DN-60499:B
ONYXWorks® NFN
Embedded Gateway-3
                                                                                                         Network Systems
General
The NOTI•FIRE•NET™ Gateway is an intelligent gateway
interface for the ONYXWorks® fire monitoring workstation.
This gateway facilitates complete monitoring and control of a
NOTI•FIRE•NET™ network. In addition, it supports full panel
programming and network diagnostics.
The embedded gateway is a standalone version and is
equipped with IP capability thus enabling ONYX® Series users
to monitor multiple sites over an Ethernet network without the
need for remote workstations.
Features
• Enables ONYX® Series workstation to monitor alarm, pre-
  alarm, trouble, disabled events, etc. for NFN fire alarm
  control panels.
• ONYXWorks® supports up to 50 intelligent gateways.
                                                                                         NFN-GW-EM-3
• Compatible      with     standard      and     high     speed
  NOTI•FIRE•NET™ network.
                                                                  Standards and Codes
• Adds acknowledge, silence, reset, enable/disable, and
  activate/deactivate control capability to the workstation.      The NOTI•FIRE•NET™ Gateway complies with the following
• Supports fire alarm control panel programming upload/           UL/ULC Standards and NFPA 72 Fire Alarm Systems
  downloads and modifications.                                    requirements:
• Embedded gateway allows remote IP connections and                   – UL 864
  increases scalability of network.                                   – UL 1076
• Supervised IP connections for remote workstations and               – UL 2017
  gateways.                                                           – ULC S559-04
• Multiple workstations can access the gateway at the same            – ULC S527-99
  time.
• Gateway redundancy for network survivability.                   Listings and Approvals
                                                                  These listings and approvals apply to the modules specified in
Compatibility                                                     this document. In some cases, certain modules or applications
The NOTI•FIRE•NET™ Gateway is compatible with                     may not be listed by certain approval agencies, or listing may
ONYXWorks® and ONYX FirstVision and interfaces to                 be in process. Consult factory for latest listing status.
NOTI•FIRE•NET™ version 5.0 and higher, as well as a high
                                                                  •   UL / ULC: S5697
speed NOTI•FIRE•NET™ network for the following panels and
devices:                                                          •   FM Approved
•   ONYX Series                                                   •   CSFM: 7300-1525:103
•   AM2020/AFP1010 (version 5.0 SIB-NET)                          •   MEA: 286-07-E
•   AFP-200 (version 5.0 NAM)                                     •   FDNY: COA #6041
•   AFP-300/AFP-400 (version 5.0 NAM)
                                                                  Ordering Information
•   BACnet Gateway
•   NCA-2/NCA Network Control Annunciator                         NFN-GW-EM-3: NOTI•FIRE•NET™ Gateway, embedded.
                                                                  Includes PC board, NUP to NUP cable (75577), USB Cable
•   NOTI•FIRE•NET™Web Server                                      (75665) and NFN Configuration.
                                                                  Additional EMBEDDED         VERSION       Gateway      required
Specifications                                                    components:
•   Power input: 24 VDC                                           • NCM for connection to NOTI•FIRE•NET™.
•   Input current: 450 mA @ 24 VDC (without NCM).                 • HS-NCM for connection to high speed NOTI•FIRE•NET™.
•   Operating temperature: 0°C to 49°C (32°F to 120°F).           • IBM®-compatible PC with Windows® XP.
•   Direct connection to NFS2-640, NFS-640, NFS-320, NFS2-        • Standard Ethernet network cable with RJ45 to RJ45
    3030, and NFS-3030 fire alarm control panels. NCM               connectors.
    required for connection to NOTI•FIRE•NET™, and HS-NCM
    for connection to high-speed network. (See data sheets        • ONYXWorks Workstation V3.12 or above .
    DN-6861 and DN-60454.)                                        • NFN Network Version 5.0 or above.
                                                                  • Verifire Tools Version 5.71 or above.
                                                                                              DN-60499:B • 04/09/2010 — Page 1 of 2
 Remote Monitoring
                                                  NFN-GW-EM-3
                                                                                                                                                  7060ap2a.wmf
                                                                      or High Speed
                                                                     NOTI•FIRE•NET™
                                                                             High Speed
                                                                           NOTI•FIRE•NET™
                                                                                  or
                                                                           NION®, NOTIFIER®, ONYX® and ONYXWorks® are registered trademarks
                                                                           and NOTI•FIRE•NET™, NOTIFIY-IP™, and ONYX FirstVision™ are
                                                                           trademarks of Honeywell International Inc. Windows® is a registered
                                                                           trademark of Microsoft Corporation.
                                                                           ©2010 by Honeywell International Inc. All rights reserved. Unauthorized use
                                                                           of this document is strictly prohibited.
                                         This document is not intended to be used for installation purposes.
                                           We try to keep our product information up-to-date and accurate.
                                        We cannot cover all specific applications or anticipate all requirements.
                                               All specifications are subject to change without notice.
                                                                                                                                 Made in the U.S. A.
                                For more information, contact Notifier. Phone: (203) 484-7161, FAX: (203) 484-7118.
                                                                 www.notifier.com
Page 2 of 2 — DN-60499:B • 04/09/2010