The detect 3000 Fire Control Panels

detection and analysis


Characteristics
The detect 3000 fire control panels have been developed to • detect 3400 and detect 3016 are modular micro-
cover a wide range of applications from small loop opera- processor controlled fire control panels
tions to networked systems. The powerful software and
• Third party certified to the latest European standard
configurable performance parameters provide a high level of
including EN 54, BDE0833 and VDS
system integration and customised functionality.
detect 3000 has achieved world-wide acceptance through • Connect up to 16 with loop3000 detection system devices
variation in housing and system, system design with a wide • detect 3400 the latest application of leading edge tech-
range of language options plus internationally accepted nology and system integration in fire detection systems
third party certification by VDS to the European EN54 part II with up to 32 redundant fire control panels
standard.
• Comprehensive range of options and accessories
The detect 3000 system offers overall wide ranging functio- • Various language kits for international operations
nality evolved from the latest technology to provide a reliable
state-of-the-art solution. • Each loop3000 has the capacity for 126 loop devices
System application and design is simplified by modular with a maximum loop length of 3.000 m
construction and a comprehensive range of options in- • A modular range of housings for various applications
cluding redundant processors, printers and pre-engineered
solutions such as control of extinguishing systems. • Interfaces for LAN (Local Area Networks) connections
or superior systems (ESPA 4.44)

detect 3016 • Loop and host system layer redundancy


• Extensive diagnostic and maintenance functions via
processing mode
• Auxiliary equipment interfaces including dialling devices,
key deposit boxes etc
• Simple system expansion
• Control and link time-switched operations via integrated
calendar and time controlled switch functions
• Graphic displays of the bus structure with the powerful
I-check software

• Extensive event memory for system diagnostics


• Interfaces for graphic display systems and remote
maintenance
• Extensive alarm management

Approved and third party certified to EN54 standards for:


Austria, Belgium, China, Czech Republic, Germany, Great Britain,
Hungary, Russia, Slovakia, Spain, Switzerland, Ukraine, etc.
detect 3004

The Group
www.detectomat.com
Typ detect 3004 Typ detect 3016
Name Fire Control Panel Name Fire Control Panel
Brief description A modular microprocessor based fire control panel for use Brief description A modular microprocessor based fire control panel for use
with the loop3000 detection system. Third party certified with the loop3000 detection system. Third party certified
to the European standards – DIN EN 54, VDE0833 and VDS to the European standards – DIN EN 54, VDE0833 and VDS
Specification summary Specification summary
• Operation and display panel certified to DIN EN54 part 2 • Operation and display panel certified to DIN EN54 part 2
• Four row alpha-numeric back illuminated display • Four row alpha-numeric back illuminated display
• Two slots for loop cards (max. 4 loops / 16 fire detection zones) • Up to eight slots for loop cards
• Slot for fire brigade and networking interface • Maximum 2.016 loop devices in 16 loops
• 128 detector zones user-programmable • Slot for networking interface
• Up to 4 x 126 loop devices • Integrated fire brigade interface
• Up to 16 conventional fire zone inputs • 192 fire detection zones user-programmable
• Maximum loop cable length 3.000 m per loop (Screened TP - 2 x 0,8 mm) • Up to 16 x 126 loop devices
• Short circuit and broken wire proof loop operation • Up to 64 conventional fire zone inputs
• Fire brigade interface for key deposit box, fire brigade control panel • Maximum loop cable length 3.000 m per loop (Screened TP - 2 x 0,8 mm)
• Three relays with potential-free contacts (250V / 5A) • Short circuit and broken wire proof loop operation
• Nine open collector outputs (30V / 90mA) • Three relays with potential-free contacts (250V / 5 A)
• Conventional monitored sounder circuit output 400 mA, expandable • Nine open collector outputs (30V / 90mA)
• 2 x RS 232 for PC, printer, modem or management systems • Conventional monitored sounder circuit output 400 mA, expandable
• Networking option via BitBus-Interface with up to 32 FCP’s or 63 other • 2 x RS 232 for PC, printer, modem or management systems
BitBus-devices including repeater panels • Networking option via BitBus-Interface with up to 32 FCP’s or 63 other BitBus-
• First In First Out Memory (FIFO) for the last 500 events devices including repeater panels
• Alarm zone indicators and integrated printer option • First In First Out Memory (FIFO) for the last 500 events
• Optional redundant host processor • Alarm zone indicators and integrated printer option
• Power Supply 72 W with monitored battery contacts • Optional redundant host processor
• Storage space for two batteries 12 V up to 26 Ah • Power supply with 192 W with monitored battery contact
• Also available in 19“ version • Storage space for two batteries 12 V / 45 Ah (65 Ah in 19” version)
• Also available in 19“ version

Mains voltage 230 V AC (-15 % / +10%) Mains voltage 230 V AC (-15 % / +10%)
Frequency 50 / 60 Hz Frequency 50 / 60 Hz
Operating voltage 21.0 to 29.2 V DC Operating voltage 21,0 to 29,2 V DC
Power supply performance 72 watts Power supply performance 192 watts
Emergency supply Max. 2 x 12 V / 26 Ah Emergency supply Max. 2 x 12 V / 45 Ah
Quiescent current 86 mA Quiescent current 86 mA
Operational current 146 mA Operational current 156 mA
Interfaces 2 x RS 232 / RS 422 (opt.) / 1 x Bitbus (opt.) Interfaces 2 x RS 232 / RS 422 (opt.) / 1 x Bitbus (opt.)
Display LCD 4 x 20 characters Display LCD 4 x 20 characters
Alarm zone indicator Max. 48 zones Alarm zone indicator Max. 192 zones
Conventional sounder circuit 24 V DC / 400 mA monitored Conventional sounder circuit 24 V DC / 400 mA monitored
Auxilary supply 24 V DC / 800 mA not monitored Auxilary supply 2 x 24 V DC / 800 mA not monitored
Potential-free relays 3 x 250 V / 5 A Potential-free relays 3 x 250 V / 5 A
OC-output 9 x 30 V DC / 90 mA OC-output 9 x 30 V DC / 90 mA
Ambient air temperature 28.4 ° F up to 104° Ambient air temperature 28.4 ° F up to 104°
Humidity Max. 95% Humidity Max. 95%
Protection class IP 30 Protection class IP 30
Colour housing RAL 7035 light-grey Colour housing RAL 7035 light-grey
Colour front film RAL 7046 tele-grey Colour front film RAL 7046 tele-grey
Material Steel plate Material Steel plate
Weight 12,50 kg Weight 30,00 kg
Height in mm 490 Height in mm 750
Width in mm 420 Width in mm 600
Depth in mm 210 Depth in mm 240
Standard DIN EN54 part 2 Standard DIN EN54 part 2
Third party certification VdS Ref G 203068 Third party certification VdS Ref G 203067

Your specialist supplier