LEDSIGN-GW Instant and Integrated Emergency Notification System
General
The OAX2-24V2 LED sign is a UL-listed display that integrates
seamlessly with NOTIFIER fire alarm control panels,
NOTI•FIRE•NET networks, and ONYXWorks®.
In the event of an emergency, the signs will automatically display
emergency messages along with optional color changes that
demand attention. These messages can be securely controlled from
the NOTIFIER fire alarm control panel (FACP) through encrypted
network protocols.
OAX2-24V2
NOTIFIER LED SIGN GATEWAY
The FeaturedProduct Sign Interface is a key part of an Emergency IP Requirements
Communications Response System (ECRS). The FeaturedProduct
monitors events on one or more NFN network(s) and generates An Internet or Intranet IP network connection is required. The Inter-
appropriate messages for up to ten OAX2-24V2 LED Displays. The net or Intranet IP network connection must meet the following
NFN networks communicate with the FeaturedProduct Sign Inter- requirements:
face through NFN Gateways over TCP/IP. Multiple sign gateways
can communicate on the same NFN network if more than 10 signs Parameter Requirements
are required.
Ethernet Network Private or Business LAN
Configuration
Features
TCP/IP Requirements Static IP address required
The FeaturedProduct:
• Controls up to 10 signs with message displays. Peer-to-Peer/Domain Support Peer-to-Peer
• Receives zone activations from up to 50 NFN Gateways. Ethernet Connection Standard 10/100Base-T
• Stores 100 messages per FeaturedProduct. Connection
• Contains predefined industry standard emergency messages that Bandwidth Requirements Minimal network traffic
can be edited.
• Transmits custom or default messages according to defined prior- DNS Support No
ities. Ports 22 (OAX2-24V2 sign)
• Enables a predefined “System Normal” message to be displayed
when there are no events. Encryption SSH (OAX2-24V2 sign)
• Overrides system-generated messages if it receives manually
activated messages from the ONYXWorks Workstation. ONYX- FeaturedProduct Architecture
Works is not a required component but does add additional capa-
bilities to the gateway. CAPABILITY
Compatible NFN Node Types and Parameter Requirements
Networked Panels Maximum number of NFN Gateways per sign 50
FeaturedProduct is compatible with NOTI•FIRE•NET and High- interface
Speed NOTI•FIRE•NET. An NFN gateway v3.16 (or later) must be Maximum number of sign gateways per NFN 25*
used to interface with the NFN or fire alarm control panel. gateway
Required Equipment Maximum number of signs per 10
FeaturedProduct
FeaturedProduct: UL-listed sign gateway. Interfaces with
NOTI•FIRE•NET networks. Maximum number of OAX2-24V2 signs 250
supported per NFN gateway
– Includes PNET-1 surge suppressor.
– Includes RJ45-RJ45 standard Ethernet network cable Time from event initiation to display on sign 8 seconds
(PN 75585, provides gateway’s TCP connection). (typical)
OAX2-24V2: UL-listed LED sign. Sold separately. Number of messages stored in 100
– Includes PNET-1 surge suppressor. FeaturedProduct
– Customer to supply RJ45-RJ45 standard Ethernet network Maximum number of logic equations 50
cable (provides PNET-1’s internet/intranet connection) and
standard Ethernet network cable (connects sign to gateway). * The NFN gateway supports up to 50 client connections. This number
includes workstations and other clients that get data from the gateway.
DN-60679:A4 • 02/04/19 — Page 1 of 2
SYSTEM ARCHITECTURE AND DATA FLOW
IP Browser
(For use during
FACP system setup &
NFN Network
or ONYX maintenance only)
FACP
NFN Gateway F I RE
OAX2-24V2 Sign #1
FACP F I RE
OAX2-24V2 Sign #2
IP Network
LEDSIGNGW-network.wmf
F I RE
OAX2-24V2 Sign #10
Up to 10 signs displaying
messages sent by
the sign interface.
Workstation
Sign Interface (Optional)
LEDSIGN-GW
System Specifications Compliance
OAX2-24V2 SPECIFICATIONS The products in this document have been investigated to, and found
to be in compliance with the following requirements from Underwrit-
LED Colors: Three colors (red, yellow, green). ers Laboratories, Underwriters Laboratories Canada, and National
LED Size (Diameter): 0.2” (5 mm). Fire Protection Association:
LED Spacing (Pitch): 0.3” (7.6 mm). • NFPA 72 National Fire Alarm Code.
Character Set: Block profile (sans serif), upper/lower case. LED Sign OAX2-24V2
Ethernet: TCP/IP connectivity. • UL 1638: Visual Signaling Appliances - Private Mode Emergency
and General Utility Signaling, 3rd Edition.
Power: 24V DC, 0.5A
• CSA C22.2 No. 205-M1983: Signal Equipment.
Mounting: Tilt Wall Mount Bracket, VESA 100mm included
ONYXWorks® Sign Gateway FeaturedProduct
Weight: 6 lbs.
• UL 864: Control Units for Fire Alarm Systems, 9th Edition.
Dimensions: 7"H x 36"W x 1.75"D • UL 1076: Proprietary Burglar Alarm Units and Systems.
FEATUREDPRODUCT SPECIFICATIONS • CAN/ULC-S527-99: Standard for Control Units for Fire Alarm
The FeaturedProduct requires +24VDC @400mA nominal and Systems, 2nd Edition.
supervised battery backup in accordance with local code require- • CAN/ULC-S559-04: Equipment for Fire Signal Receiving Centres
ments. and Systems, 1st Edition.
TEMPERATURE AND HUMIDITY RANGES Agency Listings and Approvals
This system meets NFPA requirements for operation at 0 – 49°C/32
– 120°F and at a relative humidity 93% ± 2% RH (noncondensing) The listings and approvals below apply to the basic product. In some
at 32°C ± 2°C (90°F ± 3°F). However, the useful life of the system's cases, certain peripherals may not be listed by certain approval
standby batteries and the electronic components may be adversely agencies, or listing may be in process. Consult factory for latest list-
affected by extreme temperature ranges and humidity. Therefore, it ing status.
is recommended that this system and its peripherals be installed in • UL/ULC: S25007 (OAX2-24V2), S5697 (FeaturedProduct).
an environment with a normal room temperature of 15 – 27°C/60 –
80°F.
This document is not intended to be used for installation purposes.
We try to keep our product information up-to-date and accurate.
We cannot cover all specific applications or anticipate all requirements.
All specifications are subject to change without notice.
NOTIFIER® and ONYXWorks are registered trademarks of Honeywell
NOTIFIER International Inc.
12 Clintonville Road
©2012 by Honeywell International Inc. All rights reserved. Unauthorized
Northford, CT 06472 use of this document is strictly prohibited.
203.484.7161
www.notifier.com Country of Origin: Mexico