Product: 9843

RS485, 3 Pr #24 Str TC, PE Ins, OS+TC Brd, PVC Jkt, CM

Product Description
RS-485, 3 Pair 24AWG (7x32) Tinned Copper, PE Insulation, Overall Beldfoil®+Tinned Copper Braid(90%) Shield, PVC Outer Jacket, CM

Technical Specifications

Product Overview

RS-485, POS; Computer communications; Low Voltage Analog Signals (4-20ma, 0-10v, ...); Low Voltage Digital Control (24v, …); Line Level Audio; Panel Wiring; serial communication
Suitable Applications:
(RS-485 standard) comprising of PLCs, VFDs, HMIs, motors, RTU, SCADA, etc. within noisy environments over long distance, etc.

Construction Details

Conductor

Element No. of Elements Size Stranding Material

Pair(s) 3 24 AWG 7x32 TC - Tinned Copper

Insulation

Element Material Nom. Thickness Nom. Insulation Diameter Color Code

Pair(s) PE - Polyethylene 0.022 in (0.56 mm) 0.068 in (1.7 mm) White/Blue Stripe & Blue/White Stripe, White/Orange Stripe & Orange/White Stripe, White/Green Stripe & Green/White Stripe

Outer Shield

Shield Type Material Coverage Drainwire Type

Tape Bi-Laminate (Alum+Poly) 100% 24 AWG (7x32) TC

Braid Tinned Copper (TC) 90%

Outer Jacket

Material Nom. Thickness Nom. Diameter

PVC - Polyvinyl Chloride 0.035 in (0.89 mm) 0.360 in (9.14 mm)

Overall Cable Diameter 0.360 in (9.14 mm)


(Nominal):

Electrical Characteristics

Electricals

Nom. Conductor Nom. Capacitance Nom. Capacitance Cond-to-Other (Conds + Nom. Characteristic Nom. Velocity of
Element Max. Current
DCR Cond-to-Cond Shield) Impedence Prop.

1.54 Amps per Conductor at


Pair(s) 24 Ohm/1000ft 12.8 pF/ft (42.0 pF/m) 23 pF/ft 120 Ohm 66%
25ºC

Nom. Outer Shield DCR: 2.3 Ohm/1000ft (7.5 Ohm/km)

High Frequency (Nominal/Typical)

Element Frequency [MHz] Nom. Insertion Loss (Attenuation)

Pair(s) 1 0.6 dB/100ft

Voltage

UL Voltage Rating

300 V (CM), 30 V (UL AWM 2919)

Mechanical Characteristics
Temperature

UL Temperature Operating

80°C -30°C to +80°C

Bend Radius

Stationary Min. Installation Min.

3.75 in (95.3 mm) 3.75 in (95.3 mm)

Max. Pull Tension: 105.5 lbs (47.85 kg)

Bulk Cable Weight: 62 lbs/1000ft

Standards and Compliance

Environmental Suitability: Indoor

Flammability / Reaction UL 1685 UL Loading, IEC 60332-1-2


to Fire:

CPR Compliance: CPR Euroclass: Eca; CPR UKCA Class: Eca

NEC / UL Compliance: Article 800, CM

AWM Compliance: AWM 2919

CEC / C(UL) CM
Compliance:

European Directive EU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)
Compliance:

UK Regulation UKCA Mark


Compliance:

APAC Compliance: China RoHS II (GB/T 26572-2011)

History

Update and Revision: Revision Number: 0.576 Revision Date: 04-30-2024

Part Numbers

Variants

Item # Color Putup Type Length UPC/EAN Footnote

9843 0101000 Black Reel 1,000 ft 612825495604

9843 060100 Chrome Reel 100 ft 612825259589

9843.00305 Chrome Reel 305 m 8719605023339

9843 060500 Chrome Reel 500 ft 612825259602 C

9843 0601000 Chrome Reel 1,000 ft 612825259596 C

9843 0605000 Chrome Reel 5,000 ft 612825259619 C

© 2024 Belden, Inc


All Rights Reserved.
Although Belden makes every reasonable effort to ensure their accuracy at the time of this publication, information and specifications described here in are subject to error or omission and to change without
notice, and the listing of such information and specifications does not ensure product availability.
Belden provides the information and specifications herein on an "ASIS" basis, with no representations or warranties, whether express, statutory or implied. In no event will Belden be liable for any damages
(including consequential, indirect, incidental, special, punitive, or exemplary damages) whatsoever, even if Belden has been advised of the possibility of such damages, whether in an action under contract,
negligence or any other theory, arising out of or in connection with the use, or inability to use, the information or specifications described herein.
All sales of Belden products are subject to Belden's standard terms and conditions of sale.
Belden believes this product to be in compliance with all applicable environmental programs as listed in the data sheet. The information provided is correct to the best of Belden's knowledge, information and belief
at the date of its publication. This information is designed only as a general guide for the safe handling, storage, and any other operation of the product itself or the one that it becomes a part of. The Product
Disclosure is not to be considered a warranty or quality specification. Regulatory information is for guidance purposes only. Product users are responsible for determining the applicability of legislation and
regulations based on their individual usage of the product.

You might also like