AL624
Linear Power Supply/Charger
                                                           Overview:
Altronix AL624 linear power supply/charger converts low voltage AC input into 6VDC or 12VDC @ 1.2A or 24VDC @ 750mA of
continuous supply current (see specifications). This general purpose power supply has a wide range of applications for access
control, security, and CCTV system accessories that require additional power.
                                                       Specifications:
Input:                                                         Visual Indicators:
• 16VAC to 24VAC, 20VA to 40VA                                     • AC input and DC output LED indicators.
  (Transformer Selection Table).                                   Features:
Output:                                                 • Extremely compact design.
•	Switch selectable 6VDC-12VDC-24VDC.                  • Battery leads included.
• 6VDC or 12VDC @ 1.2A or 24VDC @ 0.75A supply current. • Snap Trac compatible (order Altronix model #ST3).
• Filtered and electronically regulated output.         • DIN Rail mount version available
• Short circuit and thermal overload protection.          (order Altronix model #DPS1).
Battery Backup:                                                    Board Dimensions (L x W x H approx.):
•   Built-in charger for sealed lead acid or gel type batteries.      3” x 2.5” x 1.125” (76.2mm x 63.5mm x 28.6mm).
•   Automatic switch over to stand-by battery when AC fails.
•   Maximum charge current 0.3A.                                                             FACTORY SET AT 12V
                                                                                             CUT J1 FOR 24V
•   PTC battery protection.                                                                  CUT J2 FOR 6V
                                                                                              J1
                                                                                              J2
Voltage Output/
Transformer Selection Table:
Output                Voltage Selector (JMPR)                Transformer
                                                            16.5VAC / 20VA
12VDC @ 1.2A           Leave J1 and J2 Intact          (Altronix model TP1620)
                                                             24VAC / 40VA
24VDC @ 750mA            Cut Jumper J1 Only            (Altronix model TP2440)
                                                             12VAC / 20VA
6VDC @ 1.2A              Cut Jumper J2 Only                                                 AC                                   DC
                                                       (Altronix model TP1220)
                                                                                                     AC AC        + DC – BAT +
                                               Installation Instructions:
1. Mount AL624 in the desired location/enclosure (mounting hardware included).
2. Unit is factory set for 12VDC. For 6VDC output cut jumper J2, for 24VDC output cut Jumper J1.
3. Connect proper transformer to the terminals marked [AC] (refer to Voltage Output/Transformer Selection Table).
   Use 18 AWG or larger for all power connections (Battery, DC output).
4. Measure output voltage before connecting devices. This helps avoiding potential damage.
5. Connect devices to be powered to the terminals marked [+ DC] and [DC - BAT], carefully observing polarity.
6. Connect battery to the terminals marked [BAT +] and [DC - NEG] (battery leads included)
   Note: To avoid damage connect batteries as follows:
   - For 6VDC operation connect one (1) 6VDC battery.
   - For 12VDC operation connect one (1) 12VDC battery or two (2) 6VDC batteries wired in series.
   - For 24VDC operation connect two (2) 12VDC batteries wired in series.
   Note: When batteries are not used, a loss of AC will result in a loss of output voltage.
                                                     LED Diagnostics:
Red (DC)                 Green (AC)             Power Supply Status
ON                       ON                     Normal operating condition.
ON                       OFF                    Loss of AC. Stand-by battery supplying power.
OFF                      ON                     No DC output. Short circuit or thermal overload condition.
OFF                      OFF                    No DC output. Loss of AC. Discharged or no battery present.
                                                Terminal Identification:
Terminal Legend          Function/Description
AC / AC                  Low voltage AC input (refer to voltage output/transformer selection table).
+ DC –                   6VDC-12VDC @ 1.2A continuous supply current or 24VDC @ 750mA continuous supply current.
– BAT +                  Stand-by battery connections. Maximum charge rate 300mA.
Altronix is not responsible for any typographical errors.
––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––
140 58th Street, Brooklyn, New York 11220 USA | phone: 718-567-8181 | fax: 718-567-9056
website: www.altronix.com | e-mail: info@altronix.com | Lifetime Warranty
IIAL624 - Rev. 050405                                         G12V                                               MEMBER