Acclimatise EGCP2 - Generator Operator s Quick Reference Guide
Operation of the generators is determined by the position of two selector switches
mounted on the control panel door in conjunction with the EGCP-2 controller internal
setpoints.
Control Mode Selection Switch
The main control panel has a Woodward EGCP-2 unit as the generator controller. A
Control Mode Switch is included, allowing four modes of operation for the generator:
The various Control Switch positions are outlined as follows:
1. OFF: Generator will not start
2. AUTO: Generator will start on loss of mains or on receipt of a remote start signal
   (see Modes of Operation section for specific requirements).
3. MANUAL: Generator will run off load. (Note: Generator breaker may close. See
   Modes of Operation section for details)
4. RUN: Generator will synchronise to the mains and ramp up to its base load point.
                                    Page 1              Revision 1: 05 Dec 2006
   Acclimatise EGCP2 - Generator Operator s Quick Reference Guide
Sync Mode Selector Switch
As well as a Control Mode Switch, the control also features a Sync Mode Switch.
The various Sync Switch positions are as follows:
1. NORMAL - Enables island mode operation and sync to the mains when there is
   mains breaker control available.
2. PARALLEL ONLY         Enables the generator to sync to the mains when there is
   no available mains breaker control.
3. STANDBY ONLY - Enables island mode operation of the generator. The EGCP-
   2 AMF function is inhibited and a remote signal is required to start the generator.
                                      Page 2            Revision 1: 05 Dec 2006
   Acclimatise EGCP2 - Generator Operator s Quick Reference Guide
Modes of Operation
There are four possible modes of operation for the generators:
1. Island Mode
a. With Mains Breaker Control (Includes AMF and sync)
b. Without Mains Breaker Control (Breaker control and timing by others. Remote
   Start signal required)
2. Sync with other Generators
a. Prime Power (No mains)
b. Standby to Mains (Remote Start signal required)
3. Sync with the Mains
a. With Mains Breaker control (Includes AMF operation)
b. Without Mains Breaker control (no Island Mode operation)
c. Without Mains Breaker control (in Manual Mode)
d. Without Mains Breaker Control (in Remote Control)
4. Sync with the Mains and other Generators
a. Normal Operation
b. In Manual Mode
c. In Remote Control
                                   Page 3              Revision 1: 05 Dec 2006
  Acclimatise EGCP2 - Generator Operator s Quick Reference Guide
1a. Island Mode - with Mains Breaker Control (includes AMF and sync)
   Sync Mode Switch       NORMAL
   Control Mode Switch     AUTO
   No Remote Control Enabled
   Generator starts AND closes its breaker on sensing a Mains Failure
   No break re-transfer
EGCP-2 Settings:
   Check Mains Circuit Breaker     Enabled
   Operating Mode     Mains Parallel
   Mains Voltage Limits    LOM
   Mains Frequency Limits     LOM
   Mains Sensing    Enabled
                                    Page 4           Revision 1: 05 Dec 2006
   Acclimatise EGCP2 - Generator Operator s Quick Reference Guide
1b. Island Mode - without Mains Breaker Control (breaker control and timing
   by others. Remote start signal required)
   Sync Mode Switch       STANDBY ONLY
   Control Mode Switch     AUTO
   No Remote Control Enabled
   Generator starts AND closes its breaker on receipt of a Remote Start Signal
EGCP-2 Settings:
   Check Mains Circuit Breaker    Disabled
   Operating Mode     No Mains Parallel
   Mains Voltage Limits    Disabled
   Mains Frequency Limits - Disabled
   Mains Sensing    Disabled
                                  Page 5              Revision 1: 05 Dec 2006
  Acclimatise EGCP2 - Generator Operator s Quick Reference Guide
2a. Sync with other Generators      Prime Power (no mains)
   Sync Mode Switch       NORMAL
   Control Mode Switch     AUTO
   No Remote Control Enabled
   10 - way communications plug connected between generators for loadsharing,
   otherwise generators shall run in baseload.
   Generator starts AND closes its breaker when switched to AUTO
EGCP-2 Settings:
   Check Mains Circuit Breaker     Disabled
   Operating Mode     No Mains Parallel
   Mains Voltage Limits    High Disabled, Low LOM
   Mains Frequency Limits      Disabled
   Mains Sensing    Disabled
                                   Page 6           Revision 1: 05 Dec 2006
   Acclimatise EGCP2 - Generator Operator s Quick Reference Guide
2b. Sync with other Generators - Standby to Mains (Remote Start Signal
   required)
   Sync Mode Switch      STANDBY ONLY
   Control Mode Switch    AUTO
   No Remote Control Enabled
   4-way communications plug connected between generators for loadsharing,
   otherwise generators shall run in baseload
   Generators start AND close their breakers on receipt of a remote start signal
EGCP-2 Settings:
   Check Mains Circuit Breaker     Disabled
   Operating Mode     No Mains Parallel
   Mains Voltage Limits    High Disabled, Low LOM
   Mains Frequency Limits - Disabled
   Mains Sensing     Disabled
                                   Page 7              Revision 1: 05 Dec 2006
   Acclimatise EGCP2 - Generator Operator s Quick Reference Guide
3a. Sync with the Mains - with Mains Breaker Control (Includes AMF operation)
   Sync Mode Switch       NORMAL
   Control Mode Switch     AUTO
   No Remote Control Enabled
   No break retransfer
   Generator starts AND closes its breaker on sensing a mains failure
EGCP-2 Settings:
   Check Mains Circuit Breaker     Enabled
   Operating Mode     Mains Parallel
   Mains Voltage Limits    LOM
   Mains Frequency Limits - LOM
   Mains Sensing    Enabled
                                   Page 8            Revision 1: 05 Dec 2006
  Acclimatise EGCP2 - Generator Operator s Quick Reference Guide
3b. Sync with the Mains - Without Mains Breaker Control (no island mode
   operation)
   Sync Mode Switch       PARALLEL ONLY
   Control Mode Switch - AUTO
   No Remote Control Enabled
   Generator starts AND closes its breaker when switched to AUTO
EGCP-2 Settings:
   Check Mains Circuit Breaker    Enabled
   Operating Mode     Mains Parallel
   Mains Voltage Limits    LOM
   Mains Frequency Limits - LOM
   Mains Sensing    Enabled
                                  Page 9           Revision 1: 05 Dec 2006
  Acclimatise EGCP2 - Generator Operator s Quick Reference Guide
3c. Sync with the Mains - Without Mains Breaker Control (in Manual Mode)
   Sync Mode Switch       PARALLEL ONLY
   Control Mode Switch - MANUAL
   No Remote Control Plug
   Breaker Open/Close pushbuttons active
   Manually sync using speed and volts raise/lower switches and synchroscope
   Press breaker close pushbutton when synchronised
   Load level determined by speed adjust
EGCP-2 Settings:
   Check Mains Circuit Breaker   Disabled
   Operating Mode     No Mains Parallel
   Mains Voltage Limits    High Disabled, Low LOM
   Mains Frequency Limits - Disabled
   Mains Sensing    Disabled
                                 Page 10            Revision 1: 05 Dec 2006
   Acclimatise EGCP2 - Generator Operator s Quick Reference Guide
3d. Sync with the Mains - without Mains Breaker Control (in Remote Control)
   Sync Mode Switch       PARALLEL ONLY
   Control Mode Switch     MANUAL/AUTO/RUN have no effect on generator. OFF
   position shuts down the generator
   Remote Control Plug installed
   Breaker Open/Close pushbuttons active
   Manual sync using speed and volts raise/lower switches and synchroscope
   Press breaker close pushbutton when synchronised
   Load level determined by speed adjust
   Generator starts on receipt of signal from remote panel
EGCP-2 Settings:
   Check Mains Circuit Breaker     Enabled
   Operating Mode     Mains Parallel
   Mains Voltage Limits    High Disabled, Low LOM
   Mains Frequency Limits - LOM
   Mains Sensing    Enabled
                                   Page 11            Revision 1: 05 Dec 2006
  Acclimatise EGCP2 - Generator Operator s Quick Reference Guide
4a. Sync with the Mains and other Generators
   Sync Mode Switch       PARALLEL ONLY
   Control Mode Switch - AUTO
   No Remote Control Plug
   Generator starts AND closes breaker on sensing a mains failure
   4-way communications plug connected between generators for loadsharing,
   otherwise generators shall run in baseload.
   No break retransfer
EGCP-2 Settings:
   Check Mains Circuit Breaker    Enabled
   Operating Mode     Mains Parallel
   Mains Voltage Limits    LOM
   Mains Frequency Limits     LOM
   Mains Sensing    Enabled
                                  Page 12            Revision 1: 05 Dec 2006
  Acclimatise EGCP2 - Generator Operator s Quick Reference Guide
4b. Sync with the Mains and other Generators (in Manual Mode)
   Sync Mode Switch       PARALLEL ONLY
   Control Mode Switch - MANUAL
   No Remote Control Plug
   Breaker Open/Close pushbuttons active
   No automatic loadsharing through 4-way communications plug
   Manual sync using speed and volts raise/lower switches and synchroscope
   Press breaker close pushbutton when synchronised
   Load level determined by speed adjust
EGCP-2 Settings:
   Check Mains Circuit Breaker    Enabled
   Operating Mode     Mains Parallel
   Mains Voltage Limits    LOM
   Mains Frequency Limits      LOM
   Mains Sensing    Disabled
                                  Page 13          Revision 1: 05 Dec 2006
  Acclimatise EGCP2 - Generator Operator s Quick Reference Guide
4c. Sync with the Mains and other Generators (in Remote Control)
   Sync Mode Switch       PARALLEL ONLY
   Control Mode Switch     MANUAL/AUTO/RUN have no effect on generator. OFF
   position shuts down the generator
   Remote Control Plug installed
   Breaker Open/Close pushbuttons active
   No automatic loadsharing through 4-way communications plug
   Manual sync using speed and volts raise/lower switches and synchroscope
   Press breaker close pushbutton when synchronised
   Load level determined by speed adjust
EGCP-2 Settings:
   Check Mains Circuit Breaker     Enabled
   Operating Mode     Mains Parallel
   Mains Voltage Limits    LOM
   Mains Frequency Limits - LOM
   Mains Sensing    Enabled
                                   Page 14         Revision 1: 05 Dec 2006
   Acclimatise EGCP2 - Generator Operator s Quick Reference Guide
Symbols Key
   Generator                Mains Supply                      Load
Circuit Breaker    Circuit Breaker Interlock                 Control
Acknowledge/Clear Faults
A general fault indicated by the ALARM LED on the left of EGCP2 controller and by
the buzzer sounding.
The alarm is muted when the ALARM CLEAR is pressed.
Faults can be viewed through in the ALARM/EVENT Log.
In the event of a Hard Shutdown the engine will be locked out until the fault is
acknowledged by pressing the ALARM CLEAR push-button while in the
Alarm/Event Log.
The faults can be cleared while in the ALARM/EVENT Log by pressing ALARM
CLEAR a second time.
                                  Page 15             Revision 1: 05 Dec 2006
   Acclimatise EGCP2 - Generator Operator s Quick Reference Guide
Change Setpoints
Press the CONFIG key.
Enter password & press the ENTER key.
Use the SCROLL keys to select the relevant menu.
Press the ENTER   key to enter the menu.
Use the SCROLL    keys to select the parameter to be changed.
ENTER .
Use the SCROLL    keys to change setting.
Press the ENTER   key to confirm.
Use the ESC key to cancel entry without saving.
Note: Only trained personnel should use this equipment.
  All standard safety procedures should be followed.