PV H1Z2Z2-K                                                   ETP-63
Construction Products Regulation (EU) No 305/2011                                Ed. 11/2022 Rev. 2
                                                Electric cables for photovoltaic systems
DESCRIPTION
Cables manufactured with cross linked elastomer insulation and outer sheath. Suitable for photovoltaic installations.
Construction is according to EN 50618 / IEC 62930
APLICATIONS
Indoor, outdoor, industrial, agricultural, fixed or mobile photovoltaic solar installations with trackers. It can be installed in trays, ducts
and equipment. Suitable for direct burial. Suitable for use with class II equipment.
CONSTRUCTION
1 ‐ Conductor:                                    Tinned copper, flexible class 5                             a/EN 60228
n2 ‐ Insulation:                                  Cross linked compound, type Z2                              a/EN 50618
3 – Outer sheath:                                 Cross linked compound, type Z2                              a/EN 50618
                                                  ∙ Exterior colour: red, black or blue
TECHNICAL SPECIFICATIONS
Rated voltage:                                     1.000/1.000 V ac o 1.500/1.500 V dc
Max voltage:                                       1.200/1.200 V ac o 1.800/1.800 V dc
Test voltage:                                     6.500 V ac
Operating temperature:                            ‐40 to +120 ºC
Maximum short‐circuit temperature:                250 ºC (max. 5 s)
Bending radius:                                   5Ø
Water resistance:                                 AD7                                                         a/IEC 60364‐3
Contamination resistance:                         AF3                                                         a/IEC 60364‐3
UV and ozone resistance:                          Complies                                                    a/EN 50618
Service life:                                     20.000 h at 120 ºC operating temperature                    a/IEC 60216
                                                  25 years at 90 ºC operating temperature
FIRE BEHAVIOUR SPECIFICATIONS
CPR classification (class):                       Dca‐s2, d2, a1                                              a/EN 50575
          TEST                                            STANDARDS                            VALUES
          Flame retardant                                 EN 60332‐1‐2, IEC 60332‐1‐2          O.K.
          Low Smoke emission:                             EN 61034‐2, IEC 61034‐2              O.K., transmittance > 60%
          Halogen free (HCl)                              EN 60754‐1, IEC 60754‐1              < 0,5, O.K.
          Determination of degree of acidity of gases     EN 60754‐2, IEC 60754‐2              pH ≥ 4,3 / Conductivity ≤ 10 µS/mm
                                                                                                                        page 1 of 2
                                                              PV H1Z2Z2-K                                                              ETP-63
                                          Construction Products Regulation (EU) No 305/2011                                         Ed. 11/2022 Rev. 2
                                            Electric cables for photovoltaic systems
DATA AND DIMENSIONS
Dimensions and weights are approximate, subject to small variations due to the process. Other sizes are possible on request.
                       Cross Section          Insulation         Outer sheath               Outer Ø             Weight
                           mm²              thickness, mm       thickness, mm                mm                 Kg/km
                           1x2,5                 0,7                     0,8                  5,0                 43
                            1x4                  0,7                     0,8                  5,6                 59
                            1x6                  0,7                     0,8                  6,4                 81
                           1x10                  0,7                     0,8                  7,1                 123
                           1x16                  0,7                     0,9                  8,7                 192
Current carrying capacities have been calculated for the installations conditions provided for in the standard, for other installation
conditions must be used appropriated correction factors.
                              Conductor          Insulation resistance                      Current carrying capacities
         Cross Section                                  MΩ∙km                          A (T. air 60 ºC – T. conductor 120 ºC)
                              resistance
                                                                               Single cable free    Single cable on a    Two cables on a
             mm²            Ω/km at 20 ºC       at 20 ºC       at 90 ºC                                  surface            surface
                                                                                     in air
             1x2,5                 8,21          > 690          > 0,69               41                    39                  33
              1x4                  5,09          > 580          > 0,58               55                    52                  44
              1x6                  3,39          > 500          > 0,50               70                    67                  57
             1x10                  1,95          > 420          > 0,42               98                    93                  79
             1x16                  1,24          > 340          > 0,34               132                  125                 107