SecureConnect 200 Installation Guide

This document provides instructions for mounting and operating the SECUREconnect 200 power and data transmission unit. It contains safety warnings and information about the unit's components, technical specifications, and schematic view. Instructions are given for installation in door frames and door leaves.

Uploaded by

acabral
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
858 views31 pages

SecureConnect 200 Installation Guide

This document provides instructions for mounting and operating the SECUREconnect 200 power and data transmission unit. It contains safety warnings and information about the unit's components, technical specifications, and schematic view. Instructions are given for installation in door frames and door leaves.

Uploaded by

acabral
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 31

Mounting und operating instructions

SECUREconnect 200
Power and data transmission unit

1. Safety instructions

Warning symbols

DANGER denotes a dangerous situation which, if


DANGER ignored, could lead to death or serious injury.

WARNING denotes a dangerous situation which, if


WARNING ignored, could lead to death or serious injury.

CAUTION denotes a dangerous situation which, if


CAUTION ignored, could lead to injuries.

ATTENTION denotes a situation which could lead to


ATTENTION material damage.

NOTE NOTE denotes a statement which is provided for


information only.

2. Information

Thank you for having decided to purchase SECUREconnect 200, a safe and
compact power and data transmission unit intended for use with motor-
driven or electromechanical locking systems.

2.1 General advice


This manual contains important advice which must be followed in order
to prevent hazard, ensure the reliable functioning and long service life of
SECUREconnect 200, and to reduce downtimes and repair cost.

38 EN 12.2013 | 15887EE | Printed in Germany


The instructions must be read carefully by every person handling
SECUREconnect 200, e.g., during

„„
Installation and electrical connection

„„
Start-up and maintenance

It is essential that the information given in this manual, especially the


chapters concerned with safety, should be observed.

After installation, the instruction manual must be handed over to the


operating company/user who should read it carefully before operating the
unit the first time and keep it for later service and maintenance. Please point
out the necessity to read these instructions thoroughly to all users and
responsible persons.

2.2 Delivery contents


The package contains:

Delivery contents

Qty. Designation

1 pc. SECUREconnect 200R (component for door frame)

1 pc. SECUREconnect 200F (component for door leaf)

4m 230 V mains cable with Europlug

4m Connecting cable with input terminals

1 pc. SECUREconnect 200R plastic contact holder with 3 contact


plates

1 bag 8 fastening screws for attachment of face plates


1 rubber grommet, 1 cable tie for strain relief

1 pc. Mounting and operating Instructions

1 pc. Installation manual

39
Mounting und operating instructions

SECUREconnect 200
Power and data transmission unit

3. Technical description

3.1 Range of application


The SECUREconnect 200R and 200F components are designed for vertical
installation in the the frame and the door leaf, respectively.

It is not permitted to operate the unit in exterior gate or door assemblies


where ambient conditions require a higher protection class than IP 40.

SECUREconnect 200 must not be used for purposes other than the intended
use.

'Intended use' comprises the observance of the manufacturer's operating


and service instructions which is essential for the avoidance of damage and
injury.

The companies GU and BKS exclude any liability for damage arising from
changes made on the lock or on the lock connection without their consent.

Suitable for installation in timber, PVC, and metal door assemblies with the
use of profile-specific screw-on type faceplates.

„„
Short-circuit proof power transmission between door frame and leaf.

„„
Encrypted data transmission.

„„
All deliveries are made on the basis of the General Terms and Conditions
of the company GU.

3.1.1 SECUREconnect 200R for installation in the door frame


„„
Power and data transmission unit for motor-driven or electromechanical
locking systems from GU and BKS.

„„
Communication interface to the BKS-NET bus, output of lock status to
IO module (module IO5 or IO10).

„„
Status indicator LEDs.

„„
Optional voltage supply of DC 24 V or AC 230 V

40 EN 12.2013 | 15887EE | Printed in Germany


3.1.2 SECUREconnect 200F for installation in the door leaf
„„
Power and data transmission unit for motor-driven or electromechanical
locking systems from GU and BKS.

„„
Long-life tappet contacts (no need of a cable duct).

„„
Any door opening angle possible

„„
Unhindered hinging and unhinging of door leaf.

„„
4 inputs for transmission of lock status

„„
Power output 20 mA for connection of LED signalling 'open'.

„„
Status indicator LEDs.

„„
Compartment for extension modules for possible future applications.

„„
Once installed, the unit is maintenance-free.

3.2 Technical data


Supply voltage AC 230 V 50/60 Hz 0.25 A or
DC 24 V stabilised 1.0 A

Type of protection IP 40
Protection class II

Operating temperature -20 °C … +45 °C

41
Mounting und operating instructions

SECUREconnect 200
Power and data transmission unit

3.3 Schematic view


J-Y(ST) Y2x2x0.6

IO10 IO10

Potential-free
control contact, e.g.
pushbutton, intercom,
access control, timer
switch.
For various control
options see chapter 6.
SECUREconnect 200R
SECUREconnect 200F

Connecting cable with


input terminals

For metal and PVC doors use rubber


For various grommet enclosed in package.
control options
see chapter 6.

Door leaf with SECUREconnect 200F Frame with SECUREconnect 200R


(Position and cable route) Position and cable route
(AC 230 V, DC 24 V, BUS, control line, IO10)

For detailed recess dimensions see drawing 0-45733-L0.

42 EN 12.2013 | 15887EE | Printed in Germany


4. Safety advice

It is necessary to ensure that only trained specialists (for the definition


thereof see EN 50110-1, DIN VDE 0105 or IEC 60364) are charged with jobs
related to the product (planning, transport, assembly, installation, start-up,
maintenance, repair, dismantling).

Moreover, it is necessary to ensure that the documents required for


installation, start-up, operation, maintenance and repair of the product are
made available to the specialists and observed by them duly.

Installation works involving the use of electrical


DANGER equipment are dangerous.

Insufficient wire cross sections may cause a fire.


Therefore it is important to always observe the
specified cross sections.

Connections to a 230 V mains are dangerous to life !

The installation of electrical components must


be carried out by trained electricians only. Non-
observance of the installation advice may result in
fire and other hazards.

„„
Observe operating instructions before connection to the mains.

„„
Relieve supply line from strain by an appropriate means.

„„
Do not damage connecting cables.

„„
Use enclosed rubber grommet on cable outlet from profile.

„„
Observe standards and regulations for extra-low voltage (SELV) during
installation and laying of cables.

„„
By no means switch a 'permanent OPEN' contact when using the unit on
smoke and fire protection doors (DIN 18250)! This will nullify the door
assembly's fire approval.

43
Mounting und operating instructions

SECUREconnect 200
Power and data transmission unit

„„
The door leaf part of SECUREconnect has an integral energy storage
ensuring that in the event of a power failure during short-time 'OPEN',
the retracted latchbolts of all mechatronic GU-BKS locks will eject to be
ready for locking. This provides for safe and reliable door locking in the
event of a fire.

„„
SECUREconnect 200R features an internal 2 A fuse which is not
accessible from outside and not suitable for being exchanged. Opening
the device will damage it and nullify its warranty.

„„
Disconnecting the unit from the mains is done by pulling the power plug
from the socket.
The socket must be freely accessible.
If SECUREconnect 200 is connected to the electricity supply
permanently, it is necessary to provide for switch off by means of a
suitable and appropriately marked device on the building's distribution
board, e.g. a switch, fuse, or automatic cutout.

„„
This manual is part of the product and must remain with the end user.

5. Mounting preparations

The electronic components should be installed with utmost care since


chafed or defective cables, damaged contacts etc. may seriously affect the
safety of the system and cause its failure. Ensure that all components are in
faultless state before mounting them.
It is imperative to observe the attached assembly
ATTENTION drawing!

5.1 Mounting the faceplates


Attach SECUREconnect 200R and SECUREconnect 200F to the
corresponding faceplate, each, using the special 4 x 7 Torx screws included
in the bag (8 altogether).

Tighten screws with a max. torque of 1.0 Nm using a TORX T20 suitable tool
only.

44 EN 12.2013 | 15887EE | Printed in Germany


5.2 Mounting the contact holder with contact plates
After having attached the faceplate, mount the contact holder with the 3
contacts to SECUREconnect 200R.

The 3 contact plates are firmly attached to the contact holder, so all you
have to do is press the unit through the faceplate bores into the provided
jacks, you will feel the part snap in lightly.
If necessary, the contact unit can be levered out again carefully using an
appropriate tool, e.g. an screw driver.

Contact holder with


contact plates

45
Mounting und operating instructions

SECUREconnect 200
Power and data transmission unit

5.3 Regulating the rebate clearance


The factory setting of SECUREconnect 200F regarding the rebate clearance
is 0 - 6 mm. For increasing this value to 6 - 12 mm, it is possible to pull out
the restricting brackets on the side of the tappet contacts using a small
screwdriver. In doing so, the adhesive label "Hubverstellung der Kontakte"
(adjustment of contact travel) must be removed carefully and re-attached
afterwards. The tappet contacts now protrude 12 mm from the device.

Do not reinsert the restriction brackets with the rebate clearance set
to 6 - 12 mm !

If you wish to limit SECUREconnect 200F to a rebate clearance of 6 mm


again, press back the tappet contacts until stop and reinsert the restricting
brackets.

Do not adjust to 6 - 12 mm rebate clearance if the


ATTENTION clearance is smaller than 6 mm. This would increase
the strain on the contacts and reduce the service
life of the device.

Reattach the adhesive label for protection !

46 EN 12.2013 | 15887EE | Printed in Germany


5.4 Installation in the door
Depending on the door material (timber, metal, PVC), different fastening
screws must be used for the installation of SECUREconnect 200; type and
length of the screws vary according to the door profile used.

It is important, however, that the max. screw diametre does not exceed
4.0 mm. The fastening screws should allow for being inserted through the
faceplate and SECUREconnect 200 without any resistance.

Ensure that there is sufficient space for a cable loop.

Be careful to not deform the faceplate when fastening SECUREconnect 200


to the door (this refers especially to flat faceplates).

In installed condition, the tappet contacts of SECUREconnect 200F and


the contact surfaces of SECUREconnect 200R must be exactly aligned, the
maximum tolerable offset is 2 mm.

Max. offset 2mm

Figure shows installation in timber doors.

In the case of metal and PVC doors, SECUREconnect 200F is fastened by the
faceplate screws.

Please consider enclosed installation drawing 0-45733-LO.

47
Mounting und operating instructions

SECUREconnect 200
Power and data transmission unit

6. Wiring advice

6.1 Wiring and electrical connection


Observe standards and regulations for extra-low
CAUTION voltage (SELV) during installation and laying of
cables.
The cables must be laid in such a way that they cannot be squeezed in or
dammaged in the area of the lock forend during installation.

Distribution boxes must be accessible for maintenance work. Cable types,


lengths, and cross sections must conform to the specifications.

6.2 SECUREconnect 200 terminals


To facilitate connection, all terminals can be
disconnected from the front.

6.3 Connection terminals of SE-


CUREconnect 200F (leaf part)
6.3.1 Terminals for monitoring contacts (I1 - 14 / V4)
This is where the door monitoring contacts of the electromechanical or
motor-driven locks (if provided) are connected.

With the door closed, the feedback signals are transmitted to


SECUREconnect 200R (frame part) in an encrypted way and put out 1:1
to a potential-free changeover contact via the relays of a connected I/O
module IO10 (optional)-
see connection diagram in
chapter 8.

48 EN 12.2013 | 15887EE | Printed in Germany


6.3.2 Connection terminals for electrical locks
The terminals GS, VS, and 90 are
provided for the connection of
mechatronic locks from GU-BKS (for
particular connection diagrams see
chapter 8).

6.3.3 Connection terminals for LED


Terminals 56 and GS are provided for
the connection of an LED signalling
unlocked status. This is useful, e.g.,
for illuminated door knobs or push
bars. The power output is short circuit
protected and limited to 20 mA which
allows the LED to be connected without
pre-resistor.

Approx. 3 s after door release, the power output is switched on for the
duration of release. The duty ratio depends on the charge condition of the
capacitors with the door OPEN or permanent OPEN mode

6.3.4 Connection terminals for access control module


These terminals are provided for
connection to an access control
module (i.g. finger scanner or PIN code
keypad). A pre-configured system cable
is delivered with the access control
modules. For further details to operate
the access control modules please refer
to the corresponding manuals.

49
Mounting und operating instructions

SECUREconnect 200
Power and data transmission unit

6.4 Connection terminals of SECUREconnect 200R


(frame part)
6.4.1 Terminals for external DC 24 V voltage supply
The terminals V42 and G42 are provided for the connection of an external
DC 24 V voltage supply to operate SECUREconnect 200

Only DC 24 V voltage sources in accordance with


ATTENTION EN 60950 may be used.

SECUREconnect 200R
Connection to “output”

Stabilized power supply


AC 230 / DC 24 V, 1 A

6.4.2 Connection terminals for BKS-NET bus


Terminals LA and LB are assigned for the connection of the BKS-NET bus.

This bus allows SECUREconnect 200 to


communicate with other compatible bus
participants (e.g. escape door control unit
FTNT10). Further functional details are to
be taken from the BKS-NET installation and
operating instructions.

50 EN 12.2013 | 15887EE | Printed in Germany


6.4.3 Connection terminals for control inputs
The terminals V4, 91, 92, 93 are provided
for potential-free contacts required to
open and close the door. (Pushbutton,
relays, access control etc.)

6.4.4 Connecting a AC 230 V voltage supply


SECUREconnect 200 is suited for operation with AC 230 V voltage.

SECUREconnect 200R

Ø20
for drill hole Ø20

With metal and PVC doors, it is necessary to drill a


ATTENTION cable inlet with a minimum diametre of 20 mm.

51
Mounting und operating instructions

SECUREconnect 200
Power and data transmission unit

The mains cable is plugged in at the bottom side of SECUREconnect 200R


and must be fixed by all means with the attached cable tie to prevent it from
coming loose.

The borehole must be fitted with the enclosed rubber grommet to protect
the lead.

All edges touched by the mains cable must be unsharp and free of burrs.

If SECUREconnect 200 is connected to AC 230 V, a DC 24 V (0.2 A) voltage


for external devices will be available at terminals V42 and G42.

7. Start-up

Please observe the mounting advice given in chapter 5!

„„
Install SECUREconnect 200F in the door leaf and connect the electrical
lock according to the particular connection diagram.

Cables may be damaged when turning in the


ATTENTION fastening screws.

We recommend: Insert screw through device and fix


cable beside the screw with adhesive tape.

„„
Install SECUREconnect 200R in the door frame exactly on the opposite
side.

„„
Ensure that the tappet contacts of SECUREconnect 200F exactly
coincide with the contact surfaces of SECUREconnect 200R as the door
closes (see also installation drawing 0-45733-L0).

„„
Connect SECUREconnect 200R to the operating voltage supply’
(AC 230 V or DC 24 V).

52 EN 12.2013 | 15887EE | Printed in Germany


7.1 Establishing communication
7.1.1 Pairing
At start-up, the status LED of SECUREconnect 200 will be flashing alternately
red and green as soon as the operating voltage has been applied. The
status LED on SECUREconnect 200F flashes green as soon as the door has
been closed once for a short time and supplied with voltage. This indicates
normal functioning. At this stage every SECUREconnect 200R component
could communicate openly and function perfectly with any SECUREconnect
200F component. Data transmission between the two components are AES-
encrypted.

SECUREconnect 200R and SECUREconnect 200F – after having been


connected with each other for 15 minutes – enter into an inseparable
„partnership“ (pairing) by generating a random code which will
be exchanged between the two components later on. Afterwards
SECUREconnect 200R and SECUREconnect 200F will no longer accept any
other frame or leaf parts.

A pairing process between SECUREconnect 200F and the connected access


control module is also effected. Once the access control module has been
connected to a SECUREconnect 200F it is impossible to exchange it.

7.1.2 Re-pairing
In order to exchange a component of the door system (SECUREconnect
200R, SECUREconnect 200F or access control module) you have to start a
re-pairing procedure.

For doing so, close the reset contact on the board of the SECUREconnect
200F or the SECUREconnect 200R for 3 s. We recommend to use an alliga-
tor clip while doing. Afterwards remove the clip. The pairing process for
SECUREconnect 200R, SECUREconnect 200F and the access control module
restart.

53
Mounting und operating instructions

SECUREconnect 200
Power and data transmission unit

7.2 LED signalling


The LED indication of SECUREconnect 200 is an important means during
start-up or when it comes to trouble shooting. It provides information on
the different status of the device.

7.2.1 LED indication on SECUREconnect 200R


LED green / LED red Normal status, not paired, no
0.5 Hz flashing alternately communication with other devices linked
to the BKS-NET bus
LED green / LED red Normal status, not paired, communication
1 Hz flashing alternately with at least one device linked to the BKS-
NET bus
LED green Normal status, paired, no communication
0.5 Hz flashing with other devices linked to the BKS-NET
bus
LED green Normal status, paired, communication
1 Hz flashing with at least one device linked to the BKS-
NET bus
LED red Temperature too high
2 Hz flashing
LED red Trouble: Short circuit
5 Hz flashing
Display with door open and closed.

7.2.2 LED indication on SECUREconnect 200F


LED green Normal status, not paired
1 Hz flashing
LED green Normal status, paired
0.5 Hz flashing
LED green Power supply between SECUREconnect 200R
off and 200F interrupted for a longer period of
time
LED green Trouble:
5 Hz flashing Short circuit, switch-off, capacitors....
Display with door closed, and up to 15 s after door opening

54 EN 12.2013 | 15887EE | Printed in Germany


Explanation:

5 Hz = 5 flashes per second

2 Hz = 2 flashes per second

1 Hz = LED 0.5 seconds on, 1 flash per second

0.5 Hz = LED 1 second on

7.3 Functions with motor-driven locks


7.3.1 Short-time OPEN (short-term release)
If a potential-free contact connected to terminals 93 / V4 is actuated with
the door closed, SECUREconnect 200F receives the signal to release the
electrical lock and to retract the latch.

When the door is opened, the electrical lock will extend the latch again after
3 s, so the door will be locked without delay as it is closed again.

If the door remains closed, the latchbolt will extend after 2 - 20 s (time
adjustable).

Here it may happen that the extended latchbolt


ATTENTION hits the striker. In that case, please check the
locking status of the door.

If a potential-free contact (gating pulse) connected to terminals 93 / V4 is


actuated permanently, the electrical lock remains open for the duration of
the signal.

„„
When the door is opened, the electrical lock will extend the latch again
after 3 s.

„„
When the door is closed again, the electrical lock will retract the latch.

55
Mounting und operating instructions

SECUREconnect 200
Power and data transmission unit

7.3.2 Permanent OPEN (unlocking)


If a potential-free contact connected to terminals 91 / V4 is actuated with
the door closed, SECUREconnect 200F receives the signal to retract the
latch.

The latch remains retracted permanently.

The electrical lock will not re-lock automatically.


ATTENTION
The application of this function is not permitted
with fire rated doors (DIN 18250) ! Non-compliance
will result in the revocation of the door‘s
fire approval !

7.3.3 Door locking


If a potential-free contact (gating pulse) connected to terminals 92 / V4 is
actuated with the door closed, SECUREconnect 200F receives the signal to
re-lock the electrical lock.

Here it may happen that the extended latchbolt


ATTENTION hits the striker.

In that case, please check the locking status of the


door.

If the functions „Permanent OPEN“ and „Door


NOTE locking“ are controlled via a time switch and if the
input „Door locking“ is permanently closed, the
door can always be opened via the „Short-time
OPEN“ function.

56 EN 12.2013 | 15887EE | Printed in Germany


7.4 Function with electromechanical locks (‘EK’)
7.4.1 Short-time OPEN (engaging the lever handle)
If a potential-free contact connected to terminals 93 / V4 is actuated with
the door closed, SECUREconnect 200F receives the signal to engage the
lever handle.

„„
If the door remains closed, the lever handle will be disengaged again
after 20 s.

„„
If the door is opened, the lever handle will be disengaged again after 3 s.

„„
If a potential-free contact connected to terminals 93 / V4 is actuated
permanently, the lever handle remains engaged remains for the duration
of the signal (see above).

„„
If the door is opened, the lever handle will be disengaged again after 3 s.

„„
If the door is closed again, the lever handle will be re-engaged.

7.4.2 Permanent OPEN (unlocking)


If a potential-free contact (gating pulse) connected to terminals 91 / V4 is
actuated with the door closed, SECUREconnect 200F receives the signal to
engage the lever handle.

„„
If the door remains closed, the lever handle will remain engaged.

„„
If the door is opened, the lever handle will be disengaged again after 3 s

„„
If the door is closed again, the lever handle will be re-engaged.

7.4.3 Door closing (disengaging the lever handle)


If a potential-free contact connected to terminals 92 / V4 is actuated with
the door closed, SECUREconnect 200F receives the signal to disengage the
lever handle.

57
Mounting und operating instructions

SECUREconnect 200
Power and data transmission unit

Enclosed connection cable with terminals


brown
white
Short-time OPEN (impulse)
yellow
Close (impulse / handle disengaging)
green
Permanent OPEN (impulse)

If voltage from external component is applied to


ATTENTION terminals V4, 91-93, this lead to the destruction of
the switching inputs!

58 EN 12.2013 | 15887EE | Printed in Germany


7.5 Electrical function test
In order to verify if an assembly group has been connected properly, it is
necessary to carry out the following work steps:

„„
Close door manually

„„
Apply supply voltage to SECUREconnect 200R (e.g. 230 V AC by means
of a Europlug)

„„
Bridge V4 and 93 (brown and white wire of connecting cable) on
SECUREconnect 200R

The lock function 'short-time OPEN' will be activated causing the electrical
lock to unlock and the outside lever handle to engage for a short moment,
each.

8. Connection diagrams

8.1 Latchbolt monitoring

System cable for


latchbolt monitoring

SECUREconnect 200F

59
Mounting und operating instructions

SECUREconnect 200
Power and data transmission unit

8.2 Connection diagram Secury Automatic with A-opener


Impulse-controlled door opening time approx. 2 s (cannot be adjusted).
Permanent door opening time corresponds to duration of control signal

SECUREconnect 200F

Connecting cable Signal


Grey (blue) GND
Brown + 24 V
Black Control line

60 EN 12.2013 | 15887EE | Printed in Germany


8.3 Switching the A-opener’s acoustic signal on and off
„„
Connect A-opener to SECUREconnect 200F according to connection
diagram.

„„
Disconnect SECUREconnect 200R from power supply.

„„
Bridge terminals V4, 93, 92, 91.

SECUREconnect 200R

„„
Wait until SECUREconnect 200F stops flashing.

„„
Connect SECUREconnect 200R and 200F (e.g., by closing the door)

„„
Switch-on voltage on SECUREconnect 200R.

An automatic switching sequence will be started and completed after 30 s.


During this period of time, the A-opener will not be active.

SECUREconnect 200R and 200F must not be


ATTENTION separated during this period (e.g. by opening the
door).

„„
Disconnect SECUREconnect 200R from power supply and remove
bridges.

„„
Wait until SECUREconnect 200F stops flashing.

„„
Switch on power.

61
Mounting und operating instructions

SECUREconnect 200
Power and data transmission unit

8.4 Connection diagram of motor-driven lock


series 19 (with 14-wire connecting cable)

Connecting Signal
cable
Blue Locked COM
Red Locked NO
Black Unlocked COM
Purple Unlocked NO
Grey-pink Cyl. locking cam COM
Red-blue Cyl. locking cam NO
White-green Function output COM
Brown-green Function output NO
Green Not assigned
Yellow Function input
White GND
Brown + 24 V
Grey Door contact
Pink Control line

62 EN 12.2013 | 15887EE | Printed in Germany


8.5 Connection diagram of ‘EK‘ lock
series 19 (with 14-wire connecting cable)

Connecting Signal
cable
Blue Locked COM
Green Locked NO
Grey Locked NC
Red Cyl. locking cam COM
Yellow Cyl. locking cam NO
Purple Handle side 1 COM
Red-blue Handle side 1 NO
Brown-green Handle side 1 NC
White-green Handle side 2 COM
Grey-pink Handle side 2 NO
Black Handle side 2 NC
White GND
Brown + 24 V
Pink Control line

63
Mounting und operating instructions

SECUREconnect 200
Power and data transmission unit

8.6 Connection diagram of ‘EK‘ lock series 21


(with 14-wire connecting cable)

Connecting Signal
cable
Blue Locked COM
Green Locked NO
Grey LockedNC
Red Cyl. locking cam COM
Yellow Cyl. locking cam NO
Pink Schließbart NC
Purple Handle side 1 COM
Red-blue Handle side 1 NO
Brown-green Handle side 1 NC
White-green Handle side 2 COM
Grey-pink Handle side 2 NO
Black Handle side 2 NC
White GND
Brown + 24 V

64 EN 12.2013 | 15887EE | Printed in Germany


8.7 Connection diagram of ‘EK‘ lock series 21
(with 8-wire connecting cable)

Connecting Signal
cable
Blue Locked COM
Grey Locked NO
Green Locked NC
Red Cyl. locking cam COM
Yellow Cyl. locking cam NO
White GND
Brown + 24 V
Pink Control line

65
Mounting und operating instructions

SECUREconnect 200
Power and data transmission unit

8.8 Control via IO modules


Please bear in mind that each IO10 module has a different address setting.

Adressjumper
Closed: Device 1
Open: Device 2
COM

COM

COM

COM

COM

COM

COM

COM
NO

NO

NO

NO

NO

NO

NO

NO
NC

NC

NC

NC

NC

NC

NC

61 41 51 62 42 52 Adresse 63 43 53 64 44 54 NC
61 41 51 62 42 52 Adresse 63 43 53 64 44 54

Service Service

IO10-1 IO10-2

G1 V1 LA LB V9 I1 V9 I2 V9 I3 V9 I4 G1 V1 LA LB V9 I1 V9 I2 V9 I3 V9 I4

66 EN 12.2013 | 15887EE | Printed in Germany


8.8.1 IO module inputs
Two IO10 or IO5 modules can be connected to SECUREconnect 200R via
terminals LA and LB.

Input and output parameters are preset in compliance with the BKS-NET
concept.

Input IO10 Device 1 Function

Input 1: terminal I1, V9 Permanent OPEN (unlocking)

Input 2: Terminal I2, V9 Close (locking)

Input 3: Terminal I3, V9 Priority locking

Input 4: Terminal I4, V9 Priority unlocking

Input IO10 Device 2 Function

Input 1: Terminal I1, V9 Non-priority unlocking

Input 2: Terminal I2, V9 -

Input 3: Terminal I3, V9 Short-time OPEN

Input 4: Terminal I4, V9 -

Input IO5 Function

Input 1: Terminal I1, V9 Permanent OPEN (unlocking)

67
Mounting und operating instructions

SECUREconnect 200
Power and data transmission unit

8.8.2 IO module outputs


The input status (SECUREconnect 200F) are put out directly to the IO modu-
le relays.

Input Output
(SECUREconnect 200F) IO10 Adresse 1

Input 1: Terminal I1, V4 Relay 1: Terminal 41, 51, 61

Input 2: Terminal I2, V4 Relay 2: Terminal 42, 52, 62

Input 3: Terminal I3, V4 Relay 3: Terminal 43, 53, 63

Input 4: Terminal I4, V4 Relay 4: Terminal 44, 54, 64

Input Output
(SECUREconnect 200F) IO10 Adresse 2

Input 1: Terminal I1, V4 Relay 1: Terminal 41, 51, 61

Input 2: Terminal I2, V4 Relay 2: Terminal 42, 52, 62

Input 3: Terminal I3, V4 Relay 3: Terminal 43, 53, 63

Input 4: Terminal I4, V4 Relay 4: Terminal 44, 54, 64

Input Output
(SECUREconnect 200F) IO5

Input 1: Terminal I1, V4 Relay 1: Terminal 41, 51, 61

Input 2: Terminal I2, V4 Relay 2: Terminal 42, 52, 62