Omron - Motor Timer H2C

The H2C Motor Timer is a DIN-sized device designed for switching time specifications ranging from 6 seconds to 30 hours, featuring simple operation and multiple time settings. It is certified for UL and CSA safety standards and conforms to EN 61812-1 and CE Marking. Various models and accessories are available, with specific operational and resetting systems to suit different applications.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
49 views12 pages

Omron - Motor Timer H2C

The H2C Motor Timer is a DIN-sized device designed for switching time specifications ranging from 6 seconds to 30 hours, featuring simple operation and multiple time settings. It is certified for UL and CSA safety standards and conforms to EN 61812-1 and CE Marking. Various models and accessories are available, with specific operational and resetting systems to suit different applications.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 12

Motor Timer

H2C CSM_H2C_DS_E_2_2

DIN-sized 48 x 48 Motor Timer with Simple


Operation for Switching Time Specifications
• Three Motor Timers cover the wide time range of 6 s to 30 h with
easy operation from the operation panel.
• Five time specifications for each model with linked time display.
• DIN-standard size of 48 x 48 mm.
• Easily check operation with neon lamp.
• Models with sockets and models with top wiring are also avail-
able.
• Certified for UL and CSA safety standards.
• Conforms to EN 61812-1 (except models that end with “-F”) and
CE Marking.

Model Number Structure


■ Model Number Legend
H2C-@ @-@
1 2 3
1. External Connection/Attachment 2. Operation/Resetting System
None: 11-pin socket None: Time-limit operation/self-resetting
8: 8-pin socket R: Time-limit operation/electric resetting
F: Front screw 3. Attachment
S: Time setting ring

Ordering Information
■ List of Models
Operation/resetting Internal Terminal Time-limit Instantaneous Attachment Model
system connection contact contact
Time-limit operation/ Parallel motor and 8-pin socket SPDT SPDT --- H2C-8
self-resetting clutch connection
Separate motor 11-pin socket H2C
and clutch Y92A-Y1 Time H2C-S
connection Setting Ring
Front screw --- H2C-F
Time-limit operation/ 8-pin socket SPDT --- --- H2C-8R
electric resetting 11-pin socket SPDT H2C-R
Y92A-Y1 Time H2C-R-S
Setting Ring
Front screw --- H2C-FR

Note: Specify both the supply voltage and time range code (A, B, or C) in addition to the model number when ordering.
Example: H2C-S 24 VAC B
Time range code
Supply voltage

1
H2C
■ Accessories (Order Separately)
Name/specifications Models
Flush Mounting Adapter Y92F-30
Time Setting Ring (See note 1.) Y92A-Y1
Mounting Track 50 cm (l) × 7.3 mm (t) PFP-50N
1 m (l) × 7.3 mm (t) PFP-100N
1 m (l) × 16 mm (t) PFP-100N2
End Plate PFP-M
Spacer PFP-S
Protective Cover Y92A-48B
Track Mounting/Front Connecting 8-pin P2CF-08
Socket 8-pin, finger safe type P2CF-08-E
11-pin P2CF-11
11-pin, finger safe type P2CF-11-E
Back Connecting Socket 8-pin, screw terminal P3G-08
8-pin, finger safe type P3G-08 with Y92A-48G (See note 2.)
11-pin P3GA-11
11-pin, finger safe type P3GA-11 with Y92A-48G (See note 2.)
Hold-down Clip (See note 3.) For PL08 and PL11 Sockets Y92H-1
For PF085A Socket Y92H-2

Note: 1. Supplied with H2C-S/-R-S models.


2. Y92A-48G is a finger safe terminal cover which is attached to the P3G-08 or P3GA-11 Socket.
3. Hold-down Clips are sold in sets of two.

Specifications
■ Time Ranges
Five time ranges are available for each timer by turning the time range selector every 60 degrees.
Note: Rated time is displayed on the window.

Time range code Position of time range selector

A 1.25 to 30 s 7.5 s to 3 min 1.25 to 30 min 7.5 min to 3 h 1.25 to 30 h


B 0.2 to 6 s 2 to 60 s 0.2 to 6 min 2 to 60 min 0.2 to 6 h
C 0.5 to 12 s 5 to 120 s 0.5 to 12 min 5 to 120 min 0.5 to 12 h

■ Ratings
Item H2C
Rated supply voltage (motor and 24, 48, 100, 110, 115, 120, 200, 220, or 240 VAC (50/60 Hz) (see note)
clutch)
Operating voltage range 85% to 110% of rated supply voltage
Power consumption 4.2 VA max. (3.96 W max.)
Reset voltage 10% max. of rated supply voltage
Reset time Minimum power-opening time: 0.5 s
Minimum pulse width: 0.5 s
Control outputs 6 A at 250 VAC, resistive load (cosφ = 1)
Mounting method Flush mounting (except for H2C-F/-FR models), surface mounting, DIN track mounting

Note: The front panel of the timer is color coded to identify the following supply voltage classifications:
100 to 120 V: Blue
200 to 240 V: Red
Other classes: Black

2
H2C
■ Characteristics
Accuracy of operating time ±0.5% FS max. 〈±1% max. at 0.2 to 6 s for the time range code B or at 0.5 to 12 s for the time range
code C)
Setting error ±2% FS max.
Reset time 0.5 s max.
Influence of voltage ±1% FS max.
Influence of temperature ±2% FS max.
Insulation resistance 100 MΩ min. (at 500 VDC)
Dielectric strength 2,500 VAC, 50/60 Hz for 1 min (between current-carrying and non-current-carrying parts)
2,000 VAC, 50/60 Hz for 1 min (between contact and control circuit and between contacts of different
polarities)
1,000 VAC, 50/60 Hz for 1 min (between non-continuous contacts)
Vibration resistance Destruction: 10 to 55 Hz with 0.375-mm single amplitude for 1 h each in three directions
Malfunction: 10 to 55 Hz with 0.25-mm single amplitude for 10 min each in three directions
Shock resistance Destruction: 1,000 m/s2
Malfunction: 150 m/s2
Ambient temperature Operating: –10°C to 50°C
Storage: –25°C to 65°C
Ambient humidity Operating: 45% to 85%
Life expectancy Mechanical: 10,000,000 operations min. (under no load at 1,800 operations/h)
Electrical: 200,000 operations min. (3 A at 250 VAC, resistive load at 1,800 operations/h)
See Life-test Curve for other details.
Motor life expectancy 20,000 h
Approved standards UL917, CSA C22.2 No.14.
Conforms to EN61812-1 and IEC60664-1 4 kV/1 (except for H2C-F@ models).
Output category according to EN60947-5-1 (except for H2C-F@ models).
EMC (except for H2C-F@ models) (EMI) EN61812-1
Emission Enclosure: EN55011 Group 1 class A
Emission AC Mains: EN55011 Group 1 class A
(EMS) EN61812-1
Immunity ESD: IEC61000-4-2: 6 kV contact discharge (level 3)
8 kV air discharge (level 3)
Immunity RF-interference from AM Radio Waves: IEC61000-4-3: 10 V/m (80 MHz to 1 GHz) (level 3)
Immunity Burst: IEC61000-4-4: 2 kV power-line (level 3)
2 kV I/O signal-line (level 4)
Immunity Surge: IEC61000-4-5: 1 kV line to line (level 3)
2 kV line to ground (level 3)
Case color Light gray (Munsell 5Y7/1)
Degree of protection IP40 (panel surface)
Weight H2C series: approx. 180 g
H2C-F series: approx. 270 g

3
H2C
Connections
■ Terminal Arrangement
Note: The connections diagrams are for when the clutch is in the excited, reset state.

H2C-8 H2C-8R

H2C(-F)/H2C-S H2C-(F)R/H2C-R-S
Clutch coil Clutch coil

(B2) 6 6
5 (B1)(B2) 7
(16) 5 (B2) 7
(18) 4 (16)
(22)(B1) 8 (B1) 8
(24) 4 (16)
(A1) (18)
(22) (22)
(A2) (18)
3 (21)
(15) (24) 9 3 (24) 9
(A1) (A2) (A1) (A2)
2 (15) (21) 10 2 (15) (21) 10
1 11 1 11

(DIN 46 199-5) (DIN 46 199-5)

4
H2C
Operation
■ Timing Chart
H2C-8 H2C-8R Power failure
Rt Rt time (t') Rt
t t Rt Rt t
Power (2-7) Power and motor (2-7)
Time-limit contacts t+t'
NC (8-5)
Power and clutch (1-4)
Time-limit contacts
NO (8-6) Time-limit contacts
Instantaneous contacts NC (8-5)
NC (1-4)
Time-limit contacts
Instantaneous contacts NO (8-6)
NO (1-3)
Timing operation indicator Timing operation indicator
lamp (OFF at time-up) lamp (OFF at time-up)
Rt: Resetting time Rt: Resetting time
Power failure
H2C(-F)/H2C-S H2C-(F)R/H2C-R-S Rt Rt time (t')
t Rt t Rt
t Rt
Power and motor Power and motor
2(A1)-10(A2) 2(A1)-10(A2)
t+t'
Power and clutch Power and clutch
7(B1)-6(B2) 7(B1)-6(B2)
Time-limit contacts Time-limit contacts
NC 1(15)-4(16) NC 1(15)-4(16)
Time-limit contacts Time-limit contacts
NO 1(15)-3(18) NO 1(15)-3(18)
Instantaneous contacts Instantaneous contacts
NC 11(21)-8(22) NC 11(21)-8(22)

Instantaneous contacts Instantaneous contacts


NO 11(21)-9(24) NO 11(21)-9(24)
Timing operation indicator Timing operation indicator
lamp (OFF at time-up) lamp (OFF at time-up)
(See note.) Rt: Resetting time (See note.) Rt: Resetting time

Note: For the types rated at 24 and 48 VAC, the timing operation indicator is not equipped.

Nomenclature
Timing operation Time range
indicator selector

Rated voltage
color code

5
H2C
Dimensions
Note: All units are in millimeters unless otherwise indicated.

H2C/H2C-S/H2C-R/H2C-R-S/H2C-8/H2C-8R
For Flush Mounting

37 dia. 44.8 x 44.8 45+0.6


−0

+0.6
45 −0

For a load current of 3 A max., dimension L becomes


3 mm min. with an interval of 0 mm between timers.
For a load current of 6 A max., dimension L becomes
8 mm min. with an interval of 5 mm between timers.
When using in locations with high ambient
temperatures, ensure that there is an interval of at
least 5 mm between timers.

H2C-F/H2C-FR Mounting Holes


Two, M4 or 4.5 dia. holes

For a load current of 1 A max., dimension L becomes


10 mm min. with an interval of 0 mm between timers.
For a load current of 3 A max., dimension L becomes
15 mm min. with an interval of 5 mm between timers.
For a load current of 6 A max., dimension L becomes
20 mm min. with an interval of 10 mm between timers.
Dimensions with Front Connecting Socket Dimensions with Back Connecting Socket
P2CF-08-@/P2CF-11-@ P3G-08/P3GA-11

81.5 92.2
16.3 16.3
80 85.7

H2C
H2C-S H2C-8 H2C
H2C-R H2C-8R H2C-S H2C-8
100.8* H2C-R-S 103.1* H2C-R H2C-8R
H2C-R-S +
+ Adapter
Adapter
P3GA-11 P3G-08
Y92F-30 Y92F-30
(When (When
P2CF-11 P2CF-08 Y92A-48G Y92A-48G
P2CF-11-E P2CF-08-E mounted) mounted)

*These dimensions vary with the kind of DIN track (reference value).

6
H2C
■ Accessories (Order Separately)
Adapter for Flush Mounting
Y92F-30

Track Mounting/Front Connecting Socket


P2CF-08
Eight, 3 4.5
M3.5 x 7.5 sems 7.8

70 max. 35.4
Two, 4.5 dia. Terminal Arrangement/
holes Internal Connections
(Top View) Surface Mounting Holes
4
50 max. Two, 4.5 dia. or two, M4
20.3 max.
P2CF-08-E (Finger Safe Terminal Type)
Conforming to VDE0106/P100 40±0.2

Eight,
M3.5 x 7.5 sems 5 4.5
7.8

1.3
70 max. 35.4
Two, 4.5 dia.
holes

4
40±0.2 19
50 max. 20.3
21.5 max.

7
H2C
Track Mounting/Front Connecting Socket
P2CF-11
3 4.5
Eleven, 7.8
M3.5 x 7.5 sems

Terminal Arrangement/
70 max. 35.4 Internal Connections
Two, 4.5 dia. (Top View) Surface Mounting Holes
holes
Two, 4.5 dia. or two, M4
4
50 max.
31.2 max.
40±0.2

P2CF-11-E (Finger Safe Terminal Type)


Conforming to VDE0106/P100
Eleven,
M3.5 x 7.5 sems 7.8 5 4.5

1.2
70 max. 35.4
Two, 4.5 dia.
holes

4
40±0.2 30
50 max.
31.2 max.

Back Connecting Socket


Terminal Arrangement/
P3G-08 27 dia.
Internal Connections
(Bottom View)

45

45 4.9 17

P3GA-11 Terminal Arrangement/


27 dia.
Internal Connections
(Bottom View)

45 25.6

45 4.5 6.2
16.3

Finger Safe Terminal Cover


Conforming to VDE0106/P100

Y92A-48G
Twelve, 6.4 dia. holes
(Attachment for P3G-08/
P3GA-11 Socket)
34 47.7 x 47.7 48 x 48

16.5
24.6 27.6

8
H2C
Mounting Track
PFP-100N, PFP-50N PFP-100N2

16
7.3±0.15
4.5 4.5
35±0.3 27±0.15 35±0.3 27 24 29.2

15 25 25 25 25 15 25 25 25 25 15
1 1 1.5
10 10 15 (5) 10 10
1,000 (500) (see note) 1,000
(see note)

Note: The value shown in parentheses are for the


PFP-50N.

End Plate Spacer 16


10 12
PFP-M 6.2
PFP-S 5
1.8

1
50 35.5 35.3 34.8
1.8 44.3

11.5 1.3
10 M4 x 8 4.8
pan head 16.5
screw

Time Setting Ring Protective Cover


Y92A-Y1 Y92A-48B
The time setting ring locks the time setting knob to The protective cover shields the front panel, particu-
store the set time to facilitate its resetting. A maximum larly the time setting section, from dust, dirt, and water,
of two time setting rings are connectable per timer. as well as prevents the set value from being altered
due to accidental contact with the time setting knob.

Timer Hold-down Clips


Y92H-2 Y92H-1
(for PF085A/PF113A (for PL08/PL11
Connecting Socket) Connecting Socket)

9
H2C
Safety Precautions
Refer to Safety Precautions for All Timers.

!CAUTION ■ Precautions for Correct Use


This may occasionally cause electric shock, fire, or malfunction.
Never disassemble, repair, or modify the H2C. How to Change the Time Range
This may occasionally cause electric shock, fire, or malfunction. Change the time range by turning the knob clockwise using a flat-
Do not allow metal fragments or lead wire scraps to fall inside the blade screwdriver or an Allen wrench. There are five possible
H2C. settings. The selected time is displayed in the time range display
window above the knob.

■ Precautions for Safe Use


Observe the following items to ensure the safe use of this product.
Time range
Environmental Precautions display window

• Store the H2C within the specified ratings. If the H2C has been
stored at temperatures –10°C or lower, let it stand for 3 hours or
longer at room temperature before turning ON the power supply. Groove for Hex. hole for
flat-blade Allen wrench
• Use the H2C within the specified ratings for operating temperature
screwdriver
and humidity.
• Do not operate the H2C in locations subject to sudden or extreme Do not change the time range while the timer is in operation.
changes in temperature, or locations where high humidity may
result in condensation. How to Select Power Frequency
• Do not use the H2C in locations subject to vibrations or shock.
Extended use in such locations may result in damage due to stress. Before using the timer, set the frequency selector located at the rear
panel to the proper power frequency (50 to 60 Hz).
• Do not use the H2C in locations subject to excessive dust,
corrosive gas, or direct sunlight.
• Install the H2C well away from any sources of static electricity, such
as pipes transporting molding materials, powders, or liquids.
• The H2C is not waterproof or oil resistant. 50 Hz
Do not use it in locations subject to water or oil.
• The life expectancy of internal components may be reduced if the
H2C is mounted side-by-side. 60 Hz
• Do not use organic solvents (such as paint thinner or benzine),
strong alkaline, or strong acids because they will damage the
external finish.

Usage Precautions How to Mount the Timer on Mounting


• Install a switch or circuit breaker that allows the operator to
immediately turn OFF the power, and label it to clearly indicate its
Track
function. Mounting
• Be sure to wire the terminals correctly.
First hook portion A of the timer to the mounting track, then press the
• Do not install input lines in the same duct or conduit as power
timer in direction B.
supply or other high-voltage lines. Doing so may result in
malfunction due to noise. Separate the input lines from high- Dismounting
voltage lines.
• Internal elements may be destroyed if a voltage outside the rated Pull out portion C with a round-blade screwdriver and remove the
voltage is applied. timer from the mounting track.
• Maintain voltage fluctuations in the power supply within the
specified range.
• Use a switch, relay, or other contact so that the rated power supply
A
voltage will be reached within 0.1 s. If the power supply voltage is
not reached quickly enough, the H2C may malfunction or outputs
may be unstable.
• Leaving the H2C with outputs ON at a high temperature for a long
time may hasten the degradation of internal parts (such as
electrolytic capacitors). Therefore, use the H2C in combination with C
relays and avoid leaving the H2C for more than 1 month with an
output turned ON. B

Electrical Set
X2/b T/a X1/a X1/a
The motor and clutch do not need to be reset simultaneously.
Use the voltage applied to the clutch for resetting with the H2C-@R.
T X1 X2 X Auxiliary relay Do not allow power to be continuously applied to the motor and
(e.g., MY Relay) clutch for extended periods of time.

10
H2C
Others
Do not turn the operation time setting knob beyond the range of the
scale. To achieve higher accuracy in setting, measure the operation
time while turning the operation time setting knob.
The deviation and setting error for the operation time shows the
percent of FS. The absolute value of the deviation and setting error
will not change even if the set time is changed. The time
specifications should therefore be selected to use the operation time
as close to FS as possible.
At high temperatures, the operation voltage will be 90% or less if
voltage is applied continuously after timeout. Be sure to keep the
voltage within the allowable voltage fluctuation range.

Precautions for EN61812-1


The H2C (except for H2C-F@) as a built-in timer conforms to
EN61812-1, provided that the following conditions are satisfied.

Handling
Before dismounting the H2C from the Socket, make sure that no
voltage is imposed on any terminal of the H2C.
Applicable Sockets: P2CF-@@, P2CF-@@-E, PF085A, PL@@.

Wiring
Basic insulation is ensured between the motor circuit, clutch circuit,
and control output circuit. (However, the H2C-8 motor circuit and
clutch circuit use the same input.) Basic insulation is also ensured
between the output circuits of models with instantaneous output.
Basic insulation: Overvoltage category III, pollution degree 1 (See
note.)
Operating parts: Reinforced insulation (double insulation)
(with a clearance of 5.5 mm and a creepage distance of 5.5 mm at
240 VAC)
Output parts: Basic insulation
(with a clearance of 3.0 mm and a creepage distance of 3.0 mm at
240 VAC)
Note: Overvoltage category II, pollution degree 1 if the Timer is
mounted to the PL11 Socket.

ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.


To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.

In the interest of product improvement, specifications are subject to change without notice.

11
Read and Understand This Catalog
Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have any questions or
comments.

Warranty and Limitations of Liability

WARRANTY
OMRON's exclusive warranty is that the products are free from defects in materials and workmanship for a period of one year (or other period if specified)
from date of sale by OMRON.

OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, REGARDING NON-INFRINGEMENT, MERCHANTABILITY, OR


FITNESS FOR PARTICULAR PURPOSE OF THE PRODUCTS. ANY BUYER OR USER ACKNOWLEDGES THAT THE BUYER OR USER ALONE HAS
DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE. OMRON DISCLAIMS ALL OTHER
WARRANTIES, EXPRESS OR IMPLIED.

LIMITATIONS OF LIABILITY
OMRON SHALL NOT BE RESPONSIBLE FOR SPECIAL, INDIRECT, OR CONSEQUENTIAL DAMAGES, LOSS OF PROFITS OR COMMERCIAL LOSS
IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED ON CONTRACT, WARRANTY, NEGLIGENCE, OR STRICT
LIABILITY.

In no event shall the responsibility of OMRON for any act exceed the individual price of the product on which liability is asserted.

IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY, REPAIR, OR OTHER CLAIMS REGARDING THE PRODUCTS UNLESS
OMRON'S ANALYSIS CONFIRMS THAT THE PRODUCTS WERE PROPERLY HANDLED, STORED, INSTALLED, AND MAINTAINED AND NOT
SUBJECT TO CONTAMINATION, ABUSE, MISUSE, OR INAPPROPRIATE MODIFICATION OR REPAIR.

Application Considerations

SUITABILITY FOR USE


OMRON shall not be responsible for conformity with any standards, codes, or regulations that apply to the combination of products in the customer's
application or use of the products.

At the customer's request, OMRON will provide applicable third party certification documents identifying ratings and limitations of use that apply to the
products. This information by itself is not sufficient for a complete determination of the suitability of the products in combination with the end product,
machine, system, or other application or use.

The following are some examples of applications for which particular attention must be given. This is not intended to be an exhaustive list of all possible
uses of the products, nor is it intended to imply that the uses listed may be suitable for the products:

• Outdoor use, uses involving potential chemical contamination or electrical interference, or conditions or uses not described in this catalog.

• Nuclear energy control systems, combustion systems, railroad systems, aviation systems, medical equipment, amusement machines, vehicles,
safety equipment, and installations subject to separate industry or government regulations.

• Systems, machines, and equipment that could present a risk to life or property.

Please know and observe all prohibitions of use applicable to the products.

NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY WITHOUT ENSURING THAT THE
SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON PRODUCTS ARE PROPERLY RATED AND
INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM.

PROGRAMMABLE PRODUCTS
OMRON shall not be responsible for the user's programming of a programmable product, or any consequence thereof.

Disclaimers

CHANGE IN SPECIFICATIONS
Product specifications and accessories may be changed at any time based on improvements and other reasons.

It is our practice to change model numbers when published ratings or features are changed, or when significant construction changes are made.
However, some specifications of the products may be changed without any notice. When in doubt, special model numbers may be assigned to fix or
establish key specifications for your application on your request. Please consult with your OMRON representative at any time to confirm actual
specifications of purchased products.

DIMENSIONS AND WEIGHTS


Dimensions and weights are nominal and are not to be used for manufacturing purposes, even when tolerances are shown.

PERFORMANCE DATA
Performance data given in this catalog is provided as a guide for the user in determining suitability and does not constitute a warranty. It may represent the
result of OMRON’s test conditions, and the users must correlate it to actual application requirements. Actual performance is subject to the OMRON
Warranty and Limitations of Liability.

ERRORS AND OMISSIONS


The information in this document has been carefully checked and is believed to be accurate; however, no responsibility is assumed for clerical,
typographical, or proofreading errors, or omissions.

2009.9
In the interest of product improvement, specifications are subject to change without notice.

OMRON Corporation
Industrial Automation Company
http://www.ia.omron.com/
(c)Copyright OMRON Corporation 2009 All Right Reserved.