AMTROBOX EEx ia

Type series booklet


8526.12/11--10 AMTRONIC EEx ia
Intrinsically safe
remote indication and control box

0081 II 1 G
EEx ia IIC T6

Position monitoring
and on/off pneumatic distribution functions

AMTROBOX EEx ia and AMTRONIC EEx ia (R 1172) remote indication and control boxes are of intrinsically safe protection design
for use in explosive atmospheres.
They are in accordance with ATEX 94/9/CE directive and 0081 II 1 G. marking.
EC type examination certificate: LCIE 03 ATEX 6435 X.
They are approved EEx ia IIC T6 in accordance with EN 50014 and EN 50020 standards.
The representative gas of explosion risk is hydrogen, the maximum temperature of the box is 85° C.

Perfectly waterproof (IP 67protection level), they can be used in any industrial environment.

AMTROBOX EEx ia R 1172


Specially designed for use with double acting ACTAIR and spring return DYNACTAIR pneumatic actuators and MR manual reducers,
this box integrates, in a modular form, the following electric functions:
• Position detection (opening and closing) by microswitches or inductive proximity detectors.
• Feed--back position by angle sensor and 4--20 mA transmitter (option).

AMTRONIC EEx ia R 1172


Specially designed for use with double acting ACTAIR and spring return DYNACTAIR pneumatic actuators, this box ensures the
following functions:
• Position detection (opening and closing) by microswitches or inductive proximity detectors.
• Feed--back position by angle sensor and 4--20 mA transmitter (option).
• On/off pneumatic distribution.

Fitted on to the top of the actuator housing, the AMTRONIC EEx ia box ensures the direct control of air supply to the actuator
and only requires one pneumatic and one electric supply, preventing thus the stacking of accessories such as limit switch box,
pneumatic valve, etc. and the various pneumatic piping and electric wiring systems.

This leaflet is also to be used as a start--up guide (ref. 42 042 911)


AMTROBOX EEx ia
AMTRONIC EEx ia

AMTROBOX EEx ia

Transparent sight glass

Pointer

Adjustable cams

Microswitches or
inductive proximity detectors
on supporting plate
Angle sensor (option)

4--20 mA transmitter (option)

External earth terminal

2
AMTROBOX EEx ia
AMTRONIC EEx ia

AMTRONIC EEx ia

Transparent sight glass

Pointer
Push--buttons
for emergency control
of the electric pilots

Adjustable cams

Electric pilots
Microswitches or
inductive proximity detectors
on supporting plate Angle sensor (option)

Pneumatic
valves

4--20 mA transmitter (option)

External earth terminal

Operating time
adjustment

3
AMTROBOX EEx ia
AMTRONIC EEx ia

Contents

Page
General technical data 5

Overall dimensions and weight 5

Parts common to all versions 6

Position detection: AMTROBOX EEx ia and AMTRONIC EEx ia


-- General 8
-- Construction 8

By microswitches -- Boxes ref. R 1172--A2....


-- Technical characteristics of microswitches 9
-- Wiring diagram 9
-- Barriers and interfaces 9

By inductive proximity detectors -- Boxes ref. R 1172--K3.... and R 1172--J7....


-- Technical characteristics of detectors 10
-- Wiring diagram 10
-- Barriers and interfaces 10

On/off pneumatic distribution: AMTRONIC EEx ia


-- Construction 11
-- Various available configurations 12
-- Technical data of electro--pneumatic valve -- Wiring diagram -- Barriers and interfaces 13

Optional feed--back position 0° to 90° by a 4--20 mA signal 14

Pneumatic supply 15

Commissioning
-- Warning 16
-- Electric connection 16
-- Pneumatic connection 16
-- Operating time adjustment (AMTRONIC EEx ia) 17
-- Open/close position detection adjustment 17
-- Angle sensor adjustment 18
-- 4--20 mA feed--back adjustment 18

Declaration of conformity 19

Product features 20

4
AMTROBOX EEx ia
AMTRONIC EEx ia

General technical data

Environment
-- Protection level: IP 67
-- Resistance to impacts: 5 g according to CEI 68--2--27
-- Resistance to vibrations: 2 g, 6 mm from 5 to 500 Hz as per STANAG 4370 3 axis
-- Working temperature: from -- 10° C up to + 50° C
-- Control air temperature: from -- 10° C up to + 30° C (AMTRONIC EEx ia)

-- Electromagnetic compatibility:
EN 61000--6--2; EN 61000--6--4
-- generic standards
EN 55011; EN 61000--4--2; EN 61000--4--3; EN 61000--4--4; EN 61000--4--5;
-- test standards
EN 61000--4--6
-- Protection against explosive EN 50014; EN 50020 standards
environment since intrinsically safe

Housing
-- Material: Aluminium
-- Coating: Black cataphoresis
-- Position indication: By visual pointer under transparent sight glass
-- Bolting: A2--70 (316L) stainless steel

Air distribution:
-- Pressure connection Port marked “P” equiped with an internal filter on the base (1/4 gas)
-- Central discharge connection Port marked “E” fitted with a silencer or connectable to exhausted network (1/4” gas)
-- Working pressure 3,5 to 8 bar (50 to 115 psi), dry or lubricated
-- Filtration level < 50 µm
-- Dew point --5° C
-- Maximum flow rate 300 Nl/mn at 6 bar (4/3) / 400 Nl/mn at 6 bar (4/2)
-- Pneumatic consumption when idle None

Overall dimensions (mm) and weight (kg)


F
View from F
209

58
144

P E 78

Pneumatic connection 2 x 1/4” gas


Weight: 1,5 kg

5
AMTROBOX EEx ia
AMTRONIC EEx ia

Parts common to all versions

A B

554.2 900.3 817.1 412.1 191.1 81--2.2 900.4 81--2.1

160

191.1 890 188.1 900.5 410.2 747 412.2 900.9 81--18.1

A B

Section B--B Section A--A

629 626

412.1 210

970.1 970.2

819 553.1
62--2 81--84.1

554.2 191.1
81--33 932.1

900.2 81--29
900.1 314

554.1 903.1

410.1

6
AMTROBOX EEx ia
AMTRONIC EEx ia

Common parts to all versions

Item Designation Materials


160 Cover Aluminium with black cataphoresis coating
188.1 Sheet Steel
191.1 Sheet support Polyamide 6
210 Operating shaft Acetal
314 Thrust washer 304 stainless steel
410.1 Cover gasket Nitrile
410.2 Base gasket Nitrile
412.1 Sigh glass O--Ring Nitrile
412.2 O--Ring Nitrile
553.1 Thrust Steel
554.1 Plain washer A2--70 stainless steel
554.2 Plain washer A2--70 stainless steel
62--2 3--cam sub--assembly Acetal + 30% fibreglass
626 Sight glass Transparent polycarbonate
629 Pointer Polyamide 6--6 with anti U.V. treatment
747 Check valve sub--assembly ------
81--18.1 Snap ------
81--2.1 500 SV type ground wire 1,5 mm2 Copper
81--2.2 Ground wire + cable terminal Copper
81--29 EEx 05--0012--0002 earth terminal Bartec
81--33 Detection sheet for inductive proximity detector Steel
81--84.1 Wiring diagram Aluminium sticker
817.1 Cable way Skiffy
819 Terminal block Entrelec
890 Base Aluminium with black cataphoresis coating
900.1 Cheese--head screw A2--70 stainless steel
900.2 Cheese--head screw A2--70 stainless steel
900.3 Cheese--head screw A2--70 stainless steel
900.4 Self--cutting screw Zinc coated steel cl. 8--8
900.5 Cheese--head screw A2--70 stainless steel
900.9 Pozidriv screw Zinc coated steel cl. 8--8
903.1 Plug 1/4’’ Gas Polyamide 6--6
932.1 Spring retaining ring Steel
970.1 Identity plate Adhesive polyester
970.2 Instruction notice Paper

7
AMTROBOX EEx ia
AMTRONIC EEx ia

Position detection: AMTROBOX EEx ia and AMTRONIC EEx ia


General
The intrinsically safe microswitches and inductive proximity detectors fitted in AMTROBOX EEx ia and AMTRONIC EEx ia are in
accordance with EN 50014 and EN 50020 standards relating to components installed in explosive environment.
They must be connected individually to an approved safety barrier. Situated in a safe area, these barriers allow the power supply of
the microswitches installed in hazardous area.

Construction

View from F
F
Microswitches
554.4 900.7 920.1 839

Proximity detectors View from F


F
900.7 554.4 818
196

Item Designation Materials


196 Securing plate Steel
554.4 Plain washer Steel
Detector EEx--ia ref. NS 5002 or IFM Effector (box ref. R 1172--J7....) or
818
Detector V3 DIN 41635 NJ2--V3--N Pepper & Fuchs (box ref. R 1172--K3....)
839 Microswitch V4 DIN 4635B ref. 83 136 069 Crouzet (box ref. R 1172--A2....)
900.7 Cheese--head screw Steel cl. 8.8
920.1 Hexagonal nut Steel cl. 8.8

8
AMTROBOX EEx ia
AMTRONIC EEx ia

Position detection by microswitches -- Box ref. R 1172--A2....

Technical characteristics of microswitches

• Manufacture: Crouzet
• Type: 83 186 069 lever 170A R=24 -- V4
• Conformity certificate: Material according to EN 50020 §5 standard -- Common material
• Electrical output: By 3--wire cable, section 0.5 mm2
• Protection level: IP 67
• Wiring: The two microswitches are workshop--connected to the main terminal block by means of
spring connectors, capacity 2.5 mm2. Refer to wiring diagram below.
• Max. voltage: 60 VDC
• Mechanical and electrical
life: 2 . 106 cycles
• Working temperature: From -- 25° C up to + 70° C
• Resistance to impacts: 5 g according to CEI 68--2--27
• Resistance to vibrations: 2,5 g from 5 to 500 Hz as per STANAG 4370 3 axis
• Function: Change--over

Special conditions for safe use

• Working ambient
From -- 10° C to + 50° C
temperature :
• Max. voltage U0: ≤ 26,5 VDC
• Max. current I0: ≤ 127 mA

Wiring diagram

Hazardous area Safe area

Barriers and Interfaces


The barriers and interfaces recommanded by KSB--AMRI can be ordered to one of the manufacturers in the following table. When
ordering, specify that these components are intended for the electric supply of Crouzet type 83 186 069 microswitches.

Interface Laboratory Permitted


Manufacturer Barrier reference Gas group
reference certificate areas
RDN 11 LCIE 02 ATEX 6104 X II C
GEORGIN
RDN 211 LCIE 02 ATEX 6104 X II C
NAEV--DI 2 N--A230 LCIE 00 ATEX 6034 X II C A area
Any
AP 3
NAEV--DI 2 N--A115 LCIE 00 ATEX 6034 X II C

Any other barrier or interface of different construction may be used provided it complies with regulations requirements and that
calculation and installation rules are respected.
For each reference defined in the above table, KSB--AMRI can supply to the user the corresponding loop calculations.

9
AMTROBOX EEx ia
AMTRONIC EEx ia

Position detection by inductive proximity detectors -- Boxes ref. R 1172--K3.... or R 1172--J7....


Technical characteritics of detectors
Box ref. R 1172--J7.... Box ref. R 1172--K3...
• Manufacturer: IFM Effector Pepperl & Fuchs
• Type: NS 5002 NJ2--V3--N
• Conformity certificate: PTB 01 ATEX 2191 PTB 00 ATEX 2032 X
• Nominal voltage: 8.2 VDC 8 VDC
• Voltage: 5 to 25 VDC ----------
• Off state ondulation: < 5% ----------
• Cable max. resistance: 50 Ω ----------
• Output activation: < 1 mA < 1 mA
• Output non activation: < 2.2 mA < 3 mA
• Self capacity: < 70 ηF < 35 ηF
• Self inductance: < 190 µH < 50 µH
• Switching frequency: 800 hz 1000 hz
• Resistance to impacts: < 30g on 10 ms ----------
• Resistance to vibrations: < 10g to 55 hz. a = 1 mm ----------
• Protection level: IP 67 IP 67
• Rated operating distance: 2 mm 1,62 mm
• Output type: NF NF
• Connection: Cable PVC : 2 x 0.14 mm2 Cable PVC : 2 x 0.14 mm2
• Working temperature From -- 25° C up to + 70° C From -- 25° C up to + 70° C

Special conditions for safe use


IFM Effector NS--5002 Pepperl & Fuchs NJ2--V3--N
• Working ambient temperature : From -- 10° C to + 50° C From -- 10° C to + 50° C
• Max. voltage U0 : ≤ 16 VDC ≤ 15,5 VDC
• Max. current I0 : ≤ 50 mA ≤ 52 mA
• Max. Consumption P0: ≤ 150 mW ≤ 169 mW
Wiring diagram Hazardous area Safe area

Nc

Nc

Barriers and Interfaces


The barriers and interfaces recommanded by KSB--AMRI can be ordered to any of the manufacturers in the following table. When
ordering, specify that these components are intended for the supply of proximity detectors IFM Effector NS 5002 or Pepperl & Fuchs
NJ2--V3--N.
Manufacturer Barrier reference Interface Laboratory Gas group Permitted
reference certificate areas
GEORGIN RDN 11 LCIE 02 ATEX 6104 X II C
RDN 211 LCIE 02 ATEX 6104 X II C Any area
NAEV--DI 2 N--A230 LCIE 00 ATEX 6034 X II C
AP 3
NAEV--DI 2 N--A115 LCIE 00 ATEX 6034 X II C
Any other barrier or interface of different construction may be used provided it complies with regulations requirements and that the
calculation and installation rules are respected.
For each reference defined in the above table, KSB--AMRI can supply to the user the corresponding loop calculations.

10
AMTROBOX EEx ia
AMTRONIC EEx ia

On/off pneumatic distribution: AMTRONIC EEx ia

In AMTRONIC EEx ia,the on/off pneumatic distribution is added to the position detection function.
This distribution function is ensured by means of a pneumatic valve with intrinsically safe solenoid valve in accordance with
EN 50014 and EN 50020 standards.

Construction
412.4 412.6

486.1

553
59--52

950.2

950.1

74--7
81--2.5 412.3 909 932.2 745 81--1

Item Designation Materials


412.3 O--Ring Nitrile
412.4 O--Ring Nitrile
412.6 Toric rope Nitrile
486.1 Ball Stainless steel
553 Thrust Acetal
59--52 Push--button for emergency control Acetal
74--7 Electro--pneumatic valve ------
745 Filter Bronze
81.1 Connector EEx--ia ref. 81516082 Crouzet
81--2.5 Wire Copper
909 Operating time adjustment screw Steel
932.2 Threaded rod Steel
950.1 Spring Stainless steel
950.2 Spring Steel

Note: in case of 4/2 monostable electro--pneumatic valve , the cover is equipped with only one push--button for emergency control
and one ball. In other cases, the cover is equipped with two push--buttons.

All AMTRONIC are equipped with a bronze silencer ref. 88--5.

11
AMTROBOX EEx ia
AMTRONIC EEx ia

Available configurations

• For ACTAIR double acting actuators


Configuration Case 1a Case 1b Case 2 Case 6a
Safety by In open or closed
In open position In closed position Stand in position
lack of current position(*)
4/3 centre closed
Pneumatic valve 4/2 monostable 4/2 monostable 4/2 bistable
to pressure
One 3/2 NC One 3/2 NC Two 3/2 NC Two 3/2 NC
Solenoid valve
solenoid valve solenoid valve solenoid valves solenoid valves
Operating pressure 3.5 to 8 bar 3.5 to 8 bar 3.5 to 8 bar 3.5 to 8 bar
(*) In bistable version, the actuator stays in the position defined by the last signal received (memory).

Case Case 1b Case 2 Case 6a


O 1a C C O O C O C

(O) (O)

(C) (O) (C)

(C)

• For DYNACTAIR spring return actuators


Configuration Case 4a Case 4b Case 7a Case 7c
Safety by In closed Stand Stand
In open position
lack of current position in position in position
4/3 centre closed 4/3 centre closed
Pneumatic valve 4/2 monostable 4/2 monostable
to pressure to pressure
One 3/2 NC One 3/2 NC Two 3/2 NC Two 3/2 NC
Solenoid valve
solenoid valve solenoid valve solenoid valve solenoid valve
Operating pressure 3.5 to 8 bar 3.5 to 8 bar 3.5 to 8 bar 3.5 to 8 bar

Case 4a Case 4b Case 7a Case 7c


O C O C O C F O

(O) (F)

(C) (O)

(C) (O)

12
AMTROBOX EEx ia
AMTRONIC EEx ia

Technical characteristics of electro--pneumatic solenoid valve

• Manufacturer: Crouzet
• Type: 81 519 335
• Conformity certificate: LCIE 02 ATEX 6122 X
• Nominal voltage: 24 VDC
• Max. allowable voltage: 28 VDC
• Consumption: ≤ 0.7 W
• Manual emergency control: By impulse
• Control fluid: Air or neutral gas
• Operating pressure: 3 to 7 bar
• Working temperature: From --10° C up to +50° C
• Fluid temperature: From --10° C up to +30° C
• Changeover time: 8 to 15 ms
• Mechanical life: < 1.5 x 107 operations
• Working ratio: 100 %
• Isolation class: F
• Ignition intensity: 55.5 mA
• Max. allowable intensity with k = 1.5: 37 mA
• Capacity: 0 ηF
• Resistance at + 20° C: 580 Ω
• Resistance at -- 10° C: > 476 Ω
• Resistance at + 50° C: < 690 Ω

Breaking capacity according to the standard CEI 60947--5--1: 6000 cycles


Alternating current (AC)
I (A)
24 V 48 V 110 to 127 V 220 to 240 V 380 to 440 V
AC--12 6 6 6 6 5
AC--13 2 1,5 1 1 0,5
AC--14 ≤ 72 VA
AC--15 2 1,5 1 1 0,5

Direct current (DC)


I (A)
24 V 48 V 110 to 127 V 220 to 240 V
DC--12 6 2 0,4 0,2
DC--13 3 1 0,2 0,1
DC--14 0,6 0,15 0,02 0,01

I (A) : Allowable maximum intensity (A)

AC--12: Control of resistive loads and solid state loads with isolation by optocouplers
AC--13: Control of solid state loads with transformer isolation
AC--14: Control of small electromagnetic loads (≤ 72 VA)
AC--15: Control of electromagnetic loads (≥ 72 VA)
DC--12: Control of resistive loads and solid state loads with isolation by optocouplers
DC--13: Control of electromagnets
DC--14: Control of electromagnetic loads having economy resistors in circuit
This microswitch is designed to operate indifferently on circuits of bi--level type: low intensity (1 mA, 4 V minimum) or medium inten-
sity (6 A maximum). However, a microswitch must change over only one and same type of PCB during its all use.

Special conditions for safe use

• Working ambient temperature : From -- 10° C to + 50° C


• Max. voltage U0 : ≤ 28 VDC
• Current going through the solenoid valves: ≤ 37 mA
13
AMTROBOX EEx ia
AMTRONIC EEx ia

Wiring diagram
Hazardous area Safe area

Solenoid valve 1 U max 28 Vdc +


+ B I max 37 mA +
- C - -
+
+ D +
- E - -
U max 28 Vdc
Solenoid valve 2
I max 37 mA

Barriers and Interfaces


The barriers and interfaces recommanded by KSB--AMRI can be ordered to any of the manufacturers in the following table. When
ordering, specify that these components are intended for the supply of electro--pneumatic solenoid valve Crouzet type 81 519 335.

Manufacturer Barrier reference Laboratory certificate Gas group Permitted areas


GEORGIN BZC 24/50/1/A1 LCIE 01 ATEX 6070 X II C
Any area
AP 3 NAEV--...--DO2H LCIE 00 ATEX 6034 X II C

Optional feed--back position 0° to 90° by 4-- 20 mA signal


This option is common to AMTROBOX EEx--ia and AMTRONIC EEx ia (boxes ref. RTC 1172).
The feed--back position consists in a 4.7 kΩ on 100° potentiometric angle sensor associated with a transmitter self--supplied by the
4--20 mA current loop.
Construction 81--2.4 81--2.3 554.3 900.6
191.2 62--9 816

Item Designation Materials


191.2 Support Steel
554.3 Plain washer Stainless steel
62--9 Transmitter XT42--SI--NIV 4--20 mA Puissance 3
81--2.3 Black wire Copper
81--2.4 Red wire Copper
816 Angle sensor sub--assembly ------
900.6 Cheese--head screw Zinc coated steel

14
AMTROBOX EEx ia
AMTRONIC EEx ia

Wiring diagram
The wiring of the angle sensor and transmitter assembly is carried out in workshop, the connection to the current loop is through the
terminal no. 10 for and on the terminal no. 11 for .
Two adjustments are available for the zero adjustment (4 mA) and the gain (20 mA).
When the AMTRONIC EEx ia box is delivered with its actuator, the assembly is preadjusted in workshop.
Hazardous area Safe area
Angle sensor Orange
Green
Violet

Transmitter
XT42-- SI-- NIV + U0
Icc
--

The intrinsically safe parameters concerning the elements could be connected on the terminals 10 and 11,
must not exceed the values below:
CAUTION !
U0 P0 C0 L0 Icc
30 V 820 mW 60 nF 50 mH 27,5 mA
27 V 980 mW 90 nF 40 mH 30,0 mA
24 V 990 mW 120 nF 51 mH 26,5 mA
21 V 870 mW 190 nF 62 mH 23,5 mA
18 V 750 mW 290 nF 90 mH 20,0 mA
Interface Laboratory Permitted
Manufactuer Barrier reference Gas group
reference certificate areas
BZC 24/50/1/A1
LCIE 01 ATEX 6070X II C
GEORGIN BZC 24/50/22/A1
Any
Converter BXNT1 LCIE 02 ATEX 6104 X II C area
AP 3 PROF SI 38--...--PAS LCIE 03 ATEX 6078 X II C

Detection of faulty box or angle sensor connections.


1
0%
Defect Transmitter response
2
M wire 1 open I output ≈ 20 mA
wire 2 open I output ≈ 25 mA
3 wire 3 open I output ≤ 4 mA
100 % No sensor I output ≈ 25 mA

Pneumatic supply - Pneumatic connection for AMTRONIC


The pneumatic valve works with 50 µ filtered air.
Before pneumatic connection, check the pipe is without impurities, mainly when starting--up.
As a measure of safety, the box is equipped with a filter in the input port in order to prevent the clogging of the pneumatic
distributor with the impurities.
This filter can be replaced if it is clogged (the distributor don’t work): extract it by means of a screw and put in the port a new
clean filter.
Working pressure from 3.5 to 8 bar (50 to 115 psi).

• Pressure connection: port marked ’’P’’.


• Exhaust connection: port marked ’’E’’ fitted with a silencer or connectable to
exhaust network.

15
AMTROBOX EEx ia
AMTRONIC EEx ia

Commissioning

WARNING
CAUTION !

The installation and start--up of the electro--pneumatic actuators must be according to the best safety practices and
mainly:

Piping:
Starting--up of a new installation requires cleaning the piping by air before connection to the actuator. This will remove any
impurities impossible to eliminate during construction (fillings, flux, paste, PTFE, etc.).
As a safety measure, the box is equipped with a filter in the input port to prevent clogging of the air valve by impurities. This
filter can be replaced (if clogged, the air valve does not work) by extracting it by means of a screw and inserting a new clean
filter.

Electric wiring:
-- The electric components are “CE” marked in accordance with 89/336/EEC european directive.
-- The electric supply voltage and the electric values of the signals must be checked before connecting the components.
-- The components of the intrinsically safe electric loops should be checked to ensure the inputs and outputs as well as
wiring, do meet the regulations in force.
KSB--AMRI shall keep at the disposition of users the loop calculations for the recommended associated equipment.
-- An external earth terminal allows grounding of the metal parts of the control box.

Never exceed the values stipulated in this leaflet!


This box is a pressurized electric device. As such, it may be a source of danger for property or even personnel.
Any excess of these values may cause damage.

Never uncouple or disassemble the AMTRONIC EEx ia box or its accessories when pressurized or energized.
Always make sure that the actuator chambers are free from air pressure by pushing on the buttons for emergency control
of the pilots before disassembling the pneumatic valve, solenoid valvesor the box itself.

During workshop or on- site checking, the valve associated with the actuator and its AMTRONIC EEx ia box can
be operated from full open to full closed position.
This operation may be of a high significant risk of personnal injury if the safety steps required are not taken to
prevent access between the disc and the seat.

Electric connections
The electric connection is obtained via 2 packing--gland PG 13,5 (plastic or stainless steel).
Gland capacity: cable external dia. 8 to 13 mm, wiring to be connected to spring terminal max. are 2.5 mm2.
The good tightness of the box depends on cable selection and the tightening level of the packing--gland.

Pneumatic connection

AMTROBOX EEx ia

The pneumatic connection is done directly on the actuator or on the solenoid valve fittedon the actuator

Direct connection Connection on solenoid valve

16
AMTROBOX EEx ia
AMTRONIC EEx ia

AMTRONIC EEx ia

The pneumatic valve works with 50 µm filtered air. Working pressure from 3.5 to 8 bar (50 to 115 psi).
Before connecting pneumatic supply, check the piping is clean, without any impurities, mainly when starting--up of a new installa-
tion.
As a measure of safety, the box is equipped with a filter in the input port in order to prevent the clogging of the distributor with
impurities. This filter can be cleaned if clogged (in this case, the air valve does not work): extract it by means of a wood screw and
clean it with solventor compressed air.

• Direct connection on AMTRONIC.


• Working pressure: 3.5 to 8 bar (50 to 115 psi).
• Pressure connection: port marked ’’P’’.
• Exhaust connection: port marked ’’E’’ fitted with a silencer or connectable to exhaust network.

Operating time adjustment (AMTRONIC EEx ia)


The operating time can be adjusted by means of two independent flow adjusters: one for opening and one for closure time.
Depending on the actuator type, the operating times can be adjusted as stated in the following table.

Double acting actuators Spring return actuators


Operating time Operating time
Type Type
minimum maximum minimum maximum
ACTAIR 3 1 second 5 seconds DYNACTAIR 1.5 2 seconds 5 seconds
ACTAIR 6 1 second 7 seconds DYNACTAIR 3 2 seconds 7 seconds
ACTAIR 12 2 seconds 15 seconds DYNACTAIR 6 2 seconds 15 seconds
ACTAIR 25 3 seconds 20 seconds DYNACTAIR 12 4 seconds 20 seconds
ACTAIR 50 4 seconds 30 seconds DYNACTAIR 25 6 seconds 30 seconds
ACTAIR 100 6 seconds 40 seconds DYNACTAIR 50 10 seconds 40 seconds
ACTAIR 200 9 seconds 60 seconds DYNACTAIR 100 15 seconds 60 seconds
ACTAIR 400 15 seconds 120 seconds DYNACTAIR 200 40 seconds 120 seconds
ACTAIR 800 30 seconds 150 seconds DYNACTAIR 400 75 seconds 150 seconds
ACTAIR 1600 60 seconds 180 seconds DYNACTAIR 800 150 seconds 180 seconds
For a shorter operating time than the min. one or for a longer operating time than the max. one, please consult us.
CAUTION!
The set screws of the exhaust flow rate adjustors are under line air pressure.
THEREFORE they must not be excessively unscrewed otherwise the screws may be expelled
by the pressure.
The top of the screw must not protrude from its hole by more than one millimetre.
Open/close position detection adjustment
The limit switches or detectors are factory adjusted.
It is not necessary to re--adjust before valve mounting on site.
Nevertheless, if you wish to re--adjust after a maintenance operation, proceed as follows:
-- Remove the cover of the box.
-- Put the disc in extreme position (opening or closing).
-- Unscrew the two metal screws one turn.
-- Adjust triggering of the required detector by turning the coloured screw corresponding to the colour of the cam to adjust.
-- Proceed in the same manner with the opposite switch.
-- Each cam is adjusted independently and the adjustment does not affect in any way the adjustment of the other cam.
-- When adjustments are completed, slightly tighten the two metal screws to prevent adjustments being changed.
-- Replace the cover of the box.

1 -- Loosen the metal screws 2 -- Adjust the cams 3 -- Tighten the metallic screws
17
AMTROBOX EEx ia
AMTRONIC EEx ia

Angle sensor adjustment


’’N’’ mounting
The Box / Actuator assemblies are delivered for “N” mounting on the valve. Angle
Box sensor
Any other mounting must be specified when ordering and requires a modification to
the position of the angle sensor. ED

If the actuator is designed for an “M” mounting, it is necessary to change the


position of the angle sensor in compliance with the opposite diagram.
To perform this operation, it is necessary to previously remove the cover and to disas-
semble the following in the given order:
-- the control solenoid valves (AMTRONIC EEx ia), ’’M’’ mounting
-- the pointer, Angle
-- the securing plate with the position detectors, Box sensor
-- the angle sensor attachment screw.
Now turn the angle sensor casing 90° and repeat the previous operations in reverse
order. ED

4--20 mA feed--back position adjustment

When the box is delivered with its actuator, the transmitter is preadjusted in workshop.
It is not necessary to re--adjust it before valve mounting on site.
Nevertheless, if you wish to re--adjust it after a maintenance operation, proceed as follows:
-- rRmove the cover of the box.
-- Remove the electric pilots (AMTRONIC EEx ia).
-- Remove the supporting plate of the position detectors to access to the transmitter.
-- Two adjustments are available for the zero adjustment (4 mA) and the gain (20 mA).
-- Repeat the previous operations in reverse order.

Zero adjustment (4 mA) : ±5%


Gain adjustment (20 mA) : ± 10 % Zero Gain
Accuracy : ± 1 % of full scale

18
AMTROBOX EEx ia
AMTRONIC EEx ia

Declaration of Conformity

Hereby we, KSB S.A.S.


Zone industrielle Gagnaire Fonsèche
24490 LA ROCHE CHALAIS
Registered Office: 92635 -- Gennevilliers
France

declare that the automation boxes used in potentially explosive gaseous or dusty atmosphere and listed below com-
ply with the requirements of the Directives 94/9/EC, 89/336/EC (EMC) and 73/23/EC (Low Voltage).

Description of automation boxes: -- AMTRONIC R1172


-- AMTRONIC RTC1172
-- AMTROBOX R1172

As per harmonized european standards: Electrical equipment for potentially explosive atmosphere;
-- EN 50014 ; EN 50020

Electromagnetic compatibility;
-- EN 50081--2 ; EN 50082--2

Electrical equipment suitable for: Group II category 1 (zone 0)

Marking:
II 1 G - EEx ia IIC T6
LCIE 03 ATEX 6435X

Name and address of the authorizing and L.C.I.E.


monitoring notified body: 33, avenue Division Leclerc
92260 FONTENAY--AUX--ROSES
FRANCE

Number of notified body: 0081

Michel Delobel
Quality Assurance 04/05 -- rev.1
(This document was prepared electronically and is valid without signature)

19
AMTROBOX EEx ia
AMTRONIC EEx ia

Product features - to our Customers’ Benefit

Pointer under
transparent sight glass
The valve position is visible remotely

Adjustable cams

and may be amended without notice.


The detection position is
Position detection

This leaflet is not contractual


adjustable on the full stroke of
The position detection is
the valve
ensured by intrinsically safe
microswitches or inductive
proximity detectors

Integrated pneumatic valve


The control equipments are
Feed--back position protected by the housing against
0° to 90° by a 4--20 mA signal impacts, corrosin an dust
(option) (AMTRONIC EEx--ia)
The valve position is continuously
conveyed by an angle sensor
associated with a transmitter
self--supplied by the 4--20 mA
current loop

09.02.06

Operating time adjustment


Anti hydraulic schocks system:
the operating time, on opening
852612/11--10

and on closing, can be adjusted


by reducing the air flow on the
exhaust (AMTRONIC EEx ia)