Pc-Ee-681 Lab
Pc-Ee-681 Lab
ListofExperimentasperSyllabus
Sl.No. NameoftheExperiment
1 Designingaheatingelementwithspecifiedwattage,voltageandambienttemperature.
  2      Designinganair-coregroundingreactorwithspecifiedoperatingvoltage,nominalcurrent and
         faultcurrent.
3 Designingthepowerdistributionsystemforasmalltownship.
4 Designingadoublecircuittransmissionlineforagivenvoltagelevelandpower(MVA) transfer.
6 Designingofasubstation
7 DesigninganONANdistributiontransformer.
8 Designingathreephasesquirrelcageinductionmotor.
9 Designingathreephasewoundrotorinductionmotor.
 10      Designingasplitphasesquirrelcageinductionmotorforaceilingfanoradomesticpump.
 11      Designingapermanentmagnetfractionalhpservomotor.
                                          EXPERIMENT NO -1
    Designing a heating element with specified wattage, voltage and ambient
                                 temperature
INTRODUCTION:
            When current is passed through a conductor, it gets heated up due to I2R losses and this
heating characteristic of the electric current is being utilized in industrial and domestic appliances.
             Heating is required for domestic purposes such as cooking and heating of buildings whereas
for industrial purposes and heating is required for melting of metals , hardening and tempering and in
welding.
                       The main advantages of electric heating over other systems of heating (i.e coal, gas,
or oil) heating are:
    2. Cleanliness: Since dust and ash are completely eliminated in electric heatingsystem,
so it is clean system and cleaning costs are rendered to a minimum.
    3. Absence of fuel gases: Since no fuel gases are produced in this system,
the atmosphere around is clean and pollution free.
    4. Ease of control: Simple, accurate and reliable temperature of a furnace can be had
with the help of manual or automatic devices. Desired temperature can be had in electric
heating system which is not convenient in other heating systems.
    7. Better working conditions: Electric heating system produces no irritation noise and
also the radiation losses are low. Thus working with electric furnaces is convenient and cool.
Heating element:
The heating effect of electric current can be produced by passing electric current through Heating element
and the material used for heating element must have fallowing properties
    1. It should have high specific resistance so that a small length of wire (R =               ,p=      )
        is sufficient to produce the required amount of heat.
2. It should have high melting point so that high temperature can be obtained.
    3. It should have low temperature co-efficient since for accurate temperature control, the
       resistance should be nearly constant at all temperature and this is possible only if the
       resistance does not change with temperature.
    4. It should not oxidize at higher temperatures otherwise its life is shortened andneeds
       frequent replacement.
        The most commonly used heating elements are either alloy of nickel and chromium or nickel-
        chromium iron, nickel-chromium-aluminium, nickel-copper. The use of iron reduces the cost but
        lowers the life of the element.
            The heating element used for electric heating may be circular or rectangular like a ribbon but
ribbon type of element requires more wattage per unit area. Hence circular heating elements are preferred.
            By knowing the electrical input and its voltage the size and length of the heating element required
to produce given temperature can be calculated.
Causes of failure of heating element
            There are so many causes are there for the failure of heating element. Some of them are
explained below.
    1. Formation of Hot Spots: Hot spots are the points in heating element which are at
       higher temperature than the main body of the element. Hot spots may be due to any of
       the fallowing causes:
        (a) High rate of local oxidation may reduce the cross-section of the element wire
            thereby increasing the resistance at that spot. Thus more heat will be produced
            locally giving rise to the breakdown of the element.
        (b) Shielding of element by supports etc. will reduce the local heat loss by radiation
            and causes a rise of temperature of shielded portion of the element therefore
            minimum number of supports without producing distortion of the element should
            be used.
        (c) Due to too high element temperatures, insufficient support for the element or
           selection of wrong material, sagging and wrapping of element may result which
           may causes uneven spacing of sections there by producing hot spots.
    3. Embrittlement due to grain, growth: All heating alloys containing iron, tend to form
       large brittle grains at high temperatures. When cold the elements are very brittle and
       liable to rupture easily on slightest handling and jerks.
The heat from one body to another body can be transferred by any one of the fallowing methods.
               For example when one end of solid is heated, the molecules at that end absorb the heat energy
   and begin to vibrate rapidly when these molecules collide with neighboring molecules, some energy is
   passed them with in turn begin to vibrate faster and pass some energy to their molecules. Thus heat is
   transferred from one molecule to another molecule without their actual movement.
               If the heat is to be conducted from one object to another object, the fallowing conditions must be
   met.
               2. The temperature of the two bodies should be different i.e. temperature gradient
                  should exixt.
        Definition of conduction: The process in which heat is transferred from one particle to another in
direction of fall of temperature without the actual movement of particles of medium is called conduction.
       The rate of conduction of heat along a substance depends upon the temperature gradient and is
expressed in Mj/hr/m2/m/c0 or in watts/cm2 in case of electric heating.
       In a plate of thickness t meters having X-sectional area of its two parallel feces A sq.meters and
temperature of two faces is T1 and T2 absolute, the quantity of heat transferred through it during T hours is
given by
Q= (T1 – T2) T
2. Convection:
               Def: The process of heat transference in which heat is transferred from one place to another (from
    hotter to colder one) by actual movement of particles of medium is calles convection.
               For example in case of heater used for heating buildings, the air in contact with a heat radiator
    element in a room receives heat from contact with the element. The heated air expands and rises, cold air
    flowing into takes place. Thus there is a constant flow of air upwards across the heating elements. Thus in
    this way the room gets heated up.
          A similar action takes place in an electric water heater, a continuous floe of water passing
 upwards across the immersed heating element, with the result that the whole of the water in the tank
 becomes hot.
           The quantity of heat absorbed from the heater by convection depends mainlyupon the
 temperature of the heating element above the surroundings and upon the size of surface of the heater. It
 also depends partly on the portion of the heater.
3.        Radiation:
         Def: The process of transmission of heat in which heat energy is transferred from hotter body
to colder body without heating the medium in between is called radiation.
   Foe example we receive energy from the sun by radiation through there in distance of about 150
million Kms between sun and earth.
                                                 4
     dissipation           H = 5.72× 10 Ke                              –
                                    e – emissivity which is 1 for black body. And 0.9 for resistance heating
                                         elements.
Electric heating methods:
       Electric heating methods can be classified as:
Electric heating
    ARC HEATING:
                When a high voltage is applied across in air gap, the air in the gap gets ionized under
electrostatic forces and become conducting medium. Current flows in the form of a continuous spark called the
arc. A very high voltage is required to establish an arc across the air gap but to maintain an arc small voltage
should be sufficient.
              Alternatively an arc can also be produced by short circuiting the two electrodes momentarily and
then withdrawing them back. Arc between the two electrodes produces heat and has a temperature between
1000 0c and 3500 0c depending upon the material of electrodes used. The use of this principle may be in electric
arc furnace.
               Usually arc furnaces are of cylindrical shape but recently conical shaped shells have been used due
to the advantage of a large surface area per unit volume. Moreover the conical shaped furnace consumes less
power, radiation loss and melting time is also reduced.
               The arc chamber of the furnace consists of a suitable acid or basic refractory lining supported on
a metal frame. Each furnace is provided with charging door and tap hole for introducing the charge and taking
out the molten metal. The electrodes project through the top or sides of chamber and are arranged for easy
replacement and adjustment. The electrodes used in arc furnace are either made of carbon or graphite. Graphite
is mostly preferred however carbon electrodes are used with small furnaces.
             Types of furnaces:
     Arc furnaces may be classifies into two types.
     Since in direct arc furnace, the arc is in direct contact with the charge and heat is also produced by current
flowing through the charge itself, the can therefore be heated to highest temperature.
      In case of single phase arc furnace, two electrodes are taken vertically downward through the roof of
furnace to the surface of charge whereas in case of three phase arc furnace three electrodes put at the corners
of an equivalent triangle are used which produces three arcs, the charge itself thus forms a star point.
     The most common application of this type of furnace is for production of steel. This is advantageous
as compared to cupola method for production of steel due to the fallowing reasons.
     1. By using this method, purer product can be obtained as referring process can be easily
     controlled.
     2. Arc furnace can operate on 100% steel scrap which is cheaper than pig iron whereas
     cupola requires a proportion of pig iron in cupola charge.
This is the reason, direct arc furnace even being costlier in initial as well as operating costs is preferred.
        The temperature of the charge in the indirect-arc furnace is lower than in the direct-arc
 furnace, since heat is transmitted to it solely by radiation. As no current flows through the charge there is no
 inherent stirring action, and the furnace must be rocked mechanically; for this reason a cylindrical shape is
 adopted, with the electrodes projecting through the chamber at each end along the horizontal axis. This
 construction limits the number of electrodes to two and arc is produced by bringing the electrodes into solid
 contact and then with drawing them. Power input is regulated by adjusting the arc length by moving the
 electrodes.
       Due to the indirect heating, the furnace is suitable for comparatively lower melting point such as
 melting of non-ferrous metals. They are also used in iron foundries where intermittent supply of molten
 metal is required.
Resistance heating:
   Direct Resistance:
        In this method, current is passed through substance to be heated. The resistence offered by the substance
to flow of current produces ohmic losses I2R which results in heating the substance.
        In other words, the material to be heated is taken as resistance and current is passed through it. The
material may be in form of powder, pieces or a liquid. The electrodes in case of
d.c. or single phase a.c. or three electrodes in case of 3-phase a.c. are immerced in the charge and connected to
the supply. The current flows through the charge and heat is produced. This method has high efficiency since
heat is produced in charge itself.
        This method of heating is employed in resistance welding, in electrodes boiler for heating water and in
salt bath furnace.
                This type of furnace consists of a bath of same salt as sodium chloride and two electrodes
immersed in it. When the current is passed through the electrodes immersed in salt, heat developed and
temperature of salt may vary between 10000c -15000c depending upon type of salt used. In this Bath the material
to be heated is dipped and necessary heat treatment is given to it. As d.c. would cause electrolysis of salt,
therefore alternating current is used. In this method, it must be ensured that the current flows through the salt and
not through the job is used.
Since the voltage required is of order of 20V, therefore a tap changing transformer is used.
        D.c supply is not preferable as it results in electrolysis of water which in turn results in evolution of H2 at
negative electrode and oxygen at positive electrode. But passage of a.c. hardly results in evolution of gas, but
heats the water. Thus a.c. is recommended.
                In case of industrial heating where a large amount of charge is to be heated the heating element is
kept in cylindrical surrounded by the jacket containing the charge as shown
                This arrangement provides a uniform temperature control can be provided in this case by
presetting the time duration.
                This type of heating is used in room heater, immersion heaters, in bimetallic strips and various
types of resistance ovens used in domestic and commercial cooking.
                       In certain types of ovens, two electrodes project from the opposite walls of the oven and
a high current is passed through these electrodes. This type of ovens is used where high temperature is
desirable. The shape and size of the oven depend upon nature of the job.
                       Resistance ovens are used for various purposes such as heat treatment of metals, drying,
backing of pottery materials, cooking of food e.t.c.
                        The temperature of oven (I2Rt) can be controlled by controlling (i) voltage or current (ii)
time and (iii) resistance
               Voltage can be varied by using tapped transformer for supply to the oven or by using series
 resistance so that some voltage dropped across this series resistaor.
              The automatic control of temperature can be obtained by providing thermostat which will operate
 a switch to OFF or ON the circuit as soon as the temperature exceeds of fall below the adjusted value.
             In order to control the temperature by means of resistance various series and parallel
 combinations are used for single phase supply and different star-delta arrangements for three-phase supply.
               3. Flexibility.
               And this method of heating founds wide applications in
       Induction Heating:
                Induction heating is based on the principle of a.c. transformers. There is a primary winding
through which an a.c. current is passed which is magnetically coupled to the charge to be heated. When an a.c.
current is passed through primary heating coil, an electric current is induced in the charge and the value of the
induced current is dependent on
The heat develops depend upon the power drawn by the charge and since P = therefore
to develop heat sufficient to melt the charge the resistance should be low which is possible only with metals
and the voltage must be higher which is obtaining by employing higher flux since the higher the flux linked,
the higher is the voltage induced. Thus magnetic materials are found to be suitable for this type of heating
because of their higher permeability.
          In case of charge to be heated is non-magnetic, the heat generated is due to eddy current losses whereas
if it is a magnetic material there will be a hysteresis losses in addition. Eddy current loss is proportional to
frequency and hysteresis loss is proportional to square of frequency and these laws holds good upto a limited
temperature (curie point) since the magnetic materials lose their magnetic properties above curie temperature.
               The high frequency require for induction heating is obtained from motor generator set, spark
gap converter and vacuum tube oscillator.
             1. Magnitude of primary current Ip since if the primary current is high the flux is
       high and hence Is is high and thus heat developed ishigh.
      1. Current flows only on the outer surface of the metal and in doing so heats up the
 outer surface because if an alternating current is passed through a surface it tends to crowd at
 the outer surface(skin effect) because of large inductance at the centre.
      2. the current flow is restricted axially to that surface of the metal which is directly
 in plane with the primary coil and thus heat produced is restricted to that portion.
      3. As the heat is developed directly in side the metal which is to be heated, the the
 transfer of heat is very quick.
      4. There is no mechanical or chemical contact between the source of energy and the metal
 to be heated up. Thus no care is to be paid towards the connection.
     5. The temperature attained by this type of heating is extremely high since there is no
 medium as heat is produced in the metal itself.
Induction furnaces:
     1. As the magnetic coupling is between the primary and secondary is poor, since leakage
reactance is high and p.f. is low. To overcome this difficulty the furnace must be designed
foe a low frequency as low as 10Hz which can be achieved by using a frequency changer
which involves extra cost.
     3. If the current density exceeds 5 A/m2 , the pinch effect (formation of bubble) due to
electromagnetic forces may cause complete interruption of secondary circuit.
currents α B2 F2
       In a coreless furnace there is no core and thus flux density will be low. Hence for compensating the
low flux density, the primary current applied to the primary should have sufficiently high frequency. Thus
by applying current of high frequency the core of induction furnace can be eliminated there by reducing its
weight and increasing the flexibility.
       The furnace consists of a ceramic crucible cylindrical in shape enclosed within a coil.
Which forms the primary of the transformer and the charge in the crucible, the secondary of the transformer?
The charge is put into the crucible and primary winding coil is connected to high frequency a.c supply. The
flux created by primary winding set up eddy currents in the charge which flow concentrically with those in the
primary winding. These eddy currents heat up the charge to its melting point and set up electromagnetic forces
producing stirring action which is essential for obtaining uniform quality of metal.
        Because of high frequency employed, which is necessary to induce the required voltage in the secondary,
the skin effect in the primary coil increases the effective resistance of the coil and hence copper losses tend to
high and artificial cooling is necessary. Thus the primary winding coils are since made of hallow copper
conductors through which cooling water can be circulated. Insulated supporting structure is employed for such
furnaces as the stray magnetic field due to the current in the primary coil may induce eddy currents in the metal
supporting structures there by leading to the over heating of strictures and reduction of efficiency.
       The choice of frequency of primary current can be ascertained by the fallowing penetration formula in
which the secondary current is assumed to be uniformly distributed over a cylindrical layer at the outside edge
of the crucible and having a thickness.
Advantages:
 2. Precise control of power into the charge can be employed and thus uniform quality of
product obtained is unattainable by any other method.
      1. These furnaces are used for production of steel and are also used for melting of non-
ferrous metals like brass, bronze, copper, aluminium, magnesium e.t.c.
       2. They are also used for specialized applications such as vacuum melting, duplexing
steel, heating of charges of non-conducting materials by use of conducting crucibles.
1. surface Hardening: The materials used for making parts such as spildle, saw blades,
gears, axles should be hard and tough to withstand the wear which possible with induction
heating since with induction heating it is possible to concentrate the heating effect to
desirableportion.
2. Deep hardening: With the help of induction heating, hardening of material to any depth is
possible and hence this type of heating is used for deep hardening of articles such as screw
driver, tools, drills e.t.c.
3. Tempering: In some mechanical process, the work pieces becomes more hard than required
and may need tempering to loose their hardness for tempering accurate control of heat is
required which is possible only with induction heating.
4. Smalting: Induction heating at high frequency is preferred for extraction of metal from ore
where the process is to be carried out in some protective atmosphere or vacuum.
5. Soldering; For soldering it is essential that required amount of heat is to developed at the
soldering point where as the remaining portion of the solder may remain cold which can be
achieved economically and efficiently by induction heating. With the help of induction it is
possible to melt various metals in suitable furnaces.
      Since the eddy current loss is proportional to the product of square of supply frequency and flux
density.
Therefore by controlling frequency and flux density, the amount of heat can be controlled.
  Induced eddy current is of greatest magnitude at the surface of material to be heated and its value decreases as
we go inside the material due to the skin effect.
   Since the depth of penetration of eddy currents into the charge is inversely proportional to supply frequency as
given by
   Therefore eddy current heating can be restricted to any depth of the material by judicious selection of
frequency of heating current. This frequency employed is in range of 10,000- 400,000 Hz.
  In case of magnetic material, in addition to eddy current loss, hysteresisloss also contribute of production of
heat.
Advantages:
2. Amount of heat wasted is less since heat is produced in the body to be heated up.
4. The can be made to penetrate into metal surface to any desired depth.
6. The amount of heat produced can be accurately controlled by suitable timing devices.
     7. With this type of heating, it is possible to heat many different objects of different
shapes and sizes with the same coil.
Disadvantages:
Applications:
      1. The high frequency eddy current heating is used for surface hardening in which the
desired depth of penetration of heat can be obtained by judicious selection of frequency
which reduces the cost, labour and time considerably.
      2. This method is employed in annealing of metals which saves a lot of time along with
the prevention of scales on metals obtained by conventional methods.
     3. Eddy current heating can be economically employed for soldering precisely for high
temperatures.
   4. This method of heating is also used for welding, drying of paints, melting ofprecious
metals, sterilization of surgical instruments and forgoing of bolt heads and river heads.
Dielectric Heating:
                When non-metallic metals i.e. insulators such as wood, plastic, china glass, ceramics e.t.c. are
subjected to high alternating voltage their temperature willincrease after some time. This increase in temperature
is due to the conversion of dielectric loss to heat. The material to be heated is placed as slab between the metallic
plates or electrodes connected to high frequency a.c. supply.
               Dielectric loss is depend upon the frequency and high voltage therefore for obtaining
adequate heating effect high voltage at about 20 Kv and frequency of about 10-30 MHz are usually
employed. High frequency is obtained from valve oscillator.
               The current drawn by the capacitor when connected to an a.c. supply voltage does not lead the
supply voltage by exactly 900 since it is not possible to get a pure capacitor and there is always some resistance
due to which heat is always produced in the dielectric material placed in between the two plates of capacitor.
The electric energy dissipated in the form of heat energy in dielectric material is known as dielectric loss.
Advantages:
Applications:
      The cost of the equipment required for dielectric heating is so high than it is employed where other
methods are impracticable and too slow. Some of the applications of this type of heating are:
       (i) synthetics: The raw materials called plastic performs used for synthetics are required
to be heated uniformly before putting them in hot moulds so that the whole mass becomes fluid
at a time, otherwise if the raw material is put directly in the moulds usually heated by steam the
outer surface of the perform will become hot and starts curing while inner surface does not reach
the fluid temperature there by resulting in unequal hardening of plastic.
      (ii) Diathermy: Dielectric heating is employed for heating tissues, and bones of
body required for the treatment of certain types of pains and diseases.
      (iv) Baking of foundary cores: Dielectric heating is more suitable foe baking foundary
cores where thermo setting binders are employed as they set instantaneously when brought to
polymerizing temperature.
      (v) Textile industry: In textile industry, dielectric heating is employed for drying
purpose.
       (vi) Food processing: The dielectric heating for food processing is one
of the most modern method and set fourth such processes which are outside.
(b) Cooking of sea foods such as oysters without removing the outer shell.
      1. The quantity of heat can be accurately controlled with the help of electric
clocks which are function of frequencies as they are run by synchronous motors.
2. The working atmosphere is free from flue gases, smoke and dirt.
3. The equipment used is compact and hence the space required is less.
      5. Operation of high frequency equipments is easy and does not required skilled
         labour.
Abstract:
Dry type air core reactors are devices which are used at both distribution and transmission
voltages for a variety of applications such as fault current limiting, power flow control,
reactive compensation (shunt reactors), and as the inductive part of tuned harmonic filters.
They may be relatively small devices weighing tens or hundreds of pounds with power
ratings less than 100 kvar, up to very large coils weighing as much as 100,000 lbs. or more,
and having power ratings in the range of 600 Mvar (60 Hz equivalent.)
Although they are well established and proven devices which have been widely used for many
years by electric utilities around the world, much confusion and misunderstanding still exists
in terms of how to properly make reliable electrical connections to air core reactors, how to
properly ground their supports and how to deal with the effects of their stray magnetic fields.
These issues arise as a consequence of the fact that air core reactors do not have a magnetic
core to constrain the magnetic field and as a result the magnetic field is “broadcast” in and
around the reactor. This broadcasted field or so called “stray field” induces eddy currents in
any metallic objects on which it impinges, hysteresis losses in ferromagnetic material, and
potentially large currents in closed loops such as can be formed by concrete reinforcements,
fencing, or improperly arranged support grounding connections. These eddy currents and
closed loop currents can give rise to severe heating problems on terminal connections,
concrete reinforcements and fencing under steady state conditions, and also to damaging
forces during short circuit.
This practical paper illustrates the basic nature of the magnetic field of air core reactors and
the theory behind the formation of eddy currents, closed loop currents and hysteresis losses.
Guidance is given on how to arrange the electrical connection, and the characteristics of
connectors to use, to minimize terminal heating and avoid damaging forces during short
circuit. The concepts of magnetic clearances are explained and alternative methods of
handling concrete reinforcement and fencing are illustrated along with the “Do’s and
Don’ts” of reactor support grounding.
Introduction:
   Dry type air core reactors are devices which are used at both distribution and
   transmission voltages in both AC and DC systems for a variety of applications such as
   fault current limiting, power flow control, reactive compensation (shunt reactors), DC
   Smoothing and Coupling reactors, and as the inductive part of tuned harmonic filters,
   among others. They may be relatively small devices weighing tens or hundreds of
   pounds with power ratings less than 100 kvar, up to very large coils weighing as much as
   100,000 lbs. or more, and having power ratings in the range of 600 Mvar (60 Hz
   equivalent.) Despite the wide range of applications and sizes, dry type air core reactors
   share a basic common structure (with numerous variations in construction details
   depending on ratings and application).
                                                1
                                                                                                 3
                                                                               4
                                               5
                                                        – winding
                                                        – spider
                                                        – terminal
                                               6
                                                        – glass fiber duct stick 5 – insulator
                                                        6 – mounting bracket
     Since air core reactors do not have a magnetic core to constrain the magnetic field, the
     magnetic field is “broadcast” in and around the reactor. The strength of this “broadcasted
     field” or more commonly referred to as “stray field” depends on the power rating of the
     reactor. In general, the higher the kvar rating of the reactor, the higher the strength of the
     stray field. This stray field impinges on both the reactor components themselves such as
     windings, spiders, corona electrodes and supports, but also adjacent parts such as
     terminals, connectors, connecting bus or cable, bus supports, and in general any adjacent
     electrically conductive material.
     Figure 2 illustrates the magnetic field distribution of a typical air core reactor, its
     magnitude is in milli Tesla [mT]. Note that the stray field of an air core reactor has
     rotational symmetry.
     As can be seen from the magnetic field lines (Plot d.)), in the mid-plane as well as on
     the rotational axis (Plot a.) and c.)), the field is directed in axial direction, whereas in all
     other locations the field has components in both the axial and radial direction. In vicinity
     of the winding ends of the reactor the magnetic field is predominantly directed in radial
     direction (Plot b.)).
The external magnetic field of a dry-type air-core reactor winding at a significant distance
from the winding may be approximated by the field of a current loop as shown in Figure 3.
This approximation holds for coils having a winding length shorter than about three times
the winding diameter. The field produced by a current carrying winding loop in a
distance r of more than around three times the loop diameter may be approximated
according to [5] by the equations (2) and (3). (For locations much closer to the reactor,
numerical techniques are required.)
                      2
   |𝐵| =   µ0.𝑛.𝐼.𝐷
                          ƒ(Θ)
                  3                                              ƒ(Θ) = √sin2(Θ)     cos2(Θ)
                                                                                        4          (3)
   (2)                                                           +
            8.𝑟
Using (2) and (3) in the lateral direction Θ = 0, f(Θ) = 0.5) the magnitude of the magnetic
flux density at moderate distances away from the reactor may be estimated by
                                                   2
                                 |𝐵| =   𝜋.𝑛.𝐼.𝐷
                                                       10−7 Tesla       (4)
                                         4.𝑟   3
As it can be seen from equation (4), the field strength quickly drops off with increasing
distance from the reactor; being inversely proportional to the cube of the distance.
In the case of air core reactors carrying alternating current, the stray magnetic field will
induce eddy currents and associated eddy current losses in any electrically conductive
parts which reside in the stray field, whether they be made of either ferromagnetic or
nonmagnetic material. Where the stray field links closed conducting loops; very large
closed loop currents may be induced, with associated steady state heating and potentially
large forces under short circuit conditions. Finally, where the stray field interacts with
current carrying conductors, such as buswork or cables; oscillatory vibration forces will be
induced under steady state conditions and correspondingly larger forces under short circuit
conditions.
Eddy Current Losses
In order to reach an estimation of the eddy losses in the structural elements of an air core
reactor such as spiders and the terminals as well as the connection bus work an approach
as described in [10] chapter 2 can be chosen.
The terminals and spiders are considered as a plate with thickness d (profile thickness)
with the assumption that the thickness is less than the so called “skin depth” or
“penetration depth”  and the field direction is parallel with the plane of the plate.
                                     2
                                                         (5)
where:
 penetration depth [m]
 2 f, f in [Hz]
 specific conductance
[S/m] µ permeability,
[H / m]
The skin depth in aluminum at 100°C ( = 23.1 MS/m) is 14.8mm at 50Hz and 13.5mm at 60Hz
                                   B2 3h
                              p          wher                  (6)
                                   6 2 e       d
                                       0
where                                               
:
p specific eddy losses [Watt / m]
B magnetic flux density [Tpeak] at the spider or terminal
location d thickness of profile [m]
h height of profile
[m] µ0 4 10-7 H/m
 specific conductance, [S/m]
 penetration depth [m]
   Faradays law of induction states that the EMF (electromotive force) induced in a
   closed loop is proportional to the negative of the time rate of change of the magnetic flux
   linked by the loop.
             𝐸𝑀𝐹
             𝑑ɸ
                 = −
                                           (7)
                        𝑑𝑡
In the case of a magnetic field 𝐵 the flux linking the loop is:
                                      ɸ = ∫𝐴
                                       𝐵∙               
                                       𝑑𝐴
   where 𝑑𝐴 = 𝑑𝐴. 𝑛 is a vector normal to the small surface 𝑑𝐴 and n is a unit vector
   normal to this surface.
   From equations (7) and (8) it is clear that the EMF will depend on the size of the loop and
   its orientation relative to the 𝐵 field direction; being thus proportional to the component of
   𝐵 which is normal to the plane of the loop and to the loop area.
   The loop current, I, which results from the induced EMF, will be in accordance with ohms
   law where the inductance and resistance of the loop are considered.
                                                 2       2
                                  𝑍𝑙𝑜𝑜𝑝 = √(𝑅𝑙𝑜𝑜𝑝 + X𝑙𝑜𝑜𝑝 )     (10)
   In order to analyze specific cases, the loop inductances and resistances must be
   calculated along with the linking flux and resulting EMF.
   Calculation of the flux linking a loop by formulas may be done only for simple
   geometries. More complex geometries typically require either purpose built software or
   finite element modelling.
  Short Circuit Forces
The Lorentz force law states that the force on a current carrying conductor in a time
varying magnetic field is:
𝐹⃗ = 𝐼 𝑙⃗𝑥𝐵̅⃗ (11)
                     Figure 5 – right hand rule
The direction of the force, in accordance with the well-known right hand rule, is such that it is
directed normal to the plane formed by the B-field vector and the current direction vector.
Another method for calculating the magnetic field forces is to determine the change in the
magnetic energy which is produced by an imaginary change in the configuration of the current
circuit [11]. If any dimension x of a current-carrying circuit is changed by a small distance dx,
magnetic field forces must be overcome (in addition to the elastic stresses). If we denote the
magnetic field force in the direction of x with Fx, a displacement of dx becomes a mechanical
work done.
Assuming the current I is held constant in this change, e.g. by providing a sufficiently high
resistance in the circuit, the total flux of the current circuit,
Φ=𝐿𝐼 (13)
This requires an electrical work for the current I during the time dt of
                                                      ∂𝐿
                              𝑑W2 =         𝐼 𝑑𝑡 = 𝐼2    𝑑𝑥              (16)
                                                    ∂𝑥
                                  𝑢𝐿
Finally, the energy accumulated in the magnetic field is increased
                         W𝑚 = 1 𝐿 𝐼2 𝑏𝑦 𝑑W𝑚 = 1 𝐼2                6𝐿
                                                                       𝑑𝑥       (17)
                                2                          2     6𝑥
Since the energy expended must equal the energy obtained, it follows
The force is therefore always directed to increase the inductance. It can be calculated if the
dependence of the inductance of the current circuit of x is known.
In the case of two different circuits 1 and 2, the forces occurring between the circuits can be
found by a similar consideration. The displacement dx of the two current circuits relative to
one another results in a change in the mutual inductance, by which, on the one hand, the
voltages induced in the two current circuits and on the other hand, the change in the field
energy. This follows the force acting in the direction
of the displacement and to bring the current loops into such a position that the mutual
inductance becomes as high as possible
                                         𝐹 = 𝐼 𝐼 ∂𝑀           (20)
                                           𝑥    12
                                                     ∂𝑥
Additional to the effects of the force to the current carrying structures it should also be noted
that this force has a vibrational nature (in the case of AC systems). Whereby the mechanical
frequency of this force is twice the excitation frequency (fmech=120Hz in case of a 60Hz AC
system). Thus also considerable noise emissions may be triggered due to the vibration of the
affected structures.
      The following points serve to summarize the basic installation clearance requirements
      associated with air core reactors.
      Electrical Clearance:
      As the normal air core reactor has exposed live parts at essentially all points on its outer
      surface, provision must be made for electrical clearance from the reactor surface to nearby
      grounded surfaces and to the surface of other reactors or other live parts in adjacent
      phases or circuits. Standard electrical substation clearances to live parts are perfectly
      adequate. No special precautions over and above normal substation practices are required.
      Ventilation Clearance:
      For a typical air core reactor which is mounted such that the cooling ducts are oriented in
      the vertical direction, adequate provision must be made for the unimpeded entrance and
      exit of cooling air at the bottom and the top of the cooling ducts respectively. In most
      cases, the ventilation clearance will be less than the magnetic clearance requirements and
      as such it is typically not a decisive factor in the installation arrangement (Refer to Figure
      6).
      Magnetic Clearances:
      The magnetic clearance requirements for air core reactors arise as a consequence of the
      interaction of their stray magnetic fields with conductive parts in the vicinity of the
      reactor and the resulting currents which may be induced in those parts. The induced
      currents are of two types and as such they give rise to two types of clearance requirements:
         Eddy Currents; which are induced in nearby conductive parts give rise to a minimum clearance
          required to metallic parts which do not form closed loops. These clearances are typically referred
          to as MC1 clearance (Refer to Figure 6).
         Circulating Currents; caused by the coil flux linking a closed electrically conducting loop.
Examples of such loops are those formed by concrete reinforcement rebar, nearby fencing, nearby
structural members in a building, inappropriately arranged grounding connections, or a
combination of the above. These clearances are typically referred to as MC2 Clearance (Refer to
Figure 6).
 MC2
The above MC1 and MC2 clearance guidelines are normally provided on manufacturer’s
outline drawings. The manufacturer will typically arrive at theses clearances based upon
the distance at which the field strength has decayed to internal manufacturer specified
values. In approximate terms, the MC2 clearances are generally about double the MC1
clearances and correspond roughly to a distance of a full diameter from the reactor surface,
above and below and to the side of the reactor. MC1 clearances typically then, are in the
range of one half of a diameter from the reactor surface (refer to Figure 6).
A second common misconception is the belief that these magnetic clearance guidelines
are “absolutes”; scientifically calculated values that if respected will lead 100% of the time
to a problem free installation, and if not respected, will always result in problems. This is
not so, in either respect. As hopefully has and will become clear in this paper, the issue of
magnetic clearances is about both the coil magnetic field (magnitude and direction in the
area of interest) as well as about the size, orientation, conductivity and magnetic
permeability of the part or loop which may interact with the
   magnetic field. To perfectly summarize all of this in a very simple and generic “two
   number practical clearance distance” (MC1, MC2) on a drawing is impossible, as although
   the magnetic field of the reactor can be very accurately calculated by the manufacturer, the
   other half of the equation - the very important details of the nearby metallic parts and/or
   loops; usually are not known by the reactor designer. This leads to two important
   conclusions:
      First, the magnetic clearance guidelines (MC1 and MC2) shown on manufacturer’s drawings are
       to a significant extent based on manufacturer’s experience, extensive testing, and on “what
       historically works”. They are intended to provide conservative figures that will lead to problem
       free installations in most, if not all, circumstances. That said, for very good reasons, there is
       guidance in the standards that also recommends, particularly in new installations, to simply avoid
       closed loop formation wherever possible (see Annex E, Section E.4 of reference [1]).
      The converse of the above is also true, also as outlined in the same standard. In many instances
       magnetic clearance distances which are significantly less than the standard MC1 and MC2 figures
       will still result in a satisfactory installation; however such cases should be referred to the
       manufacturer for analysis and advice based on the specific circumstances. Such analyses very
       often result in being able to fit air core reactors into existing installation locations where the
       initial MC1 and/or MC2 clearances on proposal drawings would suggest that they simply do not
       fit into the available space. Further examples are shown in reference [7].
   The admissible limits for the terminal temperature rise of reactors are given in Table 5 of
   IEEE C57.16-2011 “ IEEE Standard Requirements, Terminology, and Test Code for Dry-
   Type Air Core Series- Connected Reactors” Section 8.2.4. (The shunt reactor standard,
   IEEE C57.21-2008, also references this clause.) A similar table is included in the IEC
   reactor standard; IEC Std. 60076-6: 2007 "Power transformers – part 6: Reactors" Table
   1. [1][2][3]
To mitigate eddy current heating of the terminal and the connector it is important to have
geometries that are “streamlined” to the magnetic field, or in other words, which do not
provide a large frontal area to the magnetic field. This is achieved by providing terminals
with rectangular cross section of limited thickness (e.g. 3/8 in (10 mm)) normal to the
radial and axial field direction; like an extension of the spider arm. The required cross
sectional area of the terminal is provided by increasing its width in vertical direction. The
reasons for this are evident when the theory presented in section I.1 is considered (eddy
losses are strongly proportional to the dimension normal to the field direction) and noting
the strongly radial nature of the field in the terminal vicinity, as can be seen in Figure 2
and Figure 7 .
The same concept is applicable to the connector bolted to the terminal. The connector
should have large contact surface area, but should not present a large frontal area to the
radial or axial magnetic field and where multiple cables are involved, should not create a
flux linking loop between the parallel cables.
The factors influencing the eddy current heating of the terminal by the connector attached
to the terminal are demonstrated by a practical example of a high current / high Mvar
power, two coil stacked thyristor controlled shunt reactor (TCR):
The direction and magnitude of the field to which the terminal and the connector are
exposed is shown by the field plot in Figure 7. The flux density lines indicate the direction
of the magnetic field, and the colors, its magnitude in Tesla (rms value) for a current of
3160 A rms.
Figure 7 - Magnetic field plot (contour plot and field line plot) of terminal plus connector
                                     arrangement
As the figure shows, the field drops significantly with distance from the winding so that
the field strength at a distance of about 8 inches (200 mm) from the winding is reduced to
less than 50 % of the field in the immediate vicinity of the winding.
Referring to Figure 8, the connector flag is represented by a plate of 11.8 x 6.3 inches
(300 x 160 mm) (radial x vertical) which is firmly attached to the terminal. The contact
area between flag and terminal is 3.9 x 6.3 inch (100 x 160 mm) (radial x vertical). The
density of eddy currents induced in the connector flag are illustrated by the color scale.
(Note: through current is not considered). As can be seen in the figure, the eddy current
density is concentrated at the end of the flag which is closest to the winding.
Figure 8 - Eddy current density of a connector flag attached to the reactor terminal
Figure 9 shows both the through current I²R losses and the eddy losses of the connector
flag, depending on its thickness. The losses arising from contact resistance are disregarded.
Calculation of eddy losses is done by 3D FE methods.
The losses in the connector plate (and in the terminal) will increase when the terminal
and the attached connector are orientated in horizontal position, due to the increase in
losses contributed by the axial component of the field, while retaining similar losses
resulting from the radial field component.
          Figure 10 - Connector losses at in-plane vs. out-of-plane arrangement
Besides the general question of the type, size, and physical construction of connectors to
be used with air core reactors, another question which often arises relates to their various
possible physical arrangements. The following example, illustrated with actual
measurements of terminal temperature, shows again the same principle at work;
minimizing the frontal area of the connection arrangement presented normally to the
predominant direction of the magnetic field of the reactor and avoiding the creation of flux
linking loops.
The results in Table 1 are showing the measured terminal temperatures resulting from
arranging the connectors axially, one above the other on one side of the terminal, as
compared to arranging the same connectors on opposite sides of the terminal. Clearly the
axial arrangement on one side of the terminal is the better arrangement, with the “opposite
sides configuration” resulting in a 25% higher temperature rise. These results are
completely as one would expect when considering the frontal area the two different
arrangements present to the magnetic field of the reactor, as well as the formation of a
small flux linking loop by the “opposite sides configuration”; all as outlined in earlier
sections of this paper.
   Notes: Test Current: 4000 Amp, Cables: 2x1600 MCM each 6 feet in length, 4 hole terminal palm compression
The above example illustrates the issues resulting from a large frontal area to the field and
the formation of closed loops where cable connections are not arranged in an
appropriate manner. The same comments apply in the event of attempting to use bus
tube to make connection to air core reactors of significant power rating. Owing to the
large frontal area which bus tube presents to the field, it is generally problematic to
bring bus tube right up to the reactor terminal, and especially so if it is oriented
tangentially rather than radially to the reactor (refer also to the case study at the end of
this paper).
 The connector flag (as well as the terminal) should be arranged vertically.
 The height of the connector flag should preferably be the same as the height of the terminal and all
  holes of terminal should be used for bolting; use stainless steel bolts with Belleville spring
  washers on both sides.
 The thickness of the connector flag should not exceed approximately 1/2 inch or 12mm.
 The material of the connector may be either aluminum alloy or copper (in case of copper to
  aluminum, a bi-metal plate should be inserted). Nickel plating of the contact surface area may be
  considered, in order to allow higher terminal temperature (115°C instead of 90°C).
 The end of the customer connector flag may be configured as a crimped connection (Figure 14) or
  prepared for a welded connection as shown in Figure 15 or a clamped connector arrangement as
  shown in Figure 16. A minimum distance of this connection point of approximately 8 inches (or
  200 mm) from the winding surface is recommended in order that it be located in a reduced field
  area.
           Figure 14 - crimped                Figure 15 - welded              Figure 16 - clamped
       The connecting leads in the vicinity of the reactor shall be placed in a radial direction and
        perpendicular to coil vertical axis, to minimize the heating effect and the magnetic force.
       In cases where parallel cables are utilized they should be axially aligned in order to avoid the
        induction of closed loop currents between the cables by the axial magnetic field of the reactor.
        Refer to Figure 12.
       Connection leads should be provided with sufficient sag so as to provide adequate mechanical
        decoupling of the reactor terminals from connecting bus-work.
       For non-plated terminals and connectors, the contact areas must be abraded lightly by using 3M
        Scotch-Brite pads which have been saturated with contact grease (e.g. Penetrox-A). Guidance in
        this regard is also given in the Trench instruction manual.
   The purpose of this section is not to describe the guidelines for choosing cable ampacities
   in the substation. Rather, the focus here is on the last 10 feet or so of cable or bus-bar that
   makes the connection to the coil terminals. The desire is not only to have sufficient
   conductor cross section to handle the current, but also to have sufficient heat sink capacity
   from the connecting cable or bus-bar to aid in maintaining a cool terminal temperature.
   The connector geometry and configurations were addressed earlier. Here, we address
   strictly the ampacity selection of the cable or bus-bar connected to the reactor. For cable
   connections, in order to ensure adequate heat sinking of the terminal connection, the total
   cable ampacity (in MCM) connected to a coil terminal should be a minimum of twice the
   rated current in amperes. For a bus-bar connection, a current density of not greater than
   500 Amps/in2 (0.775 amps/mm2 should be used.
For a cable connection: Total Cable MCM = 2000A x 2 = 4000 MCM (2027 mm2)
   For a bus-bar connection: Total bus-bar cross sectional area = 2000 A / 500 A/in2 = 4 in2 (2580
   mm2)
III. 2) Circulating Currents in Horizontal Plane Closed loops Such as Foundation Reinforcement
   By necessity, concrete foundations and floors very often use steel rebar reinforcement to
   satisfy the mechanical loading demands of the foundation or floor. The rebar is typically
tied together with steel wire when assembling the rectangular rebar grid. This creates many
small rectangular short circuited loops which will experience circulating currents, losses
and short circuit current forces. The
   expansion and contraction of the rebar during load cycling of the reactor current can also
   cause cracks and degradation of the concrete.
   Solutions:
   (a) When the foundation or floor already exists, the coil must be installed at MC2 height above the
       foundation or floor to minimize the magnetic field effects.
   (b) If sufficient height is not available to allow satisfying the MC2 clearance, and also providing the
       power rating of the reactor is not too high, aluminum magnetic shields can be placed on the
       foundation or floor to keep the magnetic field from penetrating to the rebar. This shield will still
       have losses and forces on it but will save the foundation or floor integrity. Note: Such shielding
       measures should only be done in consultation with the reactor manufacturer.
   (c) If the foundation or floor is not yet constructed, applying short tubes of rubber hose at the rebar
       crossover points to isolate them (and also avoiding making electrical connection of the bars via
       the steel wires) will eliminate the closed loops. Alternatively, fiber glass reinforcing mesh can be
       used in lieu of steel rebar.
III. 3) Circulating Currents in Vertical Plane Closed loops Such as Fencing, Large Beams and Columns
   In view of the fact that the external surfaces of air core reactors are live parts, common
   practices to ensure personnel safety are to either fence the area around the reactors or to
   raise the reactors on support structures such that the height of the base of the insulators is
   a minimum of 8'6" (2600mm) above grade level. With either of these approaches, care
   must be taken in respect of both grounding and, for reactors of sizeable power rating, the
   formation of closed flux linking loops near to the coil.
   When traditional metallic fencing is arranged around air core reactors, there are
   multiple opportunities to create problematic loops:
      horizontal plane loops formed by the posts and the horizontal crossbars of the fence encircling the
       complete reactor arrangement.
      vertical plane loops in individual or multiple fence sections formed by the fence posts and
       connecting crossbar(s) or stringer mesh support wires at the top and bottom of the fence
      loops formed by a combination of the vertical plane of a fence section and closing of the loop by
       multiple connections to the ground grid.
   Loops created when adjacent sections of fence which are separately grounded become electrically
    connected and form a loop through the latch and lock of a closed gate
In most cases the main problems which arise from the presence of such flux linking loops are:
       The existence of points of high resistance or intermittent contact in the path of the loop
        current; giving rise to extreme local heating or arcing at the high resistance contact point (eg.
        latch and lock of a gate)
       inducing large currents, sometimes hundreds of amps, in the ground grid
The challenge in addressing these issues is to simultaneously avoid creating loops which
are problematic while at the same time satisfying the utility, NESC and IEEE guidelines in
terms of fence grounding, and step and touch potentials. [Refer to references 12 and 13].
Solutions:
First and foremost, whatever solution is employed, it must be ensured to be a safe one and
meet the intent and requirements of the NESC and IEEE 80.
Given the wide variation in situations and fence design specifics, only some general
pointers from the perspective of managing the reactor magnetic field are possible in this
paper. The user/station design engineer must ensure that the result is satisfactory from the
grounding perspective:
   involve the reactor manufacturer in the project at the earliest possible stage. The extent to which
    fence loops may be problematic is dependent on the specific reactor ratings and planned physical
    arrangement. (Note that reactors of moderate size may present little or no problem.) The
    manufacturer should be able to provide helpful guidance in specific cases.
   use double posts at one corner of the fence, thereby avoiding a large horizontal plane loop
   to ensure a safe installation in respect of step and touch potentials, fences are typically connected
    to ground at intervals ranging from 5 to 15m along the length of the fence. This can result in large
    vertical plane loops involving the ground grid. A possible solution to the involvement of the
    ground grid in such loops is to break the fence into multiple sections of suitable length using
    multiple posts, and then ground each section at only one location. In cases where it is also
    necessary to eliminate loops in the individual fence sections, these can be avoided by isolating the
    stringer wire or crossbar at a single point to break the loop. (Refer to Figure 19)
   the problem of the latch and lock of a gate being involved in a high current loop can be avoided in
    a few different ways; one of these is to provide a low resistance alternate path for the loop current
    through a suitably arranged electrically parallel copper conductor of significant ampacity
Figure 19 - Sectionalizing fencing to allow multiple ground connections
It should also be mentioned that there are very often cases where air core reactors are
raised on support structures to provide, for example, a minimum 8’6” (2600mm) clearance
to live parts, and the reactors are sometimes still fenced as well. In such instances,
especially where there are also long insulators, closed loops in fences which are located
well within MC2 in the lateral direction may not link significant flux due to the coil
elevation above grade level. In such situations, a brief consultation with the reactor
manufacturer may simplify the installation and reduce the necessary size of the fenced
area and/or the need to avoid vertical plane loops in the fence. In addition, in the case of
transmission voltage class air core reactors, the electrical strike distance requirements from
the live reactor surface to an adjacent fence will most often exceed the MC2 distance;
thereby making the electrical clearance the decisive clearance distance parameter.
In cases where air core reactors are located in the vicinity of interconnected columns and
beams, similar closed loop and eddy current issues arise as to those with fencing. In this
case however, the beams and columns are often made of structural steel. This exacerbates
the problem as the ferromagnetic nature of the material results in a tendency for portions
of the structure to concentrate the coil flux, leading to even more severe eddy current
heating problems at certain locations. Also as a result of the ferromagnetic material, the
closed loop currents and eddy currents will flow in a thin layer on the surface of the
material resulting in relatively higher resistance values and more severe heating under
most circumstances. Even greater problems may arise when sizeable reactors are placed
in the vicinity of building walls and ceilings which are constructed of metal cladding
which is bolted or riveted to the structural members. In these circumstances it is not
unusual to find that some of the bolted or riveted connections create high resistance
contact points in the path of closed loop currents; resulting in very severe local heating at
the high resistance contact points. The severity of such local heating can be sufficient to
cause bolted or riveted connections to glow red hot and even potentially lead to building
fires if there is combustible material in contact with the hot parts.
Solutions:
The situations described above are some of the most difficult magnetic clearance
problems to deal with, particularly with existing structures. The following techniques can
often provide solutions:
   involve the reactor manufacturer in the project at the earliest possible stage; a full or partial
    magnetic clearance analysis will usually provide valuable guidance (over and above the simple
    MC1 and MC2 distances) as to the specific issues with a planned installation, along with steps to
    take to avoid problems
   wherever possible, avoid the formation of flux linking loops
   as with fencing, take care to avoid the formation of loops involving the ground grid; which can be
    created by multiple point grounding of the structure
   avoid connecting metallic fences directly to metallic structures such as buildings by terminating
    the fence at a post which is located a few inches from the building
   observe the magnetic clearance guidelines
   with the support of the reactor manufacturer, in some circumstances problems can be solved
    through a magnetic clearance analysis and the judicious use of shielding techniques
III. 4) Circulating Currents in Elevating Support Stands
    Personnel protection can be achieved by using elevating support stands to keep live parts
    out of reach of substation personnel. This commonly is done instead of fencing within the
    station. Such elevating pedestals may be provided by the reactor supplier in the form of
    fiberglass pedestals or individual aluminum, steel, or stainless steel columns under each
    insulator. Often however, utilities construct lattice type structures, usually made of steel,
    which form closed loops under the coil. For small reactors, such loops may not present
    difficulties, but for larger Mvar coils they may well lead to problems.
Solutions:
       Steel parts can be isolated from each other to avoid closed loops by using isolated bolting
        techniques, however this is not simple, and always presents concerns about whether the isolated
        bolting will be correctly installed in the field
       Maintain at least MC2 distance to the support structure parts if they form closed loops
       For moderate size reactors; utilize a single post mounting pole with mounting arms extending
        radially outwards from the center to support the insulators, instead of a square frame structure.
        (Refer to Figure 20)
       Ground the bases of the structure at a single point only; using star point or daisy-chain connections.
        (Refer to Figure 21)
         Figure 20 - Single Post Mounting of Reactors Figure 21 - Daisy Chain and Star-Point single
         point
                                                                        grounding
IV) Case
       Study: Thyristor Controlled Shunt Reactors (TCR’s) with an
  Inappropriate Connection Arrangement:
  The subject SVC is comprised of three TC reactor banks: TCR1, TCR2 and TCR3. Each
  phase of the TCRs consists of two stacked coils (bottom and top coil) with porcelain
  insulators between the coils. Three such stacks form a 3-phase reactor bank.
The reactances per phase (at 60 Hz) and the rated currents and Mvar ratings of the
  The arrangement of the TC reactors of each bank, TCR1, TCR2 and TCR3 is illustrated in
  Figure 22 and Figure 23. All reactors are mounted as 2 coils stacked per phase, phases
This tangential alignment is in contrast to the recommendations outlined in this paper and
also as stated in the Trench reactor installation and operation manual [8], which requires
that the connection leads to be aligned in the radial direction to minimize heating effects
in the leads due to eddy currents.
As has been outlined in earlier parts of this paper, air core reactors produce a magnetic
field which fringes out from the winding ends. For reactors of significant MVAR rating,
such as those shown in this case study, the fringing fields are of substantial magnitude.
The radial component of this magnetic field which is directed perpendicular to the plane
of the tangential loop created by the cables of the connection leads between the reactor
terminal and the fastener (see Figs. 2, 3, 4, 4a) will, in this case, induce a current in the
loop which is significantly larger than the normal rated current flowing through the leads;
and thereby create an unacceptable terminal heating situation.
These results can be calculated, however for this specific case, it was decided to
construct a mock-up of the in-field situation to demonstrate the expected outcomes
experimentally and arrive at actual measured currents and temperatures.
            B                   I1
                     B
           B                      B
                                 BB
                                  B
                                  B
I2
Figure 27 - radial field linking tangentially arranged conductor loops and inducing a
circulating current (loop enlarged for illustration purposes)
A mock-up test arrangement was prepared. It consisted of very similar aluminum cables,
connector and fastener and a test coil which created a very similar magnetic field to the
on-site reactor. During the heat run test, the cable and terminal temperature-rise as well as
the induced closed loop current in the cables were measured.
The overall test arrangement was as shown in Figure 28 and Figure 29. The cable mock-
up was placed in the magnetic field of the test reactor in such a way that the magnetic flux
density in the reactor's radial direction was equivalent to the original setup at the SVC
site, having a value of 30.5 mT rms (the same as the on-site TCR1 at rated current). The
length of the mock-up loop was 1.5 m (4.9 feet), the center-center distance between
adjacent cables was 100 mm (3.9 inches). These critical parameters are virtually identical
to the on-site figures.
      Figure 28 - test setup with connector cables arranged tangentially to reactor surface
                                                                            thermocouples
As can be seen from the results above, the induced current in the cable loops was on the
order of 4500 Amps. As expected, the middle cable carried very little net induced current
due to the cancelling effect of the upper loop current and lower loop currents flowing in
opposing directions in the center cable. The temperatures in the upper and lower cables
were approximately 250 degrees C after allowing for a 25 degree C ambient. Clearly a
modified arrangement was necessary.
VI) Conclusion:
  For those who are unfamiliar with the peculiarities of air core reactors; applying them, and installing them
  can initially seem to be a confusing and difficult task. However, to a significant extent this is more a
  matter of familiarity than fundamental difficulty. With a basic understanding that results from applying
  simple electromagnetic concepts as are outlined in this paper, the principles become clear. With this
  understanding, it can be seen that applying reactors, making reliable connections, implementing
  appropriate grounding, and dealing with their stray magnetic fields are all relatively straight forward
  issues that can most often be easily solved. In the more complex cases, the reactor supplier should be able
  to provide support in finding a clear way forward.
                            EXPERIMENT NO – 3
           Designing the power distribution system for a small township
INTRODUCTION
        Electricity is the most convenient and useful form of energy. Without it the present social
infrastructure cannot be feasible. The increasing per capital consumption of electricity
throughout the world reflects a growing standard of living of people (Pablo, 2000) and the
optimum utilization by society of this form of energy can be ensured by effective supply and
distribution system. Distribution system differs from transmission system in several ways. Apart
from voltage magnitude, the number of branches and source is much higher in distribution
system and the general structure topology is different. Transmission is normality implied, the
bulk transfers of power by high voltage between main load centers. Distribution on the other
hand is mainly concerned with the conveyance of power of consumer by means of lower voltage
network.
       Due to expansion in the use of electricity, the demand on the distribution become greater
and more complex.Therefore, the distribution network are designed to be able to carry the load
imposed upon it without causing excessive heating in the consumers conductor and consequent
damages to the insulator. The voltage drop through the network must be kept to minimum so as
to maintain the voltage at the customer terminal within specified units (i.e 6% of the nominal
value) whatever the loading conditions [NKPA
electricity distribution manual 1977]. Electrical wiring is one of the major parts of building construction.
Electrical wiring is the connection of electrical accessories such as:sockets, lamp holder, distribution
boards, fuses or cutouts, ceiling rose, etc. with electrical wire or cable of the appropriate rating.
According to Electrical Engineering Portal (EEP), wires used in electrical wiring are normally coded
with colour codes for easy identification. In electrical wiring, current entered a circuit through the hot
(live) wire (usually red color) and returned along neutral wire (Uguru, and Obukoeroro, 2020). An
electrical circuit is a continuous loop, which carries electricity from the mains (e.g. distribution line),
throughout the house, then returns it back to the mains. Switches and other electrical appliances are
usually connected to a single electrical circuit (EEP, 2020). Electrical wiring are done by trained
professionals, but in some countries like Nigeria, due to lack of skill workforce, people with informal
education, commonly called “engineers” within the locality, are mainly employed to carry out the
electrical wiring of buildings. The utilization of substandard electrical materials or wrong connection of
the circuit is very dangerous, as it can lead to electrical fires or breakdown of the system. Electrical fires
are fires comprising the potential energization of electrical appliances and accessories.Electrical fires
are mainly caused by either over-loading of the circuit or short-circuiting the system (Fair, 2014). Safely
of human lives and materials in residential, administrative or commercial buildings is of high priority to
every country. Electrical fire has become a serious threat to the life and materials in residential and
commercial buildings (Madueme, 1997).
        The paper is aimed at designing an electrical distribution network for the newly completed 500
housing estate. Toward the development of the area, power demand is necessary. Consideration is given
to the future expansion of the area, also the maximum load demand of the Varian load centers and the
effective maximum demand (i.e the total maximum load demands required by the consumers) are
conserved for successful.
               Methodology
       This chapter deals with how the electrical distribution network for 500 housing unit was
designed, the distribution network was also designed to be overhead type which technically suit the
area.The type of line support and their accessories are also designed to the technical standard.
Distribution substation is also designed to receive energy from a higher voltage system, convert into a
form suitable for local distribution.
               LINE SUPPORTS
       For the purpose of this project, a steel reinforced concrete pole was designed, the poles were
designed to be 8.5m length for the low voltages and 10m length for the high voltage line.
       The span length for the low voltage lines was designed to be 40m while that of high voltage line
was designed to be 50m, this is to avoid the difficulties of terrains, urban development and natural
hazards.
       The reinforced concrete pole have the advantage of longer life, shattering tendency when hit by
vehicles and can be used in areas that have high humidity
               ACCESSORIES OF OVERHEAD LINES DESIGNED FOR THESE PROJECT
               ARE:
       i.      CROSS-ARM
              A hot dip galvanized cross - arms are designed for the project, the length of the cross
- arm should be 1.63m long and, the bolts and nuts of 5mc and 8mc respectively should be used.
               The hot dip galvanized has the following advantages:
       a.      It has longer life.
       b.      They cannot be attack by termites
       c.      They are stronger than the wood types.
       ii.   INSULATORS
        For the insulation of the distribution lines, use shall be made of porcelain insulators as specified
in B.S. 137.
        The Disc type insulator of approximately 254mm in diameter, 6.3kg In weight and mechanical
failing load of 10.6KN should be used for the high voltage lines.
       Also for the low - voltages a single groove type shackle insulator of 76mm in diameter, 0.4kg in
weight with a mechanical failing land of 19KIM should be used.
               iii.   CONDUCTORS
        Conductors used are aluminum conductors (AAC), conductors shall be 50mm 2 and 100mm2 in
size for the high voltage and the low voltage respectively. Base conductors shall be used in normal
conditions, conductors shall be hard-drawn aluminum twisted wires made of aluminum for electric
purposes. However, it major advantage is that it is cheaper than copper.
               Design of Electrical Installation for Buildings
The total load was used to determine the actual size of the transformer required for the area.
According to IEE Regulation A30 - 36, that the cables supplying lighting load need only be rated for
50% of the full load current.
        The diversity factor is taken into consideration due to the fact that the likely-hood of all the
domestic installation been ON at the same time is remote, hence it reduces imbalance in the lighting
loads. (George G. 1975).
               Finally, the diversity factors suggested in the I.E.E regulations A27 & A28 are:
       1.      Lighting circuit is 65%
       2.      13A socket outlet is 65%
       3.      15A socket outlet is 80%
       4.      Electric Cooker is 65%
               The breakdowns of the load demand are as follows:-
               The total lumens is given by
θ           = E x A/n x p                                                                   (1)
Where E = is the illumination in Im/m2
                           A = is the Area of working plane to be illuminated in m2
                           p = Maintenance factor n
                           = utilization factor.
Using the standard table of installation (T. G. Francis 5th edition).
               P           =          0.8 for bedrooms and living room. n
                           =          0.5 for bed rooms and living room.
               E     =                40lm/m2 for Bedrooms and living room. Lumen/watt for (4 x 4)m2 size
               = 10lm/w.
               Now, for Bedrooms;
       a)    Two Bedrooms Flat: There are 350 two bedroom flats, the load demand of single 2-
       bedroom was calculated and multiplied by 350 to give the total load demand of the flats.
       i.      For the bedroom with size (3.5 x 3.5)m2, the following standard were obtained using
               electrical installation IEE standard table (M. A. Laughton, 2003). As stated in (A) above.
                   P       =              0.7
                   n       =              0.5
                   E       =          40lm/m2
                               E ×A
               θ       =       n×p
                                          40×(3.5×3.5)       = 1400𝑙𝑚
                                      =     0.5×0.7
                            E ×A
       θ       =            n×p           40×(4.5×4.5)       = 2314𝑙𝑚
                                      =     0.5×0.8
       b)      One Bedroom Flat: there are 150 one bedroom flats, the load demand of single one
               bedroom was calculated and multiplied by 150 to give the total load demand of the all
               flats.
       i.      For the bedroom with size (3.5 x 3.5)m2, the total number of wattage required was the
               same with that of two bedroom, since they have same size, hence the same illumination
               was required.
       ii.     Therefore, two lamps of 60w each was designed.
       ii.     For the living room; with size (4.2 x 4.2)m2,            the following    data's   were
               extracted from the standard installation table.
               Lumen/watt = 17im/w, n = 0.5, E = 40lm/m2, P = 0.8, A
               = (4.2 x 4.2)m2.
               From:
                 E ×A
       θ       = n×p        40×(14.2×4.3)    = 1764𝑙𝑚
                        =      0.8×0.5
                                                                                               (KW)
                   Lightings                  15 x60           0.9            65                0,59
             PROTECTION REQUIREMENTS
       (i)     According to I.E.E Regulation A8-A10, every consumers installation supplied from a
               external source shall be adequately controlled by protection equipment accessible to
               consumer, the protection equipment should incorporate:
       i.      Means of Isolation
       ii.   Means of excess current protection.
        Circuit breakers was designed for the protection of excess current every conductor in the
installation is to be protected by a circuit breakers fitted at the origin of the circuit.
The current rating of the circuit breaker should not exceed the current rating of the lowest rated
conductor in the protected circuit.
       (ii)        Earthing: According to IEE Regulation D1, every conductor shall be prevented from
                   giving rise to earth leakage current by earthing of exposed metal parts. For this purpose
                   of this project, it was designed that all conductor are earth to ground using earth
                   electrode.
       3.0 Results and discussion
                   Based on the design of this project, the following results were obtained.
       Table 2:            Results for overhead line Design
        From table 2 above, it can be seen that concrete poles were designed for the project, wooden
poles are rather short in service life because they are inapplicable in place that have higher humidity and
liable to be affected by insects or animals. It can be concluded that concrete poles have advantage over
wooden poles.
       Although pin type insulators are also available but because of it low level of insulation, disc type
was used as specified by B.S 137.
        All aluminium conductors of 50mm2 were designed for the high voltage line while 100mm2 was
designed for the low voltage line. Aluminium was used because of it cheaperness and easy to machine
handle.
        Standard cross-arms shall have a size of either 1.63 or 2.24m. for places that require span length
size cross-arm will be used, but for the purpose of this project which the span length is not more 80m,
1.63 size was designed.
       Table 3: Maximum load demand for whole unit.
             6.                           Boreholes                                       180
             7.                          Street light                                     1.5
       The total load demand for each unit was calculated in table 1.6 above.
This load demand was added to have maximum load demand for the whole unit.
The transformers designed for the whole unit was obtained by considering this
maximum load demand of the area. It can be concluded that ten number of
500KVA transformers was designed for the purpose of this project.
       CONCLUSION
        The objective of the design is to provide electrical power supply to 500
housing units, because the optimum utilization by society of electrical energy
can be ensured by effective supply and distribution systems.Also, electricity is
the most convenient and useful from of energy, without it the present social
infrastructure cannot be feasible, hence there is a need to electrify the area.
         The designed network of the area can carry the load imposed upon it
without excessive heating in the conductor and consequently damages to the
insulation. The voltage at the consumer terminal is kept within the specified
limit (i.e 6% of the nominal value). (NEPA Manual, 1975)
        The system as designed can meet the load variations which are likely to
arise in near future and provide continuity of supply and should a fault occur on
the system, interruption in the supply to the consumers should last for a shortest
possible time.The system is very simple to maintain and operate and routine
maintenance should be carried out with minimum interruption to power supply.
        From the above results, it can be concluded that the system is quite
reliable. Since the reliability of any good designed system depends on efficient
control equipment such as circuit breakers, lighting arresters, fuses etc., hence it
becomes necessary to incorporate in this design to obtain reliable system. The
overhead lines distribution and the electrical installation designed for this
project will suite the area, because it is cheaper and easy to maintain.
                            EXPERIMENT NO – 4
Designing a double circuit transmission line for a given voltage level and power
                                (MVA) transfer.
 1.   INTRODUCTION
         Nowadays, power systems are extensively interconnected requiring the huge
 transfer of electric power. Considering that a typical transmission line with a certain
 voltage level, can only carry a limited capacity, to carry an enormous power it is required
 to construct extra high voltage (EHV) transmission lines [1]. Due to the vastness of Iran
 and energy demand increase, using 765kV EHV transmission lines can be a good choice to
 meet the needs.
         765 kV transmission lines have been established in some countries including South
 Korea, India and the United States of America [1, 2] and different standards are provided
 for these transmission lines by IEEE, BS and ANSI [3]. However, to make in parameters
 these standards with respect to Iran’s current conditions, such as for weather conditions,
 require the combination and analysis of international standards and national standards
 which are available for other voltage levels.
         In this paper, using IEEE and ANSI standards related to 765kV transmission lines,
 and 230kV and 400kV standards, electrical design of all parts of a 765kV transmission line
 is presented.
        Considering the issues related to high power transmission and corona phenomenon
in EHV lines the use of several conductors in a bundle is essential [4]. Studies on a variety
of existing 765kV transmission lines show that these lines are designed to transfer a power
of 4000 MVA (or even more), for which line current is calculated using Eq. (1).
           S
I                                                                                                               (1)
     3.V
       Where:
       S: Cross section of conductor (mm)
       ISC: Standard short circuit current (A)
       t: The persistence time of short circuit current (s)
       k: Constant coefficient related to the conductor material which is dependent to the
following parameters:
       w: Specific weight of the conductor (gr/cm3)
       C: Specific heat of conductor metal (Calory/g-oc)
       ∆ϴ : The conductor temperature rise (0c)
       : Specific resistance of the conductor (ohm.m/mm2).
        K value for ACSR conductors is 85, Isc value for 765kV line is 70kA, and the t is
0.5s. Inserting these values in Eq. (2), the required cross section is obtained to be 582.32
mm2 which is able to withstand short circuit level compared to the six-wire bundled Rail
conductor.
4.    DETERMINING THE APPROPRIATE DISTANCE FROM THE BUNDLE, GMD AND GMR
        The studied transmission line is a horizontal single-circuit line with six
        conductors per bundle.
According to the standards, maximum distance between conductors in bundled lines is
457mm.
        By studying various transmission lines, phase distance from the next phase is about
18m while this distance in lateral phases is about 36m [7].
        Then geometric mean radius (GMR) and the geometric mean distance (GMD) are
calculated using Eqs. (4) and (5) [8]:
        6
GMR  6D. d      5                                                                      (4)
GMD     D12  D13  D 23
         3
                                                                                        (5
                                                                                         )
             Where:
             GMR : Geometric mean
             radius (m) GMD: Geometric
             mean distance (m)
             d: Distance between the conductors in the bundle (m)
             D: Distance between the phases (m).
             Inserting d = 0.430 m and D = 18 m, GMR and GMD values are obtained as follows:
             GMD=22.678
             m
             GMR=0.371
             m
       By calculating the GMR and GMD, the inductance and the capacitance values of
transmission line are obtained using Eqs. (6) and (7).
                2 0
C                                                                               (6)
         ln( GMD GMR )
    2       7          GMD
L         10     ln
                       1 / 4                                                    (7)
                       e  GMR
          Where:
          C : The line capacitance (F/ m)
          ε0 : The dielectric coefficient of vacuum which is
          8.85*10-12 (F/m) GMD : Geometric mean distance (m)
          GMR : Geometric mean radius (m).
         By placing GMR and GMD values, inductance and capacitance values are obtained
         as follows:
L  0.8725     H
                   m
C  0.01351 nF
                   m
X L  2. f .L                                                                         (8)
B  2. f .C
                                                                                        (9
                                                                                         )
               
X L  0.274        km
                    6   1
B     4.24241 10
                          .km
       Rail conductors’ permitted current value is equal to 985A. Also, regarding the line
characteristic for which the transmitted power is considered about 5000 MW, it can be
claimed that the amount of current passing through each phase with respect to line voltage
765kV is 3770A. And given that there are six wires for each phase, therefore for each
bundled conductors’ current passing is 630A in steady state.
       As a result, Rail conductors can easily pass constant current through transmission
       line.
(
      C 2 )0.5
      C1                                                                                 (7
                                                                                          )
V     V           Sinh( .K )
kg
                 . Sinh( .n )                                                          (8)
      ng
        Where, C1 and C2 values given in [9] are the capacitance between the metal part and
earth, and insulator capacitance, respectively. Consequently, having the value of α,
distributed voltage in two ends of insulators is obtained. If the voltage distribution curve is
considered to be linear along insulators, in this case, C1/C2=12 and α=0.2887. In addition,
K, n, Vng and Vkg are insulator numbers we can calculate the voltage across it, the total
number of insulators, phase voltage of transmission line, and Kth insulator voltage,
respectively. Inserting all of these parameters in Eq. (8), the number of insulators is obtained
to be 35.
         Where:
         gmax: The maximum voltage gradient at the surface of
         conductors (kV/cm) V: Line phase voltage (KV)
         n: The number of bundled conductors
         per phase r: Radius of conductor (cm)
         C: Line capacitance (F/ km)
         GMR: Geometric mean radius of the bundled
         conductors (cm) Bs: Distance from the bundle
         conductors (cm).
         According to the Standard of Power Ministry [7], g max value should not exceed the
critical voltage gradient g0=15.9 kV/cm, which the performed calculations also are in the
desired range. However to limit the amount of voltage gradient in the surrounding insulator
strings and fittings, corona rings can be used [10].
gv  g         0.3
         .(1         )                                                                   (12)
0        
             .r
   298P
  T                                                   (13)
V C  gv .m..r.ln( GMD / r )                           (14)
       Where:
       gv : Critical voltage gradient (kV/cm)
       g0 : The threshold breakdown voltage
       (KV / cm) r : Radius of conductor (cm)
       δ : Relative
       density P : Air
       pressure (At.)
       T : Air temperature (K◦)
       m : Coefficient of conductor surface roughness
       GMD : Geometric mean distance between
       conductors (cm).
        Due to different climatic conditions existing in Iran, the temperature of 40 0C and
height of 1000m is considered which can be a good condition in summer in most parts of
the country. The value of m for ACSR conductors is 0.85. It is noteworthy that the values
of g0 and GMD are mentioned formerly.
        By inserting the mentioned parameters in Eqs. (12) to (14), the critical voltage is
        VC=267.843 kV.
V ph       441.686
                     1.65 p 1.8
VC         267.843
PC     0.00314.F.(          V
                       log( GMD / r ) )                                                 (15)
       Where:
       PC : Corona losses (kW / km)
       V : Effective-phase voltage (kV)
       GMD : Geometric mean distance between
       conductors (cm). r : Radius of conductor (cm)
       F: Constant coefficient and the critical voltage
       Studies show that when corona losses are low, the mentioned equation has no good
accuracy, and at this situation using Peterson method would has good accuracy as shown in
Eq. (16).                  r
                                  GMD
        0.545
                                                                                       (16)
 PC       
              (
                  V V C )    .
       In which;
       Pc: Corona losses (kW / km)
       V : Effective-phase voltage
       (kV) Vc : A critical voltage
       (KV)
       GMD : Geometric mean distance between
       conductors (cm). r : Radius of conductor (cm)
       Given that the amount of Vph/VC is less than 1.8, therefore, to calculate corona losses
Peterson equation is used as follows:
       Pc=1.44 kW/km
       Corona losses in a 1000km transmission line are almost 1.5MW/km which is a good
       value.
        After determining the corona ring dimensions, the height of the corona ring is also
examined along insulator strings. Finally, with the simulation software and changing the
height respect to the first insulator, it was determined that the height of 4cm above the first
insulator to corona rings that is placed along with insulators, and the second corona ring on
the connections of end clamp create the best position to decrease the voltage gradient [10,
12].
VR% 
         V s V r 100
            V                                                                             (17)
             r
Where:
VR%: Line voltage regulation
percentage Vs : Sending end
voltage (kV)
Vr : Receiving end voltage (kV)
Vr is the line rated voltage. And Vs is obtained in long transmission lines as follows:
V s   A B  V r
                                                                                        (18)
                
             C D
 I s        I r 
Where:
Is : The sending end current (A)
Ir : The receiving end current (A). Values of A, B, C and D are obtained from
Eq. (19) to (22).
                                                                                          (19)
A  cosh l 
                                                                                          (20)
B   Z c sinh l.
     1
C
     Z C sinh l                                                                        (21)
D  cosh l                                                                              (22)
          In
          which:
                                                      (23)
  z.y
     z
ZC  y                                                (24)
Where:
y: Parallel Admittance of transmission line (Ψ/ Km)
z: Series impedance of transmission line (Ω/ Km).
Inserting the parameters obtained from section three, voltage regulation percentage will be:
VR%= 0.042
        Given that the voltage changes from ±10% in line is allowed, the amount of voltage
regulation percentage is appropriate.
12. SIGNIFICANTLY REDUCING INSTALLATION PERMITTED DISTANCE AND COST OF TRANSMISSION LINES
        One of the most striking features of the transmission lines are the permitted
distance which is directly related to the cost of transmission lines installations [2].
Permitted distances requirements depend on several transmission line factors which are
considered during calculations. These factors include: electric and magnetic fields, and the
safety distance required for each voltage level, considering the distance required between
conductors in the line to prevent the effects of wind and storm, planning and future
development of lines due to the increase in consumer demand, and mechanical
considerations and considering the permitted distance between the line conductors to
prevent the occurrence of galloping in two circuits transmission line [5]. In most cases, the
allocation of extra line distances in designing and constructing the line leads to better
control of the line and thereby increase network reliability. However, it is impossible in
many cases due to lack of space, expensive lands, and/or a favorable ground for the
construction of this line. So the best solution to solve the permitted distance problem is the
use of high voltage lines, which in this case by replacing high voltage lines instead of low
voltage lines will lead to a significant reduction in the size and permitted distance.
        As it is depicted in Figs. (3) and (4), for construction of a 765 kV single circuit
transmission line with 6 conductors per phase about 200 feet permitted distance is required,
while for a 400kV two circuits transmission this value is about 150 feet. Thus, for
transmitting the equal electric power by 400 kV power transmission line, it is required to
have three 400 kV transmission lines of two circuits or six single-circuit transmission line.
In this case, the permitted distance is increased 450 feet (2.5 times) for two-circuit line and
900 feet (4.5 times) for single-circuit line. Also, as it can be seen from Figs. (3) and (4), by
the voltage reduction the problem of permitted distance is resolved. Given the importance
of construction of high voltage lines, it is clear that this will result in lower costs [13, 4].
Figure 3. Comparison between 345kV and 765 kV permitted distance with equal
transmission capacity
  Figure 4. Comparison between 132kV and 765 kV permitted distance with equal transmission capacity
14. CONCLUSION
        Given the growing need for electrical energy, appropriate measures are essential to overcome the
problems of electric power transmission lines, reducing permitted distances, increasing network reliability from
the view point of less outage, power loss reduction especially corona losses, communication disturbances
reduction and many other issues. In this paper, the importance of increasing voltage of transmission lines and
the benefits that resolve many of the problems are studied, and finally, a single circuit 765kV transmission line
with six conductors per phase were compared with lower voltage levels transmission lines and the results were
analyzed.