product

Information on oil, gas and dual fuel burners

Industrial burners
Industrial burners sizes 30 to 70 • flexible and reliable
Weishaupt Industrial Burners:
Flexible and reliable
For more than 50 years, Weishaupt industrial burners have set
global standards in terms of reliability, energy efficiency, noise
levels and ease of use.

With firing rate between 3,400 and 40,000 MBH, the spectrum
of application possibilities covers from heating and steam boilers
to air heaters and modern high efficiency boilers.

With its wide range of industrial burners, which can be used with
almost any gaseous or liquid fuel, Weishaupt has the right burner
for virtually any job.

Digital combustion management, included as standard with


industrial burners, contributes not only to the economical use
of oil and gas, but also simplifies the operation and servicing
of the burner. Moreover, the integration into various monitoring
and control systems and into complete building management
systems is made possible.

The clear layout of the burners with their easily accessible


components enables quick and reliable service and therefore
also faster commissioning.

Selected materials combined with experience gained over


decades in a modern research and development centre and
an extensive service network guarantee Weishaupt proverbial
reliability.

2
3
Burner housing can
Burner motor be hinged open to the
left or to the right
Air pressure switch

Mixing head

Flame sensor

Digital combustion manager


with display and operating
unit ABE

Stepping motor for


sliding sleeve

Stepping motor for air


damper control

Fan wheel
Index of contents

Oil burners version Standard multiflam® oil burners version 3LN 50


Burner selection 10 Burner selection 51
Scope of delivery / Accessories 14 Scope of delivery / Accessories /
Technical data 15 Technical data 52

multiflam® gas burners version 3LN


Gas burners NR Burner selection 53
Burner selection 20 Scope of delivery / Accessories 55
Scope of delivery / Accessories 22 Technical data 56
Technical data 23
multiflam® dual fuel burners version 3LN
Gas burners 1LN Burner selection 57
Burner selection 24 Scope of delivery / Accessories 60
Scope of delivery / Accessories/ Technical data 61
Technical data 25

Gas burners LN Dimensions 63


Burner selection 26
Scope of delivery / Accessories 28
Technical data 29 Fuel systems 69

Dual fuel burners NR Pump and preheater station 71


Burner selection 32
Scope of delivery / Accessories 37
Technical data 39

Dual fuel burners 1LN


Burner selection 44
Scope of delivery / Accessories 46
Technical data 47

5
Weishaupt industrial burners sizes 30 to 70
High capacity and flexible application range
Weishaupt industrial burners have Applicable fuels The most important advantages:
been especially designed for • Light oil #2 • Large capacity and application range
industrial applications. The viscosity up to 6 cSt (6 mm2/s) at • Stable fan characteristics
monobloc burners are noteworthy 68F (20 °C) to ASTM D396 • Good combustion behaviour
for their large capacity and • Medium #4 to heavy fuel #6 oil • Burner housing can be hinged open
operational ranges and numerous viscosity up to 50 cSt (50 mm2/s at • Easy installation, commissioning and
technical details: 212F (100 °C) to ASTM D396 service
• Natural Gas • Increased safety provided by nozzle
Flexible application range • Propane head shut off device with dedicated
The burners can be used on heat nozzle shut off solenoid
exchangers such as hot water boilers, Permissible ambient conditions: • Nozzle circulation and precise oil
steam boilers, air heaters and for • Ambient temperature temperature regulation on heavy fuel
certain process applications. As the -10 to +40 °C (14 to 104F) oil burners
burners are capable of overcoming high -15 to +40 °C (5 to 104F) • Compliance with current emission
combustion chamber resistances, they • Air humidity: max. 80% relative standards worldwide
are primarily used on high efficiency humidity, no condensation • High turndown ratio (RL, RGL)
boilers. • Suitable only for indoor operation
• For installation in unheated rooms
Digital combustion management under some circumstances special
Digital combustion management solutions are required (contact
ensures simple and safe operation Weishaupt)
of combustion application. All important
functions, such as fuel and air supply or Any discrepancy from the above de-
flame monitoring are controlled with scribed applications requires written
digital precision. Operational functions confirmation from Weishaupt Corpora-
are optimized, economy is maximized tion. The maintenance interval could be
and emissions are minimized. shortened according to conditions
The integral ModBus interface allows where the burners are installed.
communication with building
automization/ management system. Approvals
The burners are in compliance with
Energy saving with speed control most North American and European
and O2 trim applicable standards.
Electrical consumption is definitely
a cost factor for large combustion Outstanding service
application. Weishaupt maintains an extensive
Speed control uses frequency drive global sales and service network.
to match fan speed to the actual air Customer service is available every day
requirement, allowing for significant around the clock. In-house training by
savings of electricity, particularly at low Weishaupt ensures the high standard
fire. With O2 trim the flue gases are of their service engineers.
continuously monitored and controlled
to ensure the best possible degree of
combustion efficiency and thus lower
fuel consumption and increased
reliability.

6
Characteristics of the different variations
Version Standard Version 3LN
Oil, gas and dual fuel burners for LowNOx gas and dual fuel burners
installations without specific NOx with patented multiflam mixing head
requirements. Suitable for Natural Gas, for installations with more stringent low
Propane, #2 - #6 oil, as well as special NOx requirements. Low NOx values are
gases and special oils on request. achieved by fuel distribution method.
Suitable for Natural Gas, Propane and
Version NR #2 oil.
Gas and dual fuel burners with
advanced, standard mixing head for
applications where there is NOx
requirements on gas side. NR means:
lower NOx emission on gas side com-
pared to the standard version. Oil side
as standard version. Suitable for
Natural Gas, Propane, #2 - #6 oil.

Version 1LN
LowNOx gas and dual fuel burners with
special mixing head for applications,
where there are requirements for lower
NOx emission on gas and oil side. 1LN
means: lower NOx values compared to
version NR.
Suitable for Natural Gas, Propane, #2
oil.

Version LN
LowNOx gas burners with special
mixing head for installations where
there is requirement for lower NOx
emission on gas operation.
Lower NOx value compared to vers.
1LN . Suitable for Natural Gas and
Propane.

7
Oil burners
Burner selection
Oil burners size 30, version Standard
Burner model MS30Z/2-A Burner model RMS30/2-A
Combustion head M30/2 - 190k x 65 Combustion head M30/2 - 190k x 65
Capacity in MBH 2,300 – 8,330 Capacity in MBH 2,300 – 8,330
Capacity in GPH#6 15 – 54.5 Capacity in GPH#6 15 – 54.5
“WC “WC
5 6

4 5

4
3

3
2

High fire
2

range
1
1

0
0

-1 -1

-2 -2
MBH 0 1,000 2,000 3,000 4,000 5,000 6,000 7,000 8,000 9,000 MBH 0 1,000 2,000 3,000 4,000 5,000 6,000 7,000 8,000 9,000

GPH #6 7.5 15 22.5 30 37.5 45 52.5 60 GPH #6 7.5 15 22.5 30 37.5 45 52.5 60

Fuels
#6 oil

Burner model vers. Order No.


MS30Z/2-A – 212 303 02
RMS30/2-A ZM 212 305 02

The stated oil throughputs in GPH refer to #6 oil with a


calorific value of 153,000 BTU/Gal.

The capacity graphs are based on air temperature of


68F (20 °C) an installation altitude of 1,640 ft (500 m)
above sea level. A reduction of burner capacity of 1 %
for every 325 ft (100 m) should be taken into
consideration depending on installation altitude.

Voltages and frequencies:


The burners are equipped with three phase motor in 208 -
600 V, 60 Hz as standard. Different voltage and frequency
are available upon request.

Standard burner motor:


Insulation class F, protection IP 55.

10
Burner selection
Oil burners size 40, version Standard
Burner model MS40Z/1-B MS40Z/1-B Burner model RMS40/1-B
Combustion head M30/2 - 200x50 M30/2 - 175x50 Combustion head M30/2 - 190k x 65
Capacity in MBH 3,445 – 8,740 3,445 – 10,170 Capacity in MBH 2,680 – 9,965
Capacity in GPH#6 22.5 – 57 22.5 – 66 Capacity in GPH#6 17.5 – 65
“WC “WC
6 8

7
5
6
4
5
3
4
High fire

2 3
range

High fire
range
1 2

1
0
0
-1
-1

-2 -2
MBH 0 1,000 2,000 3,000 4,000 5,000 6,000 7,000 8,000 9,000 10,000 11,000 12,000 MBH 0 1,000 2,000 3,000 4,000 5,000 6,000 7,000 8,000 9,000 10,000 11,000 12,000

GPH #6 10 20 30 40 50 60 70 80 GPH #6 10 20 30 40 50 60 70 80

Burner model RMS40/2-A Burner model Vers. Order No.


Combustion head M40/2 - 217k x 75
Capacity in MBH 3,445 – 12,590 MS40Z/1-B – 212 402 00
Capacity in GPH#6 22.5 – 82.3 RMS40/1-B ZM 212 404 00
“WC
8 RMS40/2-A ZM 212 405 02
7

4 The stated oil throughputs in GPH refer to #6 oil with a


3 calorific value of 153,000 BTU/Gal.
High fire
range

1 The capacity graphs are based on air temperature of


0 68F (20 °C) an installation altitude of 1,640 ft (500 m)
-1 above sea level. A reduction of burner capacity of 1 %
MBH
-2
0 1,000 2,000 3,000 4,000 5,000 6,000 7,000 8,000 9,000 10,000 11,000 12,000 13,000 14,000 for every 325 ft (100 m) should be taken into
GPH #6 10 20 30 40 50 60 70 80 90 consideration depending on installation altitude.

Voltages and frequencies:


Fuels The burners are equipped with three phase motor in 208 -
#6 oil
600 V, 60 Hz as standard. Different voltage and frequency
are available upon request.

Standard burner motor:


Insulation class F, protection IP 55.

11
Burner selection
Oil burners size 50, version Standard
Burner model L50T/2-A Burner model RL50/1-B RMS50/1-B
Combustion head M50/1 - 185x50 Combustion head M40/2 - 217x75 M40/2 - 217x75
Capacity in MBH 3,445 – 16,260 Capacity in MBH 2,440 – 13,000 3,840 – 13,000
Capacity in GPH#2 25 – 116 Capacity in GPH#2 17 – 93 –
“WC “WC GPH#6 – 25 – 85
8 9

8
7
7
6
6
5
5
4
4
3

High fire
3

range
2
2
1 1

0 0

-1 -1

-2 -2
MBH 0 2,000 4,000 6,000 8,000 10,000 12,000 14,000 16,000 18,000 MBH 0 1,000 2,000 3,000 4,000 5,000 6,000 7,000 8,000 9,000 10,000 11,000 12,000 13,000 14,000

GPH 15 30 45 60 75 90 105 120 GPH #2 10 20 30 40 50 60 70 80 90

GPH #6 10 20 30 40 50 60 70 80 90

Burner model RL50/2-A RMS50/2-A Burner model Vers. Order No.


Combustion head M50/2 - 290x185 M50/2 - 290x185
Capacity in MBH 3,860 – 21,060 4,980 – 21,060 L50T/2-A - 211 509 02
Capacity in GPH#2 27 – 150 – RL50/1-B ZM 211 504 00
“WC GPH#6 – 33 – 137.6
9 RMS50/1-B ZM 212 504 00
8
RL50/2-A ZM 211 505 02
7

6
RMS50/2-A ZM 212 505 02
5

4
High fire

3
range

2 The stated oil throughputs in GPH refer to #2 oil with a


1
calorific value of 140,000 BTU/Gal and #6 oil with a
0

-1
calorific value of 153,000 BTU/Gal.
-2
MBH 0 2,000 4,000 6,000 8,000 10,000 12,000 14,000 16,000 18,000 20,000 22,000 24,000
The capacity graphs are based on air temperature of
GPH #2 20 40 60 80 100 120 140 160
68F (20 °C) an installation altitude of 1,640 ft (500 m)
GPH #6 20 40 60 80 100 120 140 160
above sea level. A reduction of burner capacity of 1 %
for every 325 ft (100 m) should be taken into
consideration depending on installation altitude.
Fuel oils
#2 oil
Voltages and frequencies:
#6 oil The burners are equipped with three phase motor in 208 -
600 V, 60 Hz as standard. Different voltage and frequency
are available upon request.

Standard burner motor:


Insulation class F, protection IP 55.

12
Burner selection
Oil burners size 60 and 70, version Standard
Burner model RL60/2-A RMS60/2-A Burner model RL70/1-A RMS70/1-A
Combustion head M60/2-345-230 M60/2-345-230 Combustion head M70/1a-425-290 M70/1a-425-290
Capacity in MBH 4,470– 24,795 6,140 – 24,795 Capacity in MBH 6,500 – 29,860 6,910 – 29,860
Capacity in GPH#2 32– 176 – Capacity in GPH#2 46 – 213 –
“WC GPH#6 – 40 – 162 “WC GPH#6 – 45 – 195
9 9

8 8

7 7

6 6

5 5

4 4
High fire

High fire
3 3
range

range
2 2

1 1

0 0

-1 -1

-2 -2
MBH 0 2,000 4,000 6,000 8,000 10,000 12,000 14,000 16,000 18,000 20,000 22,000 24,000 26,000 MBH 0 2,500 5,000 7,500 10,000 12,500 15,000 17,500 20,000 22,500 25,000 27,500 30,000 32,500 35,000

GPH #2 20 40 60 80 100 120 140 160 180 GPH #2 20 40 60 80 100 120 140 160 180 200 220 240

GPH #6 20 40 60 80 100 120 140 160 GPH #6 20 40 60 80 100 120 140 160 180 200 220

Burner model RL70/2-A RMS70/2-A Burner model Vers. Order No.


Combustion head M70/1a-425-290 M70/1a-425-290
Capacity in MBH 6,500 – 37,200 6,910 – 37,200 RL60/2-A ZM 211 605 02
Capacity in GPH#2 46 – 265 – RMS60/2-A ZM 212 605 02
“WC GPH#6 – 45 – 243
10 RL70/1-A ZM 211 704 02
9
RMS70/1-A ZM 212 704 02
8
7 RL70/2-A ZM 211 705 02
6
RMS70/2-A ZM 212 705 02
5
4
High fire
range

3
2 The stated oil throughputs in GPH refer to #2 oil with a
1 calorific value of 140,000 BTU/Gal and #6 oil with a
0
calorific value of 153,000 BTU/Gal.
-1

-2
MBH 0 3,000 6,000 9,000 12,000 15,000 18,000 21,000 24,000 27,000 30,000 33,000 36,000 39,000
The capacity graphs are based on air temperature of
GPH #2 25 50 75 100 125 150 175 200 225 250 275
68F (20 °C) an installation altitude of 1,640 ft (500 m)
GPH #6 25 50 75 100 125 150 175 200 225 250
above sea level. A reduction of burner capacity of 1 %
for every 325 ft (100 m) should be taken into
consideration depending on installation altitude.
Fuels
#2 oil Voltages and frequencies:
#6 oil The burners are equipped with three phase motor in 208 -
600 V, 60 Hz as standard. Different voltage and frequency
are available upon request.

Standard burner motor:


Insulation class F, protection IP 55.

13
Scope of delivery/Accessories
Oil burners size 30 to 70, version Standard
Scope of delivery MS30 MS40 RMS30 RMS40 RMS50 RMS60 RMS70 L50 RL50 RL60 RL70

Burner housing, hinge flange, housing cover,


Weishaupt burner motor, air intake housing fan wheel,
combustion head, ignition unit, ignition cable, ignition electrodes
nozzle assembly with oil nozzle/s, combustion manager with
operating unit, flame sensor, stepping motors, flange gasket,
limit switch on hinge flange, fixing screws ● ● ● ● ● ● ● ● ● ● ●
Combustion manager W-FM100 – – ● ● ● ● ● ● ● ● ●
Air pressure switch – – – – – ● ● – – – –
Oil pressure switch in return ● ● ● ● ● ● ● ● ● ● ●
Oil pressure switch in supply – – – – – ● ● – – – –
Adjustable regulating sleeve in mixing head ● – – – – – – – – – –
Sliding sleeve in mixing head – – ● ● ● ● ● – ● ● ●
Oil pump, fitted ● ● ● ● ● – – ● ● ● ●
Oil preheater, fitted ● ● ● ● ● – – – – – –
Oil hoses ● ● ● ● ● ● ● ● ● ● ●
3 oil solenoid valves, 1 safety shut off valve,
three stage nozzle head without shut off device – – – – – – – ● – – –
1 normally closed solenoid valve in supply and return, nozzle head
with shut off device (nozzle solenoid on RL and RMS,
hydraulically controlled ball valve on MS) ● ● ● ● ● – – – ● ● ●
1 normally closed solenoid valve in supply and return, bypass
solenoid valve, nozzle head with shut off device (nozzle solenoid) – – – – – ● ● – – – –
Downward firing version ● ● ● ● ● ● ● ● ● ● ●
Heating cartridges ● ● ● ● ● ● ● – – – –

Accessories
Intake flange for connection of air duct ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
Stainless steel oil hoses, heated ○ ○ ○ ○ ○ ○ ○ – – – –
Magnetic coupling – – ○ ○ ○ – – ○ ○ ○ ○
Combustion head extension ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
Media preheater with fittings ○ ○ ○ ○ ○ ○ ○ – – – –
Speed control – – ○ ○ ○ ○ ○ ○ ○ ○ ○
O2 trim – – ○ ○ ○ ○ ○ ○ ○ ○ ○
W-FM loosed for installation in remote panel – – ○ ○ ○ ○ ○ ○ ○ ○ ○

● Scope of delivery
○ Accessories

Additional accessories on request.

14
Technical data
Oil burners size 30 and 40, version Standard
Technical data MS30Z/2-A RMS30/2-A
Burner motor 3~208 - 600V Model W-D112/140-2/4K5 W-D112/140-2/4K5
Motor rating HP (kW) 6.6 (4.5) 6.6 (4.5)
FLA at 460V A 8.6 8.6
Speed (60 Hz) rpm 3,510 3,510
Fan wheel Color / ø red / 248 x 104 red / 248 x 104
Combustion manager Model LAL2.25 W-FM100
Ignition unit Model W-ZG02 W-ZG02
Stepping motor Air Model 1055/80 SQM45
Fuel Model – SQM45
Mixing head Model – SQM45
Pump fitted Model E7 TA3
Oil preheater Model EV2D EV2D
Oil throughput GPH and (kg/h) 72 (270) 72 (270)
Heat rating kW 13.2 13.2
Oil solenoid valves 110V 1/8” 19 W Model 121 K 2423 –
110V 1/8” 19 W Model 122 K 9321 –
55V 3/8” (supply) 20 W Model 321 H 2322 321 H 2322
55V 3/8” (return) 20 W Model 121 G 2320 121 G 2320
Oil pressure switches 1 – 10 bar (return fuel oil EL - 5 bar) Model – –
1 – 10 bar (return fuel oil S - 7 bar) Model DSA 46 F001 DSA 46 F001
Oil hoses DN, length in inch and (mm) 20/40” (1000) 20/40” (1000)
(on MS, RMS and RGMS, high pressure metal hoses) 20/51” (1300) 20/51” (1300)
Burner weight approx. lbs (kg) 297 (135) 309 (140)

Technical data MS40Z/1-B RMS40/1-B RMS40/2-A


Burner motor 3~208 - 600V Model W-D112/170-2/5K5 W-D112/170-2/5K5 W-D112/170-2/7K0
Motor rating HP (kW) 8.6 (6.5) 8.6 (6.5) 10.4 (7.8)
FLA at 460V A 12 12 14
Speed (60 Hz) rpm 3,530 3,530 3,500
Fan wheel Color / ø red / 275 x 104 red / 275 x 104 red / 275 x 104
Combustion manager Model LAL2.25 W-FM100 W-FM100
Ignition unit Model W-ZG02 W-ZG02 W-ZG02
Stepping motor Air Model SQM10 SQM45 SQM45
Fuel Model – SQM45 SQM45
Mixing head Model – SQM45 SQM45
Pump fitted Model E7 TA3 TA3
Oil preheater Model EV2D EV2D EV2D 2) 3)
Oil throughput in GPH and (kg/h) 75 (270) 75 (270) 75 (270)
Heat rating kW 13.2 13.2 13.2
Oil solenoid valves 110V 1/8” 19 W Model 121 K 2423 – –
110V 1/4” (safety v.) 20 W Model – – –
110V 1/8“ 19 W Model 122 K 9321 – –
55V 3/8” (supply) 20 W Model 321 H 2322 321 H 2322 321 H 2322
55V 3/8” (return) 20 W Model 121 G 2320 121 G 2320 121 G 2320
Oil pressure switches 1 – 10 bar (return #2 oil - 5 bar) Model – – –
1 – 10 bar (return #6 oil - 7 bar) Model DSA 46 F001 DSA 46 F001 DSA 46 F001
Oil hoses DN, length in inch and (mm) 20/40” (1000) 20/40” (1000) 20/40” (1000)
(on MS, RMS and RGMS, high pressure metal hoses) 20/51” (1300) 20/51” (1300) 20/51” (1300)
Burner weight approx. lbs (kg) 350 (159) 366 (166) 380 (172)
1) 2)
Burners above 75 GPH (270 kg/h): Oil preheater WEV2.2 in lieu of EV2D, Burners above 82.5 GPH (300 kg/h): Oil preheater WEV3 in lieu of
Refer to ‘Accessories’ WEV2.2, Refer to ‘Accessories’

15
Technical data
Oil burners size 50, version Standard
Technical data L50T/2-A RL50/1-B RL50/2-A
Burner motor 3~208 V - 600V Model W-D132/210-2/14K0 W-D132/170-2/9K0 W-D132/210-2/14K0
Motor rating HP (kW) 20 (15) 14.6 (11) 20 (15)
FLA at 460V A 25 19 25
Speed (60 Hz) rpm 3,520 3,500 3,520
Fan wheel Colour / ø red / 330 x 104.5 red / 330 x 104.5 red / 330 x 104.5
Combustion manager Model W-FM100 W-FM100 W-FM100
Ignition unit Model W-ZG02 W-ZG02 W-ZG02
Stepping motor Air Model SQM45 SQM45 SQM45
Fuel Model – SQM45 SQM45
Mixing head Model – SQM45 SQM45
Pump, fitted Model TA2C TA4C T2C
Oil preheater Model – – –
Oil throughput in GPH and (kg/h) – – –
Heat rating kW – – –
Oil solenoid valve 110V 1/8” 19 W Model 121 K 2423 (3 off) – –
110V 1/4” (safety v.) 20 W Model 121 K 6220 – –
55V 3/8” (supply) 20 W Model – 321 H 2322 321 H 2322
55V 3/8” (return) 20 W Model – 121 G 2320 121 G 2320
Oil pressure switches 1 – 10 bar (return #2 oil - 5 bar) Model – DSA 46 F001 DSA 46 F001
1 – 10 bar (return #6 oil - 7 bar) Model – – –
Oil hoses DN, length in inch and (mm) 20/51” (1300) 25/51” (1300) 25/51” (1300)
Burner weight approx. lbs (kg) 440 (200) 458 (208) 463 (210)

Technical data RMS50/1-B RMS50/2-A


Burner motor 3~208 - 600V Model W-D132/170-2/9K0 W-D132/210-2/14K0
Motor rating HP (kW) 14.6 (11) 20 (15)
FLA at 460V A 19 25
Speed (60 Hz) rpm 3,500 3,520
Fan wheel Colour / ø red / 330 x 104.5 red / 330 x 104.5
Combustion manager Model W-FM100 W-FM100
Ignition unit Model W-ZG02 W-ZG02
Stepping motor Air Model SQM45 SQM45
Fuel Model SQM45 SQM45
Mixing head Model SQM45 SQM45
Pump, fitted Model TA4C T2C
Oil preheater Model WEV2.2/01 1) WEV3/01
Oil throughput in GPH and (kg/h) 82.5 (300) 137.5 (500)
Heat rating kW 13.8 22.4
Oil solenoid valve 55V 3/8” (supply) 20 W Model 321 H 2322 321 H 2322
55V 3/8” (return) 20 W Model 121 G 2320 121 G 2320
Oil pressure switches 1 – 10 bar (return #2 oil - 5 bar) Model – –
1 – 10 bar (return #6 oil - 7 bar) Model DSA 46 F001 DSA 46 F001
Oil hoses DN, length in inch and (mm) 25/45” (1150) 25/45” (1150)
(on MS, RMS and RGMS, high pressure metal hoses) 25/59” (1500) 25/59” (1500)
Burner weight approx. lbs (kg) 546 (248) 552 (250)

1)
Burners above 82.5 GPH (300 kg/h): Oil preheater WEV3 in lieu of WEV2.2,
Refer to ‘Accessories’

16
Technical data
Oil burners size 60 and 70, version Standard
Technical data RL60/2-A RMS60/2-A
Burner motor 3~208 - 600V Model W-D132/210-2/14K0 W-D132/210-2/14K0
Motor rating HP (kW) 20 (15) 20 (15)
FLA at 460V A 25 25
Speed (60 Hz) rpm 3,520 3,520
Fan wheel Colour / ø red / 465 x 103 red / 465 x 103
Combustion manager Model W-FM100 W-FM100
Ignition unit Model W-ZG02 W-ZG02
Stepping motor Air Model SQM45 SQM45
Fuel Model SQM45 SQM45
Mixing head Model SQM45 SQM45
Pump fitted Model T2C –
Oil solenoid valves 55V 3/8” (supply) 20 W Model 321 H 2322 321 H 2322
55V 3/8” (return) 20 W Model 121 G 2320 121 G 2320
110V 3/8” (bypass) 19 W Model – 322 H 7306
Oil pressure switches 3 – 25 bar (supply-18 bar) Model – DSA 58 F 001
1 – 10 bar (return #2 oil-5 bar) Model DSA 46 F 001 –
1 – 10 bar (return #6 oil-7 bar) Model – DSA 46 F 001
Oil hoses DN, length in inch and (mm) 25/51” (1300) 16/45” (1150)
(on RMS and RGMS, high pressure metal hoses) – 16/59” (1500)
Burner weight approx. lbs (kg) 552 (250) 463 (210) 2)

Technical data RL70/1-A RL70/2-A RMS70/1-A RMS70/2-A


Burner motor 3~208 - 600V Model W-D160/215-2/14K0 W-D160/240-2/22K0 W-D160/215-2/14K0 W-D160/240-2/22K0
Motor rating HP (kW) 21.3 (16) 26.6 (20) 21.3 (16) 26.6 (20)
FLA at 460V A 28 33 28 33
Speed (60 Hz) rpm 3,540 3,550 3,540 3,550
Fan wheel Colour / ø yellow / 475 x 128 green / 530 x 120 yellow / 475 x 128 green / 530 x 120
Combustion manager model W-FM100 W-FM100 W-FM100 W-FM100
Ignition unit model W-ZG02 W-ZG02 W-ZG02 W-ZG02
Stepping motor Air model SQM45 SQM45 SQM45 SQM45
Fuel model SQM45 SQM45 SQM45 SQM45
Mixing head model SQM45 SQM45 SQM45 SQM45
Pump fitted model T2C (up to 173 GPH/ 600 kg/h) – –
model T3C (from 173 GPH/ 600 kg/h) – –
Oil solenoid valves 55V 3/8” (supply) 20 W Model 321 H 2322 321 H 2322 321 H 2322 321 H 2322
55V 3/8” (return) 20 W Model 121 G 2320 121 G 2320 121 G 2320 121 G 2320
110V 3/8” (bypass) 19 W Model – – 322 H 7306 322 H 7306
Oil pressure switch 3 – 25 bar (supply-18 bar) Model – – DSA 58 F 001 DSA 58 F 001
1 – 10 bar (return #2 oil-5 bar) Model DSA 46 F 001 DSA 46 F 001 – –
1 – 10 bar (return #6 oil-7 bar) Model – – DSA 46 F 001 DSA 46 F 001
Oil hoses DN, length in inch and (mm) 25/51” (1300) 25/51” (1300) 20/45” (1150) 20/45” (1150)
(on RMS and RGMS, high pressure metal hoses) – – 20/59” (1500) 20/59” (1500)
Burner weight approx. lbs (kg) 772 (350) 772 (350) 684 (310) 2) 684 (310) 2)

2)
Weight without pump and preheater station

17
Gas burners
Burner selection
Gas burners size 50 to 70, version NR
Burner model G50/1-B, vers. ZM-NR Burner model G50/2-A, vers. ZM-NR
Combustion head G40/2-NR 217x75 Combustion head G50/2-NR 290x85
Capacity in MBH Nat Gas 1,875 – 13,650 Capacity in MBH Nat Gas 2,050 – 18,430
Propane 1,875 – 13,650 Propane 2,050 – 18,430
“WC “WC
9 9

8 8

7 7

6 6

5 5

4 4

High fire
High fire

3 3

range
range

2 2

1 1

0 0

-1 -1

-2 -2
0 1,000 2,000 3,000 4,000 5,000 6,000 7,000 8,000 9,000 10,000 11,000 12,000 13,000 14,000 0 2,000 4,000 6,000 8,000 10,000 12,000 14,000 16,000 18,000 20,000 22,000

Burner model G60/2-A, vers. ZM-NR Burner model G70/1-B, vers. ZM-NR
Combustion head G60/2-NR 345x230 Combustion head G60/2-NR 345x230
Capacity in MBH Nat Gas 2,730 – 20,800 Capacity in MBH Nat Gas 2,730 – 25,250
Propane 2,730 – 20,800 Propane 2,730 – 25,250
“WC “WC
9 9

8 8

7 7

6 6

5 5

4 4
High fire

High fire

3 3
range

range

2 2

1 1

0 0

-1 -1

-2 -2
0 2,000 4,000 6,000 8,000 10,000 12,000 14,000 16,000 18,000 20,000 22,000 0 2,000 4,000 6,000 8,000 10,000 12,000 14,000 16,000 18,000 20,000 22,000 24,000 26,000

Fuels
Nat gas
Propane

Burner model Vers. Order No. The capacity graphs are based on air temperature of
G50/1-B ZM-NR 217 504 15 68F (20 °C) and installation altitude of 1,640 ft (500 m).
A reduction of burner capacity of 1 % for every 325 ft
G50/2-A ZM-NR 217 505 13
(100 m) should be taken into consideration depending
G60/2-A ZM-NR 217 605 12 on installation altitude.
G70/1-B ZM-NR 217 704 42
Voltages and frequencies:
The burners are equipped with three phase motor in 208 -
600 V, 60 Hz as standard. Different voltage and frequency
are available upon request.

Standard burner motor:


Insulation class F, protection IP 55.

20
Burner selection
Gas burners size 70, version NR
Burner model G70/3-A, vers. ZM-NR Burner model G70/4-A, vers. ZM-NR
Combustion head G70/3-NR 425x290 Combustion head G70/3-NR 425x290
Capacity in MBH Nat Gas 3,400 – 36,500 Capacity in MBH Nat Gas 3,400 – 39,930
Propane 4,780 – 36,500 Propane 4,780 – 39,930
“WC “WC

10 10

9 9

8 8

7 7

6 6

5 5

4 4

High fire
High fire

range
range

3 3

2 2

1 1

0 0

-1 -1

-2 -2
0 3,000 6,000 9,000 12,000 15,000 18,000 21,000 24,000 27,000 30,000 33,000 36,000 39,000 42,000 0 3,000 6,000 9,000 12,000 15,000 18,000 21,000 24,000 27,000 30,000 33,000 36,000 39,000 42,000

Fuels
Nat gas
Propane

Burner model Vers. Order No. The capacity graphs are based on air temperature of
G70/3-A ZM-NR 217 714 14 68F (20 °C) and installation altitude of 1,640 ft (500 m).
A reduction of burner capacity of 1 % for every 325 ft
G70/4-A ZM-NR 217 734 14
(100 m) should be taken into consideration depending
on installation altitude.

Voltages and frequencies:


The burners are equipped with three phase motor in 208 -
600 V, 60 Hz as standard. Different voltage and frequency
are available upon request.

Standard burner motor:


Insulation class F, protection IP 55.

21
Scope of delivery/Accessories
Gas burners size 50 to 70, version NR
Scope of delivery G50 G60 G70
Burner housing, hinge flange, housing cover, Weishaupt burner motor, air regulator housing,
fan wheel, combustion head, ignition unit, ignition cable, ignition electrode, combustion
manager with operating unit, flame sensor, stepping motors, flange gasket, limit switch
on hinge flange, fixing screws ● ● ●
Combustion manager W-FM100 ● ● ●
Two gas safety shut off valves ● ● ●
Gas butterfly valve ● ● ●
Ignition pilot ● ● ●
Air pressure switch ● ● ●
Gas pressure switches ● ● ●
Servomotor driven sliding sleeve in mixing head ● ● ●
Stepping motor for Gas /Air ratio control with W-FM100
Stepping motor for air damper ● ● ●
Stepping motor for gas butterfly valve ● ● ●
Stepping motor for sliding sleeve ● ● ●

Accessories
Downward firing burner ○ ○ ○
Intake flange for the connection of an air duct ○ ○ ○
Solenoid valve for air pressure switch test for cont. run fan or post-purge ○ ○ ○
Combustion head extension ○ ○ ○
Speed control ○ ○ ○
O2 trim ○ ○ ○
W-FM loosed for installation in remote control panel ○ ○ ○

● Scope of delivery
○ Accessories

Additional accessories on request.

22
Technical data
Gas burners size 50 to 70, version NR
Technical data G50/1-B G50/2-A G60/2-A
Burner motor 3~208 - 600V Model W-D132/170-2/9K0 W-D132/210-2/14K0 W-D132/210-2/14K0
Motor rating HP (kW) 14.6 (11) 20 (15) 20 (15)
FLA at 460V A 19 25 25
Speed (60 Hz) rpm 3,500 3,520 3,520
Fan wheel Colour red red red
ø 330 x 104.5 330 x 104.5 465 x 103
Combustion manager Model W-FM100 W-FM100 W-FM100
Ignition unit Model W-ZG02 W-ZG02 W-ZG02
Stepping motor Air Model SQM45 SQM45 SQM48
Mixing head Model SQM45 SQM45 SQM45
Fuel Model SQM45 SQM45 SQM45

Burner weight approx. lbs (kg) 408 (185) 408 (185) 606 (275)

Technical data G70/1-B G70/3-A G70/4-A


Burner motor 3~208 - 600V Model W-D160/240-2/18K0 W-D160/240-2/22K0 W-D160/240-2/28K0
Motor rating HP (kW) 22 (16.5) 26.6 (20) 37.3 (28)
FLA at 460 V A 30.5 33 53 (at 400V)
Speed (60/55 Hz) rpm 3,560 3,550 3220 (55 Hz)
Fan wheel Colour green green blue
ø 530 x 120 530 x120 590 x 160
Combustion manager Model W-FM100 W-FM100 W-FM200
Ignition unit Model W-ZG02 W-ZG02 W-ZG02
Stepping motor Air Model SQM48 SQM48 SQM48
Mixing head Model SQM45 SQM48 SQM48
Fuel Model SQM45 SQM45 SQM45
Burner weight approx. lbs (kg) 860 (390) 860 (390) 860 (390)

* Operation at 55 Hz only in conjunction with frequency drive.

23
Burner selection
Gas burners size 50 to 70, version 1LN
Burner model G50/1-B, vers. ZM-1LN Burner model G70/1-B, vers. ZM-1LN
Combustion head G40/2-LN 217x35 Combustion head G60/2-1LN 300x75
Capacity in MBH Nat Gas 1,700 – 11,600 Capacity in MBH Nat Gas 2,730 – 24,900
Propane 1,700 – 11,600 Propane 3,400 – 24,900
“WC “WC
9 9
8 8

7 7

6 6
5
High fire

5
range

4 4

High fire
range
3 3
2 2
1 1

0 0
-1 -1

-2 -2
0 1,000 2,000 3,000 4,000 5,000 6,000 7,000 8,000 9,000 10,000 11,000 12,000 13,000 14,000 0 2,000 4,000 6,000 8,000 10,000 12,000 14,000 16,000 18,000 20,000 22,000 24,000 26,000

Burner model G50/2-A, vers. ZM-1LN Burner model G70/2-A, vers. ZM-1LN
Combustion head G50/2-LN 260x40 Combustion head G70/2-1LN 365x85
Capacity in MBH Nat Gas 2,050 – 16,720 Capacity in MBH Nat Gas 3,400 – 34,100
Propane 2,730 – 16,720 Propane 4,440 – 34,100
“WC “WC

9 10

8 9
8
7
7
6
6
5
5
4
4
High fire

High fire

3
range

range

3
2
2
1 1
0 0

-1 -1

-2 -2
0 2,000 4,000 6,000 8,000 10,000 12,000 14,000 16,000 18,000 0 3,000 6,000 9,000 12,000 15,000 18,000 21,000 24,000 27,000 30,000 33,000 36,000

Fuels
Nat gas
Propane

Burner model Vers. Order No. The capacity graphs are based on air temperature of
G50/1-B ZM-1LN 217 504 17 68F (20 °C) an installation altitude at sea level. A
reduction of burner capacity of 1 % for every 325 ft
G50/2-A ZM-1LN 217 505 16
(100 m) should be taken into consideration in case of
G70/1-B ZM-1LN 217 704 45 installation altitude above 0 ft.
G70/2-A ZM-1LN 217 705 45
Voltages and frequencies:
The burners are equipped with three phase motor in 208 -
600 V, 60 Hz as standard. Different voltage and frequency
are available upon request.

Standard burner motor:


Insulation class F, protection IP 55.

24
Scope of delivery/Accessories/ Technical data
Gas burners size 50 and 70, version 1LN
Scope of delivery G50 G70
Burner housing, hinge flange, housing cover, Weishaupt burner motor, air regulator housing, fan wheel,
combustion head, ignition unit, ignition cable, ignition electrode, combustion manager with operating
unit, flame sensor, stepping motors, flange gasket, limit switch on hinge flange, fixing screws ● ●
Combustion manager W-FM100 ● ●
Two gas safety shut off valves ● ●
Gas butterfly valve ● ●
Ignition pilot ● ●
Air pressure switch ● ●
Gas pressure switches ● ●
Adjustable flame tube in mixing head ● ●
Stepping motor for Gas/Air ratio control with W-FM100
Stepping motor for air damper ● ●
Stepping motor for gas butterfly valve ● ●

Accessories
Downward firing burner ○ ○
Intake flange for the connection of an air duct ○ ○
Solenoid valve for air pressure switch test for cont. run fan or post-purge ○ ○
Combustion head extension ○ ○
Speed control ○ ○
O2 trim ○ ○
W-FM loosed for installation in remote control panel ○ ○

● Scope of delivery
○ Accessories

Additional accessories on request.

Technical data G50/1-B G50/2-A G70/1-B G70/2-A


Burner motor 3~208 - 600V Model W-D132/170-2/9K0 W-D132/210-2/14K0 W-D160/240-2/18K0 W-D160/240-2/22K0
Motor rating HP (kW) 14.6 (11) 20 (15) 22 (16.5) 26.6 (20)
FLA at 460V A 19 25 30.5 33
Speed (60 Hz) rpm 3,500 3,520 3,560 3,550
Fan wheel Colour red red green green
ø 330 x 104.5 330 x 104.5 530 x 120 530 x 120
Combustion manager Model W-FM100 W-FM100 W-FM100 W-FM100
Ignition unit Model W-ZG02 W-ZG02 W-ZG02 W-ZG02
Stepping motor Air Model SQM45 SQM45 SQM48 SQM48
Fuel Model SQM45 SQM45 SQM45 SQM45
Burner weight approx. lbs (kg) 408 (185) 408 (185) 860 (390) 860 (390)

25
Burner selection
Gas burners size 50, version LN
Burner model G50/1-B, vers. ZM-LN Burner model G50/2-A, vers. ZM-LN
Combustion head G40/2-3a 210x60 Combustion head G50/2-3a 250x90
Capacity in MBH Nat Gas 1,700 – 10,230 Capacity in MBH Nat Gas 2,050 – 15,350

“WC “WC
9 9
8 8
7 7
6 6
5 5
High fire
range

4 4

High fire
range
3 3
2 2
1 1
0 0
-1 -1
-2 -2
0 1,000 2,000 3,000 4,000 5,000 6,000 7,000 8,000 9,000 10,000 11,000 12,000 0 2,000 4,000 6,000 8,000 10,000 12,000 14,000 16,000 18,000

Fuels – capacity with


combustion head open close
Nat gas

Burner model Vers. Order No. The capacity graphs are based on air temperature of
G50/1-B ZM-LN 217 504 19 68F (20 °C) an installation altitude at sea level. A
reduction of burner capacity of 1 % for every 325 ft
G50/2-A ZM-LN 217 505 18
(100 m) should be taken into consideration in case of
installation altitude above 0 ft.

Voltages and frequencies:


The burners are equipped with three phase motor in 208 -
600 V, 60 Hz as standard. Different voltage and frequency
are available upon request.

Standard burner motor:


Insulation class F, protection IP 55.

26
Burner selection
Gas burners size 60 and 70, version LN
Burner model G60/2-A, vers. ZM-LN Burner model G70/1-B, vers. ZM-LN
Combustion head G60/2-3a 300x100 Combustion head G60/2-3a 300x100
Capacity in MBH Nat Gas 2,135 – 19,795 Capacity in MBH Nat Gas 2,390 – 23,890

“WC
“WC
9 9

8 8

7 7

6 6

5 5

4 4

High fire
High fire

range
3
range

2 2

1 1

0 0

-1 -1

-2 -2
0 2,000 4,000 6,000 8,000 10,000 12,000 14,000 16,000 18,000 20,000 22,000 0 2,000 4,000 6,000 8,000 10,000 12,000 14,000 16,000 18,000 20,000 22,000 24,000 26,000

Burner model G70/2-A, vers. ZM-LN


Combustion head G70/2-3a 355x120
Capacity in MBH Nat Gas 2,730 – 29,000

“WC
10
9
8

4
High fire
range

2
1
0

-1

-2
0 3,000 6,000 9,000 12,000 15,000 18,000 21,000 24,000 27,000 30,000 33,000 36,000

Fuels – capacity with


combustion head open close
Nat gas

Burner model Vers. Order No. The capacity graphs are based on air temperature
G60/2-A ZM-LN 217 605 13 of 68F (20 °C) an installation altitude at sea level. A
reduction of burner capacity of 1% for every 325 ft
G70/1-B ZM-LN 217 704 43
(100 m) should be taken into consideration in case of
G70/2-A ZM-LN 217 705 43 installation altitude above 0 ft.

Voltages and frequencies:


The burners are equipped with three phase motor in 208 -
600 V, 60 Hz as standard. Different voltage and frequency
are available upon request.

Standard burner motor:


Insulation class F, protection IP 55.

27
Scope of delivery/Accessories
Gas burners size 50 to 70, version LN
Scope of delivery G50 G60 G70
Burner housing, hinge flange, housing cover,
Weishaupt burner motor, air regulator housing, fan wheel,
combustion head, ignition unit, ignition cable, ignition electrodes,
combustion manager with operating unit, flame sensor,
stepping motors, flange gasket, limit switch on
hinge flange, fixing screws ● ● ●
Combustion manager W-FM100 ● ● ●
Two safety gas shut off valves ● ● ●
Gas butterfly valve ● ● ●
Air pressure switch ● ● ●
Gas pressure switches ● ● ●
Adjustable flame tube in mixing head ● ● ●
Stepping motor for Gas /Air ratio control with W-FM100
Stepping motor for air damper ● ● ●
Stepping motor for gas butterfly valve ● ● ●

Accessories
Downward firing burner ○ ○ ○
Intake flange for the connection of an air duct ○ ○ ○
Combustion head extension ○ ○ ○
Speed control ○ ○ ○
O2 trim ○ ○ ○
W-FM loosed for installation in remote panel ○ ○ ○

● Scope of delivery
○ Accessories

Additional accessories on request.

28
Technical data
Gas burners size 50 to 70, version LN
Technical data G50/1-B G50/2-A
Burner motor 3~208 - 600V Model W-D132/170-2/9K0 W-D132/210-2/14K0
Motor rating HP (kW) 14.6 (11) 20 (15)
FLA at 460 V A 19 25
Speed (60 Hz) rpm 3,500 3,520
Fan wheel Colour red red
ø 330 x 104.5 330 x 104.5
Combustion manager Model W-FM100 W-FM100
Ignition unit Model W-ZG02 W-ZG02
Stepping motor Air Model SQM45 SQM45
Fuel Model SQM45 SQM45
Burner weight approx. lbs (kg) 408 (185) 408 (185)

Technical data G60/2-A G70/1-B G70/2-A


Burner motor 3~208 - 600V Model W-D132/210-2/14K0 W-D160/215-2/14K0 W-D160/240-2/22K0
Motor rating HP (kW) 20 (15) 21.3 (16.0) 26.6 (20)
FLA at 460 V A 25 28 33
Speed (60 Hz) rpm 3,520 3,540 3,550
Fan wheel Colour red green green
ø 465 x 103 530 x 120 530 x 120
Combustion manager Model W-FM100 W-FM100 W-FM100
Ignition unit Model W-ZG02 W-ZG02 W-ZG02
Stepping motor Air Model SQM48 SQM48 SQM48
Fuel Model SQM45 SQM45 SQM45
Burner weight approx. lbs (kg) 606 (275) 860 (390) 860 (390)

29
Dual fuel burners
Burner selection
Dual fuel burners size 30, version NR
Burner model RGL30/2-A, RGMS30/2-A, Fuels
vers. ZM-NR vers. ZM-NR #2 oil
Combustion head G30/2-NR 190x65 G30/2-NR 190x65 #6 oil
Capacity in MBH Gas 1,025 – 7,850 1,025 – 7,850 Nat gas
GPH #2 oil 11.6 – 56 – Propane
GPH #6 oil – 15 – 51

“WC
6
The stated oil throughputs in GPH refer to #2 oil with a
5
calorific value of 140,000 BTU/Gal and #6 oil with a
4
calorific value of 153,000 BTU/Gal.
3

The capacity graphs are based on air temperature of


High fire

2
range

1
68F (20 °C) and installation altitude of 1,640 ft (500 m).
A reduction of burner capacity of 1 % for every 325 ft
0
(100 m) should be taken into consideration depending
-1 on installation altitude.
-2
0 500 1,000 1,500 2,000 2,500 3,000 3,500 4,000 4,500 5,000 5,500 6,000 6,500 7,000 7,500 8,000

GPH #2 10 20 30 40 50
Voltages and frequencies:
GPH #6 10 20 30 40 50
The burners are equipped with three phase motor in 208 -
600 V, 60 Hz as standard. Different voltage and frequency
are available upon request.
Burner model Vers. Order No.
Standard burner motor:
RGL30/2-A ZM-NR 218 305 13
Insulation class F, protection IP 55.
RGMS30/2-A ZM-NR 219 305 13

32
Burner selection
Dual fuel burners size 40, version NR
Burner model RGL40/1-B, RGMS40/1-B, Burner model RGL40/2-A, RGMS40/2-A,
vers. ZM-NR vers. ZM-NR vers. ZM-NR vers. ZM-NR
Combustion head G30/2-NR 190x58 G30/2-NR 190x58 Combustion head G40/2-NR 217x75 G40/2-NR 217x75
Capacity in MBH Gas 1,540 – 9,215 1,540 – 9,215 Capacity in MBH Gas 1,710 – 11,775 1,710 – 11,775
GPH #2 oil 13 – 65.8 – GPH #2 oil 15.8 – 84 –
GPH #6 oil – 17.6 – 60 GPH #6 oil – 22.3 – 76.9

“WC “WC

7 7

6 6

5 5
High fire
range

4 4

3 3
High fire

High fire
range

range
2 2

1 1

0 0

-1 -1

-2 -2
0 1,000 2,000 3,000 4,000 5,000 6,000 7,000 8,000 9,000 10,000 0 1,000 2,000 3,000 4,000 5,000 6,000 7,000 8,000 9,000 10,000 11,000 12,000 13,000

GPH #2 10 20 30 40 50 60 70 GPH #2 10 20 30 40 50 60 70 80 90

GPH #6 10 20 30 40 50 60 GPH #6 10 20 30 40 50 60 70 80

Fuels The stated oil throughputs in GPH refer to #2 oil with a


#2 oil
#6 oil calorific value of 140,000 BTU/Gal and #6 oil with a
Nat gas calorific value of 153,000 BTU/Gal.
Propane
The capacity graphs are based on air temperature of
68F (20 °C) and installation altitude of 1,640 ft (500 m).
Burner model Vers. Order No. A reduction of burner capacity of 1 % for every 325 ft
RGL40/1-B ZM-NR 218 404 13 (100 m) should be taken into consideration depending
RGMS40/1-B ZM-NR 219 404 13 on installation altitude.
RGL40/2-A ZM-NR 218 405 15
Voltages and frequencies:
RGMS40/2-A ZM-NR 219 405 15
The burners are equipped with three phase motor in 208 -
600 V, 60 Hz as standard. Different voltage and frequency
are available upon request.

Standard burner motor:


Insulation class F, protection IP 55.

33
Burner selection
Dual fuel burners size 50, version NR
Burner model RGL50/1-B, RGMS50/1-B, Burner model RGL50/2-A, RGMS50/2-A,
vers. ZM-NR vers. ZM-NR vers. ZM-NR vers. ZM-NR
Combustion head G40/2-NR 217x75 G40/2-NR 217x75 Combustion head G50/2-NR 290x185 G50/2-NR 290x185
Capacity in MBH Gas 1,880 – 13,650 1,880 – 13,650 Capacity in MBH NG 2,050 – 18,430 2,050 – 18,430
GPH #2 oil 16 – 97.5 – MBH Propane 2,730 – 18,430 2,730 – 18,430
GPH #6 oil – 25 – 89 GPH #2 oil 27.5 – 131.6 –
GPH #6 oil – 32.6 – 120.4
“WC “WC

9 9

8 8

7 7
High fire

6 6
range

5 5

4 4
High fire

High fire
3 3
range

range
2 2

1 1

0 0

-1 -1

-2 -2
0 1,000 2,000 3,000 4,000 5,000 6,000 7,000 8,000 9,000 10,000 11,000 12,000 13,000 14,000 0 2,000 4,000 6,000 8,000 10,000 12,000 14,000 16,000 18,000 20,000 22,000

GPH #2 10 20 30 40 50 60 70 80 90 100 GPH #2 20 40 60 80 100 120 140

GPH #6 10 20 30 40 50 60 70 80 90 GPH #6 20 40 60 80 100 120 140

Fuels The stated oil throughputs in GPH refer to #2 oil with a


#2 oil
#6 oil calorific value of 140,000 BTU/Gal and #6 oil with a
Nat gas calorific value of 153,000 BTU/Gal.
Propane
The capacity graphs are based on air temperature of
68F (20 °C) and installation altitude of 1,640 ft (500 m).
Burner model Vers. Order No. A reduction of burner capacity of 1 % for every 325 ft
RGL50/1-B ZM-NR 218 504 42 (100 m) should be taken into consideration depending
RGMS50/1-B ZM-NR 219 504 42 on installation altitude.
RGL50/2-A ZM-NR 218 505 42
Voltages and frequencies:
RGMS50/2-A ZM-NR 219 505 42
The burners are equipped with three phase motor in 208 -
600 V, 60 Hz as standard. Different voltage and frequency
are available upon request.

Standard burner motor:


Insulation class F, protection IP 55.

34
Burner selection
Dual fuel burners size 60 and 70, version NR
Burner model RGL60/2-A, RGMS60/2-A, Burner model RGL70/1-B, RGMS70/1-B,
vers. ZM-NR vers. ZM-NR vers. ZM-NR vers. ZM-NR
Combustion head G60/2-NR 345x230 G60/2-NR 345x230 Combustion head G60/2-NR 345x230 G60/2-NR 345x230
Capacity in MBH Gas 2,730 – 20,815 2,730 – 20,815 Capacity in MBH Gas 2,730 – 25,250 2,730 – 25,250
GPH #2 oil 32 – 148.7 – GPH #2 oil 29 – 180 –
GPH #6 oil – 40.1 – 136 GPH #6 oil – 43.9 – 180

“WC “WC

9 9

8 8

7 7
High fire

6 6
range

5 5

4 4
High fire

High fire
3 3
range

range
2 2

1 1

0 0

-1 -1

-2 -2
0 2,000 4,000 6,000 8,000 10,000 12,000 14,000 16,000 18,000 20,000 22,000 0 2,000 4,000 6,000 8,000 10,000 12,000 14,000 16,000 18,000 20,000 22,000 24,000 26,000

GPH #2 20 40 60 80 100 120 140 160 GPH #2 20 40 60 80 100 120 140 160 180

GPH #6 20 40 60 80 100 120 140 GPH #6 20 40 60 80 100 120 140 160

Fuels The stated oil throughputs in GPH refer to #2 oil with a


#2 oil
#6 oil calorific value of 140,000 BTU/Gal and #6 oil with a
Nat gas calorific value of 153,000 BTU/Gal.
Propane
The capacity graphs are based on air temperature of
68F (20 °C) and installation altitude of 1,640 ft (500 m).
Burner model Vers. Order No. A reduction of burner capacity of 1 % for every 325 ft
RGL60/2-A ZM-NR 218 605 42 (100 m) should be taken into consideration depending
RGMS60/2-A ZM-NR 219 605 42 on installation altitude.
RGL70/1-B ZM-NR 218 704 42
Voltages and frequencies:
RGMS70/1-B ZM-NR 219 704 42
The burners are equipped with three phase motor in 208 -
600 V, 60 Hz as standard. Different voltage and frequency
are available upon request.

Standard burner motor:


Insulation class F, protection IP 55.

35
Burner selection
Dual fuel burners size 70, version NR
Burner model RGL70/3-A, RGMS70/3-A, Burner model RGL70/4-A, RGMS70/4-A,
vers. ZM-NR vers. ZM-NR vers. ZM-NR vers. ZM-NR
Combustion head G70/3-NR 425x290 G70/3-NR 425x290 Combustion head G70/3-NR 425x290 G70/3-NR 425x290
Capacity in MBH Gas 3,400 – 36,500 3,400 – 36,515 Capacity in MBH NG 3,400 – 39,930 3,400 – 39,930
MBH Propane 4,780 – 36,500 4,780 – 36,515 MBH Propane 4,780 – 39,930 4,780 – 39,930
GPH #2 oil 42.5 – 259.8 – GPH #2 oil 42.5 – 285.2 –
GPH #6 oil – 39 – 238.7 GPH #6 oil – 39 – 261
“WC “WC
10 10
9 9
8 8
7 7
6 6
5 5
4 4
High fire

High fire
range

range
3 3
2 2
1 1
0 0
-1 -1
-2 -2
0 3,000 6,000 9,000 12,000 15,000 18,000 21,000 24,000 27,000 30,000 33,000 36,000 39,000 42,000 0 3,000 6,000 9,000 12,000 15,000 18,000 21,000 24,000 27,000 30,000 33,000 36,000 39,000 42,000

GPH #2 25 50 75 100 125 150 175 200 225 250 275 300 GPH #2 25 50 75 100 125 150 175 200 225 250 275 300

GPH #6 25 50 75 100 125 150 175 200 225 250 275 GPH #6 25 50 75 100 125 150 175 200 225 250 275

Fuels The stated oil throughputs in GPH refer to #2 oil with a


#2 oil
#6 oil calorific value of 140,000 BTU/Gal and #6 oil with a
Nat gas calorific value of 153,000 BTU/Gal.
Propane
The capacity graphs are based on air temperature of
68F (20 °C) and installation altitude of 1,640 ft (500 m).
Burner model Vers. Order No. A reduction of burner capacity of 1 % for every 325 ft
RGL70/3-A ZM-NR 218 714 14 (100 m) should be taken into consideration depending
RGMS70/3-A ZM-NR 219 714 14 on installation altitude.
RGL70/4-A ZM-NR 218 734 14
Voltages and frequencies:
RGMS70/4-A ZM-NR 219 734 14
The burners are equipped with three phase motor in 208 -
600 V, 60 Hz as standard. Different voltage and frequency
are available upon request.

Standard burner motor:


Insulation class F, protection IP 55.

36
Scope of delivery/Accessories
Dual fuel burners size 30 to 50, version NR
Scope of delivery RGMS30 RGMS40 RGMS50 RGL30 RGL40 RGL50
Burner housing, hinge flange, housing cover, Weishaupt burner motor, air regulator
housing, fan wheel, combustion head, ignition unit, ignition cable, ignition electrodes,
nozzle assembly with oil nozzle/s, combustion manager with operating unit, flame sensor,
stepping motors, flange gasket, limit switch on hinge flange, fixing screws ● ● ● ● ● ●
Combustion manager W-FM100 ● ● ● ● ● ●
Two safety gas shut off valves ● ● ● ● ● ●
Gas butterfly valve ● ● ● ● ● ●
Ignition pilot ● ● ● ● ● ●
Air pressure switch ● ● ● ● ● ●
Oil pressure switch in return ● ● ● ● ● ●
Gas pressure switches ● ● ● ● ● ●
Servomotor driven sliding sleeve in mixing head ● ● ● ● ● ●
Stepping motor for Gas /Air ratio control with W-FM100
Stepping motor for air damper ● ● ● ● ● ●
Stepping motor for gas butterfly valve ● ● ● ● ● ●
Stepping motor for regulating/sliding sleeve ● ● ● ● ● ●
Oil pump, fitted ● ● ● ● ● ●
Oil preheater, fitted ● ● ● – – –
Oil hoses ● ● ● ● ● ●
Two oil solenoid valves in supply and return – – – ● – –
1 solenoid valve in supply and in return,
nozzle head with shut off device (nozzle solenoid) ● ● ● – ● ●
Magnetic coupling ● ● ● ● ● ●

Accessories
Downward firing burner – – ○ ○ ○ ○
Intake flange for the connection of an air duct – – ○ ○ ○ ○
Solenoid valve for air pressure switch test for cont. run fan or post-purge – – ○ ○ ○ ○
Combustion head extension – – ○ ○ ○ ○
Speed control – – ○ ○ ○ ○
O2 trim – – ○ ○ ○ ○
W-FM loose to fit into control panel – – ○ ○ ○ ○
Separate pump station ○ ○ ○ ○ ○ ○
Separate preheater station (electric or media) ○ ○ ○ – – –

● Scope of delivery
○ Accessories

Additional accessories on request.

37
Scope of delivery/Accessories
Dual fuel burners size 60 and 70, version NR
Scope of delivery RGMS60 RGMS70 RGL60 RGL70
Burner housing, hinge flange, housing cover, Weishaupt burner motor, air regulator
housing, fan wheel, combustion head, ignition unit, ignition cable, ignition electrodes,
nozzle assembly with oil nozzle/s, combustion manager with operating unit, flame sensor,
stepping motors, flange gasket, limit switch on hinge flange, fixing screws ● ● ● ●
Combustion manager W-FM100 ● ● ● ●
Two safety gas shut off valves ● ● ● ●
Gas butterfly valve ● ● ● ●
Ignition pilot ● ● ● ●
Air pressure switch ● ● ● ●
Oil pressure switch in return ● ● ● ●
Gas pressure switches ● ● ● ●
Servomotor driven sliding sleeve in mixing head ● ● ● ●
Stepping motor for Gas /Air ratio control with W-FM100
Stepping motor for air damper ● ● ● ●
Stepping motor for gas butterfly valve ● ● ● ●
Stepping motor for regulating/sliding sleeve ● ● ● ●
Oil pump, fitted – – ● ●
Oil hoses ● ● ● ●
1 solenoid valve in supply and in return,
nozzle head with shut off device (nozzle solenoid) ● ● ● ●
Magnetic coupling ● ● ● ●

Accessories
Downward firing burner ○ ○ ○ ○
Intake flange for the connection of an air duct ○ ○ ○ ○
Solenoid valve for air pressure switch test for cont. run fan or post-purge ○ ○ ○ ○
Combustion head extension ○ ○ ○ ○
Speed control ○ ○ ○ ○
O2 trim ○ ○ ○ ○
W-FM loose to fit into control panel ○ ○ ○ ○
Separate pump station ○ ○ ○ ○
Separate preheater station (electric or media) ○ ○ – –

● Scope of delivery
○ Accessories

Additional accessories on request.

38
Technical data
Dual fuel burners size 30 and 40, version NR
Technical data RGL30/2-A RGMS30/2-A
Burner motor 3~208 - 600V Model W-D112/140-2/4K5 W-D112/140-2/4K5
Motor rating HP (kW) 6.6 (5.0) 6.6 (5.0)
FLA at 460V A 8.6 8.6
Speed (60 Hz) rpm 3,510 3,510
Fan wheel Colour / ø red / 248 x 104 red / 248 x 104
Combustion manager Model W-FM100 W-FM100
Ignition unit Model W-ZG02 W-ZG02
Stepping motor Air Model SQM45 SQM45
Mixing head Model SQM45 SQM45
Fuel Model SQM45 SQM45
Pump, fitted Model TA3 TA3
Oil preheater Model – EV2D
Oil throughput GPH (kg/h) – 72 (270)
Heat rating kW – 13.2
Oil solenoid valves 55V 1/4” (supply) 20 W Model 121 K 6220 –
55V 1/8” (return) 20 W Model 121 K 2423 –
55V 3/8” (supply) 20 W Model – 321 H 2322
55V 3/8” (supply) 20 W Model – 121 G 2320
Oil pressure switches 1 – 10 bar (return #2 oil - 5 bar) Model DSA 46 F001
1 – 10 bar (return #6 oil - 7 bar) Model – DSA 46 F001
Oil hoses DN, length in inch (mm) 20/40” (1000) –
(on RGMS, high pressure metal hoses) DN, lenght in inch (mm) – 20/51” (1300)
Burner weight approx. lbs (kg) 320 (145) 386 (175)

Technical data RGL40/1-B RGMS40/1-B


Burner motor 3~208 - 600V Model W-D112/170-2/5K5 W-D112/170-2/5K5
Motor rating HP (kW) 8.6 (6.5) 8.6 (6.5)
FLA at 460V A 12 12
Speed (60 Hz) rpm 3,530 3,530
Fan wheel Colour / ø red / 275 x 104 red / 275 x 104
Combustion manager Model W-FM100 W-FM100
Ignition unit Model W-ZG02 W-ZG02
Stepping motor Air Model SQM45 SQM45
Mixing head Model SQM45 SQM45
Fuel Model SQM45 SQM45
Pump, fitted Model TA3 TA3
Oil preheater Model – EV2D
Oil throughput GPH (kg/h) – 75 (270)
Heat rating kW – 13.2
Oil solenoid valves 55V 3/8” (supply) 20 W Model 321 H 2322 321 H 2322
55V 3/8” (return) 20 W Model 121 G 2320 121 G 2320
Oil pressure switches 1 – 10 bar (return fuel oil EL - 5 bar) Model DSA 46 F001 –
1 – 10 bar (return fuel oil S - 7 bar) Model – DSA 46 F001
Oil hoses DN, length in inch (mm) 20/40” (1000) –
(on RGMS, high pressure metal hoses) DN, length in inch (mm) – 20/51” (1300)
Burner weight approx. lbs (kg) 419 (190) 419 (190)

39
Technical data
Dual fuel burners size 40 and 50, version NR
Technical data RGL40/2-A RGMS40/2-A
Burner motor 3~208 - 600V (40/2) Model W-D112/170-2/7K0 W-D112/170-2/7K0
Motor rating HP (kW) 10.4 (7.8) 10.4 (7.8)
FLA at 460V A 14 14
Speed (60 Hz) rpm 3,500 3,500
Fan wheel Colour / ø red / 275 x 104 red / 275 x 104
Combustion manager Model W-FM100 W-FM100
Ignition unit Model W-ZG02 W-ZG02
Stepping motor Air Model SQM45 SQM45
Mixing head Model SQM45 SQM45
Fuel Model SQM45 SQM45
Pump, fitted Model TA3 TA3
Oil preheater Model – EV2D
Oil throughput GPH (kg/h) – 75 (270)
Heat rating kW – 13.2
Oil solenoid valves 55V 3/8” (supply) 20 W Model 321 H 2322 321 H 2322
55V 3/8” (return) 20 W Model 121 G 2320 121 G 2320
Oil pressure switches 1 – 10 bar (return fuel oil EL - 5 bar) Model DSA 46 F001 –
1 – 10 bar (return fuel oil S - 7 bar) Model – DSA 46 F001
Oil hoses DN, length in inch (mm) 20/40” (1000) –
(on RGMS, high pressure metal hoses) DN, length in inch (mm) – 20/51” (1300)
Burner weight approx. lbs (kg) 419 (190) 419 (190)

Technical data RGL50/1-B RGL50/2-A


Burner motor 3~208 - 600V Model W-D132/170-2/9K0 W-D132/210-2/14K0
Motor rating HP (kW) 14.6 (11) 20 (15)
FLA at 460V A 19 25
Speed (60 Hz) rpm 3,500 3,520
Fan wheel Colour red red
ø 330 x 104.5 330 x 104.5
Combustion manager Model W-FM100 W-FM100
Ignition unit Model W-ZG02 W-ZG02
Stepping motor Air Model SQM45 SQM45
Mixing head Model SQM45 SQM45
Fuel Model SQM45 SQM45
Pump, fitted Model TA4C T2C
Oil solenoid valves 55V 3/8” (supply) 20W Model 321 H 2322 321 H 2322
55V 3/8” (return) 20W Model 121 G 2320 121 G 2320
Oil pressure switch 1 – 10 bar (return #2 oil - 5 bar) Model DSA 46 F001 DSA 46 F001
Oil hoses DN, length in inch and (mm) 25/51” (1300) 25/51” (1300)
Burner weight approx. lbs (kg) 508 (230) 508 (230)

40
Technical data
Dual fuel burners size 50 and 60, version NR
Technical data RGMS50/1-B RGMS50/2-A
Burner motor 3~208 - 600V Model W-D132/170-2/9K0 W-D132/210-2/14K0
Motor rating HP (kW) 14.6 (11) 20 (15)
FLA at 460V A 19 25
Speed (60 Hz) rpm 3,500 3,520
Fan wheel Colour red red
ø 330 x 104.5 330 x 104.5
Combustion manager Model W-FM100 W-FM100
Ignition unit Model W-ZG02 W-ZG02
Stepping motor Air Model SQM45 SQM45
Mixing head Model SQM45 SQM45
Fuel Model SQM45 SQM45
Oil preheater Model WEV2.2/01 2) WEV3/01
Oil throughput GPH (kg/h) 82.5 (300) 137.5 (500)
Heat rating kW 13.8 22.4
Pump, fitted Model TA4C T2C
Oil solenoid valves 55V 3/8” (supply) 20W Model 321 H 2322 321 H 2322
55V 3/8” (return) 20W Model 121 G 2320 121 G 2320
Oil pressure switch 1 – 10 bar (return #6 oil) Model DSA 46 F001 DSA 46 F001
Oil hoses DN/length 25/59” (1500) 25/59” (1500)
Burner weight approx. lbs (kg) 672 (305) 672 (305)

2)
Burners above 82.5 GPH (300 kg/h): Oil preheater WEV3 in lieu of WEV2.2 (refer to Accessories)

Technical data RGL60/2-A RGMS60/2-A


Burner motor 3~208 - 600V Model W-D132/210-2/14K0 W-D132/210-2/14K0
Motor rating HP (kW) 20 (15) 20 (15)
FLA at 460V A 28 28
Speed (60 Hz) rpm 3,520 3,520
Fan wheel Colour red red
ø 465 x 103 465 x 103
Combustion manager Model W-FM100 W-FM100
Ignition unit Model W-ZG02 W-ZG02
Stepping motor Air Model SQM48 SQM48
Mixing head Model SQM45 SQM45
Fuel Model SQM45 SQM45
Pump, fitted Model T2C –
Oil solenoid valves 55V 3/8” (supply) 20W Model 321 H 2322 321 H 2322
55V 3/8” (return) 20W Model 121 G 2320 121 G 2320
110V 3/8” (bypass) 19W Model – 322 H 7306
Oil pressure switches 3 – 25 bar (supply - 18 bar) Model – DSA 58 F001
1 – 10 bar (return #2 oil - 5 bar) Model DSA 46 F001 –
1 – 10 bar (return #6 oil - 7 bar) Model – DSA 46 F001
Oil hoses DN, length in inch and (mm) 25/51” (1300) –
(on RGMS, high pressure metal hoses) DN, length in inch and (mm) – 16/59” (1500)
Burner weight approx. lbs (kg) 684 (310) 640 (290) 2)

2)
Weight without pump and preheater stations

41
Technical data
Dual fuel burners size 70, version NR
Technical data RGL70/1-B RGL70/3-A
Burner motor 3~208 - 600V Model W-D160/240-2/18K0 W-D160/240-2/22K0
Motor rating HP (kW) 22 (16.5) 26.6 (20)
FLA at 460V A 30.5 33
Speed (60 Hz) rpm 3,560 3,550
Fan wheel Colour green green
ø 530 x 120 530 x 120
Combustion manager Model W-FM100 W-FM100
Ignition unit Model W-ZG02 W-ZG02
Stepping motor Air Model SQM48 SQM48
Mixing head Model SQM45 SQM45
Fuel Model SQM45 SQM45
Pump, fitted Model T2C (up to 173 GPH/ 600 kg/h)
Model T3C (from 173 GPH/ 600 kg/h)
Oil solenoid valves 55V 1/2” (supply) 20W Model 321 H 2522 321 H 2522
55V 1/2” (return) 20W Model 121 G 2520 121 G 2520
110V 3/8” (bypass) 19W Model – –
Oil pressure switch 3 – 25 bar (supply - 18 bar) Model – –
1 – 10 bar (return #2 oil - 5 bar) Model DSA 46 F001 DSA 46 F001
1 – 10 bar (return #6 oil - 7 bar) Model – –
Oil hoses DN, length in inch and (mm) 25/1300 25/1300
(on RGMS, high pressure metal hoses) DN, length in inch and (mm) – –
DN, length in inch and (mm) – –
Burner weight approx. lbs (kg) 948 (430) 948 (430)

Technical data RGMS70/1-B RGMS70/3-A


Burner motor 3~208 - 600V Model W-D160/240-2/18K0 W-D160/240-2/22K0
Motor rating HP (kW) 22 (16.5) 26.6 (20)
FLA at 460V A 30.5 33
Speed (60 Hz) rpm 3,560 3,550
Fan wheel Colour green green
ø 530 x 120 530 x 120
Combustion manager Model W-FM100 W-FM100
Ignition unit Model W-ZG02 W-ZG02
Stepping motor Air Model SQM48 SQM48
Mixing head Model SQM48 SQM48
Fuel Model SQM45 SQM45
Pump, fitted Model – –
Model – –
Oil solenoid valves 55V 1/2” (supply) 20W Model 321 H 2522 321 H 2522
55V 1/2” (return) 20W Model 121 G 2520 121 G 2520
110V 3/8” (bypass) 19W Model 322 H 7306 322 H 7306
Oil pressure switch 3 – 25 bar (supply - 18 bar) Model DSA 58 F001 DSA 58 F001
1 – 10 bar (return #2 oil - 5 bar) Model – –
1 – 10 bar (return #6 oil - 7 bar) Model DSA 46 F001 DSA 46 F001
Oil hoses DN, length in inch and (mm) – –
(on RGMS, high pressure metal hoses) DN, length in inch and (mm) 20/1150 20/1150
DN, length in inch and (mm) 20/1500 20/1500
Burner weight approx. lbs (kg) 848 (385) 2) 848 (385) 2)
Technical data
Dual fuel burners size 70, version NR
Technical data RGL70/4-A RGMS70/4-A
Burner motor 3~208 - 600V Model W-D160/240-2/28K0 W-D160/240-2/28K0
Motor rating HP (kW) 37.3 (28) 37.3 (28)
FLA at 400V A 53 53
Speed (55 Hz) rpm 3,220 3,220
Fan wheel Colour blue blue
ø 590 x 160 590 x 160
Combustion manager Model W-FM200 W-FM200
Ignition unit Model W-ZG02 W-ZG02
Stepping motor Air Model SQM48 SQM48
Mixing head Model SQM48 SQM48
Fuel Model SQM45 SQM45
Pump, fitted Model T4C –
Oil solenoid valves 55V 1/2” (supply) 20W Model 321 H 2522 321 H 2522
55V 1/2” (return) 20W Model 121 G 2520 121 G 2520
110V 3/8” (bypass) 19W Model – 322 H 7306
Oil pressure switches 3 – 25 bar (supply - 18 bar) Model – DSA 58 F001
1 – 10 bar (return fuel oil EL - 5 bar) Model DSA 46 F001 –
1 – 10 bar (return fuel oil S - 7 bar) Model – DSA 46 F001
Oil hoses DN, length in inch and (mm) 25/51” (1300) –
(on RGMS, high pressure metal hoses) DN, length in inch and (mm) – 20/45” (1150)
DN, length in inch and (mm) – 20/59” (1500)
Burner weight approx. kg 948 (430) 848 (385) 2)
2)
Weight without pump and preheater stations * Operation with 55 Hz frequency converter only.

43
Burner selection
Dual fuel burners size 50, version 1LN
Burner model RGL50/1-B, vers. ZM-1LN Burner model RGL50/2-A, vers. ZM-1LN
Combustion head G40/2-LN 217x35K Combustion head G50/2-LN 260x40
Capacity in MBH NG 1,710 – 11,600 Capacity in MBH NG 2,050 – 16,725
MBH Propane 1,710 – 11,600 MBH Propane 2,730 – 16,725
GPH #2 oil 19.5 – 82.8 GPH #2 oil 21.3 – 119.4

“WC “WC
9 9

8 8

7 7

6
High fire

6
range

5 5
High fire

4 4
range

High fire
3 3

range
2 2

1 1

0 0

-1 -1

-2 -2
0 1,000 2,000 3,000 4,000 5,000 6,000 7,000 8,000 9,000 10,000 11,000 12,000 13,000 14,000 0 2,000 4,000 6,000 8,000 10,000 12,000 14,000 16,000 18,000

GPH 10 20 30 40 50 60 70 80 90 100 GPH 20 40 60 80 100 120

Fuels The stated oil throughputs in GPH refer to #2 oil with a


#2 oil
Nat gas calorific value of 140,000 BTU/Gal.
Propane
The capacity graphs are based on air temperature of
68F (20 °C) and installation at sea level. A reduction of
burner capacity of 1 % for every 325 ft (100 m) should
Burner model Vers. Order No. be taken into consideration depending on installation
RGL50/1-B ZM-1LN 218 504 16 altitude.
RGL50/2-A ZM-1LN 218 505 17
Voltages and frequencies:
The burners are equipped with three phase motor in 208 -
600 V, 60 Hz as standard. Different voltage and frequency
are available upon request.

Standard burner motor:


Insulation class F, protection IP 55.

44
Burner selection
Dual fuel burners size 70, version 1LN
Burner model RGL70/1-B, vers. ZM-1LN Burner model RGL70/2-A, vers. ZM-1LN
Combustion head G60/2-1LN 300x75 Combustion head G70/2-1LN 365x85
Capacity in MBH NG 2,730 – 24,915 Capacity in MBH NG 3,415 – 34,130
MBH Propane 3,415 – 24,915 MBH Propane 4,780 – 34,130
GPH #2 oil 28.8 – 178 GPH #2 oil 46.3 – 243.8

“WC “WC

9 10

8 9
8
7
7
High fire

6
range

6
5
5
4
4
High fire

High fire
3
range

range
2
2
1 1
0 0

-1 -1

-2 -2
0 2,000 4,000 6,000 8,000 10,000 12,000 14,000 16,000 18,000 20,000 22,000 24,000 26,000 0 3,000 6,000 9,000 12,000 15,000 18,000 21,000 24,000 27,000 30,000 33,000 36,000

GPH 20 40 60 80 100 120 140 160 180 GPH 25 50 75 100 125 150 175 200 225 250

Fuels The stated oil throughputs in GPH refer to #2 oil with a


#2 oil
Nat gas calorific value of 140,000 BTU/Gal.
Propane
The capacity graphs are based on air temperature of
68F (20 °C) and installation at sea level. A reduction of
burner capacity of 1 % for every 325 ft (100 m) should
Burner model Vers. Order No. be taken into consideration depending on installation
RGL70/1-B ZM-1LN 218 704 43 altitude.
RGL70/2-A ZM-1LN 218 705 43
Voltages and frequencies:
The burners are equipped with three phase motor in 208 -
600 V, 60 Hz as standard. Different voltage and frequency
are available upon request.

Standard burner motor:


Insulation class F, protection IP 55.

45
Scope of delivery/Accessories
Dual fuel burners size 50 and 70, version 1LN
Scope of delivery RGL50 RGL70
Burner housing, hinge flange, housing cover, Weishaupt burner motor, air regulator housing, fan wheel,
combustion head, ignition unit, ignition cable, ignition electrode, nozzle assembly with oil nozzle/s,
combustion manager with operating unit, flame sensor stepping motors, flange gasket,
limit switch on hinge flange, fixing screws ● ●
Combustion manager W-FM100 ● ●
Two safety gas valves ● ●
Gas butterfly valve ● ●
Ignition pilot ● ●
Air pressure switch ● ●
Oil pressure switch in return ● ●
Gas pressure switches ● ●
Adjustable regulating sleeve in mixing head ● –
Adjustable flame tube in mixing head – ●
Stepping motor for Gas/Air ratio control with W-FM100
Stepping motor for air regulator ● ●
Stepping motor for gas butterfly valve ● ●
Stepping motor for oil regulator ● ●
Oil pump, fitted ● ●
Oil hoses ● ●
2 oil solenoid valves, 1 safety valve, two stage nozzle head with shut off device (nozzle solenoid) ● ●
Magnetic coupling ● ●

Accessories
Downward firing burner ○ ○
Intake flange for the connection of an air duct ○ ○
Solenoid valve for air pressure switch test for cont. run fan or post-purge ○ ○
Combustion head extension ○ ○
Speed control ○ ○
O2 trim ○ ○
W-FM loose to fit into control panel ○ ○

● Scope of delivery
○ Accessories

Additional accessories on request.

46
Technical data
Dual fuel burners size 50 and 70, version 1LN
Technical data RGL50/1-B RGL50/2-A
Burner motor 3~208 - 600V Model W-D132/170-2/9K0 W-D132/210-2/14K0
Motor rating HP (kW) 14.6 (11) 20 (15)
FLA at 460V A 19 25
Speed (60 Hz) rpm 3,500 3,520
Fan wheel Colour red red
ø 330 x 104.5 330 x 104.5
Combustion manager Model W-FM100 W-FM100
Ignition unit Model W-ZG02 W-ZG02
Stepping motor Air Model SQM45 SQM45
Fuel Model SQM45 SQM45
Pump, fitted Model TA4C T2C
Oil solenoid valves 55V 3/8” (supply) 20 W Model 321 H 2322 321 H 2322
55V 3/8” (return) 20 W Model 121 G 2320 121 G 2320
Oil pressure switch 1 – 10 bar (return - 5 bar) Model DSA 46 F001 DSA 46 F001
Oil hoses DN, length in inch and (mm) 25/51” (1300) 25/51” (1300)
Burner weight approx. lbs (kg) 508 (230) 508 (230)

Technical data RGL70/1-B RGL70/2-A


Burner motor 3~400V 1) Model W-D160/240-2/18K0 W-D160/240-2/22K0
Motor rating HP (kW) 22 (16.5) 26.6 (20)
FLA at 460V A 30.5 33
Speed (60 Hz) rpm 3,560 3,550
Fan wheel Colour green green
ø 530 x 120 530 x 120
Combustion manager Model W-FM100 W-FM 100
Ignition unit Model W-ZG02 W-ZG02
Stepping motor Air Model SQM48 SQM48
Fuel Model SQM45 SQM45
Pump, fitted Model T2C (up to 173 GPH/ 600 kg/h)
T3C (from 173 GPH/ 600 kg/h)
Oil solenoid valves 55V 1/2” (supply) 20 W Model 321 H 2522 321 H 2522
55V 1/2” (return) 20 W Model 121 G 2520 121 G 2520
Oil pressure switch 2 – 40 bar (supply - 18 bar) Model – –
1 – 10 bar (return - 5 bar) Model DSA 46 F 001 DSA 46 F 001
Oil hoses DN, length in inch and (mm) 25/1300 25/1300
Burner weight approx. lbs (kg) 948 (430) 948 (430)

47
®
multiflam Burners
multiflam® principle:
emission reduction as standard
ppm ppm

100 100

90 90

80 80

70 70

60 60

NOx
50 50

40 40
The multiflam® flame shows efficient
combustion
30 30
NOx

In 1998, Weishaupt made history with 20 20


the introduction of multiflam technology

CO
into the market. Unprecedented low
CO

10 10
emission values stunned the industry.
With the patented mixing head,
Weishaupt was able to reduce the Gas #2 Oil
Nitrous Oxide emissions (NOx) for
medium and large burners to values Example values for hot water plant depend on the combustion chamber
normally only seen with compact
burners. Weishaupt has set the stan-
dards with values below 60 ppm for #2
oil and 30 ppm for natural gas, depend- Secondary nozzle 1
ing on the relevant combustion cham-
ber geometry. Secondary nozzle 2

The multiflam® burners therefore com-


ply with the most stringent regulations Secondary diffuser
worldwide and are leaders among in-
dustrial burners particularly in countries Primary diffuser
with strict environmental
Primary nozzle
regulations.

The core of multiflam technology is the


specialy designed mixing head, in which
Primary air
the fuel is distributed in multiple points
and energy released to secondary and
Secondary nozzle 3
primary flames, making combustion
more efficient then ever before. This is Secondary nozzle 4
achieved by the recirculation of flue Secondary air
gases directly in the mixing head.

Schematic of the mixing head

50
Burner selection
Oil burners size 30 to 50, vers. 3LN – multiflam®
Burner model RL30/2-A, version 3LN Burner model RL40/2-A, version 3LN
Combustion head M30/2-4a Combustion head M40/2-4A
Capacity in MBH 1,025– 7,320 Capacity in MBH 1,620 – 10,170
Capacity in GPH#2 7.3– 52.3 Capacity in GPH#2 11.6 – 72.6
“WC “WC

6 7

5 6

5
4

4
3
3
High fire

High fire
2
range

range
2
1
1

0
0

-1 -1

-2 -2
0 500 1,000 1,500 2,000 2,500 3,000 3,500 4,000 4,500 5,000 5,500 6,000 6,500 7,000 7,500 8,000 0 1,000 2,000 3,000 4,000 5,000 6,000 7,000 8,000 9,000 10,000 11,000 12,000 13,000

GPH#2 10 20 30 40 50 GPH#2 10 20 30 40 50 60 70 80 90

Burner model RL50/1-B, version 3LN Burner model Vers. Order No.
Combustion head M50/1-4a
Capacity in MBH 1,825 – 12,800 RL30/2-A 3LN 211 305 24
Capacity in GPH#2 13 – 91.4 RL40/2-A 3LN 211 405 24
“WC

9
RL50/1-B 3LN 211 504 24
8

5 The stated oil throughputs in GPH refer to #2 oil with a


4 calorific value of 140,000 BTU/Gal.
High fire

3
range

1
The capacity graphs are based on air temperature of
0
68F (20 °C) an installation altitude of 1,640 ft (500 m)
-1
above sea level. A reduction of burner capacity of 1 %
-2 for every 325 ft (100 m) should be taken into
0 1,000 2,000 3,000 4,000 5,000 6,000 7,000 8,000 9,000 10,000 11,000 12,000 13,000 14,000
consideration depending on installation altitude.
GPH#2 10 20 30 40 50 60 70 80 90

Voltages and frequencies:


Fuels
#2 oil The burners are equipped with three phase motor in 208 -
600 V, 60 Hz as standard. Different voltage and frequency
are available upon request.

Standard burner motor:


Insulation class F, protection IP 55.

51
Scope of delivery / Accessories / Technical data
Oil burners size 30 to 50, version 3LN
Scope of delivery RL30 RL40 RL50
Burner housing, hinge flange, housing cover, Weishaupt burner motor,
air regulator housing, fan wheel, combustion head, ignition unit, ignition cable,
ignition electrodes, combustion manager with operating unit, UV flame sensor,
stepping motors, flange gasket, limit switch on hinge flange,
fixing screws ● ● ●
Combustion manager W-FM100 ● ● ●
Oil pressure switch in return ● ● ●
Oil pump, fitted ● ● ●
Oil hoses ● ● ●

Accessories
Intake flange for the connection of an air duct ○ ○ ○
Combustion head extension ○ ○ ○
Speed control ○ ○ ○
O2 trim ○ ○ ○
W-FM loose to fit into control panel ○ ○ ○

● Scope of delivery
○ Accessories

Additional accessories available on request.

Technical data RL30/2-A 3LN RL40/2-A 3LN RL50/1-B 3LN


Burner motor 3~208 - 600V Model W-D112/140-2/4K5 W-D112/170-2/7K0 W-D132/170-2/9K0
Motor rating HP (kW) 6.6 (4.5) 10.4 (7.8) 14.6 (11)
FLA at 460 V A 8.6 14 19
Speed (60 Hz) rpm 3,510 3,500 3,500
Fan wheel Colour red red red
ø 248 x 104 275 x 104 330 x 104.5
Combustion manager Model W-FM100 / W-FM200 W-FM100 / W-FM200 W-FM100 / W-FM200
Ignition unit Model W-ZG02 W-ZG02 W-ZG02
Stepping motor Air Model SQM45 SQM45 SQM45
Fuel Model SQM45 SQM45 SQM45
Mixing head Model SQM48 SQM48 SQM48
Pump, fitted Model TA2C TA3C TA4C
Oil solenoid valves 55V 1/4” (supply) 20 W Model 121 K 6220 – –
55V 1/4” (return) 20 W Model 121 K 6220 – –
55V 3/8” (supply) 20 W Model – 321 H 2322 321 H 2322
55V 3/8” (return) 20 W Model – 121 G 2320 121 G 2320
Oil pressure switch 1 – 10 bar (return fuel #2 oil - 5 bar) Model DSA 46 F001 DSA 46 F001 DSA 46 F001
Oil hoses DN, length in inch and (mm) 20/39” (1000) 20/39” (1000) 25/51” (1300)
Burner weight approx. lbs (kg) 220 (100) 313 (142) 458 (208)

52
Burner selection
Gas burners size 30 and 50, version 3LN
Burner model G30/2-A, version 3LN Burner model G40/2-A, version 3LN
Combustion head G30/2-3LN Combustion head G40/2-3LN
Capacity in MBH Nat Gas 1,025 – 6,825 Capacity in MBH Nat Gas 1,365 – 9,555

“WC “WC

6 7

6
5

5
4

4
3
3
2
High fire

High fire
2
range

range
1
1

0
0

-1 -1

-2 -2
0 500 1,000 1,500 2,000 2,500 3,000 3,500 4,000 4,500 5,000 5,500 6,000 6,500 7,000 7,500 8,000 0 1,000 2,000 3,000 4,000 5,000 6,000 7,000 8,000 9,000 10,000
MBH MBH

Burner model G50/1-B, version 3LN Burner model G50/2-A, version 3LN
Combustion head G50/1-3LN Combustion head G50/2-3LN
Capacity in MBH Nat Gas 1,535 – 11,945 Capacity in MBH Nat Gas 1,710 – 15,360

“WC “WC
9 9
8 8

7 7

6 6
5 5

4 4
High fire
High fire

3 3
range
range

2 2
1 1

0 0
-1 -1

-2 -2
0 1,000 2,000 3,000 4,000 5,000 6,000 7,000 8,000 9,000 10,000 11,000 12,000 13,000 14,000 0 2,000 4,000 6,000 8,000 10,000 12,000 14,000 16,000 18,000
MBH MBH

Fuels – capacity with


combustion head open close
Nat gas

Burner model Vers. Order No. The capacity graphs are based on air temperature
G30/2-A 3LN 217 305 08 of 68F (20 °C) an installation altitude at sea level. A
reduction of burner capacity of 1 % for every 325 ft
G40/2-A 3LN 217 405 10
(100 m) should be taken into consideration in case
G50/1-B 3LN 217 504 10 of installation altitude above 0 ft.
G50/2-A 3LN 217 505 44
Voltages and frequencies:
The burners are equipped with three phase motor in 208 -
600 V, 60 Hz as standard. Different voltage and frequency
are available upon request.

Standard burner motor:


Insulation class F, protection IP 55.

53
Burner selection
Gas burners size 60 and 70, version 3LN
Burner model G60/2-A, version 3LN Burner model G70/1-B, version 3LN
Combustion head G60/2-3LN Combustion head G70/1-3LN
Capacity in MBH Nat Gas 2,220 – 19,795 Capacity in MBH Nat Gas 2,560 – 23,890

“WC “WC
9 9

8 8

7 7

6 6

5 5

4 4

High fire
High fire

3 3

range
range

2 2

1 1

0 0

-1 -1

-2 -2
0 2,000 4,000 6,000 8,000 10,000 12,000 14,000 16,000 18,000 20,000 22,000 0 2,000 4,000 6,000 8,000 10,000 12,000 14,000 16,000 18,000 20,000 22,000 24,000 26,000
MBH MBH

Burner model G70/2-A, version 3LN


Combustion head G70/2-3LN
Capacity in MBH Nat Gas 3,075 – 31,055

“WC
10
9
The capacity graphs are based on air temperature
8 of 68F (20 °C) an installation altitude at sea level. A
7 reduction of burner capacity of 1 % for every 325 ft
6
(100 m) should be taken into consideration in case
5

4
of installation altitude above 0 ft.
High fire
range

2 Voltages and frequencies:


1
The burners are equipped with three phase motor in 208 -
0

-1
600 V, 60 Hz as standard. Different voltage and frequency
-2
are available upon request.
0 3,000 6,000 9,000 12,000 15,000 18,000 21,000 24,000 27,000 30,000 33,000 36,000
MBH
Standard burner motor:
Fuels – capacity with Insulation class F, protection IP 55.
combustion head open close
Nat gas

Burner model Vers. Order No.


G60/2-A 3LN 217 605 44
G70/1-B 3LN 217 704 44
G70/2-A 3LN 217 705 54

54
Scope of delivery/Accessories
Gas burners size 30 to 70, version 3LN
Scope of delivery G30 G40 G50 G60 G70
Burner housing, hinge flange, housing cover, Weishaupt burner motor, air regulator
housing, fan wheel, combustion head, ignition unit, ignition cable, ignition electrodes,
combustion manager with operating unit, UV flame sensor, stepping motors,
flange gasket, limit switch on hinge flange, fixing screws ● ● ● ● ●
Combustion manager W-FM100 ● ● ● ● ●
Two safety gas shut off valves ● ● ● ● ●
Ignition pilot ● ● ● ● ●
Air pressure switch ● ● ● ● ●
Gas pressure switch ● ● ● ● ●
Ratio controlled sliding sleeve in mixing head ● ● ● ● ●
Stepping motor for
Air regulator ● ● ● ● ●
Gas butterfly valve ● ● ● ● ●
Mixing head ● ● ● ● ●

Accessories
Intake flange for the connection of an air duct ○ ○ ○ ○ ○
Combustion head extension ○ ○ ○ ○ ○
Speed control ○ ○ ○ ○ ○
O2 trim ○ ○ ○ ○ ○
W-FM loose to fit into control panel ○ ○ ○ ○ ○

● Scope of delivery
○ Accessories

Additional accessories available on request.

55
Technical data
Gas burners size 30 to 70, version 3LN
Technical data G30/2-A 3LN G40/2-A 3LN G50/1-B 3LN G50/2-A 3LN
Burner motor 3~208 - 600V Model W-D112/140-2/4K5 W-D112/170-2/7K0 W-D132/170-2/9K0 W-D132/210-2/14K0
Motor rating HP (kW) 6.6 (5.0) 10.4 (7.8) 14.6 (11) 20 (15)
FLA at 460V A 8.6 14 19 25
Speed (60 Hz) rpm 3,510 3,500 3,500 3,520
Fan wheel Colour red red red red
ø 248 x 104 275 x 104 330 x 104.5 330 x 104.5
Combustion manager Model W-FM100 W-FM100 W-FM100 W-FM100
Model W-FM200 W-FM200 W-FM200 W-FM200
Ignition unit Model W-ZG02 W-ZG02 W-ZG02 W-ZG02
Stepping motor Air Model SQM45 SQM45 SQM45 SQM45
Fuel Model SQM45 SQM45 SQM45 SQM45
Mixing head Model SQM48 SQM48 SQM48 SQM48
Burner weight approx. lbs (kg) 320 (145) 353 (160) 518 (235) 530 (240)

Technical data G60/2-A 3LN G70/1-B 3LN G70/2-A 3LN


Burner motor 3~208 - 600V Model W-D132/210-2/14K0 W-D160/240-2/18K0 W-D160/240-2/22K0
Motor rating HP (kW) 20 (15) 22 (16.5) 26.6 (20)
FLA at 460V A 28 30.5 33
Speed (60 Hz) rpm 3,520 3,560 3,550
Fan wheel Colour no color code green green
ø 450 x 127.5-R 530 x 120 530 x 120
Combustion manager Model W-FM100 W-FM100 W-FM100
Model W-FM200 W-FM200 W-FM200
Ignition unit Model W-ZG02 W-ZG02 W-ZG02
Stepping motor Air Model SQM45 SQM45 SQM45
Fuel Model SQM45 SQM45 SQM45
Mixing head Model SQM48 SQM48 SQM48
Burner weight approx. lbs (kg) 728 (330) 960 (435) 960 (435)
)

56
Burner selection
Dual fuel burners size 30 and 40, version 3LN
Burner model RGL30/2-A, version 3LN Burner model RGL40/2-A, version 3LN
Combustion head G30/2-3LN Combustion head G40/2-3LN
Capacity in MBH NG 1,025 – 6,825 Capacity in MBH NG 1,365 – 9,555
MBH #2 1,220 – 6,825 MBH #2 1,625 – 9,555
GPH #2 oil 8.7 – 49 GPH #2 oil 11.6 – 68.2

“WC “WC

6 7

6
5

5
4
fire
range range

4
3
High fireHigh

3
2

High fire
2

range
1
1

0
0

-1 -1

-2 -2
0 500 1,000 1,500 2,000 2,500 3,000 3,500 4,000 4,500 5,000 5,500 6,000 6,500 7,000 7,500 8,000 0 1,000 2,000 3,000 4,000 5,000 6,000 7,000 8,000 9,000 10,000

GPH #2 10 20 30 40 50 GPH #2 10 20 30 40 50 60 70

Fuels The stated oil throughputs in GPH refer to #2 oil with a


#2 oil
Nat gas calorific value of 140,000 BTU/Gal.

The capacity graphs are based on air temperature of


68F (20 °C) and installation at sea level. A reduction of
burner capacity of 1 % for every 325 ft (100 m) should
Burner model Vers. Order No. be taken into consideration depending on installation
RGL30/2-A 3LN 218 305 18 altitude.
RGL40/2-A 3LN 218 405 18
Voltages and frequencies:
The burners are equipped with three phase motor in 208 -
600 V, 60 Hz as standard. Different voltage and frequency
are available upon request.

Standard burner motor:


Insulation class F, protection IP 55.

57
Burner selection
Dual fuel burners size 50, version 3LN
Burner model RGL50/1-B, version 3LN Burner model RGL50/2-A, version 3LN
Combustion head G50/1-3LN Combustion head G50/2-3LN
Capacity in MBH NG 1,540 – 11,945 Capacity in MBH NG 1,710 – 15,360
MBH #2 1,830 – 11,945 MBH #2 2,030 – 15,360
GPH #2 oil 13 – 85 GPH #2 oil 14.5 – 109.7

“WC “WC
9 9

8 8

7 7

6 6
High fire
High fire range

5 5

4 4

High fire
3 3

range
range

2 2

1 1

0 0

-1 -1

-2 -2
0 1,000 2,000 3,000 4,000 5,000 6,000 7,000 8,000 9,000 10,000 11,000 12,000 13,000 14,000 0 2,000 4,000 6,000 8,000 10,000 12,000 14,000 16,000 18,000

GPH #2 10 20 30 40 50 60 70 80 90 GPH #2 10 20 30 40 50 60 70 80 90 100 110 120

Fuels The stated oil throughputs in GPH refer to #2 oil with a


#2 oil
Nat gas calorific value of 140,000 BTU/Gal.

The capacity graphs are based on air temperature of


68F (20 °C) and installation at sea level. A reduction of
burner capacity of 1 % for every 325 ft (100 m) should
Burner model Vers. Order No. be taken into consideration depending on installation
RGL50/1-B 3LN 218 504 44 altitude.
RGL50/2-A 3LN 218 505 44
Voltages and frequencies:
The burners are equipped with three phase motor in 208 -
600 V, 60 Hz as standard. Different voltage and frequency
are available upon request.

Standard burner motor:


Insulation class F, protection IP 55.

58
Burner selection
Dual fuel burners size 60 and 70, version 3LN
Burner model RGL60/2-A, version 3LN Burner model RGL70/1-B, version 3LN
Combustion head G60/2-3LN Combustion head G70/1-3LN
Capacity in MBH NG 2,220 – 18,770 Capacity in MBH NG 2,560 – 23,890
MBH #2 3,655 – 18,770 MBH #2 4,065 – 23,890
GPH #2 oil 26 – 134 GPH #2 oil 29 – 170

“WC “WC

9 9

8 8

7 7
High fire

6 6
range

5 5

4 4

High fire
High fire

3 3

range
range

2 2

1 1

0 0

-1 -1

-2 -2
0 2,000 4,000 6,000 8,000 10,000 12,000 14,000 16,000 18,000 20,000 22,000 0 2,000 4,000 6,000 8,000 10,000 12,000 14,000 16,000 18,000 20,000 22,000 24,000 26,000

GPH #2 20 40 60 80 100 120 140 GPH #2 20 40 60 80 100 120 140 160 180

Burner model RGL70/2-A, version 3LN The stated oil throughputs in GPH refer to #2 oil with a
Combustion head G70/2-3LN
Capacity in MBH NG 3,075 – 31,055 calorific value of 140,000 BTU/Gal.
MBH #2 5,285 – 31,055
GPH #2 oil 37.7 – 221.8 The capacity graphs are based on air temperature of
68F (20 °C) and installation at sea level. A reduction of
burner capacity of 1 % for every 325 ft (100 m) should
“WC
10
be taken into consideration depending on installation
9 altitude.
8

7
Voltages and frequencies:
High fire
range

5
The burners are equipped with three phase motor in 208 -
4 600 V, 60 Hz as standard. Different voltage and frequency
High fire

are available upon request.


range

2
1
0
Standard burner motor:
-1 Insulation class F, protection IP 55.
-2
0 3,000 6,000 9,000 12,000 15,000 18,000 21,000 24,000 27,000 30,000 33,000 36,000

GPH #2 25 50 75 100 125 150 175 200 225 250

Burner model Vers. Order No.


RGL60/2-A 3LN 218 605 44
RGL70/1-B 3LN 218 704 44
Fuels
#2 oil RGL70/2-A 3LN 218 705 44
Nat gas

59
Scope of delivery/Accessories
Dual fuel burners size 30 and 70, version 3LN
Scope of delivery RGL30 RGL40 RGL50 RGL60 RGL70
Burner housing, hinge flange, housing cover, Weishaupt burner motor, air regulator
housing, fan wheel, combustion head, ignition unit, ignition cable, ignition electrodes,
atomising system with oil nozzle/s, combustion manager with operating unit, flame sensor,
stepping motors, flange gasket, limit switch on hinge flange, fixing screws ● ● ● ● ●
Combustion manager W-FM100 ● ● ● ● ●
Two gas shut off valves ● ● ● ● ●
Ignition pilot ● ● ● ● ●
Gas butterfly valve ● ● ● ● ●
Air pressure switch ● ● ● ● ●
Gas pressure switches ● ● ● ● ●
Ratio control sliding sleeve in mixing head ● ● ● ● ●
Stepping motor for
Air regulator ● ● ● ● ●
Gas butterfly valve ● ● ● ● ●
Mixing head ● ● ● ● ●

Accessories
Intake flange for the connection of an air duct ○ ○ ○ ○ ○
Solenoid valve for air pressure switch test for cont. run fan or post-purge ○ ○ ○ ○ ○
Combustion head extension ○ ○ ○ ○ ○
Speed control ○ ○ ○ ○ ○
O2 trim ○ ○ ○ ○ ○
W-FM loose for installation in a remote control panel ○ ○ ○ ○ ○

● Scope of delivery
○ Accessories

Additional accessories available on request.

60
Technical data
Dual fuel burners size 30 to 50, version 3LN
Technical data RGL30/2-A 3LN RGL40/2-A 3LN
Burner motor 3~208 - 600V Model W-D112/140-2/4K5 W-D112/170-2/7K0
Motor rating HP (kW) 6.6 (5.0) 10.4 (7.8)
FLA at 460V A 8.6 14
Speed (60 Hz) rpm 3,510 3,500
Fan wheel Colour red red
ø 248 x 104 275 x 104
Combustion manager Model W-FM100 / W-FM200 W-FM100 / W-FM200
Ignition unit Model W-ZG02 W-ZG02
Stepping motor Air Model SQM45 SQM45
Fuel Model SQM45 SQM45
Mixing head Model SQM48 SQM48
Pump, fitted Model TA3C TA3C
Oil solenoid valves 55V (supply) Model 121 K 6220 321 H 2322
55V (return) Model 121 K 6220 121 G 2320
Oil pressure switch 1 – 10 bar Model DSA 46 F001 DSA 46 F001
(return #2 oil - 5 bar)
Oil hoses DN, length in inch (mm) 20/40” (1000) 20/40” (1000)
Burner weight approx. lbs (kg) 320 (145) 353 (160)

Technical data RGL50/1-B 3LN RGL50/2-A 3LN


Burner motor 3~208 - 600V Model W-D132/170-2/9K0 W-D132/210-2/14K0
Motor rating HP (kW) 14.6 (11) 20 (15)
FLA at 460V A 19 25
Speed (60 Hz) rpm 3,500 3,520
Fan wheel Colour red red
ø 330 x 104.5 330 x 104.5
Combustion manager Model W-FM100 / W-FM200 W-FM100 / W-FM200
Ignition unit Model W-ZG02 W-ZG02
Stepping motor Air Model SQM45 SQM45
Fuel Model SQM45 SQM45
Mixing head Model SQM48 SQM48
Pump, fitted Model TA4C T2C
Oil solenoid valves 55V (supply) Model 321 H 2322 321 H 2322
55V (return) Model 121 G 2320 121 G 2320
Oil pressure switch 1 – 10 bar Model DSA 46 F001 DSA 46 F001
(return #2 oil - 5 bar)
Oil hoses DN, length in inch and (mm) 25/51” (1300) 25/51” (1300)
Burner weight approx. lbs (kg) 518 (235) 530 (240)

61
Technical data
Dual fuel burners size 60 and 70, version 3LN
Technical data RGL60/2-A 3LN RGL70/1-B 3LN RGL70/2-A 3LN
Burner motor 3~208 - 600V Model W-D132/210-2/14K0 W-D160/240-2/18K0 W-D160/240-2/22K0
Motor rating HP (kW) 20 (15) 22 (16.5) 26.6 (20)
FLA at 460V A 28 30.5 33
Speed (60 Hz) rpm 3,520 3,560 3,550
Fan wheel Colour / ø no color / 450 x 127.5-R green / 530 x 120 green / 530 x 120
Combustion manager Model W-FM100 / W-FM100 / W-FM100 /
W-FM200 W-FM200 W-FM200
Ignition unit Model W-ZG02 W-ZG02 W-ZG02
Stepping motor Air Model SQM45 SQM45 SQM45
Fuel Model SQM45 SQM45 SQM45
Mixing head Model SQM48 SQM48 SQM48
Pump, fitted Model T2C T2C (up to T3C
130 GPH / 450 kg/h)
T3C (from
130 GPH / 450 kg/h)
Oil solenoid valves 55V (supply) Model 321 H 2322 321 H 2522 321 H 2522
55V (return) Model 121 G 2320 121 G 2520 121 G 2520
Oil pressure switch 1 – 10 bar Model DSA 46 F001 DSA 46 F001 DSA 46 F001
(return #2 oil - 5 bar)
Oil hoses DN, length in inch and (mm) 25/51” (1300) 25/51” (1300) 25/51” (1300)
Burner weight approx. lbs (kg) 728 (330) 960 (435) 960 (435)

62
Oil burner dimensions
Size 30 to 70

d1
h1
b 4 d2 b1
h3 r2
b2
r1
approx. 10.4
d5
(264 mm)*

l3 l1

d7
* depending on oil preheater d6

Burner Dimensions in inches and (mm)


model b1 b2 b4 d1 d2 d5 d6 d7 h1 h3 l1 l3 r1 r2
MS30Z/2-A 32.0 15.7 16.5 11.0 9.8 14.2 11.2 22.5 16.0 35.1 11.9 37.4 35.0
(813) (399) (418) (280) (250) M12 (360) (285) (572) (407) (892) (303) (950) (890)
RMS30/2-A 32.1 15.7 16.5 11.0 9.8 14.2 11.2 22.5 16.0 35.1 11.9 37.4 35.0
(815) (399) (418) (280) (250) M12 (360) (285) (572) (407) (892) (303) (950) (890)
MS40Z/1-B 34.9 17.4 18.2 11.0 9.8 14.2 11.2 23.9 16.6 36.9 11.9 43.3 38.2
(887) (441) (462) (280) (250) M12 (360) (285) (607) (422) (937) (303) (1100) (970)
RMS40/1-B 35.0 17.4 18.2 11.0 9.8 14.2 11.2 23.9 16.6 36.9 11.9 43.3 38.2
(889) (441) (462) (280) (250) M12 (360) (285) (607) (422) (937) (303) (1100) (970)
RMS40/2-A 35.0 17.4 18.2 12.6 11.4 15.7 12.8 23.9 16.6 36.9 14.2 43.3 38.2
(889) (441) (462) (320) (290) M12 (400) (325) (607) (422) (937) (361) (1100) (970)
L50T/2-A 39.1 19.4 21.7 15.0 11.0 18.9 15.4 28.7 20.2 39.0 14.1 43.3 40.4
(992) (493) (550) (380) (280) M16 (480) (390) (728) (513) (990) (357) (1100) (1025)
RL50/1-B 38.2 18.2 21.7 12.6 11.4 15.7 13.0 28.7 20.2 38.8 14.2 43.3 39.4
(970) (463) (550) (320) (290) M12 (400) (330) (728) (513) (985) (361) (1100) (1000)
RMS50/1-B 38.2 18.2 21.7 12.6 11.4 15.7 13.0 28.7 20.2 38.8 14.2 43.3 39.4
(970) (463) (550) (320) (290) M12 (400) (330) (728) (513) (985) (361) (1100) (1000)
RL50/2-A 39.1 19.4 21.7 15.0 13.8 18.9 15.4 28.7 20.2 39.0 15.2 43.3 40.4
(993) (493) (550) (380) (350) M16 (480) (390) (728) (513) (990) (386) (1100) (1025)
RMS50/2-A 39.1 19.4 21.7 15.0 13.8 18.9 15.4 28.7 20.2 39.0 15.2 43.3 40.4
(993) (493) (550) (380) (350) M16 (480) (390) (728) (513) (990) (386) (1100) (1025)
RL60/2-A 43.3 20.4 26.4 16.9 15.7 18.5 17.1 36.6 26.4 46.8 16.0 49.6 44.9
(1100) (517) (670) (429) (400) M16 (470) (435) (930) (670) (1189) (407) (1260) (1140)
RMS60/2-A 44.6 20.4 26.4 16.9 15.7 18.5 17.1 36.6 26.4 46.8 16.0 49.6 44.9
(1132) (517) (670) (429) (400) M16 (470) (435) (930) (670) (1189) (407) (1260) (1140)
RL70/1-A 50.3 23.7 29.9 18.5 18.9 21.7 19.7 42.3 30.5 53.9 16.4 59.1 51.6
(1277) (603) (760) (470) (480) M16 (550) (500) (1075) (775) (1368) (417) (1500) (1310)
RMS70/1-A 50.8 23.7 29.9 18.5 18.9 21.7 19.7 42.3 30.5 53.9 16.4 59.1 51.6
(1290) (603) (760) (470) (480) M16 (550) (500) (1075) (775) (1368) (417) (1500) (1310)
RL70/2-A 51.1 24.5 29.9 18.5 18.9 21.7 19.7 42.3 30.5 53.9 16.4 59.1 51.6
(1297) (623) (760) (470) (480) M16 (550) (500) (1075) (775) (1368) (417) (1500) (1310)
RMS70/2-A 51.6 24.5 29.9 18.5 18.9 21.7 19.7 42.3 30.5 53.9 16.4 59.1 51.6
(1310) (623) (760) (470) (480) M16 (550) (500) (1075) (775) (1368) (417) (1500) (1310)
Refer to burner manual for additional dimensions

63
Oil burner dimensions
Size 30 to 70

d1
h1
b 4 d2 b1
h3 r2
b2
r1
approx. 10.4
d5
(264 mm)*

l3 l1

d7
* depending on oil preheater d6

Burner Dimensions in inches and (mm)


model b1 b2 b4 d1 d2 d5 d6 d7 h1 h3 l1 l3 r1 r2
RL30/2-A 3LN 31.9 15.7 16.5 11.0 10.1 14.2 11.2 22.5 16.0 35.1 14.1 37.4 35.0
(811) (399) (418) (280) (256) M12 (360) (285) (572) (407) (892) (359) (950) (890)
RL40/2-A 3LN 35.0 17.4 18.2 12.6 11.7 15.7 12.8 23.9 16.6 36.9 14.8 43.3 38.2
(889) (441) (462) (320) (296) M12 (400) (325) (607) (422) (937) (376) (1100) (970)
RL50/1-B 3LN 38.2 18.2 21.7 12.6 11.7 15.7 12.8 28.7 20.2 39.0 14.8 43.3 39.4
(970) (463) (550) (320) (296) M12 (400) (325) (728) (513) (990) (376) (1100) (1000)
Refer to burner manual for additional dimensions

64
Gas burner dimensions
Size 30 to 70

d5

b 4 d 1 d2 r2 b1
h1
b2
h3
d7
d6 r1
l10
l3 l9
l1

(Shown version 3LN)

Burner Dimensions in inches and (mm)


model b1 b2 b4 d1 d2 d5 d6 d7 h1 h3 l1 l3 l9 l10 r1 r2
G50/1-B ZM-NR 33.8 18.8 21.7 12.6 11.4 15.7 12.8 28.7 20.2 47.0 13.1 10.2 5.2 41.7 39.4
(858) (478) (550) (320) (290) M12 (400) (325) (730) (513) (1195) (332) (258) (133) (1060) (1000)
G50/2-A ZM-NR 35.0 19.5 21.7 15.0 13.8 18.9 15.4 28.7 20.2 49.0 13.1 12.1 6.2 41.7 40.4
(890) (495) (550) (380) (350) M16 (480) (390) (730) (513) (1245) (332) (308) (158) (1060) (1025)
G60/2-A ZM-NR 39.8 20.4 26.4 17.0 15.7 18.5 17.1 36.6 26.4 58.2 14.1 13.7 7.0 49.2 44.9
(1010) (517) (670) (432) (400) M16 (470) (435) (930) (670) (1478) (357) (348) (178) (1250) (1140)
G70/1-B ZM-NR 46.0 25.4 29.9 17.0 15.7 18.5 17.1 42.3 30.5 64.9 14.1 13.7 7.0 56.7 51.6
(1169) (646) (760) (432) (400) M16 (470) (435) (1075) (775) (1648) (357) (348) (178) (1440) (1310)
G70/3-A ZM-NR 45.1 24.5 29.9 20.1 18.9 22.8 20.9 42.3 30.5 65.4 18.4 14.5 7.3 56.7 51.6
(1145) (622) (760) (510) (480) M16 (580) (530) (1075) (775) (1660) (467) (368) (186) (1440) (1310)
G70/4-A ZM-NR 45.1 24.5 29.9 20.1 18.9 22.8 20.9 42.3 30.5 65.4 18.4 14.5 7.3 56.7 51.6
(1145) (622) (760) (510) (480) M16 (580) (530) (1075) (775) (1660) (467) (368) (186) (1440) (1310)
G50/1-B ZM-1LN 33.8 18.8 21.7 12.6 11.4 15.7 12.8 28.7 20.2 47.0 13.1 10.2 5.2 41.7 39.4
(858) (478) (550) (320) (290) M12 (400) (325) (730) (513) (1195) (332) (258) (133) (1060) (1000)
G70/1-B ZM-1LN 46.0 25.4 29.9 17.0 16.0 18.5 17.1 42.3 30.5 64.9 16.5 13.7 7.0 56.7 51.6
(1169) (646) (760) (432) (406) M16 (470) (435) (1075) (775) (1648) (419) (348) (178) (1440) (1310)
G50/2-A ZM-1LN 35.0 19.5 21.7 15.0 13.8 18.9 15.4 28.7 20.2 49.0 17.6 12.1 6.2 41.7 40.4
(890) (495) (550) (380) (350) M16 (480) (390) (730) (513) (1245) (447) (308) (158) (1060) (1025)
G70/2-A ZM-1LN 46.9 24.5 29.9 18.5 18.9 21.7 19.7 42.3 30.5 65.7 17.6 14.5 7.4 56.7 51.6
(1190) (622) (760) (470) (480) M16 (550) (500) (1075) (775) (1668) (447) (368) (188) (1440) (1310)
G50/1-B ZM-LN 33.8 18.8 21.7 12.6 11.7 15.7 12.8 28.7 20.2 47.0 14.4 10.2 5.2 41.7 39.4
(858) (478) (550) (320) (296) M12 (400) (325) (730) (513) (1195) (367) (258) (133) (1060) (1000)
G50/2-A ZM-LN 35.0 19.5 21.7 15.0 13.8 18.9 15.4 28.7 20.2 49.0 15.2 12.1 6.2 41.7 40.4
(890) (495) (550) (380) (350) M16 (480) (390) (730) (513) (1245) (387) (308) (158) (1060) (1025)
G60/2-A ZM-LN 39.8 20.4 26.4 17.0 16.0 18.5 17.1 36.6 26.4 58.2 17.0 13.7 7.0 49.2 44.9
(1010) (517) (670) (432) (406) M16 (470) (435) (930) (670) (1478) (432) (348) (178) (1250) (1140)
G70/1-B ZM-LN 46.0 23.7 29.9 17.0 16.0 18.5 17.1 42.3 30.5 64.9 17.0 13.7 7.0 56.7 51.6
(1169) (601) (760) (432) (406) M16 (470) (435) (1075) (775) (1648) (432) (348) (178) (1440) (1310)
G70/2-A ZM-LN 46.9 24.5 29.9 18.5 18.9 21.7 19.7 42.3 30.5 65.7 17.2 14.5 7.4 56.7 51.6
(1190) (622) (760) (470) (480) M16 (550) (500) (1075) (775) (1668) (437) (368) (188) (1440) (1310)
Refer to burner manual for additional dimension

65
Gas burner dimensions
Size 30 to 70

d5

b 4 d 1 d2 r2 b1
h1
b2
h3
d7
d6 r1
l10
l3 l9
l1

(Shown version 3LN)

Burner Dimensions in inches and (mm)


model b1 b2 b4 d1 d2 d5 d6 d7 h1 h3 l1 l3 l9 l10 r1 r2
G30/2-A 3LN 28.7 15.7 16.5 11.0 10.1 14.2 11.2 22.5 16.0 42.6 14.4 9.4 4.8 33.1 35.0
(729) (400) (418) (280) (256) M12 (360) (285) (572) (407) (1083) (366) (238) (123) (840) (890)
G40/2-A 3LN 31.3 17.4 18.2 12.6 11.7 15.7 12.8 23.9 16.6 45.2 15.0 10.2 5.2 35.2 38.2
(795) (441) (462) (320) (296) M12 (400) (325) (607) (422) (1148) (380) (258) (133) (895) (970)
G50/1-B 3LN 33.8 18.8 21.7 12.6 11.7 15.7 12.8 28.7 20.2 47.0 15.0 10.2 5.2 41.7 39.4
(858) (478) (550) (320) (296) M12 (400) (325) (730) (513) (1195) (380) (258) (133) (1060) (1000)
G50/2-A 3LN 44.1 20.7 21.7 15.0 13.2 18.9 15.4 28.7 20.2 49.0 17.7 12.1 6.2 41.7 40.4
(1119) (525) (550) (380) (335) M16 (480) (390) (730) (513) (1245) (450) (308) (158) (1060) (1025)
G60/2-A 3LN 39.8 20.4 26.4 17.0 14.8 18.5 17.1 36.6 26.4 58.2 18.9 13.7 7.0 53.1 44.9
(1010) (517) (670) (432) (376) M16 (470) (435) (930) (670) (1478) (480) (348) (178) (1350) (1140)
G70/1-B 3LN 47.8 25.4 29.9 17.0 14.8 18.5 17.1 42.3 30.5 64.9 18.9 13.7 7.0 59.1 51.6
(1214) (646) (760) (432) (376) M16 (470) (435) (1075) (775) (1648) (480) (348) (178) (1500) (1310)
G70/2-A 3LN 46.9 24.5 29.9 18.5 17.5 21.7 19.7 42.3 30.5 65.7 18.7 14.5 7.4 59.1 51.6
(1190) (622) (760) (470) (444) M16 (550) (500) (1075) (775) (1668) (475) (368) (188) (1500) (1310)
Refer to burner manual for additional dimension

66
Dual fuel burner dimensions
Size 30 to 70

d5

b1
r2
b4 d1 d2

h1
b2
h3 d7
d6 r1
l10
l3 l9
l1

(Shown version 3LN)

Burner Dimensions in inches and (mm)


model b1 b2 b4 d1 d2 d5 d6 d7 h1 h3 l1 l3 l9 l10 r1 r2
RGMS30/2-A NR 42.6 14.6 13.0 11.0 9.8 14.2 11.2 22.5 16.0 42.6 10.7 13.3 4.8 38.2 38.6
(1083) (371) (330) (280) (250) M12 (360) (285) (572) (407) (1083) (272) (338) (123) (970) (980)
RGMS40/1-B NR 38.1 15.9 13.0 11.0 9.8 14.2 11.2 23.9 16.6 44.4 10.7 13.3 4.8 41.3 38.2
(967) (403) (330) (280) (250) M12 (360) (285) (608) (422) (1129) (272) (338) (123) (1050) (970)
RGMS40/2-A NR 38.1 15.9 14.6 12.6 11.4 15.7 12.8 23.9 16.6 45.2 13.0 14.1 5.2 41.3 38.2
(967) (403) (370) (320) (290) M12 (400) (325) (608) (422) (1148) (330) (358) (133) (1050) (970)
RGL50/1-B ZM-NR 43.2 18.8 21.7 12.6 11.4 15.7 12.8 28.7 20.2 47.0 13.1 10.2 5.2 46.5 39.4
(1098) (478) (550) (320) (290) M12 (400) (325) (730) (513) (1195) (332) (258) (133) (1180) (1000)
RGMS50/1-B ZM-NR 43.2 18.8 21.7 12.6 11.4 15.7 12.8 28.7 20.2 47.0 13.1 10.2 5.2 46.5 39.4
(1098) (478) (550) (320) (290) M12 (400) (325) (730) (513) (1195) (332) (258) (133) (1180) (1000)
RGL50/2-A ZM-NR 44.5 19.5 21.7 15.0 13.8 18.9 15.4 28.7 20.2 49.0 13.1 12.1 6.2 46.5 40.4
(1130) (495) (550) (380) (350) M16 (480) (390) (730) (513) (1245) (332) (308) (158) (1180) (1025)
RGMS50/2-A ZM-NR 44.5 19.5 21.7 15.0 13.8 18.9 15.4 28.7 20.2 49.0 13.1 12.1 6.2 46.5 40.4
(1130) (495) (550) (380) (350) M16 (480) (390) (730) (513) (1245) (332) (308) (158) (1180) (1025)
RGL60/2-A ZM-NR 49.0 20.4 26.4 17.0 15.7 18.5 17.1 36.6 26.4 58.2 14.1 13.7 7.0 53.1 44.9
(1245) (517) (670) (432) (400) M16 (470) (435) (930) (670) (1478) (357) (348) (178) (1350) (1140)
RGMS60/2-A ZM-NR 44.6 20.4 26.4 17.0 15.7 18.5 17.1 36.6 26.4 58.2 14.1 13.7 7.0 53.1 44.9
(1132) (517) (670) (432) (400) M16 (470) (435) (930) (670) (1478) (357) (348) (178) (1350) (1140)
RGL70/1-B ZM-NR 57.2 25.4 29.9 17.0 15.7 18.5 17.1 42.3 30.5 64.8 14.1 13.7 7.0 59.1 51.6
(1454) (646) (760) (432) (400) M16 (470) (435) (1075) (775) (1646) (357) (348) (178) (1500) (1310)
RGMS70/1-B ZM-NR 50.8 25.4 29.9 17.0 15.7 18.5 17.1 42.3 30.5 64.8 14.1 13.7 7.0 59.1 51.6
(1290) (646) (760) (432) (400) M16 (470) (435) (1075) (775) (1646) (357) (348) (178) (1500) (1310)
RGL70/2-A ZM-NR 56.3 24.5 29.9 18.5 18.9 21.7 19.7 42.3 30.5 65.6 14.3 14.5 7.4 59.1 51.6
(1430) (622) (760) (470) (480) M16 (550) (500) (1075) (775) (1666) (362) (368) (188) (1500) (1310)
RGMS70/2-A ZM-NR 51.6 24.5 29.9 18.5 18.9 21.7 19.7 42.3 30.5 65.6 14.3 14.5 7.4 59.1 51.6
(1310) (622) (760) (470) (480) M16 (550) (500) (1075) (775) (1666) (362) (368) (188) (1500) (1310)
RGL70/3-A ZM-NR 56.3 24.5 29.9 20.1 18.9 22.8 20.9 42.3 30.5 65.4 18.4 14.5 7.3 59.1 51.6
(1430) (622) (760) (510) (480) M16 (580) (530) (1075) (775) (1660) (467) (368) (186) (1500) (1310)
)
RGMS70/3-A ZM-NR 51.6 24.5 29.9 20.1 18.9 22.8 20.9 42.3 30.5 65.4 18.4 14.5 7.3 59.1 51.6
(1310) (622) (760) (510) (480) M16 (580) (530) (1075) (775) (1660) (467) (368) (186) (1500) (1310)
Refer to burner manual for additional dimension

67
Dual fuel burner dimensions
Size 30 to 70

d5

b1
r2
b4 d1 d2

h1
b2
h3 d7
d6 r1
l10
l3 l9
l1

(Shown version 3LN)

Burner Dimensions in inches and (mm)


model b1 b2 b4 d1 d2 d5 d6 d7 h1 h3 l1 l3 l9 l10 r1 r2
RGL70/4-A ZM-NR 56.3 24.5 29.9 20.1 18.9 22.8 20.9 42.3 30.5 65.4 18.4 14.5 7.3 59.1 51.6
(1430) (622) (760) (510) (480) M16 (580) (530) (1075) (775) (1660) (467) (368) (186) (1500) (1310)
RGMS70/4-A ZM-NR 51.6 24.5 29.9 20.1 18.9 22.8 20.9 42.3 30.5 65.4 18.4 14.5 7.3 59.1 51.6
(1310) (622) (760) (510) (480) M16 (580) (530) (1075) (775) (1660) (467) (368) (186) (1500) (1310)
RGL50/2-A ZM-1LN 44.5 19.5 21.7 15.0 13.8 18.9 15.4 28.7 20.2 49.0 17.6 12.1 6.2 46.5 40.4
(1130) (495) (550) (382) (350) M16 (480) (390) (730) (513) (1245) (447) (308) (158) (1180) (1025)
RGL70/1-B ZM-1LN 57.2 25.4 29.9 17.0 16.0 18.5 17.1 42.3 30.5 64.9 16.5 13.7 7.0 59.1 51.6
(1454) (646) (760) (432) (406) M16 (470) (435) (1075) (775) (1648) (419) (348) (178) (1500) (1310)
RGL70/2-A ZM-1LN 56.3 24.5 29.9 18.5 18.9 21.7 19.7 42.3 30.5 65.7 17.6 14.5 7.4 59.1 51.6
(1430) (622) (760) (470) (480) M16 (550) (500) (1075) (775) (1668) (447) (368) (188) (1500) (1310)
RGL30/2-A 3LN 36.4 15.7 16.5 11.0 10.1 14.2 11.2 22.5 16.0 42.6 14.4 9.4 4.8 38.2 35.0
(924) (400) (418) (280) (256) M12 (360) (285) (572) (407) (1083) (366) (238) (123) (970) (890)
RGL40/2-A 3LN 39.0 17.4 18.2 12.6 11.7 15.7 12.8 23.9 16.6 45.2 15.0 10.2 5.2 41.3 38.2
(990) (441) (462) (320) (296) M12 (400) (325) (607) (422) (1148) (380) (258) (133) (1050) (970)
RGL50/1-B 3LN 43.2 18.8 21.7 12.6 11.7 15.7 12.8 28.7 20.2 47.0 15.0 10.2 5.2 46.5 39.4
(1098) (478) (550) (320) (296) M12 (400) (325) (730) (513) (1195) (380) (258) (133) (1180) (1000)
RGL50/2-A 3LN 44.5 19.5 21.7 15.0 13.2 18.9 15.4 28.7 20.2 49.0 17.7 12.1 6.2 46.5 40.4
(1130) (495) (550) (380) (335) M16 (480) (390) (730) (513) (1245) (450) (308) (158) (1180) (1025)
RGL60/2-A 3LN 49.0 20.4 26.4 17.0 14.8 18.5 17.1 36.6 26.4 58.2 18.9 13.7 7.0 53.1 44.9
(1245) (517) (670) (432) (376) M16 (470) (435) (930) (670) (1478) (480) (348) (178) (1350) (1140)
RGL70/1-B 3LN 57.2 25.4 29.9 17.0 14.8 18.5 17.1 42.3 30.5 64.9 18.9 13.7 7.0 59.1 51.6
(1454) (646) (760) (432) (376) M16 (470) (435) (1075) (775) (1648) (480) (348) (178) (1500) (1310)
RGL70/2-A 3LN 56.3 24.5 29.9 18.5 17.5 21.7 19.7 42.3 30.5 65.7 18.7 14.5 7.4 59.1 51.6
(1430) (622) (760) (470) (444) M16 (550) (500) (1075) (775) (1668) (475) (368) (188) (1500) (1310)
Refer to burner manual for additional dimension

68
Fuel systems
GL30Z (oil side) GL30T/GL40T/L50T (oil side) RGL30 (oil side)

10 13 13a 16a 10 13 13a 16a 10 12 12 16a

110V 110V 110V 110V 55V 55V

110V 110V 55V 55V


P M

110V

13a 13a 13a 12a 14a 15 12a

MS30Z/2-A, MS40Z/1-B RL50 to RL70 RMS30 to RMS50


RGL40 to RGL70 (oil side) RGMS30 to RGMS50 (oil side)
Pump and oil preheater fitted

10 11 12 17 16 10 11 12 16 10 11 12 17 18a 16

55V 55V 55V

55V 55V 55V


P M P M

12a 14a 13b 13 12a 14a 15 12a 14a 15

69
Fuel systems
RGMS60/70 (oil side) RL30 to RL50 vers. 3LN
With separate pump and preheater stations RGL30 to RGL70 vers. 3LN (oil side)

10 17 11 18b 14b 12 16 10 11 12 12

P 16

55V 55V 55V


16

110V
16
55V 55V
55V
P M 16
P M

19 12a 12a 14a 15

12b 12a 18b 14a 15

G30 to G70 (gas side vers. NR) G30 to G70 vers. LN


RGL30 to RGL70 vers. 3LN (gas side)

6 7 4b 9
6 7 4b 9 The gas train schematics show typical con-
figuration for UL gas train. The actual gas
train shipped with burner might have differ-
ent configuration depending on applicable
code and regulation.

8
P P P P

1 2 3 4 1 5 1 2 3 4 1 5

Legend
1 Ball valve 11 Strainer 14a Oil pressure switch in return
2 Gas pressure regulator 12 Oil solenoid valve, normally closed (55V con- 14b Oil pressure switch in supply (optional, not
3 Low gas pressure switch nected in series with 12a) shown)
4 Double main SSOV 12a Oil solenoid valve, normally closed 15 Oil regulator
4b Pilot gas valves (55V connected in series with 12, installed 16 Nozzle head with shut off device
5 High gas pressure switch against the flow direction) 16a Nozzle head without shut off device
6 Pilot train ball valve 12b Bypass solenoid valve, normally open 17 Oil preheater
7 Pilot gas pressure regulator 13 Oil solenoid valve, normally closed 18a Temperature switch
8 Gas butterfly valve 13a Oil solenoid valve, normally closed 18b Temperature sensor Pt 100
9 Burner for stage 1, 2 and 3 (to monitor minimum oil temperature)
10 Oil pump 13b Oil solenoid valve, normally open 19 External oil filter 1

70
Pump and preheater stations
Scope of delivery – pump station medium used. Planning and installation
Pump unit (screw spindle pump with When selecting and sizing, please refer instructions
motor), pressure gauge, vacuum gauge, to the oil temperature diagrams in Oil filter, air/gas separator, circulation
pressure regulating valve, ball valves, chapter 5.3 of the technical brochure tank, pump station and oil preheater
suction flange, pressure flange “Weishaupt electric and medium oil station must be installed as close as
including counter flanges, screws and preheaters”, print No. 18. Weishaupt possible to the burner.
washers, suction side filter. All parts are medium oil preheaters can be used
fully assembled on an oil drip tray. universally. It is possible to change the On burners with separate oil preheater
medium at any time. The preheaters are the time required for oil circulation
The pump station is built as one of two used either alone or in conjunction with during start up depends on the length
different versions - either as a single an electric oil preheater. of the pipework between the burner
station unit with one pump, or as a twin and the air/gas separator or circulation
station unit with two pumps with one If operating steam at more than 110 PSI tank.
pump serves as a backup unit. Should or hot water between 360 F (180 °C)
one pump fail, it is possible to quickly and 390 F (200 °C) is continuously The shorter the pipeline, the shorter the
switch over to the other. available, then an electric preheater period between heat being called for
is not required. This is also possible if and oil release and burner start after a
Only tried and tested makes of pump installation with the above minimum controlled shutdown.
are used. The pumps are carefully pressures or temperatures can be
matched to the capacity of the burner. operated with #2 oil or gas.

Scope of delivery - preheater If the medium temperature is not


stations sufficient to adequately preheat the
Preheater stations are supplied fully fuel oil, then the electric oil preheater
assembled on an oil drip tray. The provides the additional heat required.
preheater ensures constant The electric oil preheater heats the
regulation of the oil temperature oil for the start up of the installation.
and thus the viscosity of the fuel oil. If the required medium temperature is
available then the station switches over
There are two basic versions of the to the medium oil preheater thus saving
preheater station available: on expensive electrical energy.
1. Electric preheater
2. Medium preheater Suitable connection for medium oil pre-
heaters can be selected, depending on
WEV.. and MV.. type preheaters are the medium. If medium oil preheaters
used. are provided without electric oil pre-
heaters, a temperature controller must
MV medium oil preheater be used with the medium connection
Medium preheaters are high capacity, fittings. Medium connection fittings are
forced circulation heat exchangers. available as an option.
High capacity is achieved with a
compact, space saving construction. General instructions
Hot water, steam or thermal fluid can When starting a boiler from a cold
be used as heating media. The oil condition with heavy oil, an electric oil
preheaters guarantee largely stable preheater capacity must be provided for
oil temperatures and thus good at least 30 % of the boiler rating.
combustion figures. The oil temperature
achieved depends on the heating

71
Pump and preheater stations
Specification

Burner Technical data - Pump Version with 1 pump Version with 2 pumps
Rating Flow rate in GPH (l/h) Speed Motor rating Pump model Pump model
GPH (based on 150cSt) rpm HP (kW)
Pump stations - frequency 60 Hz
74 – 114 265 (1,020) 3,400 2.9 (2.2) SPF 10-38 SPZ 10-38
114 – 214 532 (2,050) 3,400 3.4 (2.6) SPF 20-38 SPZ 20-38

214 – 265 705 (2,720) 3,400 5.3 (4.0) SPF 20-46 SPZ 20-46

Model Quantity Medium preheater Electric preheater (EV)


oil flow in GPH (kg/h) Oil flow in GPH (kg/h) at ΔT = 135F (75°C)
Preheater stations
WEV3.1/01 1 – 103 (375)
WEV3.1/01 2 – 205 (750)
WEV3/01 1 – 137.5 (500)
WEV3/01 2 – 275 (1000)
MV9C with temperature regulator 1 137.5 (500) –
MV9C without temperature regulator 1 137.5 (500) –
MV10A with temperature regulator 1 275 (1000) –
MV10A without temperature regulator 1 275 (1000) –

72
That is not a Facade. Weishaupt has been one of the
leading company in heating and combustion industry
since years with headquarter in Schwendi and branches
all over the world. That is Reliability.
Weishaupt is Trustworthy, quality,
Reliability. good customer service,
The family business innovation and experi-
in Schwendi was ence are values on
established by Max which the Pioneer Max
Weishaupt in 1932. Weishaupt established
Represented in 55 his company. All this
countries by branch combined in a word is
offices and subsidiaries reliability.
Weishaupt is interna-
tional leader in the Therefore stands
areas of combustion Weishaupt today.
technology and heating
applications.

73
73
That is not an Imagination. Continuous research
and development at Weishaupt ensure environ-
mental friendly and efficient burners.
That is Reliability.

Test facility at Weishaupt R&D centre

74
Developing improvement.
Weishaupt recognizes the signs of time
and researches perpetually to get more
efficient and environmental friendly
burner systems.

This way not only Weishaupt prevents


largely unnecessary energy cost but
also actively contributes in conserving
the environment.

75
Weishaupt Corporation
6280 Danville Road
Mississauga, ON L5T 2H7, Canada
Ph: (905) 564 0946
Fax: (905) 564 0949
www.weishaupt-corp.com

Weishaupt America Inc.


2587 Millenium Drive, Unit A
Elgin, IL 60124, USA
Ph: (847) 531 5800
Fax: (847) 531 5855
www.weishaupt-america.com

Print No. 83211116, June 2012


Printed in Germany. All rights reserved.

Regular maintenance reduces heating Weishaupt customer service is there for


costs and environmental pollution. Only a you all year round. Whenever you need
properly adjusted burner can save energy help, be it the supply of spare parts,
and be environmentally friendly. Behind technical advice or a site visit. We are
each Weishaupt burner stands the whole there when you need us.
Weishaupt customer service organization.
The outstanding efforts made in
maintenance and service justify the
enormous trust placed in Weishaupt’s
burners, for at Weishaupt product and
customer service belong together.

You might also like