Product: Industrial Burners
Product: Industrial Burners
Industrial burners
Industrial burners sizes 30 to 70 • flexible and reliable
Weishaupt Industrial Burners:
Flexible and reliable
For more than 50 years, Weishaupt industrial burners have set
global standards in terms of reliability, energy efficiency, noise
levels and ease of use.
With firing rate between 3,400 and 40,000 MBH, the spectrum
of application possibilities covers from heating and steam boilers
to air heaters and modern high efficiency boilers.
With its wide range of industrial burners, which can be used with
almost any gaseous or liquid fuel, Weishaupt has the right burner
for virtually any job.
2
3
Burner housing can
Burner motor be hinged open to the
left or to the right
Air pressure switch
Mixing head
Flame sensor
Fan wheel
Index of contents
5
Weishaupt industrial burners sizes 30 to 70
High capacity and flexible application range
Weishaupt industrial burners have Applicable fuels The most important advantages:
been especially designed for • Light oil #2 • Large capacity and application range
industrial applications. The viscosity up to 6 cSt (6 mm2/s) at • Stable fan characteristics
monobloc burners are noteworthy 68F (20 °C) to ASTM D396 • Good combustion behaviour
for their large capacity and • Medium #4 to heavy fuel #6 oil • Burner housing can be hinged open
operational ranges and numerous viscosity up to 50 cSt (50 mm2/s at • Easy installation, commissioning and
technical details: 212F (100 °C) to ASTM D396 service
• Natural Gas • Increased safety provided by nozzle
Flexible application range • Propane head shut off device with dedicated
The burners can be used on heat nozzle shut off solenoid
exchangers such as hot water boilers, Permissible ambient conditions: • Nozzle circulation and precise oil
steam boilers, air heaters and for • Ambient temperature temperature regulation on heavy fuel
certain process applications. As the -10 to +40 °C (14 to 104F) oil burners
burners are capable of overcoming high -15 to +40 °C (5 to 104F) • Compliance with current emission
combustion chamber resistances, they • Air humidity: max. 80% relative standards worldwide
are primarily used on high efficiency humidity, no condensation • High turndown ratio (RL, RGL)
boilers. • Suitable only for indoor operation
• For installation in unheated rooms
Digital combustion management under some circumstances special
Digital combustion management solutions are required (contact
ensures simple and safe operation Weishaupt)
of combustion application. All important
functions, such as fuel and air supply or Any discrepancy from the above de-
flame monitoring are controlled with scribed applications requires written
digital precision. Operational functions confirmation from Weishaupt Corpora-
are optimized, economy is maximized tion. The maintenance interval could be
and emissions are minimized. shortened according to conditions
The integral ModBus interface allows where the burners are installed.
communication with building
automization/ management system. Approvals
The burners are in compliance with
Energy saving with speed control most North American and European
and O2 trim applicable standards.
Electrical consumption is definitely
a cost factor for large combustion Outstanding service
application. Weishaupt maintains an extensive
Speed control uses frequency drive global sales and service network.
to match fan speed to the actual air Customer service is available every day
requirement, allowing for significant around the clock. In-house training by
savings of electricity, particularly at low Weishaupt ensures the high standard
fire. With O2 trim the flue gases are of their service engineers.
continuously monitored and controlled
to ensure the best possible degree of
combustion efficiency and thus lower
fuel consumption and increased
reliability.
6
Characteristics of the different variations
Version Standard Version 3LN
Oil, gas and dual fuel burners for LowNOx gas and dual fuel burners
installations without specific NOx with patented multiflam mixing head
requirements. Suitable for Natural Gas, for installations with more stringent low
Propane, #2 - #6 oil, as well as special NOx requirements. Low NOx values are
gases and special oils on request. achieved by fuel distribution method.
Suitable for Natural Gas, Propane and
Version NR #2 oil.
Gas and dual fuel burners with
advanced, standard mixing head for
applications where there is NOx
requirements on gas side. NR means:
lower NOx emission on gas side com-
pared to the standard version. Oil side
as standard version. Suitable for
Natural Gas, Propane, #2 - #6 oil.
Version 1LN
LowNOx gas and dual fuel burners with
special mixing head for applications,
where there are requirements for lower
NOx emission on gas and oil side. 1LN
means: lower NOx values compared to
version NR.
Suitable for Natural Gas, Propane, #2
oil.
Version LN
LowNOx gas burners with special
mixing head for installations where
there is requirement for lower NOx
emission on gas operation.
Lower NOx value compared to vers.
1LN . Suitable for Natural Gas and
Propane.
7
Oil burners
Burner selection
Oil burners size 30, version Standard
Burner model MS30Z/2-A Burner model RMS30/2-A
Combustion head M30/2 - 190k x 65 Combustion head M30/2 - 190k x 65
Capacity in MBH 2,300 – 8,330 Capacity in MBH 2,300 – 8,330
Capacity in GPH#6 15 – 54.5 Capacity in GPH#6 15 – 54.5
“WC “WC
5 6
4 5
4
3
3
2
High fire
2
range
1
1
0
0
-1 -1
-2 -2
MBH 0 1,000 2,000 3,000 4,000 5,000 6,000 7,000 8,000 9,000 MBH 0 1,000 2,000 3,000 4,000 5,000 6,000 7,000 8,000 9,000
GPH #6 7.5 15 22.5 30 37.5 45 52.5 60 GPH #6 7.5 15 22.5 30 37.5 45 52.5 60
Fuels
#6 oil
10
Burner selection
Oil burners size 40, version Standard
Burner model MS40Z/1-B MS40Z/1-B Burner model RMS40/1-B
Combustion head M30/2 - 200x50 M30/2 - 175x50 Combustion head M30/2 - 190k x 65
Capacity in MBH 3,445 – 8,740 3,445 – 10,170 Capacity in MBH 2,680 – 9,965
Capacity in GPH#6 22.5 – 57 22.5 – 66 Capacity in GPH#6 17.5 – 65
“WC “WC
6 8
7
5
6
4
5
3
4
High fire
2 3
range
High fire
range
1 2
1
0
0
-1
-1
-2 -2
MBH 0 1,000 2,000 3,000 4,000 5,000 6,000 7,000 8,000 9,000 10,000 11,000 12,000 MBH 0 1,000 2,000 3,000 4,000 5,000 6,000 7,000 8,000 9,000 10,000 11,000 12,000
GPH #6 10 20 30 40 50 60 70 80 GPH #6 10 20 30 40 50 60 70 80
11
Burner selection
Oil burners size 50, version Standard
Burner model L50T/2-A Burner model RL50/1-B RMS50/1-B
Combustion head M50/1 - 185x50 Combustion head M40/2 - 217x75 M40/2 - 217x75
Capacity in MBH 3,445 – 16,260 Capacity in MBH 2,440 – 13,000 3,840 – 13,000
Capacity in GPH#2 25 – 116 Capacity in GPH#2 17 – 93 –
“WC “WC GPH#6 – 25 – 85
8 9
8
7
7
6
6
5
5
4
4
3
High fire
3
range
2
2
1 1
0 0
-1 -1
-2 -2
MBH 0 2,000 4,000 6,000 8,000 10,000 12,000 14,000 16,000 18,000 MBH 0 1,000 2,000 3,000 4,000 5,000 6,000 7,000 8,000 9,000 10,000 11,000 12,000 13,000 14,000
GPH #6 10 20 30 40 50 60 70 80 90
6
RMS50/2-A ZM 212 505 02
5
4
High fire
3
range
-1
calorific value of 153,000 BTU/Gal.
-2
MBH 0 2,000 4,000 6,000 8,000 10,000 12,000 14,000 16,000 18,000 20,000 22,000 24,000
The capacity graphs are based on air temperature of
GPH #2 20 40 60 80 100 120 140 160
68F (20 °C) an installation altitude of 1,640 ft (500 m)
GPH #6 20 40 60 80 100 120 140 160
above sea level. A reduction of burner capacity of 1 %
for every 325 ft (100 m) should be taken into
consideration depending on installation altitude.
Fuel oils
#2 oil
Voltages and frequencies:
#6 oil The burners are equipped with three phase motor in 208 -
600 V, 60 Hz as standard. Different voltage and frequency
are available upon request.
12
Burner selection
Oil burners size 60 and 70, version Standard
Burner model RL60/2-A RMS60/2-A Burner model RL70/1-A RMS70/1-A
Combustion head M60/2-345-230 M60/2-345-230 Combustion head M70/1a-425-290 M70/1a-425-290
Capacity in MBH 4,470– 24,795 6,140 – 24,795 Capacity in MBH 6,500 – 29,860 6,910 – 29,860
Capacity in GPH#2 32– 176 – Capacity in GPH#2 46 – 213 –
“WC GPH#6 – 40 – 162 “WC GPH#6 – 45 – 195
9 9
8 8
7 7
6 6
5 5
4 4
High fire
High fire
3 3
range
range
2 2
1 1
0 0
-1 -1
-2 -2
MBH 0 2,000 4,000 6,000 8,000 10,000 12,000 14,000 16,000 18,000 20,000 22,000 24,000 26,000 MBH 0 2,500 5,000 7,500 10,000 12,500 15,000 17,500 20,000 22,500 25,000 27,500 30,000 32,500 35,000
GPH #2 20 40 60 80 100 120 140 160 180 GPH #2 20 40 60 80 100 120 140 160 180 200 220 240
GPH #6 20 40 60 80 100 120 140 160 GPH #6 20 40 60 80 100 120 140 160 180 200 220
3
2 The stated oil throughputs in GPH refer to #2 oil with a
1 calorific value of 140,000 BTU/Gal and #6 oil with a
0
calorific value of 153,000 BTU/Gal.
-1
-2
MBH 0 3,000 6,000 9,000 12,000 15,000 18,000 21,000 24,000 27,000 30,000 33,000 36,000 39,000
The capacity graphs are based on air temperature of
GPH #2 25 50 75 100 125 150 175 200 225 250 275
68F (20 °C) an installation altitude of 1,640 ft (500 m)
GPH #6 25 50 75 100 125 150 175 200 225 250
above sea level. A reduction of burner capacity of 1 %
for every 325 ft (100 m) should be taken into
consideration depending on installation altitude.
Fuels
#2 oil Voltages and frequencies:
#6 oil The burners are equipped with three phase motor in 208 -
600 V, 60 Hz as standard. Different voltage and frequency
are available upon request.
13
Scope of delivery/Accessories
Oil burners size 30 to 70, version Standard
Scope of delivery MS30 MS40 RMS30 RMS40 RMS50 RMS60 RMS70 L50 RL50 RL60 RL70
Accessories
Intake flange for connection of air duct ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
Stainless steel oil hoses, heated ○ ○ ○ ○ ○ ○ ○ – – – –
Magnetic coupling – – ○ ○ ○ – – ○ ○ ○ ○
Combustion head extension ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
Media preheater with fittings ○ ○ ○ ○ ○ ○ ○ – – – –
Speed control – – ○ ○ ○ ○ ○ ○ ○ ○ ○
O2 trim – – ○ ○ ○ ○ ○ ○ ○ ○ ○
W-FM loosed for installation in remote panel – – ○ ○ ○ ○ ○ ○ ○ ○ ○
● Scope of delivery
○ Accessories
14
Technical data
Oil burners size 30 and 40, version Standard
Technical data MS30Z/2-A RMS30/2-A
Burner motor 3~208 - 600V Model W-D112/140-2/4K5 W-D112/140-2/4K5
Motor rating HP (kW) 6.6 (4.5) 6.6 (4.5)
FLA at 460V A 8.6 8.6
Speed (60 Hz) rpm 3,510 3,510
Fan wheel Color / ø red / 248 x 104 red / 248 x 104
Combustion manager Model LAL2.25 W-FM100
Ignition unit Model W-ZG02 W-ZG02
Stepping motor Air Model 1055/80 SQM45
Fuel Model – SQM45
Mixing head Model – SQM45
Pump fitted Model E7 TA3
Oil preheater Model EV2D EV2D
Oil throughput GPH and (kg/h) 72 (270) 72 (270)
Heat rating kW 13.2 13.2
Oil solenoid valves 110V 1/8” 19 W Model 121 K 2423 –
110V 1/8” 19 W Model 122 K 9321 –
55V 3/8” (supply) 20 W Model 321 H 2322 321 H 2322
55V 3/8” (return) 20 W Model 121 G 2320 121 G 2320
Oil pressure switches 1 – 10 bar (return fuel oil EL - 5 bar) Model – –
1 – 10 bar (return fuel oil S - 7 bar) Model DSA 46 F001 DSA 46 F001
Oil hoses DN, length in inch and (mm) 20/40” (1000) 20/40” (1000)
(on MS, RMS and RGMS, high pressure metal hoses) 20/51” (1300) 20/51” (1300)
Burner weight approx. lbs (kg) 297 (135) 309 (140)
15
Technical data
Oil burners size 50, version Standard
Technical data L50T/2-A RL50/1-B RL50/2-A
Burner motor 3~208 V - 600V Model W-D132/210-2/14K0 W-D132/170-2/9K0 W-D132/210-2/14K0
Motor rating HP (kW) 20 (15) 14.6 (11) 20 (15)
FLA at 460V A 25 19 25
Speed (60 Hz) rpm 3,520 3,500 3,520
Fan wheel Colour / ø red / 330 x 104.5 red / 330 x 104.5 red / 330 x 104.5
Combustion manager Model W-FM100 W-FM100 W-FM100
Ignition unit Model W-ZG02 W-ZG02 W-ZG02
Stepping motor Air Model SQM45 SQM45 SQM45
Fuel Model – SQM45 SQM45
Mixing head Model – SQM45 SQM45
Pump, fitted Model TA2C TA4C T2C
Oil preheater Model – – –
Oil throughput in GPH and (kg/h) – – –
Heat rating kW – – –
Oil solenoid valve 110V 1/8” 19 W Model 121 K 2423 (3 off) – –
110V 1/4” (safety v.) 20 W Model 121 K 6220 – –
55V 3/8” (supply) 20 W Model – 321 H 2322 321 H 2322
55V 3/8” (return) 20 W Model – 121 G 2320 121 G 2320
Oil pressure switches 1 – 10 bar (return #2 oil - 5 bar) Model – DSA 46 F001 DSA 46 F001
1 – 10 bar (return #6 oil - 7 bar) Model – – –
Oil hoses DN, length in inch and (mm) 20/51” (1300) 25/51” (1300) 25/51” (1300)
Burner weight approx. lbs (kg) 440 (200) 458 (208) 463 (210)
1)
Burners above 82.5 GPH (300 kg/h): Oil preheater WEV3 in lieu of WEV2.2,
Refer to ‘Accessories’
16
Technical data
Oil burners size 60 and 70, version Standard
Technical data RL60/2-A RMS60/2-A
Burner motor 3~208 - 600V Model W-D132/210-2/14K0 W-D132/210-2/14K0
Motor rating HP (kW) 20 (15) 20 (15)
FLA at 460V A 25 25
Speed (60 Hz) rpm 3,520 3,520
Fan wheel Colour / ø red / 465 x 103 red / 465 x 103
Combustion manager Model W-FM100 W-FM100
Ignition unit Model W-ZG02 W-ZG02
Stepping motor Air Model SQM45 SQM45
Fuel Model SQM45 SQM45
Mixing head Model SQM45 SQM45
Pump fitted Model T2C –
Oil solenoid valves 55V 3/8” (supply) 20 W Model 321 H 2322 321 H 2322
55V 3/8” (return) 20 W Model 121 G 2320 121 G 2320
110V 3/8” (bypass) 19 W Model – 322 H 7306
Oil pressure switches 3 – 25 bar (supply-18 bar) Model – DSA 58 F 001
1 – 10 bar (return #2 oil-5 bar) Model DSA 46 F 001 –
1 – 10 bar (return #6 oil-7 bar) Model – DSA 46 F 001
Oil hoses DN, length in inch and (mm) 25/51” (1300) 16/45” (1150)
(on RMS and RGMS, high pressure metal hoses) – 16/59” (1500)
Burner weight approx. lbs (kg) 552 (250) 463 (210) 2)
2)
Weight without pump and preheater station
17
Gas burners
Burner selection
Gas burners size 50 to 70, version NR
Burner model G50/1-B, vers. ZM-NR Burner model G50/2-A, vers. ZM-NR
Combustion head G40/2-NR 217x75 Combustion head G50/2-NR 290x85
Capacity in MBH Nat Gas 1,875 – 13,650 Capacity in MBH Nat Gas 2,050 – 18,430
Propane 1,875 – 13,650 Propane 2,050 – 18,430
“WC “WC
9 9
8 8
7 7
6 6
5 5
4 4
High fire
High fire
3 3
range
range
2 2
1 1
0 0
-1 -1
-2 -2
0 1,000 2,000 3,000 4,000 5,000 6,000 7,000 8,000 9,000 10,000 11,000 12,000 13,000 14,000 0 2,000 4,000 6,000 8,000 10,000 12,000 14,000 16,000 18,000 20,000 22,000
Burner model G60/2-A, vers. ZM-NR Burner model G70/1-B, vers. ZM-NR
Combustion head G60/2-NR 345x230 Combustion head G60/2-NR 345x230
Capacity in MBH Nat Gas 2,730 – 20,800 Capacity in MBH Nat Gas 2,730 – 25,250
Propane 2,730 – 20,800 Propane 2,730 – 25,250
“WC “WC
9 9
8 8
7 7
6 6
5 5
4 4
High fire
High fire
3 3
range
range
2 2
1 1
0 0
-1 -1
-2 -2
0 2,000 4,000 6,000 8,000 10,000 12,000 14,000 16,000 18,000 20,000 22,000 0 2,000 4,000 6,000 8,000 10,000 12,000 14,000 16,000 18,000 20,000 22,000 24,000 26,000
Fuels
Nat gas
Propane
Burner model Vers. Order No. The capacity graphs are based on air temperature of
G50/1-B ZM-NR 217 504 15 68F (20 °C) and installation altitude of 1,640 ft (500 m).
A reduction of burner capacity of 1 % for every 325 ft
G50/2-A ZM-NR 217 505 13
(100 m) should be taken into consideration depending
G60/2-A ZM-NR 217 605 12 on installation altitude.
G70/1-B ZM-NR 217 704 42
Voltages and frequencies:
The burners are equipped with three phase motor in 208 -
600 V, 60 Hz as standard. Different voltage and frequency
are available upon request.
20
Burner selection
Gas burners size 70, version NR
Burner model G70/3-A, vers. ZM-NR Burner model G70/4-A, vers. ZM-NR
Combustion head G70/3-NR 425x290 Combustion head G70/3-NR 425x290
Capacity in MBH Nat Gas 3,400 – 36,500 Capacity in MBH Nat Gas 3,400 – 39,930
Propane 4,780 – 36,500 Propane 4,780 – 39,930
“WC “WC
10 10
9 9
8 8
7 7
6 6
5 5
4 4
High fire
High fire
range
range
3 3
2 2
1 1
0 0
-1 -1
-2 -2
0 3,000 6,000 9,000 12,000 15,000 18,000 21,000 24,000 27,000 30,000 33,000 36,000 39,000 42,000 0 3,000 6,000 9,000 12,000 15,000 18,000 21,000 24,000 27,000 30,000 33,000 36,000 39,000 42,000
Fuels
Nat gas
Propane
Burner model Vers. Order No. The capacity graphs are based on air temperature of
G70/3-A ZM-NR 217 714 14 68F (20 °C) and installation altitude of 1,640 ft (500 m).
A reduction of burner capacity of 1 % for every 325 ft
G70/4-A ZM-NR 217 734 14
(100 m) should be taken into consideration depending
on installation altitude.
21
Scope of delivery/Accessories
Gas burners size 50 to 70, version NR
Scope of delivery G50 G60 G70
Burner housing, hinge flange, housing cover, Weishaupt burner motor, air regulator housing,
fan wheel, combustion head, ignition unit, ignition cable, ignition electrode, combustion
manager with operating unit, flame sensor, stepping motors, flange gasket, limit switch
on hinge flange, fixing screws ● ● ●
Combustion manager W-FM100 ● ● ●
Two gas safety shut off valves ● ● ●
Gas butterfly valve ● ● ●
Ignition pilot ● ● ●
Air pressure switch ● ● ●
Gas pressure switches ● ● ●
Servomotor driven sliding sleeve in mixing head ● ● ●
Stepping motor for Gas /Air ratio control with W-FM100
Stepping motor for air damper ● ● ●
Stepping motor for gas butterfly valve ● ● ●
Stepping motor for sliding sleeve ● ● ●
Accessories
Downward firing burner ○ ○ ○
Intake flange for the connection of an air duct ○ ○ ○
Solenoid valve for air pressure switch test for cont. run fan or post-purge ○ ○ ○
Combustion head extension ○ ○ ○
Speed control ○ ○ ○
O2 trim ○ ○ ○
W-FM loosed for installation in remote control panel ○ ○ ○
● Scope of delivery
○ Accessories
22
Technical data
Gas burners size 50 to 70, version NR
Technical data G50/1-B G50/2-A G60/2-A
Burner motor 3~208 - 600V Model W-D132/170-2/9K0 W-D132/210-2/14K0 W-D132/210-2/14K0
Motor rating HP (kW) 14.6 (11) 20 (15) 20 (15)
FLA at 460V A 19 25 25
Speed (60 Hz) rpm 3,500 3,520 3,520
Fan wheel Colour red red red
ø 330 x 104.5 330 x 104.5 465 x 103
Combustion manager Model W-FM100 W-FM100 W-FM100
Ignition unit Model W-ZG02 W-ZG02 W-ZG02
Stepping motor Air Model SQM45 SQM45 SQM48
Mixing head Model SQM45 SQM45 SQM45
Fuel Model SQM45 SQM45 SQM45
Burner weight approx. lbs (kg) 408 (185) 408 (185) 606 (275)
23
Burner selection
Gas burners size 50 to 70, version 1LN
Burner model G50/1-B, vers. ZM-1LN Burner model G70/1-B, vers. ZM-1LN
Combustion head G40/2-LN 217x35 Combustion head G60/2-1LN 300x75
Capacity in MBH Nat Gas 1,700 – 11,600 Capacity in MBH Nat Gas 2,730 – 24,900
Propane 1,700 – 11,600 Propane 3,400 – 24,900
“WC “WC
9 9
8 8
7 7
6 6
5
High fire
5
range
4 4
High fire
range
3 3
2 2
1 1
0 0
-1 -1
-2 -2
0 1,000 2,000 3,000 4,000 5,000 6,000 7,000 8,000 9,000 10,000 11,000 12,000 13,000 14,000 0 2,000 4,000 6,000 8,000 10,000 12,000 14,000 16,000 18,000 20,000 22,000 24,000 26,000
Burner model G50/2-A, vers. ZM-1LN Burner model G70/2-A, vers. ZM-1LN
Combustion head G50/2-LN 260x40 Combustion head G70/2-1LN 365x85
Capacity in MBH Nat Gas 2,050 – 16,720 Capacity in MBH Nat Gas 3,400 – 34,100
Propane 2,730 – 16,720 Propane 4,440 – 34,100
“WC “WC
9 10
8 9
8
7
7
6
6
5
5
4
4
High fire
High fire
3
range
range
3
2
2
1 1
0 0
-1 -1
-2 -2
0 2,000 4,000 6,000 8,000 10,000 12,000 14,000 16,000 18,000 0 3,000 6,000 9,000 12,000 15,000 18,000 21,000 24,000 27,000 30,000 33,000 36,000
Fuels
Nat gas
Propane
Burner model Vers. Order No. The capacity graphs are based on air temperature of
G50/1-B ZM-1LN 217 504 17 68F (20 °C) an installation altitude at sea level. A
reduction of burner capacity of 1 % for every 325 ft
G50/2-A ZM-1LN 217 505 16
(100 m) should be taken into consideration in case of
G70/1-B ZM-1LN 217 704 45 installation altitude above 0 ft.
G70/2-A ZM-1LN 217 705 45
Voltages and frequencies:
The burners are equipped with three phase motor in 208 -
600 V, 60 Hz as standard. Different voltage and frequency
are available upon request.
24
Scope of delivery/Accessories/ Technical data
Gas burners size 50 and 70, version 1LN
Scope of delivery G50 G70
Burner housing, hinge flange, housing cover, Weishaupt burner motor, air regulator housing, fan wheel,
combustion head, ignition unit, ignition cable, ignition electrode, combustion manager with operating
unit, flame sensor, stepping motors, flange gasket, limit switch on hinge flange, fixing screws ● ●
Combustion manager W-FM100 ● ●
Two gas safety shut off valves ● ●
Gas butterfly valve ● ●
Ignition pilot ● ●
Air pressure switch ● ●
Gas pressure switches ● ●
Adjustable flame tube in mixing head ● ●
Stepping motor for Gas/Air ratio control with W-FM100
Stepping motor for air damper ● ●
Stepping motor for gas butterfly valve ● ●
Accessories
Downward firing burner ○ ○
Intake flange for the connection of an air duct ○ ○
Solenoid valve for air pressure switch test for cont. run fan or post-purge ○ ○
Combustion head extension ○ ○
Speed control ○ ○
O2 trim ○ ○
W-FM loosed for installation in remote control panel ○ ○
● Scope of delivery
○ Accessories
25
Burner selection
Gas burners size 50, version LN
Burner model G50/1-B, vers. ZM-LN Burner model G50/2-A, vers. ZM-LN
Combustion head G40/2-3a 210x60 Combustion head G50/2-3a 250x90
Capacity in MBH Nat Gas 1,700 – 10,230 Capacity in MBH Nat Gas 2,050 – 15,350
“WC “WC
9 9
8 8
7 7
6 6
5 5
High fire
range
4 4
High fire
range
3 3
2 2
1 1
0 0
-1 -1
-2 -2
0 1,000 2,000 3,000 4,000 5,000 6,000 7,000 8,000 9,000 10,000 11,000 12,000 0 2,000 4,000 6,000 8,000 10,000 12,000 14,000 16,000 18,000
Burner model Vers. Order No. The capacity graphs are based on air temperature of
G50/1-B ZM-LN 217 504 19 68F (20 °C) an installation altitude at sea level. A
reduction of burner capacity of 1 % for every 325 ft
G50/2-A ZM-LN 217 505 18
(100 m) should be taken into consideration in case of
installation altitude above 0 ft.
26
Burner selection
Gas burners size 60 and 70, version LN
Burner model G60/2-A, vers. ZM-LN Burner model G70/1-B, vers. ZM-LN
Combustion head G60/2-3a 300x100 Combustion head G60/2-3a 300x100
Capacity in MBH Nat Gas 2,135 – 19,795 Capacity in MBH Nat Gas 2,390 – 23,890
“WC
“WC
9 9
8 8
7 7
6 6
5 5
4 4
High fire
High fire
range
3
range
2 2
1 1
0 0
-1 -1
-2 -2
0 2,000 4,000 6,000 8,000 10,000 12,000 14,000 16,000 18,000 20,000 22,000 0 2,000 4,000 6,000 8,000 10,000 12,000 14,000 16,000 18,000 20,000 22,000 24,000 26,000
“WC
10
9
8
4
High fire
range
2
1
0
-1
-2
0 3,000 6,000 9,000 12,000 15,000 18,000 21,000 24,000 27,000 30,000 33,000 36,000
Burner model Vers. Order No. The capacity graphs are based on air temperature
G60/2-A ZM-LN 217 605 13 of 68F (20 °C) an installation altitude at sea level. A
reduction of burner capacity of 1% for every 325 ft
G70/1-B ZM-LN 217 704 43
(100 m) should be taken into consideration in case of
G70/2-A ZM-LN 217 705 43 installation altitude above 0 ft.
27
Scope of delivery/Accessories
Gas burners size 50 to 70, version LN
Scope of delivery G50 G60 G70
Burner housing, hinge flange, housing cover,
Weishaupt burner motor, air regulator housing, fan wheel,
combustion head, ignition unit, ignition cable, ignition electrodes,
combustion manager with operating unit, flame sensor,
stepping motors, flange gasket, limit switch on
hinge flange, fixing screws ● ● ●
Combustion manager W-FM100 ● ● ●
Two safety gas shut off valves ● ● ●
Gas butterfly valve ● ● ●
Air pressure switch ● ● ●
Gas pressure switches ● ● ●
Adjustable flame tube in mixing head ● ● ●
Stepping motor for Gas /Air ratio control with W-FM100
Stepping motor for air damper ● ● ●
Stepping motor for gas butterfly valve ● ● ●
Accessories
Downward firing burner ○ ○ ○
Intake flange for the connection of an air duct ○ ○ ○
Combustion head extension ○ ○ ○
Speed control ○ ○ ○
O2 trim ○ ○ ○
W-FM loosed for installation in remote panel ○ ○ ○
● Scope of delivery
○ Accessories
28
Technical data
Gas burners size 50 to 70, version LN
Technical data G50/1-B G50/2-A
Burner motor 3~208 - 600V Model W-D132/170-2/9K0 W-D132/210-2/14K0
Motor rating HP (kW) 14.6 (11) 20 (15)
FLA at 460 V A 19 25
Speed (60 Hz) rpm 3,500 3,520
Fan wheel Colour red red
ø 330 x 104.5 330 x 104.5
Combustion manager Model W-FM100 W-FM100
Ignition unit Model W-ZG02 W-ZG02
Stepping motor Air Model SQM45 SQM45
Fuel Model SQM45 SQM45
Burner weight approx. lbs (kg) 408 (185) 408 (185)
29
Dual fuel burners
Burner selection
Dual fuel burners size 30, version NR
Burner model RGL30/2-A, RGMS30/2-A, Fuels
vers. ZM-NR vers. ZM-NR #2 oil
Combustion head G30/2-NR 190x65 G30/2-NR 190x65 #6 oil
Capacity in MBH Gas 1,025 – 7,850 1,025 – 7,850 Nat gas
GPH #2 oil 11.6 – 56 – Propane
GPH #6 oil – 15 – 51
“WC
6
The stated oil throughputs in GPH refer to #2 oil with a
5
calorific value of 140,000 BTU/Gal and #6 oil with a
4
calorific value of 153,000 BTU/Gal.
3
2
range
1
68F (20 °C) and installation altitude of 1,640 ft (500 m).
A reduction of burner capacity of 1 % for every 325 ft
0
(100 m) should be taken into consideration depending
-1 on installation altitude.
-2
0 500 1,000 1,500 2,000 2,500 3,000 3,500 4,000 4,500 5,000 5,500 6,000 6,500 7,000 7,500 8,000
GPH #2 10 20 30 40 50
Voltages and frequencies:
GPH #6 10 20 30 40 50
The burners are equipped with three phase motor in 208 -
600 V, 60 Hz as standard. Different voltage and frequency
are available upon request.
Burner model Vers. Order No.
Standard burner motor:
RGL30/2-A ZM-NR 218 305 13
Insulation class F, protection IP 55.
RGMS30/2-A ZM-NR 219 305 13
32
Burner selection
Dual fuel burners size 40, version NR
Burner model RGL40/1-B, RGMS40/1-B, Burner model RGL40/2-A, RGMS40/2-A,
vers. ZM-NR vers. ZM-NR vers. ZM-NR vers. ZM-NR
Combustion head G30/2-NR 190x58 G30/2-NR 190x58 Combustion head G40/2-NR 217x75 G40/2-NR 217x75
Capacity in MBH Gas 1,540 – 9,215 1,540 – 9,215 Capacity in MBH Gas 1,710 – 11,775 1,710 – 11,775
GPH #2 oil 13 – 65.8 – GPH #2 oil 15.8 – 84 –
GPH #6 oil – 17.6 – 60 GPH #6 oil – 22.3 – 76.9
“WC “WC
7 7
6 6
5 5
High fire
range
4 4
3 3
High fire
High fire
range
range
2 2
1 1
0 0
-1 -1
-2 -2
0 1,000 2,000 3,000 4,000 5,000 6,000 7,000 8,000 9,000 10,000 0 1,000 2,000 3,000 4,000 5,000 6,000 7,000 8,000 9,000 10,000 11,000 12,000 13,000
GPH #2 10 20 30 40 50 60 70 GPH #2 10 20 30 40 50 60 70 80 90
GPH #6 10 20 30 40 50 60 GPH #6 10 20 30 40 50 60 70 80
33
Burner selection
Dual fuel burners size 50, version NR
Burner model RGL50/1-B, RGMS50/1-B, Burner model RGL50/2-A, RGMS50/2-A,
vers. ZM-NR vers. ZM-NR vers. ZM-NR vers. ZM-NR
Combustion head G40/2-NR 217x75 G40/2-NR 217x75 Combustion head G50/2-NR 290x185 G50/2-NR 290x185
Capacity in MBH Gas 1,880 – 13,650 1,880 – 13,650 Capacity in MBH NG 2,050 – 18,430 2,050 – 18,430
GPH #2 oil 16 – 97.5 – MBH Propane 2,730 – 18,430 2,730 – 18,430
GPH #6 oil – 25 – 89 GPH #2 oil 27.5 – 131.6 –
GPH #6 oil – 32.6 – 120.4
“WC “WC
9 9
8 8
7 7
High fire
6 6
range
5 5
4 4
High fire
High fire
3 3
range
range
2 2
1 1
0 0
-1 -1
-2 -2
0 1,000 2,000 3,000 4,000 5,000 6,000 7,000 8,000 9,000 10,000 11,000 12,000 13,000 14,000 0 2,000 4,000 6,000 8,000 10,000 12,000 14,000 16,000 18,000 20,000 22,000
34
Burner selection
Dual fuel burners size 60 and 70, version NR
Burner model RGL60/2-A, RGMS60/2-A, Burner model RGL70/1-B, RGMS70/1-B,
vers. ZM-NR vers. ZM-NR vers. ZM-NR vers. ZM-NR
Combustion head G60/2-NR 345x230 G60/2-NR 345x230 Combustion head G60/2-NR 345x230 G60/2-NR 345x230
Capacity in MBH Gas 2,730 – 20,815 2,730 – 20,815 Capacity in MBH Gas 2,730 – 25,250 2,730 – 25,250
GPH #2 oil 32 – 148.7 – GPH #2 oil 29 – 180 –
GPH #6 oil – 40.1 – 136 GPH #6 oil – 43.9 – 180
“WC “WC
9 9
8 8
7 7
High fire
6 6
range
5 5
4 4
High fire
High fire
3 3
range
range
2 2
1 1
0 0
-1 -1
-2 -2
0 2,000 4,000 6,000 8,000 10,000 12,000 14,000 16,000 18,000 20,000 22,000 0 2,000 4,000 6,000 8,000 10,000 12,000 14,000 16,000 18,000 20,000 22,000 24,000 26,000
GPH #2 20 40 60 80 100 120 140 160 GPH #2 20 40 60 80 100 120 140 160 180
35
Burner selection
Dual fuel burners size 70, version NR
Burner model RGL70/3-A, RGMS70/3-A, Burner model RGL70/4-A, RGMS70/4-A,
vers. ZM-NR vers. ZM-NR vers. ZM-NR vers. ZM-NR
Combustion head G70/3-NR 425x290 G70/3-NR 425x290 Combustion head G70/3-NR 425x290 G70/3-NR 425x290
Capacity in MBH Gas 3,400 – 36,500 3,400 – 36,515 Capacity in MBH NG 3,400 – 39,930 3,400 – 39,930
MBH Propane 4,780 – 36,500 4,780 – 36,515 MBH Propane 4,780 – 39,930 4,780 – 39,930
GPH #2 oil 42.5 – 259.8 – GPH #2 oil 42.5 – 285.2 –
GPH #6 oil – 39 – 238.7 GPH #6 oil – 39 – 261
“WC “WC
10 10
9 9
8 8
7 7
6 6
5 5
4 4
High fire
High fire
range
range
3 3
2 2
1 1
0 0
-1 -1
-2 -2
0 3,000 6,000 9,000 12,000 15,000 18,000 21,000 24,000 27,000 30,000 33,000 36,000 39,000 42,000 0 3,000 6,000 9,000 12,000 15,000 18,000 21,000 24,000 27,000 30,000 33,000 36,000 39,000 42,000
GPH #2 25 50 75 100 125 150 175 200 225 250 275 300 GPH #2 25 50 75 100 125 150 175 200 225 250 275 300
GPH #6 25 50 75 100 125 150 175 200 225 250 275 GPH #6 25 50 75 100 125 150 175 200 225 250 275
36
Scope of delivery/Accessories
Dual fuel burners size 30 to 50, version NR
Scope of delivery RGMS30 RGMS40 RGMS50 RGL30 RGL40 RGL50
Burner housing, hinge flange, housing cover, Weishaupt burner motor, air regulator
housing, fan wheel, combustion head, ignition unit, ignition cable, ignition electrodes,
nozzle assembly with oil nozzle/s, combustion manager with operating unit, flame sensor,
stepping motors, flange gasket, limit switch on hinge flange, fixing screws ● ● ● ● ● ●
Combustion manager W-FM100 ● ● ● ● ● ●
Two safety gas shut off valves ● ● ● ● ● ●
Gas butterfly valve ● ● ● ● ● ●
Ignition pilot ● ● ● ● ● ●
Air pressure switch ● ● ● ● ● ●
Oil pressure switch in return ● ● ● ● ● ●
Gas pressure switches ● ● ● ● ● ●
Servomotor driven sliding sleeve in mixing head ● ● ● ● ● ●
Stepping motor for Gas /Air ratio control with W-FM100
Stepping motor for air damper ● ● ● ● ● ●
Stepping motor for gas butterfly valve ● ● ● ● ● ●
Stepping motor for regulating/sliding sleeve ● ● ● ● ● ●
Oil pump, fitted ● ● ● ● ● ●
Oil preheater, fitted ● ● ● – – –
Oil hoses ● ● ● ● ● ●
Two oil solenoid valves in supply and return – – – ● – –
1 solenoid valve in supply and in return,
nozzle head with shut off device (nozzle solenoid) ● ● ● – ● ●
Magnetic coupling ● ● ● ● ● ●
Accessories
Downward firing burner – – ○ ○ ○ ○
Intake flange for the connection of an air duct – – ○ ○ ○ ○
Solenoid valve for air pressure switch test for cont. run fan or post-purge – – ○ ○ ○ ○
Combustion head extension – – ○ ○ ○ ○
Speed control – – ○ ○ ○ ○
O2 trim – – ○ ○ ○ ○
W-FM loose to fit into control panel – – ○ ○ ○ ○
Separate pump station ○ ○ ○ ○ ○ ○
Separate preheater station (electric or media) ○ ○ ○ – – –
● Scope of delivery
○ Accessories
37
Scope of delivery/Accessories
Dual fuel burners size 60 and 70, version NR
Scope of delivery RGMS60 RGMS70 RGL60 RGL70
Burner housing, hinge flange, housing cover, Weishaupt burner motor, air regulator
housing, fan wheel, combustion head, ignition unit, ignition cable, ignition electrodes,
nozzle assembly with oil nozzle/s, combustion manager with operating unit, flame sensor,
stepping motors, flange gasket, limit switch on hinge flange, fixing screws ● ● ● ●
Combustion manager W-FM100 ● ● ● ●
Two safety gas shut off valves ● ● ● ●
Gas butterfly valve ● ● ● ●
Ignition pilot ● ● ● ●
Air pressure switch ● ● ● ●
Oil pressure switch in return ● ● ● ●
Gas pressure switches ● ● ● ●
Servomotor driven sliding sleeve in mixing head ● ● ● ●
Stepping motor for Gas /Air ratio control with W-FM100
Stepping motor for air damper ● ● ● ●
Stepping motor for gas butterfly valve ● ● ● ●
Stepping motor for regulating/sliding sleeve ● ● ● ●
Oil pump, fitted – – ● ●
Oil hoses ● ● ● ●
1 solenoid valve in supply and in return,
nozzle head with shut off device (nozzle solenoid) ● ● ● ●
Magnetic coupling ● ● ● ●
Accessories
Downward firing burner ○ ○ ○ ○
Intake flange for the connection of an air duct ○ ○ ○ ○
Solenoid valve for air pressure switch test for cont. run fan or post-purge ○ ○ ○ ○
Combustion head extension ○ ○ ○ ○
Speed control ○ ○ ○ ○
O2 trim ○ ○ ○ ○
W-FM loose to fit into control panel ○ ○ ○ ○
Separate pump station ○ ○ ○ ○
Separate preheater station (electric or media) ○ ○ – –
● Scope of delivery
○ Accessories
38
Technical data
Dual fuel burners size 30 and 40, version NR
Technical data RGL30/2-A RGMS30/2-A
Burner motor 3~208 - 600V Model W-D112/140-2/4K5 W-D112/140-2/4K5
Motor rating HP (kW) 6.6 (5.0) 6.6 (5.0)
FLA at 460V A 8.6 8.6
Speed (60 Hz) rpm 3,510 3,510
Fan wheel Colour / ø red / 248 x 104 red / 248 x 104
Combustion manager Model W-FM100 W-FM100
Ignition unit Model W-ZG02 W-ZG02
Stepping motor Air Model SQM45 SQM45
Mixing head Model SQM45 SQM45
Fuel Model SQM45 SQM45
Pump, fitted Model TA3 TA3
Oil preheater Model – EV2D
Oil throughput GPH (kg/h) – 72 (270)
Heat rating kW – 13.2
Oil solenoid valves 55V 1/4” (supply) 20 W Model 121 K 6220 –
55V 1/8” (return) 20 W Model 121 K 2423 –
55V 3/8” (supply) 20 W Model – 321 H 2322
55V 3/8” (supply) 20 W Model – 121 G 2320
Oil pressure switches 1 – 10 bar (return #2 oil - 5 bar) Model DSA 46 F001
1 – 10 bar (return #6 oil - 7 bar) Model – DSA 46 F001
Oil hoses DN, length in inch (mm) 20/40” (1000) –
(on RGMS, high pressure metal hoses) DN, lenght in inch (mm) – 20/51” (1300)
Burner weight approx. lbs (kg) 320 (145) 386 (175)
39
Technical data
Dual fuel burners size 40 and 50, version NR
Technical data RGL40/2-A RGMS40/2-A
Burner motor 3~208 - 600V (40/2) Model W-D112/170-2/7K0 W-D112/170-2/7K0
Motor rating HP (kW) 10.4 (7.8) 10.4 (7.8)
FLA at 460V A 14 14
Speed (60 Hz) rpm 3,500 3,500
Fan wheel Colour / ø red / 275 x 104 red / 275 x 104
Combustion manager Model W-FM100 W-FM100
Ignition unit Model W-ZG02 W-ZG02
Stepping motor Air Model SQM45 SQM45
Mixing head Model SQM45 SQM45
Fuel Model SQM45 SQM45
Pump, fitted Model TA3 TA3
Oil preheater Model – EV2D
Oil throughput GPH (kg/h) – 75 (270)
Heat rating kW – 13.2
Oil solenoid valves 55V 3/8” (supply) 20 W Model 321 H 2322 321 H 2322
55V 3/8” (return) 20 W Model 121 G 2320 121 G 2320
Oil pressure switches 1 – 10 bar (return fuel oil EL - 5 bar) Model DSA 46 F001 –
1 – 10 bar (return fuel oil S - 7 bar) Model – DSA 46 F001
Oil hoses DN, length in inch (mm) 20/40” (1000) –
(on RGMS, high pressure metal hoses) DN, length in inch (mm) – 20/51” (1300)
Burner weight approx. lbs (kg) 419 (190) 419 (190)
40
Technical data
Dual fuel burners size 50 and 60, version NR
Technical data RGMS50/1-B RGMS50/2-A
Burner motor 3~208 - 600V Model W-D132/170-2/9K0 W-D132/210-2/14K0
Motor rating HP (kW) 14.6 (11) 20 (15)
FLA at 460V A 19 25
Speed (60 Hz) rpm 3,500 3,520
Fan wheel Colour red red
ø 330 x 104.5 330 x 104.5
Combustion manager Model W-FM100 W-FM100
Ignition unit Model W-ZG02 W-ZG02
Stepping motor Air Model SQM45 SQM45
Mixing head Model SQM45 SQM45
Fuel Model SQM45 SQM45
Oil preheater Model WEV2.2/01 2) WEV3/01
Oil throughput GPH (kg/h) 82.5 (300) 137.5 (500)
Heat rating kW 13.8 22.4
Pump, fitted Model TA4C T2C
Oil solenoid valves 55V 3/8” (supply) 20W Model 321 H 2322 321 H 2322
55V 3/8” (return) 20W Model 121 G 2320 121 G 2320
Oil pressure switch 1 – 10 bar (return #6 oil) Model DSA 46 F001 DSA 46 F001
Oil hoses DN/length 25/59” (1500) 25/59” (1500)
Burner weight approx. lbs (kg) 672 (305) 672 (305)
2)
Burners above 82.5 GPH (300 kg/h): Oil preheater WEV3 in lieu of WEV2.2 (refer to Accessories)
2)
Weight without pump and preheater stations
41
Technical data
Dual fuel burners size 70, version NR
Technical data RGL70/1-B RGL70/3-A
Burner motor 3~208 - 600V Model W-D160/240-2/18K0 W-D160/240-2/22K0
Motor rating HP (kW) 22 (16.5) 26.6 (20)
FLA at 460V A 30.5 33
Speed (60 Hz) rpm 3,560 3,550
Fan wheel Colour green green
ø 530 x 120 530 x 120
Combustion manager Model W-FM100 W-FM100
Ignition unit Model W-ZG02 W-ZG02
Stepping motor Air Model SQM48 SQM48
Mixing head Model SQM45 SQM45
Fuel Model SQM45 SQM45
Pump, fitted Model T2C (up to 173 GPH/ 600 kg/h)
Model T3C (from 173 GPH/ 600 kg/h)
Oil solenoid valves 55V 1/2” (supply) 20W Model 321 H 2522 321 H 2522
55V 1/2” (return) 20W Model 121 G 2520 121 G 2520
110V 3/8” (bypass) 19W Model – –
Oil pressure switch 3 – 25 bar (supply - 18 bar) Model – –
1 – 10 bar (return #2 oil - 5 bar) Model DSA 46 F001 DSA 46 F001
1 – 10 bar (return #6 oil - 7 bar) Model – –
Oil hoses DN, length in inch and (mm) 25/1300 25/1300
(on RGMS, high pressure metal hoses) DN, length in inch and (mm) – –
DN, length in inch and (mm) – –
Burner weight approx. lbs (kg) 948 (430) 948 (430)
43
Burner selection
Dual fuel burners size 50, version 1LN
Burner model RGL50/1-B, vers. ZM-1LN Burner model RGL50/2-A, vers. ZM-1LN
Combustion head G40/2-LN 217x35K Combustion head G50/2-LN 260x40
Capacity in MBH NG 1,710 – 11,600 Capacity in MBH NG 2,050 – 16,725
MBH Propane 1,710 – 11,600 MBH Propane 2,730 – 16,725
GPH #2 oil 19.5 – 82.8 GPH #2 oil 21.3 – 119.4
“WC “WC
9 9
8 8
7 7
6
High fire
6
range
5 5
High fire
4 4
range
High fire
3 3
range
2 2
1 1
0 0
-1 -1
-2 -2
0 1,000 2,000 3,000 4,000 5,000 6,000 7,000 8,000 9,000 10,000 11,000 12,000 13,000 14,000 0 2,000 4,000 6,000 8,000 10,000 12,000 14,000 16,000 18,000
44
Burner selection
Dual fuel burners size 70, version 1LN
Burner model RGL70/1-B, vers. ZM-1LN Burner model RGL70/2-A, vers. ZM-1LN
Combustion head G60/2-1LN 300x75 Combustion head G70/2-1LN 365x85
Capacity in MBH NG 2,730 – 24,915 Capacity in MBH NG 3,415 – 34,130
MBH Propane 3,415 – 24,915 MBH Propane 4,780 – 34,130
GPH #2 oil 28.8 – 178 GPH #2 oil 46.3 – 243.8
“WC “WC
9 10
8 9
8
7
7
High fire
6
range
6
5
5
4
4
High fire
High fire
3
range
range
2
2
1 1
0 0
-1 -1
-2 -2
0 2,000 4,000 6,000 8,000 10,000 12,000 14,000 16,000 18,000 20,000 22,000 24,000 26,000 0 3,000 6,000 9,000 12,000 15,000 18,000 21,000 24,000 27,000 30,000 33,000 36,000
GPH 20 40 60 80 100 120 140 160 180 GPH 25 50 75 100 125 150 175 200 225 250
45
Scope of delivery/Accessories
Dual fuel burners size 50 and 70, version 1LN
Scope of delivery RGL50 RGL70
Burner housing, hinge flange, housing cover, Weishaupt burner motor, air regulator housing, fan wheel,
combustion head, ignition unit, ignition cable, ignition electrode, nozzle assembly with oil nozzle/s,
combustion manager with operating unit, flame sensor stepping motors, flange gasket,
limit switch on hinge flange, fixing screws ● ●
Combustion manager W-FM100 ● ●
Two safety gas valves ● ●
Gas butterfly valve ● ●
Ignition pilot ● ●
Air pressure switch ● ●
Oil pressure switch in return ● ●
Gas pressure switches ● ●
Adjustable regulating sleeve in mixing head ● –
Adjustable flame tube in mixing head – ●
Stepping motor for Gas/Air ratio control with W-FM100
Stepping motor for air regulator ● ●
Stepping motor for gas butterfly valve ● ●
Stepping motor for oil regulator ● ●
Oil pump, fitted ● ●
Oil hoses ● ●
2 oil solenoid valves, 1 safety valve, two stage nozzle head with shut off device (nozzle solenoid) ● ●
Magnetic coupling ● ●
Accessories
Downward firing burner ○ ○
Intake flange for the connection of an air duct ○ ○
Solenoid valve for air pressure switch test for cont. run fan or post-purge ○ ○
Combustion head extension ○ ○
Speed control ○ ○
O2 trim ○ ○
W-FM loose to fit into control panel ○ ○
● Scope of delivery
○ Accessories
46
Technical data
Dual fuel burners size 50 and 70, version 1LN
Technical data RGL50/1-B RGL50/2-A
Burner motor 3~208 - 600V Model W-D132/170-2/9K0 W-D132/210-2/14K0
Motor rating HP (kW) 14.6 (11) 20 (15)
FLA at 460V A 19 25
Speed (60 Hz) rpm 3,500 3,520
Fan wheel Colour red red
ø 330 x 104.5 330 x 104.5
Combustion manager Model W-FM100 W-FM100
Ignition unit Model W-ZG02 W-ZG02
Stepping motor Air Model SQM45 SQM45
Fuel Model SQM45 SQM45
Pump, fitted Model TA4C T2C
Oil solenoid valves 55V 3/8” (supply) 20 W Model 321 H 2322 321 H 2322
55V 3/8” (return) 20 W Model 121 G 2320 121 G 2320
Oil pressure switch 1 – 10 bar (return - 5 bar) Model DSA 46 F001 DSA 46 F001
Oil hoses DN, length in inch and (mm) 25/51” (1300) 25/51” (1300)
Burner weight approx. lbs (kg) 508 (230) 508 (230)
47
®
multiflam Burners
multiflam® principle:
emission reduction as standard
ppm ppm
100 100
90 90
80 80
70 70
60 60
NOx
50 50
40 40
The multiflam® flame shows efficient
combustion
30 30
NOx
CO
into the market. Unprecedented low
CO
10 10
emission values stunned the industry.
With the patented mixing head,
Weishaupt was able to reduce the Gas #2 Oil
Nitrous Oxide emissions (NOx) for
medium and large burners to values Example values for hot water plant depend on the combustion chamber
normally only seen with compact
burners. Weishaupt has set the stan-
dards with values below 60 ppm for #2
oil and 30 ppm for natural gas, depend- Secondary nozzle 1
ing on the relevant combustion cham-
ber geometry. Secondary nozzle 2
50
Burner selection
Oil burners size 30 to 50, vers. 3LN – multiflam®
Burner model RL30/2-A, version 3LN Burner model RL40/2-A, version 3LN
Combustion head M30/2-4a Combustion head M40/2-4A
Capacity in MBH 1,025– 7,320 Capacity in MBH 1,620 – 10,170
Capacity in GPH#2 7.3– 52.3 Capacity in GPH#2 11.6 – 72.6
“WC “WC
6 7
5 6
5
4
4
3
3
High fire
High fire
2
range
range
2
1
1
0
0
-1 -1
-2 -2
0 500 1,000 1,500 2,000 2,500 3,000 3,500 4,000 4,500 5,000 5,500 6,000 6,500 7,000 7,500 8,000 0 1,000 2,000 3,000 4,000 5,000 6,000 7,000 8,000 9,000 10,000 11,000 12,000 13,000
GPH#2 10 20 30 40 50 GPH#2 10 20 30 40 50 60 70 80 90
Burner model RL50/1-B, version 3LN Burner model Vers. Order No.
Combustion head M50/1-4a
Capacity in MBH 1,825 – 12,800 RL30/2-A 3LN 211 305 24
Capacity in GPH#2 13 – 91.4 RL40/2-A 3LN 211 405 24
“WC
9
RL50/1-B 3LN 211 504 24
8
3
range
1
The capacity graphs are based on air temperature of
0
68F (20 °C) an installation altitude of 1,640 ft (500 m)
-1
above sea level. A reduction of burner capacity of 1 %
-2 for every 325 ft (100 m) should be taken into
0 1,000 2,000 3,000 4,000 5,000 6,000 7,000 8,000 9,000 10,000 11,000 12,000 13,000 14,000
consideration depending on installation altitude.
GPH#2 10 20 30 40 50 60 70 80 90
51
Scope of delivery / Accessories / Technical data
Oil burners size 30 to 50, version 3LN
Scope of delivery RL30 RL40 RL50
Burner housing, hinge flange, housing cover, Weishaupt burner motor,
air regulator housing, fan wheel, combustion head, ignition unit, ignition cable,
ignition electrodes, combustion manager with operating unit, UV flame sensor,
stepping motors, flange gasket, limit switch on hinge flange,
fixing screws ● ● ●
Combustion manager W-FM100 ● ● ●
Oil pressure switch in return ● ● ●
Oil pump, fitted ● ● ●
Oil hoses ● ● ●
Accessories
Intake flange for the connection of an air duct ○ ○ ○
Combustion head extension ○ ○ ○
Speed control ○ ○ ○
O2 trim ○ ○ ○
W-FM loose to fit into control panel ○ ○ ○
● Scope of delivery
○ Accessories
52
Burner selection
Gas burners size 30 and 50, version 3LN
Burner model G30/2-A, version 3LN Burner model G40/2-A, version 3LN
Combustion head G30/2-3LN Combustion head G40/2-3LN
Capacity in MBH Nat Gas 1,025 – 6,825 Capacity in MBH Nat Gas 1,365 – 9,555
“WC “WC
6 7
6
5
5
4
4
3
3
2
High fire
High fire
2
range
range
1
1
0
0
-1 -1
-2 -2
0 500 1,000 1,500 2,000 2,500 3,000 3,500 4,000 4,500 5,000 5,500 6,000 6,500 7,000 7,500 8,000 0 1,000 2,000 3,000 4,000 5,000 6,000 7,000 8,000 9,000 10,000
MBH MBH
Burner model G50/1-B, version 3LN Burner model G50/2-A, version 3LN
Combustion head G50/1-3LN Combustion head G50/2-3LN
Capacity in MBH Nat Gas 1,535 – 11,945 Capacity in MBH Nat Gas 1,710 – 15,360
“WC “WC
9 9
8 8
7 7
6 6
5 5
4 4
High fire
High fire
3 3
range
range
2 2
1 1
0 0
-1 -1
-2 -2
0 1,000 2,000 3,000 4,000 5,000 6,000 7,000 8,000 9,000 10,000 11,000 12,000 13,000 14,000 0 2,000 4,000 6,000 8,000 10,000 12,000 14,000 16,000 18,000
MBH MBH
Burner model Vers. Order No. The capacity graphs are based on air temperature
G30/2-A 3LN 217 305 08 of 68F (20 °C) an installation altitude at sea level. A
reduction of burner capacity of 1 % for every 325 ft
G40/2-A 3LN 217 405 10
(100 m) should be taken into consideration in case
G50/1-B 3LN 217 504 10 of installation altitude above 0 ft.
G50/2-A 3LN 217 505 44
Voltages and frequencies:
The burners are equipped with three phase motor in 208 -
600 V, 60 Hz as standard. Different voltage and frequency
are available upon request.
53
Burner selection
Gas burners size 60 and 70, version 3LN
Burner model G60/2-A, version 3LN Burner model G70/1-B, version 3LN
Combustion head G60/2-3LN Combustion head G70/1-3LN
Capacity in MBH Nat Gas 2,220 – 19,795 Capacity in MBH Nat Gas 2,560 – 23,890
“WC “WC
9 9
8 8
7 7
6 6
5 5
4 4
High fire
High fire
3 3
range
range
2 2
1 1
0 0
-1 -1
-2 -2
0 2,000 4,000 6,000 8,000 10,000 12,000 14,000 16,000 18,000 20,000 22,000 0 2,000 4,000 6,000 8,000 10,000 12,000 14,000 16,000 18,000 20,000 22,000 24,000 26,000
MBH MBH
“WC
10
9
The capacity graphs are based on air temperature
8 of 68F (20 °C) an installation altitude at sea level. A
7 reduction of burner capacity of 1 % for every 325 ft
6
(100 m) should be taken into consideration in case
5
4
of installation altitude above 0 ft.
High fire
range
-1
600 V, 60 Hz as standard. Different voltage and frequency
-2
are available upon request.
0 3,000 6,000 9,000 12,000 15,000 18,000 21,000 24,000 27,000 30,000 33,000 36,000
MBH
Standard burner motor:
Fuels – capacity with Insulation class F, protection IP 55.
combustion head open close
Nat gas
54
Scope of delivery/Accessories
Gas burners size 30 to 70, version 3LN
Scope of delivery G30 G40 G50 G60 G70
Burner housing, hinge flange, housing cover, Weishaupt burner motor, air regulator
housing, fan wheel, combustion head, ignition unit, ignition cable, ignition electrodes,
combustion manager with operating unit, UV flame sensor, stepping motors,
flange gasket, limit switch on hinge flange, fixing screws ● ● ● ● ●
Combustion manager W-FM100 ● ● ● ● ●
Two safety gas shut off valves ● ● ● ● ●
Ignition pilot ● ● ● ● ●
Air pressure switch ● ● ● ● ●
Gas pressure switch ● ● ● ● ●
Ratio controlled sliding sleeve in mixing head ● ● ● ● ●
Stepping motor for
Air regulator ● ● ● ● ●
Gas butterfly valve ● ● ● ● ●
Mixing head ● ● ● ● ●
Accessories
Intake flange for the connection of an air duct ○ ○ ○ ○ ○
Combustion head extension ○ ○ ○ ○ ○
Speed control ○ ○ ○ ○ ○
O2 trim ○ ○ ○ ○ ○
W-FM loose to fit into control panel ○ ○ ○ ○ ○
● Scope of delivery
○ Accessories
55
Technical data
Gas burners size 30 to 70, version 3LN
Technical data G30/2-A 3LN G40/2-A 3LN G50/1-B 3LN G50/2-A 3LN
Burner motor 3~208 - 600V Model W-D112/140-2/4K5 W-D112/170-2/7K0 W-D132/170-2/9K0 W-D132/210-2/14K0
Motor rating HP (kW) 6.6 (5.0) 10.4 (7.8) 14.6 (11) 20 (15)
FLA at 460V A 8.6 14 19 25
Speed (60 Hz) rpm 3,510 3,500 3,500 3,520
Fan wheel Colour red red red red
ø 248 x 104 275 x 104 330 x 104.5 330 x 104.5
Combustion manager Model W-FM100 W-FM100 W-FM100 W-FM100
Model W-FM200 W-FM200 W-FM200 W-FM200
Ignition unit Model W-ZG02 W-ZG02 W-ZG02 W-ZG02
Stepping motor Air Model SQM45 SQM45 SQM45 SQM45
Fuel Model SQM45 SQM45 SQM45 SQM45
Mixing head Model SQM48 SQM48 SQM48 SQM48
Burner weight approx. lbs (kg) 320 (145) 353 (160) 518 (235) 530 (240)
56
Burner selection
Dual fuel burners size 30 and 40, version 3LN
Burner model RGL30/2-A, version 3LN Burner model RGL40/2-A, version 3LN
Combustion head G30/2-3LN Combustion head G40/2-3LN
Capacity in MBH NG 1,025 – 6,825 Capacity in MBH NG 1,365 – 9,555
MBH #2 1,220 – 6,825 MBH #2 1,625 – 9,555
GPH #2 oil 8.7 – 49 GPH #2 oil 11.6 – 68.2
“WC “WC
6 7
6
5
5
4
fire
range range
4
3
High fireHigh
3
2
High fire
2
range
1
1
0
0
-1 -1
-2 -2
0 500 1,000 1,500 2,000 2,500 3,000 3,500 4,000 4,500 5,000 5,500 6,000 6,500 7,000 7,500 8,000 0 1,000 2,000 3,000 4,000 5,000 6,000 7,000 8,000 9,000 10,000
GPH #2 10 20 30 40 50 GPH #2 10 20 30 40 50 60 70
57
Burner selection
Dual fuel burners size 50, version 3LN
Burner model RGL50/1-B, version 3LN Burner model RGL50/2-A, version 3LN
Combustion head G50/1-3LN Combustion head G50/2-3LN
Capacity in MBH NG 1,540 – 11,945 Capacity in MBH NG 1,710 – 15,360
MBH #2 1,830 – 11,945 MBH #2 2,030 – 15,360
GPH #2 oil 13 – 85 GPH #2 oil 14.5 – 109.7
“WC “WC
9 9
8 8
7 7
6 6
High fire
High fire range
5 5
4 4
High fire
3 3
range
range
2 2
1 1
0 0
-1 -1
-2 -2
0 1,000 2,000 3,000 4,000 5,000 6,000 7,000 8,000 9,000 10,000 11,000 12,000 13,000 14,000 0 2,000 4,000 6,000 8,000 10,000 12,000 14,000 16,000 18,000
58
Burner selection
Dual fuel burners size 60 and 70, version 3LN
Burner model RGL60/2-A, version 3LN Burner model RGL70/1-B, version 3LN
Combustion head G60/2-3LN Combustion head G70/1-3LN
Capacity in MBH NG 2,220 – 18,770 Capacity in MBH NG 2,560 – 23,890
MBH #2 3,655 – 18,770 MBH #2 4,065 – 23,890
GPH #2 oil 26 – 134 GPH #2 oil 29 – 170
“WC “WC
9 9
8 8
7 7
High fire
6 6
range
5 5
4 4
High fire
High fire
3 3
range
range
2 2
1 1
0 0
-1 -1
-2 -2
0 2,000 4,000 6,000 8,000 10,000 12,000 14,000 16,000 18,000 20,000 22,000 0 2,000 4,000 6,000 8,000 10,000 12,000 14,000 16,000 18,000 20,000 22,000 24,000 26,000
GPH #2 20 40 60 80 100 120 140 GPH #2 20 40 60 80 100 120 140 160 180
Burner model RGL70/2-A, version 3LN The stated oil throughputs in GPH refer to #2 oil with a
Combustion head G70/2-3LN
Capacity in MBH NG 3,075 – 31,055 calorific value of 140,000 BTU/Gal.
MBH #2 5,285 – 31,055
GPH #2 oil 37.7 – 221.8 The capacity graphs are based on air temperature of
68F (20 °C) and installation at sea level. A reduction of
burner capacity of 1 % for every 325 ft (100 m) should
“WC
10
be taken into consideration depending on installation
9 altitude.
8
7
Voltages and frequencies:
High fire
range
5
The burners are equipped with three phase motor in 208 -
4 600 V, 60 Hz as standard. Different voltage and frequency
High fire
2
1
0
Standard burner motor:
-1 Insulation class F, protection IP 55.
-2
0 3,000 6,000 9,000 12,000 15,000 18,000 21,000 24,000 27,000 30,000 33,000 36,000
59
Scope of delivery/Accessories
Dual fuel burners size 30 and 70, version 3LN
Scope of delivery RGL30 RGL40 RGL50 RGL60 RGL70
Burner housing, hinge flange, housing cover, Weishaupt burner motor, air regulator
housing, fan wheel, combustion head, ignition unit, ignition cable, ignition electrodes,
atomising system with oil nozzle/s, combustion manager with operating unit, flame sensor,
stepping motors, flange gasket, limit switch on hinge flange, fixing screws ● ● ● ● ●
Combustion manager W-FM100 ● ● ● ● ●
Two gas shut off valves ● ● ● ● ●
Ignition pilot ● ● ● ● ●
Gas butterfly valve ● ● ● ● ●
Air pressure switch ● ● ● ● ●
Gas pressure switches ● ● ● ● ●
Ratio control sliding sleeve in mixing head ● ● ● ● ●
Stepping motor for
Air regulator ● ● ● ● ●
Gas butterfly valve ● ● ● ● ●
Mixing head ● ● ● ● ●
Accessories
Intake flange for the connection of an air duct ○ ○ ○ ○ ○
Solenoid valve for air pressure switch test for cont. run fan or post-purge ○ ○ ○ ○ ○
Combustion head extension ○ ○ ○ ○ ○
Speed control ○ ○ ○ ○ ○
O2 trim ○ ○ ○ ○ ○
W-FM loose for installation in a remote control panel ○ ○ ○ ○ ○
● Scope of delivery
○ Accessories
60
Technical data
Dual fuel burners size 30 to 50, version 3LN
Technical data RGL30/2-A 3LN RGL40/2-A 3LN
Burner motor 3~208 - 600V Model W-D112/140-2/4K5 W-D112/170-2/7K0
Motor rating HP (kW) 6.6 (5.0) 10.4 (7.8)
FLA at 460V A 8.6 14
Speed (60 Hz) rpm 3,510 3,500
Fan wheel Colour red red
ø 248 x 104 275 x 104
Combustion manager Model W-FM100 / W-FM200 W-FM100 / W-FM200
Ignition unit Model W-ZG02 W-ZG02
Stepping motor Air Model SQM45 SQM45
Fuel Model SQM45 SQM45
Mixing head Model SQM48 SQM48
Pump, fitted Model TA3C TA3C
Oil solenoid valves 55V (supply) Model 121 K 6220 321 H 2322
55V (return) Model 121 K 6220 121 G 2320
Oil pressure switch 1 – 10 bar Model DSA 46 F001 DSA 46 F001
(return #2 oil - 5 bar)
Oil hoses DN, length in inch (mm) 20/40” (1000) 20/40” (1000)
Burner weight approx. lbs (kg) 320 (145) 353 (160)
61
Technical data
Dual fuel burners size 60 and 70, version 3LN
Technical data RGL60/2-A 3LN RGL70/1-B 3LN RGL70/2-A 3LN
Burner motor 3~208 - 600V Model W-D132/210-2/14K0 W-D160/240-2/18K0 W-D160/240-2/22K0
Motor rating HP (kW) 20 (15) 22 (16.5) 26.6 (20)
FLA at 460V A 28 30.5 33
Speed (60 Hz) rpm 3,520 3,560 3,550
Fan wheel Colour / ø no color / 450 x 127.5-R green / 530 x 120 green / 530 x 120
Combustion manager Model W-FM100 / W-FM100 / W-FM100 /
W-FM200 W-FM200 W-FM200
Ignition unit Model W-ZG02 W-ZG02 W-ZG02
Stepping motor Air Model SQM45 SQM45 SQM45
Fuel Model SQM45 SQM45 SQM45
Mixing head Model SQM48 SQM48 SQM48
Pump, fitted Model T2C T2C (up to T3C
130 GPH / 450 kg/h)
T3C (from
130 GPH / 450 kg/h)
Oil solenoid valves 55V (supply) Model 321 H 2322 321 H 2522 321 H 2522
55V (return) Model 121 G 2320 121 G 2520 121 G 2520
Oil pressure switch 1 – 10 bar Model DSA 46 F001 DSA 46 F001 DSA 46 F001
(return #2 oil - 5 bar)
Oil hoses DN, length in inch and (mm) 25/51” (1300) 25/51” (1300) 25/51” (1300)
Burner weight approx. lbs (kg) 728 (330) 960 (435) 960 (435)
62
Oil burner dimensions
Size 30 to 70
d1
h1
b 4 d2 b1
h3 r2
b2
r1
approx. 10.4
d5
(264 mm)*
l3 l1
d7
* depending on oil preheater d6
63
Oil burner dimensions
Size 30 to 70
d1
h1
b 4 d2 b1
h3 r2
b2
r1
approx. 10.4
d5
(264 mm)*
l3 l1
d7
* depending on oil preheater d6
64
Gas burner dimensions
Size 30 to 70
d5
b 4 d 1 d2 r2 b1
h1
b2
h3
d7
d6 r1
l10
l3 l9
l1
65
Gas burner dimensions
Size 30 to 70
d5
b 4 d 1 d2 r2 b1
h1
b2
h3
d7
d6 r1
l10
l3 l9
l1
66
Dual fuel burner dimensions
Size 30 to 70
d5
b1
r2
b4 d1 d2
h1
b2
h3 d7
d6 r1
l10
l3 l9
l1
67
Dual fuel burner dimensions
Size 30 to 70
d5
b1
r2
b4 d1 d2
h1
b2
h3 d7
d6 r1
l10
l3 l9
l1
68
Fuel systems
GL30Z (oil side) GL30T/GL40T/L50T (oil side) RGL30 (oil side)
110V
10 11 12 17 16 10 11 12 16 10 11 12 17 18a 16
69
Fuel systems
RGMS60/70 (oil side) RL30 to RL50 vers. 3LN
With separate pump and preheater stations RGL30 to RGL70 vers. 3LN (oil side)
10 17 11 18b 14b 12 16 10 11 12 12
P 16
110V
16
55V 55V
55V
P M 16
P M
6 7 4b 9
6 7 4b 9 The gas train schematics show typical con-
figuration for UL gas train. The actual gas
train shipped with burner might have differ-
ent configuration depending on applicable
code and regulation.
8
P P P P
1 2 3 4 1 5 1 2 3 4 1 5
Legend
1 Ball valve 11 Strainer 14a Oil pressure switch in return
2 Gas pressure regulator 12 Oil solenoid valve, normally closed (55V con- 14b Oil pressure switch in supply (optional, not
3 Low gas pressure switch nected in series with 12a) shown)
4 Double main SSOV 12a Oil solenoid valve, normally closed 15 Oil regulator
4b Pilot gas valves (55V connected in series with 12, installed 16 Nozzle head with shut off device
5 High gas pressure switch against the flow direction) 16a Nozzle head without shut off device
6 Pilot train ball valve 12b Bypass solenoid valve, normally open 17 Oil preheater
7 Pilot gas pressure regulator 13 Oil solenoid valve, normally closed 18a Temperature switch
8 Gas butterfly valve 13a Oil solenoid valve, normally closed 18b Temperature sensor Pt 100
9 Burner for stage 1, 2 and 3 (to monitor minimum oil temperature)
10 Oil pump 13b Oil solenoid valve, normally open 19 External oil filter 1
70
Pump and preheater stations
Scope of delivery – pump station medium used. Planning and installation
Pump unit (screw spindle pump with When selecting and sizing, please refer instructions
motor), pressure gauge, vacuum gauge, to the oil temperature diagrams in Oil filter, air/gas separator, circulation
pressure regulating valve, ball valves, chapter 5.3 of the technical brochure tank, pump station and oil preheater
suction flange, pressure flange “Weishaupt electric and medium oil station must be installed as close as
including counter flanges, screws and preheaters”, print No. 18. Weishaupt possible to the burner.
washers, suction side filter. All parts are medium oil preheaters can be used
fully assembled on an oil drip tray. universally. It is possible to change the On burners with separate oil preheater
medium at any time. The preheaters are the time required for oil circulation
The pump station is built as one of two used either alone or in conjunction with during start up depends on the length
different versions - either as a single an electric oil preheater. of the pipework between the burner
station unit with one pump, or as a twin and the air/gas separator or circulation
station unit with two pumps with one If operating steam at more than 110 PSI tank.
pump serves as a backup unit. Should or hot water between 360 F (180 °C)
one pump fail, it is possible to quickly and 390 F (200 °C) is continuously The shorter the pipeline, the shorter the
switch over to the other. available, then an electric preheater period between heat being called for
is not required. This is also possible if and oil release and burner start after a
Only tried and tested makes of pump installation with the above minimum controlled shutdown.
are used. The pumps are carefully pressures or temperatures can be
matched to the capacity of the burner. operated with #2 oil or gas.
71
Pump and preheater stations
Specification
Burner Technical data - Pump Version with 1 pump Version with 2 pumps
Rating Flow rate in GPH (l/h) Speed Motor rating Pump model Pump model
GPH (based on 150cSt) rpm HP (kW)
Pump stations - frequency 60 Hz
74 – 114 265 (1,020) 3,400 2.9 (2.2) SPF 10-38 SPZ 10-38
114 – 214 532 (2,050) 3,400 3.4 (2.6) SPF 20-38 SPZ 20-38
214 – 265 705 (2,720) 3,400 5.3 (4.0) SPF 20-46 SPZ 20-46
72
That is not a Facade. Weishaupt has been one of the
leading company in heating and combustion industry
since years with headquarter in Schwendi and branches
all over the world. That is Reliability.
Weishaupt is Trustworthy, quality,
Reliability. good customer service,
The family business innovation and experi-
in Schwendi was ence are values on
established by Max which the Pioneer Max
Weishaupt in 1932. Weishaupt established
Represented in 55 his company. All this
countries by branch combined in a word is
offices and subsidiaries reliability.
Weishaupt is interna-
tional leader in the Therefore stands
areas of combustion Weishaupt today.
technology and heating
applications.
73
73
That is not an Imagination. Continuous research
and development at Weishaupt ensure environ-
mental friendly and efficient burners.
That is Reliability.
74
Developing improvement.
Weishaupt recognizes the signs of time
and researches perpetually to get more
efficient and environmental friendly
burner systems.
75
Weishaupt Corporation
6280 Danville Road
Mississauga, ON L5T 2H7, Canada
Ph: (905) 564 0946
Fax: (905) 564 0949
www.weishaupt-corp.com