0% found this document useful (0 votes)
74 views1 page

Characteristics: H3CR-A

This document summarizes the specifications of a solid-state multi-functional timer. It includes details on accuracy, reset time, voltage influence, insulation resistance, dielectric strength, temperature influence, impulse withstand voltage, noise immunity, vibration resistance, ambient operating conditions, EMC standards compliance, and expected life. Key specifications include an accuracy of ±0.2% FS, reset time of ±5% FS +50 ms, operating temperature range of -10°C to 55°C, and mechanical life expectancy of 20,000,000 operations minimum.

Uploaded by

Bin Mulyadin
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
74 views1 page

Characteristics: H3CR-A

This document summarizes the specifications of a solid-state multi-functional timer. It includes details on accuracy, reset time, voltage influence, insulation resistance, dielectric strength, temperature influence, impulse withstand voltage, noise immunity, vibration resistance, ambient operating conditions, EMC standards compliance, and expected life. Key specifications include an accuracy of ±0.2% FS, reset time of ±5% FS +50 ms, operating temperature range of -10°C to 55°C, and mechanical life expectancy of 20,000,000 operations minimum.

Uploaded by

Bin Mulyadin
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

Characteristics

Accuracy of operating time Setting error Reset time Reset voltage Influence of voltage Insulation resistance Dielectric strength

0.2% FS max. (0.2%10 ms max. in a range of 1.2 s) 5% FS 50 ms (See note 1)


Min. power-opening time: 0.1 s max. Min. pulse width: 0.05 s (H3CR-A/-AS) 10% max. of rated supply voltage

0.2% FS max. (0.2%10 ms max. in a range of 1.2 s)


100 M min. (at 500 VDC) 2,000 VAC (1,000 VAC for H3CR-A@S), 50/60 Hz for 1 min (between current-carrying metal parts and exposed noncurrent-carrying metal parts) 2,000 VAC (1,000 VAC for H3CR-A@S), 50/60 Hz for 1 min (between control output terminals and operating circuit) 2,000 VAC, 50/60 Hz for 1 min (between contacts of different polarities) 1,000 VAC, 50/60 Hz for 1 min (between contacts not located next to each other) 2,000 VAC, 50/60 Hz for 1 min (between input and control output terminals and operation circuit) for H3CR-AP 3 kV (between power terminals) for 100 to 240 VAC/100 to 125 VDC, 1 kV for 24 to 48 VAC/12 to 48 VDC 4.5 kV (between current-carrying terminal and exposed non-current-carrying metal parts) for 100 to 240 VAC/100 to 125 VDC, 1.5 kV for 24 to 48 VAC/12 to 48 VDC and 24 to 48 VAC/VDC

Influence of temperature 1% FS max. (1%10 ms max. in a range of 1.2 s)

Impulse withstand voltage Noise immunity Static immunity Vibration resistance Shock resistance Ambient temperature Ambient humidity Life expectancy EMC

1.5 kV (between power terminals) and 600 V (between no-voltage input terminals), square-wave noise by noise simulator (pulse width: 100 ns/1 s, 1-ns rise)
Malfunction: 8 kV Destruction: 15 kV Destruction: 10 to 55 Hz with 0.75-mm single amplitude each in 3 directions for 2 hours each Malfunction: 10 to 55 Hz with 0.5-mm single amplitude each in 3 directions for 10 minutes each Destruction: 1,000 m/s2 3 times each in 6 directions Malfunction: 100 m/s2 3 times each in 6 directions Operating: Storage: Operating:

10C to 55C (with no icing) 25C to 65C (with no icing)


35% to 85%

Mechanical: 20,000,000 operations min. (under no load at 1,800 operations/h) Electrical: 100,000 operations min. (5 A at 250 VAC, resistive load at 1,800 operations/h) (See note 2) EN61812-1 EN55011 Group 1 class A EN55011 Group 1 class A EN61812-1 IEC61000-4-2: 6 kV contact discharge (level 3) 8 kV air discharge (level 3) Immunity RF-interference from AM Radio Waves: IEC61000-4-3: 10 V/m (80 MHz to 1 GHz) (level 3) Immunity RF-interference from Pulse-modulated Radio Waves: IEC61000-4-3: 10 V/m (9005 MHz) (level 3) Immunity Conducted Disturbance: IEC61000-4-6: 10 V (0.15 to 80 MHz) (level 3) Immunity Burst: IEC61000-4-4: 2 kV power-line (level 3) 2 kV I/O signal-line (level 4) Immunity Surge: IEC61000-4-5: 1 kV line to line (level 3) 2 kV line to ground (level 3) Light gray (Munsell 5Y7/1) IP40 (panel surface) Approx. 90 g (EMI) Emission Enclosure: Emission AC Mains: (EMS) Immunity ESD:

Case color Degree of protection Weight

Note: 1. The value is 5% FS +100 ms to 0 ms max. when the C, D, or G mode signal of the H3CR-AP is OFF. 2. Refer to the Life-test Curve.