Product: Industrial Burners
Product: Industrial Burners
Industrial burners
Industrial burners sizes 30 to 70 • flexible and reliable
Weishaupt Industrial Burners:
Flexible and reliable
For more than 50 years, Weishaupt industrial burners have set
global standards in terms of reliability, energy efficiency, noise
levels and ease of use.
With firing rate between 3,400 and 40,000 MBH, the spectrum
of application possibilities covers from heating and steam boilers
to air heaters and modern high efficiency boilers.
With its wide range of industrial burners, which can be used with
almost any gaseous or liquid fuel, Weishaupt has the right burner
for virtually any job.
2
3
                                             Burner housing can
Burner motor                                 be hinged open to the
                                             left or to the right
                       Air pressure switch
Mixing head
Flame sensor
                     Fan wheel
Index of contents
                                                                                           5
Weishaupt industrial burners sizes 30 to 70
High capacity and flexible application range
Weishaupt industrial burners have             Applicable fuels                          The most important advantages:
been especially designed for                  • Light oil #2                            • Large capacity and application range
industrial applications. The                    viscosity up to 6 cSt (6 mm2/s) at      • Stable fan characteristics
monobloc burners are noteworthy                 68F (20 °C) to ASTM D396                • Good combustion behaviour
for their large capacity and                  • Medium #4 to heavy fuel #6 oil          • Burner housing can be hinged open
operational ranges and numerous                 viscosity up to 50 cSt (50 mm2/s at     • Easy installation, commissioning and
technical details:                              212F (100 °C) to ASTM D396                service
                                              • Natural Gas                             • Increased safety provided by nozzle
Flexible application range                    • Propane                                   head shut off device with dedicated
The burners can be used on heat                                                           nozzle shut off solenoid
exchangers such as hot water boilers,         Permissible ambient conditions:           • Nozzle circulation and precise oil
steam boilers, air heaters and for            • Ambient temperature                       temperature regulation on heavy fuel
certain process applications. As the            -10 to +40 °C (14 to 104F)                oil burners
burners are capable of overcoming high          -15 to +40 °C (5 to 104F)               • Compliance with current emission
combustion chamber resistances, they          • Air humidity: max. 80% relative           standards worldwide
are primarily used on high efficiency           humidity, no condensation               • High turndown ratio (RL, RGL)
boilers.                                      • Suitable only for indoor operation
                                              • For installation in unheated rooms
Digital combustion management                   under some circumstances special
Digital combustion management                   solutions are required (contact
ensures simple and safe operation               Weishaupt)
of combustion application. All important
functions, such as fuel and air supply or     Any discrepancy from the above de-
flame monitoring are controlled with          scribed applications requires written
digital precision. Operational functions      confirmation from Weishaupt Corpora-
are optimized, economy is maximized           tion. The maintenance interval could be
and emissions are minimized.                  shortened according to conditions
The integral ModBus interface allows          where the burners are installed.
communication with building
automization/ management system.              Approvals
                                              The burners are in compliance with
Energy saving with speed control              most North American and European
and O2 trim                                   applicable standards.
Electrical consumption is definitely
a cost factor for large combustion            Outstanding service
application.                                  Weishaupt maintains an extensive
Speed control uses frequency drive            global sales and service network.
to match fan speed to the actual air          Customer service is available every day
requirement, allowing for significant         around the clock. In-house training by
savings of electricity, particularly at low   Weishaupt ensures the high standard
fire. With O2 trim the flue gases are         of their service engineers.
continuously monitored and controlled
to ensure the best possible degree of
combustion efficiency and thus lower
fuel consumption and increased
reliability.
6
Characteristics of the different variations
Version Standard                           Version 3LN
Oil, gas and dual fuel burners for         LowNOx gas and dual fuel burners
installations without specific NOx         with patented multiflam mixing head
requirements. Suitable for Natural Gas,    for installations with more stringent low
Propane, #2 - #6 oil, as well as special   NOx requirements. Low NOx values are
gases and special oils on request.         achieved by fuel distribution method.
                                           Suitable for Natural Gas, Propane and
Version NR                                 #2 oil.
Gas and dual fuel burners with
advanced, standard mixing head for
applications where there is NOx
requirements on gas side. NR means:
lower NOx emission on gas side com-
pared to the standard version. Oil side
as standard version. Suitable for
Natural Gas, Propane, #2 - #6 oil.
Version 1LN
LowNOx gas and dual fuel burners with
special mixing head for applications,
where there are requirements for lower
NOx emission on gas and oil side. 1LN
means: lower NOx values compared to
version NR.
Suitable for Natural Gas, Propane, #2
oil.
Version LN
LowNOx gas burners with special
mixing head for installations where
there is requirement for lower NOx
emission on gas operation.
Lower NOx value compared to vers.
1LN . Suitable for Natural Gas and
Propane.
                                                                                       7
Oil burners
Burner selection
Oil burners size 30, version Standard
                Burner model                  MS30Z/2-A                                                                  Burner model                   RMS30/2-A
                Combustion head               M30/2 - 190k x 65                                                          Combustion head                M30/2 - 190k x 65
                Capacity in MBH               2,300 – 8,330                                                              Capacity in MBH                2,300 – 8,330
                Capacity in GPH#6             15 – 54.5                                                                  Capacity in GPH#6              15 – 54.5
     “WC                                                                                                    “WC
       5                                                                                                        6
4 5
                                                                                                                4
       3
                                                                                                                3
       2
                                                                                                                                                                           High fire
                                                                                                                2
                                                                                                                                                                            range
       1
                                                                                                                1
       0
                                                                                                                0
-1 -1
       -2                                                                                                       -2
 MBH        0   1,000   2,000    3,000      4,000        5,000          6,000    7,000    8,000   9,000   MBH        0   1,000   2,000     3,000      4,000        5,000          6,000    7,000    8,000   9,000
GPH #6 7.5 15 22.5 30 37.5 45 52.5 60 GPH #6 7.5 15 22.5 30 37.5 45 52.5 60
 Fuels
 #6 oil
10
Burner selection
Oil burners size 40, version Standard
                 Burner model                                                 MS40Z/1-B                               MS40Z/1-B                                                      Burner model                                      RMS40/1-B
                 Combustion head                                              M30/2 - 200x50                          M30/2 - 175x50                                                 Combustion head                                   M30/2 - 190k x 65
                 Capacity in MBH                                              3,445 – 8,740                           3,445 – 10,170                                                 Capacity in MBH                                   2,680 – 9,965
                 Capacity in GPH#6                                            22.5 – 57                               22.5 – 66                                                      Capacity in GPH#6                                 17.5 – 65
  “WC                                                                                                                                                                  “WC
      6                                                                                                                                                                    8
                                                                                                                                                                           7
      5
                                                                                                                                                                           6
      4
                                                                                                                                                                           5
      3
                                                                                                                                                                           4
                                                                                                                         High fire
      2                                                                                                                                                                    3
                                                                                                                          range
                                                                                                                                                                                                                                               High fire
                                                                                                                                                                                                                                                range
      1                                                                                                                                                                    2
                                                                                                                                                                           1
      0
                                                                                                                                                                           0
      -1
                                                                                                                                                                           -1
      -2                                                                                                                                                                   -2
MBH        0   1,000          2,000      3,000       4,000            5,000      6,000         7,000        8,000      9,000        10,000        11,000    12,000   MBH        0   1,000        2,000    3,000   4,000        5,000     6,000      7,000        8,000   9,000   10,000        11,000   12,000
GPH #6 10 20 30 40 50 60 70 80 GPH #6 10 20 30 40 50 60 70 80
                                                                                                                                                                                                                                                                                                           11
Burner selection
Oil burners size 50, version Standard
                 Burner model                                      L50T/2-A                                                                                        Burner model                                             RL50/1-B                               RMS50/1-B
                 Combustion head                                   M50/1 - 185x50                                                                                  Combustion head                                          M40/2 - 217x75                         M40/2 - 217x75
                 Capacity in MBH                                   3,445 – 16,260                                                                                  Capacity in MBH                                          2,440 – 13,000                         3,840 – 13,000
                 Capacity in GPH#2                                 25 – 116                                                                                        Capacity in GPH#2                                        17 – 93                                –
     “WC                                                                                                                                           “WC                         GPH#6                                        –                                      25 – 85
       8                                                                                                                                              9
                                                                                                                                                       8
       7
                                                                                                                                                       7
       6
                                                                                                                                                       6
       5
                                                                                                                                                       5
       4
                                                                                                                                                       4
       3
                                                                                                                                                                                                                                                   High fire
                                                                                                                                                       3
                                                                                                                                                                                                                                                    range
       2
                                                                                                                                                       2
       1                                                                                                                                               1
0 0
-1 -1
       -2                                                                                                                                              -2
 MBH        0     2,000              4,000      6,000           8,000           10,000        12,000       14,000        16,000         18,000   MBH        0   1,000        2,000   3,000   4,000        5,000    6,000      7,000        8,000    9,000     10,000 11,000 12,000 13,000 14,000
GPH #6 10 20 30 40 50 60 70 80 90
       6
                                                                                                                                                   RMS50/2-A                          ZM                                                                            212 505 02
       5
       4
                                                              High fire
       3
                                                               range
       -1
                                                                                                                                                  calorific value of 153,000 BTU/Gal.
       -2
 MBH        0   2,000        4,000      6,000   8,000        10,000      12,000    14,000     16,000     18,000     20,000   22,000     24,000
                                                                                                                                                  The capacity graphs are based on air temperature of
 GPH #2                 20             40          60                 80            100            120            140             160
                                                                                                                                                  68F (20 °C) an installation altitude of 1,640 ft (500 m)
 GPH #6                 20               40             60                 80               100            120           140             160
                                                                                                                                                  above sea level. A reduction of burner capacity of 1 %
                                                                                                                                                  for every 325 ft (100 m) should be taken into
                                                                                                                                                  consideration depending on installation altitude.
 Fuel oils
 #2 oil
                                                                                                                                                  Voltages and frequencies:
 #6 oil                                                                                                                                           The burners are equipped with three phase motor in 208 -
                                                                                                                                                  600 V, 60 Hz as standard. Different voltage and frequency
                                                                                                                                                  are available upon request.
12
Burner selection
Oil burners size 60 and 70, version Standard
                 Burner model                                                RL60/2-A                                      RMS60/2-A                                                 Burner model                                 RL70/1-A                               RMS70/1-A
                 Combustion head                                             M60/2-345-230                                 M60/2-345-230                                             Combustion head                              M70/1a-425-290                         M70/1a-425-290
                 Capacity in MBH                                             4,470– 24,795                                 6,140 – 24,795                                            Capacity in MBH                              6,500 – 29,860                         6,910 – 29,860
                 Capacity in GPH#2                                           32– 176                                       –                                                         Capacity in GPH#2                            46 – 213                               –
  “WC                        GPH#6                                           –                                             40 – 162                                  “WC                         GPH#6                            –                                      45 – 195
     9                                                                                                                                                                  9
8 8
7 7
6 6
5 5
      4                                                                                                                                                                  4
                                                                                                  High fire
                                                                                                                                                                                                                                     High fire
      3                                                                                                                                                                  3
                                                                                                   range
                                                                                                                                                                                                                                      range
      2                                                                                                                                                                  2
1 1
0 0
-1 -1
      -2                                                                                                                                                                 -2
MBH        0   2,000        4,000        6,000        8,000        10,000    12,000     14,000        16,000      18,000    20,000   22,000     24,000    26,000   MBH        0   2,500   5,000    7,500    10,000 12,500    15,000 17,500      20,000 22,500      25,000      27,500      30,000 32,500   35,000
GPH #2 20 40 60 80 100 120 140 160 180 GPH #2 20 40 60 80 100 120 140 160 180 200 220 240
GPH #6 20 40 60 80 100 120 140 160 GPH #6 20 40 60 80 100 120 140 160 180 200 220
      3
      2                                                                                                                                                             The stated oil throughputs in GPH refer to #2 oil with a
      1                                                                                                                                                             calorific value of 140,000 BTU/Gal and #6 oil with a
      0
                                                                                                                                                                    calorific value of 153,000 BTU/Gal.
      -1
      -2
MBH        0   3,000        6,000        9,000    12,000       15,000        18,000     21,000      24,000        27,000    30,000   33,000     36,000    39,000
                                                                                                                                                                    The capacity graphs are based on air temperature of
GPH #2           25             50               75           100           125          150              175         200          225         250        275
                                                                                                                                                                    68F (20 °C) an installation altitude of 1,640 ft (500 m)
GPH #6            25                50            75                100           125           150             175          200         225           250
                                                                                                                                                                    above sea level. A reduction of burner capacity of 1 %
                                                                                                                                                                    for every 325 ft (100 m) should be taken into
                                                                                                                                                                    consideration depending on installation altitude.
Fuels
#2 oil                                                                                                                                                              Voltages and frequencies:
#6 oil                                                                                                                                                              The burners are equipped with three phase motor in 208 -
                                                                                                                                                                    600 V, 60 Hz as standard. Different voltage and frequency
                                                                                                                                                                    are available upon request.
                                                                                                                                                                                                                                                                                                             13
Scope of delivery/Accessories
Oil burners size 30 to 70, version Standard
     Scope of delivery                                                     MS30   MS40   RMS30 RMS40 RMS50 RMS60 RMS70 L50   RL50   RL60   RL70
     Accessories
     Intake flange for connection of air duct                              ○      ○      ○     ○     ○     ○     ○     ○     ○      ○      ○
     Stainless steel oil hoses, heated                                     ○      ○      ○     ○     ○     ○     ○     –     –      –      –
     Magnetic coupling                                                     –      –      ○     ○     ○     –     –     ○     ○      ○      ○
     Combustion head extension                                             ○      ○      ○     ○     ○     ○     ○     ○     ○      ○      ○
     Media preheater with fittings                                         ○      ○      ○     ○     ○     ○     ○     –     –      –      –
     Speed control                                                         –      –      ○     ○     ○     ○     ○     ○     ○      ○      ○
     O2 trim                                                               –      –      ○     ○     ○     ○     ○     ○     ○      ○      ○
     W-FM loosed for installation in remote panel                          –      –      ○     ○     ○     ○     ○     ○     ○      ○      ○
 ●         Scope of delivery
 ○         Accessories
14
Technical data
Oil burners size 30 and 40, version Standard
 Technical data                                                                    MS30Z/2-A                      RMS30/2-A
 Burner motor 3~208 - 600V                                               Model     W-D112/140-2/4K5               W-D112/140-2/4K5
 Motor rating                                                          HP (kW)     6.6 (4.5)                      6.6 (4.5)
 FLA at 460V                                                                 A     8.6                            8.6
 Speed (60 Hz)                                                             rpm     3,510                          3,510
 Fan wheel                                                             Color / ø   red / 248 x 104                red / 248 x 104
 Combustion manager                                                      Model     LAL2.25                        W-FM100
 Ignition unit                                                           Model     W-ZG02                         W-ZG02
 Stepping motor               Air                                        Model     1055/80                        SQM45
                              Fuel                                       Model     –                              SQM45
                              Mixing head                                Model     –                              SQM45
 Pump fitted                                                             Model     E7                             TA3
 Oil preheater                                                           Model     EV2D                           EV2D
                              Oil throughput GPH and (kg/h)                        72 (270)                       72 (270)
                              Heat rating kW                                       13.2                           13.2
 Oil solenoid valves          110V 1/8”                          19   W Model      121 K 2423                     –
                              110V 1/8”                          19   W Model      122 K 9321                     –
                              55V 3/8” (supply)                  20   W Model      321 H 2322                     321 H 2322
                              55V 3/8” (return)                  20   W Model      121 G 2320                     121 G 2320
 Oil pressure switches        1 – 10 bar     (return fuel oil EL - 5 bar) Model    –                              –
                              1 – 10 bar       (return fuel oil S - 7 bar) Model   DSA 46 F001                    DSA 46 F001
 Oil hoses                                   DN, length in inch and (mm)           20/40” (1000)                  20/40” (1000)
 (on MS, RMS and RGMS, high pressure metal hoses)                                  20/51” (1300)                  20/51” (1300)
 Burner weight                                                  approx. lbs (kg)   297 (135)                      309 (140)
                                                                                                                                                                15
Technical data
Oil burners size 50, version Standard
     Technical data                                                                   L50T/2-A             RL50/1-B            RL50/2-A
     Burner motor 3~208 V - 600V                                            Model     W-D132/210-2/14K0    W-D132/170-2/9K0    W-D132/210-2/14K0
     Motor rating                                                         HP (kW)     20 (15)              14.6 (11)           20 (15)
     FLA at 460V                                                                A     25                   19                  25
     Speed (60 Hz)                                                            rpm     3,520                3,500               3,520
     Fan wheel                                                           Colour / ø   red / 330 x 104.5    red / 330 x 104.5   red / 330 x 104.5
     Combustion manager                                                     Model     W-FM100              W-FM100             W-FM100
     Ignition unit                                                          Model     W-ZG02               W-ZG02              W-ZG02
     Stepping motor            Air                                          Model     SQM45                SQM45               SQM45
                               Fuel                                         Model     –                    SQM45               SQM45
                               Mixing head                                  Model     –                    SQM45               SQM45
     Pump, fitted                                                           Model     TA2C                 TA4C                T2C
     Oil preheater                                                          Model     –                    –                   –
                               Oil throughput in GPH and (kg/h)                       –                    –                   –
                               Heat rating kW                                         –                    –                   –
     Oil solenoid valve        110V 1/8”                            19   W Model      121 K 2423 (3 off)   –                   –
                               110V 1/4” (safety v.)                20   W Model      121 K 6220           –                   –
                               55V 3/8” (supply)                    20   W Model      –                    321 H 2322          321 H 2322
                               55V 3/8” (return)                    20   W Model      –                    121 G 2320          121 G 2320
     Oil pressure switches     1 – 10 bar          (return #2 oil - 5 bar) Model      –                    DSA 46 F001         DSA 46 F001
                               1 – 10 bar          (return #6 oil - 7 bar) Model      –                    –                   –
     Oil hoses                                         DN, length in inch and (mm)    20/51” (1300)        25/51” (1300)       25/51” (1300)
     Burner weight                                                 approx. lbs (kg)   440 (200)            458 (208)           463 (210)
 1)
      Burners above 82.5 GPH (300 kg/h): Oil preheater WEV3 in lieu of WEV2.2,
      Refer to ‘Accessories’
16
Technical data
Oil burners size 60 and 70, version Standard
                              Technical data                                     RL60/2-A                    RMS60/2-A
 Burner motor 3~208 - 600V                                             Model     W-D132/210-2/14K0           W-D132/210-2/14K0
 Motor rating                                                        HP (kW)     20 (15)                     20 (15)
 FLA at 460V                                                               A     25                          25
 Speed (60 Hz)                                                           rpm     3,520                       3,520
 Fan wheel                                                          Colour / ø   red / 465 x 103             red / 465 x 103
 Combustion manager                                                      Model   W-FM100                     W-FM100
 Ignition unit                                                           Model   W-ZG02                      W-ZG02
 Stepping motor               Air                                        Model   SQM45                       SQM45
                              Fuel                                       Model   SQM45                       SQM45
                              Mixing head                                Model   SQM45                       SQM45
 Pump fitted                                                             Model   T2C                         –
 Oil solenoid valves          55V 3/8” (supply)                 20 W Model       321 H 2322                  321 H 2322
                              55V 3/8” (return)                 20 W Model       121 G 2320                  121 G 2320
                              110V 3/8” (bypass)                19 W Model       –                           322 H 7306
 Oil pressure switches        3 – 25 bar              (supply-18 bar)    Model   –                           DSA 58 F 001
                              1 – 10 bar         (return #2 oil-5 bar)   Model   DSA 46 F 001                –
                              1 – 10 bar         (return #6 oil-7 bar)   Model   –                           DSA 46 F 001
 Oil hoses                                 DN, length in inch and (mm)           25/51” (1300)               16/45” (1150)
 (on RMS and RGMS, high pressure metal hoses)                                    –                           16/59” (1500)
 Burner weight                                                approx. lbs (kg)   552 (250)                   463 (210) 2)
2)
     Weight without pump and preheater station
                                                                                                                                                                     17
Gas burners
Burner selection
Gas burners size 50 to 70, version NR
                      Burner model                                G50/1-B, vers. ZM-NR                                                                Burner model                                   G50/2-A, vers. ZM-NR
                      Combustion head                             G40/2-NR 217x75                                                                     Combustion head                                G50/2-NR 290x85
                      Capacity in MBH Nat Gas                     1,875 – 13,650                                                                      Capacity in MBH Nat Gas                        2,050 – 18,430
                                  Propane                         1,875 – 13,650                                                                                  Propane                            2,050 – 18,430
 “WC                                                                                                                                “WC
     9                                                                                                                                9
8 8
7 7
6 6
5 5
4 4
                                                                                                                                                                                          High fire
                                                                           High fire
3 3
                                                                                                                                                                                           range
                                                                            range
2 2
1 1
0 0
-1 -1
     -2                                                                                                                              -2
          0   1,000     2,000   3,000    4,000   5,000    6,000    7,000     8,000     9,000   10,000 11,000 12,000 13,000 14,000         0    2,000      4,000       6,000       8,000      10,000     12,000      14,000   16,000     18,000       20,000    22,000
                      Burner model                                G60/2-A, vers. ZM-NR                                                                Burner model                                   G70/1-B, vers. ZM-NR
                      Combustion head                             G60/2-NR 345x230                                                                    Combustion head                                G60/2-NR 345x230
                      Capacity in MBH Nat Gas                     2,730 – 20,800                                                                      Capacity in MBH Nat Gas                        2,730 – 25,250
                                  Propane                         2,730 – 20,800                                                                                  Propane                            2,730 – 25,250
 “WC                                                                                                                                “WC
     9                                                                                                                                9
8 8
7 7
6 6
5 5
     4                                                                                                                                4
                                                                                 High fire
High fire
     3                                                                                                                                3
                                                                                  range
range
2 2
1 1
0 0
-1 -1
     -2                                                                                                                              -2
          0     2,000       4,000       6,000     8,000     10,000     12,000         14,000    16,000   18,000   20,000   22,000         0   2,000    4,000      6,000   8,000    10,000     12,000   14,000    16,000   18,000   20,000   22,000    24,000   26,000
 Fuels
 Nat gas
 Propane
 Burner model                       Vers.                                                           Order No.                        The capacity graphs are based on air temperature of
 G50/1-B                            ZM-NR                                                           217 504 15                       68F (20 °C) and installation altitude of 1,640 ft (500 m).
                                                                                                                                     A reduction of burner capacity of 1 % for every 325 ft
 G50/2-A                            ZM-NR                                                           217 505 13
                                                                                                                                     (100 m) should be taken into consideration depending
 G60/2-A                            ZM-NR                                                           217 605 12                       on installation altitude.
 G70/1-B                            ZM-NR                                                           217 704 42
                                                                                                                                     Voltages and frequencies:
                                                                                                                                     The burners are equipped with three phase motor in 208 -
                                                                                                                                     600 V, 60 Hz as standard. Different voltage and frequency
                                                                                                                                     are available upon request.
20
Burner selection
Gas burners size 70, version NR
                  Burner model                         G70/3-A, vers. ZM-NR                                                         Burner model                         G70/4-A, vers. ZM-NR
                  Combustion head                      G70/3-NR 425x290                                                             Combustion head                      G70/3-NR 425x290
                  Capacity in MBH Nat Gas              3,400 – 36,500                                                               Capacity in MBH Nat Gas              3,400 – 39,930
                              Propane                  4,780 – 36,500                                                                           Propane                  4,780 – 39,930
“WC                                                                                                               “WC
10 10
9 9
8 8
7 7
6 6
5 5
4 4
                                                                                                                                                                         High fire
                                                        High fire
                                                                                                                                                                          range
                                                         range
3 3
2 2
1 1
0 0
-1 -1
 -2                                                                                                                -2
      0   3,000    6,000   9,000   12,000 15,000 18,000 21,000 24,000 27,000 30,000 33,000 36,000 39,000 42,000         0   3,000    6,000   9,000   12,000 15,000 18,000 21,000 24,000 27,000 30,000 33,000 36,000 39,000 42,000
Fuels
Nat gas
Propane
Burner model                 Vers.                                                Order No.                        The capacity graphs are based on air temperature of
G70/3-A                      ZM-NR                                                217 714 14                       68F (20 °C) and installation altitude of 1,640 ft (500 m).
                                                                                                                   A reduction of burner capacity of 1 % for every 325 ft
G70/4-A                      ZM-NR                                                217 734 14
                                                                                                                   (100 m) should be taken into consideration depending
                                                                                                                   on installation altitude.
                                                                                                                                                                                                                                21
Scope of delivery/Accessories
Gas burners size 50 to 70, version NR
 Scope of delivery                                                                             G50   G60   G70
 Burner housing, hinge flange, housing cover, Weishaupt burner motor, air regulator housing,
 fan wheel, combustion head, ignition unit, ignition cable, ignition electrode, combustion
  manager with operating unit, flame sensor, stepping motors, flange gasket, limit switch
 on hinge flange, fixing screws                                                                ●     ●     ●
 Combustion manager W-FM100                                                                    ●     ●     ●
 Two gas safety shut off valves                                                                ●     ●     ●
 Gas butterfly valve                                                                           ●     ●     ●
 Ignition pilot                                                                                ●     ●     ●
 Air pressure switch                                                                           ●     ●     ●
 Gas pressure switches                                                                         ●     ●     ●
 Servomotor driven sliding sleeve in mixing head                                               ●     ●     ●
 Stepping motor for Gas /Air ratio control with W-FM100
      Stepping motor for air damper                                                            ●     ●     ●
       Stepping motor for gas butterfly valve                                                  ●     ●     ●
       Stepping motor for sliding sleeve                                                       ●     ●     ●
 Accessories
 Downward firing burner                                                                        ○     ○     ○
 Intake flange for the connection of an air duct                                               ○     ○     ○
 Solenoid valve for air pressure switch test for cont. run fan or post-purge                   ○     ○     ○
 Combustion head extension                                                                     ○     ○     ○
 Speed control                                                                                 ○     ○     ○
 O2 trim                                                                                       ○     ○     ○
 W-FM loosed for installation in remote control panel                                          ○     ○     ○
 ●     Scope of delivery
 ○     Accessories
22
Technical data
Gas burners size 50 to 70, version NR
Technical data                                                                      G50/1-B             G50/2-A             G60/2-A
Burner motor 3~208 - 600V                                                Model      W-D132/170-2/9K0    W-D132/210-2/14K0   W-D132/210-2/14K0
Motor rating                                                           HP (kW)      14.6 (11)           20 (15)             20 (15)
FLA at 460V                                                                  A      19                  25                  25
Speed (60 Hz)                                                              rpm      3,500               3,520               3,520
Fan wheel                                                                 Colour    red                 red                 red
                                                                               ø    330 x 104.5         330 x 104.5         465 x 103
Combustion manager                                                        Model     W-FM100             W-FM100             W-FM100
Ignition unit                                                             Model     W-ZG02              W-ZG02              W-ZG02
Stepping motor               Air                                          Model     SQM45               SQM45               SQM48
                             Mixing head                                  Model     SQM45               SQM45               SQM45
                             Fuel                                         Model     SQM45               SQM45               SQM45
Burner weight approx. lbs (kg) 408 (185) 408 (185) 606 (275)
                                                                                                                                                23
Burner selection
Gas burners size 50 to 70, version 1LN
                      Burner model                                G50/1-B, vers. ZM-1LN                                                               Burner model                            G70/1-B, vers. ZM-1LN
                      Combustion head                             G40/2-LN 217x35                                                                     Combustion head                         G60/2-1LN 300x75
                      Capacity in MBH Nat Gas                     1,700 – 11,600                                                                      Capacity in MBH Nat Gas                 2,730 – 24,900
                                  Propane                         1,700 – 11,600                                                                                  Propane                     3,400 – 24,900
 “WC                                                                                                                                “WC
     9                                                                                                                                9
     8                                                                                                                                8
7 7
     6                                                                                                                                6
     5
                                                                            High fire
                                                                                                                                      5
                                                                             range
4 4
                                                                                                                                                                                                     High fire
                                                                                                                                                                                                      range
     3                                                                                                                                3
     2                                                                                                                                2
     1                                                                                                                                1
     0                                                                                                                                0
     -1                                                                                                                              -1
     -2                                                                                                                              -2
          0   1,000    2,000   3,000    4,000     5,000   6,000     7,000     8,000    9,000   10,000 11,000 12,000 13,000 14,000         0   2,000    4,000    6,000     8,000   10,000   12,000   14,000      16,000     18,000    20,000    22,000   24,000   26,000
                      Burner model                                G50/2-A, vers. ZM-1LN                                                               Burner model                            G70/2-A, vers. ZM-1LN
                      Combustion head                             G50/2-LN 260x40                                                                     Combustion head                         G70/2-1LN 365x85
                      Capacity in MBH Nat Gas                     2,050 – 16,720                                                                      Capacity in MBH Nat Gas                 3,400 – 34,100
                                  Propane                         2,730 – 16,720                                                                                  Propane                     4,440 – 34,100
 “WC                                                                                                                                “WC
9 10
     8                                                                                                                                9
                                                                                                                                      8
     7
                                                                                                                                      7
     6
                                                                                                                                      6
     5
                                                                                                                                      5
     4
                                                                                                                                      4
                                                                       High fire
High fire
     3
                                                                        range
range
                                                                                                                                      3
     2
                                                                                                                                      2
     1                                                                                                                                1
     0                                                                                                                                0
-1 -1
     -2                                                                                                                              -2
          0       2,000         4,000           6,000       8,000           10,000       12,000      14,000     16,000     18,000         0    3,000    6,000     9,000     12,000   15,000    18,000      21,000        24,000     27,000    30,000    33,000   36,000
 Fuels
 Nat gas
 Propane
 Burner model                    Vers.                                                              Order No.                        The capacity graphs are based on air temperature of
 G50/1-B                         ZM-1LN                                                             217 504 17                       68F (20 °C) an installation altitude at sea level. A
                                                                                                                                     reduction of burner capacity of 1 % for every 325 ft
 G50/2-A                         ZM-1LN                                                             217 505 16
                                                                                                                                     (100 m) should be taken into consideration in case of
 G70/1-B                         ZM-1LN                                                             217 704 45                       installation altitude above 0 ft.
 G70/2-A                         ZM-1LN                                                             217 705 45
                                                                                                                                     Voltages and frequencies:
                                                                                                                                     The burners are equipped with three phase motor in 208 -
                                                                                                                                     600 V, 60 Hz as standard. Different voltage and frequency
                                                                                                                                     are available upon request.
24
Scope of delivery/Accessories/ Technical data
Gas burners size 50 and 70, version 1LN
Scope of delivery                                                                                                        G50             G70
Burner housing, hinge flange, housing cover, Weishaupt burner motor, air regulator housing, fan wheel,
combustion head, ignition unit, ignition cable, ignition electrode, combustion manager with operating
unit, flame sensor, stepping motors, flange gasket, limit switch on hinge flange, fixing screws                          ●               ●
Combustion manager W-FM100                                                                                               ●               ●
Two gas safety shut off valves                                                                                           ●               ●
Gas butterfly valve                                                                                                      ●               ●
Ignition pilot                                                                                                           ●               ●
Air pressure switch                                                                                                      ●               ●
Gas pressure switches                                                                                                    ●               ●
Adjustable flame tube in mixing head                                                                                     ●               ●
Stepping motor for Gas/Air ratio control with W-FM100
     Stepping motor for air damper                                                                                       ●               ●
      Stepping motor for gas butterfly valve                                                                             ●               ●
Accessories
Downward firing burner                                                                                                   ○               ○
Intake flange for the connection of an air duct                                                                          ○               ○
Solenoid valve for air pressure switch test for cont. run fan or post-purge                                              ○               ○
Combustion head extension                                                                                                ○               ○
Speed control                                                                                                            ○               ○
O2 trim                                                                                                                  ○               ○
W-FM loosed for installation in remote control panel                                                                     ○               ○
●     Scope of delivery
○     Accessories
                                                                                                                                                         25
Burner selection
Gas burners size 50, version LN
                  Burner model            G50/1-B, vers. ZM-LN                                                                 Burner model            G50/2-A, vers. ZM-LN
                  Combustion head         G40/2-3a 210x60                                                                      Combustion head         G50/2-3a 250x90
                  Capacity in MBH Nat Gas 1,700 – 10,230                                                                       Capacity in MBH Nat Gas 2,050 – 15,350
 “WC                                                                                                                “WC
     9                                                                                                                9
     8                                                                                                                8
     7                                                                                                                7
     6                                                                                                                6
     5                                                                                                                5
                                                              High fire
                                                               range
4 4
                                                                                                                                                      High fire
                                                                                                                                                       range
     3                                                                                                                3
     2                                                                                                                2
     1                                                                                                                1
     0                                                                                                                0
     -1                                                                                                              -1
     -2                                                                                                              -2
          0   1,000   2,000   3,000   4,000   5,000   6,000      7,000   8,000   9,000   10,000   11,000   12,000         0   2,000   4,000   6,000    8,000     10,000   12,000   14,000   16,000   18,000
 Burner model                 Vers.                                               Order No.                          The capacity graphs are based on air temperature of
 G50/1-B                      ZM-LN                                               217 504 19                         68F (20 °C) an installation altitude at sea level. A
                                                                                                                     reduction of burner capacity of 1 % for every 325 ft
 G50/2-A                      ZM-LN                                               217 505 18
                                                                                                                     (100 m) should be taken into consideration in case of
                                                                                                                     installation altitude above 0 ft.
26
Burner selection
Gas burners size 60 and 70, version LN
               Burner model            G60/2-A, vers. ZM-LN                                                                                  Burner model            G70/1-B, vers. ZM-LN
               Combustion head         G60/2-3a 300x100                                                                                      Combustion head         G60/2-3a 300x100
               Capacity in MBH Nat Gas 2,135 – 19,795                                                                                        Capacity in MBH Nat Gas 2,390 – 23,890
“WC
                                                                                                                               “WC
  9                                                                                                                              9
8 8
7 7
6 6
5 5
4 4
                                                                                                                                                                                           High fire
                                                          High fire
                                                                                                                                                                                            range
                                                                                                                                 3
                                                           range
2 2
1 1
0 0
-1 -1
 -2                                                                                                                             -2
       0   2,000    4,000     6,000      8,000       10,000     12,000     14,000       16,000     18,000    20,000   22,000         0   2,000   4,000   6,000   8,000   10,000   12,000    14,000    16,000   18,000   20,000   22,000   24,000   26,000
“WC
 10
  9
  8
  4
                                                               High fire
                                                                range
  2
  1
  0
-1
  -2
       0   3,000   6,000    9,000     12,000     15,000   18,000      21,000   24,000     27,000    30,000   33,000   36,000
Burner model                Vers.                                                           Order No.                          The capacity graphs are based on air temperature
G60/2-A                     ZM-LN                                                           217 605 13                         of 68F (20 °C) an installation altitude at sea level. A
                                                                                                                               reduction of burner capacity of 1% for every 325 ft
G70/1-B                     ZM-LN                                                           217 704 43
                                                                                                                               (100 m) should be taken into consideration in case of
G70/2-A                     ZM-LN                                                           217 705 43                         installation altitude above 0 ft.
                                                                                                                                                                                                                                                       27
Scope of delivery/Accessories
Gas burners size 50 to 70, version LN
 Scope of delivery                                                      G50   G60   G70
 Burner housing, hinge flange, housing cover,
 Weishaupt burner motor, air regulator housing, fan wheel,
 combustion head, ignition unit, ignition cable, ignition electrodes,
 combustion manager with operating unit, flame sensor,
 stepping motors, flange gasket, limit switch on
 hinge flange, fixing screws                                            ●     ●     ●
 Combustion manager W-FM100                                             ●     ●     ●
 Two safety gas shut off valves                                         ●     ●     ●
 Gas butterfly valve                                                    ●     ●     ●
 Air pressure switch                                                    ●     ●     ●
 Gas pressure switches                                                  ●     ●     ●
 Adjustable flame tube in mixing head                                   ●     ●     ●
 Stepping motor for Gas /Air ratio control with W-FM100
      Stepping motor for air damper                                     ●     ●     ●
       Stepping motor for gas butterfly valve                           ●     ●     ●
 Accessories
 Downward firing burner                                                 ○     ○     ○
 Intake flange for the connection of an air duct                        ○     ○     ○
 Combustion head extension                                              ○     ○     ○
 Speed control                                                          ○     ○     ○
 O2 trim                                                                ○     ○     ○
 W-FM loosed for installation in remote panel                           ○     ○     ○
 ●     Scope of delivery
 ○     Accessories
28
Technical data
Gas burners size 50 to 70, version LN
Technical data                                    G50/1-B             G50/2-A
Burner motor 3~208 - 600V              Model      W-D132/170-2/9K0    W-D132/210-2/14K0
Motor rating                         HP (kW)      14.6 (11)           20 (15)
FLA at 460 V                               A      19                  25
Speed (60 Hz)                            rpm      3,500               3,520
Fan wheel                               Colour    red                 red
                                             ø    330 x 104.5         330 x 104.5
Combustion manager                      Model     W-FM100             W-FM100
Ignition unit                           Model     W-ZG02              W-ZG02
Stepping motor          Air             Model     SQM45               SQM45
                        Fuel            Model     SQM45               SQM45
Burner weight                  approx. lbs (kg)   408 (185)           408 (185)
                                                                                                              29
Dual fuel burners
Burner selection
Dual fuel burners size 30, version NR
                    Burner model                            RGL30/2-A,                           RGMS30/2-A,                           Fuels
                                                            vers. ZM-NR                          vers. ZM-NR                           #2 oil
                    Combustion head                         G30/2-NR 190x65                      G30/2-NR 190x65                       #6 oil
                    Capacity in MBH Gas                     1,025 – 7,850                        1,025 – 7,850                         Nat gas
                    GPH #2 oil                              11.6 – 56                            –                                     Propane
                    GPH #6 oil                              –                                    15 – 51
 “WC
     6
                                                                                                                                       The stated oil throughputs in GPH refer to #2 oil with a
     5
                                                                                                                                       calorific value of 140,000 BTU/Gal and #6 oil with a
     4
                                                                                                                                       calorific value of 153,000 BTU/Gal.
     3
     2
                                                                                 range
     1
                                                                                                                                       68F (20 °C) and installation altitude of 1,640 ft (500 m).
                                                                                                                                       A reduction of burner capacity of 1 % for every 325 ft
     0
                                                                                                                                       (100 m) should be taken into consideration depending
     -1                                                                                                                                on installation altitude.
     -2
          0   500   1,000 1,500   2,000   2,500    3,000 3,500   4,000 4,500   5,000 5,500      6,000 6,500   7,000   7,500    8,000
      GPH #2              10                      20                30                     40                  50
                                                                                                                                       Voltages and frequencies:
      GPH #6               10                          20                30                      40                       50
                                                                                                                                       The burners are equipped with three phase motor in 208 -
                                                                                                                                       600 V, 60 Hz as standard. Different voltage and frequency
                                                                                                                                       are available upon request.
 Burner model                     Vers.                                                          Order No.
                                                                                                                                       Standard burner motor:
 RGL30/2-A                        ZM-NR                                                          218 305 13
                                                                                                                                       Insulation class F, protection IP 55.
 RGMS30/2-A                       ZM-NR                                                          219 305 13
32
Burner selection
Dual fuel burners size 40, version NR
                 Burner model                       RGL40/1-B,                                RGMS40/1-B,                                           Burner model                               RGL40/2-A,                                RGMS40/2-A,
                                                    vers. ZM-NR                               vers. ZM-NR                                                                                      vers. ZM-NR                               vers. ZM-NR
                 Combustion head                    G30/2-NR 190x58                           G30/2-NR 190x58                                       Combustion head                            G40/2-NR 217x75                           G40/2-NR 217x75
                 Capacity in MBH Gas                1,540 – 9,215                             1,540 – 9,215                                         Capacity in MBH Gas                        1,710 – 11,775                            1,710 – 11,775
                 GPH #2 oil                         13 – 65.8                                 –                                                     GPH #2 oil                                 15.8 – 84                                 –
                 GPH #6 oil                         –                                         17.6 – 60                                             GPH #6 oil                                 –                                         22.3 – 76.9
“WC “WC
7 7
6 6
  5                                                                                                                                5
                                                     High fire
                                                      range
4 4
  3                                                                                                                                3
                                                                              High fire
                                                                                                                                                                                                        High fire
                                                                               range
                                                                                                                                                                                                         range
  2                                                                                                                                2
1 1
0 0
-1 -1
 -2                                                                                                                               -2
      0        1,000        2,000   3,000   4,000        5,000        6,000          7,000         8,000        9,000   10,000         0    1,000        2,000   3,000   4,000        5,000    6,000     7,000          8,000    9,000   10,000        11,000   12,000    13,000
GPH #2 10 20 30 40 50 60 70 GPH #2 10 20 30 40 50 60 70 80 90
GPH #6 10 20 30 40 50 60 GPH #6 10 20 30 40 50 60 70 80
                                                                                                                                                                                                                                                                               33
Burner selection
Dual fuel burners size 50, version NR
                      Burner model                                      RGL50/1-B,                                  RGMS50/1-B,                                   Burner model                            RGL50/2-A,                           RGMS50/2-A,
                                                                        vers. ZM-NR                                 vers. ZM-NR                                                                           vers. ZM-NR                          vers. ZM-NR
                      Combustion head                                   G40/2-NR 217x75                             G40/2-NR 217x75                               Combustion head                         G50/2-NR 290x185                     G50/2-NR 290x185
                      Capacity in MBH Gas                               1,880 – 13,650                              1,880 – 13,650                                Capacity in MBH NG                      2,050 – 18,430                       2,050 – 18,430
                      GPH #2 oil                                        16 – 97.5                                   –                                             MBH Propane                             2,730 – 18,430                       2,730 – 18,430
                      GPH #6 oil                                        –                                           25 – 89                                       GPH #2 oil                              27.5 – 131.6                         –
                                                                                                                                                                  GPH #6 oil                              –                                    32.6 – 120.4
 “WC                                                                                                                                                “WC
9 9
8 8
     7                                                                                                                                                7
                                                                            High fire
     6                                                                                                                                                6
                                                                             range
5 5
     4                                                                                                                                                4
                                                                                            High fire
                                                                                                                                                                                                    High fire
     3                                                                                                                                                3
                                                                                             range
                                                                                                                                                                                                     range
     2                                                                                                                                                2
1 1
0 0
-1 -1
     -2                                                                                                                                              -2
          0   1,000        2,000   3,000   4,000          5,000    6,000       7,000        8,000      9,000   10,000 11,000 12,000 13,000 14,000         0    2,000        4,000   6,000   8,000        10,000    12,000   14,000         16,000     18,000   20,000         22,000
34
Burner selection
Dual fuel burners size 60 and 70, version NR
              Burner model                                 RGL60/2-A,                                 RGMS60/2-A,                                              Burner model                                RGL70/1-B,                              RGMS70/1-B,
                                                           vers. ZM-NR                                vers. ZM-NR                                                                                          vers. ZM-NR                             vers. ZM-NR
              Combustion head                              G60/2-NR 345x230                           G60/2-NR 345x230                                         Combustion head                             G60/2-NR 345x230                        G60/2-NR 345x230
              Capacity in MBH Gas                          2,730 – 20,815                             2,730 – 20,815                                           Capacity in MBH Gas                         2,730 – 25,250                          2,730 – 25,250
              GPH #2 oil                                   32 – 148.7                                 –                                                        GPH #2 oil                                  29 – 180                                –
              GPH #6 oil                                   –                                          40.1 – 136                                               GPH #6 oil                                  –                                       43.9 – 180
“WC “WC
9 9
8 8
  7                                                                                                                                       7
                                                             High fire
  6                                                                                                                                       6
                                                              range
5 5
  4                                                                                                                                       4
                                                                              High fire
                                                                                                                                                                                                                     High fire
  3                                                                                                                                       3
                                                                               range
                                                                                                                                                                                                                      range
  2                                                                                                                                       2
1 1
0 0
-1 -1
 -2                                                                                                                                      -2
      0    2,000        4,000        6,000   8,000        10,000    12,000         14,000         16,000   18,000   20,000     22,000         0        2,000        4,000   6,000   8,000        10,000    12,000   14,000      16,000    18,000   20,000   22,000   24,000    26,000
GPH #2 20 40 60 80 100 120 140 160 GPH #2 20 40 60 80 100 120 140 160 180
                                                                                                                                                                                                                                                                                    35
Burner selection
Dual fuel burners size 70, version NR
                      Burner model                               RGL70/3-A,                                  RGMS70/3-A,                                     Burner model                               RGL70/4-A,                                RGMS70/4-A,
                                                                 vers. ZM-NR                                 vers. ZM-NR                                                                                vers. ZM-NR                               vers. ZM-NR
                      Combustion head                            G70/3-NR 425x290                            G70/3-NR 425x290                                Combustion head                            G70/3-NR 425x290                          G70/3-NR 425x290
                      Capacity in MBH Gas                        3,400 – 36,500                              3,400 – 36,515                                  Capacity in MBH NG                         3,400 – 39,930                            3,400 – 39,930
                      MBH Propane                                4,780 – 36,500                              4,780 – 36,515                                  MBH Propane                                4,780 – 39,930                            4,780 – 39,930
                      GPH #2 oil                                 42.5 – 259.8                                –                                               GPH #2 oil                                 42.5 – 285.2                              –
                      GPH #6 oil                                 –                                           39 – 238.7                                      GPH #6 oil                                 –                                         39 – 261
 “WC                                                                                                                                       “WC
     10                                                                                                                                     10
     9                                                                                                                                       9
     8                                                                                                                                       8
     7                                                                                                                                       7
     6                                                                                                                                       6
     5                                                                                                                                       5
     4                                                                                                                                       4
                                                                       High fire
                                                                                                                                                                                                              High fire
                                                                        range
                                                                                                                                                                                                               range
     3                                                                                                                                       3
     2                                                                                                                                       2
     1                                                                                                                                       1
     0                                                                                                                                       0
     -1                                                                                                                                     -1
     -2                                                                                                                                     -2
          0   3,000    6,000        9,000    12,000 15,000 18,000 21,000 24,000 27,000 30,000 33,000 36,000 39,000 42,000                        0   3,000    6,000        9,000    12,000 15,000 18,000 21,000 24,000 27,000 30,000 33,000 36,000 39,000 42,000
GPH #2 25 50 75 100 125 150 175 200 225 250 275 300 GPH #2 25 50 75 100 125 150 175 200 225 250 275 300
GPH #6 25 50 75 100 125 150 175 200 225 250 275 GPH #6 25 50 75 100 125 150 175 200 225 250 275
36
Scope of delivery/Accessories
Dual fuel burners size 30 to 50, version NR
Scope of delivery                                                                          RGMS30   RGMS40   RGMS50   RGL30   RGL40   RGL50
Burner housing, hinge flange, housing cover, Weishaupt burner motor, air regulator
housing, fan wheel, combustion head, ignition unit, ignition cable, ignition electrodes,
nozzle assembly with oil nozzle/s, combustion manager with operating unit, flame sensor,
stepping motors, flange gasket, limit switch on hinge flange, fixing screws                ●        ●        ●        ●       ●       ●
Combustion manager W-FM100                                                                 ●        ●        ●        ●       ●       ●
Two safety gas shut off valves                                                             ●        ●        ●        ●       ●       ●
Gas butterfly valve                                                                        ●        ●        ●        ●       ●       ●
Ignition pilot                                                                             ●        ●        ●        ●       ●       ●
Air pressure switch                                                                        ●        ●        ●        ●       ●       ●
Oil pressure switch in return                                                              ●        ●        ●        ●       ●       ●
Gas pressure switches                                                                      ●        ●        ●        ●       ●       ●
Servomotor driven sliding sleeve in mixing head                                            ●        ●        ●        ●       ●       ●
Stepping motor for Gas /Air ratio control with W-FM100
     Stepping motor for air damper                                                         ●        ●        ●        ●       ●       ●
      Stepping motor for gas butterfly valve                                               ●        ●        ●        ●       ●       ●
      Stepping motor for regulating/sliding sleeve                                         ●        ●        ●        ●       ●       ●
Oil pump, fitted                                                                           ●        ●        ●        ●       ●       ●
Oil preheater, fitted                                                                      ●        ●        ●        –       –       –
Oil hoses                                                                                  ●        ●        ●        ●       ●       ●
Two oil solenoid valves in supply and return                                               –        –        –        ●       –       –
1 solenoid valve in supply and in return,
nozzle head with shut off device (nozzle solenoid)                                         ●        ●        ●        –       ●       ●
Magnetic coupling                                                                          ●        ●        ●        ●       ●       ●
Accessories
Downward firing burner                                                                     –        –        ○        ○       ○       ○
Intake flange for the connection of an air duct                                            –        –        ○        ○       ○       ○
Solenoid valve for air pressure switch test for cont. run fan or post-purge                –        –        ○        ○       ○       ○
Combustion head extension                                                                  –        –        ○        ○       ○       ○
Speed control                                                                              –        –        ○        ○       ○       ○
O2 trim                                                                                    –        –        ○        ○       ○       ○
W-FM loose to fit into control panel                                                       –        –        ○        ○       ○       ○
Separate pump station                                                                      ○        ○        ○        ○       ○       ○
Separate preheater station (electric or media)                                             ○        ○        ○        –       –       –
●     Scope of delivery
○     Accessories
                                                                                                                                              37
Scope of delivery/Accessories
Dual fuel burners size 60 and 70, version NR
 Scope of delivery                                                                          RGMS60   RGMS70   RGL60   RGL70
 Burner housing, hinge flange, housing cover, Weishaupt burner motor, air regulator
 housing, fan wheel, combustion head, ignition unit, ignition cable, ignition electrodes,
 nozzle assembly with oil nozzle/s, combustion manager with operating unit, flame sensor,
 stepping motors, flange gasket, limit switch on hinge flange, fixing screws                ●        ●        ●       ●
 Combustion manager W-FM100                                                                 ●        ●        ●       ●
 Two safety gas shut off valves                                                             ●        ●        ●       ●
 Gas butterfly valve                                                                        ●        ●        ●       ●
 Ignition pilot                                                                             ●        ●        ●       ●
 Air pressure switch                                                                        ●        ●        ●       ●
 Oil pressure switch in return                                                              ●        ●        ●       ●
 Gas pressure switches                                                                      ●        ●        ●       ●
 Servomotor driven sliding sleeve in mixing head                                            ●        ●        ●       ●
 Stepping motor for Gas /Air ratio control with W-FM100
      Stepping motor for air damper                                                         ●        ●        ●       ●
       Stepping motor for gas butterfly valve                                               ●        ●        ●       ●
       Stepping motor for regulating/sliding sleeve                                         ●        ●        ●       ●
 Oil pump, fitted                                                                           –        –        ●       ●
 Oil hoses                                                                                  ●        ●        ●       ●
 1 solenoid valve in supply and in return,
 nozzle head with shut off device (nozzle solenoid)                                         ●        ●        ●       ●
 Magnetic coupling                                                                          ●        ●        ●       ●
 Accessories
 Downward firing burner                                                                     ○        ○        ○       ○
 Intake flange for the connection of an air duct                                            ○        ○        ○       ○
 Solenoid valve for air pressure switch test for cont. run fan or post-purge                ○        ○        ○       ○
 Combustion head extension                                                                  ○        ○        ○       ○
 Speed control                                                                              ○        ○        ○       ○
 O2 trim                                                                                    ○        ○        ○       ○
 W-FM loose to fit into control panel                                                       ○        ○        ○       ○
 Separate pump station                                                                      ○        ○        ○       ○
 Separate preheater station (electric or media)                                             ○        ○        –       –
 ●     Scope of delivery
 ○     Accessories
38
Technical data
Dual fuel burners size 30 and 40, version NR
Technical data                                                                             RGL30/2-A          RGMS30/2-A
Burner motor 3~208 - 600V                                                       Model      W-D112/140-2/4K5   W-D112/140-2/4K5
Motor rating                                                                  HP (kW)      6.6 (5.0)          6.6 (5.0)
FLA at 460V                                                                         A      8.6                8.6
Speed (60 Hz)                                                                     rpm      3,510              3,510
Fan wheel                                                                    Colour / ø    red / 248 x 104    red / 248 x 104
Combustion manager                                                               Model     W-FM100            W-FM100
Ignition unit                                                                    Model     W-ZG02             W-ZG02
Stepping motor            Air                                                    Model     SQM45              SQM45
                          Mixing head                                            Model     SQM45              SQM45
                          Fuel                                                   Model     SQM45              SQM45
Pump, fitted                                                                     Model     TA3                TA3
Oil preheater                                                                  Model       –                  EV2D
                          Oil throughput                                   GPH (kg/h)      –                  72 (270)
                          Heat rating                                             kW       –                  13.2
Oil solenoid valves       55V 1/4” (supply)            20   W                    Model     121 K 6220         –
                          55V 1/8” (return)            20   W                    Model     121 K 2423         –
                          55V 3/8” (supply)            20   W                    Model     –                  321 H 2322
                          55V 3/8” (supply)            20   W                    Model     –                  121 G 2320
Oil pressure switches     1 – 10 bar (return #2 oil - 5 bar)                     Model     DSA 46 F001
                          1 – 10 bar (return #6 oil - 7 bar)                     Model     –                  DSA 46 F001
Oil hoses                                                       DN, length in inch (mm)    20/40” (1000)      –
(on RGMS, high pressure metal hoses)                            DN, lenght in inch (mm)    –                  20/51” (1300)
Burner weight                                                           approx. lbs (kg)   320 (145)          386 (175)
                                                                                                                                 39
Technical data
Dual fuel burners size 40 and 50, version NR
 Technical data                                                                            RGL40/2-A          RGMS40/2-A
 Burner motor 3~208 - 600V                            (40/2)                     Model     W-D112/170-2/7K0   W-D112/170-2/7K0
 Motor rating                                                                  HP (kW)     10.4 (7.8)         10.4 (7.8)
 FLA at 460V                                                                         A     14                 14
 Speed (60 Hz)                                                                     rpm     3,500              3,500
 Fan wheel                                                                   Colour / ø    red / 275 x 104    red / 275 x 104
 Combustion manager                                                              Model     W-FM100            W-FM100
 Ignition unit                                                                   Model     W-ZG02             W-ZG02
 Stepping motor            Air                                                   Model     SQM45              SQM45
                           Mixing head                                           Model     SQM45              SQM45
                           Fuel                                                  Model     SQM45              SQM45
 Pump, fitted                                                                    Model     TA3                TA3
 Oil preheater                                                                 Model       –                  EV2D
                           Oil throughput                                  GPH (kg/h)      –                  75 (270)
                           Heat rating                                            kW       –                  13.2
 Oil solenoid valves       55V 3/8” (supply)            20 W                     Model     321 H 2322         321 H 2322
                           55V 3/8” (return)            20 W                     Model     121 G 2320         121 G 2320
 Oil pressure switches     1 – 10 bar (return fuel oil EL - 5 bar)               Model     DSA 46 F001        –
                           1 – 10 bar (return fuel oil S - 7 bar)                Model     –                  DSA 46 F001
 Oil hoses                                                      DN, length in inch (mm)    20/40” (1000)      –
 (on RGMS, high pressure metal hoses)                           DN, length in inch (mm)    –                  20/51” (1300)
 Burner weight                                                          approx. lbs (kg)   419 (190)          419 (190)
40
Technical data
Dual fuel burners size 50 and 60, version NR
 Technical data                                                                              RGMS50/1-B          RGMS50/2-A
 Burner motor 3~208 - 600V                                                         Model     W-D132/170-2/9K0    W-D132/210-2/14K0
 Motor rating                                                                    HP (kW)     14.6 (11)           20 (15)
 FLA at 460V                                                                           A     19                  25
 Speed (60 Hz)                                                                       rpm     3,500               3,520
 Fan wheel                                                                         Colour    red                 red
                                                                                        ø    330 x 104.5         330 x 104.5
 Combustion manager                                                                Model     W-FM100             W-FM100
 Ignition unit                                                                     Model     W-ZG02              W-ZG02
 Stepping motor               Air                                                  Model     SQM45               SQM45
                              Mixing head                                          Model     SQM45               SQM45
                              Fuel                                                 Model     SQM45               SQM45
 Oil preheater                                                                   Model       WEV2.2/01 2)        WEV3/01
                              Oil throughput                                 GPH (kg/h)      82.5 (300)          137.5 (500)
                              Heat rating                                           kW       13.8                22.4
 Pump, fitted                                                                      Model     TA4C                T2C
 Oil solenoid valves          55V 3/8” (supply)                            20W     Model     321 H 2322          321 H 2322
                              55V 3/8” (return)                            20W     Model     121 G 2320          121 G 2320
 Oil pressure switch          1 – 10 bar (return #6 oil)                           Model     DSA 46 F001         DSA 46 F001
 Oil hoses                                                                    DN/length      25/59” (1500)       25/59” (1500)
 Burner weight                                                            approx. lbs (kg)   672 (305)           672 (305)
2)
     Burners above 82.5 GPH (300 kg/h): Oil preheater WEV3 in lieu of WEV2.2 (refer to Accessories)
2)
     Weight without pump and preheater stations
                                                                                                                                     41
Technical data
Dual fuel burners size 70, version NR
Technical data                                                                RGL70/1-B             RGL70/3-A
Burner motor 3~208 - 600V                                          Model      W-D160/240-2/18K0     W-D160/240-2/22K0
Motor rating                                                     HP (kW)      22 (16.5)             26.6 (20)
FLA at 460V                                                            A      30.5                  33
Speed (60 Hz)                                                        rpm      3,560                 3,550
Fan wheel                                                            Colour   green                 green
                                                                          ø   530 x 120             530 x 120
Combustion manager                                                   Model    W-FM100               W-FM100
Ignition unit                                                        Model    W-ZG02                W-ZG02
Stepping motor            Air                                        Model    SQM48                 SQM48
                          Mixing head                                Model    SQM45                 SQM45
                          Fuel                                       Model    SQM45                 SQM45
Pump, fitted                                                         Model    T2C (up to 173 GPH/ 600 kg/h)
                                                                     Model    T3C (from 173 GPH/ 600 kg/h)
Oil solenoid valves       55V 1/2” (supply)                    20W   Model    321 H 2522            321 H 2522
                          55V 1/2” (return)                    20W   Model    121 G 2520            121 G 2520
                          110V 3/8” (bypass)                   19W   Model    –                     –
Oil pressure switch       3 – 25 bar (supply - 18 bar)               Model    –                     –
                          1 – 10 bar (return #2 oil - 5 bar)         Model    DSA 46 F001           DSA 46 F001
                          1 – 10 bar (return #6 oil - 7 bar)         Model    –                     –
Oil hoses                                    DN, length in inch and (mm)      25/1300               25/1300
(on RGMS, high pressure metal hoses)         DN, length in inch and (mm)      –                     –
                                             DN, length in inch and (mm)      –                     –
Burner weight                                              approx. lbs (kg)   948 (430)             948 (430)
                                                                                                                                 43
Burner selection
Dual fuel burners size 50, version 1LN
                      Burner model                            RGL50/1-B, vers. ZM-1LN                                                           Burner model                  RGL50/2-A, vers. ZM-1LN
                      Combustion head                         G40/2-LN 217x35K                                                                  Combustion head               G50/2-LN 260x40
                      Capacity in MBH NG                      1,710 – 11,600                                                                    Capacity in MBH NG            2,050 – 16,725
                      MBH Propane                             1,710 – 11,600                                                                    MBH Propane                   2,730 – 16,725
                      GPH #2 oil                              19.5 – 82.8                                                                       GPH #2 oil                    21.3 – 119.4
 “WC                                                                                                                                 “WC
     9                                                                                                                                 9
8 8
7 7
                                                                                                                                       6
                                                                  High fire
     6
                                                                   range
     5                                                                                                                                 5
                                                                             High fire
     4                                                                                                                                 4
                                                                              range
                                                                                                                                                                                     High fire
     3                                                                                                                                 3
                                                                                                                                                                                      range
     2                                                                                                                                 2
1 1
0 0
-1 -1
     -2                                                                                                                               -2
          0   1,000    2,000   3,000   4,000     5,000    6,000     7,000    8,000      9,000   10,000 11,000 12,000 13,000 14,000         0   2,000        4,000    6,000   8,000      10,000        12,000   14,000   16,000         18,000
44
Burner selection
Dual fuel burners size 70, version 1LN
                  Burner model                       RGL70/1-B, vers. ZM-1LN                                                                       Burner model                             RGL70/2-A, vers. ZM-1LN
                  Combustion head                    G60/2-1LN 300x75                                                                              Combustion head                          G70/2-1LN 365x85
                  Capacity in MBH NG                 2,730 – 24,915                                                                                Capacity in MBH NG                       3,415 – 34,130
                  MBH Propane                        3,415 – 24,915                                                                                MBH Propane                              4,780 – 34,130
                  GPH #2 oil                         28.8 – 178                                                                                    GPH #2 oil                               46.3 – 243.8
“WC “WC
9 10
  8                                                                                                                                  9
                                                                                                                                     8
  7
                                                                                                                                     7
                                                         High fire
  6
                                                          range
                                                                                                                                     6
  5
                                                                                                                                     5
  4
                                                                                                                                     4
                                                                                   High fire
                                                                                                                                                                                                         High fire
  3
                                                                                    range
                                                                                                                                                                                                          range
  2
                                                                                                                                     2
  1                                                                                                                                  1
  0                                                                                                                                  0
-1 -1
 -2                                                                                                                                  -2
      0   2,000    4,000   6,000   8,000   10,000    12,000    14,000     16,000    18,000    20,000   22,000   24,000    26,000          0    3,000   6,000    9,000        12,000    15,000   18,000     21,000   24,000   27,000    30,000     33,000    36,000
GPH 20 40 60 80 100 120 140 160 180 GPH 25 50 75 100 125 150 175 200 225 250
                                                                                                                                                                                                                                                                 45
Scope of delivery/Accessories
Dual fuel burners size 50 and 70, version 1LN
 Scope of delivery                                                                                        RGL50   RGL70
 Burner housing, hinge flange, housing cover, Weishaupt burner motor, air regulator housing, fan wheel,
 combustion head, ignition unit, ignition cable, ignition electrode, nozzle assembly with oil nozzle/s,
 combustion manager with operating unit, flame sensor stepping motors, flange gasket,
 limit switch on hinge flange, fixing screws                                                              ●       ●
 Combustion manager W-FM100                                                                               ●       ●
 Two safety gas valves                                                                                    ●       ●
 Gas butterfly valve                                                                                      ●       ●
 Ignition pilot                                                                                           ●       ●
 Air pressure switch                                                                                      ●       ●
 Oil pressure switch in return                                                                            ●       ●
 Gas pressure switches                                                                                    ●       ●
 Adjustable regulating sleeve in mixing head                                                              ●       –
 Adjustable flame tube in mixing head                                                                     –       ●
 Stepping motor for Gas/Air ratio control with W-FM100
      Stepping motor for air regulator                                                                    ●       ●
       Stepping motor for gas butterfly valve                                                             ●       ●
       Stepping motor for oil regulator                                                                   ●       ●
 Oil pump, fitted                                                                                         ●       ●
 Oil hoses                                                                                                ●       ●
 2 oil solenoid valves, 1 safety valve, two stage nozzle head with shut off device (nozzle solenoid)      ●       ●
 Magnetic coupling                                                                                        ●       ●
 Accessories
 Downward firing burner                                                                                   ○       ○
 Intake flange for the connection of an air duct                                                          ○       ○
 Solenoid valve for air pressure switch test for cont. run fan or post-purge                              ○       ○
 Combustion head extension                                                                                ○       ○
 Speed control                                                                                            ○       ○
 O2 trim                                                                                                  ○       ○
 W-FM loose to fit into control panel                                                                     ○       ○
 ●     Scope of delivery
 ○     Accessories
46
Technical data
Dual fuel burners size 50 and 70, version 1LN
Technical data                                                               RGL50/1-B            RGL50/2-A
Burner motor 3~208 - 600V                                          Model     W-D132/170-2/9K0     W-D132/210-2/14K0
Motor rating                                                     HP (kW)     14.6 (11)            20 (15)
FLA at 460V                                                            A     19                   25
Speed (60 Hz)                                                        rpm     3,500                3,520
Fan wheel                                                          Colour    red                  red
                                                                        ø    330 x 104.5          330 x 104.5
Combustion manager                                                 Model     W-FM100              W-FM100
Ignition unit                                                      Model     W-ZG02               W-ZG02
Stepping motor           Air                                       Model     SQM45                SQM45
                         Fuel                                      Model     SQM45                SQM45
Pump, fitted                                                       Model     TA4C                 T2C
Oil solenoid valves      55V 3/8” (supply)                20 W     Model     321 H 2322           321 H 2322
                         55V 3/8” (return)                20 W     Model     121 G 2320           121 G 2320
Oil pressure switch      1 – 10 bar (return - 5 bar)               Model     DSA 46 F001          DSA 46 F001
Oil hoses                                     DN, length in inch and (mm)    25/51” (1300)        25/51” (1300)
Burner weight                                             approx. lbs (kg)   508 (230)            508 (230)
                                                                                                                      47
       ®
multiflam Burners
multiflam® principle:
emission reduction as standard
                                                  ppm                                                       ppm
100 100
90 90
80 80
70 70
60 60
                                                                                                                                    NOx
                                                50                                                       50
                                                40                                                       40
The multiflam® flame shows efficient
combustion
                                                30                                                       30
                                                                                 NOx
                                                                                                                   CO
into the market. Unprecedented low
                                                                CO
                                                10                                                        10
emission values stunned the industry.
With the patented mixing head,
Weishaupt was able to reduce the                                       Gas                                              #2 Oil
Nitrous Oxide emissions (NOx) for
medium and large burners to values           Example values for hot water plant depend on the combustion chamber
normally only seen with compact
burners. Weishaupt has set the stan-
dards with values below 60 ppm for #2
oil and 30 ppm for natural gas, depend-                                                                                  Secondary nozzle 1
ing on the relevant combustion cham-
ber geometry.                                                                                                            Secondary nozzle 2
50
Burner selection
Oil burners size 30 to 50, vers. 3LN – multiflam®
                      Burner model                                          RL30/2-A, version 3LN                                                                                Burner model                            RL40/2-A, version 3LN
                      Combustion head                                       M30/2-4a                                                                                             Combustion head                         M40/2-4A
                      Capacity in MBH                                       1,025– 7,320                                                                                         Capacity in MBH                         1,620 – 10,170
                      Capacity in GPH#2                                     7.3– 52.3                                                                                            Capacity in GPH#2                       11.6 – 72.6
“WC                                                                                                                                                        “WC
6 7
5 6
                                                                                                                                                             5
  4
                                                                                                                                                             4
  3
                                                                                                                                                             3
                                                                      High fire
                                                                                                                                                                                                                             High fire
  2
                                                                       range
                                                                                                                                                                                                                              range
                                                                                                                                                             2
  1
                                                                                                                                                             1
  0
                                                                                                                                                             0
-1 -1
 -2                                                                                                                                                         -2
      0   500         1,000 1,500        2,000   2,500     3,000 3,500           4,000 4,500        5,000 5,500   6,000 6,500   7,000      7,500   8,000         0       1,000    2,000   3,000   4,000     5,000    6,000    7,000     8,000    9,000   10,000   11,000   12,000    13,000
GPH#2 10 20 30 40 50 GPH#2 10 20 30 40 50 60 70 80 90
                      Burner model                                          RL50/1-B, version 3LN                                                            Burner model                      Vers.                                                      Order No.
                      Combustion head                                       M50/1-4a
                      Capacity in MBH                                       1,825 – 12,800                                                                   RL30/2-A                          3LN                                                        211 305 24
                      Capacity in GPH#2                                     13 – 91.4                                                                        RL40/2-A                          3LN                                                        211 405 24
“WC
  9
                                                                                                                                                             RL50/1-B                          3LN                                                        211 504 24
  8
  3
                                                                              range
  1
                                                                                                                                                            The capacity graphs are based on air temperature of
  0
                                                                                                                                                            68F (20 °C) an installation altitude of 1,640 ft (500 m)
 -1
                                                                                                                                                            above sea level. A reduction of burner capacity of 1 %
 -2                                                                                                                                                         for every 325 ft (100 m) should be taken into
      0       1,000    2,000        3,000    4,000       5,000    6,000          7,000      8,000    9,000   10,000 11,000 12,000 13,000 14,000
                                                                                                                                                            consideration depending on installation altitude.
      GPH#2       10                20           30              40               50            60           70         80            90
                                                                                                                                                                                                                                                                                          51
Scope of delivery / Accessories / Technical data
Oil burners size 30 to 50, version 3LN
 Scope of delivery                                                                         RL30                    RL40                 RL50
 Burner housing, hinge flange, housing cover, Weishaupt burner motor,
 air regulator housing, fan wheel, combustion head, ignition unit, ignition cable,
 ignition electrodes, combustion manager with operating unit, UV flame sensor,
 stepping motors, flange gasket, limit switch on hinge flange,
 fixing screws                                                                             ●                       ●                    ●
 Combustion manager W-FM100                                                                ●                       ●                    ●
 Oil pressure switch in return                                                             ●                       ●                    ●
 Oil pump, fitted                                                                          ●                       ●                    ●
 Oil hoses                                                                                 ●                       ●                    ●
 Accessories
 Intake flange for the connection of an air duct                                           ○                       ○                    ○
 Combustion head extension                                                                 ○                       ○                    ○
 Speed control                                                                             ○                       ○                    ○
 O2 trim                                                                                   ○                       ○                    ○
 W-FM loose to fit into control panel                                                      ○                       ○                    ○
 ●     Scope of delivery
 ○     Accessories
52
Burner selection
Gas burners size 30 and 50, version 3LN
                    Burner model            G30/2-A, version 3LN                                                                                          Burner model            G40/2-A, version 3LN
                    Combustion head         G30/2-3LN                                                                                                     Combustion head         G40/2-3LN
                    Capacity in MBH Nat Gas 1,025 – 6,825                                                                                                 Capacity in MBH Nat Gas 1,365 – 9,555
“WC “WC
6 7
                                                                                                                                              6
  5
                                                                                                                                              5
  4
                                                                                                                                              4
  3
                                                                                                                                              3
  2
                                                          High fire
                                                                                                                                                                                                            High fire
                                                                                                                                              2
                                                           range
                                                                                                                                                                                                             range
  1
                                                                                                                                              1
  0
                                                                                                                                              0
-1 -1
 -2                                                                                                                                          -2
      0     500     1,000 1,500   2,000   2,500    3,000 3,500       4,000 4,500        5,000 5,500   6,000 6,500   7,000   7,500   8,000         0     1,000    2,000     3,000      4,000       5,000        6,000      7,000     8,000    9,000   10,000
      MBH                                                                                                                                         MBH
                    Burner model            G50/1-B, version 3LN                                                                                          Burner model            G50/2-A, version 3LN
                    Combustion head         G50/1-3LN                                                                                                     Combustion head         G50/2-3LN
                    Capacity in MBH Nat Gas 1,535 – 11,945                                                                                                Capacity in MBH Nat Gas 1,710 – 15,360
“WC                                                                                                                                         “WC
  9                                                                                                                                           9
  8                                                                                                                                           8
7 7
  6                                                                                                                                           6
  5                                                                                                                                           5
  4                                                                                                                                           4
                                                                                                                                                                                              High fire
                                                                             High fire
  3                                                                                                                                           3
                                                                                                                                                                                               range
                                                                              range
  2                                                                                                                                           2
  1                                                                                                                                           1
  0                                                                                                                                           0
 -1                                                                                                                                          -1
 -2                                                                                                                                          -2
      0     1,000    2,000   3,000    4,000       5,000     6,000    7,000   8,000       9,000   10,000 11,000 12,000 13,000 14,000               0      2,000     4,000      6,000       8,000           10,000       12,000     14,000    16,000   18,000
      MBH                                                                                                                                         MBH
Burner model                      Vers.                                                                Order No.                             The capacity graphs are based on air temperature
G30/2-A                           3LN                                                                  217 305 08                            of 68F (20 °C) an installation altitude at sea level. A
                                                                                                                                             reduction of burner capacity of 1 % for every 325 ft
G40/2-A                           3LN                                                                  217 405 10
                                                                                                                                             (100 m) should be taken into consideration in case
G50/1-B                           3LN                                                                  217 504 10                            of installation altitude above 0 ft.
G50/2-A                           3LN                                                                  217 505 44
                                                                                                                                             Voltages and frequencies:
                                                                                                                                             The burners are equipped with three phase motor in 208 -
                                                                                                                                             600 V, 60 Hz as standard. Different voltage and frequency
                                                                                                                                             are available upon request.
                                                                                                                                                                                                                                                          53
Burner selection
Gas burners size 60 and 70, version 3LN
                    Burner model            G60/2-A, version 3LN                                                                                             Burner model            G70/1-B, version 3LN
                    Combustion head         G60/2-3LN                                                                                                        Combustion head         G70/1-3LN
                    Capacity in MBH Nat Gas 2,220 – 19,795                                                                                                   Capacity in MBH Nat Gas 2,560 – 23,890
 “WC                                                                                                                                     “WC
     9                                                                                                                                     9
8 8
7 7
6 6
5 5
4 4
                                                                                                                                                                                                        High fire
                                                                              High fire
3 3
                                                                                                                                                                                                         range
                                                                               range
2 2
1 1
0 0
-1 -1
     -2                                                                                                                                   -2
          0     2,000    4,000     6,000      8,000       10,000   12,000        14,000           16,000     18,000    20,000   22,000         0     2,000    4,000   6,000   8,000   10,000   12,000    14,000    16,000   18,000   20,000   22,000   24,000   26,000
          MBH                                                                                                                                  MBH
 “WC
     10
     9
                                                                                                                                          The capacity graphs are based on air temperature
     8                                                                                                                                    of 68F (20 °C) an installation altitude at sea level. A
     7                                                                                                                                    reduction of burner capacity of 1 % for every 325 ft
     6
                                                                                                                                          (100 m) should be taken into consideration in case
     5
     4
                                                                                                                                          of installation altitude above 0 ft.
                                                                   High fire
                                                                    range
     -1
                                                                                                                                          600 V, 60 Hz as standard. Different voltage and frequency
     -2
                                                                                                                                          are available upon request.
          0     3,000   6,000    9,000     12,000     15,000   18,000    21,000          24,000     27,000    30,000   33,000   36,000
          MBH
                                                                                                                                          Standard burner motor:
 Fuels – capacity with                                                                                                                    Insulation class F, protection IP 55.
 combustion head       open                                             close
 Nat gas
54
Scope of delivery/Accessories
Gas burners size 30 to 70, version 3LN
Scope of delivery                                                                          G30   G40   G50   G60   G70
Burner housing, hinge flange, housing cover, Weishaupt burner motor, air regulator
housing, fan wheel, combustion head, ignition unit, ignition cable, ignition electrodes,
combustion manager with operating unit, UV flame sensor, stepping motors,
flange gasket, limit switch on hinge flange, fixing screws                                 ●     ●     ●     ●     ●
Combustion manager W-FM100                                                                 ●     ●     ●     ●     ●
Two safety gas shut off valves                                                             ●     ●     ●     ●     ●
Ignition pilot                                                                             ●     ●     ●     ●     ●
Air pressure switch                                                                        ●     ●     ●     ●     ●
Gas pressure switch                                                                        ●     ●     ●     ●     ●
Ratio controlled sliding sleeve in mixing head                                             ●     ●     ●     ●     ●
Stepping motor for
     Air regulator                                                                         ●     ●     ●     ●     ●
      Gas butterfly valve                                                                  ●     ●     ●     ●     ●
      Mixing head                                                                          ●     ●     ●     ●     ●
Accessories
Intake flange for the connection of an air duct                                            ○     ○     ○     ○     ○
Combustion head extension                                                                  ○     ○     ○     ○     ○
Speed control                                                                              ○     ○     ○     ○     ○
O2 trim                                                                                    ○     ○     ○     ○     ○
W-FM loose to fit into control panel                                                       ○     ○     ○     ○     ○
●     Scope of delivery
○     Accessories
                                                                                                                         55
Technical data
Gas burners size 30 to 70, version 3LN
 Technical data                                           G30/2-A 3LN        G40/2-A 3LN        G50/1-B 3LN        G50/2-A 3LN
 Burner motor 3~208 - 600V                    Model       W-D112/140-2/4K5   W-D112/170-2/7K0   W-D132/170-2/9K0   W-D132/210-2/14K0
 Motor rating                                HP (kW)      6.6 (5.0)          10.4 (7.8)         14.6 (11)          20 (15)
 FLA at 460V                                       A      8.6                14                 19                 25
 Speed (60 Hz)                                   rpm      3,510              3,500              3,500              3,520
 Fan wheel                                      Colour    red                red                red                red
                                                     ø    248 x 104          275 x 104          330 x 104.5        330 x 104.5
 Combustion manager                             Model     W-FM100            W-FM100            W-FM100            W-FM100
                                                Model     W-FM200            W-FM200            W-FM200            W-FM200
 Ignition unit                                  Model     W-ZG02             W-ZG02             W-ZG02             W-ZG02
 Stepping motor          Air                    Model     SQM45              SQM45              SQM45              SQM45
                         Fuel                   Model     SQM45              SQM45              SQM45              SQM45
                         Mixing head            Model     SQM48              SQM48              SQM48              SQM48
 Burner weight                         approx. lbs (kg)   320 (145)          353 (160)          518 (235)          530 (240)
56
Burner selection
Dual fuel burners size 30 and 40, version 3LN
                 Burner model                           RGL30/2-A, version 3LN                                                                        Burner model                       RGL40/2-A, version 3LN
                 Combustion head                        G30/2-3LN                                                                                     Combustion head                    G40/2-3LN
                 Capacity in MBH NG                     1,025 – 6,825                                                                                 Capacity in MBH NG                 1,365 – 9,555
                 MBH #2                                 1,220 – 6,825                                                                                 MBH #2                             1,625 – 9,555
                 GPH #2 oil                             8.7 – 49                                                                                      GPH #2 oil                         11.6 – 68.2
“WC “WC
6 7
                                                                                                                                       6
  5
                                                                                                                                       5
  4
                                                                           fire
                                                               range range
                                                                                                                                       4
  3
                                                              High fireHigh
                                                                                                                                       3
  2
                                                                                                                                                                                                   High fire
                                                                                                                                       2
                                                                                                                                                                                                    range
  1
                                                                                                                                       1
  0
                                                                                                                                       0
-1 -1
 -2                                                                                                                                   -2
      0    500   1,000 1,500   2,000   2,500    3,000 3,500       4,000 4,500    5,000 5,500   6,000 6,500   7,000   7,500   8,000         0        1,000        2,000   3,000   4,000     5,000        6,000   7,000   8,000        9,000   10,000
GPH #2 10 20 30 40 50 GPH #2 10 20 30 40 50 60 70
                                                                                                                                                                                                                                                  57
Burner selection
Dual fuel burners size 50, version 3LN
                      Burner model                            RGL50/1-B, version 3LN                                                                         Burner model                   RGL50/2-A, version 3LN
                      Combustion head                         G50/1-3LN                                                                                      Combustion head                G50/2-3LN
                      Capacity in MBH NG                      1,540 – 11,945                                                                                 Capacity in MBH NG             1,710 – 15,360
                      MBH #2                                  1,830 – 11,945                                                                                 MBH #2                         2,030 – 15,360
                      GPH #2 oil                              13 – 85                                                                                        GPH #2 oil                     14.5 – 109.7
 “WC                                                                                                                                       “WC
     9                                                                                                                                       9
8 8
7 7
     6                                                                                                                                       6
                                                                          High fire
                                                                  High fire range
5 5
4 4
                                                                                                                                                                                            High fire
     3                                                                                                                                       3
                                                                                                                                                                                             range
                                                                   range
2 2
1 1
0 0
-1 -1
     -2                                                                                                                                     -2
          0   1,000    2,000   3,000   4,000     5,000    6,000       7,000          8,000    9,000   10,000 11,000 12,000 13,000 14,000         0       2,000        4,000   6,000        8,000       10,000        12,000    14,000     16,000         18,000
58
Burner selection
Dual fuel burners size 60 and 70, version 3LN
                   Burner model                                   RGL60/2-A, version 3LN                                                                                       Burner model                         RGL70/1-B, version 3LN
                   Combustion head                                G60/2-3LN                                                                                                    Combustion head                      G70/1-3LN
                   Capacity in MBH NG                             2,220 – 18,770                                                                                               Capacity in MBH NG                   2,560 – 23,890
                   MBH #2                                         3,655 – 18,770                                                                                               MBH #2                               4,065 – 23,890
                   GPH #2 oil                                     26 – 134                                                                                                     GPH #2 oil                           29 – 170
“WC “WC
9 9
8 8
  7                                                                                                                                                       7
                                                                     High fire
  6                                                                                                                                                       6
                                                                      range
5 5
4 4
                                                                                                                                                                                                                             High fire
                                                                                         High fire
3 3
                                                                                                                                                                                                                              range
                                                                                          range
2 2
1 1
0 0
-1 -1
 -2                                                                                                                                                      -2
      0        2,000         4,000     6,000          8,000      10,000         12,000      14,000         16,000     18,000         20,000    22,000         0        2,000    4,000   6,000   8,000     10,000    12,000   14,000     16,000    18,000   20,000   22,000   24,000    26,000
GPH #2 20 40 60 80 100 120 140 GPH #2 20 40 60 80 100 120 140 160 180
                   Burner model                                   RGL70/2-A, version 3LN                                                                 The stated oil throughputs in GPH refer to #2 oil with a
                   Combustion head                                G70/2-3LN
                   Capacity in MBH NG                             3,075 – 31,055                                                                         calorific value of 140,000 BTU/Gal.
                   MBH #2                                         5,285 – 31,055
                   GPH #2 oil                                     37.7 – 221.8                                                                           The capacity graphs are based on air temperature of
                                                                                                                                                         68F (20 °C) and installation at sea level. A reduction of
                                                                                                                                                         burner capacity of 1 % for every 325 ft (100 m) should
“WC
 10
                                                                                                                                                         be taken into consideration depending on installation
  9                                                                                                                                                      altitude.
  8
  7
                                                                                                                                                         Voltages and frequencies:
                                                                     High fire
                                                                      range
  5
                                                                                                                                                         The burners are equipped with three phase motor in 208 -
  4                                                                                                                                                      600 V, 60 Hz as standard. Different voltage and frequency
                                                                            High fire
  2
  1
  0
                                                                                                                                                         Standard burner motor:
 -1                                                                                                                                                      Insulation class F, protection IP 55.
 -2
      0        3,000        6,000    9,000        12,000    15,000    18,000        21,000      24,000       27,000       30,000     33,000    36,000
                                                                                                                                                                                                                                                                                            59
Scope of delivery/Accessories
Dual fuel burners size 30 and 70, version 3LN
 Scope of delivery                                                                           RGL30   RGL40   RGL50   RGL60   RGL70
 Burner housing, hinge flange, housing cover, Weishaupt burner motor, air regulator
 housing, fan wheel, combustion head, ignition unit, ignition cable, ignition electrodes,
 atomising system with oil nozzle/s, combustion manager with operating unit, flame sensor,
 stepping motors, flange gasket, limit switch on hinge flange, fixing screws                 ●       ●       ●       ●       ●
 Combustion manager W-FM100                                                                  ●       ●       ●       ●       ●
 Two gas shut off valves                                                                     ●       ●       ●       ●       ●
 Ignition pilot                                                                              ●       ●       ●       ●       ●
 Gas butterfly valve                                                                         ●       ●       ●       ●       ●
 Air pressure switch                                                                         ●       ●       ●       ●       ●
 Gas pressure switches                                                                       ●       ●       ●       ●       ●
 Ratio control sliding sleeve in mixing head                                                 ●       ●       ●       ●       ●
 Stepping motor for
      Air regulator                                                                          ●       ●       ●       ●       ●
       Gas butterfly valve                                                                   ●       ●       ●       ●       ●
       Mixing head                                                                           ●       ●       ●       ●       ●
 Accessories
 Intake flange for the connection of an air duct                                             ○       ○       ○       ○       ○
 Solenoid valve for air pressure switch test for cont. run fan or post-purge                 ○       ○       ○       ○       ○
 Combustion head extension                                                                   ○       ○       ○       ○       ○
 Speed control                                                                               ○       ○       ○       ○       ○
 O2 trim                                                                                     ○       ○       ○       ○       ○
 W-FM loose for installation in a remote control panel                                       ○       ○       ○       ○       ○
 ●     Scope of delivery
 ○     Accessories
60
Technical data
Dual fuel burners size 30 to 50, version 3LN
Technical data                                                          RGL30/2-A 3LN       RGL40/2-A 3LN
Burner motor 3~208 - 600V                                    Model      W-D112/140-2/4K5    W-D112/170-2/7K0
Motor rating                                               HP (kW)      6.6 (5.0)           10.4 (7.8)
FLA at 460V                                                      A      8.6                 14
Speed (60 Hz)                                                  rpm      3,510               3,500
Fan wheel                                                     Colour    red                 red
                                                                   ø    248 x 104           275 x 104
Combustion manager                                            Model     W-FM100 / W-FM200   W-FM100 / W-FM200
Ignition unit                                                 Model     W-ZG02              W-ZG02
Stepping motor            Air                                 Model     SQM45               SQM45
                          Fuel                                Model     SQM45               SQM45
                          Mixing head                         Model     SQM48               SQM48
Pump, fitted                                                  Model     TA3C                TA3C
Oil solenoid valves       55V (supply)                        Model     121 K 6220          321 H 2322
                          55V (return)                        Model     121 K 6220          121 G 2320
Oil pressure switch       1 – 10 bar                          Model     DSA 46 F001         DSA 46 F001
(return #2 oil - 5 bar)
Oil hoses                                    DN, length in inch (mm)    20/40” (1000)       20/40” (1000)
Burner weight                                        approx. lbs (kg)   320 (145)           353 (160)
                                                                                                                61
Technical data
Dual fuel burners size 60 and 70, version 3LN
 Technical data                                                          RGL60/2-A 3LN           RGL70/1-B 3LN         RGL70/2-A 3LN
 Burner motor 3~208 - 600V                                    Model      W-D132/210-2/14K0       W-D160/240-2/18K0     W-D160/240-2/22K0
 Motor rating                                               HP (kW)      20 (15)                 22 (16.5)             26.6 (20)
 FLA at 460V                                                      A      28                      30.5                  33
 Speed (60 Hz)                                                  rpm      3,520                   3,560                 3,550
 Fan wheel                                                 Colour / ø    no color / 450 x 127.5-R green / 530 x 120    green / 530 x 120
 Combustion manager                                            Model     W-FM100 /               W-FM100 /             W-FM100 /
                                                                         W-FM200                 W-FM200               W-FM200
 Ignition unit                                                 Model     W-ZG02                  W-ZG02                W-ZG02
 Stepping motor            Air                                 Model     SQM45                   SQM45                 SQM45
                           Fuel                                Model     SQM45                   SQM45                 SQM45
                           Mixing head                         Model     SQM48                   SQM48                 SQM48
 Pump, fitted                                                  Model     T2C                     T2C (up to            T3C
                                                                                                 130 GPH / 450 kg/h)
                                                                                                 T3C (from
                                                                                                 130 GPH / 450 kg/h)
 Oil solenoid valves       55V (supply)                        Model     321 H 2322              321 H 2522            321 H 2522
                           55V (return)                        Model     121 G 2320              121 G 2520            121 G 2520
 Oil pressure switch       1 – 10 bar                          Model     DSA 46 F001             DSA 46 F001           DSA 46 F001
 (return #2 oil - 5 bar)
 Oil hoses                                DN, length in inch and (mm)    25/51” (1300)           25/51” (1300)         25/51” (1300)
 Burner weight                                        approx. lbs (kg)   728 (330)               960 (435)             960 (435)
62
Oil burner dimensions
Size 30 to 70
                      d1
                                                                        h1
                                                                                     b 4 d2                                                                 b1
                 h3                                                                                                                  r2
                                                                                                                                                       b2
                                                                                                                      r1
                   approx. 10.4
                                                            d5
                   (264 mm)*
l3 l1
                                                                   d7
* depending on oil preheater                                       d6
                                                                                                                                                                 63
Oil burner dimensions
Size 30 to 70
                        d1
                                                                                h1
                                                                                             b 4 d2                                                           b1
                   h3                                                                                                                       r2
                                                                                                                                                         b2
                                                                                                                                  r1
                     approx. 10.4
                                                                     d5
                     (264 mm)*
l3 l1
                                                                           d7
 * depending on oil preheater                                              d6
64
Gas burner dimensions
Size 30 to 70
d5
                                                                                           b 4 d 1 d2                                     r2                            b1
                                                           h1
                                                                                                                                                                   b2
h3
                                                                         d7
                                                                         d6                                                          r1
                l10
                                                                                                         l3          l9
                                                                                                                                    l1
                                                                                                                                                                         65
Gas burner dimensions
Size 30 to 70
d5
                                                                                           b 4 d 1 d2                                     r2                             b1
                                                           h1
                                                                                                                                                                    b2
h3
                                                                         d7
                                                                         d6                                                          r1
                l10
                                                                                                         l3          l9
                                                                                                                                    l1
66
Dual fuel burner dimensions
Size 30 to 70
d5
                                                                                                                                                                   b1
                                                                                                                                         r2
                                                                                            b4 d1 d2
                                                             h1
                                                                                                                                                              b2
     h3                                                                       d7
                                                                              d6                                                     r1
                      l10
                                                                                                          l3           l9
                                                                                                                                     l1
                                                                                                                                                                        67
Dual fuel burner dimensions
Size 30 to 70
d5
                                                                                                                                                                 b1
                                                                                                                                       r2
                                                                                             b4 d1 d2
                                                              h1
                                                                                                                                                            b2
      h3                                                                       d7
                                                                               d6                                                  r1
                       l10
                                                                                                           l3           l9
                                                                                                                                   l1
68
Fuel systems
GL30Z (oil side)                              GL30T/GL40T/L50T (oil side)                 RGL30 (oil side)
110V
10 11 12 17 16 10 11 12 16 10 11 12 17 18a 16
                                                                                                                                                  69
Fuel systems
 RGMS60/70 (oil side)                                                  RL30 to RL50 vers. 3LN
 With separate pump and preheater stations                             RGL30 to RGL70 vers. 3LN (oil side)
10 17 11 18b 14b 12 16 10 11 12 12
P 16
                                 110V
                                                                                                                                          16
                                                                                         55V          55V
                                  55V
                                                                                                            P    M                        16
                                                  P        M
                    6        7                        4b       9
                                                                                                  6         7         4b   9       The gas train schematics show typical con-
                                                                                                                                   figuration for UL gas train. The actual gas
                                                                                                                                   train shipped with burner might have differ-
                                                                                                                                   ent configuration depending on applicable
                                                                                                                                   code and regulation.
                                                                   8
                        P                                      P                                        P                  P
1 2 3 4 1 5 1 2 3 4 1 5
 Legend
 1   Ball valve                                                        11        Strainer                                          14a Oil pressure switch in return
 2   Gas pressure regulator                                            12        Oil solenoid valve, normally closed (55V con-     14b Oil pressure switch in supply (optional, not
 3   Low gas pressure switch                                                     nected in series with 12a)                            shown)
 4   Double main SSOV                                                  12a       Oil solenoid valve, normally closed               15 Oil regulator
 4b Pilot gas valves                                                             (55V connected in series with 12, installed       16 Nozzle head with shut off device
 5   High gas pressure switch                                                    against the flow direction)                       16a Nozzle head without shut off device
 6   Pilot train ball valve                                            12b       Bypass solenoid valve, normally open              17 Oil preheater
 7   Pilot gas pressure regulator                                      13        Oil solenoid valve, normally closed               18a Temperature switch
 8   Gas butterfly valve                                               13a       Oil solenoid valve, normally closed               18b Temperature sensor Pt 100
 9   Burner                                                                      for stage 1, 2 and 3                                  (to monitor minimum oil temperature)
 10 Oil pump                                                           13b       Oil solenoid valve, normally open                 19 External oil filter 1
70
Pump and preheater stations
Scope of delivery – pump station              medium used.                                Planning and installation
Pump unit (screw spindle pump with            When selecting and sizing, please refer     instructions
motor), pressure gauge, vacuum gauge,         to the oil temperature diagrams in          Oil filter, air/gas separator, circulation
pressure regulating valve, ball valves,       chapter 5.3 of the technical brochure       tank, pump station and oil preheater
suction flange, pressure flange               “Weishaupt electric and medium oil          station must be installed as close as
including counter flanges, screws and         preheaters”, print No. 18. Weishaupt        possible to the burner.
washers, suction side filter. All parts are   medium oil preheaters can be used
fully assembled on an oil drip tray.          universally. It is possible to change the   On burners with separate oil preheater
                                              medium at any time. The preheaters are      the time required for oil circulation
The pump station is built as one of two       used either alone or in conjunction with    during start up depends on the length
different versions - either as a single       an electric oil preheater.                  of the pipework between the burner
station unit with one pump, or as a twin                                                  and the air/gas separator or circulation
station unit with two pumps with one          If operating steam at more than 110 PSI     tank.
pump serves as a backup unit. Should          or hot water between 360 F (180 °C)
one pump fail, it is possible to quickly      and 390 F (200 °C) is continuously          The shorter the pipeline, the shorter the
switch over to the other.                     available, then an electric preheater       period between heat being called for
                                              is not required. This is also possible if   and oil release and burner start after a
Only tried and tested makes of pump           installation with the above minimum         controlled shutdown.
are used. The pumps are carefully             pressures or temperatures can be
matched to the capacity of the burner.        operated with #2 oil or gas.
                                                                                                                                   71
Pump and preheater stations
 Specification
 Burner           Technical data - Pump                                     Version with 1 pump             Version with 2 pumps
 Rating           Flow rate in GPH (l/h) Speed     Motor rating             Pump model                      Pump model
 GPH              (based on 150cSt)      rpm       HP (kW)
 Pump stations - frequency 60 Hz
  74 – 114        265 (1,020)           3,400      2.9 (2.2)                SPF 10-38                       SPZ 10-38
 114 – 214        532 (2,050)           3,400      3.4 (2.6)                SPF 20-38                       SPZ 20-38
214 – 265 705 (2,720) 3,400 5.3 (4.0) SPF 20-46 SPZ 20-46
72
That is not a Facade. Weishaupt has been one of the
leading company in heating and combustion industry
since years with headquarter in Schwendi and branches
all over the world. That is Reliability.
                    Weishaupt is               Trustworthy, quality,
                    Reliability.               good customer service,
                    The family business        innovation and experi-
                    in Schwendi was            ence are values on
                    established by Max         which the Pioneer Max
                    Weishaupt in 1932.         Weishaupt established
                    Represented in 55          his company. All this
                    countries by branch        combined in a word is
                    offices and subsidiaries   reliability.
                    Weishaupt is interna-
                    tional leader in the       Therefore stands
                    areas of combustion        Weishaupt today.
                    technology and heating
                    applications.
                                                                        73
                                                                        73
That is not an Imagination. Continuous research
and development at Weishaupt ensure environ-
mental friendly and efficient burners.
That is Reliability.
74
Developing improvement.
Weishaupt recognizes the signs of time
and researches perpetually to get more
efficient and environmental friendly
burner systems.
                                          75
                                                                                       Weishaupt Corporation
                                                                                       6280 Danville Road
                                                                                       Mississauga, ON L5T 2H7, Canada
                                                                                       Ph: (905) 564 0946
                                                                                       Fax: (905) 564 0949
                                                                                       www.weishaupt-corp.com