Sunline Magnum ZF
Sunline Magnum ZF
Table of Contents
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Table of Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Component Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Prior Nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Features and Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Guide Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Physical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Capacity Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Airflow Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Sound Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Weights and Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Component Location
(ZF shown)
                                                                                   HIGH
                                                                                EFFICIENCY   COPPER TUBE/ALUMINUM FIN
                                              20 GAUGE
                                                                               COMPRESSORS      CONDENSER COILS
                                          ALUMINIZED STEEL
                                      TUBULAR HEAT EXCHANGERS
                   LONG LASTING
                POWDER PAINT FINISH
                                                                                                                                  ELECTRICAL
                                                                                                                                 DISCONNECT
                                                                                                                                   MOUNTING
                                                                                                                                   LOCATION
                                                                                                                                 (Field installed)
                                                                                                                                KNOCKOUT FOR
                                                                                                                                SIDE CONTROL
                                                                                                                                WIRING ENTRY
                                                                                                                                   KNOCKOUT
                                                                                                                                    FOR SIDE
2" DISPOSABLE
                                                                                                                                 POWER WIRING
    FILTERS
                                                                                                                                  ENTRY SIDE
                                                                                                          GAS/ELECTRIC
                                                                  BELT-DRIVE
                          1" NPTI                               BLOWER MOTOR                               UNIT SHOWN
                     CONDENSATE DRAIN
                                            FULL PERIMETER
                                         14 GAUGE BASE RAILS
                                          WITH LIFTING HOLES
Nomenclature
                                                                                                      Refrigeration
                                   Heat Capacity
                                                                                          A = Standard Refrigeration
               00 = Cooling Only                                                          B = ECC (E-Coat Cond Coil)
                                                                                          C = EEC (E-Coat Evap Coil)
                                 Gas MBH Input
                                                                                          F = ECC,EEC
               30 = 300 MBH Input
               40 = 400 MBH Input
                                                                                                Controls Option
                                                                                            Sensors
                                                             Voltage
                                                                                  A = No Sensors
                                                       7 = 380/415-3-50           B = PHM (Phase Monitor)
                                                                                  C = DFS (Dirty Filter Switch)
                                                    Outdoor Air Option            D = SAD (Supply Air Smoke DET)
                                                                                  E = RSD (Return Air Smoke DET)
                                            A = No Economizer                     F = PHM,DFS
                                            B = Economizer w/Barometric RLF1      G = PHM,SAD
                                            C = Economizer w/o Barometric RLF     H = PHM,RSD
                                            D = Economizer w/Power EXH1           J = DFS,SAD
                                            H = Motorized Damper                  K = DFS,RSD
                                            J = Motorized Damper w/Baro RLF1      L = SAD,RSD
                                                                                  M = PHM,DFS,SAD
                                            Note: 1. Available Downflow Only      N = PHM,DFS,RSD
                                                                                  P = PHM,SAD,RSD
                                                                                  Q = DFS,SAD,RSD
                                                            Service Options
                                                                                  R = PHM,DFS,SAD,RSD
                                                    1 = No Service Options
                                                    2 = DSC (Disconnect Switch)
Prior Nomenclature
                                                                                                    Standard Cabinet                             Hinged Filter Door & Tool Free Access Cabinet
                                  Airflow
                                                                               AA = None                                                      BA = Hinged Filter Door & Tool Free Access Panels
         A = Hi Static                                                         AB = Phase Monitor                                             BB = Phase Monitor, Hinged Filter Door & Tool Free
         B = Hi Static/Economizer                                              AC = Coil Guard                                                     Access Panels
         C = Hi Static/Economizer/Power Exhaust                                AD = Dirty Filter Switch                                       BC = Coil Guard, Hinged Filter Door & Tool Free
             (Downflow Only)                                                   AE = Phase Monitor & Coil Guard                                     Access Panels
         D = Hi Static/Motorized Damper                                        AF = Phase Monitor & Dirty Filter Switch                       BD = Dirty Filter Switch, Hinged Filter Door &
         E = Hi Static/Motorized Damper/Barometric Relief                      AG = Coil Guard & Dirty Filter Switch                               Tool Free Access Panels
         J = Hi Static/Economizer/Barometric Relief                            AH = Phase Monitor, Coil Guard & Dirty Filter Switch           BE = Phase Monitor & Coil Guard, Hinged Filter
                                                                               RC = Coil Guard & American Flag                                     Door & Tool Free Access Panels
                                                                               TA = Technicoat Condenser Coil                                 BF = Phase Monitor & Dirty Filter Switch, Hinged
                                                            Voltage            TJ = Technicoat Evaporator Coil                                     Filter Door & Tool Free Access Panels
                                                                               TS = Technicoat Evaporator & Condenser Coils                   BG = Coil Guard & Dirty Filter Switch, Hinged Filter
                                                     7 = 380/415-3-50                                                                              Door & Tool Free Access Panels
                                                                                                                                              BH = Phase Monitor, Coil Guard & Dirty Filter Switch,
                                                                                                                                                   Hinged Filter Door & Tool Free Access Panels
                                                                               ZZ = If desired option combination is not listed above, ZZ will be assigned and configuration options will be
                                                                                    located in digits 15-18.
Installation Options
                                                                        A = No Options Installed
                                                                        B = Option 1
                                                                        E = Option 3
                                                                        F = Option 4
                                                                        G = Options 1 & 3
                                                                        H = Options 1 & 4
                                                                        L = Options 1,3 & 4
                                                                        R = Options 3 & 4
Options
                                                                        1 = Disconnect
                                                                        3 = Smoke Detector S.A.
                                                                        4 = Smoke Detector R.A.
   • On-board USB Port - The new control comes with a long               • Full Perimeter Base Rails - The permanently attached
     list of features including data logging, current and                  base rails provide a solid foundation for the entire unit and
     previous system faults and software update capabilities               protect the unit during shipment. The rails offer rigging
     using the on board USB port and common flash drive.                   holes so that an overhead crane can be used to place the
     Energy use monitoring capabilities allow custom tailoring             units on a roof.
     to allow a system to work more efficiently at all times and         • Easy Installation - Gas and electric utility knockouts are
     occupancy levels. Self test and start-up reports also                 supplied in the unit underside as well as the side of the
     available from the board VIA the USB port.                            unit. Utility connections can be made quickly and with a
   • Embedded LCD Display - The board has a easy to read,                  minimum amount of field labor. All units are shipped with
     built-in LCD display and easy to use navigation joystick              2" throw-away filters installed.
     and buttons allowing the user to quickly navigate the               • Wide Range of Indoor Airflows - All supply air blowers
     menus displaying unit status, options, current function,              are equipped with a belt drive that can be adjusted to
     supply, return and outdoor temperatures, fault codes and              meet the exact requirements of the job.
     other information.                                                  • Warranty - All models include a 1-year limited warranty
   • Safety Monitoring - The control monitors the outdoor,                 on the complete unit. Compressors each carry a 5-year
     supply, and return air temperatures and the high and low              warranty. Aluminized steel and stainless steel tubular heat
     pressure switch status on the independent refrigerant                 exchangers carry a 10- year warranty.
     circuits. On units with heating the gas valve and high
     temperature limit switches are monitored on gas and             Factory Installed Options
     electric heating units. The control also monitors the           YORK® offers several equipment options factory installed, for
     voltage supplied to the unit and will protect the unit if low   the ZF Series.
     voltage due to a brown out, or other electrical issue               • Dry Bulb Economizers - All units offer a variety of
     occurs.                                                               optional factory installed down flow economizers that are
   • Low Ambient - An integrated low-ambient control allows                shipped, installed and wired with low leak dampers
     units to operate in the cooling mode down to 0°F outdoor              designed to meet ASHRAE 90.1-2010, AMCA 511 Class
     ambient without additional components or intervention.                1A damper, and the International Energy Conservation
     Optionally, the control board can be programmed to                    Code (IECC) certification requirements by achieving
     lockout the compressors when the outdoor air                          leakage rates of 3 cfm/sq. ft. at 1" of static pressure. Each
     temperature is low or when free cooling is available.                 economizer goes through a rigorous 60,000 cycle test.
   • Anti-Short Cycle Protection - To aid compressor life, an              Dry bulb, single enthalpy, and dual enthalpy (with field
     anti- short cycle delay is incorporated into the standard             installed kit) can be selected. All economizer options are
     control. Compressor reliability is further ensured by                 fully integrated into the Simplicity® SE controls. The
     programmable minimum run times. For testing, the anti-                economizer has spring return, fully modulating damper
     short cycle delay can be temporarily overridden with the              actuators and is capable of introducing up to 100%
     push of a button.                                                     outdoor air. As the outdoor air intake dampers open, the
                                                                           return air dampers close. The changeover from
   • Fan Delays - Fan on and fan off delays are fully
                                                                           mechanical refrigeration to economizer operation is
     programmable. Furthermore, the heating and cooling fan
                                                                           regulated by the outdoor air dry bulb temperature or the
     delay times are independent of one another. All units are
                                                                           outdoor air enthalpy input. The dual enthalpy kit provides
     programmed with default values based upon their
                                                                           a second input used to monitor the return air (field
     configuration of cooling and/or heating capacity.
                                                                           installed). The installer needs only to assemble the
   • Nuisance Trip Protection and Three Strikes - To                       outdoor air hood, attach the enthalpy control the hood and
     prevent nuisance calls, the control board uses a three                mount the hood to the unit (Hood and control are
     times, you're out philosophy. The high, low-pressure                  provided).
     switch, anti-freeze protection, low voltage or heating high
                                                                         • Power Exhaust - Our economizer options are available
     limit must trip three times within two hours before the unit
                                                                           with power exhaust. Whenever the outdoor air intake
     control board will lock out the associated compressor.An
                                                                           dampers are opened for free cooling, the exhaust fan will
     alarm message will be displayed on the LCD screen.
                                                                           be energized to prevent the conditioned space from being
     • Lead-Lag - An integrated Lead-Lag option allows equal               over-pressurized during economizer operation.
       run time hours on all compressors, thereby extending                The exhaust fan, motor and controls are installed and
       the life of all compressors. This option is selectable on           wired at the factory. The rain hood must be assembled
       the unit control board.                                             and installed in the field.
   • Reliable - From the beginning - All units undergo                     The power exhaust option can only be used on bottom
     computer automated testing before they leave the factory.             duct configurations.
     Units are tested for refrigerant charge and pressure, unit
                                                                         • Motorized Outdoor Air Intake Damper - Includes a
     amperage, and 100% functionality. For the long term - All
                                                                           slide-in / plug-in damper assembly with a 2- position,
     units are painted with a long lasting, powder paint that
                                                                           spring return motor actuator which opens to a pre-set
     stands up over the life of the unit. The paint used has
                                                                           position whenever the supply air blower is operating and
     been proven by a 1000 hour salt spray test.
                                                                           will drive fully closed when the blower unit shuts down.
      The rain hood is painted to match the basic unit and must       NOTE: Knobs are shipped separately within the unit to prevent
      be field assembled before installing.                                 shipping damage. These must be field installed for tool
    • Barometric Relief Damper - This damper option can be                  free operation.
      used to relieve internal building air pressure on units with       • Hinged/"Tool Free" Blower, Blower Motor, Filter And
      an economizer without power exhaust. This accessory                  Electric Access Panels - This option allows for complete
      includes a rain hood, a bird screen and a fully assembled            hinged and tool free access to the unit’s blower, blower
      damper. With bottom duct connections, the damper                     motor, filters and electrical panel sections.
      should be mounted over the opening in the return air
      panel. With horizontal ductwork, the accessory should be        Control Options
      mounted on the return air duct.
                                                                           Simplicity® SE with Communication Option Control -
    • E-Coat Condenser Coils - The condenser coils are                     The York® Simplicity® SE with Communication Option
      coated with an epoxy polymer coating to protect against              Control is factory installed. It includes all the features of
      corrosion.                                                           the Simplicity® SE control with an additional gateway to
    • E-Coat Evaporator Coils - The evaporator coils are                   BACnet MS/TP (programmable to Modbus or N2
      coated with an epoxy polymer coating to protect against              protocols).
      corrosion.
                                                                           Novar® BAS Control - The Novar® building automation
    • Filter Options - Standard units are shipped with 2" throw-           system controller is factory installed. Incudes supply air
      away filters installed. 2" pleated and 4" pleated filters are        sensor, return air sensor, dirty filter indicator switch, and
      offered as a factory installed option.                               air proving switch.
    • Disconnect Switch - For gas heat units a HACR breaker
                                                                           CPC BAS Control - The Computer Process Controls
      sized to the unit is provided.
                                                                           Model 810-3060 ARTC Advanced Rooftop building
    • Smoke Detectors - (supply air & return air) The smoke                automation system controller is factory installed. Includes
      detectors stop operation of the unit by interrupting power           supply air sensor, return air sensor, dirty filter indicator
      to the control board if smoke is detected within the air             switch and air proving switch.
      compartment.
                                                                           Honeywell BAS Control - The Honeywell W7750C
                                                                           building automation system controller is factory installed.
                                                                           Includes air supply sensor, return air sensor, dirty filter
                                                                           indicator switch, and air proving switch.
    Factory installed smoke detectors in the return air, may
                                                                      Field Installed Accessories
    be subjected to freezing temperatures during “off” times
    due to out side air infiltration. these smoke detectors have      YORK® offers several equipment accessories for field
    an operational limit of 32°F to 131°F. smoke detectors            installation, for the ZF Series.
    installed in areas that could be out side those limitations            Dry Bulb Economizers - All units offer a variety of
    will have to be moved to prevent having false alarms.                  optional factory installed down flow economizers that are
                                                                           shipped, installed and wired with low leak dampers
    • Coil Guard - Customers can purchase a coil guard kit to              designed to meet ASHRAE 90.1-2010, AMCA 511 Class
      protect the condenser coil from damage. This is not a hail           1A damper, and the International Energy Conservation
      guard kit.                                                           Code (IECC) certification requirements by achieving
    • Stainless Steel Heat Exchanger - For applications in                 leakage rates of 3 cfm/sq. ft. at 1" of static pressure. Each
      corrosive environments, this option provides a full                  economizer goes through a rigorous 60,000 cycle test.
      stainless steel heat exchanger assembly.                             Dry bulb, single enthalpy, and dual enthalpy (with field
    • Stainless Steel Drain Pan - An optional rustproof                    installed kit) can be selected. All economizer options are
      stainless steel drain pan is available to provide years of           fully integrated into the Simplicity SE controls. The
      trouble-free operation in corrosive environments.                    economizer has spring return, fully modulating damper
    • Phase Monitors - Designed to prevent unit damage. The                actuators and is capable of introducing up to 100%
      phase monitor will shut the unit down in an out-of phase             outdoor air. As the outdoor air intake dampers open, the
      condition.                                                           return air dampers close. The changeover from
    • Dirty Filter Switch - This kit includes a differential               mechanical refrigeration to economizer operation is
      pressure switch that energizes the fault light on the unit           regulated by the outdoor air dry bulb temperature or the
      thermostat, indicating that there is an abnormally high              outdoor air enthalpy input. The dual enthalpy kit provides
      pressure drop across the filters. Factory installed option or        a second input used to monitor the return air (field
      field installed accessory.                                           installed). The installer needs only to assemble the
    • Hinged Filter Door/"Tool Free" Blower And Access                     outdoor air hood, attach the enthalpy control the hood and
      Panels (Not Hinged) - This option allows for easy access             mount the hood to the unit (Hood and control are
      and maintenance.                                                     provided).
                                                                         • Motorized Outdoor Air Intake Damper - Includes a
                                                                           slide-in / plug-in damper assembly with a 2-position,
       spring return motor actuator which opens to some pre-set           Guide Specifications
       position whenever the supply air blower is operating and
       will drive fully closed when the blower unit shuts down.           General
       The rain hood is painted to match the basic unit and must
       be field assembled before installing.                              Units shall be manufactured by Johnson Controls Unitary
   •   Roof Curbs - Fourteen-inch high roof curbs provide a               Products in an ISO 9001 certified facility.
       water-tight seal between the unit and the finished roof.           ZF models have 2 condenser fan motors and compressors. All
       These full perimeter curbs meet the requirements of the            compressors include crankcase heat and internal discharge
       National Roofing Contractors Association (NRCA) and are            temperature protection. Every refrigerant circuit includes an
       shipped knocked-down for field assembly.                           expansion valve, a liquid line filter-drier, a discharge line high
       They're designed to fit inside the base rails of the unit and      pressure switch and a suction line with a freezestat and low
       include both a wood nailing strip and duct hanger supports.        pressure/loss of charge switch. The unit control circuit includes
   •   High Altitude Natural Gas - Burner orifices and pilot              75 VA and 150 VA transformers, a 24-volt circuit breaker and a
       orifices are provided for proper furnace operation at              relay board with two compressor lockout circuits, a terminal
       altitudes up to 6,000 feet.                                        strip for thermostat wiring, plus an additional set of pin
   •   Propane - Burner orifices, pilot orifices and gas valve parts      connectors to simplify the interface of additional field controls.
       are provided to convert a natural gas furnace to propane.          All units have long lasting powder paint cabinets with 1000 hour
   •   High Altitude Propane - Burner orifices and pilot orifices         salt spray test approval under ASTM-B117 procedures. All
       are provided for proper furnace operation at altitudes up          models include a 1-year limited warranty on the complete unit.
       to 6,000 feet. This accessory supplements the basic                Compressors and electric heater elements carry an additional
       propane conversion kit.                                            4-year warranty. Aluminized steel tubular heat exchangers
                                                                          carry an additional 9-year warranty.
   •   Side Duct Flanges - One-inch flanges replace the supply
       and return air panels on the rear of the unit to accommodate
                                                                          Description
       horizontal duct connections. These flanges can also be used
       individually for bottom supply / horizontal return or horizontal   ZF units shall be factory-assembled, single packaged, ZF***N
       supply/bottom return. They cannot be used on units with            Electric Cooling/Gas Heat, ZF***C Cooling designed for outdoor
       power exhaust.                                                     mounted installation.
   •   Barometric Relief Damper - This damper accessory can
       be used to relieve internal building air pressure on units         They shall have built-in field convertible duct connections for
       with an economizer without power exhaust. This                     down discharge supply/return or horizontal discharge supply/
       accessory includes a rain hood, a bird screen and a fully          return, and be available with factory installed options or field
       assembled damper. With bottom duct connections, the                installed accessories. The units shall be factory wired, piped,
       damper should be mounted over the opening in the return            charged with R-410A refrigerant and factory tested prior to
       air panel. With horizontal ductwork, the accessory should          shipment. All unit wiring shall be both numbered and color
       be mounted on the return air duct.                                 coded. All units shall be manufactured in a facility certified to
   •   Enthalpy Accessory Control Kit - This kit contains the             ISO 9001 standards and the cooling performance shall be rated
       required components to convert a single enthalpy                   in accordance with DOE and AHRI test procedures. Units shall
       economizer to dual enthalpy.                                       be classified to ANSIZ21.47 standards, UL 1995/CAN/CSA No.
                                                                          236-M90 conditions.
   •   Burglar Bars - Mount in the supply and return openings
       to prevent entry into the duct work.                               Unit Cabinet
   •   Flue Exhaust Extension Kit - In locations with wind or
       weather conditions which may interfere with proper                 Unit cabinet shall be constructed of galvanized steel, with
       exhausting of furnace combustion products, this kit can be         exterior surfaces coated with a non-chalking, powdered paint
       installed to prevent the flue exhaust from entering nearby         finish, certified at 1000 hours salt spray test per ASTM-B117
       fresh air intakes.                                                 standards. Indoor blower section shall be insulated with a
   •   Wood Skid - Allows unit to be handled with 90" forks.              minimum 1/2" thick insulation, coated on the airside. Aluminum
   •   CO2 Sensor - Senses CO2 levels and automatically                   foil faced insulation shall be used in the furnace compartment
       overrides the economizer when levels rise above the                and be fastened with rigid fasteners to prevent insulation from
       present limits.                                                    entering the air stream. Cabinet panels shall be easily
   •   Coil Guard - Customers can purchase a coil guard kit to            removable for servicing and maintenance. Full perimeter base
       protect the condenser coil from damage. This is not a hail         rails shall be provided to assure reliable transit of equipment,
       guard kit.                                                         overhead rigging and proper sealing on roof curb applications.
                                                                          Disposable 2" filters shall be furnished and be accessible
   •   Phase Monitors - Designed to prevent unit damage. The
                                                                          through a removable access door, sealed airtight. Units filter
       phase monitor will shut the unit down in an out-of phase
                                                                          track shall be designed to accommodate either 2" or 4" filters.
       condition.
                                                                          Fan performance measuring ports shall be provided on the
                                                                          outside of the cabinet to allow accurate air measurements of
                                                                          evaporator fan performance without removing panels or
creating air by-pass of the coils. Condensate pan shall be               d. The refrigeration system shall provide at least 10° F of
internally sloped and conform to ASHRAE 62-89 self-draining                 sub-cooling at design conditions.
standards. Condensate connection shall be a minimum of 1"
                                                                         e. All models shall have two independent circuits.
I.D. female and be a ridged mount connection. Unit shall
incorporate a fixed outdoor air damper with an outdoor air           Unit Controls
intake opening covered with a bird screen and a rain hood
painted to match the exterior of the unit.                               a. Unit shall be complete with self-contained low-voltage
                                                                            control circuit protected by a resettable circuit breaker on
Indoor (Evaporator) Fan Assembly                                            the 24-volt transformer side.
Fan shall be a belt drive assembly and include an adjustable-            b. Unit shall incorporate a lockout circuit which provides
pitch motor pulley. Job site selected (B.H.P.) brake horsepower             reset capability at the space thermostat or base unit,
shall not exceed the motors nameplate horsepower rating, plus               should any of the following standard safety devices trip
the service factor. Units shall be designed not to operate above            and shut off compressor.
service factor. Fan wheel shall be double-inlet type with                c. Loss-of-charge/Low-pressure switch.
forward-curved blades, dynamically balanced to operate
                                                                            1. High-pressure switch.
smoothly throughout the entire range of operation. Airflow
design shall be constant air volume.                                        2. Freeze-protection thermostat, evaporator coil. If any of
                                                                               the above safety devices trip, a LED (light-emitting
Outdoor (Condenser) Fan Assembly                                               diode) indicator shall flash a diagnostic code that
                                                                               indicates which safety switch has tripped.
The outdoor fans shall be of the direct-driven propeller type,
                                                                         d. Unit shall incorporate "AUTO RESET" compressor over
discharge air vertically, have aluminum blades riveted to
                                                                            temperature, over current protection.
corrosion resistant steel spider brackets and shall be
dynamically balanced for smooth operation. The 2 outdoor fan             e. Unit shall operate with conventional thermostat designs
motors shall be totally enclosed with permanently lubricated                and have a low voltage terminal strip for easy hook-up.
bearings, internally protected against overload conditions and
                                                                         f. Unit control board shall have on-board diagnostics and
staged independently.
                                                                            fault code display.
Refrigerant Components                                                   g. Standard controls shall include anti-short cycle and low
                                                                            voltage protection, and permit cooling operation down to
Compressors:                                                                25°F.
     a. Shall be Scroll compressors internally protected with
                                                                         h. Control board shall monitor each refrigerant safety switch
        internal discharge temperature protection over
                                                                            independently.
        temperature protection.
                                                                         i. Control board shall retain last 5 fault codes in non volatile
     b. Shall have internal spring isolation and sound muffling to
                                                                            memory, which will not be lost in the event of a power
        minimize vibration and noise, and be externally isolated
                                                                            loss.
        on a dedicated, independent mounting.
Coils:                                                               Gas Heating Section (ZF***N Models)
     a. Evaporator and condenser coils shall have aluminum           Shall be designed with induced draft combustion with post purge
        plate fins mechanically bonded to seamless internally        logic and energy saving direct spark ignition, redundant main gas
        enhanced copper tubes with all joints brazed. Special        valve. Ventor wheel shall be constructed of stainless steel for
        Phenolic coating shall be available as a factory option.     corrosion resistance. The heat exchanger shall be of the tubular
     b. Evaporator and Condenser coils shall be of the direct        type, constructed of T1-40 aluminized steel for corrosion
        expansion, draw-thru, design.                                resistance and allowing minimum mixed air entering temperature
                                                                     of 25 °F. Burners shall be of the in-shot type, constructed of
Refrigerant Circuit and Refrigerant Safety Components shall
                                                                     aluminum coated steel and contain air mixture adjustments. All
include:
                                                                     gas piping shall enter the unit cabinet at a single location through
     a. Balance-port thermostatic expansion          valve   with    either the side or curb, without any field modifications. An
        independent circuit feed system.                             integrated control board shall provide timed control of evaporator
     b. Filter drier/strainer to eliminate any moisture or foreign   fan functioning and burner ignition. Heating section shall be
        matter.                                                      provided with the following minimum protection:
                                                                         a. Primary and auxiliary high-temperature limit switches.
     c. Accessible service gage connections on both suction
        and discharge lines to charge, evacuate, and measure             b. Induced draft motor speed sensor.
        refrigerant pressure during any necessary servicing or
                                                                         c. Flame roll out switch (automatic reset).
        troubleshooting, without losing charge.
                                                                         d. Flame proving controls. Unit shall have two independent
                                                                            stages of capacity.
Unit shall be capable of starting and running at 125° F outdoor         • Roof Curb - 14" high, full perimeter curb with wood nailer
temperature, exceeding maximum load criteria of AHRI                      (shipped knocked-down).
Standard 340/360. The compressor, with standard controls,               • 100% Barometric Relief Damper - Contains a rain hood,
shall be capable of operation down to 25° F outdoor                       air inlet screen, exhaust damper and mounting hardware.
temperature. Unit shall be provided with fan time delay to                Used to relieve internal air pressure through the unit.
prevent cold air delivery before heat exchanger warms up (Gas           • Propane Conversion Kit - Contains new orifices and gas
heat only).                                                               valve parts to convert from natural to L.P. gas. One per
                                                                          unit required.
Electrical Requirements
                                                                        • High Altitude - Natural Gas - Contains orifices required
All unit power wiring shall enter unit cabinet at a single factory        for applications between 2000 and 6000 feet altitude.
provided location and be capable of side or bottom entry, to
                                                                        • High Altitude - Propane Gas - Contains orifices required
minimize roof penetrations and avoid unit field modifications.
                                                                          for applications between 2000 and 6000 feet altitude.
Separate side and bottom openings shall be provided for the
                                                                          Must be used with propane conversion kit.
control wiring.
                                                                        • Burglar Bars - Designed to work with above roof curbs,
Standard Limited Warranties                                               depending on unit model. Fits duct openings of curb
                                                                          supply and return air openings.
    • Compressor 5 Years
                                                                        • Side Duct Flange - Supply and return air duct flanges for
    • Heat Exchanger 10 Years
                                                                          side duct applications. Do not use on units with power
    • Other Parts 1 Year                                                  exhaust.
Optional Outdoor Air (Shall be made available by either/or):            • Wood Skid - Allows unit to be handled with 90" forks.
                                                                        • Economizer/motorized Damper Rain Hood
    • Dry Bulb Economizer - Outdoor and return air dampers                (ZFN/E/C240 only) - Contains all hood panels and the
      that are interlocked and positioned by a fully-modulating,          hardware for assembling.
      spring-return damper actuator. The maximum leakage
                                                                        • Anti-Recycle Timer - Assures 5-minute off time between
      rate for the outdoor air intake dampers shall be designed
                                                                          compressor cycles.
      to meet ASHRAE 90.1-2010, AMCA 511 Class 1A
      damper, and the International Energy Conservation Code            • Coil Guard Kit - Guard for cooling coil.
      (IECC) certification requirements by achieving leakage
                                                                     OTHER FACTORY INSTALLED OPTIONS
      rates of 3 cfm/sq. ft. at 1" of static pressure. During
      economizer operation, a mixed-air temperature control             • Power Exhaust Option - To work in conjunction with
      shall modulate the outdoor and return air damper                    economizers.
      assembly to prevent the supply air temperature from               • Stainless Steel Heat Exchanger
      dropping below 55°F. Changeover from compressor to
                                                                        • Stainless Steel Drain Pan
      economizer operation shall be provided by an integral
      electronic enthalpy control that feeds input into the basic       • E-Coat Epoxy Polymer Coated Condenser and
      module. The outdoor intake opening shall be covered with            Evaporator Coil
      a rain hood that matches the exterior of the unit. Water          • Electronic Single Enthalpy Economizer
      eliminator/filters shall be provided.                             • Dirty Filter Switch
     Simultaneous economizer/compressor operation is also               • Phase Monitor
     possible. Dampers shall fully close on power loss.
                                                                        • Coil Guard
    • Motorized Outdoor Air Dampers - Outdoor and return
                                                                        • Bas Controls - Simplicity ® SE, CPC, HONEYWELL,
      air dampers that are interlocked and positioned by a 2-
                                                                          NOVAR
      position, spring-return damper actuator. The maximum
      leakage rate for the outdoor air intake dampers shall not         • BAS Ready Economizer (2-10 V.D.C. Actuator Without a
      exceed 2% when dampers are fully closed and operating               Controller)
      against a pressure differential of 0.5 IWG. A unit-mounted        • Hinged Filter Door Access And Tool Free Access
      potentiometer shall be provided to adjust the outdoor and           Panels
      return air damper assembly to take in the design CFM of           • Hinged Tool Free Blower, Blower Motor, Filter And
      outdoor air to meet the ventilation requirements of the             Electrical Access Panels
      conditioned space during normal operation. Whenever the
      indoor fan motor is energized, the dampers open up to             • 2" Pleated Filters, MERV 8
      one of two pre-selected positions - regardless of the             • 4" Pleated Filters, MERV 13
      outdoor air enthalpy. Dampers return to the fully closed          • Disconnect Switch
      position when the indoor fan motor is de-energized.
                                                                        • Supply Air Smoke Detector
      Dampers shall fully close on power loss.
                                                                        • Return Air Smoke Detector
Physical Data
Capacity Performance
ZF180-240 Cooling Capacities
  1. These capacities are gross ratings. For net capacity, deduct air blower motor heat, MBh = 3.415 x kW.
  2. Capacity ratings are based on 80°F (26.7°C) Entering Air Dry Bulb Temperature.
  3. These ratings are total input kW, thus include the two condenser fan motors, compressor motors, and the supply air blower motor at 0.40"
     WC.
  1. These capacities are gross ratings. For net capacity, deduct air blower motor heat, MBh = 3.415 x kW.
  2. Capacity ratings are based on 80°F (26.7°C) Entering Air Dry Bulb Temperature.
  3. These ratings are total input kW, thus include the two condenser fan motors, compressor motors, and the supply air blower motor at 0.40"
     WC.
  1. These capacities are gross ratings. For net capacity, deduct air blower motor heat, MBh = 3.415 x kW.
  2. Capacity ratings are based on 80°F (26.7°C) Entering Air Dry Bulb Temperature.
  3. These ratings are total input kW, thus include the two condenser fan motors, compressor motors, and the supply air blower motor at 0.40"
     WC.
  1. These capacities are gross ratings. For net capacity, deduct air blower motor heat, MBh = 3.415 x kW.
  2. Capacity ratings are based on 80°F (26.7°C) Entering Air Dry Bulb Temperature.
  3. These ratings are total input kW, thus include the two condenser fan motors, compressor motors, and the supply air blower motor at 0.40"
     WC.
Airflow Performance
ZF180-240 Side Duct Application
     1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.
     2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
  1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.
  2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
     1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.
     2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
  1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.
  2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
  3. kW = BHP x 0.838.
RPM Selection
   Size                                    Motor    Blower    6 Turns               5 Turns   4 Turns   3 Turns   2 Turns   1 Turn    Fully
           Model        HP     Max BHP
  (Tons)                                  Sheave    Sheave     Open                  Open      Open      Open      Open     Open     Closed
    180
             ZF        4.0       4.72     1VP62      BK75       925                  967       1009      1051      1093     1135      N/A
   (15)
    240
             ZF         6.3      7.13     1VP75     BK100       895                  926       956       987       1018     1049      N/A
   (20)
* Maximum blower speed is 1400 RPM for ZF180 and 1200 RPM for ZF240
Drive Selection
1.     6800 CFM
2.     2.0 iwg
3.     Using the supply air blower performance table below, the following data point was located: 1020 RPM & 5.92 BHP.
4.     Using the RPM selection table below, Size X and Model Y is found.
5.     5.92 BHP exceeds the maximum continuous BHP rating of the 5.0 HP motor. The 7.5 HP motor is required.
6.     1020 RPM is within the range of the 7.5 HP drives.
7.     Using the 7.5 HP motor and drive, 3.5 turns open will achieve 1020 RPM.
1.100
1.050
                                    1.000
                                                                                                                                Sea Level
                                    0.950
                Correction Factor
                                                                                                                                1000 ft
                                    0.900                                                                                       2000 ft
                                                                                                                                3000 ft
                                    0.850
                                                                                                                                4000 ft
                                    0.800                                                                                       5000 ft
                                                                                                                                6000 ft
                                    0.750                                                                                       7000 ft
                                                                                                                                8000 ft
                                    0.700
                                                                                                                                9000 ft
                                                                                                                                10000 ft
                                    0.650
                                    0.600
                                              40           50           60             70          80           90            100
                                                                         Air Temperature (ºF)
1.100
1.050
                                     1.000
                                                                                                                         Sea Level
                                     0.950
                 Correction Factor
                                                                                                                        305 Meter
                                     0.900                                                                               610 Meter
                                                                                                                         914 Meter
                                     0.850
                                                                                                                         1219 Meter
                                     0.800                                                                               1524 Meter
                                                                                                                         1829 Meter
                                     0.750                                                                               2134 Meter
                                                                                                                         2430 Meter
                                     0.700
                                                                                                                         2743 Meter
                                                                                                                         3048 Meter
                                     0.650
                                     0.600
                                                   4.4   10           15.5      21        26.6              32          38
                                                                         Air Temperature (ºC)
Sound Performance
ZF Indoor Sound Power Levels
                                                                                                        Sound Power, dB (10-12) Watts
       Size                          ESP           Blower                             1
                        CFM                                           Sound Rating                            Octave Band Centerline Frequency (Hz)
      (Tons)                        (IWG)
                                              RPM          BHP           dB (A)             63          125       250     500           1000     2000         4000    8000
     180 (15)           6000         1.0      1,080        4.6             91               88          90        90       87            85       81           81      76
     240 (20)           8000         1.0      1,020        6.6             86               85          85        83       82            82       78           75      70
     1. These values have been accessed using a model of sound propagation from a point source into the hemispheric/free field. The dBA values
        provided are to be used for reference only. Calculation of dBA values cover matters of system design and the fan manufacturer has no way
        of knowing the details of each system. This constitutes an exception to any specification or guarantee requiring a dBA value of sound data
        in any other form than sound power level ratings.
Electrical Data
ZF180 - 240
                                 Compressors
                                                           OD Fan   Supply    Pwr
                                   (each)                                                                                            Max Fuse2/
                                                           Motors   Blower   Conv             Electric Heat Option
  Size                                                                                                                       MCA1     Breaker3
            Volt                                           (each)   Motor    Outlet
 (Tons)                                                                                                                     (Amps)      Size
                          RLA          LRA        MCC                                                                                 (Amps)
  180     380-3-50   16.7       13   111   101   26 20.3    2.1      6.3       0      NONE        -        -          -      44.4       60
  (15)    415-3-50   16.7       13   111   101   26 20.3    2.1      6.7       0      NONE        -        -          -      44.8       60
  240     380-3-50   18.6   17.9     118   118   29   28    2.1      8.2       0      NONE        -        -          -      53.6       70
  (20)    415-3-50   18.6   17.9     118   118   29   28    2.1      9.1       0      NONE        -        -          -      54.5       70
                                                                             CONTROL
     THERMOSTAT                                                              TERMINAL
      TERMINALS                                                                BLOCK
                                                                                   W1
              W1
                                                                                   W2
              W2
                      1                                                            Y1
              Y1                                                                   G
              Y2                                                                   Y2
                                                                                   OCC
               G
                                                                                   X
               R                                                                   R
          3
               C                                                              SD-24
                                                                                   C
                                                                                                                                Smoke
              RC                                                                                                               Detector
                      4
              OCC                                                                          C
                      5
               X                                                                          24V                                   24 VAC
                                                                                                                                Class 2
                                                                                           R
      1       Second stageŚĞĂƟŶŐŶot required on single stage heĂƟŶg units.
      2       Jumper is required if there is no Smoke Detector circuit.
      3       Jumper is required for any coŵďŝŶĂƟŽŶ of R, RC, or RH.
      4       OCC is an output from the thermostat to indicate the Occupied ĐŽŶĚŝƟon.
      5       X is an input to the thermostat to display Error Status condiƟons.
                                                                                  Y
                                                              X
                                                                                       FRONT
                                                       LEFT
                                         B                                                                                         C
                                                                                                                         B
                                                                  C                                                                                         D
     A                                                                                 A                                                          E
                                              FRONT                                                                                                      0)
                                                                                                                                 FRONT               ( 18 0)
                                                                                                                                                   )
                                                                                                                                                 4” 24
                                                                                                                                             4 (6 9”) (
                                                                                                                                           2     6
                            D                                                                                      F                     16 58 (
                                                                                                                                          17
ZF180-240 Unit Weights Imperial
   Size                  Weight (lbs.)   Center of Gravity 4 Point Load Location (lbs.)                                6 Point Load Location (lbs.)
              Model
  (Tons)              Shipping Operating   X         Y       A       B     C       D                          A         B       C      D        E                F
 180 (15)      ZF       1685      1680    66.5      45.7    391     443   449    397                         256       277     302    306      281              259
 240 (20)      ZF       2405      2400     70        44     558     590   643    609                         369       382     397    433      417              402
ZF180-240 Unit Accessory Weights Imperial                                       ZF180-240 Unit Accessory Weights Metric
                                                 Weight (lbs.)                                                                               Weight (kg.)
             Unit Accessory                                                                     Unit Accessory
                                             Shipping         Operating                                                                  Shipping      Operating
               Economizer                       165               160                                Economizer                            74.8             72.6
             Power Exhaust                      90                85                            Power Exhaust                              40.8             40.8
               Gas Heat1                        240               240                                Gas Heat1                            108.9             108.9
            Motorized Damper                    150               150                          Motorized Damper                            68                68
            Barometric Damper                   50                45                           Barometric Damper                           22.7             22.7
  Econ./Motorized Damper Rain Hood              60                55              Econ./Motorized Damper Rain Hood                         27.2             27.2
    Econ./Power Exhaust Rain Hood               95                90                   Econ./Power Exhaust Rain Hood                       43.1             43.1
               Wood Skid                        220               220                                Wood Skid                             99.8             99.8
                Roof Curb                       190               185                                Roof Curb                             86.2             86.2
  1. Weight given is for the maximum number of tube heat                          1. Weight given is for the maximum number of tube heat
     exchangers available (8 tube).                                                  exchangers available (8 tube).
Unit Dimensions
RETURN AIR
SUPPLY AIR
                                                                    OUTDOOR AIR
                                                                    (Discharge)
                                                                    OUTDOOR AIR
                                                                    (Economizer)
RETURN AIR
SUPPLY AIR
                                                                                   OUTDOOR AIR
                                                                                   (Discharge)
                                                                                   OUTDOOR AIR
                                                                                   (Economizer)
                                                                                                                                                         EVAPORATOR
                                                                                                                                                         SECTION
                                                                                                                                                                 DOT PLUG
                                                              1026                                                                                               (For pressure
                                                            (40-3/8")                                                                                            drop reading)
                                                                                                                                                                 FILTER
                                                                                                                                                                 ACCESS
                                                                                    SUPPLY
                                                                                    AIR
                                                                                                  RETURN
                                                                                                  AIR
                                                         COMPRESSOR
                                                                                                                     OUTDOOR
                                                         ACCESS
                                                                                                                     AIR
                                                                                                                                                       1029
                                                          SUPPLY AIR
                                                                                                                                                     (40-1/2")
                                                          ACCESS                 474
                                                                               (18-5/8")
                                                                                                                                                         1" NPT FEMALE
                        Dimensions listed are for side                                  130                                                              COND. DRAIN
                                                                    RETURN AIR        (5-1/8")                                                           CONNECTION
                        duct flange openings; see                   ACCESS
                                                                                                   705
                                                                                                 (27-3/4")
                                                                                                                                            OUTDOOR AIR
                        Field Accessories for Side                                                           ZF180 727 (28-5/8”)            COMPARTMENT
                        Duct Flange Kit.                                   REAR                              ZF240 1006 (39-5/8")           ACCESS
VIEW
NOTE: Units are shipped with the bottom duct openings covered. An accessory flange kit is available for connecting side ducts.
                                                        ECONOMIZER
                                                        MOTORIZED
           SUPPLY AIR     POWER EXHAUST                 DAMPER
           COMPARTMENT    RAIN HOOD                     RAIN HOOD
                          (on Return Air Compartment)   (on Outdoor Air Compartment)        ECONOMIZER / MOTORIZED DAMPER
                                                                                            AND POWER EXHAUST RAIN HOODS
                                                                                                                   FIXED
                                                                                                                   OUTDOOR AIR
                                                                                                                   INTAKE HOOD
                                                                                                                   (located on
                                                                                                                   Return Air
                                                                                  930                              Compartment)
                                                                                (36-5/8”)
                                                                                                                                             25 (1“) CONDENSATE
                                                                                                       410                                   DRAIN
                                                                                                     (16-1/8”)                               (Must be trapped)
127 (5”)
                                                                                                716                                  2337
                                                                                             (28-3/16”)                              (92”)
                                                                        DETAIL “Y”
                                                                  UNIT WITH RAIN HOODS
Unit Clearances And Rain hood Dimensions (15 & 20 Ton)