Henry Technologies Sight Glasses & Accumulators
Henry Technologies Sight Glasses & Accumulators
377
ACCUMULATORS AND MUFFLERS
HENRY TECHNOLOGIES HORIZONTAL ACCUMULATORS
Liquid accumulators of this design should not be used when the
temperature of the liquid refrigerant is less than +15° F in the
accumulator. These accumulators have a 1/2-in. FPT connection
for liquid injection and a 3/4-in. FPT connection for hot gas bypass.
These connections can also be used for a relief device as required
by UL 207.
RECOMMENDED TONS OF REFRIGERANT AT SUCTION
REFRIGERANT HOLDING CAP.
PART SIZE DIMENSIONS (in) EVAPORATING TEMPERATURE (°F)
(lbs 0° F SAT.)
NO CONN R-134a R-22 R-404A/R-507
R-134a R-404A/
A B C R-22 +40°F +20°F +0°F +40°F +20°F +0°F +40°F +20°F +0°F
R-507
S-7615 1-5/8 ODS 28 21.50 23.3 21.3 19.3 15 10 6.25 29 20 12.5 28.5 19 11.5
S-7621 2-1/8 ODS 6 36.75 30.25 31.6 29 26.2 28.6 19.5 12.5 50 30 25 49.1 33.2 22.9
S-7625 2-5/8 ODS 50 43.50 46.7 42.6 38.6 50 35 23 95 65 45 93.2 61.7 41.2
ACCUMULATORS AND MUFFLERS
DIMENSIONS (in)
PART NO SIZE CONN A B
S-6304 1/2 ODS 3 7.75
S-6305 5/8 ODS 3 7.75
S-6307 7/8 ODS 3 9.69
S-6311 1-1/8 ODS 3 9.69
S-6405 5/8 ODS 4 6.75
S-6407 7/8 ODS 4 7
S-6411 1-1/8 ODS 4 13.25
S-6413 1-3/8 ODS 4 13.75
S-6415 1-5/8 ODS 4 18.25
S-6621 2-1/8 ODS 6 21
S-6625 2-5/8 ODS 6 21
S-6631 3-1/8 ODS 6 22.38
378
LIQUID REFRIGERANT RECEIVERS
HENRY TECHNOLOGIES LIQUID REFRIGERANT RECEIVERS
Receivers should be selected based on the operating charge for all
system components, including the liquid lines. It is usual to add
a small percentage to cover the refrigerant in long runs of suction
and discharge lines, etc. It is essential that the maximum operating
charge be determined, e.g., winter charge in air cooled condenser
having flooded head pressure control, this being much greater than
the normal summer charge.
379
LIQUID REFRIGERANT RECEIVER ACCESSORIES
HENRY TECHNOLOGIES RECEIVER ACCESSORIES
LIQUID LEVEL GAUGES
PART NO RECEIVER DIA
S-9450 8-5/8
S-9451 10-3/4
S-9452 12-3/4
S-9453 14
S-9454 16
S-9455 18
S-9456 20
Mating flanges for level gauges not included on most receivers.
BRACKET KITS
PART NO RECEIVER DIA
3-019-908 8-5/8
3-019-910 10-3/4
3-019-912 12-3/4
ROTO-LOC VALVES
LIQUID REFRIGERANT RECEIVER ACCESSORIES
Includes gasket.
ROTO-LOC/ODS ADAPTERS
PART NO THREAD ODS
2-009-037 1″ - 14 5/8
3-009-308 1-1/4″ - 12 7/8
2-009-046 1-3/4″ - 12 1-3/8
380
OIL SEPARATORS
HENRY TECHNOLOGIES HELICAL OIL SEPARATORS
The helical oil separator features a centrifugal flow path achieving approximately
99% efficiency of oil separation with low pressure drop.
MAX. CAPACITY IN TONS OF REFRIGERATION AT
PART SIZE DIMENSIONS (in.) EVAPORATOR TEMPERATURE NOMINAL PRE-CHARGED
NO CONN R-134a R-22 R-404A/R-507 DISCHARGE AMOUNT
A B C D -40°F +40°F -40°F +40°F -40°F +40°F CFM (oz)
S-5180 1/4 ODS 2.50 6.38 1.75 .44 .50 .75 .75 1.00 .75 1.00 .75 14
S-5181 3/8 ODS 2.50 7.50 1.75 .50 .75 1.00 1.00 1.50 1.00 1.50 1.00 14
S-5182 1/2 ODS 4 13 2.75 2.44 1.00 1.50 1.50 2.00 1.50 2.00 1.50 14
S-5185 5/8 ODS 4 15 2.75 2.50 3.00 4.00 4.50 5.50 4.00 5.50 4.00 14
S-5187 7/8 ODS 4 17 3 2.94 4.50 5.50 7.00 8.00 6.50 8.50 6.00 14
S-5188 1-1/8 ODS 4 19 3 3.06 6.00 7.50 9.00 10.50 8.50 11.00 8.00 14
S-5190 1-3/8 ODS 6 15 4.25 3.69 8.00 10.00 13.00 14.00 12.00 15.00 11.00 40
S-5192 1-5/8 ODS 6 17 4.25 3.95 11.00 13.00 16.00 18.00 15.00 19.00 14.00 40
S-5194 2-1/8 ODS 6 17 4.38 4.19 18.00 21.00 25.00 30.00 24.00 31.00 22.00 40
S-5290 1-3/8 ODS 6 15 4.25 3.69 8.00 10.00 13.00 14.00 12.00 15.00 11.00 25
S-5292 1-5/8 ODS 6 17 4.25 3.95 11.00 13.00 16.00 18.00 15.00 19.00 14.00 25
S-5294 2-1/8 ODS 6 17 4.38 4.19 18.00 21.00 25.00 30.00 24.00 31.00 22.00 25
S-5202 2-1/8 ODS 8 24 5.38 5.06 22.00 27.00 35.00 39.00 31.00 41.00 29.00 25
S-5203 2-5/8 ODS 10 27 6.50 5.63 46.00 56.00 71.00 80.00 64.00 83.00 60.00 25
S-5204 3-1/8 ODS 12 30 7.75 6.45 72.00 88.00 112.00 127.00 100.00 131.00 94.00 25
OIL SEPARATORS
Minimum tonnage is 33% of rated capacity, oversizing is not acceptable.
381
OIL SEPARATORS
HENRY TECHNOLOGIES CONVENTIONAL OIL SEPARATORS
All the capacities shown are based on 100°F condensing temperature and on connection size being
the same as the compressor discharge valve we recommend for parallel compressor systems
application for our S-5700 and S-1900 series oil separators. For low temperature applications, we
recommend our S-1900 series oil separators. If operating horsepower is larger than the systems
OIL SEPARATORS
382
OIL SEPARATORS
HENRY TECHNOLOGIES CONVENTIONAL OIL SEPARATORS
OIL SEPARATORS
383
OIL SEPARATOR ACCESSORIES
HENRY TECHNOLOGIES HEAT ELEMENTS
Heat elements add heat to oil separators to prevent migration of
refrigerant to the vessel during off cycles of the compressor.
Heat elements can also be used on suction line accumulators to
warm the oil and allow oil return to the compressor on low
temperature applications.
384
OIL LEVEL REGULATORS (CONVENTIONAL)
HENRY TECHNOLOGIES OIL LEVEL REGULATORS
The oil level regulator controls the oil level in the compressor crankcase with a float operated valve. Oil level
regulators are designed to attach directly to the sight glass housing on compressor crankcases. Adapter kits are
385
OIL LEVEL REGULATORS (CONVENTIONAL)
HENRY TECHNOLOGIES ELECTRO-MECHANICAL OIL LEVEL REGULATORS
S-9030 Adjustable Regulator
The Electro-Mechanical Oil Level Regulator S-9030 provide a simplistic means
OIL LEVEL REGULATORS (CONVENTIONAL)
for controlling oil level for hermetic, semi-hermetic, reciprocating and scroll
compressors, through the use of a float switch and solenoid valve. A magnetic
reed float switch closes upon the reduction of oil level in the oil regulator body.
This action energizes the solenoid valve thereby feeding oil into the regulator
body.
The oil level is adjustable by loosening the compression nut and manually
adjusting the position of the float switch. A low level alarm is also provided, for
oil safety on hermetic and scroll compressors. If the oil level drops 1/8" below
the set point, a second magnetic reed switch closes activating a customer
supplied alarm. This alarm circuit may also be used to disconnect power from
the compressor. While the regulator is in alarm the solenoid valve remains open
trying to re-establish the oil level.
Features: S-9030 Adjustable Regulator
• Complete oil level control without The S-9030 Oil Level Regulator
variations in pressure drop. is designed to bolt directly to the
• 3/8" Flare normally closed solenoid valve. three bolt sight glass housing
• Adjustable between 1/4" and 1/2" glass. found on many compressor
• Low level alarm circuit. crankcases. Adapter kits are
• 24 Vac .25 amp. No UL considerations. available for compressors that
• Equalization connection 3/8" Flare. have a different sight glass
• Operating differential 5 to 300 psig. configuration. The sight glass
• Reliable float switch operation, 20 Va. pilot duty. from the compressor or
• All major components replaceable. supplied with an adapter kit,
• One oil level regulator for all applications bolts to the second regulator
flange for visual observation
of the oil level.
386
OIL RESERVOIRS
HENRY TECHNOLOGIES OIL RESERVOIR
Due to system design, loads & defrost cycles, build up in the Oil Reservoir to adversely affect the Oil
OIL RESERVOIRS
varying amounts of oil can be returned by the oil Regulators. To prevent this, a vent line is installed from the
separator. Because of this, a safety reserve of oil is top of the Oil Reservoir to the suction line. This line permits
required for the operation of our oil control system. the pressure in the Oil Reservoir to be approximately the
The oil reservoir is the holding vessel for this stand- same as the suction line and the compressor crankcases.
by oil. It has sight glass ports to observe the oil level The 4 gallon model Cat. No. S-9108 should be used on
inside the vessel. The valve on top of the very large systems, or systems with excessive oil charges,
Oil Reservoir receives oil from the Oil Separator, long line runs or any case where suction oil return may be
and the bottom valve distributes oil to the Oil Level impeded.
Regulators. The valves are backseating and have a
1/4" flare connection, allowing the addition or New System Start-Up
removal of oil from the reservoir. High pressure gas On system start-up of a new parallel system, oil should be
returns with the oil from the Oil Separator to the added to the OIL RESERVOIR to the upper sight glass
Oil Reservoir. Pressure could port, NOT ABOVE IT. It is commonly accepted that in a
new refrigeration system, some oil will be absorbed by the
refrigerant as the system becomes balanced out. After two
hours of operation, the OIL RESERVOIR, if necessary,
should again be filled to the upper sight glass, and also
after two days, by which time the entire refrigeration
system should be balanced out. Then the OIL
RESERVOIR must be observed on each service call. No
oil should be added again until the oil level falls below the
lower sight glass port.
387
ELECTRONIC OIL LEVEL CONTROL
OPTRONIC OP-02
ELECTRONIC OIL LEVEL CONTROL
The stand alone regulator is suitable for both Max Ambient Temp 113°F
high pressure and low pressure oil
management control systems. The oil is Max Fluid Temp 176°F
regulated at 1/2 Sight Glass using a pulse
timer. When a low condition is detected , there Supply Voltage (Conns 1 & 2) 24V AC 50 / 60 HZ
is a 15 second time delay prior to oil feed to Rated Operating Current 0.5 Amps
ensure stability and prevent overfill. Oil is then
pulsed into the compressor at 3 second on/off Alarm contacts (Conns 3 & 4) Volt Free, N/O
intervals. If demand is not satisfied after 2
minutes of continuous oil feed, a low level Alarm Contact Rating 24V DC@ 2A, 120V AC@2A
alarm is initiated by means of a fail-safe
electrical contact. During the alarm condition Electrical Connection 4 Pin M12 Circular, IEC60947-5-2
the regulator will continue to pulse feed oil. The
alarm will reset automatically if the oil returns to Protection Class IP54
1/2 glass. The alarm contact may be used to Status LED’s 4
shut down the compressor in the event of a low
level condition. Oil Supply Line 1/4” FLARE
388
OIL LEVEL REGULATORS AND CONTROL ACCESSORIES
HENRY TECHNOLOGIES OIL LEVEL REGULATOR ADAPTER KIT
All kits include necessary hardware, gaskets and sight glasses to
mount Oil Level Regulators to various compressors shown in this
table. *KIT 3-033-201 INCLUDED WITH ALL OIL LEVEL
REGULATORS NOTE: For compressors not listed above, a
universal adapter kit is available Part No. 3-033-217. This adapter kit
has a 3-hole flange to mount to the regulator. The compressor end of
the kit is a 1-1/4" OD steel tube. The existing compressor sight glass
gland or flange must be bored out or bushed down to accept the 1-
1/4” tube. The tube is then brazed or welded to the reworked gland or
flange and installed on the compressor.
ADAPTER KIT PART NO SIGHT GLASS OIL LEVEL COMPRESSOR MANUFACTURER SIGHT GLASS CONFIGURATION
3-033-201* 1/2 Dunham-Bush Big 4 3 Bolt 1-7/8 B.C.
3-033-201* 1/2 Trane 3 Bolt 1-7/8 B.C.
3-033-201* 1/2 York 3 Bolt 1-7/8 B.C.
3-033-201* 1/4 Carrier (models EA & ER) 3 Bolt 1-7/8 B.C.
389
HENRY TECHNOLOGIES OIL CONTROL COMPONENTS
PRESSURE VALVE
PART NO PRESSURE SETTING SIZE CONNECTION
S-9104 5 lbs 3/8″ Female x ; 3/8″ Male Flare
S-9104H 20 lbs 3/8″ Female x ; 3/8″ Male Flare
PART NO A B TYPE
S-9106H 3/8″ Flare 3/8″ Fem. Flare Vertical
S-9106V 3/8″ Flare 3/8″ Fem. Flare Horizontal
HENRY TECHNOLOGIES OIL CONTROL COMPONENTS
PART NO
3-033-226
390
OIL LEVEL CONTROL ACCESSORIES
HENRY TECHNOLOGIES ELECTRONIC OIL LEVEL CONTROL AND ACCESSORIES
3-033-245 Sight Glass Adapter Kit
Sight Glass Adapter Kit is for compressors with only one crank-
case sight glass. The 3-Bolt flange Oil Level Transducer (S-9330)
does not allow for a visual observation of the oil level in compressors.
This adapter kit provides an additional sight glass and a 1/4" flare
equalization/oil fill connection.
PART NO
3-033-245
PART NO
3-044-001
391
REFRIGERATION OIL FILTER DRIERS
HENRY TECHNOLOGIES OIL FILTER — POE OIL FILTER-DRIER
Our Oil Line Strainer protects the Oil Level Regulator by removing
foreign matter such as dirt, metal chips, etc. so the foreign material
will not plug the small orifice of the Oil Level Regulator. It will also
prevent foreign material from entering the compressor. The strainer’s
100 mesh screen provides adequate straining with low pressure drop.
PART NO
S-4004
S-4005
Our S-4004 Oil Filter removes foreign material from the oil as it
passes through the filter. The filter easily captures any debris
that may be in the system, such as dirt, metal chips, etc. (particle
retention 10 micron). The S-4004 is required on all Electronic Oil
Level Controllers to protect the solenoid manifold.
S-4005 POE Oil Filter & Drier for POE oil return on systems using Oil
Separators and Oil Control Systems. This is not a refrigerant Filter
Drier. It is designed to operate at a very low pressure drop in a
100% oil environment.
S-4005 POE Oil Filter & Drier was designed to clean and dry POE oil
as it is returned to the compressor crankcase or Oil Reservoir in
parallel systems. Clean and dry POE oil assures the proper operation
of the float assemblies in the Oil Separator and the Oil Level
Regulators.
REFRIGERATION OIL FILTER DRIERS
392
CHECK VALVES
HENRY TECHNOLOGIES CHECK VALVES (Globe Design)
FORGED BRASS BODY — TYPE 116
• Temperature rating –40° F to +300° F
• Maximum working pressure 500 psi
CHECK VALVES
down. Internal parts can be easily
removed to prevent damage when
soldering valve into line. Suitable for
highside or lowside installation and hot
gas applications, refrigerants and other
industrial fluids, non-corrosive to brass
and steel.
DIMENSIONS (in)
PART NO SIZE CONN A B C D WT(lb)
116003 3/8 ODS 2.94 .41 2.06 .31 .53
116004 1/2 ODS 2.94 .14 2.06 .38 .51
116005 5/8 ODS 2.94 .14 2.06 .50 .48
116007 7/8 ODS 3.88 .63 2.94 .88 2.04
DIMENSIONS (in)
PART NO SIZE CONN A B C D WT(lb)
205-7/8 7/8 4.25 .97 3.16 .75 2.73
205-1-1/8 1-1/8 4.88 1.14 3.88 .94 4.41
205-1-3/8 1-3/8 5.38 1.25 4.25 1.00 6.04
205-1-5/8 1-5/8 6.50 1.50 5.06 1.13 9.32
205-2-1/8 2-1/8 8.50 2.00 5.88 1.50 17.10
205-2-5/8 2-5/8 11.00 2.25 6.88 1.69 27.43
393
CHECK VALVES
HENRY TECHNOLOGIES CHECK VALVES (Straight Through Design)
BRASS BODY — TYPE 119
• Brass Construction with Synthetic Rubber Seat
• Complete Piston Guidance
• Stainless Steel Spring
• Operates in Any Position
• Temperature Rating –20° F to +200° F
• Maximum Working Pressure 500 PSI
CHECK VALVES
DIMENSIONS (in)
PART NO SIZE CONN A B C WT(lb)
119-1/4 1/4 FL 2.26 — .81 .22
119-3/8 3/8 FL 2.51 — .81 .26
DIMENSIONS (in)
PART NO SIZE CONN A B C WT(lb)
120-3/8 3/8 ODS 5.25 .31 .81 .28
120-1/2 1/2 ODS 6.34 .38 1.25 .57
120-5/8 5/8 ODS 6.28 .50 1.25 .64
120-7/8 7/8 ODS 6.44 .75 1.50 1.06
DIMENSIONS (in)
PART NO SIZE CONN Center to Bottom Center to Side Center to Height
215-7/8 7/8 ODS 1-1/2 1-3/4 3-3/16
215-1-1/8 1-1/8 ODS 1-3/4 2-3/16 3-7/16
215-1-3/8 1-3/8 ODS 1-15/16 2-7/16 4-3/8
215-1-5/8 1-5/8 ODS 2-5/32 2-3/4 5-1/16
394
PACKLESS VALVES
HENRY TECHNOLOGIES PACKLESS VALVES — Standard Type
• Forged Brass Cored Body and Bonnet • Backseating Lower Stem
• Recommended for Vacuum Applications and Service • Diaphragms are Changeable Under Line Pressure
Pressures up to 500 PSI • Temperature Rating–20° F to +275 F
• Non-Directional Flow
PACKLESS VALVES
6267N 7/8 ODS 4.88 .75 5.38 2.50 3.25
6268N 1-1/8 ODS 6.00 1.00 6.50 3.25 5.50
395
RECEIVER VALVES
HENRY TECHNOLOGIES RECEIVER VALVES — Packed, Angle Type
• Temperature Rating: –20° F to +300° F
7792-B 1/2 MPT 1/2 FL 4.88 1.28 1.69 .38 1/2 .62
7793-B 1/2 MPT 5/8 FL 4.88 1.53 1.69 .38 1/2 .69
*Furnished with 1/4-in. flare capped charging and testing connection above back-seat.
396
SEAL CAP VALVES
HENRY TECHNOLOGIES SEAL CAP VALVES — Backseating Design
• Forged Brass Body with Integral Mounting Flange, Plated Steel Stem; Brass Bonnet and Molded Valox Seal Cap.
• Backseating: Can Be Repacked Under Pressure.
• Temperature Rating: –20° F (–29° C) to +300° F (+149° C)
• Maximum Working Pressure: 500 PSI, (35 Kg/cm2)
• Recommended for Hot Gas Service or Other High Temperature Applications.
DIMENSIONS (in)
PART NO SIZE CONN A B C D E F WT(lb)
9261 1/4 ODS 2.69 .66 4.35 .31 1.63 .28 .79
9263 3/8 ODS 3.00 .66 4.35 .38 1.63 .28 .81
9264 1/2 ODS 3.19 .66 4.35 .44 1.63 .28 .80
9265 5/8 ODS 3.19 .66 4.35 .52 1.63 .28 .79
DIMENSIONS (in)
PART NO SIZE CONN A B C D WT(lb)
2030-AA 7/8 ODS 4.25 .97 5.62 .75 3.00
2030-BA 1-1/8 ODS 4.88 1.14 5.88 .94 4.68
2031 1-3/8 ODS 5.38 1.25 8.75 1.00 7.35
2032 1-5/8 ODS 6.50 1.50 9.94 1.13 10.40
2033 2-1/8 ODS 8.50 2.00 10.63 1.50 16.69
2034 2-5/8 ODS 11.00 2.25 11.94 1.69 28.12
2035 3-1/8 ODS 12.00 2.63 13.25 1.75 44.00
397
VALVES
HENRY TECHNOLOGIES THREE-WAY DUAL SHUT-OFF VALVES
• Bodies: 92 Series: Forged Brass; 802 Series: Forged Steel; Painted.
2
• Maximum Working Pressure: 450 PSIG (31.5 Kg/Cm )
• Temperature Rating: –20° F (–29° C) to +300° F (+149° C)
• Recommended for Use with Relief Valve Types.
• 802A Series is Suitable for Refrigerants Including Ammonia and
Other Industrial Fluids Non-Corrosive to Steel.
398
PRESSURE RELIEF VALVES
HENRY TECHNOLOGIES PRESSURE RELIEF VALVES — Atmospheric, Angle & Straight-Thru
Types
Features
• Brass Construction Set and Sealed at the Factory; All NPTF • Bodies: 5600 Series, Ductile Iron; 5300 Series, Stainless
Connections are American Standard Dryseal Tapered Pipe Threads Steel; 5200 Series, Brass
• Valves are Stamped with Catalog Number, Size, Pressure • Cap: Steel
Setting, Capacity and ASME-UV National Board Symbol; • Seat inserts, seat discs and main guides, piston
CRN Number and Flow Arrow Stainless steel
• All NPTF Connections are American Standard Dryseal • Seat material: Teflon® or Neoprene where “N”
Tapered Pipe Threads • Connections: (NPTF) pipe threaded
• Positive Pressure Relief • Other component metal parts are steel
• Consistent operation at marked pressure setting • Set and sealed at the factory and furnished with
• These relief valves are designed with HENRY’s new nameplates stamped with catalog no., size, pressure
“ Center Leading Pivot” concept allowing the piston to reseat setting, capacity and ASME-UV National Board symbol
squarely to the body seat, thus reducing the possibilities of • Temperature rating: -20°F (-28°C) to +275°F (+135°C)
leakage • Protective lacquer finish
• Suitable for Refrigerants 12, 22, 500, 502, 12, 134a, and • Suitable for ammonia, HFC’s and CFC’s, refrigerants and
Other Industrial Fluids Non-Corrosive to Brass, Monel, other industrial fluids non-corrosive to steel and Teflon as
Steel and Teflon indicated
• Factory set and sealed • Each valve has unique serialization for tagging
• Temperature Rating: –40° F requirements
(–40° C) to +225° F (+107° C)
• Orders Must Specify Catalog Relief Valves in the types and sizes shown are constructed
Number, Pressure Setting, in accordance with the requirements of the ASME. These
and Type of Refrigerant or Fluid valves are also approved by many local refrigeration and
With Which the Valve is to air conditioning codes in the USA and Canada for relief of
be Used; UV/NB Certified Setting excess pressure. In addition, these valves are stamped
Range 150-450 PSI. with ASME- UV symbol and NB to indicate National Board
Contact Henry for Non-Certified certification of capacities between 150 P.S.I. and 450 P.S.I.
Setting Range Information. Whenever conditions permit, it is advisable to have the
relief valve pressure setting (which must not exceed the
Selection of Relief Valves. Most states and municipalities which design working pressure of the vessel) at least 25 percent
have refrigeration safety codes conform to the “American Standard higher than the normal maximum operating pressure for the
Safety Code for Mechanical Refrigeration (ANSI/ASHRAE 15).” This refrigerant used.
code provides for a relief valve setting not to exceed the design
working pressure of the vessel on which the relief valve is installed.
The discharge capacity required is based on the size of the vessel
and the refrigerant used. The discharge capacity of relief valves
varies with the pressure setting. The capacities of Henry Relief
Valves at various pressure settings are shown on Data Sheet No.
399
PRESSURE RELIEF VALVES
HENRY TECHNOLOGIES PRESSURE RELIEF VALVES — Atmospheric, Angle & Straight-Thru
Types
400
PRESSURE RELIEF VALVES
HENRY TECHNOLOGIES PRESSURE RELIEF VALVES — Atmospheric, Angle & Straight-Thru
Types
Atmospheric Relief Valves
PART Connection Size Dimension (in) Orifice Dia. Weight
NO Inlet Outlet A B C (in) Lbs.
5221N 1/4” NPT Male - - -
2.5 0.188 .033
5223N 3/8” NPT Male - - -
Straight Through Relief Valves
PART Connection Size Dimension (in) Orifice Dia. Weight
NO Inlet Outlet A B C (in) Lbs.
5230 1/4” NPT Male 3.16 - - .038
3/8” Flare
5231 - - .039
3/8” NPT Male
5231AN 1/2” Flare 3.28 - - 0.25 .041
5231BN 3.58 - -
3/8” NPT Male 5/8” Flare
5232 3.94 - - 0.44 .085
5240N1/2 1/2” NPT Male - - .095
3/4” NPT Female 3.74 0.312
5242N3/4 3/4” NPT Male - - 1.03
5244N1 1” NPT Male 1” NPT Female - - 0.375 1.46
4.16
5244-1 1” NPT Male 1” NPT Female - - 0.5 1.46
5246N1 1” NPT Male 1-1/4” NPT Female 5.7 - - 0.531 2.5
5340N1/2 1/2” NPT Male - - 0.95
3/4” NPT Female 3.74 0.312
5342N3/4 3/4” NPT Male 1.03
5344-1 1” NPT Male 1” NPT Female 4.16 - - 0.5 1.46
Angeled Relief Valves
PART Connection Size Dimension (in) Orifice Dia. Weight
NO Inlet Outlet A B C (in) Lbs.
526E 3/8” NPT Male 3/8” Flare 2.96 1.41 - 0.25 .06
527E 1/2” NPT Male 5/8” Flare 3.81 1.72 - 0.44 1.25
5600
1/2” NPT Female 3/4” NPT Female
5600N
5601
1/2” NPT Female 4.97 2.69 1.63 3
5601N
5602 1” NPT Female .05
3/4” NPT Female
5602N
5603 1/2” NPT Female 1/4” NPT Female 5.53 2.88 2.00 4.75
5604 1-1/4” NPT Female 1-1/2” NPT Female 7.38 4.13 2.31 .07 6.50
401
RUPTURE DISC ASSEMBLIES
HENRY TECHNOLOGIES RUPTURE DISC
Size Conn.
ASSEMBLIES PART A B Dimensions in Inches Orifice Wt.
NO Inlet Outlet C Lbs.
D E F
5525 3/8 3/8 2.55 0.77 1.25 AF 0.38 0.61
5526 1/2 1/2 2.85 0.89 1.25 AF 0.50 0.44
5626 1/2 1/2 2.86 0.90 1.13 0.50 0.44
5627 3/4 3/4 3.19 1.13 1.50 0.75 0.76
5628 1 1 3.67 1.25 1.75 1.00 1.24
5629 1 1/4 1 1/4 3.75 1.31 2.00 AF 1.312 1.6
402
RUPTURE ASSEMBLY PRESSURE SWITCHES/INDICATORS
HENRY TECHNOLOGIES RUPTURE ASSEMBLY PRESSURE SWITCH
NOTE: Relief valve, pressure gauge and pipe plug not included with “Sentry”
Rupture Disc Assembly.
PART SIZE
NO CONNECTION
G15 1/8-in. MPT, Back
403
RUPTURE ASSEMBLY PRESSURE SWITCHES/INDICATORS
HENRY TECHNOLOGIES TRANSDUCER VALVE
RUPTURE ASSEMBLY PRESSURE SWITCHES/INDICATORS
• ForgedBrass
• Temperature Rating: –20° F (–29° C) to +300° F (+149° C)
• Maximum Working Pressure: 500 PSI (35 kg/cm2)
• Connector: 1/4-in. Flare Access with Schrader Core
• Provides Access to Systems and Mounting of a Transducer to
Monitor Systems Performance
• Provides Schrader Valve Port for Checking Transducer
Output with a Pressure Gauge
• Provides Isolation from System for Replacement of Transducer
• Suitable for Refrigerants and Other Industrial Fluids
Non-Corrosive to Brass and Steel
404