ONYXWorks® Fire Systems Command Interface
General
ONYXWorks® is the next generation in life safety management for
centralized monitoring and control of the fire alarm system. The
intuitive, graphical display allows personnel to rapidly pinpoint,
investigate, and respond to alarm events with minimal operator
training. Versatile enough for single-site, multi-site and even
worldwide applications, the ONYXWorks graphical workstation
allows end-users to manage their NOTIFIER life safety system over
a proprietary network or Ethernet. Through its intelligent gateway
architecture, ONYXWorks can easily meet the needs of expanding
systems. ONYXWorks is also an ideal retrofit solution, supporting
seamless integration with competitive panels. Additionally,
ONYXWorks provides mass notification capabilities through IP-
based voice paging.
Features
                                                                     SYSTEM SETUP
OVERVIEW
                                                                      • Graphic Editing mode allows on-site or off-site system setup.
  • Operates on Microsoft® Windows® 10 (64 bit, Enterprise)
                                                                      • Import building floor plan CAD drawings (as a .DXF, .WMF,
  • Monitor options: 24” and 43” Standard and Touchscreen
                                                                        .JPG, or .GIF).
  • Supports up to 200 intelligent gateways, with 200 nodes per
                                                                      • Customizable device icon and colors to visually represent
    gateway
                                                                        each event type.
  • Maximum Remote Users: 50
                                                                      • AutoPlace feature automatically places devices in their proper
  • Point Capacity: 250,000                                             location (.DXF's).
  • History File Capacity: 2.5 Million Records                        • User defined icons can be globally defined (.PNG, .WMF, .JPG,
  • Supports the following additional languages: Spanish, French,       and .GIF formats).
    Korean, Portuguese, Hebrew, and Chinese (Traditional and
    Simplified)                                                      SECURE ACCESS
  • Compatible with standard, high-speed NOTI•FIRE•NET™, and          • System Administrator-definable user profiles provide strict
    Ethernet-based networks                                             levels of access.
  • NOTI•FIRE•NET gateway redundancy for network survivability        • Monitoring and Control profiles delineate defined operator
                                                                        accounts.
USER INTERFACE                                                        • Operator Login/Logout/Change Password feature allows only
  • Customizable interface provides flexibility to display              authorized personnel to access the system.
    information as desired.                                           • Logs in history of any operator changes in the workstation.
  • Supports dual monitors.
  • Dynamically generated floor plan overview provides point of      OPERATIONS
    reference when using the zoom function.                           • Macros provide customizable programming to simplify
  • Global Zoom Level for devices (0 – 100%), definable by the          repetitive tasks (disable/enable, deactivate/activate).
    administrator.                                                    • Individual device control and system information through icon
  • Device information, including point address and description,        right-click function.
    can be quickly accessed through icon left-click function.         • History Manager: Filterable history reporting serves as a
  • Navigational tree, icons and configurable areas provide easy        valuable maintenance and diagnostic tool to identify patterns.
    access to system floor plans.                                     • Test Monitoring function enables unobtrusive testing of
                                                                        selected points, eliminating nuisance alarms at the
EVENT NOTIFICATION AND RESPONSE
                                                                        workstation.
  • Graphic and text display of all off-normal events.
                                                                      • Firefighter’s Graphical Smoke Control function available
  • Six states can be visually represented for each input device:       separately. (with NFS2-3030 panel only)
    Normal, Trouble, Fire Alarm, Pre-Alarm (detectors), Disabled,
    and Security.                                                    SYSTEM MAINTENANCE
  • Automatic screen navigation (configurable) to the device in       • Backup capability for screen, member, and history databases.
    alarm, based on event priority.                                   • Obtain software version numbers for network panels (ONYX®
  • Multimedia (text, audio, video and bitmaps) can be linked to        Series fire panels).
    any device, providing instructions to operators for event         • Upload/Download databases to NOTIFIER ONYX series
    response.                                                           panels and perform panel upgrades (ONYX Series only) over
  • Operator log with response tracking.                                the network using VeriFire Tools.
  • Text/E-mail notification for off-normal events.
  • Voice-Over-IP paging for mass notification.
                                                                                                       DN-7048:S • 11/15/2023 — Page 1 of 4
NOTI•FIRE•NET Monitoring
An ONYXWorks system is an ideal component of a Fire Command Center for real-time fire system status and system control options.
ONYXWorks interfaces directly to a NOTI•FIRE•NET fire system using an NFN Gateway. The NFN Gateway is an intelligent interface used
by an ONYXWorks system that facilitates monitoring and control of a NOTI•FIRE•NET (version 5.0) network and NOTIFIER fire panels. The
NFN Gateway is available in two versions: PC-based gateway and embedded gateway (see NFN Gateway data sheet DN-7060). The
embedded NFN Gateway enables users to monitor multiple sites (local or remote) over an IP network.
Minimum ONYXWorks equipment options/requirements are available on the NFN Gateway data sheet.
                                                      Local Monitoring
                                                                NOTI•FIRE•NET
                                                               Network version 5.0
                                                                  (standard or
                                                                  high-speed)
                                                                                                    Compatible ONYXWorks
                                                                                                   Fire Alarm Control Panels
                          ONYXWORKS
                                                                 Remote Monitoring
                                        Internet/
                                        Intranet*                             NOTI•FIRE•NET
                                                                             Network version 5.0
                                                                                (standard or
                                                                                high-speed)
          ONYXWORKS
                                                                                                                 Compatible ONYXWorks
                                                                                                                Fire Alarm Control Panels
                                                         NFN-GW-EM-3
* A UL listed Ethernet (TCP/IP) switch is required between a shared-IP network and the ONYXWorks equipment. Contemporary Control Systems, Inc. (www.ctrlink.com)
                                                             has several UL864 recognized switching hubs.
Building Systems Integration
In addition to NOTIFIER fire-only applications, the ONYXWorks Proprietary Supervising Station mode allows integration of competitive fire
panels and security panels into one graphical user interface. This mode allows for monitoring of local or remote (over shared IP or standard
phone lines) building systems using Digital Alarm Communicator Receiver (DACR-GW).
The flexible ONYXWorks system can interface to and monitor events received by BOSCH® D6100 Central Station receivers (contact ID
format only) by using the Receivers Gateway. See Receivers Gateway data sheet DN-7061.
                                                           Total Integration Monitoring
                                                                                                                                                   7061app1.png
                                                            DACR                 Phone Lines
                                                                                 Phone Lines                  DACT
                                                                                                                                       FACP
                         ONYXWORKS
                           ONYXWORKSwith
                            DACR-GW
                            DACR-GW
Page 2 of 4 — DN-7048:S • 11/15/2023
Specialized Client Applications
  • ONYXWorks Workstation
  • History Manager
              ONYXWorks
              Workstation
               Software
                                    7048map1-N17.jpg
               History
               Manager
                             7048his-N17.png
Specifications                                                       ELECTRICAL
DIMENSIONS*                                                          CPU Electrical: AC Input: (frequency 47 Hz – 63 Hz), 7.0 A @ 120
                                                                     V, 60Hz (95-132 V), 4.0 A @ 230 V, 60Hz (185-264 V).
CPU (desktop/rack mount unit): Width: 19.0" (48.3 cm). Depth:
                                                                     24” Monitors: Power Supply Input: 100 to 240 VAC to 12 V DC
17.7" (45 cm). Height: 7.0" (17.8 cm). Weight: 39 lbs. (17.7 kg).
                                                                     power brick. Power Consumption: 150 watts typical (maximum).
24” Monitor Dimensions*: Width: 23.5" (59.6 cm). Height: 14.4"       Current Rating: 11A (with audio).
(36.57 cm). Depth: 1.6" (10.16 cm). Weight: 22 lbs (9.97 kg).
                                                                     43” Standard Monitor: Voltage: 90-264 VAC, 50/60 Hz.
43" Monitors (Standard and Touchscreen): Width: 40.7" (103.38        Power Consumption: 200 watts (maximum). Current Rating: 1.5A
cm). Height: 25.2" (64.0 cm). Depth: 4" (10.16 cm); Weight: 41 lbs   @120 VAC (maximum).
(18.6 kg).
                                                                     43” Touchscreen Monitor: Voltage: 120 VAC, 50/60 Hz.
*DIMENSIONS NOTE: Dimensions/weights subject to change. Contact      Power Consumption: 235 watts (maximum). Current Rating: 2A
NOTIFIER for further information.                                    @120 VAC (maximum).
                                                                     ENVIRONMENTAL
                                                                     Operating Temperature: 0°C to 49°C (32°F to 120°F).
                                                                                                      DN-7048:S • 11/15/2023 — Page 3 of 4
Standards and Codes                                                                       ONYXWKS-HNMF: UL-Listed PC, ONYXWorks View+Ctrl+Paging
                                                                                          Software, HS Multi Mode Fiber PC Card. UL-Listed Monitor and Mic
ONYXWorks complies with the following UL Standards and NFPA 72
                                                                                          not included.
Fire Alarm Systems requirements:
                                                                                          SCS-ONYXWKS-HNW-2: UL-Listed PC, ONYXWorks View+Smoke
   •   UL 864 (Fire)
                                                                                          Ctrl Software, HS Wire PC Card. UL-Listed Monitor not included.
   •   UL 864 UUKL (Firefighter Smoke Control Station)
                                                                                          SCS-ONYXWORKS-HNSF:          UL-Listed  PC,     ONYXWorks
   •   UL 2017 (General Purpose Signaling)
                                                                                          View+Smoke Ctrl Software, HS Single Mode Fiber PC Card. UL-
   •   UL 2572 (Mass Notification)
                                                                                          Listed Monitor not included.
   •   UL 2610 (Burglary)
   •   CAN/ULC S527                                                                       SCS-ONYXWORKS-HNMF:          UL-Listed  PC,    ONYXWorks
                                                                                          View+Smoke Ctrl Software, HS Multi Mode Fiber PC Card. UL-
   •   CAN/ULC S559                                                                       Listed Monitor not included.
                                                                                          MON-24LCDW: UL-listed 24” widescreen HD LED color monitor
Listings and Approvals                                                                    with integrated speakers.
These listings and approvals apply to the modules specified in this
                                                                                          MON-24LCDW-TS: UL-listed 24” widescreen HD LED color
document. In some cases, certain modules or applications may not
                                                                                          touchscreen monitor with integrated speakers.
be listed by certain approval agencies, or listing may be in process.
Consult factory for latest listing status.                                                MON-43LCDW: UL-listed 43” widescreen HD LED color monitor
                                                                                          with integrated speakers.
   • UL/ULC Listed: S5526
   • CSFM:     7165-0028:0243   (NFS2-640/NFS-320),  7165-                                MON-43LCDW-TS: UL-listed 43” widescreen HD LED color
     0028:0224 (NFS2-3030)                                                                touchscreen monitor.
   • Fire Dept. of New York: COA#000688 (NFS2-640/NFS-320),                               NFN-GW-PC-F: NFN Gateway PC card with fiber.
     COA#000686 (NFS2-3030)                                                               NFN-GW-PC-W: NFN Gateway PC card with wire.
   • FM Approved                                                                          NFN-GW-EM-3: NFN Gateway, embedded.
                                                                                          NFN-GW-PC-HNSF: High-speed NFN Gateway PC card for single-
Ordering Information                                                                      mode fiber.
WARRANTY: The PC is warrantied for 3 years; monitors are
                                                                                          NFN-GW-PC-HNMF: High-speed NFN Gateway PC card for multi-
warranted from date of purchase for a period of 12 months. Please
                                                                                          mode fiber.
refer to the NOTIFIER Limited Warranty Policy for additional
information.                                                                              NFN-GW-PC-HNW-2:                      High-speed NFN Gateway PC card for wire.
ONYXWorks Workstation Components: ONYXWorks Workstation                                   NOTIFY-IP: UL-Listed Microphone, Audio Supervisor Board & Audio
Graphics User Interface (GUI) software and hardware package.                              Cables.
Includes UL-Listed rack mountable graphics PC with Intel® i7-
4700EQ, 2.4GHz, QM87, 4th Gen, (four cores/8 threads), 6 MB of
Cache, 16 GB of RAM, a 240 GB solid-state hard drive, sound,                              ONYXWorks View-Only Software. Non-listed software for monitor-
optical mouse, keyboard, Ethernet ports, and one GUI workstation                          only purposes. Requires an Embedded NFN Gateway. PC not
software license. One UL-listed monitor required per workstation;                         included. Minimum hardware requirements:
dual-monitor capable (monitors sold separately).                                               •     Laptop or desktop with Windows 10 operating system
ONYXWORKS-W: UL-Listed PC, ONYXWorks View+Ctrl+Paging                                          •     Intel i7 processor or higher
Software, Std Wire PC Card. UL-Listed Monitor and Mic not
                                                                                               •     16 GB RAM
included.
                                                                                               •     240 GB hard drive
ONYXWORKS-F: UL-Listed PC, ONYXWorks View+Ctrl+Paging
Software, Std Fiber PC Card. UL-Listed Monitor and Mic not                                     •     USB connection
included.                                                                                      •     TCP/IP Ethernet network adapter
ONYXWORKS-HNW-2: UL-Listed PC, ONYXWorks View+Ctrl+                                            •     Speakers
Paging Software, HS Wire PC Card. UL-Listed Monitor and Mic not                                •     Uninterruptible Power Supply (UPS) recommended.
included.
ONYXWKS-HNSF: UL-Listed PC, ONYXWorks View+Ctrl+Paging
Software, HS Single Mode Fiber PC Card. UL-Listed Monitor and
Mic not included.
                                                 This document is not intended to be used for installation purposes.
                                                 We try to keep our product information up-to-date and accurate.
                                                 We cannot cover all specific applications or anticipate all requirements.
                                                 All specifications are subject to change without notice.
                                                 NOTIFIER®, VeriFire®, and ONYXWorks® are registered trademarks and
                                                 NOTI•FIRE•NET™ is a trademark of Honeywell International Inc.
                                                 Microsoft® and Windows® are registered trademarks of Microsoft Corpora-
NOTIFIER                                         tion. Intel® is a registered trademark of Intel Corporation. BOSH® is a reg-
12 Clintonville Road                             istered trademark of Robert Bosch GMBH.
Northford, CT 06472                              ©2024 by Honeywell International Inc. All rights reserved. Unauthorized
                                                 use of this document is strictly prohibited.
203.484.7161
www.notifier.com                                 Country of Origin: USA