Ek 1914 en
Ek 1914 en
Operating Manual | EN
 EK1914
Blindtext Blindtext Blindtext
 TwinSAFE Bus Coupler with 2 fail-safe inputs and 2 fail-safe outputs
Table of contents
1 Notes on the documentation.................................................................................................................... 5
    1.1       Disclaimer.......................................................................................................................................... 5
              1.1.1         Trademarks ........................................................................................................................ 5
              1.1.2         Patents ............................................................................................................................... 5
              1.1.3         Limitation of liability ............................................................................................................ 6
              1.1.4         Copyright............................................................................................................................ 6
    1.2       Version numbers ............................................................................................................................... 7
    1.3       Staff qualification ............................................................................................................................... 8
    1.4       Safety and instruction........................................................................................................................ 9
              1.4.1         Explanation of symbols ...................................................................................................... 9
    1.5       Beckhoff Support and Service......................................................................................................... 10
7 Installation .............................................................................................................................................. 25
    7.1       Safety instructions ........................................................................................................................... 25
    7.2       Transport / storage .......................................................................................................................... 25
    7.3       Mechanical installation .................................................................................................................... 25
              7.3.1         Control cabinet / terminal box .......................................................................................... 26
              7.3.2         Installation position and minimum distances.................................................................... 26
              7.3.3         Installation on mounting rails............................................................................................ 27
    7.4       Electrical installation........................................................................................................................ 29
              7.4.1         Connections within a Bus Terminal block ........................................................................ 29
              7.4.2         Overvoltage protection ..................................................................................................... 30
              7.4.3         HD housing wiring ............................................................................................................ 31
9 Diagnosis ................................................................................................................................................. 49
    9.1       Diagnosis LEDs............................................................................................................................... 49
              9.1.1         Diag1 (green) ................................................................................................................... 49
              9.1.2         Diag2 (red) ....................................................................................................................... 50
    9.2       Diagnosis objects ............................................................................................................................ 51
    9.3       Possible causes of diagnostic messages........................................................................................ 53
12 Decommissioning ................................................................................................................................... 56
    12.1 Disposal .......................................................................................................................................... 56
              12.1.1        Returning to the vendor.................................................................................................... 56
13 Appendix .................................................................................................................................................. 57
    13.1 Volatility ........................................................................................................................................... 57
    13.2 Focus of certificates ........................................................................................................................ 58
    13.3 Certificate ........................................................................................................................................ 59
1.1             Disclaimer
Beckhoff products are subject to continuous further development. We reserve the right to revise the
operating instructions at any time and without prior announcement. No claims for the modification of products
that have already been supplied may be made on the basis of the data, diagrams and descriptions in these
operating instructions.
In these operating instructions we define all permissible use cases whose properties and operating
conditions we can guarantee. The use cases we define are fully tested and certified. Use cases beyond this,
which are not described in these operating instructions, require the approval of Beckhoff Automation GmbH
& Co KG.
1.1.1           Trademarks
Beckhoff®, TwinCAT®, EtherCAT®, EtherCAT G®, EtherCAT G10®, EtherCAT P®, Safety over EtherCAT®,
TwinSAFE®, XFC®, XTS® and XPlanar® are registered and licensed trademarks of Beckhoff Automation
GmbH.
The use of other brand names or designations by third parties may lead to an infringement of the rights of
the owners of the corresponding designations.
1.1.2           Patents
The EtherCAT technology is protected by patent rights through the following registrations and patents with
corresponding applications and registrations in various other countries:
    • EP1590927
    • EP1789857
    • EP1456722
    • EP2137893
    • DE102015105702
1.1.4            Copyright
© Beckhoff Automation GmbH & Co. KG, Germany.
The distribution and reproduction of this document as well as the use and communication of its contents
without express authorization are prohibited.
Offenders will be held liable for the payment of damages. All rights reserved in the event of the grant of a
patent, utility model or design.
Currentness
Please check whether you are using the current and valid version of this document. The current version can
be downloaded from the Beckhoff homepage at http://www.beckhoff.de/twinsafe. In case of doubt, please
contact Technical Support (see Beckhoff Support and Service [} 10]).
The original documentation is written in German. All other languages are derived from the German original.
Product features
Only the product properties specified in the current operating instructions are valid. Further information given
on the product pages of the Beckhoff homepage, in emails or in other publications is not authoritative.
The trained specialist personnel must ensure that the applications and use of the described product meet all
safety requirements. This includes all applicable and valid laws, regulations, provisions and standards.
Trained specialists
Trained specialists have extensive technical knowledge from studies, apprenticeships or technical training.
Understanding of control technology and automation is available. Trained specialists can:
    • Independently identify, avoid and eliminate sources of hazard.
    • Apply relevant standards and directives.
    • Implement specifications from accident prevention regulations.
    • Evaluate, prepare and set up the workplaces.
    • Evaluate, optimize and execute work independently.
Observe the warnings in the chapters so that you can handle and work with the product as intended and
safely.
1.4.1.1           Pictograms
In order to make it easier for you to find text passages, pictograms and signal words are used in warning
notices:
DANGER
WARNING
CAUTION
                                                       NOTE
Notes
Notes are used for important information on the product. The possible consequences of failure to observe
these include:
 • Malfunctions of the product
 • Damage to the product
 • Damage to the environment
          Information
          This sign indicates information, tips and notes for dealing with the product or the software.
Beckhoff Support offers technical advice on the use of individual Beckhoff products and system planning.
The employees support you in the programming and commissioning of sophisticated automation systems.
Hotline:               +49 5246/963-157
E-mail:                support@beckhoff.com
Web:                   www.beckhoff.com/support
Training
Training in Germany takes place in our training center at the Beckhoff headquarters in Verl, at subsidiaries
or, by arrangement, at the customer's premises.
Hotline:               +49 5246/963-5000
E-mail:                training@beckhoff.com
Web:                   www.beckhoff.com/training
Service
The Beckhoff Service Center supports you with after-sales services such as on-site service, repair service or
spare parts service.
Hotline:               +49 5246/963-460
E-mail:                service@beckhoff.com
Web:                   www.beckhoff.com/service
Download area
In the download area you can obtain product information, software updates, the TwinCAT automation
software, documentation and much more.
Web:                   www.beckhoff.com/download
Headquarters
For the addresses of our worldwide locations, please visit our website at Global Presence.
Ensure traceability
Ensure the traceability of the TwinSAFE component via the serial number.
Only use the TwinSAFE component in machines that comply with the Machinery Directive. This is how you
ensure safe operation.
Before commissioning, wiring faults to the sensors must be excluded. Before commissioning, carry out a
commissioning test. After a successful commissioning test, you can use the TwinSAFE component for the
intended safety-related task.
In case of wiring errors, the safety function of the product is at risk. Depending on the machine, death and
danger to life, serious bodily injury and damage to the machine may result.
Use a SELV/PELV power supply unit with an output-side voltage limit of Umax = 36 VDC to supply the
TwinSAFE component with 24 VDC.
Failure to observe this will endanger the safety function of the product. Depending on the machine, death
and danger to life, serious physical injury and damage to the machine may result.
2.1.2 In operation
Do not operate the following devices in the vicinity of the TwinSAFE component: for example, radio
telephones, radios, transmitters or high-frequency systems.
TwinSAFE components comply with the requirements of the applicable electromagnetic compatibility
standards with regard to interference emission and immunity. If you exceed the limits for emitted interference
specified in the standards, the function of the TwinSAFE component may be impaired.
Check all safety-relevant equipment for functionality before working on the TwinSAFE component. Secure
the working environment. Secure the machine or plant against being inadvertently started up. Observe the
chapter Decommissioning [} 56].
The sensors and actuators are connected with the terminals via the screwless (spring-loaded) connection
system.
Fig. 1: Slot and key system and screwless (spring-loaded) connection system
3.3              E-bus
The E-bus is the data path within a terminal strip. The E-bus is led through from the Bus Coupler through all
the terminals via six contacts on the terminals' side walls.
The basic rule for a safety system such as TwinSAFE is that failure of a part, a system component or the
overall system must never lead to a dangerous condition. The safe state is always the switched off and
wattless state.
                                                   CAUTION
Safe state
For all TwinSAFE components the safe state is always the switched-off, wattless state.
5 Product description
The EK1914 is an EtherCAT Bus Coupler with 4 standard inputs, 4 standard outputs, and 2 fail-safe inputs
and 2 fail-safe outputs.
The EK1914 fulfils the requirements of DIN EN ISO 13849-1:2008 (Cat 4, PL e).
The TwinSAFE Bus Coupler has the usual design of an EtherCAT coupler.
The EK1914 TwinSAFE Bus Coupler expands the application area of the Beckhoff Bus Terminal system by
functions that enable it to be used in the field of machine safety as well. The TwinSAFE Bus Coupler is
designed for machine safety functions and directly associated industrial automation tasks. They are therefore
only approved for applications with a defined fail-safe state. This safe state is the wattless state. Fail-safety
according to the relevant standards is required.
                                                     NOTE
Test pulses
When selecting actuators, please ensure that the EK1914 test pulses do not lead to actuator switching or a
diagnostic message from the EK1914.
This module is suitable for operation in an EtherCAT network and can be extended by EtherCAT Terminals
of the type ELxxxx.
                                                    CAUTION
Follow the machinery directive
The TwinSAFE Bus Coupler may only be used in machines in accordance with the machinery directive.
                                                    CAUTION
Ensure traceability
The buyer has to ensure the traceability of the device via the serial number.
Data Comment
Data Comment
Lifetime                              20 a
Prooftest-Intervall                   /                              Special proof tests during the entire
                                                                     service life of the TwinSAFE Bus
                                                                     Coupler are not required.
PFHD                                  2,64E-09
%SIL3                                 2,64%
PFD                                   3,92E-05
%SIL3                                 3,92%
MTTFD                                 High
DC                                    High
SFF                                   >99 %
Performance Level                     e
Category                              4
HFT                                   1
Element classification                Typ B                          According to EN 61508-2:2010
                                                                     chapter 7.4.4.1.2 and 7.4.4.1.3.
The TwinSAFE Bus Coupler can be used for safety-related applications within the meaning of EN ISO
13849-1 up to PL e (Cat4).
To calculate or estimate the MTTFd value out of the PFHD value please refer to the Application Guide
TwinSAFE or to the ISO 13849-1:2015 table K.1.
                                                   WARNING
Do not use TwinSAFE components under the following operating conditions:
 • under the influence of ionizing radiation (which exceeds the level of natural ambient radiation)
 • in a corrosive environment
 • in an environment that leads to inadmissible contamination of the TwinSAFE component.
Umweltbedingungen
• Permissible ambient temperature        0°C to +55°C
  (operation) up to HW05
• Permissible ambient temperature        -25°C to +55°C
  (operation) from HW06
• Permissible ambient temperature        -25°C to +70°C
  (transport/storage)
• Permissible air humidity               5% to 95%, non-condensing
• Permissible air pressure (operation/   750 hPa to 1100 hPa       This corresponds to a height of approx.
  storage/transport)                                               -690 m to 2450 m over sea level
                                                                   assuming an international standard
                                                                   atmosphere.
• Climate category                       3K3                       According to EN 60721-3-3:1995/
                                                                   A2:1997.
                                                                       The deviation from 3K3 is possible
                                                                       only with optimal environmental
                                                                       conditions and also applies only to the
                                                                       technical data which are specified
                                                                       differently in this documentation.
• Pollution degree                       2                             comply with the chapter Maintenance
                                                                       and cleaning [} 55].
• EMC immunity/emission                  According to EN 61000-6-2 /
                                         EN 61000-6-4
• Vibration/shock resistance             According to EN 60068-2-6 /
                                         EN 60068-2-27
• Shocks                                 15 g with pulse duration 11
                                         ms in all three axes
• Protection class                       IP20
• Permitted operating environment        In the control cabinet or
                                         terminal box, with minimum
                                         protection class IP54
                                         according to IEC 60529
• Correct installation position          See chapter Installation
                                         position and minimum
                                         distances [} 26].
5.6 Dimensions
Fig. 5: Dimensions
Width: 44 mm
Height: 100 mm
Depth: 68 mm
Ensure that the TwinSAFE component is not damaged during transport and storage. Use the manufacturer's
original packaging.
You have the option of storing the TwinSAFE component for a short or longer period. Observe the conditions
from chapter Environmental conditions [} 22].
7 Installation
                                                CAUTION
Note the specified environmental conditions
Ensure that the digital TwinSAFE components are only transported and stored under the specified ambient
conditions. The ambient conditions can be found in the technical data.
Incorrect transport or storage can damage the TwinSAFE components. Never use damaged TwinSAFE
components. Dispose of the affected product.
Mount the mounting rail horizontally for the specified installation position. The connection surfaces of the EL
terminals or KL terminals must face forwards. This can be seen from the illustration.
The components are ventilated from bottom to top, which enables optimum cooling of the electronics by
convection ventilation. The direction specification "down" corresponds to the direction of the positive
acceleration due to gravity.
                                                      NOTE
Observe minimum distances
Maintain the distances to neighboring devices and control cabinet walls specified in the figure. This is the
only way to ensure optimum convection cooling.
If sufficient convection cooling is not ensured, the devices may overheat and be damaged.
Assembly
The EtherCAT Couplers and TwinSAFE Terminals are snapped onto standard 35 mm mounting rails by
applying slight pressure. The mounting rails are top-hat rails according to EN 60715. Mount the components
in the following sequence:
 1. Plug the EtherCAT coupler onto the mounting rail.
 2. Plug the TwinSAFE terminals together with tongue and groove.
 3. ush the TwinSAFE terminals against the mounting rail until the latch audibly engages on the mounting
    rail.
Disassembly
Each TwinSAFE terminal is secured on the mounting rail by a latch. For disassembly, the locking of the
TwinSAFE terminals must be released as follows:
 4. Pull the TwinSAFE terminal down approx. 1 cm from the mounting rail by the orange-colored tab. The
    mounting rail lock of the TwinSAFE terminal is released automatically.
 5. Grip the unlocked TwinSAFE terminal simultaneously at the top and bottom of the housing surfaces with
    thumb and index finger.
 6. Pull the TwinSAFE terminal out of the Bus Terminal block with little force.
The 6 spring contacts of the E-bus take over the transmission of the data and the supply of the bus terminal
electronics.
                                                    NOTE
Observe E-bus current
Observe the maximum current that your EtherCAT coupler can supply for E-bus supply! Use the EL9410
power supply terminal if the current consumption of your TwinSAFE terminals exceeds the maximum
current that your EtherCAT coupler can supply for E-bus supply.
Power contacts
The power contacts transmit the supply for the field electronics and thus represent a supply rail within the
Bus Terminal block. The power contacts are supplied via terminals on the EtherCAT coupler.
PE power contact
The power contact labelled PE can be used as a protective earth. For safety reasons this contact mates first
when plugging together, and can ground short-circuit currents of up to 125 A.
                                                  DANGER
Serious risk of injury
Never use the PE power contact for other potentials.
                                                  CAUTION
Disconnect PE supply line for insulation test
For insulation testing disconnect the PE feed line at the EtherCAT coupler or the power terminal. In order to
decouple further supply points for the test, you can unlock these supply terminals and pull them at least 10
mm out of the interconnection of the other terminals.
Note that for EMC reasons the PE contacts are capacitively connected to the mounting rail. This can lead to
incorrect results during insulation testing and also to damage to the TwinSAFE component.
Up to 16 terminal points enable the connection of solid or finely stranded wires to the EtherCAT Terminal.
The terminal points are spring-loaded.
Solid and stranded wire conductors with ferrules can be inserted directly into the terminal point. This
eliminates steps 1 and 3 in the above illustration. For all other conductor types, the terminal point must be
opened with a screwdriver to establish the connection.
The ELx8xx / KLx8xx series Bus Terminals, like the EK1914 with 16 connection points, are characterized by
a particularly compact design, since the packing density on 12 mm is twice that of standard Bus Terminals.
Solid conductors equipped with a wire end ferrule can be plugged directly into the spring terminal point
without tools.
                                                  NOTE
Test pulses of the safe outputs
When selecting the actuators, ensure that the test pulses of the EK1914 do not lead to switching of the
actuator or a diagnostic message of the EK1914.
When connecting a single switching contact via its own continuous cabling (or via a non-metallic sheathed
cable), the maximum permitted cable length is 100 m.
                                                    NOTE
Route the signal cable separately
Route signal cable separately from potential sources of interference. Possible sources of interference are,
for example, motor supply cables or power cables with 230 VAC. Keep the distance between the cables as
large as possible.
Interference from cables routed in parallel can influence the signal shape of the test pulses and thus cause
diagnostic messages. Possible diagnostic messages are, for example, sensor errors.
The following illustrations show correct and incorrect signal routing. Observe the illustration legend.
Illustration legend
D                          Distance between cable ducts
Blue arrows                Signature lines
Red arrows                 Potential sources of interference
A common signal routing with other clocked signals in a bus also reduces the maximum extension. The
reason for this is that crosstalk of the signals may occur on a long line length and diagnostic messages
appear. If the connection via a bus line is unavoidable, the test pulses can be switched off (Sensor test
parameter). However, this then leads to a reduction in the diagnostic coverage when calculating the
performance level.
The use of contact points, connectors or additional switching contacts in the cabling also reduces the
maximum expansion.
The typical length of a test pulse (switching from 24 V to 0 V and back to 24 V) is approximately 380 µs and
occurs about 400 times per second.
In the step mat mode (parameter: "Short cut is no module fault"), test pulses with a typical length of 750 µs
are generated in addition to the typical test pulse lengths of 380 µs.
When connecting a single actuator via its own continuous cabling (or via a sheathed cable), the maximum
permitted cable length is 100 m.
                                                    NOTE
Route the signal cable separately
Route signal cable separately from potential sources of interference. Possible sources of interference are,
for example, motor supply cables or power cables with 230 VAC. Keep the distance between the cables as
large as possible.
Interference from cables routed in parallel can influence the signal shape of the test pulses and thus cause
diagnostic messages. Possible diagnostic messages are, for example, sensor errors.
The following illustrations show correct and incorrect signal routing. Observe the illustration legend.
Illustration legend
D                          Distance between cable ducts
Blue arrows                Signature lines
Red arrows                 Potential sources of interference
The common routing of signals together with other clocked signals in a common cable also reduces the
maximum propagation since crosstalk of the signals can occur over long cable lengths and cause diagnostic
messages. If connection via a common cable cannot be avoided, the test pulses can be switched off
(parameter: “Testing of outputs active”). However, this then leads to a reduction in the degree of diagnostic
cover when calculating the performance level.
The use of contact points or plug connectors in the cabling similarly reduces the maximum expansion.
The typical length of a test pulse (switching from 24 V to 0 V and back to 24 V) is 300 µs to 800 µs but can
also be longer in individual cases. Testing usually takes place 3 to 6 times per second.
The following diagram shows a typical test pulse curve for the two outputs of an EK1914. The parameter
Testing of outputs active is enabled.
Definition       Description
RTSensor         Reaction time of the sensor until the signal is provided at the interface.
                 Typically supplied by the sensor manufacturer.
RTInput          Reaction time of the safe input, such as EL1904 or EP1908. This time can
                 be found in the technical data. In the case of the EL1904 it is 4 ms.
RTComm           Reaction time of the communication This is typically 3x the EtherCAT cycle
                 time, because new data can only be sent in a new Safety-over-EtherCAT
                 telegram. These times depend directly on the higher-level standard
                 controller (cycle time of the PLC/NC).
RTLogic          Reaction time of the logic terminal. This is the cycle time of the logic
                 terminal and typically ranges from 500 µs to 10 ms for the EL6900,
                 depending on the size of the safety project. The actual cycle time can be
                 read from the terminal.
RTOutput         Reaction time of the output terminal. This typically lies within the range of 2
                 to 3 ms.
RTActor          Reaction time of the actuator. This information is typically supplied by the
                 actuator manufacturer
WDComm           Watchdog time of the communication
ReactionTimetyp = 5 ms + 4 ms + 3 * 1 ms + 10 ms + 3 * 1 ms + 3 ms + 20 ms = 48 ms
         This assumes that a signal change occurs at the sensor and is transmitted to the input. A
         communication error occurs at precisely the moment when the signal is to be transferred to the
         communication interface. This is detected by the logic following the watchdog time of the
         communication link.
         This information should then be transferred to the output, but a further communication error occurs
         here. This error is detected at the output following a safety watchdog time out and leads to a switch-
         off.
This results in the following equation for the worst-case reaction time:
ReactionTimemax = 15 ms + 15 ms + 20 ms = 50 ms
The tests were carried out as function tests only. The information provided in the respective manufacturer
documentation remains valid.
Sensors
Actuators
Manufacturer      Type                          Comment
Beckhoff          AX5801                        TwinSAFE Drive option card: safe restart lock
Siemens           SIRIUS Serie S00              Contactor
                  3RT1016-1BB42
                                                    NOTE
Recommended protective circuits
For actuators, we recommend R/C or diode protective circuits. Varistor protective circuits should not be
used.
The TwinSAFE address of the coupler must be set using the three rotary switches on the side of the EK1914
TwinSAFE Bus Coupler. TwinSAFE addresses between 1 and 4095 are available.
                                               WARNING
Unique TwinSAFE address
Each set TwinSAFE address may only occur once within a network! Address 0 is not a valid address.
The parameter settings of the EK1914 can also be set under the respective TwinSAFE connection on the
Connection and Safe Parameter tabs.
Parameter overview
                                                  CAUTION
Sensors with self-testing outputs
Only sensors with self-testing outputs whose sensor self-test does not exceed the duration of 350 µs may
be connected to the EK1914 (see figure)!
Parameter
To connect these sensors please set the following parameters for the EK1914 in the TwinCAT System
Manager:
   • Connect the two sensor signals to channels 1 and 2 and activate the entry asynchronous repetition
     OSSD or any pulse repetition for both the inputs used under the parameter Logic for channel 1 and 2.
     The difference between these settings is that with any pulse repetition simultaneous tests of the OSSD
     signals up to 350 µs are allowed.
   • Switch the sensor test of the EK1914 to false for both the inputs used
Parameter
To connect these safety mats please set the following parameters for the EK1914 in the TwinCAT System
Manager:
     • Connect the two sensor signals to channels 1 and 2 and activate the entry short cut channel x/y is no
       module fault for both the inputs used under the parameter Logic for channel 1 and 2.
     • Switch the sensor test of the EK1914 to true for both the inputs used
9 Diagnosis
Diag2 lights up
The Diag 2 LED lights up red when the bus coupler has detected an external power supply or a cross-circuit.
If the error has been eliminated, the LED goes out.
Diag2 flashes
In case of an error, the Diag 2 LED displays a blink code that describes the error in more detail. The blink
codes are structured as follows:
The errors indicated by the following flashing codes are reversible. After rectification of the error cause, the
Bus Coupler can be put back into operation with a restart.
If another flashing code is displayed, there is an internal coupler error that has stopped the Bus Coupler. In
this case the Bus Coupler must be checked by Automation GmbH & Co. KG.
                                                     NOTE
Note flashing codes; return the Bus Coupler
Note the flashing code displayed and include this information with the Bus Coupler when you return it.
                                                   CAUTION
Do not change CoE objects
Do not make any modifications to the CoE objects of the TwinSAFE Bus Coupler! Any modifications (e.g.
using the TwinCAT system manager) of the CoE objects would permanently set the Bus Coupler to the
Fail-Stop state.
                                                   NOTE
Differing diagnostic messages possible
Due to the variable order or execution of the test series, diagnostic messages differing from those given in
the table above are possible.
10              Service life
The TwinSAFE Bus Couplers are designed for a service life of 20 years. Due to the high diagnostic coverage
within the lifecycle no special proof tests are required.
The TwinSAFE Bus Couplers bear a date code, which is composed as follows:
Date Code: CW YY SW HW
12 Decommissioning
12.1             Disposal
                                                    NOTE
Correct disposal
Observe the applicable national laws and guidelines for disposal.
Incorrect disposal may result in environmental damage.
Depending on your application and the products used, make sure that the respective components are
disposed of properly:
Hand over cast iron and metal parts to scrap metal recycling.
Dispose of packaging materials made of cardboard, wood or Styrofoam in accordance with regulations.
You can recycle parts made of plastic and hard plastic via the waste management center or reuse them in
accordance with the component regulations and markings.
Dispose of oils and lubricants in separate containers. Hand over containers to the waste oil collection point.
Batteries and accumulators may also be marked with the crossed-out wheeled garbage can symbol. You
must separate these components from waste. You are legally obliged to return used batteries and
accumulators within the EU. Outside the validity of the EU Directive 2006/66/EC, observe the respective
regulations.
Send the used devices with the note "For disposal" to:
In addition, you have the option to contact a local certified specialist company for the disposal of used
electrical and electronic appliances. Dispose of the old components in accordance with the regulations
applicable in your country.
13 Appendix
13.1             Volatility
If there are requirements concerning the volatility of products in your application, for example of the U.S.
Department of Defense or similar authorities or security organizations, the following process applies:
The product has both volatile and non-volatile components. Volatile components lose their data immediately
after removing power. Non-volatile components keep the data even after loss of power.
If there is customer specific data saved on the product, it cannot be ensured that this data might not be
restored through for example forensic measures, even after the data is deleted through the provided tool
chain. If this data is confidential, the scrapping of the product after usage is recommended to protect this
data.
The current certificates of all TwinSAFE components with the underlying standards and directives can be
found at https://www.beckhoff.com/en-en/support/download-finder/certificates-approvals/.
If the document refers only to the first four figures of a product (ELxxxx), the certificate is valid for all
available variants of the component (ELxxxx-abcd). This is applicable for all components like EtherCAT
Terminals, EtherCAT Boxes, EtherCAT plug-in modules and Bus Terminals.
If you regard the example EL1918 in the picture, the certificate is valid for both the EL1918 and the available
variant EL1918-2200.
13.3 Certificate
List of figures
Fig. 1    Slot and key system and screwless (spring-loaded) connection system .....................................                                        12
Fig. 2    Bus Coupler (EtherCAT) ..............................................................................................................            13
Fig. 3    Overview of EtherCAT Terminals.................................................................................................                  14
Fig. 4    EK1914 overview .........................................................................................................................        17
Fig. 5    Dimensions ..................................................................................................................................    23
Fig. 6    Installation position and minimum distances................................................................................                      26
Fig. 7    Installation on the mounting rail ...................................................................................................            27
Fig. 8    Removal from mounting rail .........................................................................................................             28
Fig. 9    PE power contact .........................................................................................................................       30
Fig. 10   Connection of a cable to a terminal point.....................................................................................                   31
Fig. 11   HD terminals ................................................................................................................................    32
Fig. 12   Pin assignment of the EK1914.....................................................................................................                33
Fig. 13   Cable length input ........................................................................................................................      34
Fig. 14   Route signal lines correctly ..........................................................................................................          34
Fig. 15   Route signal lines incorrectly .......................................................................................................           35
Fig. 16   Cable length output ......................................................................................................................       36
Fig. 17   Route signal lines correctly ..........................................................................................................          37
Fig. 18   Route signal lines incorrectly .......................................................................................................           37
Fig. 19   Test pulses...................................................................................................................................   38
Fig. 20   Insert bus coupler.........................................................................................................................      42
Fig. 21   Address switches .........................................................................................................................       43
Fig. 22   Parameters of the EK1914...........................................................................................................              44
Fig. 23   Connection settings......................................................................................................................        45
Fig. 24   Parameter settings .......................................................................................................................       45
Fig. 25   Clock outputs ...............................................................................................................................    47
Fig. 26   Diagnosis LEDs............................................................................................................................       49
Fig. 27   Start Error code 1 Error code 2 ....................................................................................................             50
Fig. 28   Date Code of EK1914 ..................................................................................................................           54
Fig. 29   EK1914 EC Declaration of Conformity.........................................................................................                     59