Gradeschool Library E1

The document outlines the specifications and general notes for an electrical installation at St. Paul College Pasig, adhering to the Philippines Electrical Code and local regulations. It details the power supply, materials used, wiring layout, and grounding requirements, while also providing guidelines for circuit breakers and color coding. Additionally, it emphasizes that the developer may alter plans as necessary for project interests.

Uploaded by

Clarice De Luna
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
21 views1 page

Gradeschool Library E1

The document outlines the specifications and general notes for an electrical installation at St. Paul College Pasig, adhering to the Philippines Electrical Code and local regulations. It details the power supply, materials used, wiring layout, and grounding requirements, while also providing guidelines for circuit breakers and color coding. Additionally, it emphasizes that the developer may alter plans as necessary for project interests.

Uploaded by

Clarice De Luna
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

GENERAL NOTES & SPECIFICATION: LOAD SCHEDULE & COMPUTATION:

1. THE ELECTRICAL INSTALLATION HERE IN WAS DONE IN ACCORDANCE WITH THE


PROVISIONS OF THE LATEST EDITION OF THE PHILIPPINES ELECTRICAL CODED,
REQUIREMENTS OF THE LOCAL POWER COMPANY AND RULES AND REGULATIONS OF THE
LOCAL ENFORCING AUTHORITY.

2. THE POWER SUPPLY WAS 230VOLTS, 3 PHASE, 3 WIRES W/ GROUND, 60 HERTZ.

3. ALL MATERIALS USED WERE BRAND NEW AND OF APPROVED TYPE FOR LOCATION AND
PURPOSE.

4. STANDARD TYPE OF ACCESSORIES, SPLICING DEVICES TERMINATION AND OTHER


APPURTENANCES FOR THE ENTIRE ELECTRICAL INSTALLATION WAS USED.

5. ALL NON - CURRENT CARRYING METAL PARTS OF ELECTRICAL EQUIPMENT AND LIGHTING
FIXTURE WERE EFFECTIVELY GROUNDED.

6. WIRING LAYOUT INDICATED ARE DIAGRAMMATIC ONLY CONTRACTOR WERE WIRE THE
SYSTEM TO ATTAIN ITS INTENDED FUNCTION EVEN WIRES ARE NOT INDICATED ON THE
PLAN.

7. ALL STEEL MATERIALS USED IN THIS PROJECT WAS EITHER HOT DIPPED GALVANIZED OR
ZINC COATED. POWER SINGLE LINE DIAGRAM:
8. FOR EXACT LOCATION OF LIGHTING FIXTURES AND SWITCHING, REFER TO
ARCHITECTURAL PLANS.

9. WIRING LAYOUT FOR CEILING AND WALL PARTITIONS WERE ELECTRICAL METALLIC
TUBING (EMT) AND EMBEDDED PIPES FOR CONCRETE FLOOR WERE IN POLYVYNIL
CHLORIDE (PVC) PIPES.

10. ALL WIRING DEVICES SHOWN ARE APPROXIMATE LOCATION ONLY. ACTUAL SETTING CAN ELECTRICAL DESIGN ANALYSIS:

BE MOVED WITHIN 4.5 MTS. AROUND WITHOUT ADDITIONAL COST THE OWNER.

11. ALL JUNCTION BOXES AND UTILITY BOXES WERE PAINTED WITH GRAY LEAD PRIMER. PANEL PP

12. CONTROLLERS FOR ELECTRICALLY OPERATED EQUIPMENT FOR HVAC, FIRE PROTECTION &
SANITARY SYSTEM WAS PROVIDED BY RESPECTIVE CONTRACTORS. 125AT,3P,240V,MCCB

13. MINIMUM SIZE OF WIRE & CONDUIT SHALL BE 3.5mm² (# 12 WAG) THHN & 15mm 100 AT 3P 3P SPACE
*1 2*
CONDUIT (1/2) RESPECTIVELY.
20 AT 2P 2P 20 AT
*3 4*
14. FOLLOW / IMPLEMENT COLOR CODING, ( EXISTING BUILDING COLOR CODING): 20 AT 2P 2P 20 AT
*5 6*
RED - LINE 1 WHITE - NEUTRAL
20 AT 2P 2P 20 AT
YELLOW - LINE 2 GREEN - GROUND *7 8*
BLUE - LINE 3
GROUND TERMINAL

15. ALL CIRCUIT BREAKER ARE BOLT - ON TYPE AND OF THE MAGNETIC TERMINAL TYPE
COMMON TRIP WITH THE RATINGS AND NUMBER OF POLES AS INDICATED IN THE
DRAWING.

SHORT CIRCUIT ANALYSIS:

LEGEND & SYMBOLS: VICINITY MAP:


CENTER LIGHT

SPOT LIGHT

PIN LIGHT

VOLTAGE DROP ANALYSIS:


STRIPLIGHT

EMERGENCY LIGHT OUTLET


E

DOOR SENSOR OUTLET


D.S

CONVENIENCE OUTLET

BREAKER

PANEL BOARD

PROJECT TITLE / LOCATION ARCHITECT PROFESSIONAL ELECTRICAL ENGINEER: OWNER / DEVELOPER SHEET CONTENTS REVISIONS DRAWING NO.
THE DEVELOPER SHALL EXERT BEST DRAWN BY: ---
EFFORT TO CONFORM TO THE MARK DESCRIPTION DATE
SPECIFICATIONS AND PLANS SPECIFIED GENERAL NOTES & SPECIFICATIONS
ST. PAUL COLLEGE PASIG LEGEND & SYMBOLS DATE: ---
PRESCHOOL LIBRARY -- HEREIN. HOWEVER, THE DEVELOPER
RESERVES THE RIGHT, WITHOUT PRIOR
LOAD SCHEDULE & COMPUTATION

ARCHITECT NOTICE, TO ALTER THE PLANS AND


SPECIFICATIONS AS MAY DEEMED
POWER SINGLE LINE DIAGRAM
VICINITY MAP
VOLTAGE DROP ANALYSIS
SHORT CIRCUIT ANALYSIS
CHECKED BY: --- E-01
PRC REG NO.: --- DATE.: --- TIN: --- PRC REG NO.: -- DATE.: -- TIN: -- NECESSARY IN THE BEST INTEREST OF THE ELECTRICAL DESIGN ANALYSIS
PASIG PRODUCT AND THE CLIENT. 2008 DATE: ---
PTR NO.: --- DATE: --- IAPOA NO.: --- PTR NO.: -- DATE: -- ISSUED AT: --