GENERAL NOTES
PIN LIGHT (12W)
1. ALL ELECTRICAL WORKS HEREIN SHALL BE DONE IN ACCORDANCE WITH THE PROVISION OF DUPLEX CONVENIENCE
OUTLET
REQUIREMENT OF THE LOCAL POWER COMPANY & THE LAWS AND ORDINANCES OF THE
LOCAL ENFORCING AUTHORITY, NATIONAL BUILDING CODE AND FIRE CODE OF THE AIR CONDITIONING UNIT
PHILIPPINES. (ACU) 2HP ACU
2. UNLESS OTHERWISE SPECIFIED, CONDUCTORS SHALL BE COPPER TYPE THHN 90°C, 600 VOLT PANELBOARD
INSULATION THE MINIMUM SIZE OF WIRE AND CONDUIT SHALL BE 2.0MM2 & 15MM Ø
RESPECTIVELY. EXHAUST FAN
EF
DUPLEX CONVENIENCE
3. ALL MATERIALS SHALL BE BRAND NEW AND OF THE APPROVED TYPE FOR PURPOSE
INTENDED. OUTLET (TV) TV
CEILING FAN
4. ALL 20 AMPERE CIRCUIT HOMERUNS TO PANELBOARD MORE THAN 30 METERS IN LENGTH CF
SHALL BE 3.5MM2 MINIMUM, UNLESS OTHERWISE NOTED.
5. PROVIDE FLEXIBLE METAL CONDUIT FOR ALL EQUIPMENTS WHICH ARE SUBJECTED TO
VIBRATION USE LIQUID-TIGHT TYPE FOR WET AND DAMP CONDITION.
LEGENDS
6. STANDARD TYPE OF ACCESSORIES, SPLICING DEVICES, TERMINATION AND OTHER
APPURTENANCES FOR THE ENTIRE ELECTRICAL INSTALLATION SHALL BE USED.
SERVICE DROP:
7. ALL ELECTRICAL EQUIPMENTS TO BE USED HEREIN SHALL BE EQUIPPED WITH PROPER SINGLE PHASE, 230 VOLTS, 60
HERTZ, TWO (2) WIRE + ONE (1)
GROUNDING. ALL GROUND WIRES SHALL BE PROPERLY IDENTIFIED BY USING GREEN GROUND WIRE SYSTEM
INSULATION. 2-38 mm2 THHN + 1-5.5 mm2
GROUND WIRE @ 20 mm dia. RSC
8. MOUNTING HEIGHTS:
8.1. LIGHTING CONTROL SWITCHES 1.40 M. ABOVE FFL. & 150 MM FROM JAMBS
8.2. CONVENIENCE OUTLET 0.30 M ABOVE FLOOR FINISH M ELECTRIC METER
(COMMERCIAL)
8.3. COUNTER HEIGHT OUTLET 0.30 M ABOVE COUNTER FINISH
8.4. PUSH BUTTON 1.40 M ABOVE FLOOR FINISH
8.5. BELL AND BUZZER 2.20 M ABOVE FLOOR FINISH
8.6. RANGE AND AIRCON OUTLET VERIFY FROM THE ARCHITECT
8.7. PANEL BOARD 1.40 M ABOVE FLOOR FINISH 125 AT 15 AT
MAIN 1
15 AT 15 AT
2
LIGHTING
9. MATERIALS SPECIFICATIONS: LIGHTING 3 4
20 AT 20 AT LIGHTING
9.1. WIRING DEVICES PANASONIC OR TOSHIBA BRAND
9.2. RIGID METAL CONDUIT MATSUSHITA OR NIKON OR ITS EQUIVALENT C.O 5
20 AT
6 C.O
9.3. POLYVINYL CHLORIDE (PVC) PIPE ATLANTA OR MOLDEX 7 8 ACU (2HP)
C.O 30 AT 30 AT
9.4. CIRCUIT BREAKERS G.E. OR SCHEINDER
ACU (2HP) 9
30 AT
10 ACU (2HP)
30 AT
10. ALL DIMENSIONS SHOWN ON THE PLANS ARE APPROXIMATE & SHALL BE VERIFIED AS ACTUAL ACU (2HP)
ACU (2HP) 11 12
LOCATIONS, DISTANCES & LEVELS ARE GOVERNED BY ACTUAL FIELD CONDITIONS. 30 AT 30 AT
ACU (2HP) 13 14 ACU (2HP)
30 AT 30 AT
11. ALL WORKS SHALL BE DONE IN THE MOST THOROUGH, PROMPT AND WORKMAN LIKE MANNER SPARE 15 16 SPARE
IN EMPLOYING STANDARD METHOD AND GOOD ENGINEERING PRACTICES. GROUND TERMINAL
12. THE WORKS SHALL BE EXECUTED UNDER THE SUPERVISION OF A LICENSED ELECTRICAL 1 - 5.5 mm² TW
ENGINEER OR MASTER ELECTRICIAN. GROUND WIRE
13. POWER SUPPLY SHALL BE 230 VOLTS, SINGLE PHASE, 2 WIRES PLUS GROUND, 60 HERTZ
14. METHOD OF WIRING SHALL BE RIGID METAL CONDUIT FOR SERVICE ENTRANCE AND PVC
PIPE FOR BRANCH CIRCUIT, PVC INSTALLATION SHALL BE EMBEDDED IN CONCRETE AND SINGLE LINE DIAGRAM
PROVIDE ADDITIONAL CONDUCTOR SOLELY FOR BONDING & ELECTRICAL CONTINUITY
NAME OF PROJECT/ LOCATION: NAME OF THE OWNER: SHEET CONTENT: NAME OF THE DESIGNER/ ENGINEER: SHEET NO.
DOMINIC INSTITUTE OF SCIENCE AND TECHNOLOGY DOMINIC A. ORJALO GENERAL NOTES KELLY ANDREI P. CLEMENTE
MUZON EXTENSION 1/4
PRESIDENT LEGENDS ELECTRICAL ENGINEER
3RD FLOOR, MISEMASI BLDG., MUZON, CSJDM, BULACAN 3023 PHILIPPINES