NFPA 30 (2021)
PRACTICAL VIEWPOINTS TO ENSURE
CODE COMPLIANCE
Mike Snyder, PE, CSP, CFPS and Sarah Eck, PE, CCPSC
Since 1913, NFPA 30, Flammable and Combustible Liquids Code, has served as the leading information
source for safe handling and storage of “flammable and combustible liquids.” It is a widely used
Recognized and Generally Accepted Good Engineering Practice (RAGAGEP) in the field of Flammable and
Combustible Liquid Risk Management.
Introduction                                                             Establishing a Basis of Safety for Liquid
                                                                         Use and Storage
Since 1913, NFPA 30, Flammable and Combustible Liquids Code,
has served as the leading information source for safe handling and       The main purpose of NFPA 30 is to provide information that serves
storage of flammable and combustible liquids. It is a widely used        as fundamental safeguards for storage, handling, and use of liquids.
Recognized and Generally Accepted Good Engineering Practice              This is accomplished by, initially, requiring and recommending
(RAGAGEP) in the field of Flammable & Combustible Liquid Risk            measures that focus on preventing the ignition of fire. The fire
Management, and is applied by government authorities, emergency          prevention strategy relies on the reliable application of controls to
responders and end-users to ensure safe storage and handling of          break one or more than one of the legs of the Fire Triangle
liquids. Many state and regionally adopted Flammable and                 (Figure 1 on page 2).
Combustible Liquid Codes are based on recent editions of NFPA 30.
US-OSHA enforces 29 CFR 1910.106, Flammable Liquids, which is            NFPA 30 is structured to recognize that reducing fire risk from
based on the NFPA 30 (1969), and include a series of interpretive        prevention, alone, is typically not adequate to address all aspects of
letters and agency directives.                                           the liquid risk. The standard provides additional requirements for
                                                                         the use of fire and explosion safeguards or control systems to
This paper will overview the principles required to establish a basis    provide life and structural safety in the event ignition occurs. The
of safety for proper handling and storage of liquids. Six significant    extent of these protective systems is typically based on both the
changes proposed for the 2021 edition of NFPA 30 will be highlighted     flammability characteristics of the liquids being stored, handled, or
and their implications to flammable and combustible liquid safety        used and the quantity of material involved.
practices reviewed. Practical tips for the Process Safety Professional
to efficiently navigate older versions of NFPA 30 that are adopted
into present regulatory requirements.
                                                                                                                                                  1
Figure 1: The Fire Triangle
   FUEL                                                                  The fire and explosion safeguards typically utilized in NFPA 30 include:
> Proper design of containers, piping, and tanks to reduce leakage         > Drainage & containment
  and to provide containment of liquid in early stages of                  > Facility design, including use of fire walls, fire resistive
  fire exposure                                                               construction, and separation distances
> Use of low level and local exhaust ventilation to prevent                > Fixed fire protection systems
  accumulation of flammable vapors                                         > Emergency Plans
> Operational procedures to control emissions from Class I                 > Explosion protection (containment, relief venting, explosion
  liquids in containers and tanks                                             suppression)
> Housekeeping practice to control fuel sources that could
  provide initial fire exposure to liquids in use and storage            NOTE: Focus on this protection is needed when handling liquids
> Use of flash arrestor systems to limit exposure of flammable           that are highly volatile (Class IA & IB) or are chemically unstable.
  vapors within the headspace of tanks
                                                                         Overview of NFPA 30
   AIR/OXIDANT
                                                                         NFPA 30, Flammable and Combustible Liquids Code, is a widely used
> In limited situations, container transfers and tank headspaces         Recognized and Generally Accepted Good Engineering Practice
  can have oxygen concentration lowered through the                      (RAGAGEP) in the field of Flammable & Combustible Liquid Risk
  introduction of an inert gas.                                          Management. It is applied by government authorities, emergency
> The basis of safety is to ensure that the oxygen concentration is      responders and end-users to ensure safe storage and handling of liquids.
  reliably held below the lower oxygen concentration limit
  required for combustion.                                               NFPA 30 has been developed and updated through NFPA’s standards
> Personnel safety must be carefully considered when using               development process that is a full, open, consensus-based process.
  this strategy to avoid worker exposure to asphyxiation risks.          NFPA 30 is revised and updated approximately every three years.
                                                                         The standard’s cycle takes approximately two years to complete.
                                                                         Each revision cycle proceeds according to a published schedule,
   IGNITION SOURCES                                                      which includes final dates for each stage in the standards development
                                                                         process, and provides several opportunities for all members of the
> Section 6.5 of NFPA 30 provides an overview of fundamental             public to provide input and commentary for changing, updating, and
  strategies, focusing on 12 common sources of ignition in               improving the standard. This information is tracked on the
  liquid operations                                                      Document Info pages for each standard1.
> Key focus on adequate electrical (hazardous) area classification
  (Chapter 7)                                                            The four fundamental steps in the NFPA standards development
> Controls for electrostatic risks, particularly when transferring and   process are:
  dispensing liquids
> Control of hot work operations                                           > Public Input
                                                                           > Public Comment
                                                                           > NFPA Technical Meeting
                                                                           > NFPA Standards Council Action (Appeals and Issuance of
                                                                              Standard)
                                                                         The Regulations Governing the Development of NFPA Standards
                                                                         detail the procedures used during each step of the NFPA 30
                                                                         Standards development process2.
                                                                                                                                                    2
NFPA Technical Committees serve as the principal consensus bodies                  technical committees (Fundamentals, Operations, Storage & Warehousing,
responsible for developing and updating all NFPA codes and                         and Tank Storage & Piping Systems) are summarized in Table 1.
standards. Committee members appointed by the NFPA Standards
Council, representing a balance of interests. NFPA membership is not
required in order to participate on a NFPA Technical Committee.                    Common Methods for Safe Storage and
Appointment to a Technical Committee is based on such factors as                   Handling of Flammable Liquids
technical expertise, professional standing, commitment to public
safety, and the ability to bring to the table the point of view of a               NFPA 30 is a widely used Recognized and Generally Accepted Good
category of interested people or groups.                                           Engineering Practice (RAGAGEP) in the field of flammable and
                                                                                   combustible liquid risk management. It is routinely applied by
Due to the comprehensive nature of NFPA 30, there are four technical               government authorities, emergency responders and end-users to
committees and one correlating committee that manage                               ensure safe storage and handling of liquids. Successful management of
the standard’s revision and update. The purpose of the correlating                 flammable liquid risks are most efficiently provided by understanding
committee is to manage and coordinate the activities of the four                   the structure of NFPA 30 and the source of its requirements and
technical committees involved with NFPA 30 and to ensure that the                  recommendations. This allows one to effectively use this information
document sections managed by each technical committee do not                       for the design and operation of liquids operations.
contain conflicts or inconsistencies. The responsibilities for the four
Table 1: Topical Coverage and Application of NFPA 30 Chapters
                    Chapter                                         Application                                        NFPA Technical
                                                                                                                        Committee
                 1-7 (5 is reserved)   Requirements for all facilities where liquids are stored, handled, or used         Fundamentals
                         8                                             Reserved
                   9 through 12        Storage of liquids in containers, portable tanks, and intermediate bulk
                                           containers in the occupancies covered by each chapter’s scope
                         13            Storage of liquids in containers, portable tanks, and intermediate bulk
                                                    containers in detached unprotected buildings
                                                                                                                      Storage & Warehousing
                         14            Storage of liquids in containers, portable tanks, and intermediate bulk        of Containers & Portable
                                                  containers in hazardous materials storage lockers                      Tanks (FLC-SWC)
                         15                Outdoor storage of liquids in containers, portable tanks, and
                                                         intermediate bulk containers
                         16              Fire protection design criteria used to protect storage of liquid in
                                           containers, portable tanks, and intermediate bulk containers
                         17            Design and construction of facilities where liquids are processed or used
                         18             General requirements related to handling, dispensing, transfer, and
                                                                  use of liquids                                      Operations (FLC-OPS)
                                         Specific equipment & operations that use liquids (recirculating heat
                         19            transfer systems, vapor recovery & processing systems, solvent distillation,
                                                and cooking oil storage tanks in commercial kitchens)
                         20                                            Reserved
                   21 through 25                           Bulk storage of liquids in tanks.                          Tank Storage & Piping
                                                                                                                       Systems (FLC-TAN)
                         27                            Piping systems for transferring liquids
                         28                Loading and unloading systems associated with bulk storage of
                                                                liquids in tanks                                      Operations (FLC-OPS)
                         29                      Wharves associated with bulk handling of liquids
                                                                                                                                                            3
NFPA 30 provides several options for facility and tank design for the         When faced with a local adoption of NFPA 30, it is essential that you
storage, use, and handling of liquids. The options available are              have access to both the edition of NFPA 30 that was adopted, as well
generally based on the hazards presented by the commodity (flash              as a copy of any amendments made during the adoption process.
point & boiling point), construction of containers (or tanks) used,           For example, the state of Michigan has adopted the 2012 edition of
and the configuration of storage or use.                                      NFPA 30 and issued a series of amendments3 that both limit the
                                                                              application of the standard to liquids with flash points below
As an example, Chapters 9 through 16 of NFPA 30 provide number of             200°F (93°C) and direct certain state activities for inspection and
options are available for storage of liquids in containers. Depending         review to specific departments. For facilities subject to NFPA 30, this
on the risks involved and protection provided, the volume of storage          information will be necessary to ensure that both current operations
is limited – which allows several design options based on operational         and new projects are conducted in accordance with the specific
needs. The options available in storage situations include:                   state requirements.
  > Storage configurations in detached, unprotected buildings                 Typically, when a jurisdiction has adopted an older version of NFPA 30
  > Storage configurations in hazardous materials lockers                     and you desire to use features from newer editions, there are variance
  > Outdoor storage configurations                                            procedures that can be applied. Generally, the responsibility is placed
  > Indoor protected storage (large quantities in specific                    on the variance requester to demonstrate that the proposed approach
     configurations)                                                          provides equivalent safety to the original requirement. With adequate
  > Indoor unprotected storage (limited quantities and                        justification, these requests are often approved. The key to success is
      configurations)                                                         to engage the local fire code authority early in the process, to discuss
A commonly overlooked requirement from Chapter 17 is that processing          the specific details of the request and align on the best way to accomplish
and handling of Class II and Class III liquids heated at or above their       the desired objectives.
flash point shall follow the requirements for Class I liquids, unless an
engineering evaluation conducted in accordance with Chapter 6                 OSHA 1910.106 (Flammable Liquid Standard) is based on the 1969
justifies following the requirements for some other (lower hazard)            edition of NFPA 30. The OSHA standard has been given a limited
liquid class.                                                                 update to incorporate Globally Harmonized System (GHS) terminology
                                                                              (Categories) along with agency directives to address the introduction
                                                                              of plastic containers that did not exist when the 1969 edition was
Navigating Code Requirements With                                             published4.
Legacy Versions of NFPA 30
                                                                              In 1995, OSHA produced a letter of interpretation that allowed
Generally, NFPA 30 is adopted as part of a local or state level               facility owners to use a more current version of NFPA 30 in lieu of the
Flammable & Combustible Liquids Code through legislative action.              older requirements in 1910.1065. OSHA states that they will accept
Often, the adopted version is from one or two code cycles earlier than        later editions of consensus standards (such as NFPA 30) when those
the most current version, and local amendments may be made.                   later editions set forth requirements which are as protective as current
The most common amendment is to limit the coverage of the code                requirements of the standard. In such situations, the employer has the
to liquids with flash points below 200F (93C). NFPA 30 Annex H                burden of proof to demonstrate that the protective measures
provides guidance for adopting the standard in a local jurisdiction.          implemented are in fact equivalently protective.
Table 2: OSHA Citations Against 1910.106 (2010 – 2019) – 71% of Citations Issued
                       OSHA Section                             Coverage Area                             Number of Citations
                        1910.106 (e)(6)                           Sources of ignition                              1721
                        1910.106 (e)(2)             Incidental storage or use of flammable liquids                 1379
                        1910.106 (d)(2)            Design, construction, and capacity of containers                1087
                        1910.106 (e)(9)                             Housekeeping                                    768
                        1910.106 (d)(4)           Design and construction of inside storage rooms                   634
                        1910.106 (g)(3)                 Service stations: Dispensing systems                        507
                        1910.106 (d)(3)          Design, construction, and capacity of storage cabinets             505
                                                                                                                                                            4
OSHA’s Citation History Involving 1910.106                                   Key Changes Proposed for NFPA 30
(Flammable Liquids Standard)                                                 (2021 Edition)
As previously referenced, OSHA 1910.106 (Flammable Liquid                    The structure and chapter architecture of NFPA 30 (2021) will remain
Standard) is based on the 1969 edition of NFPA 30. The OSHA                  identical to that of NFPA 30 (2018). To address both continued
standard has been given a limited update to incorporate Globally             challenges experienced in liquid risk management and to resolve
Harmonized System (GHS) terminology along with agency directives             technical challenges presented by new containers and storage
to address the introduction of plastic containers that did not exist         configurations, several specific technical changes were made, which
when the 1969 edition was published. The OSHA Standard applies to            are summarized below. Two significant changes were proposed during
flammable liquids divided into four GHS categories. The standard             the first draft of the document, and through the consensus process
scope covers liquids with flash points below 199.4°F (93°C) or any           were reversed during the second draft processing. All proposed
liquid that is heat above or within 30°F (16.7°C) of its flash point.        changes will be presented to the NFPA Standards Council for
                                                                             adoption once any Notice of Intent to Make a Motion (NITMAM) are
In the period 2010 to 2019, Federal and State-based OSHA inspectors          processed at the NFPA Annual meeting in June 2020. One NITMAM
issued over 9000 individual violations that referenced a specific            was filed prior to the February 19, 2020 deadline; however, it is not
section of the OSHA 1910.106 standard6. A summary of the most                focused on any of the technical changes reviewed here.
common violations is in Table 2 below.
                                                                             Flammable & Combustible Liquid Nomenclature
The key observations from this analysis highlight the following
common risk factors in industry. Each of these areas is well covered         Throughout NFPA 30 (2021), the term “ignitable (flammable or
by the modern editions of NFPA 30:                                           combustible)” will be used to denote any liquid that has a flash point.
                                                                             When referring to a specific type of ignitable liquid, NFPA 30 uses
  > Improper ignition source management, including both electrical           liquid class to denote boiling point and flash point ranges. Liquid
    (hazardous) area classification and proper management of static          classification is summarized in Table 3 below.
    electricity hazards represent more than 10% of citations issued.
  > Many industrial and manufacturing facilities where the use and           This action begins the process of reducing the use of the terms
    handling of flammable liquids is only incidental to the principal        “flammable” or “combustible” to reduce confusion of terminology
    business have weak practices related to the handling and storage         arising from the definitions used by different agencies and the
    of liquids. Impacted businesses include automobile assembly,             Globally Harmonized System (GHS). For example, OSHA uses 140°F
    construction of electronic equipment, and furniture                      (60°C) to delineate between flammable and combustible liquid classi-
    manufacturing.                                                           fication, whereas NFPA uses 100°F (37.8°C). Longer term, use of
  > Proper containers use and selection for the storage and handling         liquid class provides more consistency in evaluating any liquid with a
    of liquids remains a common problem area.                                flash point. In these cases, any liquid with a flash point can burn
  > Housekeeping and control of materials that can become initial            (that is, are ignitable liquids) given a sufficient ignition source.
    sources of ignition remain a common threat in many industrial            When ignited, these liquids generally produce high levels of heat
    and manufacturing occupancies.                                           output. The liquid classification (e.g. Class I, Class II, and Class III)
  > The design and construction of small liquid storage rooms                can provide more of a perspective on the relative ease of ignition.
    (<500 ft2; 46.5 m2) frequently have problems with excessive
    storage volumes, electrical wiring, and ventilation.
  > Flammable liquid cabinet use, design, and loading of flammable
    liquids remains a major identified non-compliance.
  Table 3: Flash Points and Boiling Points of Liquid Classes used in NFPA 30 (Chapter 4)
                   Liquid Class                                Flash Point                                 Boiling Point
                          IA                                Below 73°F (22.8°C)                         Less than 100°F (37.8°C)
                          IB                                Below 73°F (22.8°C)                       At or Above 100°F (37.8°C)
                          IC                At or Above 73°F (22.8°C) but below 100°F (37.8°C)                   Any
                          II                At or above 100°F (37.8°C) but below 140°F (60°C)                    Any
                         IIIA                At or above 140°F (60°C) but below 200°F (93°C)                     Any
                         IIIB             At or above 200°F (93°C), subject to having a Flash Point              Any
                                                                                                                                                         5
Treatment of Beverages, Medicines, and Other                                    that previous editions of NFPA 30 had with other model Fire &
Consumer Products Containing Not More Than                                      Safety Codes on this issue.
20% Water-Miscible Liquids
                                                                                Anchoring of Tanks (Section 22.5.3)
In the 2018 edition of NFPA 30, beverages, medicines, foodstuffs,
cosmetics, and other consumer products are excluded from NFPA                   During the first revision, this new section was added to NFPA 30 to
coverage if they contained not more than 50 percent by volume of                specify the conditions under which anchorage of tanks is required.
water-miscible flammable or combustible liquids, with the remainder             The new section makes the consideration method for anchorage
of the product consisting of components that do not burn. This                  explicit and detailed.
exception in Section 9.1.4(4) applies to liquids in containers that do
not exceed 1.3 gallons (5 liters). Table 16.4.1(a) indicates that they          Metallic/Nonmetallic Composite Piping (Section 27.4.7)
were to be stored and protected as either a Class I or Class II
commodity as described in NFPA 13, Standard for the Installation of             A new subsection was added to cover metallic/nonmetallic composite
Sprinkler Systems (2019)7.                                                      piping. This listed piping material for flammable and combustible
                                                                                liquids has been in use for 20 years with a variety of flammable liquids.
During the current revision cycle, additional fire testing data was             The piping system contains an inner metallic liquid conducting tube
presented to support the reduction of this exclusion to not more than           and an outer nonmetallic tube, which contains any leakage from the
20 percent by volume of water-miscible liquid. The 2021 edition of              inner metallic tube. The space between the inner and outer tubes can
NFPA 30 will provide specific protection coverage in Tables 16.5.2.17           be monitored for pressure, to indicate leakage.
or 16.5.2.18, as applicable, or potentially treat the storage as unprotected.
Improvements to Application Flowcharts and New                                  Significant Changes Considered But
Fire Protection Design Options in Chapter 16                                    Not Implemented
(Protected Storage)
                                                                                Composite Intermediate Bulk Containers (Chapter 9)
Chapter 16 provides specifications for the design and configuration of
automatic fire protection systems for all inside storage of ignitable           The fire risks presented by composite IBCs storing combustible
liquids in containers, intermediate bulk containers (IBCs), and                 liquids are well documented in the literature9. During the first
portable tanks that are being used in accordance with the container             revision, additional restrictions on the use of composite IBCs were
requirements specified in Section 9.4. When liquids are protected in            proposed that were subsequently removed and returned to language
accordance with the applicable requirements of this chapter, they are           from the 2018 edition of NFPA 30. In summary, the requirements for
considered protected storage. Protected storage allows for virtually            use and storage of composite IBCs include:
unlimited quantities of storage in the protected configuration.
                                                                                  > Composite IBCs are not authorized for the storage of Class I
Commercial use and development of liquids continues to drive the                    liquids, except in specific limited situations detailed in
need for new containers and configurations of storage, which require                Section 9.1.4 of NFPA 30.
careful evaluation of what is required for effective fire protection              > Composite IBCs containing a Class II or Class IIIA liquid must
design. The protection criteria modifications were validated by full                be listed and labeled. Units not listed and labelled are prohibited.
scale fire testing described in reports reviewed by the FLC-SWC                   > Section 18.5.4.1, related to allowances for storage of liquids in
technical committee8. The testing information was produced in                       incidental-use applications, sets out requirements for conducting
alignment with the guidelines outlines in Annex D & Annex E of                      a hazard analysis and implementing a lower threshold for
NFPA 30, which focus on the development of fire protection system                   maximum allowable quantities that can be staged. It reduces the
design criteria used in Chapter 16.                                                 number of Composite IBCs that can be temporarily staged in an
                                                                                    operational area.
Significant additions to this Chapter include the following:
                                                                                Local Exhaust Ventilation Credit Reductions
  > Three new protection schemes are added in Section 16.5 for                  (Section 17.11)
    small (<1 gallon; 3.7 liter) containers of alcohols and 50-50
    alcohol-water mixtures                                                      During the first revision, the maximum credit available to be taken for
  > New section 16.5.2.13 and 16.6.5 adding in-rack protection                  required ventilation available from local exhaust ventilation (LEV) was
    criteria for Class II liquids in metal containers using K25.2               proposed for reduction from 75% to 50%, based on opinions expressed
    extended coverage sprinklers                                                about ventilation compromise that could exist by improper use of LEV
  > New section 16.5.2.14 provides new fire protection criteria for             equipment. This was reversed during the Technical Committee’s work
    liquids with flash points less than 200°F (93°C) in cartoned,               during second draft and restored to the maximum 75% credit.
    two-ounce, plastic bottles
  > New sections 16.5.2.15 and 16.6.4 provides new sprinkler protec-
    tion criteria for liquids with flash points greater than or equal to        Conclusion
    450°F (232°C)
                                                                                DEKRA has applied the principles within NFPA 30 for decades and
Flammable Liquid Cabinet Self Closing Doors                                     recognizes them as a key part of an effective Loss Control Engineering
(Section 9.5.3)                                                                 Program. We are committed to partnering with our clients to adapt to
                                                                                the changes presented by the 2021 edition and to apply existing requi-
NFPA 30 has been updated to require that all new flammable liquid               ements to address our Client‘s unique needs. Contact us to talk about
storage cabinets must have self-closing doors. This resolves conflicts          how to manage these and other fire hazards!
                                                                                                                                                            6
References
     1    National Fire Protection Association, “NFPA 30: Flammable and Combustible Liquid Code”. 2018, http://www.nfpa.org/30
     2    National Fire Protection Association, “Regulations Governing the Development of NFPA Standards”, Retrieved from: https://www.
          nfpa.org/Codes-and-Standards/Standards-development-process/Regulations-and-policies, Accessed on February 19, 2020
     3    State of Michigan Department of Licensing and Regulatory Affairs. (2014), “Flammable and Combustible Liquid Rules”. Retrieved
          from https://www.michigan.gov/lara/0,4601,7-154-89334_42271_4115_4237-9432--,00.html. Accessed on February 19, 2020
     4    United States Department of Labor. (1980), “Directive STD 01-05-014: U.S. Department of Transportation (DOT) Exemption Which
          allows Shipments of Combustible and Flammable Liquids In Polyethylene”. Retrieved from
          https://www.osha.gov/enforcement/directives/std-01-05-014. Accessed on February 19, 2020
     5    United States Department of Labor. (1995), “Compliance with NFPA 30 Revisions in lieu of 1910.106”. Retrieved from https://www.
          osha.gov/laws-regs/standardinterpretations/1995-07-18, Accessed on February 19, 2020
     6    United States Department of Labor. (2019), “OSHA Enforcement Data”, Data Catalog. Retrieved from
          https://enforcedata.dol.gov/views/data_summary.php, Accessed on February 17, 2020
     7    National Fire Protection Association, “NFPA 13: Standard for the Installation of Sprinkler Systems”. 2019,
          http://www.nfpa.org/13
     8    FM Global (2018). Summary Report of Fire Testing Involving Ignitable Liquids – NFPA 30. Retrieved from
          https://www.fmglobal.com/research-and-resources/standards-and-certification/code-support-reports. Accessed on
          February 19, 2020
     9    Snyder, M. D. (2019). Understand the Risks of Composite Intermediate Bulk Containers. Chemical Engineering Progress, 115(2),
          39–43.
                                                    Would you like more information?
                                                                      Contact Us
                                                               DEKRA Process Safety
                                                              dekra.us/process-safety
                                                           process-safety-usa@dekra.com
©2020 DEKRA SE or its subsidiaries. All rights reserved. All trademarks are owned by DEKRA SE or its subsidiaries, reg. U.S. Pat. & Tm. Off. and
other countries as listed on our website. No modifications, reproduction or use without written permission from DEKRA SE or its subsidiaries.