Electronic Timers
On Delay • On Pulse • Symmetrical Recycler XM
DESCRIPTION OPERATION
Multifunction timer with 4 functions and 4 time ranges. The function The function is selected via the rotary switch on the timer front. The
and the time range are selectable via 2 front mounted rotary switch may only be operated, when the supply voltage is discon-
switches. nected.
Time ranges: 0.6-6sec, 6-60sec, 0.6-6min, 6-60min. The time is
adjustable on the timer front. On delay.
The timer can directly be connected to the supply voltage in the The timing period starts when supply voltage is connected. When the
range of 10.5-265V AC/DC. preset time has elapsed, the relay is energized.
Single or double relay output with LED indication of energized relay. The relay is de-energized when the supply voltage is disconnected.
Intermittent flashing of LED indicating timing period (over 6 sec.). If the supply voltage is disconnected before the preset time has
Versions available for DIN rail or 11-pole plug-in mounting. elapsed, the timer resets.
Supply
T T
LED
On pulse.
When supply voltage is connected, the relay is energized and the
timing period starts. When the preset time has elapsed, the relay is de-
energized.
If the supply voltage is disconnected before the preset time has
elapsed, the relay will be de-energized and the timer resets.
Supply
T T
LED
Symmetrical recycler with pause or pulse start.
Depending on the setting of the function switch the timer starts with
e.g a pause period, when supply voltage is connected. When the
pause period has elapsed, the relay energizes. The relay remains
energized during the pulse period. The sequence is repeated until the
supply voltage is disconnected.
The duration of the pause and pulse periods is equal.
Supply
VERSIONS/ORDERING CODES
T T T T
Type: XM- S 1 LED
On delay.
On pulse. XM
Symmetrical recycler.
Mounting:
11-pole plug-in. S
DIN rail. D
Output relay:
SPDT. 1
DPDT. 2
47.98
Export: United Kingdom: Germany:
Tel: +45 46 74 00 00 Tel: +44 020 8546 4283 Tel: +49 208 46954-0
Fax: +45 46 75 73 36 Fax: +44 020 8547 3628 Fax: +49 208 46954-50
E-mail: bc@brodersencontrols.com E-mail: bcs@brodersen.co.uk E-mail: ba@brodersen.de
4
XM_00.p65 2 26-10-01, 14:25
Electronic Timers
On Delay • On Pulse • Symmetrical Recycler XM
INTRO...
TECHNICAL DATA WIRING DIAGRAMS
Time ranges: 0.6-6sec, 6-60sec, 0.6-6min. 6-60min. Supply voltage above 50V.
Full linearity between the ranges is provided i.e. an adjustment made The installation (all terminals) must be carried out according to the
to a specific time in seconds will give the same time in minutes just safety regulations! The control input and the supply input must be
XM
by operating the range switch. connected to the same circuit (phase and main switch). The output
relay may only be used in circuits made according to the safety
Timer accuracy: regulations.
Repeating accuracy: ± 0.5% at constant conditions.
Setting accuracy: ± 10%. Supply voltage below 50V.
XW
Temperature drift: Max. 0.15% per °C. The output relay may NOT be used for voltages above 50V unless
the entire supply circuit is made according to the safety regulations.
Reset time: Max. 100msec.
Output relay: SPDT or DPDT. 1)
XMW
Load (cosϕ=1): D1/S1: Max. 8A/240V AC 2) A1 15 26 28
5
6
7
Min. 10mA/24VDC 4 8
D2/S2: Max. 5A/240V AC 2) 3 9
Min. 100mA/24VDC 16 18 25 A2
2 10
1 11
Contact material: D1/S1: AgNi 0,15
XT
D2/S2: AgCdO Supply Supply
Frequency: Max. 1000 operations per hour at max. load. +/L -/N +/L -/N
Mechanical life time: Min. 10 x 10 6 operations.
Electrical life time: Min. 100,000 operations at max. load.
Operate time: Max. 50msec.
XOT
Release time: Max. 20msec. MECHANICAL DIMENSIONS
Mounting:
S1/S2: 11-pole plug-in. 10 47 10 27
D1/D2: Directly on DIN rail TS35 (EN50022).
SXM
Terminals: Max. conductor size 4 mm2.
(D1/D2 only)
Screw type terminals with self-lifting clamps shrouded in accord-
75
45
ance to VDE0106 (finger and back of hand protection).
SXT
Supply voltage: 10.5-265V AC/DC
Mains frequency: 40-440Hz.
13 53.5 6 53.5 6
TXM
Consumption: 0.5-3VA.
Cable lengths:
Supply voltage: Max. 50 m.
TXW
Protection:
S1/S2: IP40. OUTPUT LOAD DIAGRAMS, X & TX TIMERS.
D1/D2: IP20.
EMC: Conforming to EN 50081-1/EN 50082-2.
TXT
Fig. 1 Fig. 2
Isolation:
Supply to relay Reduction factor
for inductive load
contacts: 2kV AC according to EN 60950 class I. 1,0 10
DC load characteristics
Reduction factor
I [A] DC
0,9 5
XI
Ambient temperature:-20 to +55°C. 0,8
2
0,7
1
Housing: Black Noryl SE-1. 0,6
0,5
0,5
Weight: Typically 80 g. 0,2
XB
0,4
0,2 0,4 0,6 0,8 1,0 0,1
cosϕ 0 50 100 150 200 250 300
U [V] DC
X types SPDT.
X types DPDT
&
TX types SPDT and DPDT
XWI
NOTES/REMARKS
1) Double output relay available in S2/D2 versions.
XIW
2) When inductive or DC loads are switched the load capacity of the
output relay is reduced, see the output load diagrams on fig. 1 and
2. When inductive loads are switched, it is recommended to use a
RC-network, see accessories on page 130, to protect the relay
contacts.
XIW
XF 47.98
Export: United Kingdom: Germany:
Tel: +45 46 74 00 00 Tel: +44 020 8546 4283 Tel: +49 208 46954-0
Fax: +45 46 75 73 36 Fax: +44 020 8547 3628 Fax: +49 208 46954-50
E-mail: bc@brodersencontrols.com E-mail: bcs@brodersen.co.uk E-mail: ba@brodersen.de
5
XM_00.p65 3 26-10-01, 14:25