Sys. No.: TFA-01 Qty.: 1 Nos.

40 MPT Casing Construction Detail:


Drain Casing Panels 43 mm thick Double Skin Panels with PUF Panel Inner Skin : 0.8 mm Thick Pre Coated G.I.
having density 38±2 kg/m3 Panel Outer Skin : 0.8 mm Thick Pre Coated G.I.
N P P
T T
Panel Colour Pebble Gray (Reference - RAL 7032) Skid : 75 x 40 mm - 2 mm thick G.I. Fabricated
R.H.S Unit Structure Extruded Aluminum Hollow Profile
With Thermal Break & Internal Coving
Dampers Opposed blade type Low leakage Aerofoil
Design with concealed gears
Coil (Heat Exchanger):
Coil Type Fin & Tube Type Coil For Direct Expansion Application
DX Coil Header Liquid Line - _ _ _ _ , Suction Line - _ _ _ _ & Refrigerant - _ _ _ _
Drain Pan S.S. 304 with 19 mm thick close cell Nitrile rubber Insulation
Cooling Capacity 62.0 TR (At Specified Condition) Coil Tubes : 9.52 mm Dia, 0.3 mm wall
DX Coil Size & Depth 1016 x 1829 (40"H x 72"L) - 8 RD thickness Plain Copper
DX Circuit details - - - TR x - - - No. Circuit Coil Fins : 0.13 thick, Smooth Finish Corrugated
- - - TR x - - - No. Circuit Aluminum, Fin Spacing: (11 to 12 FPI)
Face Area 1.86 Sq. Mt. (20.00 Sq. Ft.) Velocity : 2.54 M/S (Max. Permissible)
Coil Base, Blank Off, Casing, Hardware Material Details :- GI

DX Coil
Air Flow Qty.:

2311
Fan Air qty. 17000 CMH (10000 CFM) Fresh Air qty. 17000 CMH (10000 CFM)
Supply Air qty. 17000 CMH (10000 CFM) Dehum. Air qty. 17000 CMH (10000 CFM)
Fan:
Type Plug Fan (Non Spark Proof)
Fan Model BNC-Q630/DI (I)
Designed Static Pr. 65 mm of WC
Designed Speed 1360 RPM
Shaft Power 4.60 BKW
Drive Motor:
Type 415 V, 3 Ph. TEFC, Sq. Cage, Foot Mounted, Induction Motor
Rating 5.5 KW - 4 Pole (IE-2 - Non FLP)
Air Filter:
Pre Filter G-3 + G-4 : Combination
Size - Qty. & Type 610 x 610 x 100 - 6 No. Flange Type
610 x 305 x 100 - 2 No. Flange Type
Velocity : 2.03 M/S (Max. Permissible)
L.H.S Filter Holding Frame Gl
Standard Accessories:
Access Door Cable Openble Bulk head (Non FLP) Provided In fan section
500x750 Entry Panel Limit Switch (Non FLP) Provided for fan section
PLAN Inspection Glass Provided on fan section
Pressure Mea. Port Provided across filters & fan
AVM Rubber Pad Provided Below TFA
Cable Entry Provided for fan section
S.A. Cutout
With Damper Bulk Spring Isolator Provided below fan and motor
510(H)x1250(L) Head Make Details:
P Pre Fan Make Kruger / Nicotra / Greenheck / Equi.
Filter Motor Make Hindustan / CG / Equi.
Insp. Filter Make AAF / Equi.
Glass Unit Dispatch Condition : SKD

T T
1356
1431

P P

PH01&5.7 - 036 -reknuP

AHU Panel
AHU Drain
Size as per Drawing
Openable Drain Cover Drain Pan
Jali Type

Fan Static x 2
75
300

RCC Block
U-Trap Detail For Drain Connection (Blow Through Type CSU)
(By Client)

Consultant
300 Client M/s. Freeze India - Rajkot
1343 693 Project M/s. RIL New Guesthouse, Jamnagar
CITIZEN INDUSTRIES PVT. LTD. DRN. BHAVESH S
2036 a member of DAIKIN group
1002-1003, 10th Floor, A-Wing, Commerce House-5, CHD.
ELEVATION Citizen Beside Vodafone House, Corporate Road, Prahladnagar,
a member of DAIKIN group Off S.G.Highway, Ahmedabad-380051 APPD.
Notes :- Floor Mounted Treated Fresh Air Unit
(1) Dimensional tolerance ± 5 mm.
DATE 01.11.2023
(2) RCC Block not in citizen scope. Legends
Temperature
Development Plan (GAD) SCALE SHEET NO. MAT. REV. NO. 00
(3) Air flow to be measured with Anemometer across air path before coil or filter face. T
Sensing Port Doc. No. : CIL/DND/FR-01
(4) Pressure to be measured across fan with appropriate manometer. P Pressure
Rev. No. : 00 1:1 1 OF 1 --- UNIT NO./
(5) In case of plug fans it is mandatory to run the fans using VFD. Sensing Port 689/02-23
(Supply of VFD is not in M/s. Citizen scope)
Cable
Entry Port Rev. No. Comments Issue Date : 01/03/2012 All Dimension are in MM DRG NO.