Mic 25/IU/TC
Mic 25/IU/TC
Ԏ The mic+ sensor with one analogue in the Add-on menu. Ԏ Read the operating instructions Î Assemble the sensor at the installa- Ԏ mic+ sensors have internal tempe-
output measures the distance to an Ԏ Using the LinkControl adapter (op- prior to start-up. tion location. rature compensation. Because the
object within the detection zone tional accessory) and the LinkCon- Ԏ Connection, installation and ad- Î Plug in the connector cable to the sensors heat up on their own, the
contactless. A signal proportional to trol software for Windows®, all justment works may only be car- M12 connector, see Fig. 2. temperature compensation reaches
distance is created according to the Teach-in and additional sensor pa- ried out by expert personnel. its optimum working point after
adjusted window limits of the ana- rameter settings can be optionally Ԏ No safety component in ac- 2 1 approx. 30 minutes of operation.
logue characteristic curve. undertaken. cordance with the EU Machine 3 5 4 Ԏ If an object is within the set window
Ԏ The sensor automatically detects The mic+ sensors have a blind zone in Directive, use in the area of per- colour limits of the analogue output, then
1 +UB brown
the load put to the analogue output which distance measurement is not sonal and machine protection 3 –UB blue
LED D1 lights up green, if the object
and switches to current output or possible. The operating range indica- not permitted 4 – black is outside the window limits, then
voltage output respectively. tes the distance of the sensor that can Proper Use 2 I/U white LED D1 lights up red.
Ԏ All settings are done with two push- be applied with normal reflectors with 5 Sync/Com grey Ԏ The load put to the analogue out-
mic+ ultrasonic sensors are used for
buttons and a three-digit LED dis- sufficient function reserve. When non-contact detection of objects. Fig. 2: Pin assignment with view onto sensor put is detected automatically when
Operating Manual play (TouchControl). using good reflectors, such as a calm plug and colour coding of the microso- turning supply voltage on.
Ԏ Three-colour LEDs indicate all ope- water surface, the sensor can also be Synchronisation nic connection cable
Ԏ During normal operating mode, the
mic+ Ultrasonic Sensors ration conditions. used up to its maximum range. Ob- If the assembly distance of multiple Start-up measured distance value is dis-
with one analogue output Ԏ Choosing between rising and falling jects that strongly absorb (e.g. plastic sensors falls below the values shown Î Connect the power supply. played on the LED-indicator in mm
output characteristic is possible. foam) or diffusely reflect sound (e.g. in Fig. 1 the integrated synchronisati- Î Set the parameters of the sensor (up to 999 mm) or cm (from
mic+25/IU/TC on should be used. Connect Sync/
mic+35/IU/TC Ԏ The sensors are adjustable manually pebble stones) can also reduce the manually via TouchControl (see 100 cm). Scale switches automati-
mic+130/IU/TC via TouchControl or via Teach-in defined operating range. Com-channels (pin 5 at the units re- Fig. 3 and Diagram 1) cally and is indicated by a point on
mic+340/IU/TC procedure. ceptable) of all sensors (10 maximum). Î or use the Teach-in procedure to top of the digits. Alternatively a
mic+600/IU/TC adjust the detect points (see Dia- percentage scale may be set in the
Diagram 1: Set sensor parameters numerically using LED display gram 2). add-on menu. In this connection
cm mm % Measuring Range 0 % and 100 % correspond to the
mic+25... ≥0.35 m ≥2.50 m 3-digit set window limits of the analogue
Start here mic+35... ≥0.40 m ≥2.50 m
LED-display output.
T1 + T2
LED D1 and D2 Ԏ If no objects are placed within the
mic+130... ≥1.10 m ≥8.00 m Push-buttons T1 and T2 detection zone the LED-indicator
T1 D1D2 T2
Press T1 and T2 simultaneously for about mic+340... ≥2.00 m ≥18.00 m shows »– – –«.
3 s until welcome message has passed. Fig. 3: TouchControl/LED display Ԏ The sensor can be set to its factory
mic+600... ≥4.00 m ≥30.00 m
Factory setting setting, see Diagram 3.
Fig. 1: Assembly distances, indicating synchro- Ԏ If no push-buttons are pressed for
Set analogue output nisation/multiplex mic+ sensors are delivered factory
T1 T2 made with the following settings: 20 seconds during parameter set-
Multiplex mode Ԏ Rising analogue characteristic ting mode the made changes are
T1 + T2 The Add-on-menu allows to assign an Ԏ Window limits for the analogue stored and the sensor returns to
individual address »01« to »10« to output set to blind zone and opera- normal operating mode.
Set sensor-close window each sensor connected via the Sync/ ting range Show parameters
T1 T2 limit in mm or cm.
Com-channel (Pin5). The sensors per- Ԏ Measurement range set to maxi- Î In normal operating mode shortly
T1 + T2
form the ultrasonic measurement se- mum range push T1. The LED display shows
quentially from low to high address. »PAr.«
Therefore any influence between the Maintenance
T1
Set sensor-distant window
T2 limit in mm or cm. mic+ sensors work maintenance free. Each time you tap push-button T1 the
sensors is rejected. actual settings of the analogue output
The address »00« is reserved to syn- Small amounts of dirt on the surface
T1 + T2 do not influence function. Thick layers are shown.
chronisation mode and deactivates the
multiplex mode. To use synchronised of dirt and caked-on dirt affect sensor
T1
Choose rising ( ) / falling (
T2 output characetistic curve.
)
mode all sensors must be set to function and therefore must be remo-
address »00«. ved.
T1 + T2
T1 T2
T1 + T2
Ready
Diagram 2: Set sensor parameters via Teach-in procedure Diagram 3: Key lock and factory setting
Diagram 4: Useful additional functions in Add-on menu (for experienced users only, settings not required for standard applications)
Start here
T1 + T2
T1 T2 T1 T2 T1 T2 T1 T2 T1 T2 T1 T2 T1 T2 T1 T2 T1 T2 T1 T2 T1 T2 T1 T2
T1 + T2 T1 + T2 T1 + T2 T1 + T2 T1 + T2 T1 + T2 T1 + T2 T1 + T2 T1 + T2 T1 + T2 T1 + T2 T1 + T2
T1 T2 T1 T2 T1 T2 T1 T2 T1 T2 T1 T2 T1 T2 T1 T2 T1 T2 T1 T2 T1 T2 T1 T2
T1 + T2 T1 + T2 T1 + T2 T1 + T2 T1 + T2 T1 + T2 T1 + T2 T1 + T2 T1 + T2 T1 + T2 T1 + T2 T1 + T2
T2 T1
T1 + T2 »C01«: Display »– – –«: Display in »Aut«: automatic »F00«: no filter Defines the strength Delay in seconds Minimum value: »00«: synchronisati- To optimize multi- Minimum value: Put plane reflector Affects the size of
bright mm or cm detection of the »F01«: standard of the chosen filter. between the detec- blind zone on plex speed the hig- sensor-distant vertically disposed in the detection zone.
load tion of an object hest sensor address window limit front of sensor: in
Ready »C02«: Display
dimmed
» «: Display in
%, 100 % at mini- »U«: voltage output
filter
»F02«: averaging
»P00«: weak filter
up to
and the output of
Maximum value: ne-
arwindow limit - 1
»01« to »10«: sensor
address for multi- may be set. Maximum value: an exact distance of
»E01«: high
»E02«: standard
the measured dis- plex mode Setting range »01« 999 mm for 250 mm for
»C03«: Display off mum measured val- »I«: current output filter »P09«: strong filter tance in case of ob- to »10« mic+25/..., mic+ 25... and »E03«: slight
ue »oFF«: synchronisati-
»F03«: foreground ject approach (beha- mic+35/..., mic+35... and
» «: Display in filter ves as on-delay). on deactivated 900 mm for all other
%, 100% at maxi- 999 cm for types.
»F04«: background "00": 0 s (no delay) mic+130/...,
mum measured val-
filter up to mic+340/..., Adjust display to
ue
mic+600/... 250 mm or 900 mm.
Note "20": 20 s response Confirm calibration
Changes in the Add-on menu time with T1+T2.
may impair the sensor func-
tion.
A6, A7, A8, A10, A11, A12
have influence on the res-
ponse time of the sensor. Lower power mode Display mode Choose current/ Measurement filter Filter strength Response time Foreground Multiplex mode Multiplex mode Measurement range Calibration Detection zone
voltage output suppression device addressing highest address display sensitivity
Technical data
mic+25... mic+35... mic+130... mic+340... mic+600...
TouchControl 36 width A/F TouchControl 36 width A/F TouchControl 36 width A/F TouchControl 36 width A/F TouchControl 36 width A/F
LED-Display LED-Display LED-Display LED-Display LED-Display
2 Buttons M30x1.5 5 2 Buttons M30x1.5 5 2 Buttons M30x1.5 5 2 Buttons M30x1.5 5 2 Buttons M30x1.5 5
1
+UB 2 Duo-LEDs 2 Duo-LEDs 2 Duo-LEDs 2 Duo-LEDs 2 Duo-LEDs
2
U 4
I/U
Ø47.5
Ø65
5
Sync/Com
3
–UB
M12x1
M12x1
M12x1
M12x1
M12x1
1 analogue output
19.5
22.5
33
36
51 51 51 69 72
84 84 84 102 105
10 cm
2.4 m
1.2 m
1.2 m
2.4 m
0.8 m
0.4 m
0.4 m
0.8 m
1.6 m
0.8 m
0.8 m
1.6 m
20 cm
10 cm
10 cm
20 cm
5 cm
0 cm
5 cm
0 cm
for different objects:
0m
0m
0m
The dark grey areas represent the 0 cm 0 cm 0m 0m 0m
zone where it is easy to recognise
the normal reflector (round bar).
This indicates the typical operating 5 cm
10 cm 0.8 m 1.2 m
range of the sensors. The light Plate 0.4 m Plate Plate
Plate
grey areas represent the zone Plate
where a very large reflector – for 10 cm 1.6 m 2.4 m
20 cm Round bar ø 27 mm
instance a plate – can still be re- Round bar ø 10 mm Round bar ø 27 mm
Round bar ø 10 mm 0.8 m
cognised. The requirement here is 15 cm Round bar ø 10 mm 2.4 m 3.6 m
for an optimum alignment to the 30 cm
sensor. It is not possible to evalua- 1.2 m
te ultrasonic reflections outside 35 cm
20 cm 1.3 m 3.2 m 4.8 m
this area. 40 cm 3.4 m
25 cm 1.6 m 4m 6m
50 cm
30 cm 4.8 m 7.2 m
2m
60 cm
35 cm 5.6 m 8.4 m
Registration
Enclosure Type 1 The proximity switches shall be used with a
For use only in industrial Listed (CYJV/7) cable/connector assembly ra- no. 75330-19
microsonic GmbH / Phoenixseestraße 7 / 44263 Dortmund / Germany / T +49 231 975151-0 / F +49 231 975151-51 / E info@microsonic.de / W microsonic.de
The content of this document is subject to technical changes. Specifications in this document are presented in a descriptive way only. They do not warrant any product features.
machinery NFPA 79 applications. ted minimum 32 Vdc, minimum 290 mA, in
the final installation.