V (OP) 5-9

IEEE Very Inverse Time (VI) IEEE (IEC/E) 21.6 2


IEEE Extremely Inverse Time (EI) IEEE (IEC/F) 29.1 2
Time Inverse (CO8) US 5.95 2
Short Time Inverse (CO2_P20) US 2.261 2
Short Time Inverse (CO2_P40) US 2.261 2
BNP EDF BNP EDF 0 2
RXIDG RXIDG 0 0

Note:
1. For CO2_P20, RTD is defined like in MiCOM P20 series
2. For CO2_P40, RTD is defined like in MiCOM P40 series
The difference between above two characteristics is in definition of TD setting value only.
OP
Reset DMT Characteristic
If Delay Type V> is set as DMT curve, the Reset Delay Type is consequently a DMT type.
This applies independently from Reset Delay Type cell setting.
1.2 Undervoltage Protection
The undervoltage protection included in the V11V relays provides three-stage undervoltage
protection with independent time-delay characteristics (DT or IDMT – depending on stage),
which can be set to operate from phase to phase or phase to neutral voltage. All
undervoltage settings apply to all three phases but are independent for each of the three
stages.
Each protection stage can be also selected to Trip the CB (works when all three phases are
faulty – AND option, or if any one phase is faulty – OR option) or to indicate a signal (Alarm)
only, there is possibility to chose trip and alarm with blocking option from state of CB
contacts (52a).

If an undervoltage protection stage (V<, V<< or V<<<) is set to Trip, it means that that stage
is linked to the Protect.Trip and Prot.Trip pulse functions (see LED and Output
configuration).

If an undervoltage protection stage (V<, V<< or V<<<) is set to Alarm, it means that that
stage is linked to the Alarm function (see LED and Output configuration).
If OR Trip is selected, the undervoltage stage will trip when any one phase is faulty
(works similarly for alarm option).
If AND Trip is selected, the undervoltage stage will trip when all phases are faulty
(works similarly for alarm option).
If OR Trip/52a is selected, the undervoltage stage will trip when any one phase is
faulty and there is confirmation of closed state of breaker (works similarly for alarm
option).
If AND Trip/52a is selected, the undervoltage stage will trip when all phases are faulty
and there is confirmation of closed state of breaker (works similarly for alarm option).
V11V/EN OP v1.0 Operation

(OP) 5-10 VAMP 11V

Block tV< Input V< Alarm Alarm

VTS Block V<


& Alarm Recorder
0 T

&
V< Disabled TIMER

52a tV< Time delay

V< AND/52a & OR &


DT/IDMT
with DT or IDMT
reset
tV<

V< AND

Start V<A Threshold


&
OR
Start V<B Threshold
& Start V<

Start V<C Threshold

& Instantaneous
Recorder

OR
52a & Trip Protection

V< OR/52a & OR & Trip Pulse Protection

V< OR V< Trip Fault Recorder

OP
Figure 2: Undervoltage Protection Logic Diagram
The types of IDMT characteristics are the same like in overvoltage protection. For more
information about time-delay characteristic, please refer to section 1.1.1 of this chapter,
about time delayed reset characteristic please refer to section 1.1.2.
Operation V11V/EN OP v1.0

VAMP 11V (OP) 5-11

1.3 Earth Fault Overvoltage Protection


The Earth fault element operates from a measured or calculated (from phase voltage) earth
fault voltage value.
The first earth fault stage has time-delayed characteristics which are selectable between
inverse definite minimum time (IDMT) and definite time (DT). The second and third stages
have a definite time characteristic only.
If an earth fault stage (VN>, VN>> or VN>>>) is set to Trip, it means that that stage is linked
to the Protect.Trip and Prot.Trip pulse functions (see LED and Output configuration).

If an earth fault stage (VN>, VN>> or VN>>>) is set to Alarm, it means that that stage is
linked to the Alarm function (see LED and Output configuration).
If Trip (measured) is selected, the earth fault stage will trip from measured zero
sequence of voltage.
If Alarm (measured) is selected, the earth fault stage will indicate alarm from
measured zero sequence of voltage.
If Trip (Ua+Ub+Uc) is selected, the earth fault stage will trip from calculated zero
OP
sequence of voltage.
If Alarm (Ua+Ub+Uc) is selected, the earth fault stage will indicate alarm from
calculated zero sequence of voltage

Block tUN> Input VN> Alarm Alarm

VTS Block UN> & Alarm Recorder


0 TIMER T
VN> Disable
&
Delivered VN
OR & tVN> Time delay
DT/IDMT
with DT or IDMT
tVN>
Calculated VN

Start VN> Threshold


& reset

Start VN>

& Instantaneous
Recorder

Trip Protection

VN> Trip
& Trip Pulse Protection

Fault Recorder

Figure 3: Earth Fault protection logic diagram for UN>. For other two stages, the
logic diagram is the same but without the IDMT characteristics

The types of IDMT characteristics are the same, like in overvoltage protection. For more
information about time-delay characteristic, please refer to section 1.1.1 of this chapter,
about time delayed reset characteristic please refer to section 1.1.2.
V11V/EN OP v1.0 Operation

(OP) 5-12 VAMP 11V

1.4 Negative Sequence Overvoltage Protection (Model N, A)


This function is used to protect against unbalance resulting from phase inversion or
unbalanced supply.
The negative sequence overvoltage element included in the V11V relays provides two stage
non-directional negative sequence overvoltage protection with independent time-delay
characteristics. These characteristics are selectable between inverse definite minimum time
(IDMT) and definite time (DT) for first stage, second stage can operate only with DT
characteristic.
If the V2> protection element is set to Trip, it means that the element is linked to the
Protect.Trip and Prot.Trip pulse functions (see LED and Output configuration).
If the V2> protection element is set to Alarm, it means that that element is linked to the
Alarm function (see LED and Output configuration).
If Trip is selected, the negative sequence overvoltage stage will trip when negative
sequence of voltage exceeds set threshold value.
If Alarm is selected, the negative sequence overvoltage stage will indicate when
OP negative sequence of voltage exceeds set threshold value.
If Trip/52a is selected, the negative sequence overvoltage stage will trip when
negative sequence of voltage exceeds set threshold value and there is a confirmation
of closed state of breaker.
If Alarm/52a is selected, the negative sequence overvoltage stage will indicate when
negative sequence of voltage exceeds set threshold value and there is a confirmation
of closed state of breaker.

Block tV2> Input V2> Alarm Alarm

VTS Block V2> & Alarm Recorder


0 TIMER T
V2> Disable

52a
& tV2> Time delay

V2/52a & OR &


DT/IDMT
with DT or IDMT
reset
tV2>

U2

Start V2> Threshold


&
Start V2>

& Instantaneous
Recorder

Trip Protection

V2> Trip
& Trip Pulse Protection

Fault Recorder

Figure 4: Negative sequence overvoltage protection logic


The types of IDMT characteristics are the same, like in overvoltage protection. For more
information about time-delay characteristic, please refer to section 1.1.1 of this chapter
technical manual, about time delayed reset characteristic please refer to section 1.1.2.
Operation V11V/EN OP v1.0

VAMP 11V (OP) 5-13

1.5 Positive Sequence Undervoltage Protection (Model A)


This function is used to protect motors against faulty operation due to insufficient or
unbalanced network voltage, and detection of reverse rotation of motor.
The positive sequence undervoltage element included in the V11V relays provides two stage
non-directional positive sequence undervoltage protection with independent time-delay
characteristics. These characteristics are selectable between inverse definite minimum time
(IDMT) and definite time (DT) for first stage. Second stage can operate only with DT
characteristic.
If the V1< protection element is set to Trip, it means that that element is linked to the
Protect.Trip and Prot.Trip pulse functions (see LED and Output configuration).
If the V1< protection element is set to Alarm, it means that that element is linked to the
Alarm function (see LED and Output configuration).
If Trip is selected, the positive sequence overvoltage stage will trip when positive
sequence of voltage exceeds set threshold value.
If Alarm is selected, the positive sequence overvoltage stage will indicate when
positive sequence of voltage exceeds set threshold value.
OP
If Trip/52a is selected, the positive sequence overvoltage stage will trip when positive
sequence of voltage exceeds set threshold value and there is a confirmation of closed
state of breaker.
If Alarm/52a is selected, the positive sequence overvoltage stage will indicate when
positive sequence of voltage exceeds set threshold value and there is a confirmation
of closed state of breaker.

Block tV1> Input V1> Alarm Alarm

VTS Block V1>


& Alarm Recorder
0 TIMER T
V1> Disable

52a
& tV1> Time delay

V1/52a & OR &


DT/IDMT
with DT or IDMT
reset
tV1>

V1

Start V1> Threshold


&
Start V1>

& Instantaneous
Recorder

Trip Protection

V1> Trip
& Trip Pulse Protection

Fault Recorder

Figure 5: Positive Sequence Undervoltage Protection logic


The types of IDMT characteristics are the same, like in overvoltage protection. For more
information about time-delay characteristic, please refer to section 1.1.1 of this chapter
technical manual, about time delayed reset characteristic please refer to section 1.1.2.
V11V/EN OP v1.0 Operation

(OP) 5-14 VAMP 11V

1.6 Frequency Protection (Model A)


This function has two possibilities of working: underfrequency and overfrequency.
Underfrequency is used to detect abnormal, low frequency compared to the rated frequency,
to monitor power supply quality, overfrequency option can detect abnormal, high frequency
of power supply.
The frequency element included in the V11V relay provides six stages of non-directional
overfrequency or underfrequency protection with independent time-delay characteristics.
These characteristics are only definite time (DT) characteristic.
If the f> (or f<) protection element is set to Trip, it means that that element is linked to the
Protect.Trip and Prot.Trip pulse functions (see LED and Output configuration).
If the f protection element is set to Alarm, it means that that element is linked to the Alarm
function (see LED and Output configuration).
If f> Trip is selected, the frequency stage will work in overfrequency option and trip
when frequency exceeds set threshold value.

OP If f> Alarm is selected, the frequency stage will work in overfrequency option and
indicate alarm when frequency exceeds set threshold value.
If f< Trip is selected, the frequency stage will work in underfrequency option and trip
when frequency exceeds set threshold value.
If f< Alarm is selected, the frequency stage will work in underfrequency option and
indicate alarm when frequency exceeds set threshold value.

Block tfn Input fn> Alarm Alarm

VTS Block fn
& Alarm Recorder
0 T

&
TIMER

fn> Disabled tfn Time delay


DT
tfn
Start fn> Threshold &
[81] Block (HMI,remote)

OR
Start fn

fn< Disabled & Instantaneous


Recorder

Start fn< Threshold &


[81] Block (HMI,remote)

Trip Protection

fn Trip
& Trip Pulse Protection

Fault Recorder

Block tfn Input tfn Alarm Alarm

VTS Block fn
& Alarm Recorder
0 T

& &
Disabled fn> TIMER

Start fn> Threshold


& tfn Time delay
DT
OR tfn
Disabled fn<

Start fn< Threshold


& Start fn

& Instantaneous
Recorder

Trip Protection

fn Trip
& Trip Pulse Protection

Fault Recorder

Figure 6: Frequency protection logic


Operation V11V/EN OP v1.0

VAMP 11V (OP) 5-15

1.7 Auxiliary Timers (Model NA)


Four auxiliary timers, tAux1, tAux2 and tAux3 are available and associated with logic inputs
Aux1, Aux2 and Aux3 (refer to the SETTING GROUP x/INPUTS CONFIGURATION menu).
When these inputs are energized, the associated timers start and, when the set time has
elapsed, the associated LEDs (SETTING GROUP 1(2)/LEDs CONFIGURATION menu) are
lit up or/and the associated output relays close (refer to the SETTING GROUP 1(2)/OUTPUT
RELAYS CONFIGURATION menu). Time-delays can be independently set from 0 ms to 600
s.
Each auxiliary timer can be set independently to:
- Disable: Function is turn off,
- Trip: Protection Trip signal,
- Alarm: Alarm signal.

Block AUXn Input tAUXn Alarm Alarm

AUXn Disabled & Alarm Recorder


&
AUXn Input
&
0 TIMER

tAUXn
T

Time delay
OP
tAUXn
DT

Start AUXn

& Instantaneous
Recorder

Trip Protection

AUXn Trip
& Trip Pulse Protection

Fault Recorder

Figure 7: AUX Timer Logic (AUX1-AUX3)


In the SETTING GROUP x/INPUTS CONFIGURATION menu AUX4 and/or AUX5 can be
mapped to inputs. These input functions have no timers (instantaneous action). They can be
used as bridges between inputs and LEDs or inputs and outputs. It is not possible to link this
input function to a Trip or Alarm signal.
V11V/EN OP v1.0 Operation

(OP) 5-16 VAMP 11V

1.8 Blocking Logic Function (Model N, A)


Each stage of the protection element can be blocked via an appropriately configured binary
input. Binary inputs can be assigned to the following functions (SETTING GROUPx/INPUT
CONFIGURATION Gx):
- Block.tV>, (NA)
- Block.tV>>, (NA)
- Block.tV>>>, (NA)
- Block.tV<, (NA)
- Block.tV<<, (NA)
- Block.tV<<<, (NA)
- Block.tV1<, (A)
- Block.tV1<<, (A)
OP - Block.tV2>, (NA)
- Block.tV2>>, (NA)
- Block.tVN>, (NA)
- Block.tVN>>, (NA)
- Block.tVN>>>, (NA)
- Block.tf1, (A)
- Block.tf2, (A)
- Block.tf3, (A)
- Block.tf4, (A)
- Block.tf5, (A)
- Block.tf6. (A)
Such a configured input can be used by the blocking logic function or by a protection
element disabling function (AUX).
The blocking logic function can be applied to radial feeder circuits where there is little or no
back feed. For parallel feeders, ring circuits or where there can be a back feed from
generators, directional relays should be considered.
The blocking logic function allows the upstream IDMT relay to be blocked by the start output
of a downstream relay that has detected the presence of a fault voltage above its threshold.
Thus both upstream and downstream relays can have the same voltage and time settings,
and the blocking feature will automatically provide grading.
Operation V11V/EN OP v1.0

VAMP 11V (OP) 5-17

2. OPERATION OF NON PROTECTION FUNCTIONS


2.1 VT Supervision (Model N, A)
The voltage transformer supervision function is used to detect any failure of the analog
inputs to the relay. This may be caused by internal voltage transformer faults, overloading or
faults on the interconnecting wiring to relays.

VT supervision function can block protection function according to the settings, when VT loss
is detected.

The detection mode can be selected in GLOBAL SETTINGS/VT SUPERVISION/


DETECTION MODE:

− VTS input – VT supervision function works when input “VTS” is energized,

− DELTA Vr – VT supervision function works when internal calculation confirms a problem


with VT,

− DELTA Vr and VTS – VT supervision function works when internal calculation confirms OP
a problem with VT and/or input “VTS” is energized.
There is a possibility to set time delay to activate blocked protection function by VT
supervision in GLOBAL SETTINGS/VT SUPERVISION/tVTS.

The blocking protection by VT supervision can be selected in GLOBAL SETTINGS/VT


SUPERVISION.

2.2 Circuit Breaker State Monitoring (Model A)


An operator at a remote location requires a reliable indication of the state of the switchgear.
Without an indication that each circuit breaker is either open or closed, the operator has
insufficient information to decide on switching operations. The VAMP 11V relays incorporate
circuit breaker state monitoring, giving an indication of the position of the circuit breaker.
This indication is available either on the relay front panel or via the communication network.
The CB position can be selected in SETTING GROUPx/INPUT CONFIGURATION Gx):
- CB status 52A,
- CB status 52B.
If two inputs are assigned to both above inputs, CB status is based on both indications.
If only one function is used, CB status is based on a single-bit information only (the second is
derived from the first one).
If CB Supervision function is activated (GLOBAL SETTINGS/CIRCUIT BREAKER/CB
Supervision?: 1:Yes), CB monitoring logic detects abnormal CB’s position (opened and
closed, or not opened and not closed) in the monitoring window: the max value from settings:
Max CB Close Time or Max CB Open Time (GLOBAL SETTINGS/CIRCUIT BREAKER
column). CB monitoring logic checks CB position permanently, if an abnormal CB status is
detected by the time longer than the monitoring window, the Alarm is issued (Alarm State of
CB).
The CB’s status can be displayed on the V11V front panel using programmable LEDs. To
assign an input to the CB status, an AUX function must be used.
For example:
L1 is assigned to CB status 52a and AUX4,
L2 is assigned to CB status 52a and AUX5,
LED 6 is assigned to AUX4,
LED 7 is assigned to AUX5.
V11V/EN OP v1.0 Operation

(OP) 5-18 VAMP 11V

In the above configuration LED6 indicates the CB closed position and LED7 indicates the CB
open position.
If the Control menu cell is selected as the default display, the CB status is indicated on the
LCD display:

CB status: Opened
CTRL: no operat.

OP
Operation V11V/EN OP v1.0

VAMP 11V (OP) 5-19

2.3 Local / Remote Mode (Model N, A)


The goal of this feature is to make possible to block commands sent remotely through
communication networks (such as setting parameters, control commands, etc.), so as to
prevent any accidents or mal operations during maintenance work performed on site.
Local Mode can be achieved by:
- Control Mode default cell in the menu:

LR Status: L+R
CTRL: no operat.
- A digital input labelled: Local CTRL Mode
When the Local CTRL Mode input is energized, all remote commands are blocked. When
the Local CTRL Mode input is de-energized, remote control commands can be issued. In
Local mode, only the synchronizing time signal is allowed.
The Remote mode is set in GLOBAL SETTINGS/CIRCUIT BREAKER/Remote CTRL
Mode: OP
- 0: Remote only – Only Remote control is permitted. All manual controls (HMI,
Close/Trip function keys, Binary Inputs assigned to Manual Close or Trip) are blocked,
- 1: Remote + LOC - Remote and Local controls are permitted.
Control Mode default cell:
The first line of CTRL Mode cell allows monitoring of the Local/Remote Mode status:
- Status: Local - Local mode,
- Stat: Remote – Remote Mode. GLOBAL SETTINGS/CIRCUIT BREAKER/Remote
CTRL Mode is set to 0: Remote only,
- Status: L+R – Remote Mode. GLOBAL SETTINGS/CIRCUIT BREAKER/Remote
CTRL Mode is set to 1: Remote + Loc.
The second line is used to change Local/Remote Mode in the menu:
- CTRL: no operat. – No operation,
- CTRL: Local – Local Mode command,
- CTRL: Remote – Remote Mode command.
To change from Remote to Local mode it is necessary to press the OK key, enter
Control Password (if it is set), press the OK key twice (confirm password and select
changing). Press down or up key to choose Local confirm by Enter. LR Status
indicates: LR Status: Local.
To change from Local to Remote mode it is necessary to press the OK key, enter
Control Password (if it is set), press the OK key twice (confirm the password and select
the change). Press the or key to select Remote then confirm by pressing the
OK key. LR Status indicates: LR Status L+R (option Remote CTRL Mode 1: Remote +
Local) or LR Status Remote (option Remote CTRL Mode 0: Remote) .
Note: if the Control Password is set to zero: no asking about password will appear –
the Control Password is disabled.
It is possible to map the Local Mode state to a LED by assigning the LED to the Local CTRL
Mode function (SETTING GROUP x/LEDs CONFIGURATION Gx).
V11V/EN OP v1.0 Operation

(OP) 5-20 VAMP 11V

2.4 Setting Group Selection


VAMP V11V relays has two protection setting groups called PROTECTION G1 and
PROTECTION G2. Only one group is active at the same time.
If a group is used in an application it is possible to remove the other group from the menu in
order to simplify the setting procedure. If one group only is chosen the relay uses Group 1
even if the other parameters are set to Group 2 (Input, Menu, Remote Group Setting).
The selection of the number of groups is done in GLOBAL SETTINGS/SETTING GROUP
SELECT/Number of Groups: 1: One Group or 2: Two Groups.
If 1: One Group is selected, the SETTING GROUP 2 column and the setting group cell are
hidden in the menu.
Switching between groups can be done via:
- a selected binary input assigned to the Setting Group 2 logic input (SETTING GROUP
x/INPUTS CONFIGURATION Gx submenu),
- the relay front panel interface (GLOBAL SETTINGS/SETTING GROUP SELECT/
OP Setting Group: 1: Group1 or 2: Group2),
- through the communications port (refer to the Mapping Database for detailed
information).
Switching between setting groups can be done even while a protection function is active, but
it resets all timers, LEDs on V11V front panel).
The user can check which one of the setting groups is active in the OP PARAMETERS
menu: Active Set Group cell.
The user can also assign the active group (Setting Group x function) to an output relay
(SETTING GROUP x/OUTPUT RELAYS CONFIGURATION Gx) or to any LED (SETTING
GROUP x/LEDs CONFIGURATION G1).
Setting group change via a digital input
It is possible to change the setting group by energizing a digital input (operates on level:
logic input is low – setting group 1, logic input is high – setting group 2 ).
If the setting group switchover is done via a binary input, the change from Group 1 to
Group 2 is executed after the set time-delay: t Change Setting G1->G2 (GLOBAL
SETTINGS/SETTING GROUP SELECT). The switch from Group 2 back to Group 1 is
instantaneous.
Warning: If the digital input that has been assigned to the setting group change operates on
level (low or high), it is not possible to change the setting group via remote communications.
Switch between Active Groups via a Binary Input
When powering up the relay, the selected group (Group 1 or Group 2) corresponds to the
state of the logic input assigned to Setting Group 2. This means:
A – Reverse Inp.Logic = 0 and Setting Group 2 = 1
(SETTING GROUP x/INPUTS CONFIGURATION Gx submenu),
If the programmed logic input starts being supplied with +V, then after the t Change Setting
G1->G2 time-delay the active group will be G2.
If the programmed logic input is not supplied with +V , then the active group will be G1.
B – Reverse Inp.Logic = 1 and Setting Group 2 = 1
(SETTING GROUP x/INPUTS CONFIGURATION Gx submenu),
If the programmed logic input is supplied with +V, then the active group will be G1.
If the programmed logic input stops being supplied with +V , then after the t Change Setting
G1->G2 time-delay the active group will be G2.
Operation V11V/EN OP v1.0

VAMP 11V (OP) 5-21

Notes:
1. Binary Input configuration is associated with both Setting Groups, so that if in
a Setting Group the selected binary input is assigned to Setting Group 2, in the other
group it must be set to Setting Group 2 as well, otherwise no switch will occur.
2. If the V11V is powered-up and Group 2 is selected via a binary input, the t Change
Setting G1->G2 time-delay is ignored (changing to setting group 2 is instantaneous –
without time-delay).
3. The setting group switch is based on the level of the binary input. So as long as
Setting Group 2's logic signal is high, the V11V uses Setting Group 2.

Switch between Active Groups via the Menu or a Remote Command (RS485, USB)
By using the relay front panel interface it is possible to change the active setting group:
1: Group1 or 2: Group2 (menu cell: GLOBAL SETTINGS/SETTING GROUP SELECT/
Setting Group).
This menu cell is commonly used for switching groups from the front panel interface and via
a remote command (RS485 or USB).
OP
It means that if the GLOBAL SETTINGS/SETTING GROUP SELECT/Setting Group menu
cell is set to 1: Group1 and the remote setting group 2 command is executed, the value of
menu cell: GLOBAL SETTINGS/SETTING GROUP SELECT/Setting Group will be
changed to 2: Group2 (Active group: 2).
Setting group 1 will be applied if:
- 1: Group1 is set in the GLOBAL SETTINGS/SETTING GROUP SELECT/Setting
Group menu cell from the relay's front panel interface,
- the remote setting group 1 command is executed. The value of the GLOBAL
SETTINGS/SETTING GROUP SELECT/Setting Group menu cell will then be changed
to 1: Group1.
Priority
Warning: If the digital input that has been assigned to the setting group change operating on
level (low or high), it is not possible to change the setting group via neither remote
communications nor the front panel.
The detailed logic table for setting group selection is shown below:

Front Panel
Binary Input Setting Group
and Active Group
2 (NA)
Remote Setting
Not configured G1 G1
Not configured G2 G2
G1 G1 G1
G1 G2 G1
G2 G1 G2
G2 G2 G2

Note: If a setting group change initiated by a remote command has not been effected due to
priority settings, that command is ignored (not recorded in the V11V logic for the
future, when priority settings allow changing).
It is possible to assign an Active Group state to an output contact by setting the output
contact to the Setting Group x output (SETTING GROUP x/OUTPUT RELAYS
CONFIGURATION Gx.
V11V/EN OP v1.0 Operation

(OP) 5-22 VAMP 11V

If Active Group signaling is required, some LEDs should be assigned to the Setting Group x
function (SETTING GROUP x/LEDs CONFIGURATION Gx).

OP
Operation V11V/EN OP v1.0

VAMP 11V (OP) 5-23

2.5 Commissioning
2.5.1 Maintenance Mode (Model A)
This menu allows the user to check the operation of the protection functions.
It is possible to set following Maintenance mode options (settings):

• “No” - Maintenance mode is disabled. All window cells below are hidden
(Maintenance mode is the latest cell in COMMISIONING column)

• “Yes” - Maintenance mode is enabled. In this mode all test cells in


COMMISIONING column are shown. During tests outputs are energized.

• “Yes,outp.block” - Maintenance mode is enabled and all test cells in


COMMISIONING column are shown. In this mode, the high states of output
functions are ignored (control of outputs is blocked).
This option allows the user to check the operation of the protection functions without actually
sending any external command (Tripping or signalling).
Depends on the rear protocol selected in menu, transmission of information to SCADA is OP
blocked (Modbus RTU) or sent (IEC 103) with additional information to know that V11V is in
Maintenance mode (refer to Communication chapter and EN 60870-5-103 standard).
Changing of setting from “No” to “Yes,….” from the front panel activates this mode for
10 minutes only. After this time the option is automatically switched to “No”.
The selection of the maintenance mode is possible by logic input (the level), control
command (rear or front port), or by front panel interface. The maintenance mode is
terminated by:

• Low state of logic input assigned to Maintenance mode function,

• Control command which activate this mode (rear command or setting: “Yes,….”)
and by turning off the power supply.
Note: Maintenance rear command is available in Modbus protocol only

Maintenance Mode
1: Yes

It is possible to assign the state of Maintenance Mode to programmable LEDs.


In “Yes,outp.block” case, all the output contacts are blocked, and no command can be
issued to these contacts, even if a protection threshold associated with one of these output
contacts has been crossed. (If a protection threshold is exceeded, all associated LEDs will
be ON, even the TRIP LED, if protection element is set to Trip).
If the Maintenance Mode is set in menu (“Yes” or “Yes,outp.block”) after 10 minutes this
function returns automatically to Maintenance mode “No” (function disabled).
If the input assigned to Maintenance Mode is logical high the Maintenance Mode is active
(without any time limitation) up to low state of the logical input.
2.5.2 Outputs test
This function is available after activation of Maintenance mode.
The commissioning cells allow the user to check the external wiring to the relay’s output
contacts. To do this, the user has to set to 1 the desired output contact's corresponding bit,
and this will close the contact and allow the continuity of the wiring to be checked.

Test 7654321
Pattern 0000000
V11V/EN OP v1.0 Operation

(OP) 5-24 VAMP 11V

In the cell below, the contact test time can be set:

Contact Test
Time 1.00s

If the outputs for test are selected and Time for output closing is set, the closing command
can be executed in this cell:

Test output
0: no operation

To execute the test, press OK key, press the or key to select 1: Apply test and
confirm action by OK. The contact will be closed for the duration of the Contact Test Time
pulse.
2.5.3 Functional test
OP This function is available after activation of Maintenance mode
The next commissioning cells allow the user to check the functional output configuration of
the V11V. To do this, the user has only to select which protection element will be triggered,
and this will close the contact assigned to this protection element and allow the continuity of
the wiring to be checked.

Functional Test
0: U>

In the cell below the end of the functional test can be configured:

Functional Test
End 0: CB trip

The following options are possible:


- 0: CB trip – after triggering of functional test, the test is interrupted after trip command,
- 1: Time – the protection element will be triggered for the duration of the pulse time,
If the 1: Time option is selected it is necessary to set the pulse length:

Contact Test Time


Time 001.00s

The next cell is used for functional test execution:

Functional Test
CTRL: no operation

To execute this test, press the OK key, press the or key to select 1: Operate and
confirm action by pressing OK. The contact will be closed for the duration of the Contact
Test Time pulse.
NOTE: In Maintenance Mode V11V works with full functionality (ready to trip in a fault
condition, even during functional test). During functional test of selected stage (for example
tU>), V11V measures voltages so the rest active stages (for example tU>>, tUN>, etc) work
on the measured voltage from the field. Test voltage is seen in tested stage only (for
example tU>): two times greater than tU> current setting value in all phases. After test, in the
fault record all recorded voltages values are based on the voltage measured in the field.
Operation V11V/EN OP v1.0

VAMP 11V (OP) 5-25

2.6 Circuit Breaker Control


The relay includes the following options for control of a single circuit breaker:

- Local tripping and closing, via the relay menu or function keys,

- Local tripping and closing, via relay binary inputs, (A)

- Remote tripping and closing, using the relay communications, (NA)

If a local/remote external selector switch is to be used, it is recommended that separate relay


output contacts are assigned to remote circuit breaker control and protection trip. This
enables the control outputs to be selected via a local/remote selector switch as shown in
Figure 8.
Where this feature is not required or is connected to a V11V binary input, the same output
contact(s) can be used for both protection (Protect.Trip output) and remote tripping (Trip
CB order output).

OP

Figure 8: Remote Control of Circuit Breaker

A manual trip will be permitted when the circuit breaker is initially closed. Likewise, a close
command can only be issued if the CB is initially open. To confirm these states it will be
necessary to use the breaker 52A (assigned to CB status 52A input) and/or 52B (assigned
to CB status 52B input) contacts. Under these circumstances manual CB control will be
possible. Additionally, it will be not possible to see the CB status in the Control default cell.
Once a CB Close command is initiated the output contact (Close CB order) can be set to
operate following a user-defined time-delay (Time-delay for Close setting in GLOBAL
SETTINGS/CIRCUIT BREAKER menu). This would give personnel time to move safely
away from the circuit breaker following the close command. This time-delay will apply to all
manual CB Close commands.
V11V/EN OP v1.0 Operation

(OP) 5-26 VAMP 11V

The length of the trip or close control pulse can be set via the tOpen pulse min and tClose
Pulse settings respectively (GLOBAL SETTINGS/CIRCUIT BREAKER menu). This should
be set as long enough to ensure the breaker has completed its open or close cycle before
the pulse has elapsed.
Note: The manual trip and close commands are found in the default Control
cell and the Close/Trip keys on the front panel.
If an attempt to close the breaker is being made, and a protection trip signal is generated,
the protection trip command overrides the close command.
If CB FLT Ext.Sign is assigned to a binary input this signal is checked before manual
closing of the CB. This function uses the signal received at the relay's binary input to confirm
whether the breaker is capable of closing (sufficient circuit breaker energy for example). A
user-settable time-delay, tCB FLT ext, is included for manual closure. If, following a close
command, the CB does not signal a healthy condition before the timer elapses, then the
relay will lockout and issue an alarm.
Note: Trip and close commands work independently from CB status. It means that
the Trip/Close command will be executed even if CB status is discrepancy (00
OP - undefined or 11 - faulty).
2.7 Real Time Clock Synchronization via Opto-Inputs (Model A)
In modern protective schemes it is often desirable to synchronize the relay’s real time clock
so that events from different relays can be placed in chronological order. This can be done
using the communication interface connected to the substation control system or via a binary
input. Any of the available binary inputs on the V11V relay can be selected for
synchronization. Pulsing this input will result in the real time clock snapping to the nearest
minute. The recommended pulse duration is 20 ms to be repeated no more than once per
minute. An example of the time synchronization function is shown.

Time of “Sync. Pulse” Corrected Time


19:47:00.000 to 19:47:29.999 19:47:00.000
19:47:30.000 to 19:47:59.999 19:48:00.000

Note: The above assumes a time format of hh:mm:ss


The input is configured in the SETTING GROUPx/INPUT CONFIGURATION Gx menu. The
input must be assigned to the Time Synchr. Input (Model A).

2.8 Resetting of Latched LEDs and Outputs


How latched LEDs and outputs are reset is determined by the inputs assigned to the
resetting of latched LED. Outputs can be reset via external inputs, by pressing the C clear
key on the V11V front panel if the LCD shows the default display or via the communication
port.
The resetting configuration can be entered in the GLOBAL SETTINGS/LOC menu:
- LEDs Reset:
- 0: Manual only (via Inputs, HMI C key, Remote Reset command)
- 1: Protection start (Start of a protection element set to Trip)
- Ltchd Outp. Reset:
- 0: Manual only (via Inputs, HMI C key, Remote Reset command)
- 1: Protection start (Start of a protection element set to Trip)

The Manual only option prevents a close command from being issued without readout of the
cause of trip by maintenance personnel. It reduces the risk to switch on to fault.
Operation V11V/EN OP v1.0

VAMP 11V (OP) 5-27

The Manual only option prevents a close command from being issued without readout of the
cause of trip by maintenance personnel. It reduces the risk to switch on to fault.
The Protection start option allows to signal the latest trip only: Start of any protection
element set to trip the CB, reset all latched LEDs and show the default display.

OP
V11V/EN OP v1.0 Operation

(OP) 5-28 VAMP 11V

2.9 Records
2.9.1 Fault Recorder
Each time any of the set thresholds are crossed, an instantaneous record is created and
displayed in the RECORDS/FAULT RECORD menu. Information on the last five starts is
available, with the duration of the signal.
The following information is displayed in the RECORDS/FAULT RECORD menu: time, date,
origin (crossing of a voltage threshold or start of a protection element's time-delay), and
voltage values.
Each time any of the set protection elements trips (Protect.Trip output), a fault record is
created and stored in memory. The fault record tags up to 20 faults and stores them in a
non-volatile (FRAM) memory. This allows the operator to identify and analyze system
failures. When the available memory space is exhausted, the new fault automatically
overwrites the oldest fault.
The user can view the latest fault record in the RECORD/FAULT RECORDS menu, where
the user can choose to display up to 20 stored records. These records are the fault flags, the
OP fault measurements, etc. Also note that the time stamp displayed in the fault record itself will
be more accurate than the corresponding time stamp given in the event record. This is due
to the fact that events are logged some time after the actual fault is recorded.
2.9.2 Alarm Recorder
Each time any of the set protection element issues an ALARM signal (Alarm output), an
Alarm record is created and stored in memory. The fault record tags up to 5 faults and stores
them in a non-volatile (FRAM) memory. This allows the operator to identify and analyze
system failures. When the available memory space is exhausted, the new alarm
automatically overwrites the oldest alarm.
The user can view the latest Alarm record in the RECORD/ALARM RECORDS menu, where
he or she can choose to display up to 5 stored records. These records are the alarm flags,
the alarm measurements, etc. Also note that the time stamp displayed in the Alarm record
itself will be more accurate than the corresponding time stamp given in the event record.
Operation V11V/EN OP v1.0

VAMP 11V (OP) 5-29

2.10 Disturbance Recorder (Model A)


The integral disturbance recorder has a memory space specifically dedicated to the storage
of disturbance records. Up to 4 seconds of disturbance recording can be stored. When the
available memory space is exhausted, the new record automatically overwrites the oldest
record.
The recorder stores actual samples that are taken at a rate of 16 samples per cycle.
Each disturbance record consists of analogue and digital channels. (Note that the relevant
CT ratios for the analogue channels are also extracted to enable scaling to primary
quantities).
The disturbance recorder is set in the GLOBAL SETTINGS/DISTURBANCE RECORDER
menu.
The total disturbance recording time is 4s but not more than 5 records are available.
Total number of records available in disturbance recorder is:
o One - for set Max Record Time from in range: 2.01s – 4.00s
OP
o Two – for set Max Record Time from in range: 1.51s – 2.00s
o Three – for set Max Record Time from in range: 1.01s – 1.33s
o Four – for set Max Record Time from in range: 0.81s – 1.00s
o Five - for set Max Record Time from in range: 0.10s – 0.8s
Triggering of disturbance recording depends on the Disturb.Rec.Trig. configuration:
- 0: on Inst. – Start of a protection element set to Trip,
- 1: on Trip – Trip by a protection element followed by the Protect.Trip output.
If the 0: on Inst. option is selected the record consists of: Pre-fault time + duration of the
"any Start" signal presence + Post-fault time.
If the 1: on Trip option is selected the record consists of: Pre-fault time + duration of the Trip
signal presence (Protect.Trip function active) + Post-fault time.
The pre-fault time can be set in the cell: GLOBAL SETTINGS/DISTURBANCE
RECORDER/Pre-Time. If the pre-fault time is set to 100 ms, recording starts 100 ms before
the disturbance.
The post-fault time can be set in the cell: GLOBAL SETTINGS/DISTURBANCE
RECORDER/Post Trip Time. If the post trip time is set to 100 ms, recording stops 100 ms
after the trip signal.

2.11 Event Records (Model N, A)


The relay records and time-tags up to 200 events and stores them in a non-volatile (FRAM)
memory. This allows the system operator to analyze the sequence of events that has
occurred within the relay after a particular power system condition, or switching sequence,
etc. When the available space is exhausted, the new fault automatically overwrites the oldest
fault.
The real time clock within the relay time-tags each event, with a resolution of 1 ms.
The user can view the event records either locally via the USB port, or remotely, via the rear
EIA(RS)485 port.
Application Notes V11V/EN AP v1.0

Vamp 11V

AP

APPLICATION NOTES

Date: 1st December 2015


Software Version: 1A
Connection Diagrams: 10V11V02
V11V/EN AP v1.0 Application Notes

Vamp 11V

AP
Application Notes V11V/EN AP v1.0

Vamp 11V (AP) 6-1

CONTENTS

1. INTRODUCTION 3
1.1 Description of relay V11V 3

2. APPLICATION OF INDIVIDUAL PROTECTION FUNCTIONS 4


2.1 Earth and phase overvoltage functions 4
2.1.1 Instantaneous function 5
2.1.2 DMT timer stages 5
2.1.3 IDMT timer stages 6
2.1.4 Reset timer 6
2.1.5 Earth fault protection 8
2.2 Phase undervoltage functions 8
2.3 Positive sequence undervoltage (A) 9
2.4 Negative sequence overvoltage (N, A) 9
2.5 Underfrequency protection (A) 10
2.5.1 Setting guidelines 10
AP
2.6 Overfrequency protection (A) 11
2.6.1 Setting guidelines 11
2.7 LOCAL / REMOTE MODE (N, A) 11
2.7.1 General 11
2.7.2 Setting 11
2.8 Auxiliary timers (N, A) 12
2.9 Setting Group Selection 12
2.10 Maintenance Mode (A) 14
2.11 Circuit Breaker State Monitoring (Model A) 15
2.12 Circuit Breaker Condition Monitoring (A) 15
2.13 Real time clock synchronization via opto-inputs (A) 15
2.14 Event Records (A, N) 16
2.15 Disturbance Recorder (A) 16
2.16 External trip (N, A) 17

3. VT REQUIREMENTS 18
4. AUXILIARY SUPPLY FUSE RATING 19

FIGURES

Figure 1: V11V single-line functional diagram (all options included) 4

Figure 2: Logic diagram for the phase stages V>, V>> and V>>> 5
Figure 13: Example of Local/Remote Application 12
V11V/EN AP v1.0 Application Notes

(AP) 6-2 Vamp 11V

AP
Application Notes V11V/EN AP v1.0

Vamp 11V (AP) 6-3

1. INTRODUCTION
1.1 Description of relay V11V
The relay V11V range is Schneider Electric universal voltage/frequency protection. This
protection have been designed to control, protect and monitor industrial power network,
public power grid.
Before carrying out any work on the equipment, the user should be familiar
with the contents of the Safety Guide, SFTY/4L M/E11 or later issue, or
the safety and technical data section of the technical manual and also the
ratings on the equipment rating label.

For safety reasons, no work must be carried out on the V11V until all
power sources to the unit have been disconnected.

AP
V11V/EN AP v1.0 Application Notes

(AP) 6-4 Vamp 11V

2. APPLICATION OF INDIVIDUAL PROTECTION FUNCTIONS


The following sections detail individual protection functions in addition to where and how they
may be applied. Each section provides some worked examples on how the settings are
applied to the relay.

Figure 1: V11V single-line functional diagram (all options included)


AP
2.1 Earth and phase overvoltage functions
Vamp 11V relays provide definite and independent time-delayed overvoltage protection.
Each phase voltage and earth voltage (or calculated earth voltage) input is associated with
three stages.
The first and second timer stages for phase overvoltage and first stage for earth fault can be
set to definite time-delay or inverse time-delay using the IEC_SI, IEC_VI, IEC_EI, IEC_LTI,
UK_STI, C02_P20, US_ C08, IEEE_MI, IEEE_VI, IEEE_EI, RXIDG, BPN EDF, RI, RECT,
C02_P40 curves. Their parameters are shown in the Technical Data chapter of this
Technical Guide.
The third stage for o/v and second and third for e/f o/v can be set as definite time-delay only.

The instantaneous stages are labeled “V>” for the first stage, “V>>” and “V>>>” for the
second and third instantaneous stages respectively (“VN>”, “VN>>” and “VN>>>” for earth
fault elements).

The time-delayed stages are labeled “tV>” for the first stage, “tV>>” and “tV>>>” for the
second and third time-delayed stages respectively (“tVN>”, “tVN>>” and “tVN>>>” for the
time-delayed earth fault stages).
The protection elements trip when the following conditions are realized:
- A phase to phase or phase to neutral voltages exceeds the set overvoltage threshold
- The relevant time-delay has elapsed
- The blocking logic (if used) is not activated.
The following diagrams show the functionality for each stage.
Application Notes V11V/EN AP v1.0

Vamp 11V (AP) 6-5

Start V >

Max V>

& IDMT / DT tV >


Block.tV > Input

Start V >>

Max V>>

& IDMT /DT tV >>


Block.tV >> Input

Start V>>>

Max V >>>

& DT t V>>>
Block.tV >>> Input

P0942ENa

Figure 2: Logic diagram for the phase stages V>, V>> and V>>>
The logic associated with the earth fault stage is identical to the logic described above. The
stages V> & tV>, V>> & tV>> and V>>> & tV>>> are respectively replaced by the stages
VN> & tVN>, VN>> & tVN>>, VN>>> & tVN>>>. AP
Thanks to the "Blocking Logic" function, it is possible to freeze the timer as long as the
"Block Logic" signal is active.
As soon as the blocking “Block Logic" signal drops, if the overvoltage value is still over the
set threshold, the time-delay resumes using the value prior to the activation of the blocking
function as its new initial value. This allows faster clearance of the fault after resetting of the
“Block Logic" signal.
2.1.1 Instantaneous function
As soon as a phase (or earth) timer stage starts running, the instantaneous output
associated with that stage is activated. This output indicates that the protection element has
detected a phase (or earth) fault and that the corresponding time-delay has started. This
time-delay can be blocked via the associated "Block Logic" logic input. If this blocking input
is activated by an output contact of a downstream relay, the logic that will lead to the trip
command is then blocked only if the relay that is the closest to the fault can see and
therefore eliminate the fault. This principle is known as «Blocking logic» or «Blocking». It is
described in more detail in this document.
2.1.2 DMT timer stages
The three phase (earth) overvoltage stages can be assigned definite time-delays. The time
to operate is equal to the set time-delay plus the time for the output contact to operate
(typically about 30 ms) and the time required to detect the overvoltage condition (maximum
20 ms at 50 Hz).
For DMT stages, a definite-time "tReset" reset timer is associated with the first phase o/v
stage, and with the first earth fault stage.
V11V/EN AP v1.0 Application Notes

(AP) 6-6 Vamp 11V

2.1.3 IDMT timer stages

The first and the second (V>, V>>) and e/f (VN>) overvoltage stages can be selected with
an inverse maximum time (IDMT) characteristic.
The time-delay in relay operation is calculated with a mathematical formula that depends on
the relay voltage and TMS (IEC and UK) or TD (IEEE and US) values.
There are twelve inverse time characteristics available:

• SI: Standard Inverse Time Characteristic (IEC/A)

• VI: Very Inverse Time Characteristic (IEC/B)

• EI: Extremely Inverse Time Characteristic (EC/C)

• LTI: Long Time Inverse Characteristic (IEC)

• STI: Short Time Inverse Characteristic (FR)

• RC: Rectifier Characteristic (UK)

• MI: Medium Inverse Time Characteristic (IEEE, IEC/D)

• VI: Very Inverse Time Characteristic (IEEE, IEC/E)

• EI: Extremely Inverse Time Characteristic (IEEE, IEC/F)

AP • CO2 P20: Short Time Inverse Characteristic (US)

• CO2 P40: Short Time Inverse Characteristic (US)

• CO8: Inverse Characteristic (US)

• RI: Electromechanical Inverse Characteristic

• BNP Time Charactristic (EDF)

• RXIDG Time Charactristic


The mathematical formulae and curves for the twelve Inverse Time characteristics available
with the V11V are presented in chapter OP (“Operation”).
2.1.4 Reset timer

The first overvoltage [V>] and the first earth fault [VN>] stages have a reset timer.
The value that is set for this reset timer corresponds to the minimum time during which the
voltage value needs to be lower than 95% of the phase to phase or phase to neutral (or
earth) threshold before the corresponding phase (or earth) time-delay is reset.
Note: This rule does not apply when the protection element is triggered.
When the protection element is triggered, the time-delay tV> (or tVN>)
is immediately reset.
DMT stages have DMT reset timers only.
IDMT characteristics can be associated with either a DMT or an IDMT reset timer. This
selection is made in the menu:
- phase voltage: SETTING GROUP x/PROTECTION Gx /[59] PHASE O/V Gx
/Reset Delay Type: 0:DT High State or 1: IDMT
- earth voltage: SETTING GROUP x/PROTECTION Gx /[59N] E/GND FAULT O/V
Gx/Reset Delay Type: 0: DT High State or 1: IDMT
Application Notes V11V/EN AP v1.0

Vamp 11V (AP) 6-7

DMT Reset Timer

Type of timer associated with the first


DMT Reset Timer
& second phase (50/51 only) stages

DT High State (see note below) 0 ms to 600 s


IDMT 0 ms to 600 s

For the first phase and earth overvoltage stages, the Vamp 11V has a timer hold facility,
DMT tReset, which can be set to a definite time value or to an inverse time characteristic.
This timer hold facility is used to reduce fault clearance times and is also useful in situations
where intermittent faults may be experienced. This can for example be the case on a plastic-
insulated cable. In that case, the fault energy may cause the cable insulation to melt and
reseal, thereby extinguishing the fault. This process repeats itself a couple of times giving a
succession of fault current pulses, each of increasing duration with reducing intervals
between the pulses, until the fault becomes permanent.
When the reset time of the overvoltage relay is instantaneous the relay will be repeatedly
reset and unable to trip until the fault becomes permanent. By using the Timer Hold facility,
the relay will integrate the fault voltage pulses, thereby reducing fault clearance time.
The Vamp 11V's reset timer DMT tReset can be found in the following menu cells:

• SETTING GROUP x/PROTECTION Gx /[59] PHASE O/V Gx /DMT tReset


for the phase. AP
• SETTING GROUP x/PROTECTION Gx /[59N] E/GND FAULT O/V Gx /DMT
tReset for the earth.
IDMT Reset Timer (IDMT Reset Characteristic)
When the reset time of the overvoltage relay is instantaneous, the relay will be repeatedly
reset and unable to trip until the fault becomes permanent. By using the Timer Hold facility
for IDMT characteristics the relay will integrate the fault voltage pulses, thereby reducing
fault clearance time.
For IDMT it is possible to set the timer hold facility based on the following formulae:

 
 
 tr 
IEC: t = RTMS ×  p 
 1 −  G  
 
  Gs  
 
 
 tr 
IEEE and US: t = RTD ×  p 
 1 −  G  
 
  Gs  
where:
t Reset time
tr, p Constant (see table)
G Value of the measured voltage

Gs Value of the programmed threshold (pick-up value)


RTMS Reset time multiplier setting between 0.02 and 1.5.
RTD Reset time multiplier setting between 0.02 and 100.
V11V/EN AP v1.0 Application Notes

(AP) 6-8 Vamp 11V

Type of curve Standard tr p


US Short time inverse C02_P40 2.261 2
US Short time inverse C02_P20 2.261 2
Long time inverse C08 5.95 2
IEEE Moderately inverse (MI) IEEE 4.9 2
IEEE Very inverse (VI) IEEE 21.6 2
IEEE Extremely Inverse (EI) IEEE 29.1 2
IEC Standard Inverse Time (SI) IEC/A 12.1 2
IEC Very Inverse Time (VI) IEC/B 43.2 2
IEC Extremely Inverse Time (EI) IEC/C 80 2
IEC Long Time Inverse (LTI) IEC 0 2
FR Short Time Inverse (STI) FR 0 2
UK Rectifier (Rect) UK 0 2
BNP EDF BNP EDF 0 2
RXIDG RXIDG 0 0
RI RI 0 2
AP
Table 1: The value of “tr” for IDMT characteristics

Notes: 1. According to the IEEE and US standards, RTD should be equal to


TD. By separately setting the values for RTD and TD it is possible to
adapt the reset time to a specific application.
2. Typically for IEC characteristic RTMS can be set equal to TMS.
2.1.5 Earth fault protection
Earth fault (E/F) voltage can be measured on the e/f input (A,N) or calculated from phase
voltage.

Three stages are available: VN>, VN>> and VN>>>. The first stage has IDMT or DT
characteristics. The types of characteristics are the same as for V> (refer to section 2.1.3).
2.2 Phase undervoltage functions
Vamp 11V relays provide definite and independent time-delayed undervoltage protection.
Each phase voltage input is associated with three stages.
The first timer stage for phase undervoltage can be set to definite time-delay or inverse
time-delay using the IEC_SI, IEC_VI, IEC_EI, IEC_LTI, UK_STI, C02_P20, US_ C08,
IEEE_MI, IEEE_VI, IEEE_EI, RXIDG, BPN EDF, RI, RECT, C02_P40 curves. Their
parameters are shown in the Technical Data chapter of this Technical Guide.
The second and third stage for u/v can be set as definite time-delay only.

The instantaneous stages are labeled “V<” for the first stage, “V<<” and “V<<<” for the
second and third instantaneous stages respectively.

The time-delayed stages are labeled “tV<” for the first stage, “tV<<” and “tV<<<” for the
second and third time-delayed stages respectively.
The protection elements trip when the following conditions are realized:
- A phase to phase or phase to neutral voltages exceeds the set undervoltage threshold
- The relevant time-delay has elapsed
- The blocking logic (if used) is not activated.
Application Notes V11V/EN AP v1.0

Vamp 11V (AP) 6-9

The first phase undervoltage stages [V</tV<] has a reset timer.


The value that is set for this reset timer corresponds to the minimum time during which the
voltage value needs to be higher than 102% of threshold before the corresponding phase
time-delay is reset.
Note: This rule does not apply when the protection element is triggered.
When the protection element is triggered, the time-delay tV< is
immediately reset.

All other information about undervoltage functions are similar to o/v function. Refer to 2.1.
2.3 Positive sequence undervoltage (A)
Positive sequence undervoltage function has two independent stages. Each stage can work
to trip and signal to alarm.
We have possibility to block this function from sate of the connector (when state is open
function is blocked) or from input.

The first s positive sequence undervoltage stage can be set to definite time-delay or inverse
time-delay using the IEC_SI, IEC_VI, IEC_EI, IEC_LTI, UK_STI, C02_P20, US_ C08,
IEEE_MI, IEEE_VI, IEEE_EI, RXIDG, BPN EDF, RI, RECT, C02_P40 curves. Their
parameters are shown in the Technical Data chapter of this Technical Guide.
The second stage can be set as definite time-delay only.
AP
The instantaneous stages are labeled “V1<” for the first stage, “V1<<” for the second
instantaneous stages respectively.

The time-delayed stages are labeled “tV1<” for the first stage, “tV1<<” for the second
time-delayed stages respectively.
The protection elements trip when the following conditions are realized:
- A positive sequence of the voltage exceeds the set undervoltage threshold
- The relevant time-delay has elapsed
- The blocking logic (if used) is not activated.

The first stage [V1</tV1<] has a reset timer.


The value that is set for this reset timer corresponds to the minimum time during which the
voltage value needs to be higher than 102% of threshold before the corresponding phase
time-delay is reset.
Note: This rule does not apply when the protection element is triggered.
When the protection element is triggered, the time-delay tV1< is
immediately reset.
All other information about undervoltage functions are similar to o/v function. Refer to 2.1.

2.4 Negative sequence overvoltage (N, A)


Negative sequence overvoltage function has two independent stages. Each stage can work
to trip and signal to alarm.
We have possibility to block this function from sate of the connector (when state is open
function is blocked) or from input.

The first negative sequence overvoltage stage can be set to definite time-delay or inverse
time-delay using the IEC_SI, IEC_VI, IEC_EI, IEC_LTI, UK_STI, C02_P20, US_ C08,
IEEE_MI, IEEE_VI, IEEE_EI, RXIDG, BPN EDF, RI, RECT, C02_P40 curves. Their
parameters are shown in the Technical Data chapter of this Technical Guide.
The second stage can be set as definite time-delay only.
V11V/EN AP v1.0 Application Notes

(AP) 6-10 Vamp 11V

The instantaneous stages are labeled “V2>” for the first stage, “V2>>” for the second
instantaneous stages respectively.

The time-delayed stages are labeled “tV2>” for the first stage, “tV2>>” for the second time-
delayed stages respectively.
The protection elements trip when the following conditions are realized:
- A negative sequence of the voltage exceeds the set overvoltage threshold
- The relevant time-delay has elapsed
- The blocking logic (if used) is not activated.
All other information about undervoltage functions are similar to o/v function. Refer to 2.1.

2.5 Underfrequency protection (A)


Frequency variations on a power system are an indication that the power balance between
generation and load has been lost. In particular, under-frequency implies that the net load is
in excess of the available generation. Such a condition can arise, when an interconnected
system splits, and the load left connected to one of the subsystems is in excess of the
capacity of the generators in that particular subsystem. Industrial plants that are dependent
on utilities to supply part of their loads will experience under-frequency conditions when the
incoming lines are lost.

AP An underfrequency condition at nominal voltage can result in over-fluxing of generators and


transformers and many types of industrial loads have limited tolerances on the operating
frequency and running speeds e.g. synchronous motors. Sustained underfrequency has
implications on the stability of the system, whereby any subsequent disturbance may lead to
damage to frequency sensitive equipment and even blackouts, if the underfrequency
condition is not corrected sufficiently fast.

The underfrequency protection settings are found in the


SETTING GROUP x/PROTECTION Gx /[81O/81U] FREQUENCY/f?/f< trip/alarm.
2.5.1 Setting guidelines
In order to minimize the effects of underfrequency on a system, a multi stage load shedding
scheme may be used with the plant loads prioritized and grouped. During an
underfrequency condition, the load groups are disconnected sequentially depending on the
level of underfrequency, with the highest priority group being the last one to be
disconnected.

The effectiveness of each stage of load shedding depends on what proportion of the power
deficiency it represents. If the load shedding stage is too small compared to the prevailing
generation deficiency, then the improvement in frequency may be non-existent. This aspect
should be taken into account when forming the load groups.

Time delays should be sufficient to override any transient dips in frequency, as well as to
provide time for the frequency controls in the system to respond. This should be balanced
against the system survival requirement since excessive time delays may jeopardize system
stability. Time delay settings of 5 - 20s are typical.

The relatively long time delays are intended to provide time for the system controls to
respond and will work well in a situation where the decline of system frequency is slow. For
situations where rapid decline of frequency is expected, the load shedding scheme above
should be supplemented by rate of change of frequency protection elements.
Application Notes V11V/EN AP v1.0

Vamp 11V (AP) 6-11

2.6 Overfrequency protection (A)


Over frequency running of a generator arises when the mechanical power input to the
machine exceeds the electrical output. This could happen, for instance, when there is a
sudden loss of load due to tripping of an outgoing feeder from the plant to a load center.
Under such over speed conditions, the governor should respond quickly so as to obtain a
balance between the mechanical input and electrical output, thereby restoring normal
frequency. Over frequency protection is required as a back-up to cater for slow response of
frequency control equipment.

The underfrequency protection settings are found in the


SETTING GROUP x/PROTECTION Gx /[81O/81U] FREQUENCY/fx/f< trip/alarm.
2.6.1 Setting guidelines
Following faults on the network, or other operational requirements, it is possible that various
subsystems will be formed within the power network and it is likely that each of these
subsystems will suffer from a generation to load imbalance. The “islands” where generation
exceeds the existing load will be subject to over frequency conditions, the level of frequency
being a function of the percentage of excess generation. Severe over frequency conditions
may be unacceptable to many industrial loads, since running speeds of motors will be
affected.

2.7 LOCAL / REMOTE MODE (N, A)


2.7.1 General
AP
The goal of this feature is to make it possible to block commands sent remotely through
communication networks (such as setting parameters, control commands, etc.), so as to
prevent any accidents or maloperation during maintenance work performed on site.
A digital input labeled “Local CTRL mode” is assigned to this feature. In Local mode, only
the synchronizing time signal is allowed.
The local mode can also be set in default CTRL mode cell. The Local/Remote mode state is
displayed in this cell.
2.7.2 Setting
The Remote Mode state can be set in the GLOBAL SETTINGS/CIRCUIT BREAKER/
Remote Mode cell:
- 0: Remote only – Local control via an input or/and the HMI or/and the Close/Trip key
are blocked.
- 1: Remote + Local – Local and Remote control are permitted.
When the “Local” input is energized, all remote commands are blocked. When the “Local”
input is de-energized, remote control commands are accepted.
If local/remote switching has to be done outside of the V11V, the output configuration can be
as follows (Figure 3):
- the protection trip is assigned to the Prot.Trip pulse output,
- the remote close command is assigned to the Close CB Order output,
- the remote trip command is assigned to the Trip CB Order output.
V11V/EN AP v1.0 Application Notes

(AP) 6-12 Vamp 11V

REMOTE: opened
V11V DC V - DC V + LOCAL: closed
Switch
REMOTE/LOCAL
Local CTRL Mode

RL2
Trip CB Order Manual Trip CB
Coil

RL 3
Close Order Close CB Coil

RL 1
Protection Protection Trip
Trip (pulse ) CB Coil

AP P0947ENa

Figure 3: Example of Local/Remote Application

2.8 Auxiliary timers (N, A)


Two for model N and three auxiliary timers tAux1, tAux2, tAux3 are available and associated
with Aux1, Aux2, Aux3 logic inputs (refer to SETTING GROUP x/INPUTS menu).
When these inputs are energized, the associated timers start and, when the set time has
elapsed, the associated output relays close (refer to SETTING GROUP x/OUTPUT RELAYS
CONFIGURATION Gx). Time-delays can be independently set from 0 ms to 600 s
(SETTING GROUP x/PROTECTION Gx/AUX TIMERS menu).
AUX function can be configured to:
- Trip (Protect.Trip, Prot.Trip pulse, Disturbance and Fault Recorder, TRIP LED and
FLAG)
- Alarm (Alarm, Alarm LED),
For more details about: Trip, Alarm refer to the Operation Chapter (V11V/EN OP)
AUX and tAUX signal can be assigned to LEDs or outputs.
Binary Inputs can be configured to AUX4 and AUX5. These AUX functions have no timers
and can be used as logic bridge between inputs and: LEDs and/or outputs.

2.9 Setting Group Selection


V11V relays have two protection setting groups called PROTECTION G1 and PROTECTION
G2. Only a one group is active at any time.
If a group is used in an application it is possible to remove the other group from the menu in
order to simplify the setting procedure. If one group only is chosen the relay uses Group 1
even if the other parameters are set to Group 2 (Inputs, Menu, Remote Group Setting).
The selection of the number of groups is done at GLOBAL SETTINGS/SETTING GROUP
SELECT/ Number of Groups: 1: One Group or 2: Two Groups.
Application Notes V11V/EN AP v1.0

Vamp 11V (AP) 6-13

If 1: One Group is selected, the SETTING GROUP 2 column and the setting group cell are
hidden in relay menu.
Switching between the groups can be done via:
- a selected binary input assigned to the Setting Group 2 logic input (SETTING
GROUP x/INPUTS submenu),
- the relay front panel interface (GLOBAL SETTINGS/SETTING GROUP SELECT/
Number of Groups: 0: One Group or 1: Two Groups),
- through the communications port (refer to Mapping Database for detailed
information).
Switching between setting groups can be done even while a protection function is active (no
timers are resetting).
The user can check which one of the setting groups is active looking in the OP
PARAMETERS menu: Active Set Group cell.
The user can also assign the active group (Setting Group x function) to an output relay
(SETTING GROUP x/OUTPUT RELAYS CONFIGURATION Gx) or to an LED (SETTING
GROUP x/LEDs CONFIGURATION G1).
Setting group change via a digital input
It is possible to change the setting group by energizing a digital input (on level).
If the setting group switchover is done via a binary input, the change from One Group to Two AP
Groups is executed.
Switch between Active Groups via a Binary Input
When powering up the relay, the selected group (One Group or Two Groups) corresponds to
the state of the logic input assigned to Setting Group 2. This means:
A – Reverse Inp.Logic = 0 and Setting Group 2 = 1
(SETTING GROUP x/INPUTS CONFIGURATION Gx submenu),
If the programmed logic input starts being supplied with +V, then after the t Change Setting
G1->G2 time-delay the active group will be G2. If the programmed logic input is not supplied
with +V, then the active group will be G1.
B – Reverse Inp.Logic = 1 and Setting Group 2 = 1
(SETTING GROUP x/INPUTS CONFIGURATION Gx submenu),
If the programmed logic input is supplied with +V, then the active group will be G1.
If the programmed logic input stops being supplied with +V, then after the t Change Setting
G1->G2 time-delay the active group will be G2.
Notes: 1. Binary Input configuration is associated with both Setting Groups,
so that if in a Setting Group the selected binary input is assigned to
Setting Group 2, in the other group it must be set to Setting Group 2
as well, otherwise no switch will occur.
2. If the V11V is powering up and Group 2 is selected via a binary
input, the t Change Setting G1->G2 time-delay is ignored (changing
to setting group 2 is instantaneous – without time-delay).
3. The setting group switch is based on the level of the binary input.
So as long as Setting Group 2's logic signal is high, the V11V uses
Setting Group 2.
Switch between Active Groups via the Menu or a Remote Command (RS485, USB)
By using the relay front panel interface it is possible to change the active setting group:
0: One Group or 1: Two Groups (menu cell: GLOBAL SETTINGS/SETTING GROUP
SELECT/ Setting Group).
Above menu cell is common for changing from panel interface and via remote command
(RS485 or USB).
V11V/EN AP v1.0 Application Notes

(AP) 6-14 Vamp 11V

Above menu cell is common for changing from panel interface and via remote command
(RS485 or USB).
It means that if the GLOBAL SETTINGS/SETTING GROUP SELECT/ Setting Group menu
cell is set to 0: One Group and the remote setting group 2 command is executed, the value
of menu cell: GLOBAL SETTINGS/SETTING GROUP SELECT/ Setting Group will be
changed to 1: Two Groups value (Active group: 2).
Setting group 1 will be applied if:
- 0: One Group is set in the GLOBAL SETTINGS/SETTING GROUP SELECT/ Number
of Groups menu cell from the relay's front panel interface,
or
- the remote setting One Group command is executed. The value of the GLOBAL
SETTINGS/SETTING GROUP SELECT/ Number of Groups menu cell will then be
changed to 0: One Group.
WARNING: If the digital input has been assigned to the setting group change, it is not
possible to change the setting group via remote communications. If changing via
Menu or RS485 is required ensure that no input is assigned to Setting Group 2.
Priority
The detailed logic table for setting group selection is shown below:

Front Panel
Binary Input Setting
and Active Group
AP Group 2
Remote Setting
Not configured G1 G1
Not configured G2 G2
G1 G1 G1
G1 G2 G1
G2 G1 G2
G2 G2 G2

Note: If a setting group change initiated by a remote command has not been effected due of
priority settings, that command is ignored (not recorded in the V11V's logic for the future,
when priority settings allow changing).
It is possible to assign an Active Group state to an output contact by setting the output
contact to the Setting Group x output (SETTING GROUP x/OUTPUT RELAYS
CONFIGURATION Gx.
If Active Group signaling is required, some LEDs should be assigned to the Setting Group x
function (SETTING GROUP x/LEDs CONFIGURATION Gx).
2.10 Maintenance Mode (A)
This menu allows the user to check the operation of the protection functions.
It is possible to set following Maintenance mode options (settings):

• “No” - Maintenance mode is disabled. All window cells below are hidden
(Maintenance mode is the latest cell in COMMISIONING column)

• “Yes,outp.trips” - Maintenance mode is enabled. In this mode all test cells in


COMMISIONING column are shown. During tests outputs are energized.

• “Yes,outp.block” - Maintenance mode is enabled and all test cells in


COMMISIONING column are shown. In this mode, the high state of output functions
are ignored (control of outputs are blocked).
This option allows the user to check the operation of the protection functions without
actually sending any external command (Tripping or signalling).
Application Notes V11V/EN AP v1.0

Vamp 11V (AP) 6-15

Depends on the rear protocol selected in menu, transmission of information to SCADA is


sent with some limitation (Modbus RTU) or sent (IEC 103) with additional information to
know that V11V is in Maintenance mode (refer to Communication chapter and EN 60870-5-
103 standard).
Changing of setting from “No” to “Yes,….” from the front panel activate this mode for 5
minutes only. After this time the option is automatically switched to “No”.
The selection of the maintenance mode is possible by logic input (the level), control
command (rear or front port), or by front panel interface. The maintenance mode is
terminated by:

• Low state of logic input assigned to Maintenance mode function,

• Control command which activate this mode (rear command or setting: “Yes,….”)
and by turning off the power supply.
Note: Maintenance rear command is available in Modbus protocol only
When this menu is activated (set to: “Yes,outp.trips” or “Yes,outp.block”), the Alarm led is
lit. Additionally it is possible to configure Maintenance Mode to programmable LED.
In “Yes,outp.block” case, all the output contacts are blocked, and no command can be
issued to these contacts, even if a protection threshold associated with one of these output
contacts has been crossed (If a protection threshold is crossed, all associated LEDs will be
ON, even the TRIP LED, if protection element is set to Trip).
2.11 Circuit Breaker State Monitoring (Model A) AP
An operator at a remote location requires a reliable indication of the state of the switchgear.
Without an indication that each circuit breaker is either open or closed, the operator has
insufficient information to decide on switching operations. The Vamp 11V relays incorporate
a circuit breaker state monitoring feature, giving an indication of the position of the circuit
breaker.
This indication is available either on the relay's front panel or via the communication network.
The positions of the CB contacts can be selected under the SETTING GROUP x/INPUTS
CONFIGURATION Gx and SETTING GROUP x/LEDs CONFIGURATION Gx menus using
AUX4 (in parallel with CB Status 52A) and AUX5 (in parallel with CB Status 52B).
AUX4 (CB closed) and AUX5 (CB opened) must be assigned to LEDs in SETTING GROUP
x/LEDs CONFIGURATION Gx menu.
2.12 Circuit Breaker Condition Monitoring (A)
Periodic maintenance of circuit breakers is generally based on a fixed time interval, or a fixed
number of fault current interruptions.
The relays record the following controls and statistics related to each circuit breaker trip
operation:

• time-delay setting,

• monitoring time for CB open and close operations,

• trip CB time from external signal,

• tripping and closing pulse time

2.13 Real time clock synchronization via opto-inputs (A)


In modern protection schemes it is often desirable to synchronize the relay’s real time clock
so that events from various relays can be placed in chronological order. This can be done
using the communication interface connected to the substation control system or via a binary
input. Any of the available binary inputs on the V11V relay can be selected for
synchronization. Pulsing this input will result in the real time clock snapping to the nearest
V11V/EN AP v1.0 Application Notes

(AP) 6-16 Vamp 11V

minute. Synchronization pulse should be repeated no more than once per minute. An
example of the time synchronization function is shown.

Time of “Sync. Pulse” Corrected Time


19:47:00.000 to 19:47:29.999 19:47:00.000
19:47:30.000 to 19:47:59.999 19:48:00.000

Note: The above assumes a time format of hh:mm:ss


The input is configured in the SETTING GROUPx/INPUT CONFIGURATION Gx menu.
The input must be assigned to Time Synchr.

2.14 Event Records (A, N)


The relay records and time-tags up to 200 events and stores them in a non-volatile (Fram)
memory. This allows the system operator to analyze the sequence of events that has
occurred within the relay after a particular power system condition, or switching sequence,
etc. When the available space is exhausted, the new fault automatically overwrites the oldest
fault.
The real time clock within the relay time-tags each event, with a resolution of 1 ms.
The user can view the event records either locally via the USB port, or remotely, via the rear
EIA(RS)485 port.
AP 2.15 Disturbance Recorder (A)
The integral disturbance recorder has a memory space specifically dedicated to the storage
of disturbance records. Up to 4 seconds of disturbance recording can be stored. When the
available memory space is exhausted, the new record automatically overwrites the oldest
record.
The recorder stores actual samples that are taken at a rate of 16 samples per cycle.
Each disturbance record consists of analogue and digital channels. (Note that the relevant
VT ratios for the analogue channels are also extracted to enable scaling to primary
quantities).
The disturbance recorder is set in the GLOBAL SETTINGS/DISTURBANCE RECORDER
menu.
The total disturbance recording time is 4 s but not more than 5 records are available.
Total number of records available in disturbance recorder is:
o One - for set Max Record Time from in range: 2.01s – 4.00s
o Two – for set Max Record Time from in range: 1.34s – 2.00s
o Three – for set Max Record Time from in range: 1.01s – 1.33s
o Four – for set Max Record Time from in range: 0.81s – 1.00s
o Five - for set Max Record Time from in range: 0.10s – 0.80s
Triggering of disturbance recording depends on the Disturb.Rec.Trig. configuration:
- 0: on Inst. – Start of a protection element set to Trip,
- 1: on Trip – Trip by a protection element followed by the Protect.Trip output.
If the 0: on Inst. option is selected the record consists of: Pre-fault time + duration of the
"any Start" signal presence + Post-fault time.
If the 1: on Trip option is selected the record consists of: Pre-fault time + duration of the Trip
signal presence (Protect.Trip function active) + Post-fault time.
Application Notes V11V/EN AP v1.0

Vamp 11V (AP) 6-17

The pre-fault time can be set in the cell: GLOBAL SETTINGS/DISTURBANCE


RECORDER/Pre-Time. If the pre-fault time is set to 100 ms, recording starts 100 ms before
the disturbance.
The post trip time can be set in the cell: GLOBAL SETTINGS/DISTURBANCE
RECORDER/Post Trip Time. If the post-fault time is set to 100 ms, recording stops 100 ms
after the disturbance.
2.16 External trip (N, A)
A Binary Input can be configured to CB trip by using the AUX1, AUX2 (Model N) or AUX1,
AUX2, AUX3 (Model A) functions.
The AUX1 – AUX3 functions have a timer so a trip can be time-delayed.
tAUX1 – tAUX3 can be mapped to:
- RL1,
- RL2,
- RL3,
- RL4,
- RL5,
- RL6, (Model A only),
- RL7, (Model A only); AP
- Trip (protection trip)
- Alarm signal
- Programmable LEDs
If it is configured to Trip (protection trip), tAUX1 – tAUX3 will illuminate the “Trip” LED.
V11V/EN AP v1.0 Application Notes

(AP) 6-18 Vamp 11V

3. VT REQUIREMENTS
In choosing the VT for use with the V11V relays, it is only necessary to consider the
accuracy requirements and the output burden of the VT is sufficient to supply the
relay demands. Protection classes 3P or 6P are usually adequate in terms of accuracy but
care should be taken that the VT is not over-sized as this may lead to resonance problems.
Typically, the output burden of the VT could be 10% higher than the total connected burden
of all connected devices

AP
Application Notes V11V/EN AP v1.0

Vamp 11V (AP) 6-19

4. AUXILIARY SUPPLY FUSE RATING


In the Safety section of this manual, the maximum allowable fuse rating of 16 A is quoted.
To allow time grading with upstream fuses, a lower fuse link current rating is often
preferable. Use of standard ratings of between 6 A and 16 A is recommended. Low voltage
fuse links, rated at 250 V minimum and compliant with IEC 60269-2 general application type
gG, with high rupturing capacity are acceptable. This gives equivalent characteristics to
HRC "red spot" fuses type NIT/TIA often specified historically.
The table below recommends advisory limits on relays connected per fused spur.
This applies to the V11V, as these have inrush current limitation on switch-on, to conserve
the fuse-link.

Maximum Number of V11V Relays Recommended Per Fuse


Battery Nominal Voltage 6A 10 A Fuse 15 or 16 A Fuse Fuse Rating > 16 A
24 to 60 Vac/dc 2 4 6 Not permitted
90 to 240 Vac/
6 10 16 Not permitted
90 to 250 Vdc

Alternatively, miniature circuit breakers (MCB) may be used to protect the auxiliary supply
circuits.

AP
Measurements and Recording V11V/EN MR v1.0

VAMP 11V

MEASUREMENTS AND RECORDING MR

Date: 1st December 2015


Software Version: 1A
Connection Diagrams: 10V11V01
V11V/EN MR 1.0 Measurements and Recording

VAMP 11V

MR
Measurements and Recording V11V/EN MR v1.0

VAMP 11V (MR) 7-1

CONTENTS

1. MEASUREMENTS AND RECORDING 3


1.1 Introduction 3
1.2 Event records 3
1.3 Fault records 4
1.4 Alarm records 4
1.5 Alarm status 5
1.6 Measurements 6
1.7 Counters 7
1.8 Disturbance Recorder (Model A) 7
1.9 Measurement Settings 9
1.9.1 VT Ratio 9
1.9.2 Default Measuring Window 10

MR
V11V/EN MR v1.0 Measurements and Recording

(MR) 7-2 VAMP 11V

MR
Measurements and Recording V11V/EN MR v1.0

VAMP 11V (MR) 7-3

1. MEASUREMENTS AND RECORDING


1.1 Introduction
The V11V is equipped with integral fault recording facilities suitable for analysis of complex
system disturbances. Fault records can be read out by setting software MiCOM S1 Studio
(5.1.0 software version) via the USB port accessible on the V11V front panel (model N and
A). The USB port offers a communications facility to the V11V.
Communications can be established via the USB port even if the V11V is not supplied by the
auxiliary voltage. (A)
Access to the USB port is protected by means of a plastic cover.
1.2 Event records (not available in model L)
The relay records and time tags up to 200 events and stores them in non-volatile FRAM
memory. This enables the system operator to establish the sequence of events that occurred
within the relay following a particular power system condition, switching sequence etc. When
the available space is exhausted, the oldest event is automatically overwritten by the most
recent.
The real time clock within the relay provides the time tag for each event, to a resolution of
1 ms.
The event records are available for remote viewing, via the communications ports RS485 or
USB.
For extraction from a remote source via communications ports, refer to the SCADA
Communications section (V11V/EN CT), where the procedure is fully explained.
Types of event
An event may be a change of state of a control input or output relay, a trip condition, etc. The
following sections show the various items that constitute an event. MR
Change of state of binary inputs
If one or more of the binary inputs has changed state since the last time that the protection
algorithm ran, the new status is logged as an event. The information is available if the event
is extracted and viewed via a PC.
Change of state of one or more output relay contacts
If one or more of the output relay contacts have changed state since the last time that the
protection algorithm ran, then the new status is logged as an event. The information is
available if the event is extracted and viewed via PC.
Relay alarm conditions
Any alarm conditions generated by the relays will also be logged as individual events.
The following table shows examples of some of the alarm conditions and how they appear in
the event list:

Alarm Condition Event Text Event Value


Auxiliary Supply Fail Vx Fail ON/OFF Bit position 0 in 32 bit field
VT Supply Fail VT Supply Fail ON/OFF Bit position 1 in 32 bit field

The above table shows the abbreviated description that is given to the various alarm
conditions and also a corresponding value between 0 and 31. This value is appended to
each alarm. It is used by the event extraction software, such as MiCOM S1 Studio, to identify
the alarm. Either ON or OFF is shown after the description to signify whether the particular
condition is operational or has reset.
V11V/EN MR v1.0 Measurements and Recording

(MR) 7-4 VAMP 11V

Protection element trips


Any operation of protection elements (a trip condition) will be logged as an event record,
consisting of a text string indicating the operated element and an event value. Again, this
value is intended for use by the event extraction software, such as MiCOM S1 Studio.
1.3 Fault records
Each fault record is generated with time stamp.
The following data is recorded for any relevant elements that operated during a fault, and
can be viewed in each of the last 20 fault records:
(i) Event Text (the reason for a trip):
V> trip
V>> trip
V>>> trip
V< trip
V<< trip
V<<< trip
VN> trip
VN>> trip
VN>>> trip
V2> trip (N, A)
V2>> trip (N, A)
V1< trip (A)
V1<< trip (A)
f1 trip (A)
f2 trip (A)
f3 trip (A)
f4 trip (A)
f5 trip (A)
MR f6 trip (A)
AUX1 trip (N, A)
AUX2 trip (N, A)
AUX3 trip (N, A)

(ii) Active setting Group


(iii) Fault Time an Fault Date
(iv) Fault Orgin: type of fault (for example: phase A-B, A-B-C, etc)
(v) Event Value:

Per phase record of the voltage value during the fault: Vϕ and measured VN.

Fault records are stored in non-volatile memory (FRAM memory). This type of memory does
not require any maintenance (no battery inside the V11V). Fault records are stored without
any time limitation even if the V11V is not supplied from any power source.
1.4 Alarm records
Each alarm record is generated with time stamp.
The following data is recorded for any relevant elements that operated during an alarm, and
can be viewed in each of the last 5 alarm records:
(i) Event Text (the reason for a protection alarm):
V> alarm
V>> alarm
V>>> alarm
V< alarm
V<< alarm
V<<< alarm
Measurements and Recording V11V/EN MR v1.0

VAMP 11V (MR) 7-5

VN> alarm
VN>> alarm
VN>>> alarm
V2> alarm (N, A)
V2>> alarm (N, A)
V1< alarm (A)
V1<< alarm (A)
f1 trip (A)
f2 trip (A)
f3 trip (A)
f4 trip (A)
f5 trip (A)
f6 trip (A)
AUX1 trip (NA)
AUX2 trip (NA)
AUX3 trip (NA)

(ii) Active setting Group


(iii) Alarm Time an Alarm Date
(iv) Alarm Orgin: type of alarm (for example: phase A-B, A-B-C, etc)
(v) Event Value:

Per phase record of the voltage value during the alarm: Vϕ and measured VN

Alarm records are stored in non-volatile memory (FRAM memory). This type of memory does
not require any maintenance (no battery inside the V11V). Alarm records are stored without
any time limitation even if the V11V is not supplied from any power source.
1.5 Alarm status
MR
Alarm status presents the current Alarm signals.
The Alarm signals information can be with latching or without latching, depends on the
setting value GLOBAL SETTINGS/LOC/
- Alarms Info 0:Self-reset – only current Alarm status is displayed,
- Alarms Info 1:Latching – Alarm information is latched up to reset in cell: ALARM
STATUS/Reset Press ENTER cell.

The following Alarm is viewed:

tV> Alarm Alarm by the first phase overvoltage stage


tV>> Alarm Alarm by the second phase overvoltage stage
tV>>> Alarm Alarm by the third phase overvoltage stage
tV< Alarm Alarm by the first phase undervoltage stage
tV<< Alarm Alarm by the second phase undervoltage stage
tV<<< Alarm Alarm by the third phase undervoltage stage
tVN> Alarm Alarm by the first earth fault overvoltage stage
tVN>> Alarm Alarm by the second earth fault overvoltage stage
tVN>>> Alarm Alarm by the third earth fault overvoltage stage
tV2> Alarm (NA) Alarm by the first negative sequence overvoltage stage
tV2>> Alarm (NA) Alarm by the second negative sequence overvoltage stage
tV1< Alarm (A) Alarm by the first positive sequence undervoltage stage
tV1<< Alarm (A) Alarm by the second positive sequence undervoltage stage
tf1 Alarm (A) Alarm by the first frequency protection stage
tf2 Alarm (A) Alarm by the second frequency protection stage
tf3 Alarm (A) Alarm by the third frequency protection stage
tf4 Alarm (A) Alarm by the fourth frequency protection stage
tf5 Alarm (A) Alarm by the fifth frequency protection stage
V11V/EN MR v1.0 Measurements and Recording

(MR) 7-6 VAMP 11V

tf5 Alarm (A) Alarm by the fifth frequency protection stage


tf6 Alarm (A) Alarm by the sixth frequency protection stage
CB Time Monit. Alarm. (A) The monitoring time for CB opening/closing
CB Curr.Diagn. Alarm. (A) Summation of the current interrupted by the CB
CB Nb Diagn. Alarm. (A) CB open operations counter monitoring
Hardw.Warning Alarm Any hardware problem detected
State of CB Alarm (NA) The abnormal CB’s position for two bits CB’s connection (00
or 11)
tAUX2 Alarm (NA) tAUX2 time-delay elapsed
tAUX3 Alarm (NA) tAUX3 time-delay elapsed
tAUX4 Alarm (NA) tAUX4 time-delay elapsed
tCB FLTY Ext.Sign. Alarm An input mapped to this function detects CB problems that
(A) may influence control possibilities (for example spring
problem, insufficient pressure, etc.)

1.6 Measurements
The relay produces a variety of directly measured power system quantities:
Va, Vb, Vc - fundamental harmonic values,
Vab, Vbc, Vca - fundamental harmonic values,
V1 (A), V2 (N, A) - calculated fundamental harmonic ratio,
f (A) - frequency,

MR
Measurements and Recording V11V/EN MR v1.0

VAMP 11V (MR) 7-7

1.7 Counters
The V11V counters are available in the RECORDS/COUNTERS menu:
- CONTROL COUNTER:
- No. Trips – Number of manual trip commands (inputs, menu default Control
Window, trip key, remote control via RS485 or USB)
- No. Close - Number of manual close commands (inputs, menu default Control
Window, trip key, remote control via RS485 or USB)
Counters can be reset in the CONTROL COUNTER column.
- FAULT COUNTER:
- No. Fault Trips – Number of trip commands from protection elements (voltage-
based protection element trip, AUX trips and Auto-recloser trips)
- No. Fault Starts – Number of timer starts by protection elements set to trip
(voltage-based protection element and AUX)
- No. Alarms - Number of Alarm signals from protection elements set to Alarm
or functions mapped to an Alarm signal,
- No. HW Warnings – Number of hardware problems detected by the self-
monitoring function.
Counters can be reset in the FAULT COUNTER column.
1.8 Disturbance Recorder (Model A)
The integral disturbance recorder has an area of memory specifically set aside for record
storage. The number of records that may be stored by the relay is dependent upon the
selected recording duration:
Total number of records available in disturbance recorder is:
o One - for set Max Record Time from in range: 2.01s – 4.00s MR
o Two – for set Max Record Time from in range: 1.51s – 2.00s
o Three – for set Max Record Time from in range: 1.01s – 1.33s
o Four – for set Max Record Time from in range: 0.81s – 1.00s
o Five - for set Max Record Time from in range: 0.10s – 0.8s
The recorder stores actual samples that are taken at a rate of 16 samples per cycle. Each
disturbance record consists of eight analog data channels and thirty-two digital data
channels. The relevant VT ratios for the analog channels are also extracted to enable scaling
to primary quantities.
Note: If a VT ratio is set to less than a unit, the relay will choose a scaling
factor of zero for the appropriate channel.

The "DISTURBANCE RECORDER" menu column is shown in the following table:

Setting Range
Menu Text Default Setting Step Size
Min. Max.
Pre-Time 0.1 s 0.1 s 2s 0.01 s
Setting for the disturbance record pre-fault time. The pre-fault time adjusts the beginning of
the disturbance record: In this example, the record starts 100ms before the disturbance. Its
length can be limited by setting.
Post-Fault Time 0.1 s 0.1 s 1s 0.01 s
V11V/EN MR v1.0 Measurements and Recording

(MR) 7-8 VAMP 11V

Setting for the disturbance record post-fault time. The total disturbance recording time is:
pre-fault time + high state of triggering criteria (Start or Trip time)+ post-fault time.
The above total recording time is limited by setting.
0: on Inst.
Disturbance Rec.Trig. 0: on Inst.
1: on Trip
Setting for the trigger criteria:
0: on Inst. – the trigger is the disturbance indicated by the starting of a protection element
set to trip the CB. If this option is chosen the total recording time is: pre-fault time + duration
of protection start + post-fault time, but no longer than the value of Max Record Time.
When delay time of any protection function exceeds Max Record Time and after this delay
time TRIP signal occurs then TRIP is recorded in the next additional record.
1: on Trip. – the trigger is the disturbance indicated by a protection element trip. If this
option is chosen the total recording time is: pre-fault time + duration of protection trip+ post-
fault time, but no longer than the value of Max Record Time.
Max Record Time 1.5 s 0.1 s 4s 0.01 s
Setting for the maximum total recording time. If default value is kept (4 s) it means that
4 records will be recorded.

It is not possible to display the disturbance records locally on the LCD; they must be
extracted using suitable software such as MiCOM S1 Studio.

MR
Measurements and Recording V11V/EN MR v1.0

VAMP 11V (MR) 7-9

1.9 Measurement Settings


The following settings under the measurements heading can be used to configure the relay
measurement function.
1.9.1 VT Ratio
GLOBAL SETTINGS/VT RATIO menu

Setting Range
Menu Text Default Setting Step Size
Min. Max.
Line VT Primary 0.1 kV 0.05k 65k 0.01k
Sets the phase voltage transformer input's primary voltage rating.
Line VT Sec 100 V 57 130 0.1
Sets the phase voltage transformer input's secondary voltage rating.
E/Gnd VT Primary 0.1kV 0.05k 65k 0.01k
Sets the earth fault voltage transformer input's primary voltage rating.
E/Gnd VT Sec 100 V 57 130 0.1
Sets the earth fault voltage transformer input's secondary voltage rating.
3Upn, 3Upn+UN, 2Upp+UN,
VT connection 3Upn N/A
3Upp+UN
Sets the VT connection type to analog input V11V
Protection config
P–P P – P, P – N N/A
V>
Selection of the overvoltage protection type: Phase – Phase or Phase – Neutral
Protection config
MR
P–P P – P, P – N N/A
V<
Selection of the undervoltage protection type: Phase – Phase or Phase – Neutral
V11V/EN MR v1.0 Measurements and Recording

(MR) 7-10 VAMP 11V

1.9.2 Default Measuring Window


Default window is after connection of power supply to V11V or after resetting of signaling.
GLOBAL SETTINGS/LOC menu

Menu Text Default Setting Available Settings

0: Meas. P – P [V]
1: Meas. P – P [Un]
2: Meas. P – N [V]
Default Display 0:Meas. P – P
3: Meas. P – N [Un]
4: Control CB (N, A)
5: Local Mode (A)
This cell is used to change the default display window
0: Measurements in volts (phase to phase)
1: Measurements referred to Un (phase to phase)
2: Measurements in volts (phase to neutral)
3: Measurements referred to Un (phase to neutral)
4: Control Mode window for changing of the CB control mode (N, A)
5: Local/Remote mode and for presenting Control Mode state information (A)

MR
Commissioning V11V/EN CM v1.0

VAMP 11F (CM) 8-1

COMMISSIONING

CM

Date: 1st December 2015


Software Version: 1A
Connection Diagrams: 10V11V01
V11V/EN CM v1.0 Commissioning

(CM) 8-2 VAMP 11V

CM
Commissioning V11V/EN CM v1.0

VAMP 11F (CM) 8-3

CONTENTS

1. SETTING FAMILIARIZATION 4
2. EQUIPMENT REQUIRED FOR COMMISSIONING 5
2.1 Minimum equipment required 5

3. PRODUCT CHECKS 5
3.1 With the relay de-energized 5
3.1.1 Visual inspection 6
3.1.2 Insulation 6
3.1.3 External wiring 6
3.1.4 Auxiliary supply voltage (Vx) 6
3.2 With the relay energized 7
3.2.1 Light emitting diodes (LEDs) 7
3.2.2 Binary Inputs 8
3.2.3 Output Relays 8
3.2.4 Rear Communications Port (A) 9
3.2.5 USB communications port 9
3.2.6 Voltage inputs 10

4. SETTING CHECKS 11
4.1 Apply application-Specific Settings 11
4.2 Demonstrate correct relay operation 11
4.2.1 Overvoltage protection testing 11

5. FUNCTIONAL TESTS 16
6. COMMISSIONING TEST RECORD 18 CM
7. SETTING RECORD 22
V11V/EN CM v1.0 Commissioning

(CM) 8-4 VAMP 11V

INTRODUCTION
The VAMP 11V feeder protection relays are fully numerical in design, implementing all
protection and non-protection functions in software. The relays employ a high degree of
self-monitoring. The commissioning tests do not need to be as extensive as with non-
numeric electronic or electro-mechanical relays.
In the commissioning of numeric relays, it is only necessary to verify that the hardware is
functioning correctly and that the application-specific software settings have been applied to
the relay. It is considered unnecessary to test every function of the relay if the settings have
been verified by one of the following methods:

• Extracting the settings applied to the relay using appropriate setting software
(preferred method),

• Via the operator interface.


Unless previously agreed to the contrary, the customer will be responsible for determining
the application-specific settings applied to the relay and for testing of any scheme logic
applied by external wiring.
Blank commissioning test and setting records are provided at the end of this chapter for
completion as required.
BEFORE CARRYING OUT ANY WORK ON THE EQUIPMENT, THE
USER SHOULD BE FAMILIAR WITH THE CONTENTS OF THE SAFETY
GUIDE SFTY/4L M/E11 OR LATER ISSUE, OR THE SAFETY AND
TECHNICAL DATA SECTION OF THE TECHNICAL MANUAL AND
ALSO THE RATINGS ON THE EQUIPMENT RATING LABEL.

For safety reasons, no work must be carried out on the V11V until all
power sources to the unit have been disconnected.

1. SETTING FAMILIARIZATION
CM When commissioning a VAMP 11V relay for the first time, sufficient time should be allowed
to enable the user to become familiar with the method by which the settings are applied.
The Getting Started chapter (V11V/EN GS) contains a detailed description of the V11V relay.
Via the front panel all the settings can be changed (refer to Settings chapter V11V/EN ST of
this manual), LEDs and alarms reset, and fault and event records cleared. However, menu
cells with access levels higher than the default level will require the appropriate password to
be entered, before changes can be made.
Alternatively, if a portable PC is available together with suitable setting software (such as
MiCOM S1 Studio 5.1.0 or higher), the menu can be viewed a page at a time to display a full
column of data and text. This PC software also allows settings to be entered more easily,
saved to a file on disk for future reference or printed to produce a setting record. Refer to the
PC software user manual for details (refer to Getting Started V11V/EN GS). If the software is
being used for the first time, allow sufficient time to become familiar with its operation.
Commissioning V11V/EN CM v1.0

VAMP 11F (CM) 8-5

2. EQUIPMENT REQUIRED FOR COMMISSIONING


2.1 Minimum equipment required
Voltmeter test set with chronometer (range: 0 to 240 VAC).
Multimeter with suitable ac current range, and AC/DC voltage ranges of 0 – 250 V
respectively.
Continuity tester (if not included in multimeter).
Phasemeter.
Indicates the order of succession of phases.
Note: Modern test equipment may contain many of the above features in
one unit.

3. PRODUCT CHECKS
These product checks cover all aspects of the relay and should be carried out to ensure that
the unit has not been physically damaged prior to commissioning, that it is functioning
correctly and that all input quantity measurements are within the stated tolerances.
If the application-specific settings have been applied to the relay prior to commissioning, it is
advisable to make a copy of the settings to allow their restoration later. This could be done
by:

• Obtaining a setting file from the customer.

• Extracting the settings from the relay itself (this again requires a portable PC with
appropriate setting software)

• Manually creating a setting record. This could be done using a copy of the setting
record located at the end of this chapter to record the settings. As the relay’s menu is
scrolled through sequentially via the front panel user interface.
3.1 With the relay de-energized
The following group of tests should be carried out without powering the V11V.
WARNING: NEVER OPEN CIRCUIT THE SECONDARY CIRCUIT OF A CURRENT
TRANSFORMER SINCE THE HIGH VOLTAGE PRODUCED MAY BE
CM
LETHAL AND COULD DAMAGE INSULATION.
The voltage transformer connections must be isolated from the relay for these checks. If an
P991 test block is provided, the required isolation can easily be achieved by inserting test
plug type P992 which effectively open circuits all wiring routed through the test block.
Before inserting the test plug, reference should be made to the scheme (wiring) diagram to
ensure that this will not potentially cause damage or a safety hazard.
If a test block is not provided, the voltage transformer supply to the relay should be isolated
by means of the panel links or connecting blocks. Where means of isolating the auxiliary
supply and trip circuit (e.g. isolation links, fuses, MCB, etc.) are provided, these should be
used. If this is not possible, the wiring to these circuits will have to be disconnected and the
exposed ends suitably terminated to prevent them from being a safety hazard.
V11V/EN CM v1.0 Commissioning

(CM) 8-6 VAMP 11V

3.1.1 Visual inspection


The rating information given under the top access cover on the front of the relay
should be checked. Check that the relay being tested is correct for the protected
line/circuit. Ensure that the circuit reference and system details are entered into the
setting record sheet. Double-check the VT primary voltage rating, and be sure to
record the actual VT setting used.
Carefully examine the relay to check that no physical damage has occurred since
installation.
3.1.2 Insulation
Insulation resistance tests are only necessary during commissioning and if they have not
been performed during installation.
Isolate all wiring from the earth and test the insulation with an electronic or brushless
insulation tester at a dc voltage not exceeding 500V. Terminals of the grouped circuits
should be temporarily connected together.
The main groups of relay terminals are:
Voltage transformer circuits,
Auxiliary voltage supply
Binary control inputs (NA)
Relay contacts
EIA(RS)485 communication port (NA)

The insulation resistance should be greater than 100 MΩ at 500 V.


On completion of the insulation resistance tests, ensure all external wiring is correctly
reconnected to the relay.
3.1.3 External wiring
Check that the external wiring is correct when compared to the relevant relay and
scheme diagram. Ensure as far as practical that the phase sequence is as expected.
The relay diagram number appears on the rating label on the upper side of the case.
CM The connections should be checked against the scheme (wiring) diagram.
3.1.4 Auxiliary supply voltage (Vx)
The relay can be operated from either a dc only or AC/DC auxiliary supply depending on the
relay’s nominal supply rating. The incoming voltage must be within the operating range
specified in Table 1.
Without energizing the relay measure the auxiliary supply to ensure it is within the operating
range.

Nominal auxiliary voltage Vx 24 – 60 Vdc/ 24 – 60 Vac (50/60 Hz) (A and N)


(ordering options) 24 – 250 Vdc/ 24 – 240 Vac (50/60 Hz) (only L)
90 – 250 Vdc/ 90 – 240 Vac (50/60 Hz) (A and N)
Operating range 19 – 72 V (dc), 19 – 66 V (ac) (A and N)
19 – 300 V (dc), 19 – 265 V (ac) (only L)
72 – 300 V (dc), 72 – 265 V (ac) (A and N)
Tolerable AC ripple Up to 12% for a dc supply, per IEC 60255-11: 2008

Table 1: Operational range of auxiliary supply Vx

It should be noted that the relay can withstand an ac ripple of up to 12% of the upper rated
voltage on the dc auxiliary supply.
Commissioning V11V/EN CM v1.0

VAMP 11F (CM) 8-7

Do not energize the relay or interface unit using the battery charger with the battery
disconnected as this can irreparably damage the relay’s power supply circuitry.
Energize the relay only if the auxiliary supply is within the specified operating ranges. If a test
block is provided, it may be necessary to link across the front of the test plug to connect the
auxiliary supply to the relay.
Note: Vx nominal supply rating is common to auxiliary voltage supply and
binary control inputs
3.2 With the relay energized
The following group of tests verifies that the relay hardware and software are functioning
correctly and should be carried out while the V11V is powered.
MV isolators should be opened and the MV side should be connected to the earth to allow
safe operation of the CB.
3.2.1 Light emitting diodes (LEDs)
On power up the green LED should have lit up and stayed on indicating that the relay is
healthy. The relay has a non-volatile memory that remembers the state (on or off) of the
alarm, trip and, if configured to latch, LED indicators when the relay was last energized from
an auxiliary supply. Therefore these indicators may also lit up when the auxiliary supply is
applied.
Latching of LEDs can be configured via MiCOM S1 Studio 5.1.0 (or higher) setting software
(USB port) or manually by the front panel
Default configuration of LEDs (except Trip LED): without latching
Note: The above default configuration can be changed using the MiCOM S1
Studio 5.1.0 (or higher) setting software (USB port).
Trip LED is fixed to protection trip with latching.
The eight LEDs are on the front panel of the relay:

• The green Healthy LED indicates that the V11V is powered and no internal faults are
detected. A flashing LED indicates a hardware problem on the V11V. Not lit – V11V
has no power supply

• Red Trip LED: indicates that the time-delay of the protection element set to trip has CM
elapsed

• Yellow Alarm LED: indicates that the time-delay of the protection element set to Alarm
has elapsed or that non-protection functions as issued an Alarm signal. This LED can
be programmed as 3-7 LEDs too.
Note: By default Alarm LED is not configured to Alarm. It is necessary to configure
this LED for Alarm function via MiCOM S1 Studio 5.1.0 (or higher) setting software
(USB port) or manually by the front panel
After establishing the connection between PC and V11V via the USB port, the green Healthy
LED should be lit permanently (it means that the V11V is powered), even if V11V is not
connected to auxiliary voltage supply.
The remaining LEDs can be checked via the “LEDs Reset” function. This function can be
mapped to the L1 – L8 inputs.
All red LEDs should be lit within 1 s.
Default LEDs setting (both Setting Groups):
- LED2 – LED7: not configured.
V11V/EN CM v1.0 Commissioning

(CM) 8-8 VAMP 11V

3.2.2 Binary Inputs


This test checks that all the binary inputs on the relay are functioning correctly.
The binary inputs should be energized one at a time, see external connection diagrams
(V11V/EN IN) for terminal numbers.
The V11V is fitted with an LCD display which makes it possible to view the state of the binary
inputs, in the COMMISSIONING/Opto I/P Status menu cell. This information is also
available via the MiCOM S1 Studio 5.1.0 (or higher) Measurement Viewer software. Refer to
MiCOM S1 Studio 5.1.0 (or higher) user manual for details.
If it is not possible to use the Measurement Viewer software, it is necessary to check the
binary inputs by means of a functional test of the entire configuration.
Check that the correct nominal voltage and correct polarity are applied to the opto-inputs,
then connect the field voltage to the appropriate terminals for the input being tested.
Note: The binary inputs may be energized from an external DC auxiliary
supply (e.g. the substation battery) in some installations. Check that
this is not the case before connecting the field voltage, otherwise
damage to the relay may result. If an external 24/27 V, 30/34 V,
48/54 V, 110/125 V, 220/250 V supply is being used it will be directly
connected to the relay's optically isolated inputs. If an external supply
is being used then it must be energized for this test but only if it has
been confirmed that it is suitably rated with less than 12% AC ripple.
Default factory settings:
- L1 binary input (NA): not configured
- L2 binary input (NA): not configured
- L3 binary input(A): not configured
- L4 binary input(A): not configured
- L5 binary input (A): not configured
- L6 binary input (A): not configured
Reverse Input Logic indicates the low state of the Binary Input triggered by a
CM programmable function.
3.2.3 Output Relays
To check output contacts it is necessary to carry out a functional test of the entire
configuration.
Note: It should be ensured that thermal ratings of anything connected to the
output relays during the contact test procedure are not exceeded by
the associated output relay being operated for too long. It is therefore
advised that the time between application and removal of the contact
test is kept to the minimum.
Default factory settings:
- RL1 binary input (LNA): not configured
- RL2 binary input (LNA): not configured
- RL3 binary inputL(LNA): not configured
- RL4 binary input(NA): not configured
- RL5 binary input (NA): not configured
- RL6 binary input (A): not configured
- RL7 binary input (A): not configured
Commissioning V11V/EN CM v1.0

VAMP 11F (CM) 8-9

Reverse Output Logic means that after powering the V11V, n/o contacts are closed. Output
triggering via a programmable function opens the contacts (rest position).
3.2.4 Rear Communications Port (NA)
This test should only be performed where the relay is to be accessed from a remote location
and will vary depending on the communications standard adopted.
It is not the intention of the test to verify the operation of the complete system from the relay
to the remote location, just the relay’s rear communications port and any protocol converter
necessary.
3.2.4.1 IEC60870-5-103 (VDEW) communications
IEC60870-5-103/VDEW communication systems are designed to have a local Master Station
and this should be used to verify that the relay’s EIA(RS)485 port, is working.
The relay address and baud rate settings for EIA(RS)485 can be set by using local
communication via the USB port (setting software) or via the relay's front panel.
Default Factory Setting:
- Baud Rate: 19.2 bps
- Parity: No parity
- Stop Bits: one stop bit
- Data Bits: 8 (fixed)
Also ensure that the relay's address and baud rate settings in the application software are
the same as those set via the USB port.
Check that, using the Master Station, communications with the relay can be established.
3.2.4.2 MODBUS communications
Connect a portable PC running the appropriate MODBUS Master Station software to the
relay’s first rear EIA(RS)485 port via an EIA(RS)485 to EIA(RS)232 interface converter. The
terminal numbers for the relay's EIA(RS)485 port are up to 31.
The relay address, Parity and Baud Rate settings for EIA(RS)485 are set by using local
communication via USB port (MiCOM S1 Studio 5.1.0 (or higher) software).
CM
Default Factory Setting:
- Baud Rate: 19.2 bps
- Parity: No parity
- Stop Bits: one stop bit
- Data Bits: 8 (fixed)
Ensure that the relay's address and baud rate settings in the application software are the
same as those set via the USB port.
Check that communications with the relay can be established.
3.2.5 USB communications port
The USB port is used for local communications between a PC and the V11V.
Note: Max current necessary to supply V11V from USB port is 450mA. USB
standard offers 500mA for a one PC’s USB controller, so it is not
recommended to connect any additional devices to the same PC’s USB
controller. If the total power consumption from a one PC’s USB controller is
greater than 500mA, V11V can be in permanent rest (V11V display and the
green Healthy LED will be flashing)
The USB port integrates electronic boards only to allow communications with the V11V via
the HMI and USB interfaces. Input (binary and voltage) and Output boards are not supplied.
V11V/EN CM v1.0 Commissioning

(CM) 8-10 VAMP 11V

For local communications, the MiCOM S1 Studio 5.1.0 (or higher) setting software is used.
USB parameters (not settable in the V11V):
- Protocol: Modbus RTU
- Address: 1
- Baud Rate: 115.2 kbits/s
- Data Bits: 8
- Stop bit: 1
- Parity: None
3.2.6 Voltage inputs
This test verifies that the accuracy of voltage measurement is within the acceptable
tolerances.
The V11V measures the fundamental components of voltage.
Apply a voltage equal to the rating of the line voltage transformer secondary winding to each
voltage transformer input of the corresponding rating, in turn (see external connection
diagram (V11V/EN IN) for appropriate terminal numbers), checking its magnitude using a
multimeter/test set readout. The corresponding reading can then be checked in the
MEASUREMENT column of the menu or via the MiCOM S1 Studio 5.1.0 (or higher)
/Measurement Viewer connected to the V11V via USB port. Refer to the PC software user
manual for details.
If MiCOM S1 Studio 5.1.0 (or higher) is not available, it is necessary to test the protection
stages to measure the accuracy of analogue inputs.
Measuring accuracy of the relay:
Reference Conditions:
Sinusoidal signals with nominal frequency fn total harmonic distortion = 2 %, ambient
temperature 20 °C and nominal auxiliary voltage Vx.
Deviation relative to the relevant nominal value under reference conditions.

CM Operating Data

Voltage/Residual voltage: ±2% at Un

Frequency: ±10mHz
Commissioning V11V/EN CM v1.0

VAMP 11F (CM) 8-11

4. SETTING CHECKS
The setting checks ensure that all of the application-specific relay settings (i.e. the relay’s
functions), for the particular installation, have been correctly applied to the relay.
Note: The trip circuit should remain isolated during these checks to prevent
accidental operation of the associated circuit breaker.
4.1 Apply application-Specific Settings
There are two methods of applying the settings to the relay:
Downloading them from a pre-prepared setting file to the relay using a portable PC running
the MiCOM S1 Studio 5.1.0 (or higher) support software. Communication between the PC
and the V11V is done via the relay’s USB front port, located at the bottom of front panel, or
rear communications port. This method is preferred for transferring function settings as it is
much faster and there is less margin for error.
If a setting file has been created for the particular application and is available on an external
memory disk, this will further reduce the commissioning time.
Enter them manually via the relay’s operator interface.
Application notes for the setting values are given in Application Notes chapter V11V/EN AP
of this manual.
4.2 Demonstrate correct relay operation
The above tests have already demonstrated that the relay is within calibration, thus the
purpose of these tests is as follows:

− To determine that the primary protection functions of the relay, overvoltage, earth-fault
etc. can trip according to the correct application settings.

− by monitoring the response to a selection of fault injections.

4.2.1 Overvoltage protection testing


This test, performed on stage 1 of the overvoltage protection function, demonstrates that the
relay is operating correctly at the application-specific settings.
4.2.1.1 Connection and preliminaries CM
The testing voltage for 3Up-n connection is fed via terminals: C9-C10, C11-C12, and C13-
C14 connected to VTs. The type of connection is shown in Figure 1. The external connection
diagram is also available for the V11V front panel.
Connect the auxiliary voltage supply to the V11V's terminals A1 and A2.
Connect the trip output RL1 to trip circuit of CB so that its operation will trip the test set and
stop the timer.
The timer should be compatible with the RL1 output.
Connect the voltage output of the test set to phase “A” of the relay voltage transformer input
(terminals C9 and C10).
Ensure that the timer starts when the current is applied to the relay.
V11V/EN CM v1.0 Commissioning

(CM) 8-12 VAMP 11V

CM

Figure 1: Model A Connection Diagram


Commissioning V11V/EN CM v1.0

VAMP 11F (CM) 8-13

CM

Figure 2: V11V Model N Connection Diagram


V11V/EN CM v1.0 Commissioning

(CM) 8-14 VAMP 11V

Figure 3: V11V Model L Connection Diagram

CM
Commissioning V11V/EN CM v1.0

VAMP 11F (CM) 8-15

4.2.1.2 Perform the test


Ensure that the timer is reset.
Apply to the relay a voltage of twice the setting for V> (refer to chapter V11V/EN ST of this
manual) and make a note of the time displayed when the chronometer stops.
WARNING: During injected voltage from voltage source in secondary side,
remember about separate secondary side VT – possibility induction
voltage in primary side of VT .

4.2.1.3 Check the Operating Time


Check that the operating time recorded by the timer is within the range shown in Table 2.
Notes: Except for the definite time characteristic, the operating times given in
Table 2 are for a time multiplier or time dial setting of 1. Therefore, to
obtain the operating time at other time multiplier or time dial settings,
the time given in Table 2 must be multiplied by the setting for IDMT
characteristics.
For all characteristics, allowance must be made for the accuracy of
the test equipment being used.

Operating Time at Twice Voltage Setting and Time


Characteristic Multiplier/Time Dial Setting of 1.0
Nominal (Seconds) Range (Seconds)
DT tU> Time Delay Setting Setting ±5%
IEC S Inverse 10.03 9.28 – 11.78
IEC V Inverse 13.50 12.49 – 14.51
IEC E Inverse 26.67 24.67 – 29.67
UK LT Inverse 120.00 111.00 – 129.00
UK ST Inverse 1.78 1.65 – 1.91
IEEE M Inverse 3.8 3.52 – 4.08
IEEE V Inverse 7.03 6.51 – 7.55
CM
IEEE E Inverse 9.52 8.81 – 10.23
US Inverse (CO8) 2.16 2.00 – 2.32
US Inverse (CO2 P40) 12.12 11.22 – 13.02
RI Inverse 4.52 4.19 – 4.86

Table 2: Characteristic Operating Times for U>


Reconfigure to test a phase B fault. Repeat the test in section 1, this time ensuring that the
breaker trip output relative to phase B operation trips correctly. Record the tripping time for
phase B. Repeat for phase C fault.
V11V/EN CM v1.0 Commissioning

(CM) 8-16 VAMP 11V

5. FUNCTIONAL TESTS
VAMP 11V has special functions for this purpose available in COMMISIONING column.
In Model A the special function Maintenance Mode is available for more comfortable testing
of the relay.

Note: If Maintenance Mode is not selected all test cells are hidden in V11V menu.
It is possible to set following Maintenance mode options (settings):

• “No” - Maintenance mode is disabled. All window cells below are hidden
(Maintenance mode is the latest cell in COMMISIONING column)

• “Yes” - Maintenance mode is enabled. In this mode all test cells in


COMMISIONING column are shown. During tests outputs are energized.

• “Yes,outp.block” - Maintenance mode is enabled and all test cells in


COMMISIONING column are shown. In this mode, the high state of output functions
are ignored (control of outputs are blocked).
This option allows the user to check the operation of the protection functions
without actually sending any external command (Tripping or signalling).
Depends on the rear protocol selected in menu, transmission of information to SCADA is
blocked (Modbus RTU) or sent (IEC 103) with additional information to know that V11V is in
Maintenance mode (refer to Communication chapter and EN 60870-5-103 standard).
Changing of setting from “No” to “Yes,….” from the front panel activate this mode for
10 minutes only. After this time the option is automatically switched to “No”.
The selection of the maintenance mode is possible by logic input (the level), control
command (rear or front port), or by front panel interface. The maintenance mode is
terminated by:

• Low state of logic input assigned to Maintenance mode function,

• Control command which activate this mode (rear command or setting: “Yes,….”)
and by turning off the power supply.

CM Note: Maintenance rear command is available in Modbus protocol only

Maintenance Mode
1: Yes

When this menu is activated (set to YES: “Yes” or “Yes,outp.block”), the Alarm led is lit.

In “Yes,outp.block” case, all the output contacts are blocked, and no command can be
issued to these contacts, even if a protection threshold associated with one of these output
contacts has been crossed. If a protection threshold is crossed, all associated LEDs will be
ON, even the TRIP LED, if protection element is set to Trip.
The commissioning cells allow the user to check the external wiring to the relay's output
contacts. This function is available after activation of Maintenance mode. To do this, the
user has only to set to 1 the desired output contact's corresponding bit, and this will close the
contact and allow the continuity of the wiring to be checked.

Test 7654321
Pattern 0000000

In the cell below, the contact test time can be set:

Contact Test
Time 001.00s
Commissioning V11V/EN CM v1.0

VAMP 11F (CM) 8-17

If the outputs for test are selected and Time for output closing is set, the closing command
can be executed in this cell:

Test output
0: no operation

To execute the test, press OK key, press the or key to select 1: Apply test and
confirm action by OK. The contact will be closed for the duration of the Contact Test Time
pulse.
The next commissioning cells, which appears in Maintenance mode, allows the user to
check the functional output configuration of the V11V. To do this, the user has only to select
which protection element will be triggered, and this will close the contact assigned to this
protection element and allow the continuity of the wiring to be checked.

Functional Test
0: V>

In the cell below the end of the functional test can be configured:

Functional Test
End 0: CB trip

The following options are possible:


- 0: CB trip – after triggering the functional test, the test is interrupted after trip command.
- 1: Time – the protection element will be triggered for the duration of the pulse time.
If the 1: Time option is selected it is necessary to set the pulse length:

Contact Test
Time 001.00s

The next cell is used for functional test execution:

Functional Test
CTRL: no operation

To execute this test, press the OK key, press the or key to select 1: Operate and
CM
confirm action by pressing OK. The contact will be closed for the duration of the Contact
Test Time pulse.
V11V/EN CM v1.0 Commissioning

(CM) 8-18 VAMP 11V

6. COMMISSIONING TEST RECORD

Date: Engineer:
Station: Circuit:
System Frequency: Hz

V11V Front Plate Information

Overvoltage protection relay VAMP 11V


Model number
Serial number

Test Equipment Used


This section should be completed to allow future identification of protective devices that have
been commissioned using equipment, that is later found to be defective or incompatible, but
may not be detected during the commissioning procedure.

Model:
Injection test set
Serial No:

Model:
Insulation tester
Serial No:

Type:
Setting software:
Version:

CM
Commissioning V11V/EN CM v1.0

VAMP 11F (CM) 8-19

Delete as appropriate
Have all relevant safety instructions been followed? Yes No

1. Product Checks
1.1 With the relay de-energized
1.1.1 Visual inspection
1.1.1.1 Relay damaged? Yes No
1.1.1.2 Rating information correct for installation? Yes No

Yes No
1.1.2 Insulation resistance >100MΩ at 500V dc
Not Tested
1.1.3 External wiring
1.1.3.1 Wiring checked against diagram? Yes No

1.1.4 Measured auxiliary voltage supply V ac

CM
V11V/EN CM v1.0 Commissioning

(CM) 8-20 VAMP 11V

1.2 With the relay energized

1.2.1 Light-emitting diodes and Watchdog Contact


Connect the auxiliary voltage supply to terminals A1 and
1.2.1.1 A2. Are the green Healthy LED and the WD output Yes No
contact (A3-A5) working?
Establish connection between PC and V11V via USB
1.2.1.2 Yes No
port. Green Healthy LED working?
Reset LEDs by pressing the C key on the V11V's front
1.2.1.3 Yes No
panel. Red LED flashing rapidly?

1.2.2 Inputs
Auxiliary voltage for binary control inputs:
1.2.2.1 Value measured (see: COMMISSIONING/Opto I/P V dc
Status window of menu) (NA)
1.2.2.2 L1 binary input working? (NA) Yes No
1.2.2.3 L2 binary input working? (NA) Yes No
1.2.2.4 L3 binary input working? (A) Yes No
1.2.2.5 L4 binary input working? (A) Yes No
1.2.2.6 L5 binary input working? (A) Yes No
1.2.2.7 L6 binary input working? (A) Yes No

Outputs (for tests in model B and E, COMMISSIONING/


1.2.3
Test outputs cell can be used)
1.2.3.1 Output Relays
1.2.3.1.1 Relay 1 working? (LNA) Yes No
1.2.3.1.2 Relay 2 working? (LNA) Yes No
CM 1.2.3.1.3 Relay 3 working? (LNA) Yes No
1.2.3.1.4 Relay 4 working? (NA) Yes No
1.2.3.1.5 Relay 5 working? (NA) Yes No
1.2.3.1.6 Relay 6 working? (A) Yes No
1.2.3.1.7 Relay 7 working? (A) Yes No
1.2.3.1.7 Relay WD working? (LNA) Yes No
Close CB, after which apply voltage above setting value.
1.2.3.2 Yes No
CB has opened?

Communications between PC and MiCOM S1 Studio Yes No


1.2.4
5.1.0 (or higher) setting software established?

2. Setting Checks

2.1 Protection function timing tested? Yes No


Applied voltage V
Expected operating time s
Commissioning V11V/EN CM v1.0

VAMP 11F (CM) 8-21

Measured operating time s

3. Final Checks
All test equipment, leads, shorts and test blocks removed
3.1 Yes No
safely?
Yes No
3.2 Disturbed customer wiring re-checked?
N/A
3.3 All commissioning tests disabled? Yes No
3.4 Records reset (via software)? Yes No

COMMENTS #

(# Optional, for site observations or utility-specific notes).


CM

Commissioning Engineer Customer Witness

Date: Date:
V11V/EN CM v1.0 Commissioning

(CM) 8-22 VAMP 11V

7. SETTING RECORD
Date: Engineer:
Station: Circuit:
System Frequency: Hz
VT Ratio (tap in use): / V

Front Plate Information

Overvoltage protection relay VAMP 11V


Model number
Serial number

Delete as appropriate

Column Identification of Relay


Firmware version
OP PARAMETERS
Hardware version

Column Global Setting Data


0: English 1: German
2: French 3: Spanish
Language
4: Russian 5: Turkish
6: Regional
0: Meas. P-P[V] 1: Meas. P-P[Un]
Default Display 2: Meas. P-N[V] 3: Meas. P-N[Un]
4: CB Control 5: L/R Status
CM GLOBAL
SETTINGS/ 0: Manual only 1: Protect.Start
LOC LEDs Reset
2: Close Command
0: Manual only 1: Protect.Start
Trip Info Reset
2: Close Command
Latched Alarm Reset 0: Self 1: Manual
Nominal Frequency 0: 50Hz 1: 60Hz
Control Keys Confirm. 0: No 1:Yes

GLOBAL 1: One Group


Number of Groups
SETTINGS/ 2: Two Groups
SETTING
GROUP Setting Group 0: Group 1 1: Group 2
SELECT
t Change Settings G1 G2 s
Line VT primary V
Line VT Sec V
GLOBAL E/Gnd VT primary V
SETTINGS/
CT RATIO E/Gnd VT Sec V
0: 3Upn 1: 3Upn+UN
VT connections
2: 2Upp+UN 3: 3Upp+UN
Commissioning V11V/EN CM v1.0

VAMP 11F (CM) 8-23

Column Global Setting Data


Prot. Config. V>; V2> 0: P-P 1: P-N
Prot. Config. V<; V1< 0: P-P 1: P-N
tOpen pulse min s
GLOBAL tClose Pulse s
SETTINGS/
CIRCUIT Time Delay for Close s
BREAKER (A) tCB FLT Ext. Sign. s
Remote CTRL Mode 0:Remote only 1:Remote+Local

GLOBAL IDMT Interlock by DMT 0:No 1:Yes


SETTINGS/
O/V
[27] Hysteresis
ADVANCED [59] Hysteresis
GLOBAL Prot. Freq. Blocking V
SETTINGS/
[81] Inhibit Blocking [81]> Hz/s
ADVANCED
SETTINGS (A) Meas. Valid. Nb. Of Cycle

Relay Address RS485


0: Modbus RTU
Protocol
1: IEC103
GLOBAL
4800 9600 19200
SETTINGS/ Baud Rate RS485
COMMUNICATI 38400 57600 115200
ON (A) 0: No parity 1: Odd parity
Parity RS485
2: Even parity
0: 1 stop bit
StopBits RS485
1: 2 stop bits
Pre-Time s
GLOBAL
SETTINGS/ Post Trip Time s
DISTURBANCE
RECORDER
(A)
Disturbance Rec.Trig. 0: on Inst. 1: on Trip CM
Max Record Time s
V11V/EN CM v1.0 Commissioning

(CM) 8-24 VAMP 11V

OVERVOLTAGE G1
SETTING GROUP 1/ PROTECTION G1/
Settings
PHASE O/V [59] G1
0: Disabled
1: OR Trip
2: OR Alarm
3: AND Trip
1 V> ? 4: AND Alarm
5: OR Trip/52a
6: OR Alarm/52a
7: AND Trip/52a
8: AND Alarm/52a
2 V> Threshold V
3 V> Delay Type
4 tV>/TMS/TD s
0: DMT
5 V> Reset Delay Type
1: IDMT
6 V> DMT tReset s
0: Disabled
1: OR Trip
2: OR Alarm
3: AND Trip
7 V>> ? 4: AND Alarm
5: OR Trip/52a
6: OR Alarm/52a
7: AND Trip/52a
8: AND Alarm/52a
8 V>> Threshold V
CM 9 tV>> s
0: Disabled
1: OR Trip
2: OR Alarm
3: AND Trip
10 V>>> ? 4: AND Alarm
5: OR Trip/52a
6: OR Alarm/52a
7: AND Trip/52a
8: AND Alarm/52a
11 V>>> Threshold V
12 tV>>> s
Commissioning V11V/EN CM v1.0

VAMP 11F (CM) 8-25

UNDERVOLTAGE G1
SETTING GROUP 1/ PROTECTION G1/
Settings
PHASE U/V [27] G1
0: Disabled
1: OR Trip
2: OR Alarm
3: AND Trip
1 V< ? 4: AND Alarm
5: OR Trip/52a
6: OR Alarm/52a
7: AND Trip/52a
8: AND Alarm/52a
2 V< Threshold V
3 V< Delay Type
4 tV</TMS/TD s
0: DMT
5 V< Reset Delay Type
1: IDMT
6 V< DMT tReset s
0: Disabled
1: OR Trip
2: OR Alarm
3: AND Trip
7 V<< ? 4: AND Alarm
5: OR Trip/52a
6: OR Alarm/52a
7: AND Trip/52a
8: AND Alarm/52a
8 V<< Threshold V
9 tV<< s CM
0: Disabled
1: OR Trip
2: OR Alarm
3: AND Trip
10 V<<< ? 4: AND Alarm
5: OR Trip/52a
6: OR Alarm/52a
7: AND Trip/52a
8: AND Alarm/52a
11 V<<< Threshold V
12 tV<<< s
V11V/EN CM v1.0 Commissioning

(CM) 8-26 VAMP 11V

POSITIVE SEQUENCE UNDERVOLTAGE G1 (A)


SETTING GROUP 1/ PROTECTION G1/
Settings
POSITIVE SEQUENCE U/V G1 [27D]
0: Disabled
1: Trip
1 V1< ? 2: Alarm
3: Trip/52a
4: Alarm/52a
2 V1< Threshold V
3 V1< Delay Type
4 tV1</TMS/TD s
0: DMT
5 V1< Reset Delay Type
1: IDMT
6 V1< DMT tReset s
0: Disabled
1: Trip
7 V1<< ? 2: Alarm
3: Trip/52a
4: Alarm/52a
8 V1<< Threshold V
9 tV1<< s

CM
Commissioning V11V/EN CM v1.0

VAMP 11F (CM) 8-27

NEGATIVE SEQUENCE OVERVOLTAGE G1 (NA)


SETTING GROUP 1/ PROTECTION G1/
Settings
NEGATIVE SEQUENCE O/V G1
0: Disabled
1: Trip
1 V2> ? 2: Alarm
3: Trip/52a
4: Alarm/52a
2 V2> Threshold V
3 V2> Delay Type
4 tV2>/TMS/TD s
0: DMT
5 V2> Reset Delay Type
1: IDMT
6 V2> DMT tReset s
0: Disabled
1: Trip
7 V2>> ? 2: Alarm
3: Trip/52a
4: Alarm/52a
8 V2>> Threshold V
9 tV2>> s

CM
V11V/EN CM v1.0 Commissioning

(CM) 8-28 VAMP 11V

EARTH FAULT OVERVOLTAGE G1


SETTING GROUP 1/ PROTECTION G1/
Settings
E/GND FAULT O/V [59] G1
0: Disabled
1: Trip (measured) (NA)
2: Alarm (measured) (NA)
1 VN> ?
1: Trip (measured) (NA)
3: Trip (Ua+Ub+Uc)
4: Alarm (Ua+Ub+Uc)
2 VN> Threshold V
3 VN> Delay Type
4 tVN>/TMS/TD s
0: DMT
5 VN> Reset Delay Type
1: IDMT
6 VN> DMT tReset s
0: Disabled
1: OR Trip
2: OR Alarm
3: AND Trip
7 VN>> ? 4: AND Alarm
5: OR Trip/52a
6: OR Alarm/52a
7: AND Trip/52a
8: AND Alarm/52a
8 VN>> Threshold V
9 tVN>> s
0: Disabled
1: OR Trip
CM 2: OR Alarm
3: AND Trip
10 VN>>> ? 4: AND Alarm
5: OR Trip/52a
6: OR Alarm/52a
7: AND Trip/52a
8: AND Alarm/52a
11 VN>>> Threshold V
12 tVN>>> s
Commissioning V11V/EN CM v1.0

VAMP 11F (CM) 8-29

FREQUENCY [81O/81U] G1 (A)


SETTING GROUP 1/ PROTECTION G1 / FREQUENCY
Settings
[81O/81U] G1
0: Disabled
1: f> Trip
1 f1 ? 2: f> Alarm
3: f< Trip
4: f< Alarm
2 f1 Threshold Hz
3 tf1 s
0: Disabled
1: f> Trip
4 f2 ? 2: f> Alarm
3: f< Trip
4: f< Alarm
5 f2 Threshold Hz
6 tf2 s
0: Disabled
1: f> Trip
7 f3 ? 2: f> Alarm
3: f< Trip
4: f< Alarm
8 f3 Threshold Hz
9 tf3 s
0: Disabled
1: f> Trip
10 f4 ? 2: f> Alarm
3: f< Trip
4: f< Alarm
CM
11 f4 Threshold Hz
12 tf4 s
0: Disabled
1: f> Trip
13 f5 ? 2: f> Alarm
3: f< Trip
4: f< Alarm
14 f5 Threshold Hz
15 tf5 s
0: Disabled
1: f> Trip
16 f6 ? 2: f> Alarm
3: f< Trip
4: f< Alarm
17 f6 Threshold Hz
18 tf6 s
V11V/EN CM v1.0 Commissioning

(CM) 8-30 VAMP 11V

AUX TIMERS G1 (NA)


SETTING GROUP 1/ PROTECTION G1 / AUX TIMERS G1 Group 1 Settings
0: Disabled
1 AUX1 ? (NA) 1: Trip
2: Alarm
2 tAUX1 s
0: Disabled
3 AUX2 ? (NA) 1: Trip
2: Alarm
4 tAUX2 s
0: Disabled
5 AUX3 ? (A) 1: Trip
2: Alarm
6 tAUX3 s

SETTING GROUP 1/ INPUTS CONFIGURATION G1


INPUT
CONFIGURATION L6 L5 L4 L3 L2 L1
G1 A A A A NA NA
Reverse Input
1
Logic
2 Mainten. Mode
3 Reset Latch Sign
4 Reset Latchd Out
5 Block. tV> (NA)

CM 6 Block. tV>> (NA)


Block. tV>>>
7
(NA)
8 Block. tV< (NA)
9 Block. tV<< (NA)
Block. tV<<<
10
(NA)
11 Block. tV1< (A)
12 Block. tV1<< (A)
13 Block. tV2> (NA)
Block. tV2>>
14
(NA)
15 Block. tVN> (NA)
Block. tVN>>
16
(NA)
Block. tVN>>>
17
(NA)
18 Block. f1 (A)
19 Block. f2 (A)
Commissioning V11V/EN CM v1.0

VAMP 11F (CM) 8-31

SETTING GROUP 1/ INPUTS CONFIGURATION G1


INPUT
CONFIGURATION L6 L5 L4 L3 L2 L1
G1 A A A A NA NA
20 Block. f3 (A)
21 Block. f4 (A)
22 Block. f5 (A)
23 Block. f6 (A)
24 AUX1(NA)
25 AUX2 (NA)
26 AUX2 (A)
27 AUX3 (A)
28 AUX4 (A)
29 AUX5 (A)
CB Status 52A
30
(A)
CB Status 52B
31
(A)
Setting group 2
32
(NA)
33 Manual Close (A)
34 Manual Trip (A)
35 VTS (A)
Start Distur. R.
36
(A)
Local CTRL
37
Mode (A)
38 Time Synchr. (A) CM
V11V/EN CM v1.0 Commissioning

(CM) 8-32 VAMP 11V

OUTPUT RELAYS CONFIGURATION G1


SETTING GROUP 1/
OUTPUT RELAY WD RL7 RL6 RL5 RL4 RL3 RL2 RL1
CONFIGURATION G1
LNA A A NA NA LNA LNA LNA

1 Latched outputs

Reverse outp.
2
logic
3 Protect. Trip
4 Prot.Trip pulse
Trip CB Order
5
(A)
Close CB Order
6
(A)
7 Alarm
8 Start V>
9 Start V>>
10 Start V>>>
11 Start V<
12 Start V<<
13 Start V<<<
14 Start V1< (A)
15 Start V1<< (A)
16 Start V2> (NA)
17 Start V2>> (NA)
18 Start VN>
CM
19 Start VN>>
20 Start VN>>>
21 Start f1 (A)
22 Start f2 (A)
23 Start f3 (A)
24 Start f4 (A)
25 Start f5 (A)
26 Start f6 (A)
27 AUX1 (NA)
28 AUX2 (NA)
29 AUX3 (A)
30 AUX4 (A)
31 AUX5 (A)
32 tV>
33 tV>>
34 tV>>>
Commissioning V11V/EN CM v1.0

VAMP 11F (CM) 8-33

35 tV<
36 tV<<
37 tV<<<
38 tV1< (A)
39 tV1<< (A)
40 tV2> (NA)
41 tV2>> (NA)
42 CB Alarm (AE)
43 tVN>
44 tVN>>
45 tVN>>>
46 tf1 (A)
47 tf2 (A)
48 tf3 (A)
49 tf4 (A)
50 tf5 (A)
51 tf6 (A)
52 tAUX1 (NA)
53 tAUX2 (NA)
54 tAUX3 (A)
55 CB Alarm (A)
tCB FLT Ext.Sign
56
(A)
Setting Group 1
57
(NA)
58 tVTS (A) CM
59 fout (A)
V11V/EN CM v1.0 Commissioning

(CM) 8-34 VAMP 11V

LEDs CONFIGURATION G1
SETTING GROUP 1/
LED2 LED3 LED4 LED5 LED6 LED7
LEDs CONFIGURATION G1
1 Latched LEDs
2 Alarm
3 Start V>
4 Start V>>
5 Start V>>>
6 Start V<
7 Start V<<
8 Start V<<<
9 Start V1< (A)
10 Start V1<< (A)
11 Start V2> (NA)
12 Start V2>> (NA)
13 Start VN>
14 Start VN>>
15 Start VN>>>
16 Start f1 (A)
17 Start f2 (A)
18 Start f3 (A)
19 Start f4 (A)
20 Start f5 (A)
21 Start f6 (A)
22 AUX1 (NA)
CM
23 AUX2 (NA)
24 AUX3 (A)
25 AUX4 (A)
26 AUX5 (A)
27 tV>
28 tV>>
29 tV>>>
30 tV<
31 tV<<
32 tV<<<
33 tV1< (A)
34 tV1<< (A)
35 tV2> (NA)
36 tV2>> (NA)
37 CB Alarm (AE)
38 tVN>
Commissioning V11V/EN CM v1.0

VAMP 11F (CM) 8-35

LEDs CONFIGURATION G1
SETTING GROUP 1/
LED2 LED3 LED4 LED5 LED6 LED7
LEDs CONFIGURATION G1
39 tVN>>
40 tVN>>>
41 tf1 (A)
42 tf2 (A)
43 tf3 (A)
44 tf4 (A)
45 tf5 (A)
46 tf6 (A)
47 tAUX1 (NA)
48 tAUX2 (NA)
49 tAUX3 (A)
50 CB Alarm (A)
51 tCB FLT Ext.Sign (A)
52 Setting Group 1 (NA)
53 tVTS (A)
54 fout (A)

CM
V11V/EN CM v1.0 Commissioning

(CM) 8-36 VAMP 11V

OVERVOLTAGE G2
SETTING GROUP 2/ PROTECTION G2/
Settings
PHASE O/V [59] G2
0: Disabled
1: OR Trip
2: OR Alarm
3: AND Trip
1 V> ? 4: AND Alarm
5: OR Trip/52a
6: OR Alarm/52a
7: AND Trip/52a
8: AND Alarm/52a
2 V> Threshold V
3 V> Delay Type
4 tV>/TMS/TD s
0: DMT
5 V> Reset Delay Type
1: IDMT
6 V> DMT tReset s
0: Disabled
1: OR Trip
2: OR Alarm
3: AND Trip
7 V>> ? 4: AND Alarm
5: OR Trip/52a
6: OR Alarm/52a
7: AND Trip/52a
8: AND Alarm/52a
8 V>> Threshold V
CM 9 tV>> s
0: Disabled
1: OR Trip
2: OR Alarm
3: AND Trip
10 V>>> ? 4: AND Alarm
5: OR Trip/52a
6: OR Alarm/52a
7: AND Trip/52a
8: AND Alarm/52a
11 V>>> Threshold V
12 tV>>> s
Commissioning V11V/EN CM v1.0

VAMP 11F (CM) 8-37

UNDERVOLTAGE G2
SETTING GROUP 2/ PROTECTION G2/
Settings
PHASE U/V [27] G2
0: Disabled
1: OR Trip
2: OR Alarm
3: AND Trip
1 V< ? 4: AND Alarm
5: OR Trip/52a
6: OR Alarm/52a
7: AND Trip/52a
8: AND Alarm/52a
2 V< Threshold V
3 V< Delay Type
4 tV</TMS/TD s
0: DMT
5 V< Reset Delay Type
1: IDMT
6 V< DMT tReset s
0: Disabled
1: OR Trip
2: OR Alarm
3: AND Trip
7 V<< ? 4: AND Alarm
5: OR Trip/52a
6: OR Alarm/52a
7: AND Trip/52a
8: AND Alarm/52a
8 V<< Threshold V
9 tV<< s CM
0: Disabled
1: OR Trip
2: OR Alarm
3: AND Trip
10 V<<< ? 4: AND Alarm
5: OR Trip/52a
6: OR Alarm/52a
7: AND Trip/52a
8: AND Alarm/52a
11 V<<< Threshold V
12 tV<<< s
V11V/EN CM v1.0 Commissioning

(CM) 8-38 VAMP 11V

POSITIVE SEQUENCE UNDERVOLTAGE G2 (A)


SETTING GROUP 2/ PROTECTION G2/
Settings
POSITIVE SEQUENCE U/V G2 [27D]
0: Disabled
1: Trip
1 V1< ? 2: Alarm
3: Trip/52a
4: Alarm/52a
2 V1< Threshold V
3 V1< Delay Type
4 tV1</TMS/TD s
0: DMT
5 V1< Reset Delay Type
1: IDMT
6 V1< DMT tReset s
0: Disabled
1: Trip
7 V1<< ? 2: Alarm
3: Trip/52a
4: Alarm/52a
8 V1<< Threshold V
9 tV1<< s

CM
Commissioning V11V/EN CM v1.0

VAMP 11F (CM) 8-39

NEGATIVE SEQUENCE OVERVOLTAGE G2 (NA)


SETTING GROUP 2/ PROTECTION G2/
Settings
NEGATIVE SEQUENCE O/V G2
0: Disabled
1: Trip
1 V2> ? 2: Alarm
3: Trip/52a
4: Alarm/52a
2 V2> Threshold V
3 V2> Delay Type
4 tV2>/TMS/TD s
0: DMT
5 V2> Reset Delay Type
1: IDMT
6 V2> DMT tReset s
0: Disabled
1: Trip
7 V2>> ? 2: Alarm
3: Trip/52a
4: Alarm/52a
8 V2>> Threshold V
9 tV2>> s

CM
V11V/EN CM v1.0 Commissioning

(CM) 8-40 VAMP 11V

EARTH FAULT OVERVOLTAGE G2


SETTING GROUP 2/ PROTECTION G2/
Settings
E/GND FAULT O/V [59] G2
0: Disabled
1: Trip (measured) (NA)
2: Alarm (measured) (NA)
1 VN> ?
1: Trip (measured) (NA)
3: Trip (Ua+Ub+Uc)
4: Alarm (Ua+Ub+Uc)
2 VN> Threshold V
3 VN> Delay Type
4 tVN>/TMS/TD s
0: DMT
5 VN> Reset Delay Type
1: IDMT
6 VN> DMT tReset s
0: Disabled
1: OR Trip
2: OR Alarm
3: AND Trip
7 VN>> ? 4: AND Alarm
5: OR Trip/52a
6: OR Alarm/52a
7: AND Trip/52a
8: AND Alarm/52a
8 VN>> Threshold V
9 tVN>> s
0: Disabled
1: OR Trip
CM 2: OR Alarm
3: AND Trip
10 VN>>> ? 4: AND Alarm
5: OR Trip/52a
6: OR Alarm/52a
7: AND Trip/52a
8: AND Alarm/52a
11 VN>>> Threshold V
12 tVN>>> s
Commissioning V11V/EN CM v1.0

VAMP 11F (CM) 8-41

FREQUENCY [81O/81U] G2 (A)


SETTING GROUP 2/ PROTECTION G2 / FREQUENCY
Settings
[81O/81U] G2
0: Disabled
1: f> Trip
1 f1 ? 2: f> Alarm
3: f< Trip
4: f< Alarm
2 f1 Threshold Hz
3 tf1 s
0: Disabled
1: f> Trip
4 f2 ? 2: f> Alarm
3: f< Trip
4: f< Alarm
5 f2 Threshold Hz
6 tf2 s
0: Disabled
1: f> Trip
7 f3 ? 2: f> Alarm
3: f< Trip
4: f< Alarm
8 f3 Threshold Hz
9 tf3 s
0: Disabled
1: f> Trip
10 f4 ? 2: f> Alarm
3: f< Trip
4: f< Alarm
CM
11 f4 Threshold Hz
12 tf4 s
0: Disabled
1: f> Trip
13 f5 ? 2: f> Alarm
3: f< Trip
4: f< Alarm
14 f5 Threshold Hz
15 tf5 s
0: Disabled
1: f> Trip
16 f6 ? 2: f> Alarm
3: f< Trip
4: f< Alarm
17 f6 Threshold Hz
18 tf6 s
V11V/EN CM v1.0 Commissioning

(CM) 8-42 VAMP 11V

AUX TIMERS G2 (NA)


SETTING GROUP 2/ PROTECTION G2 / AUX TIMERS G2 Group 1 Settings
0: Disabled
1 AUX1 ? (NA) 1: Trip
2: Alarm
2 tAUX1 s
0: Disabled
3 AUX2 ? (NA) 1: Trip
2: Alarm
4 tAUX2 s
0: Disabled
5 AUX3 ? (A) 1: Trip
2: Alarm
6 tAUX3 s

SETTING GROUP 2/ INPUTS CONFIGURATION G2


INPUT
CONFIGURATION L6 L5 L4 L3 L2 L1
G2 A A A A NA NA
Reverse Input
1
Logic
2 Mainten. Mode
3 Reset Latch Sign
4 Reset Latchd Out
5 Block. tV> (NA)

CM 6 Block. tV>> (NA)


Block. tV>>>
7
(NA)
8 Block. tV< (NA)
9 Block. tV<< (NA)
Block. tV<<<
10
(NA)
11 Block. tV1< (A)
12 Block. tV1<< (A)
13 Block. tV2> (NA)
Block. tV2>>
14
(NA)
15 Block. tVN> (NA)
Block. tVN>> N
16
(A)
Block. tVN>>>
17
(NA)
18 Block. f1 (A)
19 Block. f2 (A)
Commissioning V11V/EN CM v1.0

VAMP 11F (CM) 8-43

SETTING GROUP 2/ INPUTS CONFIGURATION G2


INPUT
CONFIGURATION L6 L5 L4 L3 L2 L1
G2 A A A A NA NA
20 Block. f3 (A)
21 Block. f4 (A)
22 Block. f5 (A)
23 Block. f6 (A)
24 AUX1(NA)
25 AUX2 (NA)
26 AUX2 (A)
27 AUX3 (A)
28 AUX4 (A)
29 AUX5 (A)
CB Status 52A
30
(A)
CB Status 52B
31
(A)
Setting group 2
32
(NA)
33 Manual Close (A)
34 Manual Trip (A)
35 VTS (A)
Start Distur. R.
36
(A)
Local CTRL
37
Mode (A)
38 Time Synchr. (A) CM
V11V/EN CM v1.0 Commissioning

(CM) 8-44 VAMP 11V

OUTPUT RELAYS CONFIGURATION G2


SETTING GROUP 2/
OUTPUT RELAY WD RL7 RL6 RL5 RL4 RL3 RL2 RL1
CONFIGURATION G2
LNA A A NA NA LNA LNA LNA

1 Latched outputs

Reverse outp.
2
logic
3 Protect. Trip
4 Prot.Trip pulse
Trip CB Order
5
(A)
Close CB Order
6
(A)
7 Alarm
8 Start V>
9 Start V>>
10 Start V>>>
11 Start V<
12 Start V<<
13 Start V<<<
14 Start V1< (A)
15 Start V1<< (A)

CM 16 Start V2> (NA)


17 Start V2>> (NA)
18 Start VN>
19 Start VN>>
20 Start VN>>>
21 Start f1 (A)
22 Start f2 (A)
23 Start f3 (A)
24 Start f4 (A)
25 Start f5 (A)
26 Start f6 (A)
27 AUX1 (NA)
28 AUX2 (NA)
29 AUX3 (A)
30 AUX4 (A)
31 AUX5 (A)
32 tV>
Commissioning V11V/EN CM v1.0

VAMP 11F (CM) 8-45

33 tV>>
34 tV>>>
35 tV<
36 tV<<
37 tV<<<
38 tV1< (A)
39 tV1<< (A)
40 tV2> (NA)
41 tV2>> (NA)
42 CB Alarm (A)
43 tVN>
44 tVN>>
45 tVN>>>
46 tf1 (A)
47 tf2 (A)
48 tf3 (A)
49 tf4 (A)
50 tf5 (A)
51 tf6 (A)
52 tAUX1 (NA)
53 tAUX2 (NA)
54 tAUX3 (A)
55 CB Alarm (A)
tCB FLT Ext.Sign
56
(A)
CM
Setting Group 1
57
(NA)
58 tVTS (A)
59 fout (A)
V11V/EN CM v1.0 Commissioning

(CM) 8-46 VAMP 11V

LEDs CONFIGURATION G2
SETTING GROUP 2/
LED2 LED3 LED4 LED5 LED6 LED7
LEDs CONFIGURATION G2
1 Latched LEDs
2 Alarm
3 Start V>
4 Start V>>
5 Start V>>>
6 Start V<
7 Start V<<
8 Start V<<<
9 Start V1< (A)
10 Start V1<< (A)
11 Start V2> (NA)
12 Start V2>> (NA)
13 Start VN>
14 Start VN>>
15 Start VN>>>
16 Start f1 (A)
17 Start f2 (A)
18 Start f3 (A)
19 Start f4 (A)
20 Start f5 (A)
21 Start f6 (A)
22 AUX1 (A)
CM
23 AUX2 (A)
24 AUX3 (A)
25 AUX4 (A)
26 AUX5 (A)
27 tV>
28 tV>>
29 tV>>>
30 tV<
31 tV<<
32 tV<<<
33 tV1< (A)
34 tV1<< (A)
35 tV2> (NA)
36 tV2>> (NA)
37 CB Alarm (A)
38 tVN>
Commissioning V11V/EN CM v1.0

VAMP 11F (CM) 8-47

LEDs CONFIGURATION G2
SETTING GROUP 2/
LED2 LED3 LED4 LED5 LED6 LED7
LEDs CONFIGURATION G2
39 tVN>>
40 tVN>>>
41 tf1 (A)
42 tf2 (A)
43 tf3 (A)
44 tf4 (A)
45 tf5 (A)
46 tf6 (A)
47 tAUX1 (A)
48 tAUX2 (A)
49 tAUX3 (A)
50 CB Alarm (A)
51 tCB FLT Ext.Sign (A)
52 Setting Group 1 (NA)
53 tVTS (A)
54 fout (A)

CM

Commissioning Engineer Customer Witness

Date: Date:
Maintenance V11V/EN MT v1.0

VAMP 11V (MT) 9-1

MAINTENANCE

MT

Date: 1st December 2015


Software Version: 1A
Connection Diagrams: 10V11V01
V11V/EN MT v1.0 Maintenance

(MT) 9-2 VAMP 11V

CONTENTS

1.1 Maintenance period 3


1.2 Maintenance checks 3
1.2.1 Binary Inputs 3
1.2.2 Outputs 3
1.2.3 Measurement Accuracy 3
1.3 Method of Repair 4
1.4 Cleaning 4

MT
Maintenance V11V/EN MT v1.0

VAMP 11V (MT) 9-3

Maintenance
1.1 Maintenance period
It is recommended that products supplied by SCHNEIDER ELECTRIC ENERGY receive
periodic monitoring after installation. In view of the critical nature of protective relays and
their infrequent operation, it is desirable to confirm that they are operating correctly, at
regular intervals.
SCHNEIDER ELECTRIC ENERGY protective relays are designed for a life in excess of 20
years.
VAMP 11x relays are self-monitoring and so require less maintenance than earlier designs of
relay. Most problems will set off an alarm so that remedial action can be taken. However,
some periodic tests should be carried out to ensure that the relay is functioning correctly and
that the external wiring is intact.
1.2 Maintenance checks
Although some functionality checks can be performed from a remote location by utilizing the
communications ability of the relays, these are predominantly restricted to checking that the
relay is measuring the applied voltages accurately. Therefore it is recommended that
maintenance checks are performed locally (i.e. at the substation itself).
Before carrying out any work on the equipment, the user should be
familiar with the contents of the Safety Guide SFTY/4L M/E11 or later
issue, OR the safety and technical data section of the technical
manual and also the ratings on the equipment rating label.

For safety reasons, no work must be carried out on the V11V until
all power sources to the unit have been disconnected.

1.2.1 Binary Inputs


Binary inputs can be checked to ensure that the relay responds to its energization by
repeating the commissioning test detailed in section 3.2.2 of the Commissioning chapter
(V11V/EN CM).
1.2.2 Outputs
Output relays operation can be checked by repeating the commissioning test detailed in
section 3.2.3 of the Commissioning chapter (V11V/EN CM). MT
1.2.3 Measurement Accuracy
If the power system is energized, the values measured by the relay can be compared with
known system values to check that they are in the approximate expected range. If they are,
then the analogue/digital conversion and calculations are being performed correctly by the
relay. Suitable test methods can be found in sections 3.2.6 of the Commissioning chapter
(V11V/EN CM).
Alternatively, the values measured by the relay can be checked against known values
injected into the relay via the test block, if fitted, or injected directly into the relay terminals.
These tests will prove the calibration accuracy is being maintained.
V11V/EN MT v1.0 Maintenance

(MT) 9-4 VAMP 11V

1.3 Method of Repair


It is recommended that the V11V relay is returned to an SCHNEIDER ELECTRIC ENERGY
service centre for repair.
Before carrying out any work on the equipment, the user should be
familiar with the contents of the Safety Guide SFTY/4L M/E11 or later
issue, OR the safety and technical data section of the technical
manual and also the ratings on the equipment rating label.

For safety reasons, no work must be carried out on the V11V until
all power sources to the unit have been disconnected.

1.4 Cleaning
Before cleaning the equipment ensure that all current transformers and voltage input
connections are isolated to prevent any possibility of an electric shock whilst cleaning.
The equipment may be cleaned using a lint-free cloth moistened with clean water. The
use of detergents, solvents or abrasive cleaners is not recommended as they may
damage the relay’s surface and leave a conductive residue.

MT
Troubleshooting V11V/EN TS v1.0

VAMP V11V

TROUBLESHOOTING

TS

Date: 1st December 2015


Software Version: 1A
Connection Diagrams: 10V11V01
V11V/EN TS v1.0 Troubleshooting

VAMP V11V

TS
Troubleshooting V11V/EN TS v1.0

VAMP V11V (TS) 10-1

CONTENTS

1. INTRODUCTION 2
2. INITIAL PROBLEM IDENTIFICATION 2
3. POWER UP ERRORS 3
4. MALOPERATION OF THE RELAY DURING TESTING 4
4.1 Failure of Binary Inputs (N, A only) 4
4.2 Failure of Output Contacts 4

5. REPAIR AND MODIFICATION PROCEDURE 6

TS
V11V/EN TS v1.0 Troubleshooting

(TS) 10-2 VAMP V11V

1. INTRODUCTION
BEFORE CARRYING OUT ANY WORK ON THE EQUIPMENT, THE
USER SHOULD BE FAMILIAR WITH THE CONTENTS OF THE
SAFETY GUIDE SFTY/4L M/E11 OR LATER ISSUE, or THE SAFETY
AND TECHNICAL DATA SECTION OF THE TECHNICAL MANUAL
AND ALSO THE RATINGS ON THE EQUIPMENT RATING LABEL.

For safety reasons, no work must be carried out on the V11V until
all power sources to the unit have been disconnected.

The purpose of this section of the service manual is to allow an error condition on the relay
to be identified so that appropriate corrective action can be taken.
In cases where a faulty relay is being returned to the manufacturer or one of their approved
service centers, a completed copy of the Repair/Modification Return Authorization Form
located at the end of this section should be included.

2. INITIAL PROBLEM IDENTIFICATION


Consult the table below to find the description that best matches the problem experienced,
then consult the section referenced to perform a more detailed analysis of the problem.

Symptom Refer To
Relay fails to power up Section 3
Maloperation of the relay during testing Section 4

Table 1: Problem identification

TS
Troubleshooting V11V/EN TS v1.0

VAMP V11V (TS) 10-3

3. POWER UP ERRORS
V11V can be powered up using the following power sources:

• USB connection to PC (model N, A)

• Auxiliary voltage (Vx)


If the relay does not appear to power up then the following procedure can be used to
determine whether the fault is in the external wiring or in the power supply module of the
relay.

Test Check Action


1. Connect the V11V to a PC via (i) If the green “Healthy” LED and display
the USB port. are lit then proceed to test 2.
1
2. Disconnect the PC from the (ii) If the green “Healthy” LED and display
V11V USB port. are not lit then proceed to test 2.
1. Apply a Vx auxiliary voltage on (i) If the green “Healthy” LED and display
terminals A1-A2 (check the are lit then proceed to test 3.
level on the V11V nominal (ii) If the green “Healthy” LED and display
label) are not lit then send the relay back to
2 2. Check whether the green Schneider Electric Energy's repair
“Healthy” LED on the V11V centre.
front panel is lit.
3. Disconnect the ac auxiliary
voltage from terminals A1-A2.

Table 2: Failure of relay to power up

TS
V11V/EN TS v1.0 Troubleshooting

(TS) 10-4 VAMP V11V

4. MALOPERATION OF THE RELAY DURING TESTING


4.1 Failure of Binary Inputs (N, A only)
The binary inputs are configured in the SETTING GROUPx/INPUTS CONFIGURATION
column for each setting group. If an input does not appear to be recognized by the relay
scheme logic the COMMISSIONING/Opto I/P Status menu option can be used to verify
whether the problem is in the binary input itself or the mapping of its signal to the scheme
logic functions. If the binary input appears to be read correctly then it is necessary to
examine its configuration.
Ensure the voltage rating for the opto inputs has been configured correctly with applied
voltage. If the binary input state is not read correctly by the relay the applied signal should be
tested. Verify the connections to the binary input using the correct wiring diagram. Next,
using a voltmeter verify that 80% opto setting voltage is present on the terminals of the
binary input in the energized state. If the signal is being correctly applied to the relay then the
failure may be on the input card itself.
Notes: 1. If the V11V is exclusively powered from the USB port, only some of the
relay's electronic circuits (necessary for communications) are supplied.
For this reason, inputs are in high state (independent of the voltage at the
terminals). Any action pertaining to binary inputs is blocked.
2. Only the logical state of the inputs is given in the COMMISSIONING
/Opto I/P Status cell, not presence of voltage at the terminals. For
example: If Vx (high state) and Reverse Input Logic are set (function
active in low state of binary input) at the terminals of a binary input in the
COMMISSIONING /Opto I/P Status cell, the logical state of the input is
low (logical status after application of the Reverse Input Logic function).
4.2 Failure of Output Contacts
An apparent failure of the relay's output contacts may be caused by the relay configuration;
the following tests should be performed to identify the real cause of the failure. Tests of
outputs can be performed using the COMMISSIONING/Test outputs cell. The command is
executed and the configured outputs (COMMISSIONING/Test Pattern) will be energized for
the duration of Contact Test Time (COMMISSIONING) – only model A.

Test Check Action


Is the Out of Service LED Illumination of this LED may indicate that the
illuminated? relay is in test mode or that the protection
1
has been disabled due to a hardware verify
error (see Table 2).
Examine the Test outputs (A) in If the relevant bits of the contact status are
2 the Commissioning section of the operated then proceed to test 4, if not
TS menu. proceed to test 3.
Verify by examination of the fault If the protection element does not operate
record whether the protection verify whether the test is being correctly
element is operating correctly. applied.
3 If the protection element operates then it is
necessary to check the configuration, to
ensure that the configuration of the
protection element to the contacts is correct.
Using the procedure described in If the output relay operates then the problem
the Commissioning chapter must be situated in the external wiring to the
(V11V/EN CM) energize every relay. If the output relay does not operate
output (note the correct external this could indicate a failure of the output
4
connection diagram should be relay contacts (note that the self-tests verify
consulted). A continuity tester can that the relay coil is being energized).
be connected at the rear of the Ensure that the closed resistance is not too
relay for this purpose. high for the continuity tester to detect.
Troubleshooting V11V/EN TS v1.0

VAMP V11V (TS) 10-5

Table 3: Failure of Output Contacts

TS
V11V/EN TS v1.0 Troubleshooting

(TS) 10-6 VAMP V11V

5. REPAIR AND MODIFICATION PROCEDURE


Please follow these 5 steps to return an Automation product to us:
1. Get the Repair and Modification Authorization Form (RMA)
Find a copy of the RMA form at the end of this section.
To obtain an electronic version of the RMA form for e-mailing, please connect your
local Schneider Electric Energy service.

2. Fill in RMA form


Fill in only the white part of the form.
Please ensure that all fields marked (M) are completed such as:
Equipment model
Model No. and Serial No.
Description of failure or modification required (please be specific)
Value for customs (in case the product requires export)
Delivery and invoice addresses
Contact details

3. Send RMA form to your local contact

4. Receive shipping information from local service contact


Your local service contact will provide you with all the information:
Pricing details
RMA n°
Repair center address
If required, an acceptance of the quote must be delivered before going to the next step. .

5. Send the product to the repair center

TS Address the shipment to the repair center specified by your local contact
Ensure all items are protected by appropriate packaging: anti-static bag and foam
protection
Ensure a copy of the import invoice is enclosed with the unit being returned
Ensure a copy of the RMA form is enclosed with the unit being returned
E-mail or fax a copy of the import invoice and air waybill to your local contact.
Symbols and Glossary V11V/EN SG v1.0

VAMP 11V

SYMBOLS AND GLOSSARY

Date: 1st December 2015


SG
Software Version: 1A
Connection Diagrams: 10V11V01
V11V/EN SG v1.0 Symbols and Glossary

VAMP 11V

SG
Symbols and Glossary V11V/EN SG v1.0

VAMP 11V (SG) 11-1

Logic Symbols

Symbols Explanation

> Greater than:


Used to indicate an “over” threshold, such as overvoltage.
C/O A changeover contact having normally closed and normally open connections:
Often called a “form C” contact.
CB Circuit breaker.
VT Voltage transformer.
Dly Time delay.
DT Abbreviation of “Definite Time”:
An element which always responds with the same constant time-delay on operation.
E/F Earth fault:
Directly equivalent to ground fault.
Flt. Abbreviation of “Fault”:
Typically used to indicate faulted phase selection.
FN Function.
Gnd. Abbreviation of “Ground”:
Used in distance settings to identify settings that relate to ground (earth) faults.
V Voltage
V< First stage of undervoltage protection:
Could be labeled 27-1 in ANSI terminology.
V<< Second stage of undervoltage protection:
Could be labeled 27-2 in ANSI terminology.
V<<< Third stage of undervoltage protection:
Could be labeled 27-3 in ANSI terminology.
V> First stage of overvoltage protection:
Could be labeled 59-1 in ANSI terminology.
V>> Second stage of overvoltage protection:
Could be labeled 59-2 in ANSI terminology.
V>>> Third stage of overvoltage protection:
Could be labeled 59-3 in ANSI terminology.
VN Earth Fault voltage:
Equals the neutral voltage measured at the analog input.
V2> Negative sequence overvoltage protection
Could be labeled 47 in ANSI terminology.
SG
V1< Positive sequence undervoltage protection
Could be labeled 27D in ANSI terminology.
V2 Negative sequence of voltage.
V1 Positive sequence of voltage.
F Frequency protection
AUX Auxiliary timers
VA Phase A voltage:
V11V/EN SG v1.0 Symbols and Glossary

(SG) 12-2 VAMP 11V

Symbols Explanation

Might be phase L1, red phase.. or other, in customer terminology.


VB Phase B voltage:
Might be phase L2, yellow phase.. or other, in customer terminology.
VC Phase C voltage:
Might be phase L3, blue phase.. or other, in customer terminology.
IDMT Inverse definite minimum time:
A characteristic whose trip time depends on the measured input (e.g. voltage)
according to an inverse-time curve.
Un The rated nominal voltage of the VT:
Software selectable (57-130)V.
Uen The rated nominal voltage of the E/F CT:
Software selectable (57-130)V.
VN Neutral voltage, or residual voltage:
This results from an external summation of the three measured phase voltages.
Inst. An element with “instantaneous” operation:
i.e. having no deliberate time delay.
I/O Abbreviation of “Inputs and Outputs”:
Used in connection with the number of opto-coupled inputs and output contacts within
the relay.
I/P Abbreviation of “Input”.
LD Abbreviation of “Level Detector”:
An element responding to a voltage below its set threshold.
LED Light emitting diode:
Red or green indicator on the relay front-panel.
N Indication of “Neutral” involvement in a fault:
i.e. a ground (earth) fault.
N/A Not applicable.
N/C A normally closed or “break” contact:
Often called a “form B” contact.
N/O A normally open or “make” contact:
Often called a “form A” contact.
O/P Abbreviation of “output”.
Opto An opto-coupled logic input:
Alternative terminology: binary input.
PCB Printed circuit board.
SG
Ph Abbreviation of “Phase”:
Used in distance settings to identify settings that relate to phase-phase faults.
VN> The first stage of earth fault protection element [59N]
VN>> The second stage of earth fault protection element [59N]
VN>>> The third stage of earth fault protection element [59N]
Rx Abbreviation of “Receive”:
Typically used to indicate a communication receive line/pin.
Symbols and Glossary V11V/EN SG v1.0

VAMP 11V (SG) 11-3

Symbols Explanation

T A time delay.
TE A standard for measuring the width of a relay case:
One inch = 5TE units.
TMS The time multiplier setting applied to IEC or UK inverse-time curves
TD The time multiplier setting applied to IEEE or US inverse-time curves
Tx Abbreviation of “Transmit”:
Typically used to indicate a communication transmit line/pin.

Retardation time
Retardation time is the time which protection relay needs to notice, that a fault has
been cleared during the operation time delay. This parameter is important when
grading the operation time delay settings between protection relays.

Figure 1: Definition for retardation time

Example - when there is a big fault in an outgoing feeder, it might start i.e. pick-up
both the incoming and outgoing feeder relay. However the fault must be cleared by
the outgoing feeder relay and the incoming feeder relay must not trip. Although the
operating delay setting of the incoming feeder is more than at the outgoing feeder,
the incoming feeder might still trip, if the operation time difference is not big enough.
The difference must be more than the retardation time of the incoming feeder relay
plus the operating time of the outgoing feeder circuit breaker. Figure 1 shows
overvoltage fault see from the incoming feeder, when the outgoing feeder does clear
the fault. If the operation delay setting would be slightly shorter or if the fault duration SG
would be slightly longer than in the figure, an unselective trip might happen (dotted
pulse in the above figure). In VAMP 11x devices the retardation time is less than 40
ms.
Installation V11V/EN IN v1.0

VAMP 11V

INSTALLATION

Date: 1st December 2015


Software Version: 1A
Connection Diagrams: 10V11V01 IN
V11V/EN IN v1.0 Installation

V11V

IN
Installation V11V/EN IN v1.0

VAMP 11V (IN) 12-1

CONTENTS

1. RECEIPT OF RELAYS 3
2. HANDLING OF ELECTRONIC EQUIPMENT 3
3. STORAGE 3
4. UNPACKING 4
5. RELAY MOUNTING 4
6. RELAY WIRING 4
6.1 Terminal Block Connections 5
6.2 USB Port 5
6.3 Rear Communications Port (in Model L optional) 5

7. V11V CASE AND ADAPTOR DIMENSIONS 7


8. EXTERNAL CONNECTION DIAGRAMS 9

FIGURES
Figure 1: Dimensions. V11V flush mounting basic case 7
Figure 2: Dimensions. Wall mounting case adaptor 8
Figure 3: Model A 9
Figure 4: Model N 10
Figure 5: Model L 11
Figure 6: Model A – application example 2Upp and UN 12
Figure 7: Model A – application example 3Upp and UN 13

IN
Installation V11V/EN IN v1.0

(IN) 12-2 VAMP 11V

IN
Installation V11V/EN IN v1.0

VAMP 11V (IN) 12-3

1. RECEIPT OF RELAYS
Upon receipt, relays should be examined immediately to ensure no external damage has
been sustained in transit. If damage has been sustained, a claim should be made to the
transport contractor and Schneider Electric Energy should be promptly notified.
Relays that are supplied unmounted and not intended for immediate installation should be
returned to their protective polythene bags and delivery carton. Section 3 of V11V/EN IN
gives more information about the storage of relays.

2. HANDLING OF ELECTRONIC EQUIPMENT


A person’s normal movements can easily generate electrostatic potentials of several
thousand volts. Discharge of these voltages into semi-conductor devices when handling
electronic circuits can cause serious damage that, although not always immediately apparent
can reduce the reliability of the circuit. The relay’s electronic circuits are protected from
electrostatic discharge when housed in the case. Do not expose them to risk by removing
the front panel or printed circuit boards unnecessarily.
Each printed circuit board incorporates the highest practicable protection for its semi-
conductor devices. However, if it becomes necessary to remove a printed circuit board, the
following precautions should be taken to preserve the high reliability and long life for which
the relay has been designed and manufactured.
Before removing a printed circuit board, ensure that you are at the same electrostatic
potential as the equipment by touching the case.
Handle analog input modules by the front panel, frame or edges of the circuit boards. Printed
circuit boards should only be handled by their edges. Avoid touching the electronic
components, printed circuit tracks or connectors.
Do not pass the module to another person without first ensuring you are both at the same
electrostatic potential. Shaking hands achieves equipotential.
Place the module on an anti-static surface, or on a conducting surface that is at the same
potential as you.
If it is necessary to store or transport printed circuit boards removed from the case, place
them individually in electrically conducting anti-static bags.
In the unlikely event that you are making measurements on the internal electronic circuitry of
a relay in service, it is preferable that you are earthed to the case with a conductive wrist
strap. Wrist straps should have a resistance to ground between 500 kΩ and 10 MΩ. If a
wrist strap is not available you should maintain regular contact with the case to prevent a
build-up of electrostatic potential. Instrumentation which may be used for making
measurements should also be earthed to the case whenever possible.
More information on safe working procedures for all electronic equipment can be found in
BS EN 100015: Part 1:1992. It is strongly recommended that detailed investigations on
electronic circuitry or modification work should be carried out in a special handling area such
as described in the British Standard document.

3. STORAGE
If relays are not to be installed immediately upon receipt, they should be stored in a place
free from dust and moisture in their original cartons. Where de-humidifier bags have been
included in the packing they should be retained.
IN
Care should be taken on subsequent unpacking that any dust, which has collected on the
carton, does not fall inside. In locations of high humidity the carton and packing may
become impregnated with moisture and the de-humidifier crystals will lose their efficiency.
Prior to installation, relays should be stored at a temperature of between –40°C to +70°C
(-40°F to +158°F).
Installation V11V/EN IN v1.0

(IN) 12-4 VAMP 11V

4. UNPACKING
Care must be taken when unpacking and installing the relays so that none of the parts are
damaged and additional components are not accidentally left in the packing or lost. Ensure
that any User’s CD ROM or technical documentation is NOT discarded – this should
accompany the relay to its destination substation.
Relays must only be handled by qualified persons.
The site should be well lit to facilitate inspection, clean, dry and reasonably free from dust
and excessive vibration.

5. RELAY MOUNTING
Individual relays are normally supplied with an outline diagram showing the dimensions. This
information can also be found in the product publication.
Flush mounted version:
Make a cut-out in mounting plate according to fig. 1. Then insert the relay into it. Fit fastening
elements (see fig. 1) into the slots in the sides of the housing, and keep turning the fastening
screws until the relay is securely fixed to the plate. To remove the relay undo the screws, so
that the fastening element could be taken out, and then the relay could be withdrawn from
the cut-out in the mounting plate.
Mounting on the wall:
Flush mounting case of V11V can be mounted on the wall by using optional Wall Mounting
Case Adaptor (ordering number: REL10030)
Insert the relay into wall mounting adaptor according to fig. 2. Fit fastening elements (see fig.
2) into the slots in the sides of the housing, and keep turning the fastening screws until the
relay is securely fixed to the wall mounting adaptor. To remove the relay undo the screws, so
that the fastening element could be taken out, and then the relay could be withdrawn from
the wall mounting adaptor.

6. RELAY WIRING
BEFORE CARRYING OUT ANY WORK ON THE EQUIPMENT, THE
USER SHOULD BE FAMILIAR WITH THE CONTENTS OF THE SAFETY
GUIDE SFTY/4L M/E11 OR LATER ISSUE, OR THE SAFETY AND
TECHNICAL DATA SECTION OF THE TECHNICAL MANUAL AND
ALSO THE RATINGS ON THE EQUIPMENT RATING LABEL.

For safety reasons, no work must be carried out on the V11V until all
power sources to the unit have been disconnected.

The measuring voltage inputs of the V11V should be connected to the secondary wires of
the power system VTs as shown in the connection diagrams in section 8. ”External
Connection Diagram” of this chapter V11V/EN IN.
IN
The VT types which can be connected to the V11V’s voltage input terminals are shown in
section 3 of the Applications chapter V11V/EN AP.
Installation V11V/EN IN v1.0

VAMP 11V (IN) 12-5

6.1 Terminal Block Connections


AC Voltage Input Terminals
Threaded M3 screw-type plug-in terminals, with wire protection for conductor cross-section
2
(i) 0.2 - 6 mm single-core
2
(ii) 0.2 - 4 mm finely stranded
General Input/Output Terminals
For power supply, binary and contact inputs, output contacts and COM for rear
communications.
Threaded M3 screw-type plug-in terminals, with wire protection for conductor cross-section
2
(i) 0.2 - 4 mm single-core
2
(ii) 0.2 - 2.5 mm finely stranded
Connections to the equipment must only be made using single strand wire or
stranded wire with the use of insulated crimp terminals to maintain insulation
requirements.
Where UL Listing of the equipment is not required the recommended fuse type for external
wiring is a high rupture capacity (HRC) type with a maximum current rating of 16 Amps and a
minimum DC rating of 250 Vdc, for example the Red Spot NIT or TIA type.
To maintain UL and CUL Listing of the equipment for North America a UL Listed fuse shall
be used. The UL Listed type shall be a Class J time delay fuse, with a maximum current
rating of 15 A and a minimum DC rating of 250 Vdc, for example type AJT15.
The protective fuse(s) should be located as close to the unit as possible.

6.2 USB Port


Connection to the USB (NA) port can be made by means of an USB cable. The USB port
allows the user to download settings or fault records from the V11V or change I/O
configuration.
To access this port it is necessary to remove the cover plate on the V11V front panel.
A typical cable specification would be:
Cable Type: USB 2.0
Connectors:
PC: type A male
V11V: type mini B 5-pin male
USB Cable: minimum 1P*28AWG/2C*24AWG, max: 2m
Communication software: MiCOM S1 Studio (5.1.0 or higher)
The virtual COM port for USB communications should be set in as follows:
Address: 1
Baud rate: 115 200 bits/s
IN
Data bit: 8
Stop bit: 1
Parity: None
6.3 Rear Communications Port (in Model L optional)
EIA(RS)485 signal levels, two wire
Installation V11V/EN IN v1.0

(IN) 12-6 VAMP 11V

Connections located on the general-purpose terminal block, M3 screw


For screened twisted pair cable, distance to be bridged: multi-endpoint link: max. 100m
For Modbus RTU or IEC-103 protocol; Isolation to SELV level

IN
Installation V11V/EN IN v1.0

VAMP 11V (IN) 12-7

7. V11V CASE AND ADAPTOR DIMENSIONS

101.5

Figure 1: Dimensions. V11V flush mounting basic case

IN
Installation V11V/EN IN v1.0

(IN) 12-8 VAMP 11V

Figure 2: Dimensions. Wall mounting case adaptor


IN
Installation V11V/EN IN v1.0

VAMP 11V (IN) 12-9

8. EXTERNAL CONNECTION DIAGRAMS

Figure 3: Model A

IN
Installation V11V/EN IN v1.0

(IN) 12-10 VAMP 11V

Figure 4: Model N

IN
Installation V11V/EN IN v1.0

VAMP 11V (IN) 12-11

U1
U2 U1
U3
A1 Auxiliary
Voltage
A2 Vx
U2 U3

A3
Watchdog
A4
WD
WD
C9 A5
U1
C10 A6
Output
C11 A7 Contact
U2 RL1 RL1
C12 A8

C13 A9
U3 Output
C14 A10 Contact
RL2 RL2
A11

A12 Output
RL3 Contact
A13 RL3

Figure 5: Model L

IN
Installation V11V/EN IN v1.0

(IN) 12-12 VAMP 11V

Figure 6: Model A – application example 2Upp and UN

IN
Installation V11V/EN IN v1.0

VAMP 11V (IN) 12-13

Figure 7: Model A – application example 3Upp and UN

IN
Communication Database V11V/EN CT v1.0

VAMP 11V

COMMUNICATION DATABASE

Date: 1st December 2015 CT


Software Version: 1A
Connection Diagrams: 10V11V01
V11V/EN CT v1.0 Communication Database

VAMP 11V

CT
Communication Database V11V/EN CT v1.0

VAMP 11V (CT) 13-1

CONTENT

1. INTRODUCTION 3
1.1 Purpose of this document 3
1.2 Glossary 3

2. MODBUS PROTOCOL 4
2.1 Technical characteristics of the MODBUS connection 4
2.1.1 Parameters of the MODBUS connection 4
2.1.2 Synchronisation of exchanges messages 4
2.1.3 Message validity check 4
2.2 MODBUS functions of the V11V relays 5
2.3 Presentation of the MODBUS protocol 5
2.3.1 Format of frames sent by the VAMP 11V relay 5
2.3.2 Messages validity check 6
2.4 VAMP 11V relay database organisation 7
2.4.1 Description of the application mapping 7
2.4.2 Page 0h : Product information, remote signalling, measurements 9
2.4.3 Page 1h, VAMP 11V : general remote parameters 12
2.4.4 Page 2h : setting Group 1 15
2.4.5 Page 3h : setting Group 2 22
2.4.6 Page 4h : remote controls 29
2.4.7 Pages 5h/6h 29
2.4.8 Page 7h 29
2.4.9 Page 8h : time synchronisation 29
2.4.10 Mapping access characteristics 30
2.4.11 Page 9h to 21h: disturbance record data (25 pages) 31
2.4.12 Page 22h: disturbance record index frame 33
2.4.13 Page 35h (addresses 3500h to 354Ah) : event record data (9 words) 33
2.4.14 Page 36h 38
2.4.15 Page 37h : fault record value data 38
2.4.16 Page 3Eh : most older Fault record value data 41
2.4.17 Page 38h to 3Ch: Disturbance recorder 41 CT
2.4.18 Pages 3Dh : number of disturbance records available 43
2.4.19 Description of the mapping format, VAMP 11V 44
2.4.20 Request to retrieve the oldest non-acknowledge event 52
2.4.21 Request to retrieve a dedicated event 52
2.4.22 Modbus request definition used to retrieve the fault records 52

3. IEC60870-5-103 INTERFACE 54
V11V/EN CT v1.0 Communication Database

(CT) 13-(CT) 13-2 VAMP 11V

CT
Communication Database V11V/EN CT v1.0

VAMP 11V (CT) 13-3

1. INTRODUCTION
1.1 Purpose of this document
This document describes the characteristics of the different communication protocol of
VAMP 11V relay.

The available communication protocols of VAMP 11V only model N and A relays are
as follows:

• MODBUS.

• IEC 60870-5-103.
NOTE:
V11V has hardware options which are called Models: Model N, Model A, which has
different functions.
This document shows all available functions in V11V. To see which function are
available in model refer to the rest chapters/sections of this manual.
For example: disturbance recorder is available in model A only, etc.
1.2 Glossary
VA, VB, VC : voltage measured on the concerned phases (A, B, C)
VN : residual voltage measured by earth input
pf : soft weight of a word of 16 bits
PF : heavy weight of a word of 16 bits.

CT
V11V/EN CT v1.0 Communication Database

(CT) 13-(CT) 13-4 VAMP 11V

2. MODBUS PROTOCOL
VAMP 11V relay can communicate by a RS 485 link behind the unit following the
MODBUS MODICON RTU protocol.
2.1 Technical characteristics of the MODBUS connection
2.1.1 Parameters of the MODBUS connection
The different parameters of the MODBUS connection are as follows :

• Isolated two-point RS485 connection (2kV 50Hz),

• MODBUS MODICON line protocol in RTU mode

• Communication speed can be configured by an operator dialog in the front panel of the
relay :

Baud rate
4800
9600
38400
57600
115200

Transmission mode of the configured characters by operator dialog:

Mode
1 start / 8 bits / 1 stop : total 10 bits
1 start / 8 bits / even parity / 1 stop : total 11 bits
1 start / 8 bits / odd parity / 1 stop : total 11 bits
1 start / 8 bits / 2 stop : total 11 bits

2.1.2 Synchronisation of exchanges messages


All character received after a silence on the line with more or equal to a transmission time of
3 characters is considered as a firm start.
2.1.3 Message validity check
The frame validity is working with a cyclical redundancy code CRC with 16 bits. The
generator polynomial is:
15 16
1 + x² + x + x = 1010 0000 0000 0001 binary = A001h
Address of the VAMP 11V relays
CT The address of the VAMP 11V relay on a same MODBUS network is situated between 1 and
255. The address 0 is reserved for the broadcast messages
Communication Database V11V/EN CT v1.0

VAMP 11V (CT) 13-5

2.2 MODBUS functions of the V11V relays


The MODBUS functions implemented on the VAMP relays are :
Function 3 or 4 : Reading of n words
Function 5 : Writing of 1 bit
Function 6 : Writing of 1 word
Function 7 : Fast reading of 8 bits
Function 16 : Writing of n words
2.3 Presentation of the MODBUS protocol
Master slave protocol, all exchange understands a master query and a slave response

Frame size received from VAMP 11V relay

Frame transmitted by the master (query) :

Slave Function Information CRC1 6


number code
1 byte 1 byte n bytes 2 bytes
0 à FFh 1 à 10h

Slave number:
The slave number is situated between 1 and 247.
A frame transmitted with a slave number 0 is globally addressed to all pieces of equipment
(broadcast frame )
Function code:
Requested MODBUS function (1 to 16)
Information:
Contains the parameters of the selected function.
CRC16:
Value of the CRC16 calculated by the master.
Note: The VAMP 11V relay does not respond to globally broadcast frames
sent out by the master.
2.3.1 Format of frames sent by the VAMP 11V relay
Frame sent by the VAMP 11V relay ( response)

Slave Function Data CRC16 CT


number code
1 byte 1 byte n bytes 2 bytes
1 à FFh 1 à 10h

Slave number :
The slave number is situated between 1 and 247.
Function code :
Processed MODBUS function (1 to 16) .
V11V/EN CT v1.0 Communication Database

(CT) 13-(CT) 13-6 VAMP 11V

Data :
Contains reply data to master query .
CRC 16:
Value of the CRC 16 calculated by the slave.
2.3.2 Messages validity check

When VAMP 11V relay receive a master query, it validates the frame :

• If the CRC is false, the frame is invalid. VAMP 11V relay do not reply to the query. The
master must retransmit its query. Excepting a broadcast message, this is the only case
of non-reply by VAMP 11V relay to a master query.

• If the CRC is good but the VAMP relay can not process the query, it sends an exception
response.
Warning frame sent by the VAMP relay (response)

Slave number Function code Warning code CRC16


1 byte 1 byte 1 byte 2 bytes
1 to FFh 81h or 83h or 8Ah or 8Bh pf ... PF

Slave number :
The slave number is situated between 1 and 247.
Function code :
The function code returned by the VAMP relay in the warning frame is the code in which the
most significant bit (b7) is forced to 1.
Warning code :
On the 8 warning codes of the MODBUS protocol, the VAMP relay manages two of them :

• code 01 : function code unauthorised or unknown.

• code 03 : a value in the data field is unauthorised ( incorrect data ).


Control of pages being read
Control of pages being written
Control of addresses in pages
Length of request messages
CRC16:
Value of the CRC16 calculated by the slave.
CT
Communication Database V11V/EN CT v1.0

VAMP 11V (CT) 13-7

2.4 VAMP 11V relay database organisation


2.4.1 Description of the application mapping
2.4.1.1 Settings
VAMP 11V application mapping has 9 pages of parameters.
Page 0h: Product information, remote signalling, measurements
Page 1h: General remote parameters
Page 2h: Setting group 1 remote parameters
Page 3h: Setting group 2 remote parameters
Page 4h: Remote controls
Pages 5h/6h: Reserved pages
Pages 7h: Quick reading byte
Pages 8h: Time synchronisation
2.4.1.2 Disturbance Records
Before uploading any disturbance record, a service request must be send to select the
record number to be uploaded.
The answer following this request contain the following information:

• Numbers of samples (pre and post time)

• Phase VT ratio

• Earth VT ratio

• Internal phase and earth ratios

• Number of the last disturbance mapping page

• Number of samples in this last disturbance mapping page


The mapping pages used for this service request are from 38h to 3Ch.
Pages 9h to 21h : Contain the disturbance data (25 pages)
A disturbance mapping page contains 250 words:
0900 to 09FAh : 250 disturbance data words
0A00 to 0AFAh : 250 disturbance data words
0B00 to 0BFAh : 250 disturbance data words
......
2100 to 21FAh : 250 disturbance data words
The disturbance data pages contain the sample of a single channel from a record.
Page 22h : contains the index of the disturbance CT
Page 38h to 3Ch : Selection of the disturbance record and channel
Page 3Dh : A dedicated request allows to know the number of disturbance records stored in
FRAM memory.
V11V/EN CT v1.0 Communication Database

(CT) 13-(CT) 13-8 VAMP 11V

2.4.1.3 Event records


To upload the event records two requests are allowed:

Page 35h: Request to upload an event record without acknowledge of this event.

Used addresses:
3500h : EVENT 1
.....
3563h : EVENT 100

Page 36h: Request to upload the non-acknowledged oldest stored event record.

Two modes are available for the acknowledgement: automatic acknowledgement or manual
acknowledgement
The mode depends of the state of bit 12 of telecommand word (address 400 h).
If this bit is set, then the acknowledgement is manual else the acknowledgement is
automatic.
In automatic mode, the reading of the event acknowledges the event.
In manual mode, it is necessary to write a specific command to acknowledge the oldest
event
(set the bit 13 of control word 400 h)
2.4.1.4 Fault records
Page 37h: Page dedicated to upload fault record

Used addresses:
3700h : FAULT 1
3701h : FAULT 2
.....
3704h : FAULT 5

Page 3Eh: Request to upload the non-acknowledged oldest stored fault record.

Two modes are available for the acknowledgement: automatic acknowledgement or manual
acknowledgement
The mode depends of the state of bit 12 of telecommand word (address 400 h).
If this bit is set, then the acknowledgement is manual else the acknowledgement is
automatic.
In automatic mode, the reading of the fault acknowledges automatically the event.
In manual mode, it is necessary to write a specific command to acknowledge the oldest fault.
(set the bit 14 of control word 400 h)
CT
2.4.1.5 Characteristics
Page 0h can only be read through communication.
Pages 1h, 2h, 3h and 4h can be read and write.
Page 7h can be access in quick reading only.
Page 8h can be write.
They are describe more precisely in the following chapters.
Communication Database V11V/EN CT v1.0

VAMP 11V (CT) 13-9

2.4.2 Page 0h : Product information, remote signalling, measurements


Read access only

Values Forma Default


Address Group Description Step Unit
range t Value
0000 Product Relay description 32-127 - F10 V1
Information characters 1 and 2

0001 Relay description 32-127 - F10 1V


characters 3 and 4
0002 Relay description 32-127 - F10
characters 5 and 6
0003 Unit reference characters 32-127 - F10 SE
1 and 2
0004 Unit reference characters 32-127 - F10
3 and 4
0005 Software Version 10 to 99 - F15
0006 Hardware Version 0 to 4 - F58
0007 Line VT Sec 0 to 1 - F21
0008 E/Gnd VT Sec 0 to 1 - F23
0009 Active Set Group 0 to 1 - F32 0
000A Nominal frequency 0 to 1 - F57 0
000B - 000F Reserved -
0010 Remote Logical inputs status 0 to 15 1 bits F11
signalling
0011 Voltage Protection disable 0 to 15 1 bits F12
status (1)
0012 Protection Function disable 0 to 15 1 bits F12A
status (2)
0013 Output contacts status 0 to 15 1 bits F24
0014 Logical LEDs status 0 to 15 1 bits F25
0015 Voltage Protection starting 0 to 15 1 bits F28
status (1)
0016 Protection Fuction starting 0 to 15 1 bits F28A
status (2)
0017 Voltage Protection trip status 0 to 15 1 bits F29
(1)
0018 Protection Fuction trip status 0 to 15 1 bits F29A
(2)
0019 Voltage Protection Alarm
status 1
0 to 15 1 bits F31
CT
001A Protection Fuction Alarm 0 to 15 1 bits F31A
status 2
001B CB status 0 to 4 1 - F30
001C Reserved
001D Reserved
001E Local/Romote Mode Status 0 to 2 1 - F61
001F Maintance Mode 0 to 2 1 - F62
0020 Hardware Warning 0 to 15 1 - F26
V11V/EN CT v1.0 Communication Database

(CT) 13-(CT) 13-10 VAMP 11V

Values Forma Default


Address Group Description Step Unit
range t Value
0021 Output information: V> 0 to 15 1 bits F37
0022 Output information: V>> 0 to 15 1 bits F37
0023 Output information: V>>> 0 to 15 1 bits F37
0024 Output information: V< 0 to 15 1 bits F37
0025 Output information: V<< 0 to 15 1 bits F37
0026 Output information: V<<< 0 to 15 1 bits F37
0027 Output information: VN> 0 to 15 1 bits F50
0028 Output information: VN>> 0 to 15 1 bits F50
0029 Output information: VN>>> 0 to 15 1 bits F50
002A Output information: V2> 0 to 15 1 bits F50
002B Output information: V2>> 0 to 15 1 bits F50
002C Output information: V1< 0 to 15 1 bits F50
002D Output information: V1<< 0 to 15 1 bits F50
002E Output information: AUX1 0 to 15 1 bits F50
002F Output information: AUX2 0 to 15 1 bits F50
0030 Output information: AUX3 0 to 15 1 bits F50
0031 Reserved
0032 Output information: tf1 0 to 15 1 bits F50
0033 Output information: tf2 0 to 15 1 bits F50
0034 Output information: tf3 0 to 15 1 bits F50
0035 Output information: tf4 0 to 15 1 bits F50
0036 Output information: tf5 0 to 15 1 bits F50
0037 Output information: tf6 0 to 15 1 bits F50
0038 - 003F Reserved
0040 Remote Phase VA (L1) voltage [V] 0 to 65535 1 [V]/10 F1
measurements
0041 Phase VB (L2) voltage [V] 0 to 65535 1 [V]/10 F1
0042 Phase VC (L3) voltage [V] 0 to 65535 1 [V]/10 F1
0043 Phase VAB (L1-L2) voltage [V] 0 to 65535 1 [V]/10 F1
0044 Phase VBC (L2-L3) voltage [V] 0 to 65535 1 [V]/10 F1
0045 Phase UCA (L3-L1) voltage [V] 0 to 65535 1 [V]/10 F1
0046 E/F VN (UE) measured 0 to 65535 1 [V]/10 F1
CT voltage [V]
0047 E/F 3Uo derived voltage [V] 0 to 65535 1 [V]/10 F1
0048 V1 possitive sequence voltage 0 to 65535 1 [V]/10 F1
[V]
0049 V2 negative seq. voltage [V] 0 to 65535 1 [V]/10 F1
004A Frequency 0 to 65535 1 [Hz]/100 F1
004B Reserved
004C E/F for default display 0 to 65535 1 [V]/10 F1
004D Delta Vr 0 to 65535 1 [V]/10 F1
Communication Database V11V/EN CT v1.0

VAMP 11V (CT) 13-11

Values Forma Default


Address Group Description Step Unit
range t Value
004E - 004F Reserved
0050 Phase VA (L1) voltage [Un] 0 to 65535 1 [Un]/1000 F1
0051 Phase VB (L2) voltage [Un] 0 to 65535 1 [Un]/1000 F1
0052 Phase VC (L3) voltage [Un] 0 to 65535 1 [Un]/1000 F1
0053 Phase VAB (L1-L2) voltage 0 to 65535 1 [Un]/1000 F1
[Un]
0054 Phase VBC (L2-L3) voltage 0 to 65535 1 [Un]/1000 F1
[Un]
0055 Phase VAB (L3-L1) voltage 0 to 65535 1 [Un]/1000 F1
[Un]
0056 E/F VN (UE) measured 0 to 65535 1 [Un]/1000 F1
voltage [Un]
0057 E/F 3Uo derived voltage [Un] 0 to 65535 1 [Un]/1000 F1
0058 V1 possitive sequence voltage 0 to 65535 1 [Un]/1000 F1
[Un]
0059 V2 negative seq. voltage [Un] 0 to 65535 1 [Un]/1000 F1
005A Reserved
005B Reserved
005C E/F for default display 0 to 65535 1 [Un]/1000 F1
005D - 007F Reserved
0080 Max Va 0 to 65535 1 [Un]/1000 F1
0081 Max Vb 0 to 65535 1 [Un]/1000 F1
0082 Max Vc 0 to 65535 1 [Un]/1000 F1
0083 Max Vab 0 to 65535 1 [Un]/1000 F1
0084 Max Vbc 0 to 65535 1 [Un]/1000 F1
0085 Max Vca 0 to 65535 1 [Un]/1000 F1
0086 - 00FF Reserved

CT
V11V/EN CT v1.0 Communication Database

(CT) 13-(CT) 13-12 VAMP 11V

2.4.3 Page 1h, VAMP 11V : general remote parameters


Read and write access

Values Default
Address Group Description Step Unit Format
range Value
0100 Remote Address 1 to 127 1 - F1 1
parameters
0101 Protocol for RS485 0 to 1 1 F56 0
0102 Baud Rate 0 to 5 1 F19 2
0103 Parity 0 to 2 1 F20 0
0104 Stop bits 0 to 1 1 F22 0
0105-010F Reserved
0110 Counters Trips Number 0 to 65535 1 - F1 0

0111 Close Number 0 to 65535 1 - F1 0


0112 Fault Trips Number 0 to 65535 1 - F1 0
0113 Fault Start Number 0 to 65535 1 - F1 0
0114 Alarm Number 0 to 65535 1 - F1 0
0115 HW Warnings Number 0 to 65535 1 - F1 0
0116 CB close Monitoring 0 to 65535 1 - F1 0
0117 CB open Monitoring 0 to 65535 1 - F1 0
0118-011F Reserved
0120 VT Ratio Line VT primary 5 to 6500 1 [kV]/100 F1

0121 Line VT Sec. 570 to 1300 1 [V]/10 F1


2200 to 4800
0122 E/Gnd VT Primary 5 to 6500 1 [kV]/100 F1
0123 E/GND VT Sec. 570 to 1300 1 [V]/10 F1
0124 VT connection 0 to 3 1 - F90 0
0125 Protection configuration V> 0 to 1 1 - F91 0
0126 Protection configuration V< 0 to 1 1 - F91 0
0127 - 0136 Reserved
0137 Voltage Advanced Reserved
Settings
0138 IDMT interlock by DMT stage 0 to 1 1 - F88 0
0139 [27] Hysteresis 100 to 120 1 [1]/100 F1

CT 013A [59] Hysteresis 80 to 100 1 [1]/100 F1


013B – 013F Reserved

GLOBAL SETTINGS
0140 LOC Language 0 to 6 1 - F52 0

0141 Default display 0 to 5 1 - F53 0


0142 LEDs Reset by 0 to 2 1 - F54 0
0143 Ltchd Outp Reset 0 to 2 1 - F54 0
0144 Trip Info Reset 0 to 2 1 - F54 0
0145 Alarm Display Reset 0 to 1 1 - F55 0
Communication Database V11V/EN CT v1.0

VAMP 11V (CT) 13-13

Values Default
Address Group Description Step Unit Format
range Value
0146 Nominal frequency 0 to 1 1 - F57 0
0147 Control Keys Confirmation 0 to 1 1 - F82 0
0148-014F Reserved
0150 SETTING GROUP Number of Setting 0 to 1 1 - F71 0
SELECT Groups
0151 Setting group change 0 to 1 1 - F32 0
0152 t Change Setting 0 to 20000 1 [s]/100 F1 0
G1->G2
0153-015F Reserved
0160 VT Supervision VTS Supervision 0 to 1 1 - F66

0161 Detection Mode 0 to 2 1 - F92


0162 Delta Vr 20 to 1300 1 [V]/10 F1
0163 tVTS 0 to 10000 1 [s]/100 F1
0164 Inhibit VTS/52a 0 to 1 - F63
0165 Block function V< 0 to 1 - F63
0166 Block function V> 0 to 1 - F63
0167 Block function VN> 0 to 1 - F63
0168 Block function V1< 0 to 1 - F63
0169 Block function V2< 0 to 1 - F63
016A Block function frequency 0 to 1 - F63
016A - 0173 Reserved
0174 [81] Advanced Protect. Frequency 5 to 100 1 [V] F1
settings block

0175 Reserved
0176 Meas. Validation NB 1 to 10 1 - F1 4
(halfcycles)
0176 – 017F Reserved
0180 CIRCUIT tOpen pulse min 10 to 1000 1 [s]/100 F1 50
BREAKER
0181 tClose Pulse 10 to 1000 1 [s]/100 F1 50
0182 Time Delay for close 0 to 20000 1 [s]/100 F1 0
Command
0183 Reserved
0184 tCB FLT ext.sign. 1 to 200 1 [s] F1 16 CT
0185 Remote Mode 0 to 1 1 - F73
0186 - 0188 Reserved
0189 CB Supervision? 0 to 1 1 - F63 0
018A Max CB Open Time 10 to 1000 1 [s]/100 F1 10
018B Max CB Close Time 10 to 1000 1 [s]/100 F1 10
018C - 0199 Reserved

019A DISTURBANCE Pre-Time 10 to 200 1 [s]/100 F1 10


V11V/EN CT v1.0 Communication Database

(CT) 13-(CT) 13-14 VAMP 11V

Values Default
Address Group Description Step Unit Format
range Value
RECORDER

019B Post TripTime 10 to 100 1 [s]/100 F1 10

019C Distrurb Rec Trig 0 to 1 1 - F65 0

019D Max record Time 10 to 400 1 [s]/100 F1 10

019E-01A4 Reserved

01A5 COMMISIONING Maintenace Mode 0 to 2 1 - F62 0

01A6 Test Pattern bits F36 00000000

01A7 Contact Test Time 0 to 20000 1 [s]/100 F1 10

01A8 Reserved

01A9 Functional Test Pattern 0 to 18 1 - F76 0

01AA Functional Test End 0 to 1 1 - F77 0

01AB Functional Test Time 10 to 20000 1 [s]/100 F1 10

01AC-01FF Reserved

CT
Communication Database V11V/EN CT v1.0

VAMP 11V (CT) 13-15

2.4.4 Page 2h : setting Group 1


Access in reading and in writing

Address Group Description Values Step Unit Format Default


range Value
0200 Setting Group 1 / V> ? 0-8 1 - F16 0
Protection
G1/Overvoltage
0201 V> Threshold 1 to 65535 1 [V]/10 F1
0202 V> Delay Type 1 to 15 1 - F18
0203 tV>/TMS/TD 1 to 65535 1 [s]/100 F1
0204 V> Reset Delay Type 0-1 1 - F41
0205 V> DMT tReset 1 to 65535 1 [s]/100 F1
0206 V>>? 0-8 1 - F16
0207 V>> Threshold 1 to 65535 1 [V]/10 F1
0208 tV>> 1 to 65535 1 [s]/100 F1
0209 V>>>? 0 to 15 1 - F16
020A V>>> Threshold 1 to 65535 1 [V]/10 F1
020B tV>>> 1 to 65535 1 [s]/100 F1
020C Setting Group 1 / V<? 0-8 1 - F16
Protection G1
/Undervoltage
020D V< Threshold 1 to 65535 1 [V]/10 F1
020E V< Delay Type 0 to 15 1 [-] F18
020F tV</TMS/TD 1 to 65535 1 [s] /100 F1
0210 V< Reset Delay Type 0-1 1 [-] F41
0211 V< DMT tReset 1 to 65535 1 [s] /100 F1
0212 V<<? 0-8 1 [-] F16
0213 V<< Threshold 1 to 65535 1 [V]/10 F1
0214 tV<< 1 to 65535 1 [s] /100 F1
0215 V<<<? 0-8 1 [-] F16
0216 V<<< Threshold 1 to 65535 1 [V]/10 F1
0217 tV<<< 1 to 65535 1 [s] /100 F1
0218 Setting Group 1 / V1<? 0-8 1 [-] F16
Protection G1
/Positive
sequence
undervoltage
CT
0219 V1< Threshold 1 to 65535 1 [V]/10 F1
021A V1< Delay Type 0 to 15 1 [-] F18
021B tV1< TMS/TD 1 to 65535 1 [s] /100 F1
021C V1< Reset Delay Type 0-1 1 [-] F41
021D V1< DMT tReset 1 to 65535 1 [s] /100 F1
021E V1<<? 0-8 1 [-] F16
021F V1<< Threshold 1 to 65535 1 [V]/10 F1
0220 tV1<< 1 to 65535 1 [s] /100 F1
V11V/EN CT v1.0 Communication Database

(CT) 13-(CT) 13-16 VAMP 11V

Address Group Description Values Step Unit Format Default


range Value
0221 Setting Group 1 / V2>? 0-8 1 [-] F16
Protection G1
/Negative
sequence
undervoltage
0222 V2> Threshold 1 to 65535 1 [V]/10 F1
0223 V2> Delay Type 0 to 15 1 [-] F18
0224 tV2> TMS/TD 1 to 65535 1 [s] /100 F1
0225 V2> Reset Delay Type 0-1 1 [-] F41
0226 V2> DMT tReset 1 to 65535 1 [s] /100 F1
0227 V2>>? 0-8 1 [-] F16
0228 V2>> Threshold 1 to 65535 1 [V]/10 F1
0229 tV2>> 1 to 65535 1 [s] /100 F1
022A Setting Group 1 / VN>? 0 to 4 1 [-] F95
Protection G1
/Earth fault
overvoltage
022B VN> Threshold 1 to 65535 1 [V]/10 F1
022C VN> Delay Type 0 to 15 1 [-] F18
022D tVN>/TMS/TD 1 to 65535 1 [s] /100 F1
022E VN> Reset Delay Type 0-1 1 [-] F41
022F VN> DMT tReset 1 to 65535 1 [s] /100 F1
0230 VN>>? 0 to 4 1 [-] F95
0231 VN>> Threshold 1 to 65535 1 [V]/10 F1
0232 tVN>> 1 to 65535 1 [s] /100 F1
0233 VN>>>? 0 to 4 1 [-] F95
0234 VN>>> Threshold 1 to 65535 1 [V]/10 F1
0235 tVN>>> 1 to 65535 1 [s] /100 F1
0236 Setting Group 1 / f1? 0 to 4 1 [-] F84
Protection G1
/Frequency
0237 f1 Threshold 1 to 65535 1 [Hz]/100 F1
0238 tf1 1 to 65535 1 [s] /100 F1
0239 f2? 0 to 4 1 [-] F84
023A f2 Threshold 1 to 65535 1 [Hz]/100 F1
CT 023B tf2 1 to 65535 1 [s] /100 F1
023C f3? 0 to 4 1 [-] F84
023D f3 Threshold 1 to 65535 1 [Hz]/100 F1
023E tf3 1 to 65535 1 [s] /100 F1
023F f4? 0 to 4 1 [-] F84
0240 f4 Threshold 1 to 65535 1 [Hz]/100 F1
0241 tf4 1 to 65535 1 [s] /100 F1
0242 f5? 0 to 4 1 [-] F84
0243 f5 Threshold 1 to 65535 1 [Hz]/100 F1
Communication Database V11V/EN CT v1.0

VAMP 11V (CT) 13-17

Address Group Description Values Step Unit Format Default


range Value
0244 tf5 1 to 65535 1 [s] /100 F1
0245 f6? 0 to 4 1 [-] F84
0246 f6 Threshold 1 to 65535 1 [Hz]/100 F1
0247 tf6 1 to 65535 1 [s] /100 F1
0252 Setting Group 1 / AUX1? 0 to 3 1 [-] F94
Protection G1
/Auxilirary timers
0253 tAUX1 0 to 60000 1 [s] /100 F1
0254 AUX2? 0 to 3 1 [-] F94
0255 tAUX2 0 to 60000 1 [s] /100 F1
0256 AUX3? 0 to 3 1 [-] F94
0257 tAUX3 0 to 60000 1 [s] /100 F1
0258 Setting group 1 Reverse Input Logic 0 to 5 1 [-] F35
/Inputs
configuration G1
0259 Maintenance Mode 0 to 5 1 [-] F35
025A Reset Latched Signaling 0 to 5 1 [-] F35
025B Reset Latched Outputs 0 to 5 1 [-] F35
025C Blocking tV> 0 to 5 1 [-] F35
025D Blocking tV>> 0 to 5 1 [-] F35
025E Blocking tV>>> 0 to 5 1 [-] F35
025F Blocking tV< 0 to 5 1 [-] F35
0260 Blocking tV<< 0 to 5 1 [-] F35
0261 Blocking tV<<< 0 to 5 1 [-] F35
0262 Blocking tV1< 0 to 5 1 [-] F35
0263 Blocking tV1<< 0 to 5 1 [-] F35
0264 Blocking tV2> 0 to 5 1 [-] F35
0265 Blocking tV2>> 0 to 5 1 [-] F35
0266 Blocking tVN> 0 to 5 1 [-] F35
0267 Blocking tVN>> 0 to 5 1 [-] F35
0268 Blocking tVN>>> 0 to 5 1 [-] F35
0269 Blocking tf1 0 to 5 1 [-] F35
026A Blocking tf2 0 to 5 1 [-] F35
026B Blocking tf3 0 to 5 1 [-] F35 CT
026C Blocking tf4 0 to 5 1 [-] F35
026D Blocking tf5 0 to 5 1 [-] F35
026E Blocking tf6 0 to 5 1 [-] F35
0272 AUX1 0 to 5 1 [-] F35
0273 AUX2 0 to 5 1 [-] F35
0274 AUX3 0 to 5 1 [-] F35
0275 AUX4 0 to 5 1 [-] F35
0276 AUX5 0 to 5 1 [-] F35
V11V/EN CT v1.0 Communication Database

(CT) 13-(CT) 13-18 VAMP 11V

Address Group Description Values Step Unit Format Default


range Value
0277 CB status 52A 0 to 5 1 [-] F35
0278 CB status 52B 0 to 5 1 [-] F35
0279 CB FLT ext. 0 to 5 1 [-] F35

027A Setting Group 2 0 to 5 1 [-] F35


027B Manual Close 0 to 5 1 [-] F35
027C Manual Trip 0 to 5 1 [-] F35
027D VTS 0 to 5 1 [-] F35
027E Strt Disturb 0 to 5 1 [-] F35
027F Local Mode 0 to 5 1 [-] F35
0280 Time synchr 0 to 5 1 [-] F35
0281 Setting group 1 Latched outputs 0 to 6 1 [-] F36
/Outputs
configuration G1
0282 Reverse outp. Logic 0 to 6 1 [-] F36
0283 Protect. Trip 0 to 6 1 [-] F36
0284 Protection Trip (pulse) 0 to 6 1 [-] F36
0285 Trip CB 0 to 6 1 [-] F36
0286 Close CB 0 to 6 1 [-] F36
0287 Alarm 0 to 6 1 [-] F36
0288 Start V> 0 to 6 1 [-] F36
0289 Start V>> 0 to 6 1 [-] F36
028A Start V>>> 0 to 6 1 [-] F36
028B Start V< 0 to 6 1 [-] F36
028C start V<< 0 to 6 1 [-] F36
028D start V<<< 0 to 6 1 [-] F36
028E start V1< 0 to 6 1 [-] F36
028F start V1<< 0 to 6 1 [-] F36
0290 start V2> 0 to 6 1 [-] F36
0291 Start V2>> 0 to 6 1 [-] F36
0292 Start VN> 0 to 6 1 [-] F36
0293 start VN>> 0 to 6 1 [-] F36
0294 Start VN>>> 0 to 6 1 [-] F36

CT 0295 Start f1 0 to 6 1 [-] F36


0296 Start f2 0 to 6 1 [-] F36
0297 Start f3 0 to 6 1 [-] F36
0298 Start f4 0 to 6 1 [-] F36
0299 Start f5 0 to 6 1 [-] F36
029A Start f6 0 to 6 1 [-] F36
029E AUX1 0 to 6 1 [-] F36
029F AUX2 0 to 6 1 [-] F36
02A0 AUX3 0 to 6 1 [-] F36
Communication Database V11V/EN CT v1.0

VAMP 11V (CT) 13-19

Address Group Description Values Step Unit Format Default


range Value
02A1 AUX4 0 to 6 1 [-] F36
02A2 AUX5 0 to 6 1 [-] F36
02A3 tV> 0 to 6 1 [-] F36
02A4 tV>> 0 to 6 1 [-] F36
02A5 tV>>> 0 to 6 1 [-] F36
02A6 tV< 0 to 6 1 [-] F36
02A7 tV<< 0 to 6 1 [-] F36
02A8 tV<<< 0 to 6 1 [-] F36
02A9 tV1< 0 to 6 1 [-] F36
02AA tV1<< 0 to 6 1 [-] F36
02AB tV2> 0 to 6 1 [-] F36
02AC tV2>> 0 to 6 1 [-] F36
02AD tVN> 0 to 6 1 [-] F36
02AE tVN>> 0 to 6 1 [-] F36
02AF tVN>>> 0 to 6 1 [-] F36
02B0 tf1 0 to 6 1 [-] F36
02B1 tf2 0 to 6 1 [-] F36
02B2 tf3 0 to 6 1 [-] F36
02B3 tf4 0 to 6 1 [-] F36
02B4 tf5 0 to 6 1 [-] F36
02B5 tf6 0 to 6 1 [-] F36
02B9 tAUX1 0 to 6 1 [-] F36
02BA tAUX2 0 to 6 1 [-] F36
02BB tAUX3 0 to 6 1 [-] F36
02BC CB Alarm 0 to 6 1 [-] F36
02BD tCB Faulty ext. 0 to 6 1 [-] F36
02BE Setting Group 1 0 to 6 1 [-] F36
02BF tVTS 0 to 6 1 [-] F36
02C0 fout 0 to 6 1 [-] F36
Setting group 1 Latched LEDs 0 to 5 1 [-] F39
/LED’s
02C1 configuration G1
02C2 Alarm 0 to 5 1 [-] F39
CT
02C3 Start V> 0 to 5 1 [-] F39
02C4 Start V>> 0 to 5 1 [-] F39
02C5 Start V>>> 0 to 5 1 [-] F39
02C6 Start V< 0 to 5 1 [-] F39
02C7 start V<< 0 to 5 1 [-] F39
02C8 start V<<< 0 to 5 1 [-] F39
02C9 start V1< 0 to 5 1 [-] F39
02CA start V1<< 0 to 5 1 [-] F39
V11V/EN CT v1.0 Communication Database

(CT) 13-(CT) 13-20 VAMP 11V

Address Group Description Values Step Unit Format Default


range Value
02CB start V2> 0 to 5 1 [-] F39
02CC Start V2>> 0 to 5 1 [-] F39
02CD Start VN> 0 to 5 1 [-] F39
02CE start VN>> 0 to 5 1 [-] F39
02CF Start VN>>> 0 to 5 1 [-] F39
02D0 Start f1 0 to 5 1 [-] F39
02D1 Start f2 0 to 5 1 [-] F39
02D2 Start f3 0 to 5 1 [-] F39
02D3 Start f4 0 to 5 1 [-] F39
02D4 Start f5 0 to 5 1 [-] F39
02D5 Start f6 0 to 5 1 [-] F39
02D9 AUX1 0 to 5 1 [-] F39
02DA AUX2 0 to 5 1 [-] F39
02DB AUX3 0 to 5 1 [-] F39
02DC AUX4 0 to 5 1 [-] F39
02DD AUX5 0 to 5 1 [-] F39
02DE tV> 0 to 5 1 [-] F39
02DF tV>> 0 to 5 1 [-] F39
02E0 tV>>> 0 to 5 1 [-] F39
02E1 tV< 0 to 5 1 [-] F39
02E2 tV<< 0 to 5 1 [-] F39
02E3 tV<<< 0 to 5 1 [-] F39
02E4 tV1< 0 to 5 1 [-] F39
02E5 tV1<< 0 to 5 1 [-] F39
02E6 tV2> 0 to 5 1 [-] F39
02E7 tV2>> 0 to 5 1 [-] F39
02E8 tVN> 0 to 5 1 [-] F39
02E9 tVN>> 0 to 5 1 [-] F39
02EA tVN>>> 0 to 5 1 [-] F39
02EB tf1 0 to 5 1 [-] F39
02EC tf2 0 to 5 1 [-] F39

CT 02ED
02EE
tf3
tf4
0 to 5
0 to 5
1
1
[-]
[-]
F39
F39
02EF tf5 0 to 5 1 [-] F39
02F0 tf6 0 to 5 1 [-] F39
02F4 tAUX1 0 to 5 1 [-] F39
02F5 tAUX2 0 to 5 1 [-] F39
02F6 tAUX3 0 to 5 1 [-] F39
02F7 Local Mode 0 to 5 1 [-] F39
02F8 CB Alarm 0 to 5 1 [-] F39
Communication Database V11V/EN CT v1.0

VAMP 11V (CT) 13-21

Address Group Description Values Step Unit Format Default


range Value
02F9 Maintenance Mode 0 to 5 1 [-] F39
02FA tCB FLT ext. 0 to 5 1 [-] F39
02FB Setting Group 0 to 5 1 [-] F39
02FC tVTS 0 to 5 1 [-] F39
02FD fout 0 to 5 1 [-] F39

CT
V11V/EN CT v1.0 Communication Database

(CT) 13-(CT) 13-22 VAMP 11V

2.4.5 Page 3h : setting Group 2


Access in reading and in writing

Address Group Description Values Step Unit Format Default


range Value
0300 Setting Group 2 / V> ? 0-8 1 - F16 0
Protection
G2/Overvoltage
0301 V> Threshold 1 to 65535 1 [V]/10 F1
0302 V> Delay Type 0 to 15 1 - F18
0303 tV>/TMS/TD 1 to 65535 1 [s]/100 F1
0304 V> Reset Delay Type 0-1 1 - F41
0305 V> DMT tReset 1 to 65535 1 [s]/100 F1
0306 V>>? 0-8 1 - F16
0307 V>> Threshold 1 to 65535 1 [V]/10 F1
0308 tV>> 1 to 65535 1 [s]/100 F1
0309 V>>>? 0 to 8 1 - F16
030A V>>> Threshold 1 to 65535 1 [V]/10 F1
030B tV>>> 1 to 65535 1 [s]/100 F1
030C Setting Group 2 / V<? 0 to 8 1 [-] F16
Protection G2
/Undervoltage
030D V< Threshold 1 to 65535 1 [V]/10 F1
030E V< Delay Type 0 to 15 1 [-] F18
030F tV</TMS/TD 1 to 65535 1 [s] /100 F1
0310 V< Reset Delay Type 0-1 1 [-] F41
0311 V< DMT tReset 1 to 65535 1 [s] /100 F1
0312 V<<? 0-8 1 [-] F16
0313 V<< Threshold 1 to 65535 1 [V]/10 F1
0314 tV<< 1 to 65535 1 [s] /100 F1
0315 V<<<? 0-8 1 [-] F16
0316 V<<< Threshold 1 to 65535 1 [V]/10 F1
0317 tV<<< 1 to 65535 1 [s] /100 F1
0318 Setting Group 2 / V1<? 0-8 1 [-] F16
Protection G2
/Positive
sequence
CT undervoltage
0319 V1< Threshold 1 to 65535 1 [V]/10 F1
031A V1< Delay Type 0 to 15 1 [-] F18
031B tV1< TMS/TD 1 to 65535 1 [s] /100 F1
031C V1< Reset Delay Type 0-1 1 [-] F41
031D V1< DMT tReset 1 to 65535 1 [s] /100 F1
031E V1<<? 0-8 1 [-] F16
031F V1<< Threshold 1 to 65535 1 [V]/10 F1
0320 tV1<< 1 to 65535 1 [s] /100 F1
Communication Database V11V/EN CT v1.0

VAMP 11V (CT) 13-23

Address Group Description Values Step Unit Format Default


range Value
0321 Setting Group 2 / V2>? 0-8 1 [-] F16
Protection G2
/Negative
sequence
undervoltage
0322 V2> Threshold 1 to 65535 1 [V]/10 F1
0323 V2> Delay Type 0 to 15 1 [-] F18
0324 tV2> TMS/TD 1 to 65535 1 [s] /100 F1
0325 V2> Reset Delay Type 0-1 1 [-] F41
0326 V2> DMT tReset 1 to 65535 1 [s] /100 F1
0327 V2>>? 0-8 1 [-] F16
0328 V2>> Threshold 1 to 65535 1 [V]/10 F1
0329 tV2>> 1 to 65535 1 [s] /100 F1
032A Setting Group 2 / UN>? 0 to 4 1 [-] F95
Protection G2
/Earth fault
overvoltage
032B VN> Threshold 1 to 65535 1 [V]/10 F1
032C VN> Delay Type 0 to 15 1 [-] F18
032D tVN>/TMS/TD 1 to 65535 1 [s] /100 F1
032E VN> Reset Delay Type 0-1 1 [-] F41
032F VN> DMT tReset 1 to 65535 1 [s] /100 F1
0330 VN>>? 0 to 4 1 [-] F95
0331 VN>> Threshold 1 to 65535 1 [V]/10 F1
0332 tVN>> 1 to 65535 1 [s] /100 F1
0333 VN>>>? 0 to 4 1 [-] F95
0334 VN>>> Threshold 1 to 65535 1 [V]/10 F1
0335 tVN>>> 1 to 65535 1 [s] /100 F1
0336 Setting Group 2 / f1? 0 to 4 1 [-] F84
Protection G2
/Frequency
0337 f1 Threshold 1 to 65535 1 [Hz]/100 F1
0338 tf1 1 to 65535 1 [s] /100 F1
0339 f2? 0 to 4 1 [-] F84
033A f2 Threshold 1 to 65535 1 [Hz]/100 F1
033B tf2 1 to 65535 1 [s] /100 F1 CT
033C f3? 0 to 4 1 [-] F84
033D f3 Threshold 1 to 65535 1 [Hz]/100 F1
033E tf3 1 to 65535 1 [s] /100 F1
033F f4? 0 to 4 1 [-] F84
0340 f4 Threshold 1 to 65535 1 [Hz]/100 F1
0341 tf4 1 to 65535 1 [s] /100 F1
0342 f5? 0 to 4 1 [-] F84
0343 f5 Threshold 1 to 65535 1 [Hz]/100 F1
V11V/EN CT v1.0 Communication Database

(CT) 13-(CT) 13-24 VAMP 11V

Address Group Description Values Step Unit Format Default


range Value
0344 tf5 1 to 65535 1 [s] /100 F1
0345 f6? 0 to 4 1 [-] F84
0346 f6 Threshold 1 to 65535 1 [Hz]/100 F1
0347 tf6 1 to 65535 1 [s] /100 F1
0352 Setting Group 2 / AUX1? 0 to 3 1 [-] F94
Protection G2
/Auxilirary timers
0353 tAUX1 1 to 60000 1 [s] /100 F1
0354 AUX2? 0 to 3 1 [-] F94
0355 tAUX2 1 to 60000 1 [s] /100 F1
0356 AUX3? 0 to 3 1 [-] F94
0257 tAUX3 1 to 60000 1 [s] /100 F1
0358 Setting group 2 Reverse Input Logic 0 to 5 1 [-] F35
/Inputs
configuration G2
0359 Maintenance Mode 0 to 5 1 [-] F35
035A Reset Latched Signaling 0 to 5 1 [-] F35
035B Reset Latched Outputs 0 to 5 1 [-] F35
035C Blocking tV> 0 to 5 1 [-] F35
035D Blocking tV>> 0 to 5 1 [-] F35
035E Blocking tV>>> 0 to 5 1 [-] F35
035F Blocking tV< 0 to 5 1 [-] F35
0360 Blocking tV<< 0 to 5 1 [-] F35
0361 Blocking tV<<< 0 to 5 1 [-] F35
0362 Blocking tV1< 0 to 5 1 [-] F35
0363 Blocking tV1<< 0 to 5 1 [-] F35
0364 Blocking tV2> 0 to 5 1 [-] F35
0365 Blocking tV2>> 0 to 5 1 [-] F35
0366 Blocking tVN> 0 to 5 1 [-] F35
0367 Blocking tVN>> 0 to 5 1 [-] F35
0368 Blocking tVN>>> 0 to 5 1 [-] F35
0369 Blocking tf1 0 to 5 1 [-] F35
036A Blocking tf2 0 to 5 1 [-] F35

CT 036B Blocking tf3 0 to 5 1 [-] F35


036C Blocking tf4 0 to 5 1 [-] F35
036D Blocking tf5 0 to 5 1 [-] F35
036E Blocking tf6 0 to 5 1 [-] F35
0372 AUX1 0 to 5 1 [-] F35
0373 AUX2 0 to 5 1 [-] F35
0374 AUX3 0 to 5 1 [-] F35
0375 AUX4 0 to 5 1 [-] F35
0376 AUX5 0 to 5 1 [-] F35
Communication Database V11V/EN CT v1.0

VAMP 11V (CT) 13-25

Address Group Description Values Step Unit Format Default


range Value
0377 CB status 52A 0 to 5 1 [-] F35
0378 CB status 52B 0 to 5 1 [-] F35
0379 CB FLT ext. 0 to 5 1 [-] F35

037A Setting Group 2 0 to 5 1 [-] F35


0327B Manual Close 0 to 5 1 [-] F35
037C Manual Trip 0 to 5 1 [-] F35
037D VTS 0 to 5 1 [-] F35
037E Strt Disturb 0 to 5 1 [-] F35
037F Local Mode 0 to 5 1 [-] F35
0380 Time synchr 0 to 5 1 [-] F35
0381 Setting group 2 Latched outputs 0 to 6 1 [-] F36
/Outputs
configuration G2
0382 Reverse outp. Logic 0 to 6 1 [-] F36
0383 Protect. Trip 0 to 6 1 [-] F36
0384 Protection Trip (pulse) 0 to 6 1 [-] F36
0385 Trip CB 0 to 6 1 [-] F36
0386 Close CB 0 to 6 1 [-] F36
0387 Alarm 0 to 6 1 [-] F36
0388 Start V> 0 to 6 1 [-] F36
0389 Start V>> 0 to 6 1 [-] F36
038A Start V>>> 0 to 6 1 [-] F36
038B Start V< 0 to 6 1 [-] F36
038C start V<< 0 to 6 1 [-] F36
038D start V<<< 0 to 6 1 [-] F36
038E start V1< 0 to 6 1 [-] F36
038F start V1<< 0 to 6 1 [-] F36
0390 start V2> 0 to 6 1 [-] F36
0391 Start V2>> 0 to 6 1 [-] F36
0392 Start VN> 0 to 6 1 [-] F36
0393 start VN>> 0 to 6 1 [-] F36
0394 Start VN>>> 0 to 6 1 [-] F36
0395 Start f1 0 to 6 1 [-] F36 CT
0396 Start f2 0 to 6 1 [-] F36
0397 Start f3 0 to 6 1 [-] F36
0398 Start f4 0 to 6 1 [-] F36
0399 Start f5 0 to 6 1 [-] F36
039A Start f6 0 to 6 1 [-] F36
039E AUX1 0 to 6 1 [-] F36
039F AUX2 0 to 6 1 [-] F36
03A0 AUX3 0 to 6 1 [-] F36
V11V/EN CT v1.0 Communication Database

(CT) 13-(CT) 13-26 VAMP 11V

Address Group Description Values Step Unit Format Default


range Value
03A1 AUX4 0 to 6 1 [-] F36
03A2 AUX5 0 to 6 1 [-] F36
03A3 tV> 0 to 6 1 [-] F36
03A4 tV>> 0 to 6 1 [-] F36
03A5 tV>>> 0 to 6 1 [-] F36
03A6 tV< 0 to 6 1 [-] F36
03A7 tV<< 0 to 6 1 [-] F36
03A8 tV<<< 0 to 6 1 [-] F36
03A9 tV1< 0 to 6 1 [-] F36
03AA tV1<< 0 to 6 1 [-] F36
03AB tV2> 0 to 6 1 [-] F36
03AC tV2>> 0 to 6 1 [-] F36
03AD tVN> 0 to 6 1 [-] F36
03AE tVN>> 0 to 6 1 [-] F36
03AF tVN>>> 0 to 6 1 [-] F36
03B0 tf1 0 to 6 1 [-] F36
03B1 tf2 0 to 6 1 [-] F36
03B2 tf3 0 to 6 1 [-] F36
03B3 tf4 0 to 6 1 [-] F36
03B4 tf5 0 to 6 1 [-] F36
03B5 tf6 0 to 6 1 [-] F36
03B9 tAUX1 0 to 6 1 [-] F36
03BA tAUX2 0 to 6 1 [-] F36
03BB tAUX3 0 to 6 1 [-] F36
03BC CB Alarm 0 to 6 1 [-] F36
03BD tCB Faulty ext. 0 to 6 1 [-] F36
03BE Setting Group 1 0 to 6 1 [-] F36
03BF tVTS 0 to 6 1 [-] F36
03C0 fout 0 to 6 1 [-] F36
Setting group 2 Latched LEDs 0 to 5 1 [-] F39
/LED’s
03C1 configuration G2

CT 03C2 Alarm 0 to 5 1 [-] F39


03C3 Start V> 0 to 5 1 [-] F39
03C4 Start V>> 0 to 5 1 [-] F39
03C5 Start V>>> 0 to 5 1 [-] F39
03C6 Start V< 0 to 5 1 [-] F39
03C7 start V<< 0 to 5 1 [-] F39
03C8 start V<<< 0 to 5 1 [-] F39
03C9 start V1< 0 to 5 1 [-] F39
03CA start V1<< 0 to 5 1 [-] F39
Communication Database V11V/EN CT v1.0

VAMP 11V (CT) 13-27

Address Group Description Values Step Unit Format Default


range Value
03CB start V2> 0 to 5 1 [-] F39
03CC Start V2>> 0 to 5 1 [-] F39
03CD Start VN> 0 to 5 1 [-] F39
03CE start VN>> 0 to 5 1 [-] F39
03CF Start VN>>> 0 to 5 1 [-] F39
03D0 Start f1 0 to 5 1 [-] F39
03D1 Start f2 0 to 5 1 [-] F39
03D2 Start f3 0 to 5 1 [-] F39
03D3 Start f4 0 to 5 1 [-] F39
03D4 Start f5 0 to 5 1 [-] F39
03D5 Start f6 0 to 5 1 [-] F39
03D9 AUX1 0 to 5 1 [-] F39
03DA AUX2 0 to 5 1 [-] F39
03DB AUX3 0 to 5 1 [-] F39
03DC AUX4 0 to 5 1 [-] F39
03DD AUX5 0 to 5 1 [-] F39
03DE tV> 0 to 5 1 [-] F39
03DF tV>> 0 to 5 1 [-] F39
03E0 tV>>> 0 to 5 1 [-] F39
03E1 tV< 0 to 5 1 [-] F39
03E2 tV<< 0 to 5 1 [-] F39
03E3 tV<<< 0 to 5 1 [-] F39
03E4 tV1< 0 to 5 1 [-] F39
03E5 tV1<< 0 to 5 1 [-] F39
03E6 tV2> 0 to 5 1 [-] F39
03E7 tV2>> 0 to 5 1 [-] F39
03E8 tVN> 0 to 5 1 [-] F39
03E9 tVN>> 0 to 5 1 [-] F39
03EA tVN>>> 0 to 5 1 [-] F39
03EB tf1 0 to 5 1 [-] F39
03EC tf2 0 to 5 1 [-] F39
03ED tf3 0 to 5 1 [-] F39
CT
03EE tf4 0 to 5 1 [-] F39
03EF tf5 0 to 5 1 [-] F39
03F0 tf6 0 to 5 1 [-] F39
03F4 tAUX1 0 to 5 1 [-] F39
03F5 tAUX2 0 to 5 1 [-] F39
03F6 tAUX3 0 to 5 1 [-] F39
03F7 Local Mode 0 to 5 1 [-] F39
03F8 CB Alarm 0 to 5 1 [-] F39
V11V/EN CT v1.0 Communication Database

(CT) 13-(CT) 13-28 VAMP 11V

Address Group Description Values Step Unit Format Default


range Value
03F9 Maintenance Mode 0 to 5 1 [-] F39
03FA tCB FLT ext. 0 to 5 1 [-] F39
03FB Setting Group 0 to 5 1 [-] F39
03FC tVTS 0 to 5 1 [-] F39
03FD fout 0 to 5 1 [-] F39

CT
Communication Database V11V/EN CT v1.0

VAMP 11V (CT) 13-29

2.4.6 Page 4h : remote controls (AN)


Access in writing. (MODBUS Function 5)

Address Group Description Values Step Unit Format Default


range Value
0400 Remote Remote control word 1 0 to 15 bits - F38 0
control
0401 Remote control word 2 0 to 15 bits - F38A 0

0402 Remote control word 3 0 to 15 bits - F38B 0

2.4.7 Pages 5h/6h


These pages are reserved
2.4.8 Page 7h
Access in quick reading only (MODBUS 07 function)

Address Group Description Values Step Unit Format Default


range Value
0700 Quick reading Relay status description 1 - F49 0
byte

2.4.9 Page 8h : time synchronisation


Access in writing for n words (function 16). The time synchronisation format is based on 8
bits (4 words) ( Inverted IEC 870-5-4 CP56Time2a):.

Address Nb Mask
Timer Values range Unit
(hex) bytes (hex)

1 (Hi)
0800 0 – 99
Year 1 (Lo) 7F Year
(2000-2093)
Month 1 (Hi) 0F 1 - 12 month
1–7
Day of week 0801 1 (Lo) E0 Day
(Monday – Sunday)
day of month 1 (Lo) 1F 1 – 31 Day
0–1
Season 1 (Hi) 80 (summer-winter)
Not used
Hour 0802 1 (Hi) 1F 0-23 Hour CT
Invalidity 1 (Lo) 80 0 -1 (valid – invalid)
Minute 1 (Lo) 3F 0-59 Minute
Millisecond pF+pf 0803 2 FFFF 0 – 59999 ms
V11V/EN CT v1.0 Communication Database

(CT) 13-(CT) 13-30 VAMP 11V

2.4.10 Mapping access characteristics

• Description of accessible addresses in reading of words (function 03 and 04).

PAGE 00h PAGE 01h PAGE 02h


0000h to 0054h 0100h to 0184h 0200h to 02FAh
PAGE 03h
0300h to 03F6h

• Definition of accessible addresses in writing of 1 word (function 06).


PAGE 01h PAGE 02h PAGE 03h
0100h to 0184h 0200h to 02FAh 0300h to 03FAh

• Definition of accessible addresses in writing of n words (function 16).

PAGE 01h PAGE 02h PAGE 03h


0100h to 0184h 0200h to 02FAh 0300h to 03FAh
PAGE 08h
0800h to 0803h

• Definition of accessible addresses in reading of bits (function 01 and 02).


Not available

• Definition of accessible addresses in writing of 1 bit (function 05).


PAGE 04h
0400h to 0402h
WARNING: THE BITS NUMBER MUST NOT BE HIGHER THAN 16.

CT
Communication Database V11V/EN CT v1.0

VAMP 11V (CT) 13-31

2.4.11 Page 9h to 21h: disturbance record data (25 pages)

Access in words writing (function 03)


Each disturbance mapping page contain 250 words.

Address Contents
0900h to 09FAh 250 disturbance data words
0A00h to 0AFAh 250 disturbance data words
0B00h to 0BFAh 250 disturbance data words
0C00h to 0CFAh 250 disturbance data words
0D00h to 0DFAh 250 disturbance data words
0E00h to 0DFAh 250 disturbance data words
0F00h to 0FFAh 250 disturbance data words
1000h to 10FAh 250 disturbance data words
1100h to 11FAh 250 disturbance data words
1200h to 12FAh 250 disturbance data words
1300h to 13FAh 250 disturbance data words
1400h to 14FAh 250 disturbance data words
1500h to 15FAh 250 disturbance data words
1600h to 16FAh 250 disturbance data words
1700h to 17FAh 250 disturbance data words
1800h to 18FAh 250 disturbance data words
1900h to 19FAh 250 disturbance data words
1A00h to 1AFAh 250 disturbance data words
1B00h to 1BFAh 250 disturbance data words
1C00h to 1CFAh 250 disturbance data words
1D00h to 1DFAh 250 disturbance data words
1E00h to 1EFAh 250 disturbance data words
1F00h to 1FFAh 250 disturbance data words
2000h to 20FAh 250 disturbance data words
2100h to 21FAh 250 disturbance data words
NB: The disturbance data pages contain values of one channel from one
given disturbance record.

CT
V11V/EN CT v1.0 Communication Database

(CT) 13-(CT) 13-32 VAMP 11V

2.4.11.1 Meaning of each value channel

• VA, VB, VC and VN channels:

The value is an signed 16 bits word equivalent to the ADC value

Calculation formula for phase voltage values

Values in Volts can be calculated in following way:

sample_UA ⋅ Internal_PhA ⋅ Phase_Primary_VT_Un


Value UA = 2 ⋅
Phase_ Secondary _VT_Un ⋅ 2000
sample_UB⋅ Internal_PhB ⋅ Phase_Primary_VT_Un
Value UB = 2 ⋅
Phase_ Secondary _VT_Un ⋅ 2000
sample_UC ⋅ Internal_PhC ⋅ Phase_Primary_VT_Un
Value UC = 2 ⋅
Phase_ Secondary _VT_Un ⋅ 2000
Where:
Internal_PhA, Internal_PhB, Internal_PhC: Internal scalling (see point 2.4.17 (Page 38h to 3Ch))

Calculation formula for neutral voltage values

Value in Volts can be calculated in following way:

sample_UN ⋅ Internal_N ⋅ Earth_Primary_VT_Uen


Value UN = 2 ⋅
Earth_ Secondary _VT_Uen ⋅ 2000
Where:
Internal_N: Internal scalling (see point 2.4.17 (Page 38h to 3Ch))

• Frequency channel:
Time between two samples in microseconds

• Logic channels:

Logic channel Contents


Bit 0 Binary Input 1
Bit 1 Binary Input 2
Bit 2 Binary Input 3
Bit 3 Binary Input 4
Bit 4 Binary Input 5
Bit 5 Binary Input 6
Bit 6 None (reserved)
Bit 7 None (reserved)
CT Bit 8 Output RL1
Bit 9 Output RL2
Bit 10 Output RL3
Bit 11 Output RL4
Bit 12 Output RL5
Bit 13 Output RL6
Bit 14 Protection Trip
Bit 15 Start of protection which trips
Communication Database V11V/EN CT v1.0

VAMP 11V (CT) 13-33

2.4.12 Page 22h: disturbance record index frame


Access in word reading (function 03)

Address Contents
2200h Disturbance data index frame
Disturbance record index frame
Word Contents
n° 1 Disturbance record number
n° 2 Disturbance record finish date (second)
n° 3 Disturbance record finish date (second)
n° 4 Disturbance record finish date (millisecond)
n° 5 Disturbance record finish date (millisecond)
n° 6 Disturbance record starting condition :
1 : tripping
2 : instantaneous
3 : remote command
4 : logic input

n° 7 Frequency at the post-time beginning

2.4.13 Page 35h (addresses 3500h to 354Ah) : event record data (9 words)
Word n° 1: Event meaning
Word n° 2: MODBUS associated value
Word n° 3: MODBUS address
Word n° 4: Reserved
Words n° 5 & 6 & 7 & 8: Event date is Inverted IEC 870-5-4 CP56Time2a:
See format Page 8h
Word n° 9: Acknowledge
0=event non acknowledged
1= event acknowledged)

MODBUS
Code Meaning of the event Type
address

00 No event -
01 CB closing (Remote/menu HMI) F38 ↑ 0400h (bit 15)
CT
02 CB tripping (Remote/menu HMI) F38 ↑ 0400h (bit 7)
03 Reset latched outputs (Remote) F38 ↑ 0400h (bit 2)
04 Reset signaling (Remote) F38 ↑ 0400h (bit 1)
05 Reset signaling and latched outputs (Remote) F38 ↑ 0400h (bit 3)
06 Clear fault and disturbance recorder F38A ↑ 0401h (bit 0)
07 Clear event recorder F38A ↑ 0401h (bit 1)
08 Reserved
V11V/EN CT v1.0 Communication Database

(CT) 13-(CT) 13-34 VAMP 11V

MODBUS
Code Meaning of the event Type
address

09 Warm restart ↑ -
10 START V> F37↑↓ 0021h (bit 0)
11 START V>> F37↑↓ 0022h (bit 0)
12 START V>>> F37↑↓ 0023h (bit 0)
13 START V< F37↑↓ 0024h (bit 0)
14 START V<< F37↑↓ 0025h (bit 0)
15 START V<<< F37↑↓ 0026h (bit 0)
16 START VN> F37↑↓ 0027h (bit 0)
17 START VN>> F37↑↓ 0028h (bit 0)
18 START VN>>> F37↑↓ 0029h (bit 0)
19 START V1< F37↑↓ 002Ch (bit 0)
20 START V1<< F37↑↓ 002Dh (bit 0)
21 START V2> F37↑↓ 002Ch (bit 0)
22 START V2>> F37↑↓ 002Dh (bit 0)
23 START f1 F37↑↓ 002Dh (bit 0)
24 START f2 F30 ↑ 001Bh (value 4)
25 START f3 F31A ↑ 001Ah (bit 10)
26 START f4 F51 ↑↓ 002Ah (bit 0)
27 START f5 F11 ↑↓ 0010h
28 START f6 F24 ↑↓ 0013h
29 Reserved F37↑↓ 0023h (bit 0)
30 Reserved F37↑↓ 0023h (bit 6)
31 Reserved F50 ↑↓ 002Dh (bit 0)
32 Start Aux1 F50 ↑↓ 002Dh (bit 6)
33 Start Aux2 F51 ↑↓ 0028 (bit 6)
34 Start Aux3 F51 ↑↓ 0029h (bit 6)
35 CB Fail Ext. F32↑ 0009h (bit 0)
36 CB status: opened F30 ↑ 001Bh (value 0)
37 CB status: closed F30 ↑ 001Bh (value 1)
38 CB status: faulty F30 ↑ 001Bh (value 3)
39 CB status: undefined F30 ↑ 001Bh (value 4)
CT 40 tV> F31 ↑↓ 0019h (bit 4)
41 tV>> F31 ↑↓ 0019h (bit 5)
42 tV>>> F31A ↑↓ 0020h (bit 5)
43 tV< F31A ↑↓ 0020h (bit 6)
44 tV<< F31 ↑↓ 0019h (bit 8)
45 tV<<< F31 ↑↓ 0019h (bit 10)
46 tVN> F51 ↑↓ 0027h (bit 0)
47 tVN>> F51 ↑↓ 0028h (bit 0)
Communication Database V11V/EN CT v1.0

VAMP 11V (CT) 13-35

MODBUS
Code Meaning of the event Type
address

48 tVN>>> F38 ↑ 0400h (bit 8)


49 tV1< F38 ↑ 0400h (bit 9)
50 tV1<< F38 ↑ 0400h (bit 5)
51 tV2>
52 tV2>>
53 tf1
54 tf2
55 tf3 F38A↑ 0401h (bit 9)
56 tf4 F38A↑ 0401h (bit 5)
57 tf5 F38A↑ 0401h (bit 14)
58 tf6 F38A↑ 0401h (bit 15)
59 Reserved ↑
60 Reserved F38A↑ 0401h (bit 3)
61 Reserved
62 tAUX1
63 tAUX2
64 tAUX3 F31A ↑ 001Ah (bit 10)
65 tCB Faulty External Signal. F31A ↑ 001Ah (bit 10)
66 CHANGE OF INPUT LOGIC STATE F11 ↑↓ 0010h
67 CHANGE OF OUTPUT LOGIC STATE F24 ↑↓ 0013h
68 Setting Group 1 active F32↑ 0009h (bit 0)
69 Setting Group 2 active F32↑ 0009h (bit 1)
70 tV> Alarm
71 tV>> Alarm
72 tV>>> Alarm
73 tV< Alarm
74 tV<< Alarm
75 tV<<< Alarm
76 tVN> Alarm
77 tVN>> Alarm
78 tVN>>> Alarm
79 tV1< Alarm CT
80 tV1<< Alarm
81 tV2> Alarm
82 tV2>> Alarm
83 tf1 Alarm
84 tf2 Alarm
85 tf3 Alarm
86 tf4 Alarm
V11V/EN CT v1.0 Communication Database

(CT) 13-(CT) 13-36 VAMP 11V

MODBUS
Code Meaning of the event Type
address

87 tf5 Alarm
88 tf6 Alarm
89-91 Reserved
92 tAUX1 Alarm
93 tAUX2 Alarm
94 tAUX3 Alarm
95 Reserved
96 Local CTRL mode F61↑ 001Eh (value: 2)
97 Remote CTRL mode F61↑ 001Eh (value: 1)
98 Local and remote CTRL mode F61↑ 001Eh (value: 0)
99 Setting change to Group 1 (Remote) F38↑ 0400h (bit 6)
100 Setting change to Group 2 (Remote) F38↑ 0400h (bit 11)
101 Reserved
102 Setting Group 2 set via Input F104↑↓ 0035h (bit 8)
103 Relays Test (Commissiong Test) active ↑ -
104 Functional test V> ON ↑ -
105 Functional test V> OFF ↑ -
106 Functional test V>> ON ↑ -
107 Functional test V>> OFF ↑ -
108 Functional test V>>> ON ↑ -
109 Functional test V>>> OFF ↑ -
110 Functional test V< ON ↑ -
111 Functional test V< OFF ↑ -
112 Functional test V<< ON ↑ -
113 Functional test V<< OFF ↑ -
114 Functional test V<<< ON ↑ -
115 Functional test V<<< OFF ↑ -
116 Functional test VN> ON ↑ -
117 Functional test VN> OFF ↑ -
118 Functional test VN>> ON ↑ -
119 Functional test VN>> OFF ↑ -
CT 120 Functional test VN>>> ON ↑ -
121 Functional test VN>>> OFF ↑ -
122 Functional test V2> ON ↑ -
123 Functional test V2> OFF ↑ -
124 Functional test V2>> ON ↑ -
125 Functional test V2>> OFF ↑ -
126 Functional test V1< ON ↑ -
127 Functional test V1< OFF ↑ -
Communication Database V11V/EN CT v1.0

VAMP 11V (CT) 13-37

MODBUS
Code Meaning of the event Type
address

128 Functional test f1 ON ↑ -


129 Functional test f1 OFF ↑ -
130 Functional test f2 ON ↑ -
131 Functional test f2 OFF ↑ -
132 Functional test f3 ON ↑ -
133 Functional test f3 OFF ↑ -
134 Voltage Protection disable status F12↑↓ 0011h
135 Protection disable status F12A↑↓ 0012h
136 Blocking tV> active F37↑↓ 0021h (bit 4)
137 Blocking tV>> active F37↑↓ 0022h (bit 4)
138 Blocking tV>>> active F37↑↓ 0023h (bit 4)
139 Blocking tV< active F37↑↓ 0024h (bit 4)
140 Blocking tV<< active F37↑↓ 0025h (bit 4)
141 Blocking tV<<< active F37↑↓ 0026h (bit 4)
142 Blocking tV1< active F50↑↓ 0027h (bit 4)
143 Blocking tV1<< active F50↑↓ 0028h (bit 4)
144 Blocking tV2> active F50↑↓ 0028h (bit 4)
145 Blocking tV2>> active F50↑↓ 002Ch (bit 4)
146 Blocking tVN> active F50↑↓ 002Dh (bit 4)
147 Blocking tVN>> active F50↑↓ 002Ah (bit 4)
148 Blocking tVN>>> active F50↑↓ 002Bh (bit 4)
149 Blocking tf1 active F50↑↓ 0032h (bit 4)
150 Blocking tf2 active F50↑↓ 0033h (bit 4)
151 Blocking tf3 active F50↑↓ 0034h (bit 4)
152 Blocking tf4 active F50↑↓ 0035h (bit 4)
153 Blocking tf5 active F50↑↓ 0036h (bit 4)
154 Blocking tf6 active F50↑↓ 0037h (bit 4)
155 Reserved
156 Reserved
157 Reserved
158 Acknowledgement of the hardware alarm F38↑ 0401h (bit 5)
159 Disable acknowledgment of events F38↑ 0400h (bit 12)
CT
160 Acknowledgment of the oldest event F38↑ 0400h (bit 13)
161 Acknowledgment of the oldest fault F38↑ 0400h (bit 14)
162 Acknowledgment of the oldest disturbance recorder F38A↑ 0401h (bit 8)
163 Disturbance recorder remote start F38A↑ 0401h (bit 5)
164 Fault counter reset F38A↑ 0401h (bit 12)
165 Control counter reset F38A↑ 0401h (bit 13)
166 Maintenance mode F38A↑ 0401h (bit 6)
V11V/EN CT v1.0 Communication Database

(CT) 13-(CT) 13-38 VAMP 11V

MODBUS
Code Meaning of the event Type
address

167 End of maintenance mode F38A↑ 0401h (bit 7)


168 Manual Close via Input ↑ -
169 Manual Close via Function Key ↑ -
170 Manual Trip via Input ↑ -
171 Manual trip via Function Key ↑ -
172 Start Disturbance recorder via Input ↑ -
173 Local CTRL mode via Input active ↑ -
174 Local CTRL mode via HMI or RS485 active ↑ -
175 Administrator password entered ↑ -
176 Protection password entered ↑ -
177 Control password entered ↑ -
178 Reset LEDs and latched outputs via HMI (C key) ↑ -
179 Reset signalling via Input F104↑ 0035h (bit 1)
180 Reset latched outputs via Input F104↑ 0035h (bit 2)
181 Reset signalling on close ↑ -
182 State of CB Alarm F31A↑↓ 001Ah (bit 2)
183 Alarm VTS ↑↓ -
184 f<> internally locked (fOUT) ↑↓ -
185 f<> blocked (Remote/menu HMI) ↑↓ -

Note: The double arrow ↑↓ means the event is generated on event


occurrence (↑) and on event disappearance (↓).
On event occurrence, the corresponding bit of the associated format is set to « 1 ».
On event disappearance, the corresponding bit of the associated format is set to
« 0 ».
2.4.14 Page 36h
Most older event data
Access in word reading (function 03)

Address Contents

3600h Most older event data

2.4.15 Page 37h : fault record value data


CT
Access in word reading (function 03)

Address Contents

3700h Fault value record n°1


3701h Fault value record n°2
3702h Fault value record n°3
3703h Fault value record n°4
3704h Fault value record n°5
Communication Database V11V/EN CT v1.0

VAMP 11V (CT) 13-39

Address Contents

3705h Fault value record n°6


3706h Fault value record n°7
3707h Fault value record n°8
3708h Fault value record n°9
3709h Fault value record n°10
3710h Fault value record n°11
3711h Fault value record n°12
3712h Fault value record n°13
3713h Fault value record n°14
3714h Fault value record n°15
3715h Fault value record n°16
3716h Fault value record n°17
3717h Fault value record n°18
3718h Fault value record n°19
3719h Fault value record n°20

Word n° 1 : Fault number


Words n° 2 & 3 & 4 & 5: see table below (Inverted IEC 870-5-4 CP56Time2a)

Nb
Address Mask
Timer byte Values range Unit
(hex) (hex)
s

1 (Hi)
Word n° 2 0 – 99
Year 1 (Lo) 7F Year
(2000-2093)
Month 1 (Hi) 0F 1 - 12 month
1–7
Day of week Word n° 3 1 (Lo) E0
Not used
Day

day of month 1 (Lo) 1F 1 – 31 Day


0–1
Season 1 (Hi) 80 (summer-winter)
Not used
Hour Word n° 4 1 (Hi) 1F 0-23 Hour
Invalidity 1 (Lo) 80 0 -1 (valid – invalid)
Minute 1 (Lo) 3F 0-59 Minute
CT
Millisecond pF+pf Word n° 5 2 FFFF 0 – 59999 ms (included s)

Word n° 6 : Reserved
Word n° 7 : Active setting group during the fault (1 or 2)
Word n° 8 : Fault origin
0= none
1= phase A
V11V/EN CT v1.0 Communication Database

(CT) 13-(CT) 13-40 VAMP 11V

2= phase B
3= phase C
4= phases A-B
5= phases A-C
6= phases B-C
7= phases A-B-C
8= earth
Word n° 9: Fault recording starting origin
Fault nature code meaning

Code Fault origin

00 Null event
01 Reserved

03 tV> trip
04 tV>> trip
05 tV>>> trip
06 tVN> trip
07 tVN>> trip
08 tVN>>> trip
09 Reserved

10
11 t Aux 1 trip
12 t Aux 2 trip
13 tU2> trip
14 Reserved
15 t Aux 3 trip
16 t Aux 4 trip
17 CB Fail trip
18
19 Reserved
20 CBext trip

Word n° 10: Fault value voltage (nominal value)

CT Word n° 11: Phase A voltage value (nominal value)


Word n° 12: Phase B voltage value (nominal value)
Word n° 13: Phase C voltage value (nominal value)
Word n° 14: Earth voltage value (nominal value)
Word n° 15: Acknowledge of fault 0 : fault non-acknowledged
1 : fault acknowledged
2.4.15.1 Calculation formula for phase voltage values
Line phase voltage value (primary value) = phase sampled value (e.g. word 10, 11, 12 or 13)
* {line primary VT ratio (address 0120h)/Line VT sec (address 0121h)} V/10
Communication Database V11V/EN CT v1.0

VAMP 11V (CT) 13-41

2.4.15.2 Calculation formula for neutral voltage values


Neutrale voltage value (primary value) = phase sampled value (e.g. word 10, 11, 12 or 13) *
{line primary VT ratio (address 0122h)/Line VT sec (address 0123h)} V/10
2.4.16 Page 3Eh : most older Fault record value data
Access in word reading (function 03)

Address Contents

3E00h Most older Fault record

2.4.17 Page 38h to 3Ch: Disturbance recorder


Selection of the disturbance record and channel (36 bytes are uploaded for each address
reading)
Access in word reading (function 03)

Address Disturbance record number Format


3800h 1 VA
3801h 1 VB
3802h 1 VC
3803h 1 VN
3804h 1 Frequency
3805h 1 Logic input and outputs
3900h 2 VA
3901h 2 VB
3902h 2 VC
3903h 2 VN
3904h 2 Frequency
3905h 2 Logic input and outputs
3A00h 3 VA
3A01h 3 VB
3A02h 3 VC
3A03h 3 VN
3A04h 3 Frequency
3A05h 3 Logic input and outputs CT
3B00h 4 VA
3B01h 4 VB
3B02h 4 VC
3B03h 4 VN
3B04h 4 Frequency
3B05h 4 Logic input and outputs
3C00h 1 VA
V11V/EN CT v1.0 Communication Database

(CT) 13-(CT) 13-42 VAMP 11V

3C01h 1 VB
3C02h 1 VC
3C03h 1 VN
3C04h 1 Frequency
3C05h 1 Logic input and outputs

Word n° 1 : Number of samples included in the mapping


Word n° 2 : Sample number in pre-time
Word n° 3 : Sample number in post-time
Word n° 4 : Line VT primary nominal voltage (Phase_Primary_VT_Un)
Word n° 5 : Line VT secondary nominal voltage (Phase_ Secondary _VT_Un)
Word n° 6 : E/GND VT primary nominal voltage (Earth_Primary_VT_Uen)
Word n° 7 : E/GND VT secondary nominal voltage (Earth_ Secondary _VT_Uen)
1)
Float n° 1 : Phase A Internal PhA ratio (Internal_PhA)
1)
Float n° 2 : Phase B internal PhB ratio (Internal_PhB)
1)
Float n° 3 : Phase C internal PhC ratio (Internal_PhC)
1)
Float n° 4 : Earth internal ratio (Internal_N)
Word n° 8 : Mapping last page number
Word n° 9 : Number of words in the mapping last page

1)
Float – 4 bytes floating point number
2.4.17.1 Calculation formula for phase voltage values

Values in Amps can be calculated in following way:

sample_UA(e.g.3800h) ⋅ Internal_PhA ⋅ Phase_Primary_VT_Un


Value UA = 2 ⋅
Phase_ Secondary _VT_Un ⋅ 2000
sample_UB(e.g.3801h) ⋅ Internal_PhB ⋅ Phase_Primary_VT_Un
Value UB = 2 ⋅
Phase_ Secondary _VT_Un ⋅ 2000
sample_UC(e.g.3802h)⋅ Internal_PhC ⋅ Phase_Primary_VT_Un
Value UC = 2 ⋅
Phase_ Secondary _VT_Un ⋅ 2000

2.4.17.2 Calculation formula for neutral voltage values


Value in Amps can be calculated in following way:

sample_UN(e.g.3803h)⋅ Internal_N⋅ Earth_Primary_VT_Uen


Value IN = 2 ⋅
Earth_ Secondary _VT_Uen ⋅ 2000

CT
Communication Database V11V/EN CT v1.0

VAMP 11V (CT) 13-43

2.4.18 Pages 3Dh : number of disturbance records available


Access in word reading (function 03)

Address Contents
3D00h Number of disturbance records available

Word n° 1 : Number of disturbance records available


Word n° 2: Oldest disturbance record number (n)
Words n° 3 & 4 : Oldest disturbance record date (second)
Words n° 5 & 6 : Oldest disturbance record date (millisecond)
Word n° 7 : Disturbance record starting origin
1= Protection trip
2= instantaneous threshold
3= remote command
4= logic input
Word n° 8 : Acknowledge
Word n° 9 : Disturbance record previous number (n+1)
Words n° 10 & 11: Previous disturbance record date (second)
Words n° 12 & 13: Previous disturbance record date (millisecond)
Word n° 14 : Disturbance record starting origin
1= Protection trip
2= instantaneous threshold
3= remote command
4= logic input
Word n° 15 : Acknowledge
Word n° 16 : Disturbance record previous number (n+2)
Words n° 17 & 18: Previous disturbance record date (second)
Words n° 19 & 20: Previous disturbance record date (millisecond)
Word n° 21 : Disturbance record starting origin
1= Protection trip
2= instantaneous threshold
3= remote command
4= logic input
Word n° 22 : Acknowledge
Word n° 23 : Disturbance record previous number (n+3)
Words n° 24 & 25: Previous disturbance record date (second)
Words n° 26 & 27: Previous disturbance record date (millisecond)
Word n° 28 : Disturbance record starting origin
1= Protection trip
2= instantaneous threshold
3= remote command
4= logic input
Word n° 29 : Acknowledge
Word n° 30 : Disturbance record previous number (n+4)
Words n° 31 & 32: Previous disturbance record date (second)
Words n° 33 & 34: Previous disturbance record date (millisecond)
Word n° 35 : Disturbance record starting origin
1= Protection trip
2= instantaneous threshold
CT
3= remote command
4= logic input
Word n° 36 : Acknowledge
V11V/EN CT v1.0 Communication Database

(CT) 13-(CT) 13-44 VAMP 11V

2.4.19 Description of the mapping format, VAMP 11V

CODE DESCRIPTION
F1 Unsigned integer – numerical data : 0 – 65535
F10 Characters ASCII
byte 1: ASCII character 32-127
byte 2: ASCII character 32-127
F11 Unsigned integer -Binary input status
bit 0: logic input 1
bit 1: logic input 2
bit 2: logic input 3
bit 3: logic input 4
bit 4: logic input 5
bit 5: logic input 6
bit 6-15: reserved
F12 Unsigned integer – Voltage Protection disable status
bit 0: V> disabled
bit 1: V>> disabled
bit 2: V>>> disabled
bit 3: V< disabled
bit 4: V<< disabled
bit 5: V<<< disabled
bit 6: VN> disabled
bit 7: VN>> disabled
bit 8: VN>>> disabled
bit 9: V2> disabled (AN)
bit 10: V2>> disabled (AN)
bit 11: V1< disabled (A)
bit 12: V1<< disabled (A)
bit 13 to 15: reserved
F12A Unsigned integer – Protection Function disable status
bit 0: f1 disabled (A)
bit 1: f2 disabled (A)
bit 2: f3 disabled (A)
bit 3: f4 disabled (A)
bit 4: f5 disabled (A)
bit 5: f6 disabled (A)
bit 6: reserved
bit 7: reserved
bit 8: reserved
bit 9: AUX 1 disabled (A)
bit 10: AUX 2 disabled (A)
bit 11: AUX 3 disabled (A)
bit 12 to 15: reserved
F15 Two-digit decimal number - Firmware version
1st digit - major version
2nd digit - minor version
10: 1A
11: 1B
12: 1C
13: 1D
CT etc.
Unsigned integer – Configuration
F16
0: disabled
1: enable OR Trip
2: enable OR Alarm
3: enable AND Trip
4: enable AND Alarm
5: enable OR Trip/52a (AN)
6: enable OR Alarm/52a (AN)
7: enable AND Trip/52a (AN)
8: enable AND Alarm/52a (AN)
F17 Unsigned integer - Hardware version
00: 4BO, no RS485 (Model L)
01: 4BO, RS485 (model L with RS485)
Communication Database V11V/EN CT v1.0

VAMP 11V (CT) 13-45

CODE DESCRIPTION
10: 2BI, 4BO, no RS485 (Model N)
11: 6BI, 8BO, RS485 (model A)
F18 Unsigned integer – curves type
0: DT
1: SI IEC
2: VI IEC
3: EI IEC
4: LTI (IEC)
5: STI (IEC)
6: RC Rectifier curve
7: RI curve
8: MI IEEE
9: VI IEEE
10: EI IEEE
11: STI (US C02-P20)
12: LTI (US CO8)
13: RXIDG
14: BPN EDF
15: STI (US C02-P40)
F19 Unsigned integer - Baud rate value
0: 4800 baud
1: 9600 baud
2: 19200 baud
3: 38400 baud
4: 57600 baud
5: 115200 baud
F20 Unsigned integer – Parity
0: none
1: even
2: odd
F21 Unsigned integer – VT secondary
1: 57-130V
2: 220-480V
F22 Unsigned integer – Stop
0: 1 stop
1: 2 stop
F23 Unsigned integer – VT secondary E/Gnd
0: none
1: 57-130V
F24 Unsigned integer - Logical output status
bit 0: logic output RL1
bit 1: logic output RL2
bit 2: logic output RL3
bit 3: logic output RL4
bit 4: logic output RL5
bit 5: logic output RL6
bit 6: logic output RL7
bit 7 to 15: reserved
F25 Unsigned integer - Logical LED status
bit 0: Trip
CT
bit 1: LED2 (Alarm)
bit 2: LED3
bit 3: LED4
bit 4: LED5
bit 5: LED6
bit 6: LED7
bit 7: Healthy
bit 8-15: reserved
F26 Unsigned integer - Logical heathy status
bit 0 to 3: reserved
bit 4: Healthy
bit 10-15: reserved
V11V/EN CT v1.0 Communication Database

(CT) 13-(CT) 13-46 VAMP 11V

CODE DESCRIPTION
F28 Unsigned integer - Protection start status
bit 0: V>
bit 1: V>>
bit 2: V>>>
bit 3: V<
bit 4: V<<
bit 5: V<<<
bit 6: VN>
bit 7: VN>>
bit 8: VN>>>
bit 9: V2> (AN)
bit 10: V2>> (AN)
bit 11: V1< (A)
bit 12: V1<< (A)
bit 13: starting in phase A
bit 14: starting in phase B
bit 15: starting in phase C
F28A Unsigned integer - Protection start status
bit 0: f1 (A)
bit 1: f2 (A)
bit 2: f3 (A)
bit 3: f4 (A)
bit 4: f5 (A)
bit 5: f6 (A)
bit 6: reserved
bit 7: reserved
bit 8 : reserved
bit 9: AUX1 (A)
bit 10: AUX2 (A)
bit 11: AUX3 (A)
bit 12 to 15: reserved
F29 Unsigned integer – Protection Function trip status
bit 0: tV> trip
bit 1: tV>> trip
bit 2: tV>>> trip
bit 3: tV< trip
bit 4: tV<< trip
bit 5: tV<<< trip
bit 6: tVN> trip
bit 7: tVN>> trip
bit 8: tVN>>> trip
bit 9: tV2> trip (AN)
bit 10: tV2>> trip (AN)
bit 11: tV1< trip (A)
bit 12: tV1<< trip (A)
bit 13: trip phase A
bit 14: trip phase B
bit 15: trip phase C
F29A Unsigned integer - Protection Function trip status
bit 0: tf1 trip (A)
bit 1: tf2 trip (A)
CT bit 2: tf3 trip (A)
bit 3: tf4 trip (A)
bit 4: tf5 trip (A)
bit 5: tf6 trip (A)
bit 6: reserved
bit 7: reserved
bit 8: reserved
bit 9: tAUX1 trip (A)
bit 10: tAUX2 trip (A)
bit 11: tAUX3 trip (A)
bit 12 to 15: reserved
Communication Database V11V/EN CT v1.0

VAMP 11V (CT) 13-47

CODE DESCRIPTION
F30 Unsigned integer - CB status
0: CB opened
1: CB closed
2: reserved
3: CB position faulty
4: CB position undefined
F31 Unsigned integer (bit)- Protection Alarm status
bit 0: tV> alarm
bit 1: tV>> alarm
bit 2: tV>>> alarm
bit 3: tV< alarm
bit 4: tV<< alarm
bit 5: tV<<< alarm
bit 6: tVN> alarm
bit 7: tVN>> alarm
bit 8: tVN>>> alarm
bit 9: tV2> alarm (AN)
bit 10: tV2>> alarm (AN)
bit 11: tV1< alarm (A)
bit 12: tV1<< alarm (A)
bit 13: alarm phase A
bit 14: alarm phase B
bit 15: alarm phase C
F31A Unsigned integer - Alarm Function status
bit 0: tf1 alarm (A)
bit 1: tf2 alarm (A)
bit 2: tf3 alarm (A)
bit 3: tf4 alarm (A)
bit 4: tf5 alarm (A)
bit 5: tf6 alarm (A)
bit 6: reserved
bit 7: reserved
bit 8: reserved
bit 9: tAUX1 alarm (A)
bit 10: tAUX2 alarm (A)
bit 11: tAUX3 alarm (A)
bit 12: alarm t CB not healthy (AN)
bit 13: alarm CB (AN)
bit 14: alarm tVTS (AN)
bit 15: alarm VT Supervision (AN)
F32 Unsigned integer - Setting group
0: Setting group 1
1: Setting group 2
F35 Unsigned integer -Input configuration
bit 0: Input L1
bit 1: Input L2
bit 2: Input L3
bit 3: Input L4
bit 4: Input L5
bit 5: Input L6
bit 6-15: reserved
F36 Unsigned integer -Output configuration
CT
bit 0: RL1
bit 1: RL2
bit 2: RL3
bit 3: RL4
bit 4: RL5
bit 5: RL6
bit 6: RL7
bit 7-15: reserved
V11V/EN CT v1.0 Communication Database

(CT) 13-(CT) 13-48 VAMP 11V

CODE DESCRIPTION
F37 Unsigned integer: threshold phase information status:
bit 0: information thresold exceeded (V>, V>>, V>>>, V<, V<<, V<<<)
bit 1: Instantaneous VA
bit 2: Instantaneous VB
bit 3: Instantaneous VC
bit 4: reserved
bit 5: Instantaneous information (V>, V>>, V>>>, V<, V<<, V<<<)(after blocking)
bit 6: Triping information (V>, V>>, V>>>, V<, V<<, V<<<)
bit 7 to 15: reserved
F38 Unsigned integer - Remote control word 1
bit 0: Warm restart (AN)
bit 1: Reset LEDs (AN)
bit 2: Reset Outputs (AN)
bit 3: Reset LEDs and Outputs (AN)
bit 4: Local Mode (A)
bit 5: Reset latched Alarms (AN)
bit 6: Setting change to Group 1 (AN)
bit 7: Remote or HMI CB open order (AN)
bit 8: f<> Remote blocking (A)
bit 9: f<> Remote unblocking (A)
bit 10: Remote Mode (A)
bit 11: Setting change to Group 2 (AN)
bit 12: Disable automatic acknowledgement of events (AN)
bit 13: Oldest event acknowledge (AN)
bit 14: Oldest fault acknowledge (AN)
bit 15: Remote or via HMI CB close order (AN)
F38A Unsigned integer - Remote control word 2
bit 0: Clear Recorders (AN)
bit 1: Clear Events (AN)
bit 2: reserved
bit 3: reserved
bit 4: Peak value reset (AN)
bit 5: Disturbance record remote start (A)
bit 6: Maintenance mode (A)
bit 7: End of maintenance mode (A)
bit 8: Acknowledgement of the oldest disturbance record (A)
bit 9: reserved
bit 10: reserved
bit 11: reserved
bit 12: Reset Fault counters (AN)
bit 13: Reset control counters (AN)
bit 14: reserved
bit 15: reserved
F38B Unsigned integer – Remote control word 3
bit 0: reserved
bit 1: Enable automatic acknowledgement of events (AN)
bit 2-15: reserved
F39 Unsigned integer - LED function
bit 0: LED2 (Alarm)
bit 1: LED3
bit 2: LED4
CT bit 3: LED5
bit 4: LED6
bit 5: LED7
bit 6-15: reserved
F41 Unsigned integer - Curve Type
0: DT
1: IDMT
Communication Database V11V/EN CT v1.0

VAMP 11V (CT) 13-49

CODE DESCRIPTION
F49 Unsigned integer - relay status
bit 0: Relay status (major alarms)
bit 1: Minor hardware alarm
bit 2: Presence of non-acknowledged event
bit 3: Synchronisation state
bit 4: reserved
bit 5: Presence of non-acknowledged fault record
bit 6-15: reserved
F50 Unsigned integer: threshold V2, VN, V1, f, AUXx information status:
bit 0: information threshold exceeded
bit 1: reserved
bit 2: reserved
bit 3: reserved
bit 4: reserved
bit 5: Instantaneous information (V2, V1, VN, f, AUXx)(after blockig)
bit 6: Tripping information (V2, VN, V1, f, AUXx)
bit 7 to 15: reserved
F52 Unsigned integer: information about language in menu
0: English
1: German
2: French
3: Spanish
4: Russian
5: Turkish
6: Regional
F53 Unsigned integer: information about default window in menu
0: Measurements P- P [V]
1: Measurements P-P [Un]
2: Measurements P-N [V]
3: Measurements P-N [Un]
4: Control CB
5: Local mode
F54 Unsigned integer
0: Manual only
1: Protection start
2: Close command
F55 Unsigned integer - Alarm Display Reset
0: Self-Reset
1: Manual Reset
F56 Unsigned integer - Protocol
0: Modbus
1: IEC103
F57 Unsigned integer – Nominal Frequency
0: 50Hz
1: 60Hz
F58 Unsigned integer – Hardware version
0: Standard
1: Model L
2: Model L+RS485
3: Model N
4: Model A
CT
F60 Inverted CP56Time2a Format
F61 Unsigned integer - Local/Remote Mode
0: Local and Remote
1: Remote only
2: Local only
F62 Unsigned integer – Maintenance Mode. Read only (remote modification has no
effect)
0: No
1: Yes – output trips
2: Yes – output blocking
V11V/EN CT v1.0 Communication Database

(CT) 13-(CT) 13-50 VAMP 11V

CODE DESCRIPTION
F63 Unsigned integer – Configuration
0: No
1: Yes
F64 Unsigned integer – Configuration
0: Protection reset
1: CB Reset
F65 Unsigned integer – Disturbance recorder configuration
0: On Instantenous
1: On Trip
F66 Unsigned integer – Configuration
0: Disabled
1: Enabled
F71 Unsigned integer - Number of setting groups:
0: One Group
1:Two Groups
F73 Unsigned integer - Remote Mode configuration
0: Remote Only
1:Remote + Local
F76 Unsigned integer – Functional test pattern
0: V>
1: V>>
2: V>>>
3: V<
4: V<<
5: V<<<
6: VN>
7: VN>>
8: VN>>>
9: V2>
10: V2>>
11: V1<
12: V1<<
13: f1
14: f2
15: f3
16: f4
17: f5
18: f6
F77 Unsigned integer - Functional Test End
0: CB Trip
1: Time elapsed
F82 Unsigned integer – Control key confirmation
0: without confirmation
1: with confirmation
F84 Unsigned integer - Configuration:
0: disable
1: f> Trip
2: f> Alarm
CT 3: f< Trip
4: f< Alarm
F88 Unsigned integer – IDMT Interlock by DMT
0: No
1: Yes
F90 Unsigned Integer - VT connection
0: 3Upn
1: 3Upn+UN
2: 2Upp+UN
3: 3Upp+UN
Communication Database V11V/EN CT v1.0

VAMP 11V (CT) 13-51

CODE DESCRIPTION
F91 Unsigned integer – Protection configuration
0: P-N
1: P-P
F92 Unsigned integer – VTS input
0: VTS input
1: Delta Vr=VN-3Vo
2: Delta Vr=VN-3Vo and VTS input
F94 Unsigned integer - Configuration
0: disabled
1: Trip
2: Alarm
F95 Unsigned integer - Configuration
0: disable
1: Trip (measured)
2: Alarm (measured)
3: Trip (Ua+Ub+Uc)
4: Alarm (Ua+Ub+Uc)

CT
V11V/EN CT v1.0 Communication Database

(CT) 13-(CT) 13-52 VAMP 11V

2.4.20 Request to retrieve the oldest non-acknowledge event

Slave number Function code Word address Word number CRC

xx 03h 36h 00 00 09h xx xx

This event request may be answered an error message with the error code :
EVT_EN_COURS_ECRIT (5) : An event is being written into the saved FRAM.
Note : On event retrieval, two possibilities exist regarding the event
record acknowledgement :
a) Automatic event record acknowledgement on event retrieval.
b) Non automatic event record acknowledgement on event
retrieval.

a) Automatic event record acknowledgement on event retrieval :


The bit12 of the remote order frame (format F38 – mapping address 0400h) shall be set to 0.
On event retrieval, this event record is acknowledged.

b) Non automatic event record acknowledgement on event retrieval :


The bit12 of the remote order frame (format F38 – mapping address 0400h) shall be set to 1.
On event retrieval, this event record is not acknowledged.
To acknowledge this event, an other remote order shall be sent to the relay. The bit 13 of
this frame (format F38 – mapping address 0400h) shall be set to 1.
2.4.21 Request to retrieve a dedicated event

Slave number Function code Word address Word number CRC

xx 03h Refer to mapping 00 09h xx xx

This event request may be answered an error message with the error code :
EVT_EN_COURS_ECRIT (5) : An event is being written into the saved FRAM.
Note : This event retrieval does not acknowledge this event.
2.4.22 Modbus request definition used to retrieve the fault records
Two ways can be followed to retrieve a fault record :

• Send a request to retrieve the oldest non-acknowledge fault record.

• Send a request to retrieve a dedicated fault record.


2.4.22.1 Request to retrieve the oldest non-acknowledge fault record

Slave number Function code Word address Word number CRC

xx 03h 3Eh 00 00 0Fh xx xx

Note : On fault retrieval, two possibilities exist regarding the fault


CT record acknowledgement:
a) Automatic fault record acknowledgement on event retrieval.
b) Non automatic fault record acknowledgement on event retrieval.

a) Automatic fault record acknowledgement on fault retrieval:


The bit12 of the remote order frame (format F38 – mapping address 0400h) shall be set to 0.
On fault retrieval, this fault record is acknowledged.

b) Non automatic fault record acknowledgement on fault retrieval :


The bit12 of the remote order frame (format F38 – mapping address 0400h) shall be set to 1.
On fault retrieval, this fault record is not acknowledged.
Communication Database V11V/EN CT v1.0

VAMP 11V (CT) 13-53

To acknowledge this fault, an other remote order shall be sent to the relay. The bit 14 of this
frame (format F38 – mapping address 0400h) shall be set to 1.
2.4.22.2 Request to retrieve a dedicated fault record

Slave number Function code Word address Word number CRC

xx 03h Refer to mapping 00 0Fh xx xx

Note : This fault value retrieval does not acknowledge this fault record.

CT
V11V/EN CT v1.0 Communication Database

(CT) 13-(CT) 13-54 VAMP 11V

3. IEC60870-5-103 INTERFACE

The IEC60870-5-103 interface is a master/slave interface with the relay as the slave device.
This protocol is based on the VDEW communication protocol. The relay conforms to
compatibility level 2, compatibility level 3 is not supported.
The following IEC60870-5-103 facilities are supported by this interface:
Initialisation (Reset)
Time Synchronisation
Event Record Extraction
General Interrogation
Cyclic Measurements
General Commands
Physical connection and link layer
Connection is available for IEC60870-5-103 through the rear RS485 port. It is possible to
select both the relay address and baud rate using the front panel interface. Following a
change, a reset command is required to re-establish communications.
The parameters of the communication are the following:
Even Parity
8 Data bits
1 stop bit
Data rate 9600 or 19200 bauds
Initialisation
Initialisation is implemented according to clause 7.4.1 of IEC 60870-5-103.
Whenever the relay has been powered up, or if the communication parameters have been
changed a reset command is required to initialise the communications. The relay will
respond to either of the two reset commands (Reset CU or Reset FCB), the difference being
that the Reset CU will clear any unsent messages in the relay's transmit buffer.
The relay will respond to the reset command with an identification message
ASDU 5, the Cause Of Transmission COT of this response will be either Reset CU or Reset
FCB depending on the nature of the reset command. The following information will be
contained in the data section of this ASDU:
Manufacturer Name: SE VAMP
According to the specification “Communication Architecture (ACA), Part 4: Communication
based on IEC 60870-5-103” (Issue H, April 2010) the Software Identification Section will
CT contain the relay model number and the version number to identify the type of relay.
Software Identification Section, Byte 0: Numerical part of device type, hex, low
Software Identification Section, Byte 1: Numerical part of device type, hex, low
Software Identification Section, Byte 2: Software version, hex, low
Software Identification Section, Byte 3: Software version, hex, high
Letters in the software version are converted to numerical values according to the following
rule: A=0, B=1, C=2, D=3 etc.
The Software Identification Section of V11V, version 1A, will then contain ‘111’ and ‘10’ as
hexadecimal coded values:
Communication Database V11V/EN CT v1.0

VAMP 11V (CT) 13-55

Byte 0: 74H
Byte 1: 00H
Byte 2: 10H
Byte 3: 00H
In addition to the above identification message, if the relay has been powered up it will also
produce a power up event.
Time synchronisation
Time synchronisation is implemented according to clause 7.4.2 of IEC 60870-5-103.
The relay time and date can be set using the time synchronisation feature of the IEC60870-
5-103 protocol. The relay will correct for the transmission delay as specified in IEC60870-5-
103. If the time synchronisation message is sent as a send/confirm message then the relay
will respond with a confirm. Whether the time synchronisation message is sent as a send
confirm or a broadcast (send/no reply) message, a time synchronisation message will be
returned as Class 1 data.
Spontaneous events
The events created by the relay will be passed to the master station using the compatible
range and the private range of IEC 60870-5-103 function types and information numbers.
Events are categorised using the following information:
Common Address
Function Type
Information number
3.10-3.14 contains a complete listing of all events produced by the relay.
General interrogation
General interrogation is implemented according to clause 7.4.3 of IEC 60870-5-103.
The GI request can be used to read the status of the relay, the function numbers, information
numbers and common address offsets that will be returned during the GI cycle are indicated
in 3.10-3.14.
Cyclic measurements
The relay will produce measured values using ASDU 3 and ASDU 9 on a cyclical basis.
They can be read from the relay using a Class 2 poll.
It should be noted that the measurands transmitted by the relay are sent as a proportion of
2.4 times the rated value of the analogue value. The selection of 2.4 for a particular value is
indicated in 3.10-3.14.
Commands
Command transmission is implemented according to clause 7.4.4 of IEC 60870-5-103.
CT
A list of the supported commands is contained in 3.10-3.14. The relay will respond to all
other commands with an ASDU 1, with a cause of transmission (COT) of negative
acknowledgement of a command
Blocking of monitor direction
The relay does not support a facility to block messages in the Monitor direction.
V11V/EN CT v1.0 Communication Database

(CT) 13-(CT) 13-56 VAMP 11V

Spontaneous messages managed by VAMP 11V


These messages includes a sub-assembly of events which are generated on the relay,
because some generated events are not registered in VDEW. They are the most priority
messages.
An event is always generated on the rising edge of the information.
Some events can be generated on the rising or lowering edge.
In the list below, events only generated on rising edge will be tagged with a ‘*’.
The following list of processed events contains the messages for the compatible and the
private range for all overvoltage protection functions, with the associated FUNCTION TYPE,
INFORMATION NUMBER, ASDU TYPE, CAUSE OF TRANSMISSION
FUN <160>: Function type in Public range for Overvoltage Protections (compatible).
FUN <162> ,<163>, <164>, <165>, <168>: Function type in Private range (Reserved for
Overvoltage Protections).
Status indications in monitor direction (Type Identification 1)

ASCI Description FUN INF ASDU COT ADDR Notes


LEDs and flags 1,7,11,12, *
160 19 1
indication reset 20, 21
1,7,11,12, *
Reset Latch. Sign Inp 162 223 1
20, 21
Reset Latched Outputs 1,7,11,12, *
162 46 1
(Inp+COM) 20, 21
Reset Latched *
1,7,11,12,
Signaling. and Outputs 249 131 1
20, 21
(HMI+COM)
Reset Latched Outputs *
162 86 1 1,7
(Inp)
Maintenance (Test)
162 157 1 1,7
Mode Inp
Maintenance Mode
160 21 1 11
(Test Mode)
Local Mode 160 22 1 11
Relay Blocked/faulty
160 47 1 1,7
(Hardware Warning)
1,7,11,12,
Setting Group number 1 160 23 1
20, 21
1,7,11,12,
Setting Group number 2 160 24 1
20, 21
Status of input
- it includes
Auxiliary input 1 160 27 1 1,7,11
reverse logic
CT Auxiliary input 2 160 28 1 1,7,11
configuration
as above
Auxiliary input 3 160 29 1 1,7,11 as above
Auxiliary input 4 160 30 1 1,7,11 as above
Auxiliary input 5 163 81 1 1,7,11 as above
Auxiliary input 6 163 82 1 1,7,11 as above
Presence of
the voltage on
Input 1 163 160 1 1,7
the input
terminals
Input 2 163 161 1 1,7 as above
Input 3 163 162 1 1,7 as above
Communication Database V11V/EN CT v1.0

VAMP 11V (CT) 13-57

Input 4 163 163 1 1,7 as above


Input 5 163 164 1 1,7 as above
Input 6 163 165 1 1,7 as above
Logical state
of the output
- before
Reverse
Logic. Logical
state of the
Relay output 1 249 1 1 1,7 output can
differ from
Physical state
- terminals if
Reverse Logic
for this output
is set
Relay output 2 249 2 1 1,7 as above
Relay output 3 249 3 1 1,7 as above
Relay output 4 249 4 1 1,7 as above
Relay output 5 249 5 1 1,7 as above
Relay output 6 249 6 1 1,7 as above
Relay output 7 249 7 1 1,7 as above
Relay output 8 249 8 1 1,7 as above
Manual. Trip Ext (Inp) 162 148 1 1,7 *
Trip CB Order *
162 9 1 1,7
(Inp+HMI+RS485)
Manual. Close Ext (Inp) 162 47 1 1,7 *
Manual. Close *
162 246 1 1,7
Command (Inp+HMI)
Close CB Order *
162 239 1 1,7
(Inp+HMI+RS485)
CB Status 52A Inp 163 253 1 1,7
CBM: tCB FLT (faulty)
165 45 1 1,7
Ext. Alarm
CBM: CB Time *
165 46 1 1,7
Monitoring Alarm
CBM: State of CB (not
165 47 1 1,7
correct) ALARM
FT_RC: Faulty time tag 163 74 1 1,7 *
59 Blocking tV> Ext (Inp) 163 18 1 1,7
59 Blocking tV>> Ext (Inp) 163 19 1 1,7
59 Blocking tV>>> Ext (Inp) 165 67 1 1,7
27 Blocking tV< Ext (Inp) 163 20 1 1,7
27: Blocking tV<< Ext
27 163 21 1 1,7
(Inp) CT
27 Blocking tV<<< Ext (Inp) 165 70 1 1,7
59N Blocking tVN> Ext (Inp) 163 22 1 1,7
Blocking tVN>> Ext
59N 163 23 1 1,7
(Inp)
Blocking tVN>>> Ext
59N 165 73 1 1,7
(Inp)
27D Blocking tV1< Ext (Inp) 163 26 1 1,7
27D Blocking tV1<< Ext (Inp) 163 27 1 1,7
47 Blocking tV2> Ext (Inp) 163 28 1 1,7
47 Blocking tV2>> Ext (Inp) 163 29 1 1,7
81 Blocking tf1 Ext (Inp) 162 4 1 1,7
V11V/EN CT v1.0 Communication Database

(CT) 13-(CT) 13-58 VAMP 11V

81 Blocking tf2 Ext (Inp) 164 5 1 1,7


81 Blocking tf3 Ext (Inp) 164 6 1 1,7
81 Blocking tf4 Ext (Inp) 162 7 1 1,7
81 Blocking tf5 Ext (Inp) 165 76 1 1,7
81 Blocking tf6 Ext (Inp) 165 79 1 1,7
81 f Out 165 80 1 1,7
81 Blocked by V< 164 3 1 1,7
VTS VTS Enabled 165 102 1 1,7
VTS Start VTS 163 71 1 1,7
VTS VTS Ext 165 81 1 1,7
VTS tVTS 165 101 1 1,7

Fault Indications in monitor direction (Type Identification 2)

ASCI Description FUN INF ASDU COT ADDR Notes


General Trip 160 68 2 1,7 *
Start / pick-up V>/V>>/V>>>
59 163 32 2 1,7
A (-B)
Start / pick-up V>/V>>/V>>>
59 163 33 2 1,7
B (-C)
Start / pick-up V>/V>>/V>>>
59 163 34 2 1,7
C (-A)
59 Start / pick-up V> 163 30 2 1,7
59 tV> elapsed 163 36 2 1,7 *
59 Trip tV> 165 82 2 1,7 *
59 Start / pick-up V>> 163 31 2 1,7
59 tV>> elapsed 163 38 2 1,7 *
59 Trip tV>> 165 83 2 1,7 *
59 Start / pick-up V>>> 165 65 2 1,7
59 tV>>> elapsed 165 66 2 1,7 *
59 Trip tV>>> 165 84 2 1,7 *
Start / pick-up V</V<</V<<<
27 163 41 2 1,7
A (-B)
Start / pick-up V</V<</V<<<
27 163 42 2 1,7
B (-C)
Start / pick-up V</V<</V<<<
27 163 43 2 1,7
C (-A)
27 Start / pick-up V< 163 39 2 1,7
27 tV< elapsed 163 45 2 1,7 *
27 Trip tV< 165 85 2 1,7 *
27 Start / pick-up V<< 163 40 2 1,7
27 tV<< elapsed 163 47 2 1,7 *
27 Trip tV<< 165 86 2 1,7 *
27 Start / pick-up V<<< 165 68 2 1,7
CT 27 tV<<< elapsed 165 69 2 1,7 *
27 Trip tV<<< 165 87 2 1,7 *
59N Start / pick-up VN> 163 49 2 1,7
59N tVN> elapsed 163 51 2 1,7 *
59N Trip tVN> 165 88 2 1,7 *
59N Start / pick-up VN>> 163 50 2 1,7
59N tVN>> elapsed 163 52 2 1,7 *
59N Trip tVN>> 165 89 2 1,7 *
59N Start / pick-up VN>>> 165 71 2 1,7
59N tVN>>> elapsed 165 72 2 1,7 *
59N Trip signal tVN>>> 165 90 2 1,7 *
Communication Database V11V/EN CT v1.0

VAMP 11V (CT) 13-59

27D Start / pick-up V1< 163 57 2 1,7


27D tV1< elapsed 163 59 2 1,7 *
27D Trip signal tV1< 165 91 2 1,7 *
27D Start / pick-up V1<< 163 58 2 1,7
27D tV1<< elapsed 163 60 2 1,7 *
27D Trip signal tV1<< 165 92 2 1,7 *
47 Start / pick-up V2> 163 62 2 1,7
47 tV2> elapsed 163 64 2 1,7 *
47 Trip signal tV2> 165 93 2 1,7 *
47 Start / pick-up V2>> 163 63 2 1,7
47 tV2>> elapsed 163 65 2 1,7 *
47 Trip signal tV2>> 165 94 2 1,7 *
81 Start / pick-up f1 162 8 2 1,7
81 tf1 elapsed 165 95 2 1,7 *
81 Trip signal tf1 164 12 2 1,7 *
81 Start / pick-up f2 164 13 2 1,7
81 tf2 elapsed 165 96 2 1,7 *
81 Trip signal tf2 164 17 2 1,7 *
81 Start / pick-up f3 164 18 2 1,7
81 tf3 elapsed 165 97 2 1,7 *
81 Trip signal tf3 165 22 2 1,7 *
81 Start / pick-up f4 164 23 2 1,7
81 tf4 elapsed 165 98 2 1,7 *
81 Trip signal tf4 165 64 2 1,7 *
81 Start / pick-up f5 165 74 2 1,7
81 tf5 elapsed 165 99 2 1,7 *
81 Trip signal tf5 165 75 2 1,7 *
81 Start / pick-up f6 165 77 2 1,7
81 tf6 elapsed 165 100 2 1,7 *
81 Trip signal tf6 165 78 2 1,7 *
AUX Start AUX1 163 93 2 1,7
AUX tAUX1 elapsed 163 94 2 1,7
AUX Trip tAUX1 165 22 2 1,7 *
AUX Start AUX2 163 95 2 1,7
AUX tAUX2 elapsed 163 96 2 1,7
AUX Trip tAUX2 165 23 2 1,7 *
AUX Start AUX3 163 97 2 1,7
AUX tAUX3 elapsed 163 98 2 1,7
AUX Trip tAUX3 165 24 2 1,7 *
FT_RC System disturb. runn 162 241 2 1,7
FT_RC Record. in progress 162 220 2 1,7
Start Distur. Recorder
FT_RC 162 172 2 1,7
INP+COM
FT_RC Trigger INP 162 22 2 1,7
CT
Control indications in monitor direction:
CB monitoring: FUN<242>;INF <1>; COT<1, 7,11>,<ADDR>
NOTE: The value of CB monitoring DPI can have 4 stages:
DPI
<0000 0000> "Undefined / Between closed and opened"
<0000 0001> "opened"
<0000 0010> "closed"
V11V/EN CT v1.0 Communication Database

(CT) 13-(CT) 13-60 VAMP 11V

<0000 0011> "Undefined / Faulty"

CT
Communication Database V11V/EN CT v1.0

VAMP 11V (CT) 13-61

List of data contained in General Interrogation


It is given in the answer to the General Interrogation (GI).
Relay state information are Class 1 data, they are systematically sent to the master station,
during a General Interrogation.
The list of processed data, following a General Interrogation, is given below: it is a sub-
assembly of the spontaneous message list, so like spontaneous messages, these data are
generated on rising and lowering edge.

Status indications (monitor direction):

ASCI Description FUN INF ASDU COT ADDR Notes


Maintenance (Test)
162 157 1 9
Mode Inp
Maintenance Mode
160 21 1 9
(Test Mode)
Local Mode 160 22 1 9
Relay Blocked/faulty
160 47 1 9
(Hardware Warning)
Setting Group number 1 160 23 1 9
Setting Group number 2 160 24 1 9
Status of input
Auxiliary input 1 (logical - it includes
160 27 1 9
state) reverse logic
configuration
Auxiliary input 2 (logical as above
160 28 1 9
state)
Auxiliary input 3 (logical as above
160 29 1 9
state)
Auxiliary input 4 (logical as above
160 30 1 9
state)
Auxiliary input 5 (logical as above
163 81 1 9
state)
Auxiliary input 6 (logical as above
163 82 1 9
state)
Presence of
the voltage on
Input 1 163 160 1 9
the input
terminals
Input 2 163 161 1 9 as above
Input 3 163 162 1 9 as above
Input 4 163 163 1 9 as above
Input 5 163 164 1 9 as above
Input 6 163 165 1 9 as above
Logical state
CT
of the output
- before
Reverse
Logic. Logical
Relay output 1 249 1 1 9 state of the
output can
differ from
Physical state
- terminals if
Reverse Logic
V11V/EN CT v1.0 Communication Database

(CT) 13-(CT) 13-62 VAMP 11V

for this output


is set
Relay output 2 249 2 1 9 as above
Relay output 3 249 3 1 9 as above
Relay output 4 249 4 1 9 as above
Relay output 5 249 5 1 9 as above
Relay output 6 249 6 1 9 as above
Relay output 7 249 7 1 9 as above
Relay output 8 249 8 1 9 as above
59 Blocking tV> Ext (Inp) 163 18 1 1,7
59 Blocking tV>> Ext (Inp) 163 19 1 1,7
59 Blocking tV>>> Ext (Inp) 165 67 1 1,7
27 Blocking tV< Ext (Inp) 163 20 1 1,7
27 Blocking tV<< Ext (Inp) 163 21 1 1,7
27 Blocking tV<<< Ext (Inp) 165 70 1 1,7
59N Blocking tVN> Ext (Inp) 163 22 1 1,7
Blocking tVN>> Ext
59N 163 23 1 1,7
(Inp)
Blocking tVN>>> Ext
59N 165 73 1 1,7
(Inp)
27D Blocking tV1< Ext (Inp) 163 26 1 1,7
27D Blocking tV1<< Ext (Inp) 163 27 1 1,7
47 Blocking tV2> Ext (Inp) 163 28 1 1,7
47 Blocking tV2>> Ext (Inp) 163 29 1 1,7
CB Status 52A Inp 163 253 1 9
tCB FLT (faulty) Ext.
CBM 165 45 1 9
Alarm
State of CB (not correct)
CBM 165 47 1 9
ALARM
VTS VTS Enabled 165 102 1 1,7
VTS Start VTS 163 71 1 1,7
VTS VTS Ext 165 81 1 1,7
VTS tVTS 165 101 1 1,7

Fault Indications in monitor direction

ASCI Description FUN INF ASDU CO9T ADDR Notes


Start / pick-up
59 V>/V>>/V>>> 163 32 2 9
A (-B)
Start / pick-up
59 V>/V>>/V>>> 163 33 2 9
B (-C)
Start / pick-up
CT 59
V>/V>>/V>>> C (-A)
163 34 2 9
59 Start / pick-up V> 163 30 2 9
59 Start / pick-up V>> 163 31 2 9
59 Start / pick-up V>>> 165 65 2 9
Start / pick-up
27 V</V<</V<<< 163 41 2 9
A (-B)
Start / pick-up
27 V</V<</V<<< 163 42 2 9
B (-C)
27 Start / pick-up 163 43 2 9
Firmware and Service Manual V11V/EN VH v1.0
Version History
VAMP 11V

FIRMWARE AND SERVICE MANUAL


VERSION HISTORY

Date: 1st December 2015


Software Version: 1A
Connection Diagrams: 10V11V01

VH
V11V/EN VH v1.0 Firmware and Service Manual
Version History
VAMP 11V

VH
VAMP 11V

Firmware and Service Manual Version History


Relay type: VAMP 11V
Software Technical
Version Hardware Original S1 Studio
Description of Changes Documentati
Suffix Date of Issue Compatibility
Major Minor on

1 A A April 2015 Original Issue 5.1.0 V11V/EN M11

V11V/EN VH v1.0
(VH) 14-1
Schneider Electric Energy. As standards, specifications and designs change from
35, rue Joseph Monier time to time, please ask for confirmation of the
CS 30323 information given in this publication.
92506 Rueil-Malmaison Cedex, France
Tel: +33 (0) 1 41 29 70 00 Publishing: Schneider Electric
RCS Nanterre 954 503 439 Design: Schneider Electric
Capital social 896 313 776 € Printing:
www.schneider-electric.com This document has been printed on ecological paper

Energy Automation : VAMP 11V_EN_M


Version 1.0
December 2015

You might also like