H3DE Twin Timer
H3DE Twin Timer
H3DE
Timers
DIN Track Mounted, Standard 22.5-mm Width Timer Range
• A wide AC/DC power supply range (24 to 230 VAC/DC) reduces the number of timer models kept in stock. (except for H3DE-H)
• 12-VDC model available for a specific application. (H3DE-M2)
• Nameplate provided for easy timer identification and management.
• Terminal clamp left open when delivered.
• Finger protection terminal block to meet VDE0106/P100.
• Enables easy sequence checks through instantaneous outputs for a zero set value at any time range.
• Incorporates environment-friendly, cadmium-free contacts. (except for H3DE-H)
• High immunity to inverter noise.
• Approved by UL and CSA.
• Conforms to EN61812-1 and IEC60664-1 4 kV/2 for Low Voltage, and EMC Directives.
Contents
Solid-state Timer
H3DE-M/-S...................................................................................................................................... B-55
H3DE-F ........................................................................................................................................... B-65
H3DE-G .......................................................................................................................................... B-71
H3DE-H........................................................................................................................................... B-77
Common to ALL Timers
Accessories..................................................................................................................................... B-83
Precautions ..................................................................................................................................... B-84
H3DE-M/-S
Timers
• Eight operating modes (H3DE-M) and four operating modes
(H3DE-S) cover a wide range of applications.
• Programmable contact enables the building of a self-holding re-
lay circuit (-@2 models).
• A wide time setting range of 0.10 s to 120 h.
Ordering Information
■ List of Models
Supply voltage Control output Model
Multi-function type Standard type
12 VDC Contact output: DPDT (time-limit output SPDT and switchable H3DE-M2 ---
SPDT (time-limit ←→ instantaneous)) (see note)
24 to 230 VAC/DC Contact output: DPDT (time-limit output SPDT and switchable H3DE-M2 H3DE-S2
SPDT (time-limit ←→ instantaneous)) (see note)
Contact output: SPDT (time-limit output SPDT) H3DE-M1 H3DE-S1
Note: Specify both the model number and supply voltage when ordering H3DE-M2.
Example: H3DE-M2 24 to 230 VAC/DC
Supply voltage
Note: Can be mounted to 35-mm DIN track with a plate thickness of 1 to 2.5 mm.
■ Time Ranges
Time scale display Time unit display
sec min hrs 10 h
x 0.1 0.1 to 1.2 s 0.1 to 1.2 min 0.1 to 1.2 h 1 to 12 h
x1 1 to 12 s 1 to 12 min 1 to 12 h 10 to 120 h
Note: When the main dial is set to “0” for all settings, the output will operate instantaneously.
■ Ratings
Rated supply voltage 24 to 230 VAC/DC (50/60 Hz)
(see notes 1 and 2) 12 VDC (H3DE-M2 model only)
Operating voltage range 85% to 110% of rated supply voltage
Power reset Minimum power-off time: 0.1 s
Reset voltage 2.4 VAC/DC max.
Power consump- H3DE-M1 AC: approx. 4.3 VA (2.2 W) at 230 VAC
tion (see note 3) DC: approx. 0.7 W at 24 VDC
H3DE-M2 AC: approx. 4.8 VA (2.4 W) at 230 VAC
DC: approx. 1.0 W at 24 VDC
H3DE-S1 AC: approx. 2.7 VA (1.6 W) at 230 VAC
DC: approx. 0.7 W at 24 VDC
H3DE-S2 AC: approx. 3.2 VA (1.9 W) at 230 VAC
DC: approx. 1.0 W at 24 VDC
Voltage input Max. permissible capacitance between input lines (terminals B1 and A2): 2000 pF
Load connectable in parallel with inputs (terminals B1 and A2)
H-level: 20.4 to 253 VAC/DC
L-level: 0 to 2.4 VAC/DC
Control output Contact output: 5 A at 250 VAC with resistive load (cosφ = 1)
5 A at 30 VDC with resistive load (cosφ = 1)
Ambient temperature Operating: −10°C to 55°C (with no icing)
Storage: −25°C to 65°C (with no icing)
Ambient humidity Operating: 35% to 85%
Timers
Setting error ±10% ±50 ms max. of FS (see note 1)
Signal input time 50 ms min. (see note 1)
Influence of voltage ±0.5% max. of FS (±0.5% ±10 ms max. at 1.2-s range)
Influence of temperature ±2% max. of FS (±2%±10 ms max. at 1.2-s range)
Insulation resistance 100 MΩ min. at 500 VDC
Dielectric strength Between current-carrying metal parts and exposed non-current-carrying metal parts: 2,000 VAC for 1 min.
Between control output terminals and operating circuit: 2,000 VAC for 1 min.
Between contacts of different polarities: 2,000 VAC for 1 min.
Between contacts not located next to each other: 1,000 VAC for 1 min.
Vibration resistance Malfunction: 0.5-mm single amplitude at 10 to 55 Hz
Destruction: 0.75-mm single amplitude at 10 to 55 Hz
Shock resistance Malfunction: 100 m/s2
Destruction: 1,000 m/s2
Contact material AGNi+gold plating (Use the G6RN-1 at 12 VDC.)
Impulse withstand volt- 3 kV (between power terminals)
age 4.5 kV (between current-carrying metal parts and exposed non-current-carrying metal parts)
Noise immunity Square-wave noise generated by noise simulator (pulse width: 100 ns/1 µs, 1-ns rise) ±1.5 kV
Static immunity Malfunction: 4 kV
Destruction: 8 kV
Life expectancy Mechanical: 10 million operations min. (under no load at 1,800 operations/h)
Electrical: 100,000 operations min. (5 A at 250 VAC, resistive load at 360 operations/h)
(see note 2)
EMC (EMI) EN61812-1
Emission Enclosure: EN55011 Group 1 class B
Emission AC Mains: EN55011 Group 1 class B
Harmonic Current: EN61000-3-2
Voltage Fluctuation and Flickering: EN61000-3-3
(EMS) EN61812-1
Immunity ESD: EN61000-4-2: 6 kV contact discharge (level 3)
8 kV air discharge (level 3)
Immunity RF-interference from AM Radio Waves: EN61000-4-3: 10 V/m (80 MHz to 1 GHz) (level 3)
Immunity Burst: EN61000-4-4: 2 kV power port and output port (level 3)
1 kV control port with capacitive clamp (level 3)
Immunity Surge: EN61000-4-5: 2 kV common mode (level 3)
1 kV differential mode (level 3)
Degree of protection IP30 (Terminal block: IP20)
Weight 120 g
Note: 1. With the H3DE-M@, if the voltage exceeds 26.4 VAC/DC, the following hold at signal OFF for C, D, and G modes:
Accuracy of operating time: ±1% ±50 ms max. at 1.2-s range
Setting error: ±10% +100/−50 ms max.
Signal input time: 100 ms min.
2. For reference: A maximum current of 0.15 A can be switched at 125 VDC (cosφ=1).
A maximum current of 0.1 A can be switched if L/R is 7 ms.
In both cases, a life of 100,000 operations can be expected.
The minimum applicable load is 10 mA at 5 VDC (failure level: P).
Indicator
Start input Input circuit circuit
Power-ON Output
indicator indicator
H3DE-S1/-S2
Zero setting
AC (DC) input detection Time scale/ Operating
circuit unit selectors mode selector
Indicator
circuit
Power-ON Output
indicator indicator
■ I/O Functions
Item H3DE-M1/-M2 H3DE-S1/-S2
Input Start Starts operation. No input is available.
Output Control output Outputs are turned ON according to designated out- Outputs are turned ON according to designated out-
put mode when preset value is reached. (See note.) put mode when preset value is reached. (see note.)
Note: When the output type selector switch on the bottom of the Timer is set to the instantaneous side, the relay R2 (terminal numbers 21/25, 22/
26, and 24/28) becomes an instantaneous contact and turns ON/OFF in synchronization with the changes in the power supply.
-------------------------------------------------
-------------------------------------------------
-------------------------------------------------
-------------------------------------------------
-------------------------------------------------
-------------------------------------------------
-------------------------------------------------
-------------------------------------------------
-------------------------------------------------
-------------------------------------------------
-------------------------------------------------
-------------------------------------------------
Timers
25/21
A1 15 A1 15 A1 15 A1 15 25
/21
28/24 26/22 18 16
18 16 18 16 18 16 28/2426/22
------------
------------
18 16 A2 18 16 A2 18 16 A2 18 16 A2
Note: 1. The relay R2 can be set to either instantaneous or time-limit contact using the switch located on the bottom of the Timer.
2. DC supply voltage does not require the designation of polarity.
3. The contact symbol for the H3DE is indicated with because it offers multiple operating modes and is different from the delayed
contact for conventional timers.
■ Input Connections
The inputs of the H3DE-M1/-M2 are voltage (voltage imposition or open) inputs.
(+) A2
Timer Timer
24 VDC
(−)
B1 A1
B1 A1 B1 A1
(+)
Start Start
24 VDC
(−) A2 A2
Operating
mode selector Time scale
selector
Operating
mode display
window
Timers
3. There is no start input with H3DE-S@ models. Operation starts when the power is turned ON.
4. There is no instantaneous output with H3DE-M1/-S1 models.
Instantaneous contacts:
* For power-on operation, impose voltage to the
NO 25 and 28
Start input. The Timer starts operating at the
moment the power is turned on.
** Start input is invalid while the Timer is in opera-
Power indicator tion.
B: t t
t−a
t t t
t−a
Basic operation
Flicker OFF Power (A1 and A2)
start
Start (B1 and A2) Power
(see note)
**
Output relay: NC 15 *
and 16 (25 and 26) Start
Output relay: NO t t t t
(output indicator)
15 and 18 (25 and 28) Output
Instantaneous contacts:
NC 25 and 26
* For power-on operation, impose voltage to the
Start input. The Timer starts operating at the
Instantaneous contacts: moment the power is turned on.
NO 25 and 28 ** Start input is invalid while the Timer is in opera-
tion.
Power indicator
B2: t t
t−a
t t t
t−a
Flicker ON
Power (A1 and A2) Basic operation
start
Start (B1 and A2)
(see note)
Power
Output relay: NC 15
and 16 (25 and 26) **
*
Output relay: NO Start
(output indicator)
15 and 18 (25 and 28) t t t t
Instantaneous contacts:
NC 25 and 26 Output
Note: The start input of the H3DE-M1 or H3DE-M2 model is activated by applying a voltage to B1 and A2 terminals.
The voltage can be applied by turning on the contact between B1 and A1 (Refer to Terminal Arrangement)
E: Interval t t
t−a t−a
t
Power (A1 and A2) Basic operation
J: t t
t−a t−a
t
One-shot out- Power (A1 and A2)
put Basic operation
(ON delay) Start (B1 and A2)
(see note)
Power
Output relay: NC 15
and 16 (25 and 26)
**
Output relay: NO Approx. Approx. Approx. *
(output indicator) 1+0.6 s 1+0.6 s 1+0.6 s Start
(fixed) (fixed) (fixed)
15 and 18 (25 and 28)
Instantaneous contacts:
* For power-on operation, impose voltage to the
NO 25 and 28
Start input. The Timer starts operating at the
moment the power is turned on.
** Start input is valid and re-triggerable while the
Power indicator Timer is in operation.
Note: The start input of the H3DE-M1 or H3DE-M2 model is activated by applying a voltage to B1 and A2 terminals.
The voltage can be applied by turning on the contact between B1 and A1 (Refer to Terminal Arrangement).
(Front View)
(Bottom View)
H3DE-M/-S
Surface color: Light gray 5Y7/1 (OMRON)
H3DE-F
Timers
• Operates in flicker-OFF or flicker-ON start mode with one Unit.
• Independent ON- and OFF-time settings.
Combinations of long ON- or OFF-time and short OFF- or ON-
time setting are possible.
• Long time range from 0.1 s to 12 h for both ON and OFF time
settings.
1. F: Twin timers
Ordering Information
■ List of Models
Operating mode Supply voltage Model
Flicker-OFF/Flicker-ON start 24 to 230 VAC/VDC H3DE-F
Note: Can be mounted to 35-mm DIN track with a plate thickness of 1 to 2.5 mm.
■ Time Ranges
Time scale display Time unit display
(see note 1)
sec 10 s min hrs
x 0.1 0.1 to 1.2 s 1 to 12 s 0.1 to 1.2 min 0.1 to 1.2 h
x1 1 to 12 s 10 to 120 s 1 to 12 min 1 to 12 h
Note: 1. Time scale display is applied commonly for ON and OFF time.
2. When the main dial is set to “0” for all settings, the output will operate instantaneously.
■ Ratings
Rated supply voltage (see note) 24 to 230 VAC/VDC (50/60 Hz)
Operating voltage range 85% to 110% of rated supply voltage
Power reset Minimum power-off time: 0.1 s
Reset voltage 2.4 VAC/DC max.
Power consumption AC: Approx. 3.1 VA (1.8 W) at 230 VAC
DC: Approx. 0.8 W at 24 VDC
Control output Contact output: 5 A at 250 VAC with resistive load (cosφ = 1)
5 A at 30 VDC with resistive load (cosφ = 1)
Ambient temperature Operating: −10°C to 55°C (with no icing)
Storage: −25°C to 65°C (with no icing)
Ambient humidity Operating: 35% to 85%
Timers
Influence of voltage ±0.5% max. of FS (±0.5% ±10 ms max. at 1.2-s range)
Influence of temperature ±2% max. of FS (±2% ± 10 ms max. at 1.2-s range)
Insulation resistance 100 MΩ min. at 500 VDC
Dielectric strength Between current-carrying metal parts and exposed non-current-carrying metal parts: 2,000 VAC (50/60 Hz) for 1
min.
Between control output terminals and operating circuit: 2,000 VAC (50/60 Hz) for 1 min.
Between contacts not located next to each other: 1,000 VAC (50/60 Hz) for 1 min.
Impulse withstand voltage 3 kV (between power supply terminals)
4.5 kV (between current-carrying metal parts and exposed non-current-carrying metal parts)
Noise immunity Square-wave noise generated by noise simulator (pulse width: 100 ns/1 µs, 1-ns rise) ±1.5 kV
Static immunity Malfunction: 4 kV
Destruction: 8 kV
Vibration resistance Malfunction: 0.5-mm single amplitude at 10 to 55 Hz
Destruction: 0.75-mm single amplitude at 10 to 55 Hz
Shock resistance Malfunction: 100 m/s2
Destruction: 1,000 m/s2
Life expectancy Mechanical: 10 million operations min. (under no load at 1,800 operations/h)
Electrical: 100,000 operations min. (5 A at 250 VAC, resistive load at 360 operations/h)
EMC (EMI) EN61812-1
Emission Enclosure: EN55011 Group 1 class B
Emission AC Mains: EN55011 Group 1 class B
Harmonic Current: EN61000-3-2
Voltage Fluctuation and Flickering: EN61000-3-3
(EMS) EN61812-1
Immunity ESD: EN61000-4-2: 6 kV contact discharge (level 3)
8 kV air discharge (level 3)
Immunity RF-interference from AM Radio Waves: EN61000-4-3: 10 V/m (80 MHz to 1 GHz) (level 3)
Immunity Burst: EN61000-4-4: 2 kV power port and output port (level 3)
1 kV control port with capacitive clamp (level 3)
Immunity Surge: EN61000-4-5: 2 kV common mode (level 3)
1 kV differential mode (level 3)
Degree of protection IP30 (IP20 for terminal block)
Weight Approx. 110 g
ON OFF
indicator indicator ON/OFF start
selector
One-chip microcomputer
Power Output
supply circuit
circuit
■ I/O Function
Inputs ---
Outputs Control output Outputs are turned ON/OFF according to the time set by the ON-and OFF-time setting dial.
■ Terminal Arrangement
(DIN notation)
15
A1
A2
16 18
Time Setting
OFF-time unit selector (select
one from sec, 10s, min, or hrs) Use the ON/OFF-time setting dial to set the ON/OFF time.
■ Timing Charts
Operating Timing chart
mode
Flicker-OFF 0.1 s min.
start Power (A1 and A2) ON
OFF
Output relay: NO
15 and 18 ON
(ON indicator) OFF
Output relay: NC ON
15 and 16 OFF
ON
OFF indicator OFF
tON: ON set time
tOFF: OFF set time
Output relay: ON
NO 15 and 18 OFF
(ON indicator)
Output relay: NC ON
15 and 16 OFF
ON
OFF indicator OFF
tON: ON set time
tOFF: OFF set time
(Front View)
(Bottom View)
Dimensions
Terminal block (black)
H3DE-F
Surface color:
Light gray 5Y7/1
(OMRON)
H3DE-G
Timers
• A wide star-time range (up to 120 seconds) and star-delta trans-
fer time range (up to 0.5 seconds)
1. G: Star-delta timer
Ordering Information
■ List of Models
Supply voltage Model
24 to 230 VAC/VDC H3DE-G
Note: Can be mounted to 35-mm DIN track with a plate thickness of 1 to 2.5 mm.
■ Time Ranges
Time scale display Star operation time ranges
x1 1 to 12 s
x 10 10 to 120 s
■ Ratings
Rated supply voltage (see note) 24 to 230 VAC/VDC (50/60 Hz)
Operating voltage range 85% to 110% of rated supply voltage
Power reset Minimum power-off time: 0.5 s
Reset voltage 24 VAC/DC max.
Power consumption AC: Approx. 3 VA (1.8 W) at 230 VAC
DC: Approx. 0.8 W at 24 VDC
Control output Contact output: 5 A at 250 VAC with resistive load (cosφ = 1)
5 A at 30 VDC with resistive load (cosφ = 1)
Ambient temperature Operating: −10°C to 55°C (with no icing)
Storage: −25°C to 65°C (with no icing)
Ambient humidity Operating: 35% to 85%
Timers
Total tolerance of transfer ± (25% FS + 5 ms) max.
time
Influence of voltage ±0.5% max. of FS
Influence of temperature ±2% max. of FS
Insulation resistance 100 MΩ min. at 500 VDC
Dielectric strength Between current-carrying metal parts and exposed non-current-carrying metal parts: 2,000 VAC (50/60 Hz) for 1
min.
Between control output terminals and operating circuit: 2,000 VAC (50/60 Hz) for 1 min.
Between contacts not located next to each other: 1,000 VAC (50/60 Hz) for 1 min.
Impulse withstand voltage 3 kV (between power supply terminals)
4.5 kV (between current-carrying metal parts and exposed non-current-carrying metal parts)
Noise immunity Square-wave noise generated by noise simulator (pulse width: 100 ns/1 µs, 1-ns rise) ±1.5 kV
Static immunity Malfunction: 4 kV
Destruction: 8 kV
Vibration resistance Malfunction: 0.5-mm single amplitude at 10 to 55 Hz
Destruction: 0.75-mm single amplitude at 10 to 55 Hz
Shock resistance Malfunction: 100 m/s2
Destruction: 1,000 m/s2
Life expectancy Mechanical: 10 million operations min. (under no load at 1,800 operations/h)
Electrical: 100,000 operations min. (5 A at 250 VAC, resistive load at 360 operations/h)
EMC (EMI) EN61812-1
Emission Enclosure: EN55011 Group 1 class B
Emission AC Mains: EN55011 Group 1 class B
Harmonic Current: EN61000-3-2
Voltage Fluctuation and Flickering: EN61000-3-3
(EMS) EN61812-1
Immunity ESD: EN61000-4-2: 6 kV contact discharge (level 3)
8 kV air discharge (level 3)
Immunity RF-interference from AM Radio Waves: EN61000-4-3: 10 V/m (80 MHz to 1 GHz) (level 3)
Immunity Burst: EN61000-4-4: 2 kV power port and output port (level 3)
1 kV control port with capacitive clamp (level 3)
Immunity Surge: EN61000-4-5: 2 kV common mode (level 3)
1 kV differential mode (level 3)
Degree of protection IP30 (IP20 for terminal block)
Weight Approx. 120 g
Star Star-delta
AC (DC) input operation transfer
time scale time
selector selection
Indicator
circuit
■ I/O Functions
Inputs ---
Outputs Control output Star output is turned OFF when the dial set value is reached and delta output is ON after
the preset transfer time elapses
■ Terminal Arrangement
---------------------------------------------------------------
---------------------------------------------------------------
---------------------------------------------------------------
25
Delta contact
Star contact
15 25
18 16 28 26
28 26
(DIN notation)
15 25
A1
A2
16 18 26 28
■ Timing Charts
0.5 s
Power (A1 and A2) ON
OFF
Star contact
15 and 18 ON
(star indicator) OFF
Star contact ON
15 and 16 OFF
Delta contact ON
25 and 28 OFF
(delta indicator)
Delta contact ON
25 and 26 OFF
t1: Star operation time setting
t2: Star-delta transfer time
Nomenclature
Nameplate for user use (20 x 5.4 mm white panel)
(Front View)
H3DE-G
Surface color:
Light gray 5Y7/1
(OMRON)
H3DE-H
Timers
• Two delay-time models available.
0.1 to 12 seconds (S Series)
1 to 120 seconds (L Series)
• Covers wide range of supply voltage.
Ordering Information
■ List of Models
Supply voltage Model
S Series (time range: 0.1 to 12 s) L Series (time range: 1 to 120 s)
100 to 120 VAC H3DE-H H3DE-H
200 to 230 VAC
24 VAC/VDC
48 VAC/VDC
Note: Specify both the model number and supply voltage when ordering.
Example: H3DE-H 24 VAC/DC S
Time span code
Supply voltage
Note: Can be mounted to 35-mm DIN track with a plate thickness of 1 to 2.5 mm.
■ Time Ranges
Time scale display Time ranges Min. power ON time
S series x 0.1 s 0.1 to 1.2 s 0.1 s minimum
x1s 1 to 12 s
L series x1s 1 to 12 s 0.3 s minimum
x 10 s 10 to 120 s
Note: The Timer will not operate if the specified power-on time is not kept. Be sure to supply power for at least the period specified.
■ Ratings
Rated supply voltage (see note) 100 to 120 VAC (50/60 Hz)
200 to 230 VAC (50/60 Hz)
24 VAC/VDC (50/60 Hz)
48 VAC/VDC (50/60 Hz)
Operating voltage range 85% to 110% of rated supply voltage
Power consumption 24 VAC/VDC Type AC: Approx. 0.3 VA (0.2 W) at 24 VAC
DC: Approx. 0.2 W at 24 VDC
48 VAC/VDC Type AC: Approx. 0.5 VA (0.5 W) at 48 VAC
DC: Approx. 0.5 W at 48 VDC
100 to 120 VAC Type AC: Approx. 0.8 VA (0.7 W) at 120 VAC
200 to 230 VAC Type AC: Approx. 1.6 VA (1.0 W) at 230 VAC
Control output Contact output: 5 A at 250 VAC with resistive load (cosφ = 1)
5 A at 30 VDC with resistive load (cosφ = 1)
Ambient temperature Operating: −10°C to 55°C (with no icing)
Storage: −25°C to 65°C (with no icing)
Ambient humidity Operating: 35% to 85%
Note: The ripple in DC power supply must be 20% max. A single-phase, full-wave rectifying power supply can be connected if the ripple output of
the power supply is a maximum of 20% of the whole output.
Timers
Influence of voltage ±0.5% max. of FS (±0.5% ±10 ms max. at 1.2-s range)
Influence of temperature ±2% max. of FS (±2% ± 10 ms max. at 1.2-s range)
Insulation resistance 100 MΩ min. at 500 VDC
Dielectric strength Between current-carrying metal parts and exposed non-current-carrying metal parts: 2,000 VAC (50/60 Hz) for 1
min.
Between control output terminals and operating circuit: 2,000 VAC (50/60 Hz) for 1 min.
Between contacts not located next to each other: 1,000 VAC (50/60 Hz) for 1 min.
Impulse withstand voltage 3 kV (or 1 kV for 24/48 VAC/VDC models) (between power supply terminals)
4.5 kV (or 1.5 kV for 24/48 VAC/VDC models) (between current-carrying metal parts and exposed non-current-
carrying metal parts)
Noise immunity Square-wave noise generated by noise simulator (pulse width: 100 ns/1 µs, 1-ns rise) ±1.5 kV (between power
supply terminals)
Static immunity Malfunction: 4 kV
Destruction: 8 kV
Vibration resistance Malfunction: 0.5-mm single amplitude at 10 to 55 Hz
Destruction: 0.75-mm single amplitude at 10 to 55 Hz
Shock resistance Malfunction: 100 m/s2
Destruction: 1,000 m/s2
Life expectancy Mechanical: 10 million operations min. (under no load at 1,200 operations/h)
Electrical: 100,000 operations min. (5 A at 250 VAC, resistive load at 1,200 operations/h)
EMC (EMI) EN61812-1
Emission Enclosure: EN55011 Group 1 class A
Emission AC Mains: EN55011 Group 1 class A
Harmonic Current: EN61000-3-2
Voltage Fluctuation and Flickering: EN61000-3-3
(EMS) EN61812-1
Immunity ESD: EN61000-4-2: 6 kV contact discharge (level 3)
8 kV air discharge (level 3)
Immunity RF-interference from AM Radio Waves: EN61000-4-3: 10 V/m (80 MHz to 1 GHz) (level 3)
Immunity Burst: EN61000-4-4: 2 kV power port and output port (level 3)
1 kV control port with capacitive clamp (level 3)
Immunity Surge: EN61000-4-5: 2 kV common mode (level 3)
1 kV differential mode (level 3)
Degree of protection IP30 (IP20 for terminal block)
Weight Approx. 120 g
Power failure
detection circuit
■ I/O Functions
Inputs ---
Outputs Control output The Timer operates instantaneously when the Timer is turned ON. The Timer is in counting operation
after the Timer is turned OFF and the output of the Timer is turned OFF when the preset time elapses.
■ Terminal Arrangement
(DIN notation)
15
A1
A2
16 18
■ Timing Charts
Power supply ON
(A1 and A2) OFF
Output relay: NC ON
15 and 16 OFF
Output relay: NO ON
15 and 18 OFF
Power indicator ON
OFF
t: Set time
Rt: Minimum power-on time (S-series: 0.1 s min.; L-series: 0.3 s min.)
(The output may never turn ON if this time or more is not ensured.)
Nomenclature
Nameplate for user use
(20 x 5.4 mm white panel)
Time scale
display window
(Front View)
H3DE-H
Surface color:
Light gray 5Y7/1
(OMRON)
■ Dimensions
Mounting Track
PFP-100N, PFP-50N PFP-100N2
16
7.3±0.15
4.5 4.5
27±0.15 35±0.3 27 24 29.2
35±0.3
15 25 25 25 25 * 15 25 25 25 25 15 1 1.5
1 10 10
10 10 L
L
L: Length
1m PFP-100N
50 cm PFP-50N
1m PFP-100N2
1
50 35.5 35.3 34.8
1.8 44.3
11.5 1.3
M4 x 8
10 pan head 4.8
screw 16.5
■ Changing of Setting
!Caution ■ Power Supplies
Do not change the time unit, time scale, operating mode, or output
type selector switch while the Timer is in operation or malfunction The H3DE Series is provided with a transformerless power supply
could result. system. An electric shock may be received if the input terminal or the
output type selector switch is touched while power is being supplied.
A1
When dismounting the H3DE, pull out portion (C) with a flat-blade
screwdriver and remove the Timer from the mounting track. B1
H3DE Power supply
Start
input
A2
Rectifier circuit
Circuit
t t
t: Mounting clearance (mm)
Timers
B1
70 Mounting clearance: Incorrect H3DE Power supply
50 mm
Ambient temperature (°C)
Mounting
60 clearance: 10 mm
Short-circuit A2
Maximum range of current
operating ambient
50 temperature
A1
Mounting
40 clearance: 5 mm B1
H3DE
Mounting
30 clearance: 0 mm
A2
20
■ Input/Output
B1
H3DE Power supply
Correct
B1
H3DE
B1 A1
AC/DC
power Input circuit Power supply
supply circuit A2
Since the input circuit and the power supply circuit are configured
independently, the input circuit can be turned on or off irrespective of
■ Input Wires
the on/off state of the power supply. The input wires must be as short as possible. If the floating capacity
It must be noted that a voltage equivalent to the power supply voltage of wires exceeds 2,000 pF (approx. 17 m for cables with 120 pF/m),
is applied to the input circuit. the operation will be affected. Pay particular attention when using
When connecting a relay or a transistor as an external signal input shielded cables.
device, pay attention to the following points to prevent short-circuiting
due to a sneak current to the transformerless power supply. ■ Wiring (H3DE-H)
If a relay or transistor is connected to two or more Timers, the input
terminals of those Timers must be wired properly so that they will not The H3DE has a high impedance circuit. Therefore, the H3DE may
be different in phase or the terminals will be short-circuited to one not be reset if the H3DE is influenced by inductive voltage. In order to
another (refer to the figures below). eliminate any influence of inductive voltage, the wires connected to
the H3DE must be as short as possible and should not be installed
alongside power lines. If the H3DE is influenced by inductive voltage
that is 30% or more of the rated voltage, connect a CR filter with a
capacitance of approximately 0.1 µF and a resistance of approxi-
mately 120 Ω or a bleeder resistor between the power supply termi-
nals. If there is any residual voltage due to current leakage, connect
a bleeder resistor between the power supply terminals.
Cat. No. L092-E1-05 In the interest of product improvement, specifications are subject to change without notice.