Overcurrent Protection settings of transformer Remote end Breaker proposed setting
DMT Stage of Earth fault protection IDMT Stage of Earth fault protection
Setting name Existing Settings Modified Settings Unit Setting name Modified Settings Unit
Mode on on -- Mode on --
1.25 (Primary
Threshold 2.40 (Primary Amp=1920A) A Type of character. curve IEC normal inverse --
Amp=1000A)
Operate delay 0.1 0.1 s Threshold 0.3 (Primary Amp=120A) A
IDMT Stage of Earth fault protection Time dial 0.33 --
Setting name Existing Settings Modified Settings Unit IDMT Stage of Phase fault protection
Mode on on -- Mode on --
Type of character. curve IEC normal inverse IEC normal inverse -- Type of character. curve IEC normal inverse --
Threshold 0.10 (Primary Amp=80A) 0.10 (Primary Amp=80A) A Threshold 1.0 (Primary Amp=400A) A
Time dial 0.13 0.26 -- Time dial 0.26 --
Standby earth Fault Protection of HV side-51NS-HV
Setting name Existing Settings Modified Settings Unit
Mode on on --
3.33 (Primary
Threshold 6.40 (Primary Amp=1920A) A
Amp=1000A)
Operate delay 0.3 0.3 s
Overcurrent Protection settings of line
DMT Stage of Earth fault protection
Setting name Existing Settings Modified Settings Unit
Mode on on --
Threshold 0.2 (Primary Amp=160A) 2.65 (Primary Amp=2120A) A
Operate delay 1 0.3 s
IDMT Stage of Earth fault protection
Setting name Existing Settings Modified Settings Unit
Mode on on --
Type of character. curve IEC normal inverse IEC normal inverse --
Threshold 0.2 (Primary Amp=160A) 0.12 (Primary Amp=96A) A
Time dial 1 0.26 --
DMT Stage of Phase fault protection
Setting name Existing Settings Modified Settings Unit
Mode on on --
Threshold 1.0(Primary Amp=800A) 4 (Primary Amp=3200A) A
Operate delay 0.2 0.25 s
IDMT Stage of Phase fault protection
Setting name Existing Settings Modified Settings Unit
Mode on on --
Type of character. curve IEC normal inverse IEC normal inverse --
Threshold 0.10 (Primary Amp=800A) 0.5 (Primary Amp=400A) A
Time dial 0.2 0.2 --