Ä To Testing Heater At KYUNGSHIN CAMBODIA CORP

TEMPERATURE
N0 FROM NAME OF DB BOX DB BOX IMAGE
(℃)

AUTO
1 DB-13 53.8℃
(lamp)

AUTO
2 DB-01 44.3℃
(Power)

SEMI
3 DB-02 44.℃
(Power)

MATERIL
4 DB-18 40.7℃
(Lamp)

MATERIL
5 DB-06 37.7℃
(Power)

MAN ASS'Y
6 DB-16 48.0℃
(Lamp)

MAN ASS'Y
7 DB-04 43.0℃
(Power)

8 MTS of UPS by pass UPS room 49.5℃

2nd OFFICE
9 DB-21 35.0℃
(Lamp)

2nd OFFICE
10 DB-12 68.4℃
(Power)
11 TRANSFORMER 1stOFFICE (Power) DB-11 46.6℃

1stOFFICE
12 DB-20 35.2℃
(Lamp)

EXTN ASS'Y
13 DB-14 42.2℃
(Lamp)

EXTN ASS'Y
14 DB-05 36.9℃
(Power)

A/BAG
15 DB-03 37.2℃
(Power)

A/BAG
16 DB-15 48.8℃
(Lamp)

NEW DOOR LINE


17 DB-34 72.7℃
(Power)

NEW DOOR LINE


18 DB-35 40.8℃
(Lamp))

NEW DOOR LINE


19 DB-36 56.1℃
(Power)

NEW DOOR LINE


20 DB-37 40.2℃
(Lamp))

WARE HOUSE SHPPING


21 DB-17 60.0℃
(Lamp)
WARE HOUSE SHPPING
22 DB07 43.3℃
(Power)
Standard
60℃¯

RESULTS

Normal

Normal

Normal

Normal

Normal

Normal

Normal

Normal

Normal

Hight
Temperature
Normal

Normal

Normal

Normal

Normal

Normal

Hight
Temperature

Normal

Normal

Normal

Hight
Temperature
Normal
Ä To Testing Heater Cable After Upgrad Cable At KYUNGSHIN CAMBODIA CORP

TEMPERATURE
N0 FROM NAME OF DB BOX DB BOX IMAGE
(℃)

AUTO
1 DB-13 53.8℃
(lamp)

AUTO
2 DB-01 44.3℃
(Power)

SEMI
3 DB-02 44.℃
(Power)

MATERIL
4 DB-18 40.7℃
(Lamp)

MATERIL
5 DB-06 37.7℃
(Power)

MAN ASS'Y
6 DB-16 48.0℃
(Lamp)

MAN ASS'Y
7 DB-04 43.0℃
(Power)

8 MTS of UPS by pass UPS room 49.5℃

9 2nd OFFICE DB-21 35.0℃


(Lamp)

2nd OFFICE
10 DB-12 36.3℃
(Power)
11 TRANSFORMER 1stOFFICE (Power) DB-11 46.6℃

1stOFFICE
12 DB-20 35.2℃
(Lamp)

EXTN ASS'Y
13 DB-14 42.2℃
(Lamp)

EXTN ASS'Y
14 DB-05 36.9℃
(Power)

A/BAG
15 DB-03 37.2℃
(Power)

A/BAG
16 DB-15 48.8℃
(Lamp)

NEW DOOR LINE


17 DB-34 33.8℃
(Power)

NEW DOOR LINE


18 DB-35 40.8℃
(Lamp))

NEW DOOR LINE


19 DB-36 56.1℃
(Power)

NEW DOOR LINE


20 DB-37 40.2℃
(Lamp))

WARE HOUSE SHPPING


21 DB-17 48.4℃
(Lamp)
WARE HOUSE SHPPING
22 DB07 43.3℃
(Power)
DIA CORP
Standard
60℃¯

RESULTS

Normal

Normal

Normal

Normal

Normal

Normal

Normal

Normal

Normal

Normal
Normal

Normal

Normal

Normal

Normal

Normal

Normal

Normal

Normal

Normal

Normal
Normal

You might also like