SONAIRE SERVICES                                                             Heat Load Calculation                                                         ALCOVE- GR. FL.
AREA NAME                                                    CLASS ROOM                                        AREA(SFT)              (FT.)        VOL(CU.FT)             DATE
            DBT             %RH          WBT            TH             DPT       GR/LB                         L*W                    H                         10000   24.01.2025
OUT                102.74       42.48           82.22          45.94                 134.44                                  1000.0           10                  cfm
ROOM                 73.4           55                          28.2                  67.72 AIRCHANGE/HR                                       1                166.7
DIFFRENCE       29.34          12.52            82.22        17.74                   66.72
1)VENTILATION                                                                                                  VENT.CFM            5)      SHF                                  0.801
A          PERSON                   35 CFM/HEAD                                          10                                    350 ADP FROM TABLE                                  54
B          DOORS                       CFM/HEAD                                                                                  0 6)REHEAT
C           CRACK FT.                    CFM/FT                                                                                  0
                                                                                               TOTAL                           350
2)SPACE SENSIBLE HEAT                                                                                          BTU/HR                 7) DEHUMIDIFIER TOTAL CFM
          AREA DESCRIPTION                              S.FT                     FACTOR          TD/HG                                (REHEAT)
WALL                           N                                500                   0.34              16.5                  2805
WALL                            S                               500                   0.34              28.5                  4845 8)FAN CFM                                   2219.9
WALL                            E                               200                   0.34              30.5                  2074
WALL                            W                               200                   0.34              24.5                  1666
WALL                           NE                                 0                   0.34              22.5                     0
WALL                           SE                                 0                   0.34              30.5                     0
WALL                           SW                                                     0.34              26.5                     0
WALL                           NW                                 0                   0.34              18.5                     0
ROOF                                                           1000                   0.14                 0                     0
FLOOR                                                          1000                    0.4             29.34                 11736 9)VENTL. CFM HEAT                          24587.6
GLASS                          N                                  0                   0.56                23                     0
GLASS                           S                                 0                   0.56                12                     0 GRAND SUBTOTAL                             74662.3
GLASS                           E                                 0                   0.56                12                     0 PIPE GAIN/SAFETYFACTOR                        10.0
GLASS                          W                                  0                   0.56               163                     0
GLASS                          NE                                 0                   0.56                12                     0
GLASS                          SE                                 0                   0.56                12                     0
GLASS                          SW                                 0                   0.56                85                     0
GLASS                          NW                                 0                   0.56               138                     0 GRAND TOTAL                                82128.5
GLASS - TRANS GAIN                                                0                      1.0           29.34                     0
GLASS PARTITION                                                   0                    1.0             19.34                     0 TONNAGE                                           6.8
Non AC PARTITION                                                  0                   0.23             19.34                     0
AC PARTITION                                                      0                   0.23             19.34                     0
VENTL.               0.12 BF                     350 CFM                             29.34 TEMP DIFF                      1330.8624 CFM/SFT                                       2.2
PEOPLE                                           245 SH/PERSON                          35 NOS                                 8575 CFM/TR                                      324.4
LIGHTS                                          1000 WATT                             3.41 BTU/HR                              3410 SFT/TR                                      146.1
MACHINES                                           0 WATT                             3.41 BTU/HR                                 0 GLASS AS % OF TOTAL TR                        0.0
MISC.                                                                                                                                       REMARKS
 SUBTOTAL                                                                                                                36441.8624
            DUCT GAIN FANHP                                      10              SAFETY FACTOR
                                         LESS           STORAGE EFFECT
SPACE SENSIBLE HEAT TOTAL                                                                                               40086.04864
3)SPACE LATENT HEAT GAIN                                                                                       BTU/HR
A)VENTL                                           350 CFM                            66.72 GR/LB DIFF                     1905.5232
B)INFILTR                                             CFM                                  GR/LB DIFF                             0
C)PEOPLE                                           35 NOS.                             205 LH/PERSON                           7175
MISC.
SUBTOTAL                                                                                                                  9080.5232
                                                                 10              SAFETY FACTOR
LATENT HEAT TOTAL                                                                                                        9988.57552
TOTAL SPACE HEAT                                                                                                        50074.62416