1.heat Load Calculation Sheet

The document provides a detailed heat load calculation for a classroom area, including various factors such as ventilation, sensible heat, and latent heat gains. It outlines the specific measurements and calculations for walls, roof, floor, and glass, resulting in a total heat load of 50074.62 BTU/HR. Additionally, it includes safety factors and ventilation requirements for the space.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
25 views1 page

1.heat Load Calculation Sheet

The document provides a detailed heat load calculation for a classroom area, including various factors such as ventilation, sensible heat, and latent heat gains. It outlines the specific measurements and calculations for walls, roof, floor, and glass, resulting in a total heat load of 50074.62 BTU/HR. Additionally, it includes safety factors and ventilation requirements for the space.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 1

SONAIRE SERVICES Heat Load Calculation ALCOVE- GR. FL.

AREA NAME CLASS ROOM AREA(SFT) (FT.) VOL(CU.FT) DATE


DBT %RH WBT TH DPT GR/LB L*W H 10000 24.01.2025
OUT 102.74 42.48 82.22 45.94 134.44 1000.0 10 cfm
ROOM 73.4 55 28.2 67.72 AIRCHANGE/HR 1 166.7
DIFFRENCE 29.34 12.52 82.22 17.74 66.72
1)VENTILATION VENT.CFM 5) SHF 0.801
A PERSON 35 CFM/HEAD 10 350 ADP FROM TABLE 54
B DOORS CFM/HEAD 0 6)REHEAT
C CRACK FT. CFM/FT 0
TOTAL 350
2)SPACE SENSIBLE HEAT BTU/HR 7) DEHUMIDIFIER TOTAL CFM
AREA DESCRIPTION S.FT FACTOR TD/HG (REHEAT)
WALL N 500 0.34 16.5 2805
WALL S 500 0.34 28.5 4845 8)FAN CFM 2219.9
WALL E 200 0.34 30.5 2074
WALL W 200 0.34 24.5 1666
WALL NE 0 0.34 22.5 0
WALL SE 0 0.34 30.5 0
WALL SW 0.34 26.5 0
WALL NW 0 0.34 18.5 0
ROOF 1000 0.14 0 0
FLOOR 1000 0.4 29.34 11736 9)VENTL. CFM HEAT 24587.6
GLASS N 0 0.56 23 0
GLASS S 0 0.56 12 0 GRAND SUBTOTAL 74662.3
GLASS E 0 0.56 12 0 PIPE GAIN/SAFETYFACTOR 10.0
GLASS W 0 0.56 163 0
GLASS NE 0 0.56 12 0
GLASS SE 0 0.56 12 0
GLASS SW 0 0.56 85 0
GLASS NW 0 0.56 138 0 GRAND TOTAL 82128.5
GLASS - TRANS GAIN 0 1.0 29.34 0
GLASS PARTITION 0 1.0 19.34 0 TONNAGE 6.8
Non AC PARTITION 0 0.23 19.34 0
AC PARTITION 0 0.23 19.34 0

VENTL. 0.12 BF 350 CFM 29.34 TEMP DIFF 1330.8624 CFM/SFT 2.2
PEOPLE 245 SH/PERSON 35 NOS 8575 CFM/TR 324.4
LIGHTS 1000 WATT 3.41 BTU/HR 3410 SFT/TR 146.1
MACHINES 0 WATT 3.41 BTU/HR 0 GLASS AS % OF TOTAL TR 0.0
MISC. REMARKS
SUBTOTAL 36441.8624
DUCT GAIN FANHP 10 SAFETY FACTOR
LESS STORAGE EFFECT
SPACE SENSIBLE HEAT TOTAL 40086.04864
3)SPACE LATENT HEAT GAIN BTU/HR
A)VENTL 350 CFM 66.72 GR/LB DIFF 1905.5232
B)INFILTR CFM GR/LB DIFF 0
C)PEOPLE 35 NOS. 205 LH/PERSON 7175
MISC.
SUBTOTAL 9080.5232
10 SAFETY FACTOR
LATENT HEAT TOTAL 9988.57552
TOTAL SPACE HEAT 50074.62416