Gem General Cat
Gem General Cat
G E N E R A L P R O D U C T S C ATA L O G
Back
Loss Prevention
Council
2
Back
3
Back
4
Back
5
Back
Sprinkler Head
Max. PSI
TYPE Response(6) Hazard(1,7) K Orifice, Inch Pressure Model(1) TD(1) Approvals(1)
3
Upright QR LH 2.8 ⁄8 175 A 513M UL, ULC, FM, NYC
3
QR LH 2.8 ⁄8 175 FR-1 514 UL, ULC, NYC
QR LH 3.9 — 175 A 513Q LPC, SSL, VdS
1
QR All 5.6 ⁄2 175 A 515M UL, ULC, FM, NYC, LPC, SSL, VdS
1
QR All 5.6 ⁄2 175 FR-1 516 UL, ULC, FM, NYC, LPC, SSL, VdS
17
QR All 8.0 ⁄32 175 A 525Q UL, ULC, FM, NYC, LPC, SSL, VdS
17
QR All 8.0 ⁄32 175 FR-1 526 UL, ULC, FM, NYC, SSL
5
QR All 11.2 ⁄8 175 F892QR 595A UL, C-UL, FM
1
SR LH 1.4 ⁄4 175 F950 515 UL, ULC, NYC
3
SR LH 2.8 ⁄8 175 F950 515 UL, ULC, FM, NYC
3
SR LH 2.8 ⁄8 175 A 514M UL, ULC, FM, NYC
SR LH 3.9 – 175 A 514Q LPC, SSL, VdS
7
SR LH 4.2 ⁄16 175 F950 515 UL, ULC, FM, NYC
1
SR All 5.6 ⁄2 175 A 516M UL, ULC, FM, NYC, LPC, SSL, VdS
1
SR All 5.6 ⁄2 175 F950 517 UL, ULC, FM, NYC, LPC, SSL, VdS
1
SR All 5.6 ⁄2 175 D 525M UL, ULC, FM, NYC, LPC
1
SR All 5.6 ⁄2 175 S.S. 581M –
17
SR All 8.0 ⁄32 175 A 526Q UL, ULC, FM, NYC, LPC, SSL, VdS
17
SR All 8.0 ⁄32 175 D 527Q UL, ULC, FM, NYC, LPC
17
SR All 8.0 ⁄32 175 A 529 UL, ULC, FM, NYC
17
SR All 8.0 ⁄32 175 D 529Q UL, ULC, FM, NYC
5
SR All 11.2 ⁄8 175 F892 595 UL, C-UL, FM, NYC, SSL
3
Pendent QR LH 2.8 ⁄8 175 A 513M UL, ULC, FM, NYC
3
QR LH 2.8 ⁄8 175 FR-1 514 UL, ULC, NYC
QR LH 3.9 – 175 A 513Q LPC, SSL, VdS
1
QR All 5.6 ⁄2 175 A 515M UL, ULC, FM, NYC, LPC, SSL, VdS
1
QR All 5.6 ⁄2 175 FR-1 516 UL, ULC, FM, NYC, LPC, SSL, VdS
17
QR All 8.0 ⁄32 175 A 525Q UL, ULC, FM, NYC, LPC, SSL, VdS
17
QR All 8.0 ⁄32 175 FR-1 526 UL, ULC, FM, NYC, SSL
1
SR LH 1.4 ⁄4 175 F950 515 UL, ULC, NYC
STANDARD
COVERAGE
3
SR LH 2.8 ⁄8 175 F950 515 UL, ULC, FM, NYC
3
SR LH 2.8 ⁄8 175 A 514M UL, ULC, FM, NYC
SR LH 3.9 – 175 A 514Q LPC, SSL, VdS
7
SR LH 4.2 ⁄16 175 F950 515 UL, ULC, FM, NYC
1
SR All 5.6 ⁄2 175 A 516M UL, ULC, FM, NYC, LPC, SSL, VdS
1
SR All 5.6 ⁄2 175 F950 517 UL, ULC, FM, NYC, LPC, SSL, VdS
1
SR All 5.6 ⁄2 175 D 525M UL, ULC, FM, NYC, LPC
1
SR All 5.6 ⁄2 175 S.S. 581M –
17
SR All 8.0 ⁄32 175 A 526Q UL, ULC, FM, NYC, LPC, SSL, VdS
17
SR All 8.0 ⁄32 175 D 527Q UL, ULC, FM, NYC, LPC
17
SR All 8.0 ⁄32 175 A 529 UL, ULC, FM, NYC
17
SR All 8.0 ⁄32 175 D 529Q UL, ULC, FM, NYC
3
Recessed Pendent QR LH 2.8 ⁄8 175 FR-1 514 UL, ULC, NYC
1
QR All 5.6 ⁄2 175 A 515M UL, ULC, FM, NYC, LPC, SSL
1
QR All 5.6 ⁄2 175 FR-1 516 UL, ULC, NYC
17
QR All 8.0 ⁄32 175 A 525Q UL, ULC, FM, NYC, LPC, SSL
1
SR All 5.6 ⁄2 175 A 516M UL, ULC, FM, NYC, LPC, SSL
17
SR All 8.0 ⁄32 175 A 526Q UL, ULC, FM, NYC, LPC, SSL
1
Concealed Pendent QR All 5.6 ⁄2 175 F690 578Q UL, ULC, NYC, LPC
1
SR All 5.6 ⁄2 175 F692 579Q UL, ULC, FM, NYC, LPC
1
Flush Pendent QR All 5.6 ⁄2 175 F995 520 UL, ULC, NYC, LPC, SSL
1
On-Off Pendent SR All 5.6 ⁄2 175 F927 560 FM, NYC, SSL
1
Vertical Sidewall QR LH/OH 5.6 ⁄2 175 A 532 UL, ULC, FM, NYC, LPC, SSL
1
SR LH/OH 5.6 ⁄2 175 A 533 UL, ULC, FM, NYC, LPC, SSL
1
Horizontal Sidewall QR LH/OH 5.6 ⁄2 175 A/Q-71 534 UL, ULC, FM, NYC, LPC, SSL
1
QR LH/OH 5.6 ⁄2 175 FR-1/Q-46 535 UL, ULC, FM, NYC, SSL
1
SR LH/OH 5.6 ⁄2 175 A/Q-71 535M UL, ULC, FM, NYC, LPC, SSL
1
SR LH/OH 5.6 ⁄2 175 F950/Q-46 536 UL, ULC, FM, NYC, SSL
1
Rec. Hor. Sidewall QR LH/OH 5.6 ⁄2 175 A/Q-71 534 UL, ULC, FM, NYC, LPC, SSL
1
SR LH/OH 5.6 ⁄2 175 A/Q-71 535M UL, ULC, FM, NYC, LPC, SSL
Flush Sidewall QR LH/OH 5.6 1⁄2 175 F996 538 UL, ULC, NYC, LPC, SSL
5
Upright SR OH 11.2 ⁄8 175 F895 596A UL, C-UL, FM, SSL, NYC
3
SR OH 14.0 ⁄4 175 F895 596A UL, C-UL, FM, SSL, NYC
17
Pendent QR LH 8.0 ⁄32 175 F890 594 UL, C-UL, FM, NYC
5
QR LH 11.2 ⁄8 175 F890 594M UL, C-UL, FM, NYC
COVERAGE
EXTENDED
17
SR LH 8.0 ⁄32 175 F890 594 UL, C-UL, NYC
5
SR LH 11.2 ⁄8 175 F890 594M FM , NYC
5
SR OH 11.2 ⁄8 175 F895 596A UL, C-UL, FM, SSL, NYC
3
SR OH 14.0 ⁄4 175 F895 596A UL, C-UL, FM, SSL, NYC
17
Recessed Pendent QR LH 8.0 ⁄32 175 F890 594 UL, C-UL, FM, NYC
5
QR LH 11.2 ⁄8 175 F890 594M UL, C-UL, FM, NYC
17
SR LH 8.0 ⁄32 175 F890 594 UL, C-UL, FM, NYC
5
SR LH 11.2 ⁄8 175 F890 594M UL, C-UL, FM, NYC
5
SR OH 11.2 ⁄8 175 F895 596A UL, C-UL, SSL, NYC
3
SR OH 14.0 ⁄4 175 F895 596A UL, C-UL, SSL, NYC
6
Back
Selection Chart Section 1 of 2
Sprinkler
Temperature, °F(1) Element NPT, Inch Finish(1,2) Wrench Escutcheon(3) Notes TYPE
1
135, 155, 175, 200, 286 3 mm Bulb ⁄2 B, C, P (4)
1
140, 165, 212 Solder ⁄2 B, C F799
135, 155, 175, 200, 286 3 mm Bulb ISO 3⁄8 B, C, P (4)
1
135, 155, 175, 200, 286 3 mm Bulb ⁄2 B, C, P (4)
1
140, 165, 212 Solder ⁄2 B, C F799
3
135, 155, 175, 200, 286 3 mm Bulb ⁄4 B, C, P (4)
3
140, 165, 212 Solder ⁄4 B, C F799
3
135, 155, 175, 200, 286 3 mm Bulb ⁄4 B, C Adj. Wrench
1
165, 212, 286, 350 Solder ⁄2 B, C, L, W, WOL F799
1
165, 212, 286, 350 Solder ⁄2 B, C, L, W, WOL F799
1
135, 155, 175, 200, 286, 360 5 mm Bulb ⁄2 B, C, P (4)
135, 155, 175, 200, 286, 360 5 mm Bulb ISO 3⁄8 B, C, P (4)
1
165, 212, 286, 350 Solder ⁄2 B, C, L, W, WOL F799
1
135, 155, 175, 200, 286, 360 5 mm Bulb ⁄2 B, C, P (4)
1
165, 212, 286, 350 Solder ⁄2 B, C, L, W, WOL F799
1
400, 500, 650 11 mm Bulb ⁄2 B, C, L F799
1
135, 175, 250 11 mm Bulb ⁄2 Stainless Steel F799
3
135, 155, 175, 200, 286, 360 5 mm Bulb ⁄4 B, C, P (4)
3
400, 500 11 mm Bulb ⁄4 B, C, L F799
1
135, 155, 175, 200, 286, 360 5 mm Bulb ⁄2 B, C, P (4)
1
400, 500 11 mm Bulb ⁄2 B, C, L F799
3
135, 155, 175, 200, 286 5 mm Bulb ⁄4 B, C Adj. Wrench
1
135, 155, 175, 200, 286 3 mm Bulb ⁄2 B, C, P (4)
1
140, 165, 212 Solder ⁄2 B, C F799
135, 155, 175, 200, 286 3 mm Bulb ISO 3⁄8 B, C, P (4)
1
135, 155, 175, 200, 286 3 mm Bulb ⁄2 B, C, P (4)
1
140, 165, 212 Solder ⁄2 B, C F799
3
135, 155, 175, 200, 286 3 mm Bulb ⁄4 B, C, P (4)
3
140, 165, 212 Solder ⁄4 B, C F799
1
165, 212, 286, 350 Solder ⁄2 B, C, L, W, WOL F799
STANDARD
COVERAGE
1
165, 212, 286, 350 Solder ⁄2 B, C, L, W, WOL F799
1
135, 155, 175, 200, 286, 360 5 mm Bulb ⁄2 B, C, P (4)
135, 155, 175, 200, 286, 360 5 mm Bulb ISO 3⁄8 B, C, P (4)
1
165, 212, 286, 350 Solder ⁄2 B, C, L, W, WOL F799
1
135, 155, 175, 200, 286, 360 5 mm Bulb ⁄2 B, C, P (4)
1
165, 212, 286, 350 Solder ⁄2 B, C, L, W, WOL F799
1
400, 500, 650 11 mm Bulb ⁄2 B, C, L F799
1
135, 175, 250 11 mm Bulb ⁄2 Stainless Steel F799
3
135, 155, 175, 200, 286, 360 5 mm Bulb ⁄4 B, C, P (4)
3
400, 500 11 mm Bulb ⁄4 B, C, L F799
1
135, 155, 175, 200, 286, 360 5 mm Bulb ⁄2 B, C, P (4)
1
400, 500 11 mm Bulb ⁄2 B, C, L F799
1
140, 165, 212 Solder ⁄2 B, C F798 C, WH, SP Note: (8)
1
135, 155, 175, 200 3 mm Bulb ⁄2 B, C, P F850 C, WH, SP Notes: (5, 9)
1
140, 165, 212 Solder ⁄2 B, C F798 C, WH, SP Note: (8)
3
135, 155, 175, 200 3 mm Bulb ⁄4 B, C, P F850 C, WH, SP Notes: (5, 9)
1
135, 155, 175, 200 5 mm Bulb ⁄2 B, C, P F850 C, WH, SP Note: (9)
3
135, 155, 175, 200 5 mm Bulb ⁄4 B, C, P F850 C, WH, SP Note: (9)
1 1
135, 155, 175, 200 3 mm Bulb ⁄2 – 2111 C, WH, SP ⁄2" adjustment
1 1
135, 155, 175, 200 4 mm Bulb ⁄2 – 2111 C, WH, SP ⁄2" adjustment
1
160, 212 Solder ⁄2 C, BB, WH F873 C, WH, SP Aquarius Flush Style
1
135, 175 5 mm Bulb ⁄2 B, C F737 C, WH, SP Flush mount escutcheon optional
1
135, 155, 175, 200, 286 3 mm Bulb ⁄2 B, C, P (4)
1
135, 155, 175, 200, 286, 360 5 mm Bulb ⁄2 B, C, P (4)
1
135, 155, 175, 200, 286 3 mm Bulb ⁄2 B, C, P (4)
1
140, 165, 212 Solder ⁄2 B, C F799
1
135, 155, 175, 200, 286, 360 5 mm Bulb ⁄2 B, C, P (4)
1
165, 212, 286, 350 Solder ⁄2 B, C, L, W, WOL F799
1
135, 155, 175, 200 3 mm Bulb ⁄2 B, C, P F850 C, WH, SP Notes: (5, 9)
1
135, 155, 175, 200 5 mm Bulb ⁄2 B, C, P F850 C, WH, SP Note: (9)
160, 212 Solder 1⁄2 C, BB, WH F873 C, WH, SP Aquarius Flush Style
3
135, 155, 175, 200, 286 3 mm Bulb ⁄4 B, C, WH, L F875 14' x 14' & 16' x 16'
3
135, 155, 175, 200, 286 3 mm Bulb ⁄4 B, C, WH, L F875 16' x 16' - 20' x 20'
3
135, 155, 175 3 mm Bulb ⁄4 B, C, WH F799 16' x 16' - 20' x 20'
3
135, 155, 175, 200 3 mm Bulb ⁄4 B, C, WH F851 16' x 16' - 20' x 20'
COVERAGE
EXTENDED
3
155, 200 3 mm Bulb ⁄4 B, C, WH F799 / 1948 16' x 16' - 20' x 20'
3
175 3 mm Bulb ⁄4 B, C, WH F851 16' x 16' - 20' x 20'
3
135, 155, 175, 200, 286 3 mm Bulb ⁄4 B, C, WH, L F875 14' x 14' & 16' x 16'
3
135, 155, 175, 200, 286 3 mm Bulb ⁄4 B, C, WH, L F875 16' x 16' - 20' x 20'
3
135, 155, 175 3 mm Bulb ⁄4 B, C, WH 1948 C, WH, SP 16' x 16' - 20' x 20'; Note: (8)
3
135, 155, 175, 200 3 mm Bulb ⁄4 B, C, WH F851 C, WH, SP 16' x 16' - 20' x 20'; Note: (8)
3
155, 175, 200 3 mm Bulb ⁄4 B, C, WH 1948 C, WH, SP 16' x 16' - 20' x 20'; Note: (8)
3
155, 200 3 mm Bulb ⁄4 B, C, WH F851 C, WH, SP 16' x 16' - 20' x 20'; Note: (8)
3
135, 155, 175, 200 3 mm Bulb ⁄4 B, C, WH F875 C, WH, SP 14' x 14' & 16' x 16'; Note: (10)
3
135, 155, 175, 200 3 mm Bulb ⁄4 B, C, WH F875 C, WH, SP 16' x 16' - 20' x 20'; Note: (10)
7
Back
Sprinkler Head
Max. PSI
TYPE Response(6) Hazard(1,7) K Orifice, Inch Pressure Model(1) TD(1) Approvals(1)
1
Flush Pendent QR/SR LH 5.6 ⁄2 175 F992 587 UL, ULC, SSL, NYC
1
Horizontal Sidewall QR/SR LH 5.6 ⁄2 175 A 545 UL, ULC, FM, SSL, NYC
COVERAGE
EXTENDED
17
QR/SR LH 8.0 ⁄32 175 A 547 UL, ULC, FM, SSL, NYC
1
QR/SR LH 5.6 ⁄2 175 FR-1 588 UL, ULC, FM, SSL, VdS, NYC
17
QR/SR LH 8.0 ⁄32 175 FR-1 589 UL, ULC, FM, SSL, NYC
1
Rec. Hor. Sidewall QR/SR LH 5.6 ⁄2 175 A 545 UL, ULC, FM, SSL, NYC
17
QR/SR LH 8.0 ⁄32 175 A 547 UL, ULC, FM, SSL, NYC
Flush Sidewall QR/SR LH 5.6 1⁄2 175 F993 591 UL, ULC, SSL, NYC
1
Upright QR All 5.6 ⁄2 300 A300 500A UL, ULC
1
SR All 5.6 ⁄2 300 A300 500A UL, ULC
1
Pendent QR All 5.6 ⁄2 300 A300 500A UL, ULC
1
SR All 5.6 ⁄2 300 A300 500A UL, ULC
1
Recessed Pendent QR All 5.6 ⁄2 300 A300 500A UL, ULC
PRESSURE
1
SR All 5.6 ⁄2 300 A300 500A UL, ULC
HIGH
1
Horizontal Sidewall QR LH/OH 5.6 ⁄2 300 A300/Q-71 500A UL, ULC
1
SR LH/OH 5.6 ⁄2 300 A300/Q-71 500A UL, ULC
1
Rec. Hor. Sidewall QR LH/OH 5.6 ⁄2 300 A300/Q-71 500A UL, ULC
1
SR LH/OH 5.6 ⁄2 300 A300/Q-71 500A UL, ULC
1
E. C. Sidewall QR LH 5.6 ⁄2 300 A300 QR-EC 500A UL, ULC
1
SR LH 5.6 ⁄2 300 A300 QR 500A UL, ULC
1
Rec. E.C. Sidewall QR LH 5.6 ⁄2 300 A300 QR-EC 500A UL, ULC
1
SR LH 5.6 ⁄2 300 A300 QR 500A UL, ULC
Pendent QR Residential 3.0 – 175 F680 583 UL, ULC, SSL, NYC
QR Residential 4.4 – 175 F983 584 UL, ULC, SSL, NYC
Recessed Pendent QR Residential 3.0 – 175 F680 583 UL, ULC, SSL, NYC
QR Residential 4.4 – 175 F983 584 UL, ULC, SSL, NYC
Concealed Pendent QR Residential 4.2 – 175 F978 584M UL, ULC, SSL, NYC
RESIDENTIAL
Flush Pendent QR Residential 4.2 – 175 F990 586F UL, ULC, SSL, NYC
QR Residential 5.6 – 175 F992 587 UL, ULC, SSL, NYC
Sidewall QR Residential 3.5 – 175 F685 587F UL, ULC, SSL, NYC
QR Residential 5.8 – 175 F687 587M UL, ULC, SSL, NYC
QR Residential 4.4 – 175 F984 587H UL, ULC, SSL, NYC
Recessed Sidewall QR Residential 3.5 – 175 F685 587F UL, ULC, SSL, NYC
QR Residential 5.8 – 175 F687 587M UL, ULC, SSL, NYC
QR Residential 4.4 – 175 F984 587H UL, ULC, SSL, NYC
Flush Sidewall QR Residential 5.6 – 175 F993 591 UL, ULC, SSL, NYC
INST.
1
Pendent QR All 5.6 ⁄2 175 G100 575A UL, C-UL
Sidewall QR LH/OH 5.6 12
⁄ 175 G102 575F UL, C-UL
1
Upright QR All 5.6 ⁄2 175 F960 551 UL, ULC, FM, NYC
1
SR All 5.6 ⁄2 175 F960 552 UL, ULC, FM, SSL, NYC
1
Pendent QR All 5.6 ⁄2 175 F960 551 UL, ULC, FM, NYC
1
SR All 5.6 ⁄2 175 F960 552 UL, ULC, FM, SSL, NYC
1
Recessed Pendent QR All 5.6 ⁄2 175 F960 551 UL, ULC, FM, NYC
DRY
1
SR All 5.6 ⁄2 175 F960 552 UL, ULC, FM, SSL, NYC
1
Deep Ceiling Pendent QR All 5.6 ⁄2 175 F960 551 UL, ULC, FM, NYC
1
SR All 5.6 ⁄2 175 F960 552 UL, ULC, FM, SSL, NYC
1
Horizontal Sidewall QR LH/OH 5.6 ⁄2 175 F960/Q-46 554 UL, ULC, FM, NYC
1
SR LH/OH 5.6 ⁄2 175 F960/Q-46 555 UL, ULC, FM, NYC
1
E.C. Hor. Sidewall QR LH 5.6 ⁄2 175 F960/Q-48 556 UL, ULC, NYC
SR LH 5.6 1⁄2 175 F960/Q-48 557 UL, ULC, NYC
3
ESFR Pendent QR Storage 14.0 ⁄4 175 ESFR-1 598 UL, ULC, FM, LPC, SSL, VdS, LA, NYC
QR Storage 25.2 – 175 ESFR-25 599 UL, C-UL, FM
1
Intermediate Level QR Storage 5.6, 8.0 ⁄2, 17⁄32 175 A 500M UL, ULC, FM, SSL, NYC
STORAGE
1
QR Storage 5.6 ⁄2 175 FR-1 501 UL, ULC, FM, NYC
17
QR Storage 8.0 ⁄32 175 FR-1 502M UL, ULC, FM
1
SR Storage 5.6, 8.0 ⁄2, 17⁄32 175 A 501M UL, ULC, FM, SSL, NYC
1
SR Storage 5.6 ⁄2 175 D 504 UL, ULC, FM, NYC
5
Large Drop SR Storage 11.2 ⁄8 175 F898 597 FM
5
Extra Large Orifice QR Storage 11.2 ⁄8 175 F892QR 595A UL, C-UL, FM
SR Storage 11.2 5⁄8 175 F892 595 UL, C-UL, FM, SSL, NYC
SPECIAL
1
Conventional QR Special 5.6, 8.0 ⁄2, 17⁄32 175 A 507 UL, ULC, LPC, SSL, VdS, NYC
1
(Old Style) SR Special 5.6, 8.0 ⁄2, 17⁄32 175 A 508M UL, ULC, LPC, SSL, VdS, NYC
1
SR Special 5.6 ⁄2 175 F950 509 UL, ULC, LPC, SSL
SR Special 1.4, 2.8, 5.6, 8.0 1⁄4, 3⁄8, 1⁄2, 17⁄32 175 D 510M UL, ULC, LPC, NYC
(1) Refer to the Technical Data Sheet (TD) for specific information. All versions of a sprinkler may not be listed or approved.
(2) Sprinkler Finish: B=Brass, BB=Bright Brass, C=Chrome, L=Lead Coating, P=Polyester Coating (White is standard), Wh=White,
W=Wax Coating (for 135° to 212°), EOL=Enamel over Lead Coating (286° to 360°).
(3) Escutcheon Finish:C=Chrome, Wh=White, Sp=Special Order any Color.
(4) F850 Wrench for polyester coated sprinkler.
(5) FM approval only with Model F705 Escutcheon.
8
Back
Selection Chart Section 2 of 2
Sprinkler
Temperature, °F(1) Element NPT, Inch Finish(1,2) Wrench Escutcheon(3) Notes TYPE
1
160 Solder ⁄2 C, BB, WH F873 C, WH, SP 16' x 16' - 20' x 20'; Aquarius Flush Style
1
135, 155, 175 3, 5 mm Bulb ⁄2 B, C, P (4) Max. Coverage 16' x 22'
COVERAGE
EXTENDED
3
135, 155, 175 3, 5 mm Bulb ⁄4 B, C, P (4) Max. Coverage 16' x 24'
1
165 Solder ⁄2 B, C F799 Max. Coverage 16' x 20'
3
140, 165 Solder ⁄4 B, C F799 Max. Coverage 16' x 24'
1
135, 155, 175 3, 5 mm Bulb ⁄2 B, C, P F850 Max. Coverage 16' x 22'; Notes: (5,9)
3
135, 155, 175 3, 5 mm Bulb ⁄4 B, C, P F850 C, WH, SP Max. Coverage 16' x 24'; Notes: (5,9)
160 Solder 1⁄2 C, BB, WH F873 C, WH, SP Max. Coverage 14' x 18'; Aquarius Flush Style
1
135, 155, 175, 200, 286 3 mm Bulb ⁄2 B, C, P (4)
1
135, 155, 175, 200, 286, 360 5 mm Bulb ⁄2 B, C, P (4)
1
135, 155, 175, 200, 286 3 mm Bulb ⁄2 B, C, P (4)
1
135, 155, 175, 200, 286, 360 5 mm Bulb ⁄2 B, C, P (4)
1
135, 155, 175, 200 3 mm Bulb ⁄2 B, C, P F850 C, WH, SP Note: (10)
PRESSURE
1
135, 155, 175, 200 5 mm Bulb ⁄2 B, C, P F850 C, WH, SP Note: (10)
HIGH
1
135, 155, 175, 200, 286 3 mm Bulb ⁄2 B, C, P (4)
1
135, 155, 175, 200, 286, 360 5 mm Bulb ⁄2 B, C, P (4)
1
135, 155, 175, 200 3 mm Bulb ⁄2 B, C, P F850 C, WH, SP
1
135, 155, 175, 200 5 mm Bulb ⁄2 B, C, P F850 C, WH, SP
1
135, 155, 175 3 mm Bulb ⁄2 B, C, P (4) Max. Coverage 16' x 22'; Note: (10)
1
135, 155 5 mm Bulb ⁄2 B, C, P (4) Max. Coverage 16' x 24'; Note: (10)
1
135, 155, 175 3 mm Bulb ⁄2 B, C, P F850 C, WH, SP Max. Coverage 16' x 22'; Note: (10)
135, 155 5 mm Bulb 1⁄2 B, C, P F850 C, WH, SP Max. Coverage 16' x 24'; Note: (10)
1
155, 175 3 mm Bulb ⁄2 B, C, P (4) Max. Coverage 20' x 20'
1
155, 175 3 mm Bulb ⁄2 B, C, P (4) Max. Coverage 20' x 20'
1
155, 175 3 mm Bulb ⁄2 B, C, P F850 C, WH, SP Max. Coverage 20' x 20'; Note: (9)
1
155 3 mm Bulb ⁄2 B, C, P F850 C, WH, SP Max. Coverage 20' x 20'; Note: (10)
1
155 3 mm Bulb ⁄2 – F874 C, WH, SP Max. Coverage 20' x 20'; 1⁄2 Adjustment
RESIDENTIAL
1
160 Solder ⁄2 C, BB, WH F873 C, WH, SP Max. Coverage 20' x 20'; Aquarius Flush Style
1
160 Solder ⁄2 C, BB, WH F873 C, WH, SP Max. Coverage 18' x 18'; Aquarius Flush Style
1
155, 175 3 mm Bulb ⁄2 B, C, P (4) Max. Coverage 16' x 16'
1
155 3 mm Bulb ⁄2 B, C, P F799 Max. Coverage 16' x 20'
1
155 3 mm Bulb ⁄2 B, C, P (4) Max. Coverage 16' x 16'
1
155, 175 3 mm Bulb ⁄2 B, C, P F850 C, WH, SP Max. Coverage 16' x 16'; Note: (8)
1
155 3 mm Bulb ⁄2 B, C, P 1948 C, WH, SP Max. Coverage 16' x 16'; Note: (8)
1
155 3 mm Bulb ⁄2 B, C, P F850 C, WH, SP Max. Coverage 16' x 16'; Note: (8)
160 Solder 1⁄2 C, BB, WH F873 C, WH, SP Max. Coverage 14' x 18'; Aquarius Flush Style
INST.
1
135, 155, 175, 200 2.5 mm Bulb ⁄2 C 1509-1, -3 C
135, 155, 175, 200 2.5 mm Bulb 12
⁄ C 1509-1, -3 C
135, 155, 175, 200, 286 3 mm Bulb 1 B, C Adj. Wrench Lengths 5" to 48" in 1⁄2" increments
135, 155, 175, 200, 286, 360 5 mm Bulb 1 B, C Adj. Wrench Lengths 5" to 48" in 1⁄2" increments
135, 155, 175, 200, 286 3 mm Bulb 1 B, C Adj. Wrench C, WH Lengths 2" to 48" in 1⁄2" increments
135, 155, 175, 200, 286, 360 5 mm Bulb 1 B, C Adj. Wrench C, WH Lengths 2" to 48" in 1⁄2" increments
135, 155, 175, 200 3 mm Bulb 1 B, C F870 C, WH Lengths 31⁄2" to 48" in 1⁄4" increments
DRY
135, 155, 175, 200 5 mm Bulb 1 B, C F870 C, WH Lengths 31⁄2" to 48" in 1⁄4" increments
135, 155, 175, 200, 286 3 mm Bulb 1 B, C Adj. Wrench C, WH Lengths 1⁄2" to 46" in 1⁄2" increments
135, 155, 175, 200, 286, 360 5 mm Bulb 1 B, C Adj. Wrench C, WH Lengths 1⁄2" to 46" in 1⁄2" increments
135, 155, 175, 200, 286 3 mm Bulb 1 B, C Adj. Wrench C, WH Lengths 21⁄2" to 48" in 1⁄2" increments
135, 155, 175, 200, 286, 360 5 mm Bulb 1 B, C Adj. Wrench C, WH Lengths 21⁄2" to 48" in 1⁄2" increments
135, 155, 175 3 mm Bulb 1 B, C Adj. Wrench C, WH Lengths 21⁄2" to 48" in 1⁄2" increments
135, 155, 175 5 mm Bulb 1 B, C Adj. Wrench C, WH Lengths 21⁄2" to 48" in 1⁄2" increments
3
165, 214 Solder ⁄4 B F872 35' Storage/ 45' Ceiling
165, 214 Solder 1 B Adj. Wrench 40' Storage/ 45' Ceiling
1
135, 155, 175, 200, 286 3 mm Bulb ⁄2, 3⁄4 B, C Adj. Wrench
STORAGE
1
165 Solder ⁄2 B, C F799
3
165 Solder ⁄4 B, C F799
1
135, 155, 175, 200, 286, 360 5 mm Bulb ⁄2, 3⁄4 B, C Adj. Wrench
1
135, 175, 250 11 mm Bulb ⁄2 W, L F799
3
155, 200, 286 5 mm Bulb ⁄4 B Adj. Wrench
3
135, 155, 175, 200, 286 3 mm Bulb ⁄4 B, C Adj. Wrench
3
135, 155, 175, 200, 286 5 mm Bulb ⁄4 B, C Adj. Wrench
SPECIAL
1
135, 155, 175, 200, 286 3 mm Bulb ⁄2, 3⁄4 B, C, P (4)
1
135, 155, 175, 200, 286, 360 5 mm Bulb ⁄2, 3⁄4 B, C, P (4)
1
165, 212, 286, 350 Solder ⁄2 B, C, L, W, WOL, EOL F799
135, 175, 250, 325, 400, 500 11 mm Bulb 1⁄2, 3⁄4 W, L, WOL, EOL F799
(6) Response: SR=Standard Response, QR=Quick Response
(7) Hazard: LH=Light Hazard, OH=Ordinary Hazard, All= Any Hazard
(8) Separately ordered escutcheon: F705-1⁄2" adj.
(9) Separately ordered escutcheon: F700-3⁄4" adj. or F705-1⁄2" adj.
(10) Separately ordered escutcheon: F700-3⁄4" adj.
9
Back
◆ Small orifice, standard response, spray ◆ Standard response, spray sprinkler ◆ Large orifice, standard response, spray
sprinkler ◆ Discharges a hemispherical water spray sprinklers
◆ Designed for use in light hazard pattern in the area under the sprinkler ◆ Designed for use in commercial and
occupancies ◆ Small frame, narrow profile bulb industrial applications
◆ Requires less water than standard K=5.6 Orifice Size: 1⁄2" (15 mm) ◆ Higher water discharge rate than K=5.6
orifice sprinkler Temperature Ratings: sprinklers
◆ Pintle provides visual indication that these 135°F/57°C, 155°F/68°C, 175°F/79°C,
sprinklers have an orifice other than K=5.6 ◆ Variety of finishes available to blend with
200°F/93°C, 286°F/141°C, 360°F/182°C surrounding surfaces
Orifice Size: 3⁄8" Thread Size (NPT): 1⁄2"
Temperature Ratings: Orifice Size: 17⁄32" (20 mm)
Maximum Service Pressure: 175 psi (12.1 bar)
135°F/57°C, 155°F/68°C, 175°F/79°C, Temperature Ratings:
Listings and Approvals:
200°F/93°C, 286°F/141°C, 360°F/182°C 135°F/57°C, 155°F/68°C, 175°F/79°C,
ULI, ULC, FM, LPC, SSL and VdS 200°F/93°C, 286°F/141°C, 360°F/182°C
Thread Size (NPT): 1⁄2"
Finishes: Thread Size (NPT): 3⁄4"
Maximum Service Pressure: 175 psi (12.1 bar)
Natural brass, chrome plated, and Maximum Service Pressure: 175 psi (12.1 bar)
Listings and Approvals: polyester coated in any color
ULI, ULC, and FM Listings and Approvals:
Technical Data Sheet: TD516M
(See TD514Q for SSL, LPC and VdS) ULI, ULC, FM, LPC, SSL and VdS
Finishes: Finishes:
Natural brass, chrome plated, and Natural brass, chrome plated, and
polyester coated in any color polyester coated in any color
Technical Data Sheet: TD514M Technical Data Sheet: TD526Q
11
Back
◆ Concealed standard response, spray ◆ Bulb type, standard response, spray ◆ Solder type, standard response, spray
sprinkler sprinkler sprinkler
◆ Enclosed escutcheon plate for use in those ◆ Extra-high and ultra-high temperature ◆ Discharges a hemispherical water spray
applications where aesthetics is a primary ratings and corrosion resistant coatings pattern in the area under the sprinkler
consideration Orifice Size: 1⁄2" (15mm) Orifice Size: 1⁄2"
◆ Separable, two-piece design of the Temperature Ratings: Temperature Ratings:
mounting cup and cover plate allows 135°F/57°C, 155°F/68°C, 175°F/79°C, 165°F/74°C, 212°F/100°C, 286°F/141°C,
installation of the sprinklers and pressure 200°F/93°C, 250°F/121°C, 286°F/141°C, 350°F/177°C
testing of the fire protection system prior 325°F/163°C, 360°F/182°C, 400°F/204°C, Thread Size (NPT): 1⁄2"
to installation of a suspended ceiling or 500°F/260°C, 650°F/343°C
application of the finish coating to a fixed Maximum Service Pressure: 175 psi (12.1 bar)
Thread Size (NPT): 1⁄2" Listings and Approvals:
ceiling
Maximum Service Pressure: 175 psi (12.1 bar) ULI, ULC, FM, LPC, SSL, and VdS
◆ Internally threaded closure with 1⁄2"
(13 mm) of adjustment Listings and Approvals: ULI, ULC, FM, and LPC Finishes:
Orifice Size: 1⁄2" Finishes: Natural brass, chrome plated, lead coated,
Temperature Ratings: Natural brass, chrome plated (400˚F to Corroproof® coated, and Corroproof® over
650˚F). Lead coated (135˚F to 500˚F). lead coated
135°F/57°C, 155°F/68°C, 175°F/79°C,
Corroproof® coated (135˚F to 200˚F). Technical Data Sheet: TD517
200°F/93°C
Corroproof® over lead coated (135˚F to
Thread Size (NPT): 1⁄2" 360˚F)
Maximum Service Pressure: 175 psi (12.1 bar) Technical Data Sheet: TD525M
Listings and Approvals: ULI, ULC and FM
Finishes:
Cover plate standard finishes are chrome
plated and white painted - any color cover
plate paint is available upon request
Technical Data Sheet: TD579Q
12
Back
◆ Small orifice, standard response, spray ◆ Solder type, standard response, sidewall
sprinklers sprinkler
◆ Solder type ◆ Designed for installation along a wall or on
◆ Designed for light hazard occupancies the side of a beam just beneath a smooth
requiring less water than a standard 1⁄2" ceiling
orifice sprinkler ◆ Water discharge is directed primarily
◆ A pintle, extending from the deflector, outward and downward in a quarter
provides a visual indication that these spherical pattern; however, a portion is
sprinklers have an orifice size other also directed to the backwall
than 1⁄2" Orifice Size: 1⁄2" (15 mm)
Orifice Size: Temperature Ratings:
1⁄4" (K=1.4), 3⁄8" (K=2.8) & 7⁄16" (K=4.2) 165°F/74°C, 212°F/100°C, 286°F/141°C,
Temperature Ratings: 350°F/177°C
165°F/74°C, 212°F/100°C, 286°F/141°C, Thread Size (NPT): 1⁄2"
350°F/177°C Maximum Service Pressure: 175 psi (12.1 bar)
Thread Size (NPT): 1⁄2" Listings and Approvals:
Maximum Service Pressure: 175 psi (12.1 bar) ULI and ULC (light and ordinary hazard);
Listings and Approvals: FM (light hazard); and, SSL
ULI and ULC. FM (K=2.8 only). Finishes:
Finishes: Natural brass, chrome plated, lead coated,
Natural brass, chrome plated, lead coated, Corroproof® coated, and Corroproof® over
Corroproof® coated, and Corroproof® over lead coated
lead coated Technical Data Sheet: TD536
Technical Data Sheet: TD515
13
Back
◆ Small orifice, quick response, spray ◆ Quick response, spray sprinkler ◆ Large orifice, quick response, spray
sprinklers ◆ Hemispherical water spray pattern in the sprinklers
◆ Designed for use in light hazard area under the sprinkler ◆ Designed for use in applications requiring
occupancies ◆ Small frame and narrow profile bulb higher water discharge rate than standard
◆ Discharge rate that is approximately 50% enhances their appearance K=5.6 sprinkler
of a standard K=5.6 orifice sprinkler when Orifice Size: 1⁄2" (15 mm) ◆ Commercial and industrial application
flowing at the same pressure Temperature Ratings: Orifice Size: 17⁄32" (20 mm)
◆ A pintle, extending from the deflector, 135°F/57°C, 155°F/68°C, 175°F/79°C, Temperature Ratings:
provides a visual indication that these 200°F/93°C, 286°F/141°C 135°F/57°C, 155°F/68°C, 175°F/79°C,
sprinklers have an orifice other than K=5.6 200°F/93°C, 286°F/141°C
Thread Size (NPT): 1⁄2"
Orifice Size: 3⁄8" Thread Size (NPT): 3⁄4"
Maximum Service Pressure: 175 psi (12.1 bar)
Temperature Ratings: Maximum Service Pressure: 175 psi (12.1 bar)
Listings and Approvals:
135°F/57°C, 155°F/68°C, 175°F/79°C, Listings and Approvals:
ULI, ULC, FM, LPC, SSL, and VdS
200°F/93°C, 286°F/141°C
Finishes: ULI, ULC, FM, LPC, SSL, and VdS
Thread Size (NPT): 1⁄2"
Natural brass, chrome plated, and Finishes:
Maximum Service Pressure: 175 psi (12.1 bar)
polyester coated in any color Natural brass, chrome plated, and
Listings and Approvals: polyester coated in any color
Technical Data Sheet: TD515M
ULI, ULC, and FM (See TD513Q for SSL, Technical Data Sheet: TD525Q
LPC and VdS)
Finishes:
Natural brass, chrome plated, and
polyester coated in any color
Technical Data Sheet: TD513M
◆ Quick response, spray sprinkler ◆ Low profile, quick response, spray ◆ Low profile, quick response, sidewall
◆ Concealed in an enclosed escutcheon plate sprinkler sprinkler
with flat cover for use in those applications ◆ Designed to be installed in the flush ◆ Designed for installation along a wall or
where aesthetics is a primary consider- pendent position for either new installa- lintel and just beneath a smooth ceiling
ation tions or to replace standard sprinklers to ◆ Escutcheon plates with up to 1⁄2"
◆ Separable, two-piece design of the achieve a more pleasing appearance (12.7 mm) of adjustment that allows
mounting cup and cover plate allows ◆ Escutcheon plates with up to 1⁄2" flexibility during installation
installation of the sprinklers and pressure (12.7 mm) of adjustment that allows Orifice Size: 1⁄2" (15 mm)
testing of the fire protection system prior flexibility during installation Temperature Ratings:
to installation of a suspended ceiling or Orifice Size: 1⁄2" (15 mm) 160°F/71°C, 212°F/100°C
application of the finish coating to a fixed Temperature Ratings:
ceiling Thread Size (NPT): 1⁄2"
160°F/71°C, 212°F/100°C Maximum Service Pressure: 175 psi (12.1 bar)
◆ Internally threaded closure with 1⁄2"
Thread Size (NPT): 1⁄2" Listings and Approvals:
(12.7 mm) of adjustment
Maximum Service Pressure: 175 psi (12.1 bar) ULI, ULC, LPC and SSL
Orifice Size: 1⁄2" (15 mm)
Listings and Approvals: Finishes:
Temperature Ratings:
ULI, ULC, LPC and SSL Sprinkler: Chrome plated, bright brass, or
135°F/57°C, 155°F/68°C, 175°F/79°C,
200°F/93°C Finishes: white
Thread Size (NPT): 1⁄2" Sprinkler: Chrome plated, bright brass, or Escutcheon: Chrome plated, bright brass,
white or color coated in any color
Maximum Service Pressure: 175 psi (12.1 bar)
Escutcheon: Chrome plated or color coated Technical Data Sheet: TD538
Listings and Approvals:
in any color
ULI, ULC and FM (standard response)
Technical Data Sheet: TD520
Finishes:
Cover plates are supplied chrome plated or
with any color factory applied paint
Technical Data Sheet: TD578Q
16
Back
Model FR-1 Fast Response Model FR-1/Q-46 Fast Response Model FR-1 Fast Response
K=2.8 K=5.6 K=5.6
Pendent and Upright Sprinklers Horizontal Sidewall Sprinkler Pendent and Upright Sprinklers
◆ Small orifice, fast response, spray ◆ Designed for compact installation along a ◆ Solder type, fast response, spray sprinkler
sprinklers wall or on the side of a beam just beneath ◆ Typically used in hotels, motels, office
◆ Designed for use in light hazard a smooth ceiling buildings and other commercial and
occupancies requiring less water than is ◆ Generally used in lieu of pendent or industrial applications
discharged from a standard K=5.6 orifice upright sprinklers because of aesthetics, Orifice Size: 1⁄2" (15mm)
sprinkler building construction or economic Temperature Ratings:
◆ A pintle, extending from the deflector, considerations
140°F/60°C, 165°F/74°C, 212°F/100°C
provides a visual indication that these ◆ Can be recessed with GEM’s standard
Thread Size (NPT): 1⁄2"
sprinklers have an orifice other than K=5.6 Model F705 two piece Escutcheon
Maximum Service Pressure: 175 psi (12.1 bar)
Orifice Size: 3⁄8" Orifice Size: 1⁄2" (15 mm)
Listings and Approvals:
Temperature Ratings: Temperature Ratings:
ULI, ULC, FM, LPC, SSL, and VdS
140°F/60°C, 165°F/74°C, 212°F/100°C 140°F/60°C, 165°F/74°C, 212°F/100°C
Finishes:
Thread Size (NPT): 1⁄2" Thread Size (NPT): 1⁄2"
Sprinkler: Natural brass and chrome plated
Maximum Service Pressure: 175 psi (12.1 bar) Maximum Service Pressure: 175 psi (12.1 bar)
Technical Data Sheet: TD516
Listings and Approvals: ULI and ULC Listings and Approvals:
Finishes: ULI and ULC (light and ordinary hazard);
Natural brass and chrome plated FM (light hazard); and SSL
Technical Data Sheet: TD514 Finishes:
Natural brass and chrome plated
Technical Data Sheet: TD535
◆ The addition of a Model F705 two-piece escutcheon converts the ◆ Large orifice, solder type spray sprinkler
FR-1 to an attractive recessed spray sprinkler ◆ Provides approximately 50% greater water discharge
Orifice Size: 3⁄8" (K=2.8) & 1⁄2" (15 mm) (K=5.6) than standard K=5.6 orifice sprinkler
Temperature Ratings: Orifice Size: 17⁄32" (20 mm)
140°F/60°C, 165°F/74°C, 212°F/100°C Temperature Ratings:
Thread Size (NPT): 1⁄2" 140°F/60°C, 165°F/74°C, 212°F/100°C
Maximum Service Pressure: 175 psi (12.1 bar) Thread Size (NPT): 3⁄4"
Listings and Approvals: Maximum Service Pressure: 175 psi (12.1 bar)
ULI and ULC Listings and Approvals:
Finishes: ULI, ULC, FM, and SSL
Sprinkler: Natural brass and chrome plated Finishes:
Escutcheon: Chrome plated or color coated in any color Natural brass and chrome plated
Technical Data Sheet: TD514 (K=2.8) or TD516 (K=5.6) Technical Data Sheet: TD526
17
Back
18
Back
◆ Low profile, solder type sprinkler ◆ Solder type, extended coverage horizontal sidewall sprinklers
◆ Nominal K-Factor of 5.6 provide versatility for light hazard extended coverage areas
◆ Install in flush horizontal sidewall position just below a smooth level ceiling ◆ K=5.6 for QR-EC coverage areas up to 16' x 20' (4.9 m x 6.1 m)*
◆ EC coverage areas up to 14' x 18' (4.3 m x 5.5 m) and and 18' x 16' (5.5 m x 4.9 m)
QR-EC coverage areas up to 14' x 16' (4.3 m x 4.9 m) ◆ K=8.0 for EC and QR-EC coverage areas up to 16' x 24'
◆ Escutcheon plates with up to 1⁄2" (12.7 mm) of horizontal adjustment (4.9 m x 7.3 m)*
reduce position accuracy ◆ QR-EC coverage areas up to 20' x 16' (6.1 m x 4.9 m)
Orifice Size: 1⁄2" (15mm) Orifice Size:
1⁄2" (15mm) (K=5.6) & 17⁄32" (20 mm) (K=8.0)
Temperature Ratings: 160˚F/71˚C
Thread Size (NPT): 1⁄2" Temperature Ratings:
Maximum Service Pressure: 175 psi (12.1 bar) 165°F/74°C (K=5.6) & 140˚F/60˚C, 165˚F/74˚C (K=8.0)
Listings and Approvals: ULI, ULC, and SSL. Thread Size (NPT): 1⁄2" (K=5.6) & 3⁄4" (K=8.0)
Finishes: Maximum Service Pressure: 175 psi (12.1 bar)
Sprinkler: Chrome plated, bright brass, or white. Listings and Approvals: ULI, and ULC; *FM; SSL; and VdS (K=5.6)
Escutcheon: Chrome plated, or color coated in any color Finishes: Natural brass and chrome plated
Technical Data Sheet: TD591 Technical Data Sheet: TD588 (K=5.6) or TD589 (K=8.0)
* FM approved for 16' x 20' coverage area only.
19
Back
◆ The addition of a Model F700 two-piece ◆ Standard response , spray sprinkler ◆ Recessed versions of the FR-1 solder type
escutcheon converts the 5 mm bulb Model concealed in an enclosed escutcheon plate sprinklers
A pendent to a highly attractive standard with flat cover for use in those applications ◆ Recessed versions use GEM’s standard
response, recessed spray sprinkler where aesthetics is a primary consideration Model F705, two piece escutcheon
◆ The F700 provides 3⁄4" (19.1 mm) of ◆ The separable, two-piece design of the assembly
vertical adjustment from the flush pendent mounting cup and cover plate allows ◆ Use of the K=2.8 orifice is limited to light
position installation of the sprinklers and pressure hazard occupancies
◆ Adjustment allows flexibility in the testing of the fire protection system prior
Orifice Size:
installation of the sprinkler with a drop to installation of a suspended ceiling or
3⁄8" (K=2.8) & 1⁄2" (15 mm) (K=5.6)
fitting application of the finish coating to a fixed
ceiling Temperature Ratings:
Orifice Size:
1⁄2" (15mm) (K=5.6) & ◆ Features an internally threaded closure 140˚F/60˚C, 165˚F/74˚C, 212˚F/100˚C
17⁄32" (20 mm) (K=8.0) with 1⁄2" (12.7 mm) of adjustment Thread Size (NPT): 1⁄2"
Temperature Ratings: Orifice Size: 1⁄2" (15mm) Maximum Service Pressure: 175 psi (12.1 bar)
135˚F/57˚C, 155˚F/68˚C, 175˚F/79˚C, Temperature Ratings: Listings and Approvals: ULI and ULC
200˚F/93˚C 135˚F/57˚C, 155˚F/68˚C, 175˚F/79˚C, Finishes:
Thread Size (NPT): 200˚F/93˚C Sprinkler: Natural brass or chrome plated
1⁄2" (K=5.6) & 3⁄4" (K=8.0) Thread Size (NPT): 1⁄2" Escutcheon: Chrome plate or color coated
Maximum Service Pressure: 175 psi (12.1 bar) Maximum Service Pressure: 175 psi (12.1 bar) in any color
Listings and Approvals: Listings and Approvals: Technical Data Sheet:
ULI, ULC, FM, SSL, and LPC ULI, ULC, and FM TD514 (K=2.8) or TD516 (K=5.6)
Finishes: Finishes:
Sprinkler: Natural brass, chrome plated, Cover plates are supplied chrome plated or
and polyester coated in any color with any color factory applied paint
Escutcheon: Chrome plated or color coated Technical Data Sheet: TD579Q
in any color
Technical Data Sheet:
TD516M (K=5.6) or TD526Q (K=8.0)
20
Back
ULI, ULC and FM as standard response 1⁄2" (K=5.6) & 3⁄4" (K=8.0) Maximum Service Pressure: 175 psi (12.1 bar)
Finishes: Maximum Service Pressure: 175 psi (12.1 bar) Listings and Approvals:
Cover plates are supplied chrome plated or Listings and Approvals: ULI, ULC, FM and SSL
with any color factory applied paint ULI, ULC, FM, SSL and LPC Finishes:
Technical Data Sheet: TD578Q Finishes: Sprinkler: Natural brass, chrome plated,
Sprinkler: Natural brass, chrome plated, and polyester coated in any color
and polyester coated in any color Escutcheon: Chrome plated or color coated
Escutcheon: Chrome plated or color coated in any color
in any color Technical Data Sheet:
Technical Data Sheet: TD545 (K=5.6) or TD547 (K=8.0)
TD515M (K=5.6) or TD525Q (K=8.0)
21
Back
◆ Designed for use in the protection of high- ◆ Discharge rate approximately 60% greater
◆ Utilizes a 5 mm bulb to seal the sprinkler
piled storage than K=8.0 sprinklers and approximately
outlet and a temperature sensitive
100% greater than K=5.6 sprinklers when
◆ Eliminates many of the requirements for bimetallic disc to control water flow
flowing at the same rate
in-rack sprinklers ◆ Ideal for applications where water
◆ Ideal for use in high density applications
◆ Materials may be stored up to 40 feet discharge, either during a fire or from
such as the protection of high-piled
(12.2 m) high, in buildings up to 45 feet accidental damage is a concern
storage since high flow rates can be
(13.7 m) ◆ A flush mount escutcheon providing up to produced at lower pressures
◆ ESFR-1 and ESFR-25 sprinklers use the 1" (25.4 mm) of vertical adjustment is
Orifice Size: 5⁄8"
principles of direct attack on burning fuel available to provide an aesthetically
by improved heavy sprinkler discharge pleasing, low profile installation Temperature Ratings:
◆ Patented frame design substantially ◆ Bimetallic disc cycles water on and off as 135˚F/57˚C, 155˚F/68˚C, 175˚F/79˚C
reduces the frame shadow effects that necessary to control fire 200˚F/93˚C, 286˚F/141˚C
often produce non-uniformity in spray Orifice Size: 1⁄2" (15 mm) Thread Size (NPT): 3⁄4"
pattern Temperature Ratings: Maximum Service Pressure: 175 psi (12.1 bar)
◆ Novel orifice seal and unique fast response 135˚F/57˚C, 175˚F/79˚C Listings and Approvals:
link design make the ESFR-1 and ESFR-25 UL, C-UL, FM, and SSL
Thread Size (NPT): 1⁄2"
the very latest in sprinkler technology Finishes:
Maximum Service Pressure: 175 psi (12.1 bar)
Orifice Size: Natural brass and chrome plated
3⁄4" (ESFR-1) & 1" (ESFR-25)
Listings and Approvals:
FM, and SSL. Technical Data Sheet:
Temperature Ratings: TD595 (F892) or TD595A (F892QR)
Finishes:
165˚F/74˚C, 214˚F/101˚C
Sprinkler: Natural brass or chrome plated
Thread Size (NPT):
3⁄4" (ESFR-1) & 1" (ESFR-25)
Escutcheon: Chrome plated or white color
coated
Maximum Service Pressure: 175 psi (12.1 bar)
Technical Data Sheet: TD560
Listings and Approvals:
ESFR-1: ULI, ULC, FM, SSL, LPC, and VdS
ESFR-25: FM (Others pending)
Finishes:
Natural brass
Technical Data Sheet:
TD598 (ESFR-1) or TD599 (ESFR-25)
22
Back
23
Back
24
Back
◆ Designed for use in automatic sprinkler systems for the protection ◆ Designed for the protection of high piled storage
of light hazards up to a maximum coverage area of 400ft2 ◆ Can provide a higher level of protection than standard spray
◆ Recessed version is obtained by combining the pendent sprinkler sprinklers
with the Model F705 recessed escutcheon (3/4") ◆ Can provide an advantage by eliminating in-rack sprinklers
◆ Rated for use at a maximum service pressure of 175 psi (12.1 bar) ◆ 175 psi (12.1 bar)
Orifice Size: 17⁄32" (K=8.0) & 5⁄8" (K=11.2) Orifice Size: 5⁄8"
Temperature Ratings: 135˚F/57˚C, 155˚F/68˚C, 175˚F/79˚C, 200°F/93°C Temperature Ratings: 155˚F/68˚C, 200°F/93°C, 286°F/141°C
Thread Size (NPT): 3⁄4" Thread Size (NPT): 3⁄4"
Maximum Service Pressure: 175 psi (12.1 bar) Maximum Service Pressure: 175 psi (12.1 bar)
Listings and Approvals: UL and C-UL Listed Listings and approvals:
Finishes: Approved by Factory Mutual Research Corporation
Sprinkler: Natural Brass, White Polyester, Chrome Plated Finishes:
Escutcheon: Chrome Plated, White Color Coated Natural brass finish
Technical Data Sheet: TD594 (K=8.0), & TD594M (K=11.2) Technical Data Sheet: TD597
Type 316
Stainless Steel
Bulb Type, K=5.6,
Pendent and Upright
Sprinklers
26
Back
Orifice Size: 1⁄2" (k=5.6), 17⁄32" (k=8.0) Orifice Size: 1⁄2" (k=5.6), 17⁄32" (k=8.0)
Temperature Ratings: Temperature Ratings:
135˚F/57˚C, 155˚F/68˚C, 175˚F/79˚C, 200˚F/93˚C, 286˚F/141˚C, 135˚F/57˚C, 155˚F/68˚C, 175˚F/79˚C, 200˚F/93˚C, 286˚F/141˚C
360˚F/182˚C Thread Size (NPT): 1⁄2" (k=5.6), 3⁄4" (k=8.0)
Thread Size (NPT): 1⁄2" (k=5.6), 3⁄4" (k=8.0) Maximum Service Pressure: 175 psi (12.1 bar)
Maximum Service Pressure: 175 psi (12.1 bar) Listings and Approvals: ULI, ULC, LPC, and SSL and VdS
Listings and Approvals: ULI, ULC, LPC, SSL and VdS Finishes:
Finishes: Natural brass and chrome plated and polyester coated in any color.
Natural brass, chrome plated and polyester coated in any color. Technical Data Sheets: TD507
Technical Data Sheets: TD508M
F950 Issue D
Standard Response Standard Response
K=5.6 K=1.4, 2.8, 5.6, 8.0
Conventional Conventional
(Old Style) (Old Style)
Sprinklers Sprinklers
Orifice Size: 1⁄2" (k=5.6) Orifice Size: 1⁄4" (k=1.4), 3⁄8" (k=2.8), 1⁄2" (k=5.6),17⁄32" (k=8.0)
Temperature Ratings: Temperature Ratings:
165˚F/74˚C, 212˚F/100˚C, 286˚F/141˚C, 350˚F/9177˚C 135˚F/57˚C, 155˚F/68˚C, 175˚F/79˚C, 200˚F/93˚C, 250˚F/121˚C, 286˚F/
Thread Size (NPT): 1⁄2" (k=5.6) 141˚C, 325˚F/163˚C, 360˚F/182˚C, 400˚F/204˚C, 500˚F/260˚C
Maximum Service Pressure: 175 psi (12.1 bar) Thread Size (NPT): 1⁄2" (k=1.4, 2.8, 5.6), 3⁄4" (k=8.0)
Listings and Approvals: ULI, ULC, LPC, SSL and LPC Maximum Service Pressure: 175 psi (12.1 bar)
Finishes: Listings and Approvals: ULI, ULC, and LPC (k=5.6)
Natural brass and chrome plated. Also available in lead coated, Finishes:
Corroproof® coated, and Corroproof® over lead coated Natural brass and chrome plated. Also available in lead coated,
Technical Data Sheets: TD509 Corroproof® coated, and Corroproof® over lead coated
Technical Data Sheets: TD510M
27
Back
28
Back
◆ Available at the ordinary temperature flush sidewall position ◆ Screw type engagement of the mounting
rating of 155˚F/68˚C, as well as in the ◆ Suitable for sidewall coverage areas up to plate position will not change in relation to
intermediate temperature rating of 175˚F/ 16' x 16' (4.9 m x 4.9 m) the ceiling
79˚C for use with ambient temperatures up Orifice Size: 7⁄16" (k=4.4) Orifice Size: 7⁄16" (k=4.2)
to 150˚F/66˚C with coverage areas up to Temperature Ratings: 155˚F/68˚C Temperature Ratings: 155˚F/68˚C
14' x 14' (4.3 m x 4.3 m)
Thread Size (NPT): 1⁄2" Thread Size (NPT): 1⁄2"
Orifice Size: 7⁄16" (k=4.4)
Maximum Service Pressure: 175 psi (12.1 bar) Maximum Service Pressure: 175 psi (12.1 bar)
Temperature Ratings: 155˚F/68˚C, 175˚F/79˚C*
Listings and Approvals: ULI, ULC and SSL Listings and Approvals: UL, ULC, and SSL
Thread Size (NPT): 1⁄2"
Finishes: Finishes:
Maximum Service Pressure: 175 psi (12.1 bar)
Sprinkler: Chrome plated, natural brass, Cover plates are supplied with a satin
Listings and Approvals: ULI, ULC, and SSL and polyester coated in any color chrome finish or with any color factory
Finishes: Escutcheon: Chrome plated or polyester applied paint
Sprinkler: Chrome plated, natural brass, coated in any color Technical Data Sheet: TD584M
and polyester coated in any color Technical Data Sheet: TD587H
Escutcheon: Chrome plated or polyester
coated in any color
Technical Data Sheet: TD584
*w/o Recessed Escutcheon
29
Back
◆ Aesthetically pleasing flush design ◆ Attractive flush design ◆ Good looking, low profile sprinkler
◆ Designed to be installed in the flush ◆ Designed to be installed in the flush designed for installation along a wall or
pendent position for residential coverage pendent position for residential coverage lintel and just below a smooth, level ceiling
areas up to 20' x 20' (6.1 m x 6.1 m) areas up to 18' x 18' (5.5 m x 5.5 m) ◆ Designed to be installed in the flush
◆ Escutcheon plates with up to 1⁄2" (12.7 ◆ Escutcheon plates with up to 1⁄2" (12.7 sidewall position for residential coverage
mm) of vertical adjustment allows mm) of vertical adjustment allows areas up to 14' x 14' (4.3 m x 4.3 m)
flexibility during installation flexibility during installation ◆ Escutcheon plates with up to 1⁄2" (12.7
Orifice Size: 7⁄16" (k=4.2) Orifice Size: 1⁄2" (k=5.6) mm) of horizontal adjustment allows
flexibility during installation
Temperature Ratings: 160˚F/71˚C Temperature Ratings: 160˚F/71˚C
Orifice Size: 1⁄2" (k=5.6)
Thread Size (NPT): 1⁄2" Thread Size (NPT): 1⁄2"
Temperature Ratings: 160˚F/71˚C
Maximum Service Pressure: 175 psi (12.1 bar) Maximum Service Pressure: 175 psi (12.1 bar)
Thread Size (NPT): 1⁄2"
Listings and Approvals: ULI, ULC, and SSL Listings and Approvals: ULI, ULC, and SSL
Maximum Service Pressure: 175 psi (12.1 bar)
Finishes: Finishes:
Listings and Approvals: ULI, ULC, and SSL
Sprinkler: Chrome plated, bright brass, or Sprinkler: Chrome plated, bright brass, or
white white Finishes:
Escutcheon: Chrome plated or color coated Escutcheon: Chrome plated or color coated Sprinkler: Chrome plated, bright brass, or
in any color in any color white
Technical Data Sheet: TD586F Technical Data Sheet: TD587 Escutcheon: Chrome plated or color coated
in any color
Technical Data Sheet: TD591
30
Back
Temperature Rating 155˚F/68˚C 155˚F/68˚C 160˚F/71˚C 160˚F/71˚C 160˚F/71˚C 155˚F/68˚C 155˚F/68˚C 155˚F/68˚C 155˚F/68˚C
175˚F/79˚C 175˚F/79˚C 175˚F/79˚C
Thread Size 1⁄2" 1⁄2" 1⁄2" 1⁄2" 1⁄2" 1⁄2" 1⁄2" 1⁄2" 1⁄2"
Maximum Service 175 PSI 175 PSI 175 PSI 175 PSI 175 PSI 175 PSI 175 PSI 175 PSI 175 PSI
Pressure (12.1 BAR) (12.1 BAR) (12.1 BAR) (12.1 BAR) (12.1 BAR) (12.1 BAR) (12.1 BAR) (12.1 BAR) (12.1 BAR)
Flow (Pressure) For 155°F (68°C) or 160°F (71°C) Temperature Rated Sprinklers, As Applicable
Coverage Areas F983 F984 F990 F992 F993 F978 F680 F685 F687
12' x 12' 12 GPM 13 GPM 12 GPM 17 GPM 22 GPM 16 GPM 9 GPM 12 GPM 18 GPM
One Sprinkler (7.4 PSI) (8.7 PSI) (8.2 PSI) (9.2 PSI) (15.4 PSI) (14.5 PSI) (9 PSI) (11.8 PSI) (9.6 PSI)
12' x 12' 12 GPM 12 GPM 11.5 GPM 15 GPM 15.5 GPM 12 GPM 8 GPM 11 GPM 15.5 GPM
Multiple Sprinklers (7.4 PSI) (7.4 PSI) (7.5 PSI) (7.2 PSI) (7.7 PSI) (8.2 PSI) (7.1 PSI) (9.9 PSI) (7.4 PSI)
14' x 14' 15 GPM 21 GPM 14 GPM 20 GPM 30 GPM 16 GPM 10 GPM 13 GPM
One Sprinkler (11.6 PSI) (22.8 PSI) (11.1 PSI) (12.8 PSI) (28.7 PSI) (14.5 PSI) (11.1 PSI) (13.8 PSI)
14' x 14' 12 GPM 15 GPM 11.5 GPM 17 GPM 21 GPM 12 GPM 8 GPM 12 GPM
Multiple Sprinklers (7.4 PSI) (11.6 PSI) (7.5 PSI) (9.2 PSI) (14.1 PSI) (8.2 PSI) (7.1 PSI) (11.8 PSI)
31
Back
32
Back
Universal Model A300 Universal Model A300/Q-71 Universal Model A300 QR-EC
3 mm Bulb Type, K=5.6 3 mm Bulb Type, K=5.6 3 mm Bulb Type, K=5.6
Pendent, Upright, and Horizontal Sidewall and Extended Coverage, Horizontal
Recessed Pendent Sprinklers Recessed Horizontal Sidewall Sidewall and Recessed Horizontal
Sprinklers Sidewall Sprinklers
◆ Quick response, spray sprinkler ◆ Quick response, spray sprinkler ◆ Quick response, spray sprinkler
◆ Standard coverage ◆ Standard coverage ◆ Extended coverage
◆ Discharges a hemispherical water spray ◆ Designed for installation along a wall or on ◆ Designed for installation along a wall or on
pattern in the area under the sprinkler the side of a beam just beneath a smooth the side of a beam just beneath a smooth
◆ Small frame, narrow profile bulb ceiling ceiling
◆ Model F700 two-piece escutcheon ◆ Water discharge is directed primarily ◆ Coverage areas up to 16' x 22'
converts the Model A300 to an attractive outward and downward in a quarter (4.9 m x 6.7 m)
recessed spray sprinkler spherical pattern ◆ Small frame, narrow profile bulb
Orifice Size: 1⁄2" (15 mm) ◆ Small frame, narrow profile bulb ◆ Model F700 two-piece escutcheon
Temperature Ratings: ◆ Model F700 two-piece escutcheon converts the Model A300 QR-EC to an
135˚F/57˚C, 155˚F/68˚C, 175˚F/79˚C, converts the Model A300/Q-71 to an attractive recessed spray sprinkler
200˚F/93˚C, 286˚F/141˚C attractive recessed spray sprinkler Orifice Size: 1⁄2" (15 mm)
Thread Size (NPT): 1⁄2" Orifice Size: 1⁄2" (15 mm) Temperature Ratings:
Maximum Service Pressure: 300 psi (20.7 bar) Temperature Ratings: 135˚F/57˚C, 155˚F/68˚C
Listings and Approvals: UL and ULC 135˚F/57˚C, 155˚F/68˚C, 175˚F/79˚C, Thread Size (NPT): 1⁄2"
Finishes: 200˚F/93˚C, 286˚F/141˚C Maximum Service Pressure: 300 psi (20.7 bar)
Sprinkler: Natural brass, chrome plated, Thread Size (NPT): 1⁄2" Listings and Approvals: UL and ULC
and polyester coated in any color Maximum Service Pressure: 300 psi (20.7 bar) Finishes:
Escutcheon: Chrome plated or polyester Listings and Approvals: UL and ULC Sprinkler: Natural brass, chrome plated,
coated in any color Finishes: and polyester coated in any color
Technical Data Sheet: TD500A Sprinkler: Natural brass, chrome plated, Escutcheon: Chrome plated or polyester
and polyester coated in any color coated in any color
Escutcheon: Chrome plated or polyester Technical Data Sheet: TD500A
coated in any color
Technical Data Sheet: TD500A
33
Back
34
Back
◆ Maximum service pressure of 250 psi ◆ Maximum service pressure of 450 psi ◆ Maximum service pressure of 250 psi
(17.2 bar) (31 bar) (17.2 bar)
◆ Suitable for AquaMist LH and OH Systems ◆ Suitable for providing electric alarms upon ◆ Suitable for use as an automatic water
◆ Used in conjunction with Model VSG waterflow in AquaMist LH and OH Systems control valve in AquaMist Total
Waterflow Detector ◆ Minimum flow of 3 GPM (11.4 LPM) for Compartment Deluge Systems
◆ Trim provides appropriate drain valve and alarm ◆ Intended for use with electric fire detection
water gauges ◆ Used in conjunction with Model F517 system
◆ Available in 2" through 8" (50mm through “Ready-Riser” Riser Check Valve ◆ 21⁄2" (65 mm) right angle type valve that
200 mm) sizes ◆ Available in 2" through 4" (50mm through may be installed with discharge outlet
Listings and Approvals: UL, ULC and FM 100 mm) sizes facing left or right
Technical Data Sheet: Listings and Approvals: UL Listings and Approvals: UL, ULC, FM, and VdS
TD104A and TD104B Technical Data Sheet: TD200C Technical Data Sheet: TD114M
35
Back
◆ Bulb type frangible element for use in ◆ Open orifice design type for use in deluge ◆ Large open orifice design type for use in
closed head systems systems deluge systems
◆ Discharges a filled cone of water droplets ◆ Nozzles are external deflector type nozzles Thread Size (NPT): 1"
at relatively low velocity that discharge a filled cone of water Orifice Sizes and Nominal K-factors:
Thread Size (NPT): 1⁄2" droplets at relatively low velocity No. 39 10.7 (154.1)
Temperature Ratings: Thread Size (NPT): 1⁄2" No. 44 13.5 (194.4)
135˚F/57˚C 325˚F/163˚C Orifice Sizes and Nominal K-factor: No. 48 16.4 (236.2)
175˚F/79˚C 400˚F/204˚C No. 16 1.2 (17.3) No. 50 18.1 (260.6)
250˚F/121˚C 500˚F/260˚C No. 18 1.8 (25.9) Included Angles of Discharge Pattern:
Included Angles of Discharge Pattern: No. 21 2.3 (33.1) 65˚ 110˚ 160˚
65˚ 110˚ 160˚ No. 24 3.0 (43.2) 80˚ 125˚ 180˚
80˚ 125˚ 180˚ No. 28 4.1 (59.0) 95˚ 140˚
95˚ 140˚ No. 32 5.6 (80.6) Materials and Finishes:
Materials and Finishes: No. 34 7.2 (103.7) Natural brass, chrome plated, electroless
Natural brass finish or chrome plated Included Angles of Discharge Pattern: nickel plated, lead coated or Teflon* coated
finish in 135˚F/57˚C through 500˚F/57˚C; 65˚ 110˚ 160˚ Listings and Approvals: ULI and ULC
Corroproof® or lead coated in 135˚F/57˚C 80˚ 125˚ 180˚ Technical Data Sheet: TD620B
and 175˚F/79˚C 95˚ 140˚
Listings and Approvals: ULI, ULC, FM, and SSL Materials and Finishes:
Technical Data Sheet: TD610A Natural brass, chrome plated, electroless
nickel plated, lead coated or Teflon*
coated. Stainless steel, plain only
Listings and Approvals: ULI, ULC, FM, and SSL
Technical Data Sheet: TD620A
36
Back
Type HV (High Velocity) Cooling Tower Nozzles Models F822 through F834
K=1.6, 1.8, 2.9, 4.3, 5.5 & 6.0 K=2.9, Types 1 and 2 K=2.3, 2.6, 2.7, 4.6 & 5.1
Spray Nozzles Mulsifyre® Nozzles
◆ Open, directional spray nozzles ◆ Intended for use in fire protection systems ◆ Open, internal scroll type nozzles
◆ Designed for use in fixed water spray fire for cross flow cooling towers with ◆ Designed to discharge a filled cone of
protection systems where a high velocity combustible fill sections water droplets at a relatively high velocity
water application is needed, such as the ◆ Open nozzle design for use in water spray ◆ Used in either open or water primed
protection of flammable liquids, electrical deluge system systems
transformers, circuit breakers, oil-fired ◆ Installed under the distribution basin, they ◆ A blow-off cap is used with the nozzle for a
boilers and lube oil systems discharge water in a relatively narrow, primed system
◆ Available in six different orifice sizes elongated spray pattern Thread Size: 3⁄4" NPT
◆ Produces a solid conical spray pattern ◆ Type 1 has a waterway designed for use in Nominal K-factor and Color Code
Normal K-factor and NPT Size: towers with diffusion desks, Type 2 for
Type Nominal K-factor Color Code
Type Nominal K-factor NPT Connection those without
F822 2.0 (28.8) Yellow
HV-14 1.6 (23.0) 1" Materials and Finishes:
F824 2.3 (33.1) Red
HV-17 1.8 (26.0) 1" Open nozzles are available as “standard
F826 2.7 (38.9 Orange
HV-26 2.9 (41.8) 1" order” with natural brass finish, chrome
plated finish, lead coated, and/ or F828 2.6 (37.4) White
HV-37 4.3 (62.0) 1" F832 4.6 (66.2) Aluminum
Corroproof® coated. Open nozzles are also
HV-45 5.5 (79.2) 1" available in stainless steel as “special F834 5.1 (73.4) Gray
HV-60 6.0 (86.4) 11⁄4" order” Materials and Finishes:
Materials and Finishes: Thread Size: 3⁄4" NPT Models F822 through F824 nozzles are
Natural brass or stainless steel Listings and Approvals: ULI and FM furnished in plain brass. Models F822B
Listings and Approvals: ULI, ULC, FM, and SSL Technical Data Sheet: TD730 through F824B nozzles with blow-off caps
Technical Data Sheet: TD680 are chrome plated brass with Delrin™ caps
having a silicon O-ring seal and a Teflon™
coated retaining ring. Models F822
through F834 nozzles with dust caps are
furnished in chrome plated brass with
EPDM rubber caps
Listing and Approvals:
Mulsifyre Nozzles: ULI, ULC, and FM.
Mulsifyre Nozzles with Dust Cap: ULI, ULC,
and FM. Mulsifyre Nozzles With Blow-off
Cap: ULI and ULC
Technical Data Sheet: TD675
TI-MAX®
Nozzles and
Sprinklers
◆ Unique discharge devices are made from titanium and can be used
in offshore and other marine applications
◆ Designed for use where strength, low weight, and salt water
corrosion resistance are required
◆ Medium and high velocity type nozzles are available in various
orifices, as well as standard spray sprinklers in upright and pendent
configurations
◆ Additional information is available by contacting your local GEM
office *E.I. DuPont trademark.
37
Back
Model F705
Model F937 Sprinkler Guard Model F938 Sprinkler Guard Recessed Escutcheons
◆ Universal design can be used with ◆ Low profile design for use with Model A ◆ Consists of a mounting plate and closure
Model A, F950, and FR-1 sprinklers upright and pendent sprinklers for finished appearance in ceilings or
◆ Fits Upright, Pendent, and Sidewall ◆ Model F938 with Q-76 Water Shield is soffits
(Horizontal and Vertical) Styles available for use in storage racks or ◆ Maximum 1⁄2" (12.7 mm) adjustment from
◆ Model F937 with Q-75 Water Shield is beneath grated mezzanines or other areas fully flush position
available for use in storage racks or requiring the sprinklers to be shielded ◆ Primarily designed for use with Universal
beneath grated mezzanines or other areas from possible discharge from sprinklers Model A quick response sprinklers and the
requiring the sprinklers to be shielded above Designer residential sidewall sprinklers
from possible discharge from sprinklers ◆ Can be used with either 1⁄2" or 3⁄4" NPT ◆ Available for use with 1⁄2" or 3⁄4" NPT
above sprinklers sprinkler heads
◆ Can be used with either 1⁄2" or 3⁄4" NPT Finishes: For details request the Technical Data Sheet
sprinklers Zinc plated (Guard and Q-76 shield) referenced in the individual recessed
Finishes: Listings and Approvals: UL, C-UL, and FM sprinkler description
Zinc plated (Guard and Q-75 shield) Finishes:
Listings and Approvals: UL, C-UL, and FM Standard: Chrome plated or white. Color
coated in all colors available
Model F700
Recessed Escutcheons
38
Back
Sprinkler Wrenches
◆ Available in different models for use with the various types of sprinklers:
– flush sprinklers
– recessed sprinklers in fixed and suspended ceiling installations
– solder and bulb type sprinklers
– concealed sprinklers
– among others
Technical Data Sheet:
TD820 or see the individual sprinkler Technical Data Sheet
39
Back
40
Back
Model F540
Residential
Domestic Shutoff Valve
1" & 2"
Water Motor
Alarm (Page 48)
Automatic
Sprinklers
(pages 10 to 27)
Check Valve
(Page 50) Inspector’s
Alarm Valve (Page 48) Test
Fire Dept. Connection
O. S. & Y. Gate Valve
Connection
To Control Water Supply To System
(Page 53)
Main Drain
Connection
Water Pressure
Water
Supply
41
Back
Model F311
Posi-Quick®
Model F3061 Dry Pipe Valve
Dry Pipe Valve Accelerator
◆ 2" (50 mm) and 3" (80 mm) sizes available ◆ Designed for use with Model F302 and F3021 dry pipe valves
◆ Flange x Groove body style ◆ Hastens operation of the dry pipe valve upon loss of air pressure
◆ Differential dry valves ◆ Automatically adjusts to small or slow changes in system pressure
◆ Valve operates when the system air pressure is reduced to approxi- but trips when there is a rapid and steady drop in pressure
mately one-sixth of the system water pressure ◆ Upon tripping, it transmits system air pressure to the intermediate
◆ Used to supply sprinkler installations in which sprinklers are chamber of the dry pipe valve which neutralizes the differential
subjected to freezing conditions (40˚F/4˚C or less) pressure holding the valve closed and opens the waterway clapper
Listings and Approvals: ULI, ULC, and FM ◆ Rated for use at a maximum water supply pressure of 175 psi
Technical Data Sheet: (12.1 bar) and a maximum system air (or nitrogen) pressure of 60
psi (4.1 bar)
TD106 which provides specifications and describes the trim for this
valve which is rated for use at a maximum service pressure of 175 ◆ Designed to trip when system air pressure drops at a rate exceeding
psi (12.1 bar) approximately 1 psi/minute (0.07 bar/min)
Listings and Approvals:
ULI, ULC, FM, LPC, SSL, and VdS.
Technical Data Sheet: TD109
Water Motor
Alarm (Page 48)
Automatic
Sprinklers
(pages 10 to 27)
Check Valve
(Page 50) Inspector’s
Dry Pipe Valve (Page 42 - 43) Test
Fire Dept. Connection
Connection O. S. & Y. Gate Valve
(Page 53) To Control Water Supply To System
42
Back
◆ Trim for 4" and 6" (100 and 150 mm) dry pipe valves is semi- ◆ Field adjustable
preassembled in Modules at our factory to help reduce the number ◆ Used in conjunction with a cylinder of high pressure nitrogen to
of connections that need to be made by the installing personnel control the nitrogen pressure in a sprinkler system or a dry pilot
◆ Packaging provides a convenient method for transporting materials line system
either at the job site or to other locations Listings and Approvals: ULI, ULC, and FM
Technical Data Sheet: TD113
43
Back
Double Interlock
Preaction System
44
Back
(Pneumatic/Electric Shown)
System Shut-Off Valve
Automatic Sprinklers (pages 10 to 27) Model F520/F5201
In order to actuate the double interlock Check Valve (page 50)
preaction system, two independent events,
caused by a fire condition, must occur. The Air/Nitrogen
Electric Detectors Maintenance
sprinkler system piping must lose air or Device (page 43)
nitrogen pressure due to the operation of
one or more sprinklers, and the deluge Fire Alarm
releasing panel must energize and open Bell
Model F630
the solenoid valve upon the operation of a Water Motor
Low Air Pressure
fire detection device. Alarm Switch Alarm (page 48)
45
Back
◆ Used as a system control valve in deluge, ◆ 21⁄2" (65 mm) F445 and F446 are right ◆ 2" NPT (50 mm) deluge valve
and single and double interlock preaction angle type deluge valves ◆ Used as the system control valve in
systems ◆ Available with either a grooved or threaded deluge, and single and double interlock
◆ Available in 4" (100 mm) and 6" (150 mm) inlet and outlet preaction systems
sizes ◆ For use as a control valve in deluge, or ◆ Actuates fire alarms when the system
◆ Can be reset externally without having to single or double interlock preaction operates
remove the hand-hole cover and unlatch systems ◆ Valves can be equipped with various trim
the waterway clapper ◆ F445 and F446 can be reset externally arrangements for actuation by manual,
◆ Available with three actuation trim without having to open a hand-hole cover pneumatic, electric, and hydraulic devices
arrangements: wet pilot, dry pilot, and to manually unlatch and set the center such as break-glass control station,
electric valve electric detectors, and dry pilot or wet pilot
◆ Single and double interlock preaction trims ◆ Model F445 is rated for a maximum 175 sprinklers
available psi (12.1 bar) service pressure ◆ The valve has a trip ratio of approximately
◆ Model F470H available without external ◆ Model F446 is rated for service pressures two and one half to one
reset for horizontal installations to 250 psi (17.2 bar) ◆ Rated for use at 175 psi (12.1 bar)
◆ Rated for 175 psi (12.1 bar) maximum ◆ Trim arrangements for the F445 provide maximum service pressure
service pressure wet pilot, dry pilot, and electric actuation Listings and Approvals:
Listings and Approvals: ◆ Trim for the F446 deluge valve provides ULI, ULC, FM, LPC, and SSL
ULI, ULC, FM, LPC, and SSL electric actuation Technical Data Sheet:
Technical Data Sheet: TD116 ◆ Valves may be installed with the outlet TD117A, TD117B, TD117C, TD117F, and
facing either left or right TD117V
Listings and Approvals:
F445: ULI, ULC, FM, LPC, and SSL. F446:
ULI, ULC, FM, and VdS
Technical Data Sheet:
TD114 for the F445 or TD114M for the
F446
46
Back
◆ Small deluge control valve designed for ◆ Complete riser assembly enclosed within a assembly for easy connections to the
limited size systems freestanding cabinet supply and system piping
◆ May be used as an auxiliary valve to ◆ Package is preassembled with all trim ◆ Available in deluge, single, and double
control the flow of water to specific areas installed and electric switches prewired, interlocked preaction system configura-
◆ Self contained, fixed temperature actuation making the connections for power, local, tions
device consisting of a fusible type solder remote alarms, and other external ◆ The electrical control panel for the systems
assembly, which is mounted on the top of electrical functions the only connections is normally a Potter 4410 releasing panel,
the valve needed to complete the installation but other controls are available upon
◆ Arms on top of the valve are color coded: ◆ Cabinet is constructed from 14 gauge steel request
plain for 165˚F/74˚C, and white for 212˚F/ ◆ Door is hinged for easy access ◆ Can be piped from either side for supply
100˚C temperature ratings ◆ Windows are provided for viewing system and drain functions
◆ Available in 1" (25 mm) and 11⁄2" (40 mm) gauges and other functions ◆ Discharge is vertical
sizes ◆ Grooved connections are provided on the Listings and Approvals:
◆ Rated for 175 psi (12.1 bar) service supply and discharge sides of the valve All components are UL, ULC, and FM
Listings and Approvals:
ULI, ULC, FM, LPC, and SSL
Technical Data Sheet: TD150
Valve Trim
47
Back
◆ Fire control panels provide the interface between detection system, ◆ Designed for use in wet pipe automatic sprinkler systems
deluge or single or double interlocked preaction valve, and signaling ◆ Available for 2" through 8" (50 through 200 mm) pipe sizes
circuit and devices in electrically actuated fire protection systems ◆ Vane-type sensor moves and actuates two SPDT switches when
◆ Separate supervisory zone provided for electronic supervision of water flows at sustained rate of 10 GPM (37.9 LPM)
valve position, low pressure, and other critical fire protection ◆ Waterflow detectors are used to actuate electrical alarms and/or
functions operate electrical equipment in sprinkler systems where mechanical
◆ Series 100RC is single-zone fire control panel alarms are not installed
◆ Series 4410 can be used in single zone, cross zone, sequential or ◆ Also used where sectional waterflow signals are required
cross/sequential electric deduction systems
Listings and Approvals: ULI, ULC and FM
◆ Series 4410 has programming capability
Technical Data Sheet: TD200B
Listings and Approvals: ULI and FM
Technical Data Sheets: TD270 (100RC)
48
Back
Model F512 4" (100 mm) Model F514 Models F52, F520, and F5201
Wafer Check Valves Swing Check Valve Check Valves
◆ O-ring sealed clapper, torsion spring ◆ Grooved end connection swing check ◆ Rubber faced swing check valves
loaded, butterfly type check valves valve that has a rubber faced clapper ◆ May be installed vertically or horizontally
◆ Designed for use in fire protection systems design ◆ Can be used for gravity and pressure tank
and related piping ◆ Provides a nominal pressure drop of only connections, connections from public
◆ Permits rapid closure and minimizes water 1.4 psi (0.10 bar) at 600 GPM (2270 LPM) water supplies to automatic sprinkler
hammer, which can be associated with ◆ Leak tight sealing of back pressure systems, fire pump discharge and by-pass
reverse flow greater than 1.0 psi (0.07 bar) connections and in preaction systems
◆ Available in 4" (100 mm), 6" (150 mm), ◆ Rated for use in up to 250 psi (17.2 bar) having a nominal supervisory pressure of
and 8" (200 mm) sizes service 1.5 psi (0.10 bar) or greater
◆ Rated for use at a maximum service ◆ Furnished with 1⁄2" NPT drain connection Listings and Approvals: ULI, ULC, and FM
pressure of 250 psi (17.2 bar) tap, which is ideal for use with fire Technical Data Sheet: TD318 and TD320
◆ Leak tight at back pressures at greater department connections
than 1.0 psi (0.07 bar) Listings and Approvals: ULI, ULC, and FM Model F52 Model F520 Model F5201
Groove Flange Flange
◆ May be installed in either horizontal or Technical Data Sheet: TD315 x x x
vertical lines Size Groove Flange Groove
Listings and Approvals: ULI, ULC, and FM
21⁄2"(65 mm) ◆ - -
Technical Data Sheet: TD300
4" (100 mm) ◆ ◆ ◆
6" (150 mm) ◆ ◆ ◆
8" (200 mm) - ◆ ◆
◆ = available
50
Back
Series 7800FP Models F570 and F571 Models F575 and F576
Grooved End Swing 21⁄2" (65 mm) Sectional Control 21⁄2" (65 mm) Hose Station Type
Check Valves Pressure Control Valves Pressure Reducing Valves
◆ Available in sizes 2" through 12" (50mm ◆ Straight pattern, balanced piston, valves ◆ Straight pattern, balanced piston, hose
through 300 mm) ◆ Designed to reduce inlet pressure of up to station valves
◆ Can be installed either vertically or 400 psi (27.6 bar) to a maximum outlet ◆ Designed for use in Classes I and III
horizontally pressure of 165 psi (11.4 bar) in sections standpipe system service to reduce
◆ Rated for use at a maximum pressure of or zones of wet pipe system standpipe (inlet) and pressure of up to
250 psi (17.2 bar) ◆ Model F570 has cut groove inlet and outlet 400 psi (27.6 bar) down to one of three
◆ Cut groove inlet and outlet connections connections factory set hose (outlet) pressure under
◆ Suitable for use with grooved pipe ◆ Model F571 has a 2 1⁄2" NPT threaded inlet both flow and static conditions
couplings that are listed or approved for and a cut groove outlet ◆ F575 has a cut groove inlet
fire protection service ◆ Factory set to provide 165 psi (11.4 bar) ◆ F576 has a threaded NPT inlet
Listings and Approvals: outlet pressure; therefore, there is no need ◆ The valve outlet is provided “standard
ULI, ULC, FM, and VdS to “special order” valves based on inlet order” with a 21⁄2" male hose outlet
Technical Data Sheet: TD313 pressure due to the level or floor when connection per NFPA 1963 (2.5-7.5 NH)
used in high-rise buildings ◆ Valves automatically adjust the outlet
Listings and Approvals: ULI and ULC pressure, as the inlet pressure varies from
Technical Data Sheet: TD360 the minimum setting up to 400 psi
(27.6 bar)
◆ 3 available outlet settings are
155 psi, 140 psi, and 120 psi
(10.7 bar, 9.7 bar, and 8.3 bar)
Listings and Approvals: ULI and ULC
Technical Data Sheet: TD370
51
Back
◆ Available in 3" thru 10" (80mm thru 250 mm) sizes for the model A, ◆ Available in several sizes
3" thru 8" (80mm thru 200 mm) for the model B 6" x 6" (150 mm x 150 mm)
◆ Rated for use in services up to 175 psi (12.1 bar) 8" x 8" (200 mm x 200 mm)
◆ Bodies of the model A are welded steel and 150 lb. flanges. Cast 8" with 2 - 6" outlets (200 mm with 2 - 200 mm outlets)
iron reducing inlet flanges and blind flanges complete the assembly.
10" with 2 - 8" outlets (250 mm with 2 - 200 mm outlets)
Entire assembly is hot dipped galvanized.
◆ Rated for use in services up to 250 psi (17.2 bar)
◆ Bodies of 3", 4" and 6" B-1 strainers are cast iron flanged tees. 8"
B-1 strainers are pieces of welded Schedule 30 steel pipe and Class ◆ Compact lightweight welded hot dipped assembly with flanged inlet,
150 steel flanges outlet and flushing connection.
Listings and Approvals: ULI, UL and FM ◆ Corrosion resistant Type 304 stainless steel screen especially
designed for low pressure loss
Technical Data Sheet: TD401 (Model A) and TD402 (Model B)
Listings and Approvals: ULI, C-UL and FM
Technical Data Sheet: TD402M
52
Back
Model F350 Model F713 Models F715, F716, and F717 Fire
Sectional Test and Drain Fire Department Connection Department Connections
◆ Integral sight-glass assembly ◆ Used as auxiliary water supply connection ◆ Similar in operation to model F713
◆ Simplified method of testing waterflow to automatic sprinkler systems or ◆ Models F715 (straight), F716 (45°) and
alarms and draining sections of fire standpipe fire protection systems F717 (90°) offer dual fire department
protection systems ◆ Allows fire departments to pump water hookups
Listings and Approvals: ULI and FM into a fire protection system from Listings and Approvals: ULI and FM
Technical Data Sheet: TD455 hydrants, ponds, and reservoirs Technical Data Sheet: TD411
Listings and Approvals: ULI
Technical Data Sheet: TD410
◆ Intended for use in wet pipe residential fire protection systems ◆ Automatically drains water from fire protection equipment
◆ Available in 3⁄4"–2" (20-50 mm) sizes (under low pressure)
◆ Superior heat resistance ◆ Provides visual indication of leakage past a check valve
◆ Excellent water flow characteristics ◆ Automatically drains off condensate in fire protection systems
◆ Easy to install Listings and Approvals: ULI and FM
◆ Various adapters are available to connect Flameaway pipe to metal Technical Data Sheet: TD425
piping used in fire sprinkler systems, as well as cut-grooved
adapters and male and female pipe-thread adapters
◆ All male and female thread adapters have brass inserts for durability
Listings and Approvals: ULI, C-UL, and FM
Technical Data Sheet: TD900
53
Back
S PRINKLER PIPE
Allied Tube and Conduit manufactures pipe for the North American sprinkler industry. All pipe is manufactured to the standards of the American
Society of Testing Materials (ASTM) for pipe meeting codes A-135 and/or A-795. These are also recognized by the National Fire Protection
Association (NFPA) as being acceptable for steel pipe for fire sprinkler installations.
Allied is the largest producer of sprinkler pipe in North America. Allied also produces fence products, tubular steel for recreational products,
electrical conduit, and steel channel (strut) for industrial hanger use.
Allied Allied
Dyna-Flow® Pipe BLT®/XL Pipe
◆ Represents latest technical advancement in light wall sprinkler pipe ◆ Threadable light wall sprinkler pipe manufactured in 1" through 3"
◆ Ideally suited for use in most sprinkler system installations, and sizes (25 mm through 80 mm)
offers advantageous hydraulic design characteristics ◆ XL is exterior galvanized - BLT is black
◆ Dyna-Flow is lightweight but incredibly strong, and allows for ease ◆ Engineered to provide best in low-cost sprinkler protection
of handling to facilitate installation, at significantly reduced labor ◆ For use in accordance with NFPA 13, 13D, and 13R, as threaded or
costs unthreaded in wet, dry, preaction or deluge systems
◆ Complies with ASTM A795 and is available in sizes 1" through 4" ◆ Rated for pressures of up to 300 psi (20.7 bar) and complies with
(25 through 100 mm) in lengths of 21', 24' and 25' ASTM A135
(6.4, 7.3 and 7.6 m) ◆ Available in standard lengths of 21', 24' and 25'
◆ UL, ULI Listed and FM approved as engineered lightwall pipe (6.4m, 7.3m and 7.6m)
Technical Data Sheet: ◆ UL listed and FM approved as threadable lightwall sprinkler pipe
See current Pipe Catalog and Data Sheets for more information Technical Data Sheet:
See current Pipe Catalog and Data Sheets for more information
54
Back
Customized Submittal Sheets • Product Technical Data
Sheets • CAD Details • Sprinkler Selection Guide
ASIA
SINGAPORE
65-847-0880, Fax 65-847-3919
MALAYSIA
Petaling Jaya: 60-3-572-2773, Fax 60-3-572-2755
HONG KONG
Kowloon: 852-2766-0860, Fax 852-2766-3070
TAIWAN
Taipei: 886-2-377-6226, Fax 886-2-377-5991
AUSTRALIA
NEW SOUTH WALES
Hoxton Park: 02-607-6133, Fax 02-608-4224
QUEENSLAND
Rocklea: 07-274-2575, Fax 07-274-2858
SOUTH AUSTRALIA
Athol Park: 08-268-4722, Fax 08-347-1892
MELBOURNE
Bundoora: 03-9467-7122, Fax 03-9467-7526
WESTERN AUSTRALIA
Welsapool: 09-353-4022, Fax 09-353-4015
EUROPE
NETHERLANDS
Kopersteden 1, NL-7547 TJ Enschede
P.O. Box 198, 7500 AD
Enschede, Holland
31-53-428-3434, Fax 31-53-428-3377
UNITED KINGDOM
Stockport: 44-61-429-9730, Fax 44-61-429-9735
FRANCE
Paris Nord II: 33-1-48178727, Fax 33-1-48178720
GERMANY
D-63110 Rodgau: 49-6106-84455, Fax 49-6106-18177
SPAIN
Coslada Madrid: 03-34-1-669-3906, Fax 03-34-1-669-2018 DISTRIBUTED BY
LATIN AMERICA
MIAMI, FLORIDA, USA
2610 N.W. 89th Court
Miami, FL 33172
305-448-0059, Fax 305-448-1632
ARGENTINA
Buenos Aires: 54-11-4246-4233, Fax 54-11-4246-4487
Buenos Aires: 54-11-4308-6444, Fax 54-11-4308-6445
Mendoza: 54-26-1498-0642, Fax 54-26-1498-1765
BRAZIL
Rio De Janeiro: 55-21-240-9695, Fax 55-21-240-6770
Sorocaba-São Paulo: 55-15-228-3555, 55-15-228-3391
São Paulo: 55-11-362-4011, 55-11-261-3823
CHILE
Santiago: 56-2-538-1800, Fax 56-2-538-0050
MEXICO
Guadalajara, Jalisco: 52-3-668-4000, Fax 52-3-668-4012
Mexico City: 52-5-207-5766, Fax 52-5-207-7566
VENEZUELA
Caracas, 1080-A: 58-2-991-7577, Fax 58-2-991-6409
Maracaibo: 58-61-91-0526, Fax 58-61-93-1894
PERU
Lima: 511-332-9564, Fax: 511-332-9568
NEW ZEALAND
AUCKLAND 09-827-2290, Fax 09-827-2288