Koc Ar 001 R0 28 11 2019
Koc Ar 001 R0 28 11 2019
FOR
STANDARDS TEAM
DOC. NO. KOC-AR-001 Page 2 of 59 REV. 0
TABLE OF CONTENTS
Page No.
FOREWORD 4
1.0 SCOPE 5
2.0 APPLICATION 5
3.0 TERMINOLOGY 5
3.1 Definitions 5
3.2 Abbreviations 5
15.0 DOCUMENTATION 45
15.1 General 45
15.2 Reports 46
15.3 Submittals 46
ACKNOWLEDGEMENT 59
DOC. NO. KOC-AR-001 Page 4 of 59 REV. 0
FOREWORD
This KOC Recommended Practice has been approved by the Standards Team in
consultation with the ESTC Sub-committee (Technical) for use throughout the Engineering
and Operational Functions of Kuwait Oil Company (K.S.C.).
a) To provide general technical inputs and guidance for developing project specifications
and design / construction drawings in order to ensure reliable and quality works.
b) To establish and ensure effective, functional spatial design while optimising resources
and promoting sustainability culture in the Company.
c) To unify the facade of KOC Buildings and provide unique image to KOC Buildings.
Feedback as well as any comments or suggestions derived from the application of this
Recommended Practice at any stage of design, construction, installation, maintenance and
field experiences are invited and shall be directed to:
1.0 SCOPE
1.1 This Recommended Practice (RP) specifies the basic technical requirements and
defines the engineering architectural works design basis for KOC buildings.
1.2 It describes minimum aspects shall be considered during design for the preparation
of the architectural contract documents.
1.3 This Recommended Practice shall be used as a guidance to develop complete set
of architectural drawings and documents, which are required to construct, extend
and refurbish the KOC buildings.
1.4 Structures or Shelters, which support or house process equipment are excluded
from the scope of this Recommended Practice.
2.0 APPLICATION
2.1 Architectural design works shall confirm to the requirements of the document and
further shall refer to Codes and Standards mentioned herein.
2.2 Compliance with this KOC Recommended Practice does not of itself confer
immunity from legal or statutory obligations.
2.3 Any exceptions or deviations from this Recommended Practice, along with their
merits and justifications, shall be brought to the attention of KOC’s Controlling Team
for their review, consideration and amendment by Standards Team (if required).
3.0 TERMINOLOGY
3.1 Definitions
For the purposes of this Recommended Practice, the following definition shall apply.
Building Information Modelling (BIM) is the creation of a single 3D model for the
project to which the designers, constructors and owners will contribute as well as
its a process focused on the development, use and transfer of a digital information
model of a building project to improve the design, construction and operations of a
project or portfolio of facilities.
3.2 Abbreviations
4.1 Conflicts
In the event of conflict between this Recommended Practice and the latest edition
of Standards / Codes referred herein, or other purchase or contractual
requirements, the most stringent requirement shall apply. If further clarifications are
required, the subject shall be brought to the attention of KOC Controlling Team.
The latest edition of the following Standards, Codes and specifications (including
amendment, if any) shall apply:
International Standards
American Architectural Manufacturers Association (AAMA)
American Association of Textile Chemists and Colorists (AATCC)
American Iron and Steel Institute (AISI)
American Society of Heating, Refrigerating and Air-Conditioning Engineers
(ASHRAE)
Architectural Graphic Standards (The American Institute of Architects)
Architectural Time Savers Standards
British Standards Institution (BSI)
Ceilings and Interior Systems Construction Association (CISCA)
Consumer Product Safety Commission (CPSC)
Door and Access Systems Manufacturer's Association (DASMA)
Door and Hardware Institute (DHI)
Factory Mutual Engineering Corporation (FMEC)
Factory Mutual Research Corporation (FMRC)
Federal Specifications (FED SPEC)
Federal Standards (Fed-STD)
Flat Glass Marketing Association (FGMA)
GS-11 (Green Seal Standard for Paints, Coatings, Stains and Sealers)
GS-36 (Green Seal Standard for Adhesives for Commecial Use).
International Council of Building Officials (ICBO)
International Existing Building Code (IEBC)
International Organization for Standardization (ISO)
Metric Handbook: Planning & Design Data
National Environmental Policy Act (NEPA)
National Woodwork Manufacturers Association (NWMA)
Nationally Recognized Testing Laboratory (NRTL)
Neufert Architect’s Data ebook
Occupational Safety and Health Administration (OSHA)
Steel Door Institute (SDI)
Steel Structures Painting Council (SSPC)
The Laboratory Products Association (LPA)
Tile Council of North America (TCNA)
UL-2818 (GREENGUARD Certification Program for Chemical Emissions for
Building Materials, Finishes and Furnishings)
United States Gypsum (USG)
DOC. NO. KOC-AR-001 Page 8 of 59 REV. 0
5.1 The environmental conditions in Kuwait are severe and shall be considered
carefully for selection and installation of materials. Due regard shall be given to the
consistently high levels of solar radiation experienced in Kuwait, which may develop
surface temperatures of over 80 C (176 F) in exposed metals. The atmosphere
shall be considered to be dusty, corrosive and humid with extreme ambient
temperature. The atmosphere may also contain traces of H2S / SOx / NOx gases
and airborne chemical contaminants.
5.2 Refer to KOC-G-007 “KOC Standard for Basic Design Data” which provides the
relevant information regarding the environmental, site and utility supply conditions
prevailing throughout the KOC Facilities.
All applicable HSE requirements as per the relevant National and International
Standards shall be considered during the design of the buildings, especially
consideration of environmentally sustainable requirements.
7.1 General
c) The buildings shall be designed and constructed to house the staff including
physicaly challenged persons and / or equipment in order to meet all the
requirements of functionality, operation, safety, security, emergency response
and evacuation, convenience, accessibility, ergonomics, cost effectiveness,
preservation and sustainability aspects.
7.2.1 General
(i) using clay brick or sand lime brick claddings for external walls;
(ii) pitched roof with clay roof tiles or flat concrete roof with clay roof tiles
installed in sloping pattern along external perimeter of building’s parapet
and;
d) For Control Rooms, a detailed study shall be performed to satisfy all Human
Centered Design (HCD) requirements including but not limited to the following:
(i) Efficient and reliable working and movement within control room.
e) The study shall cover the layout, spaces, access, functional areas,
communication, workstation / seating, console design, furniture, lighting, noise-
control, HVAC, colour / texture of walls, flooring / ceiling, finishes material, fire
& smoke detection, fire fighting, emergency evacuation etc. consideration for
future expansion and practical connection to the existing facilities.
a) All buildings shall maintain a minimum offset of 8.0 m from adjacent street
kerbstone for the building front side and a minimum of 2.0 m from adjacent
buildings in rear and sides.
b) Sand Protection
Type of sand / dust protection measures shall be decided based on the location
of structures / buildings / equipment and their criticality.
DOC. NO. KOC-AR-001 Page 12 of 59 REV. 0
(i) Subject to project requirements, for mega complex buildings which are
located in desert area, a study and execution plan shall be carried out
for the plantation of a green belt within the reserved space for the project
in order to minimise dust / desertification impacts to building occupants.
(ii) Subject to project requirements, for other buildings / projects which are
located in desert area, a minimum of 2.0 m high cluster of trees should
be planted 1.0 m after the fence (outside) to minimise dust /
desertification impacts to building occupants, taking into consideration
all security requirements or any other suitable measures approved by
KOC.
a) The site planning shall be in accordance with the applicable KOC Standards,
Kuwait Local Standards and International Standards, whichever is more
stringent shall apply. Site planning of buildings shall take into account all
aspects like existing site context, land use, inter-relationship of the buildings
with the whole system, traffic and road network, safety regulations, service
network, fire & safety, climatic and environmental aspects, site conditions like
site dimension, contours, sewage, surface drainage, noise control level,
visibility, future expansion, visual aspects, privacy of occupants (especially for
residential buildings), etc.
c) Climatic factors like prevailing wind direction, solar geometry shall be taken into
account in orienting the building. Orientation of building shall also consider easy
access to the main entrance, heavy rainfall, noise and smell propagation, views
and visual effect from various directions.
d) Sufficient outdoor open spaces shall be provided in the vicinity of buildings for
landscaping and recreation / sports (if required). Open spaces in and around
buildings shall be proportional to the height of the structure.
e) Site plan shall also taken into account of landscaping aspects. The inherent
characteristics of site, such as contours, land form, vegetation and terrain shall
be fully utilised in the design.
g) The clearance requirement of the buildings from the buried pipelines, cables,
underground structure shall be studied and building location at site shall be
suitably selected.
DOC. NO. KOC-AR-001 Page 13 of 59 REV. 0
h) The adjacent oil and chemical plants shall be considered in the design while
deciding the location of the building in the plant areas. The hazard assessment
of each plant operation shall be used to help establish the layout or orientation
of blocks within the plant. Sub-divide the overall site into general areas
dedicated to process units, utilities, services and offices.
i) Servicing and loading areas in buildings should be located at the rear or side
of buildings avoiding public view from main road / main entrances. Access to
servicing and loading areas should preferably be provided from secondary
roads to avoid traffic concerns.
a) Buildings located within Ahmadi township area shall not exceed Three (3)
floors and the elevation / height of the buildings shall not exceed the height of
the KOC Main office building.
b) Residential buildings shall not exceed One (1) floor (with attic space used for
utilities purposes only).
c) Height of the external fence for residential buildings shall not exceed 3 m,
while other buildings fence shall be constructed as per KOC security
requirements and Security Vulnerability Assessment (SVA).
1:20 5.00 9 45
1:16 6.25 8 50
1:14 7.14 5 35
1:12 8.33 2 15
(i) The minimum clear width of a one way ramp shall be 1000 mm and a
two way ramp 2000 mm.
(ii) Handrails shall be installed on both sides of the ramp and the ramp
handrail shall extend 400 mm into the platform. Handrail height shall be
in between 850 mm to 950 mm except for curb ramps and ramps with
rise / height of 150 mm or less.
(iii) The maximum length of the ramp shall be 9 m for single span.
(ii) Provide a ramp adjacent to the car bay with minimum width of 900 mm.
(iii) All buildings must allow 1.2 m safe distance from front and rear sides for
the safe movement of physically challenged people.
(iv) Roads adjacent to the parking for physically challenged people shall be
3.9 m for one way streets and 7.2 m for two way streets.
c) Walkways
Provide a rough surface and avoid any ground obstacles on the walkway. In
case where manholes are used, the manhole cover shall be at same level of
the walkway. The minimum width of the walkway shall be 2.5 m from the car
parking to the main entrance. Sunshade for walkways shall be provided.
d) Toilets
For all buildings, one male & one female toilet on each floor shall be provided
and equipped with all necessary accessories / fittings for physically challenged
people.
(i) Provide an obstacles free clear space of 1600 mm diameter for ease of
access at the entrance and exit of the toilet.
(ii) Doors shall open outwards, the minimum width of the door shall be
900 mm, provide push plate at a height of 300 mm – 400 mm from the
floor level.
(iii) Toilet stall along with all necessary fittings shall be fixed at a height of
750 mm - 1250 mm.
Minimum clear inner length & width shall be 2200 mm & 1500 mm
respectively.
(v) The toilet accessories shall include but not limited to the below:
Wash basin, grab bar, toilet bowl, flip-up grab bar, mirror, toilet roll, hand
air dryer, coat hooks, trash bins, toilet paper dispenser, liquid soap
dispenser and paper towel dispenser.
DOC. NO. KOC-AR-001 Page 15 of 59 REV. 0
e) Doors
(i) The minimum width of doors shall be 900 mm equipped with pushing
plate 300 mm - 400 mm from the floor level to avoid scratching of doors.
(ii) All emergency doors shall open outwards and provide ramps.
f) Elevators
(iii) The height of “emergency button” inside the cabinet shall be fixed at a
range of 750 mm -1200 mm from floor level.
a) Indoor Lighting
(i) The lighting design shall integrate and align with the building envelope
design (i.e. window fenestration) in order to leverage optimal use of
daylight and achieve energy savings and comfort.
(ii) The lighting system shall achieve desired efficiency, flexibility of use,
easy maintenance in line with the use of the space and minimum
illumination requirements as per the relevant KOC Standards and
International Codes.
(iii) The lighting design shall include appropriate selection of light fixture
(luminaire) type, lighting control, illumination levels, location as per the
type & use of the building / space, while avoiding glare & over-lighting to
maximise opportunities for energy conservation.
DOC. NO. KOC-AR-001 Page 16 of 59 REV. 0
b) Outdoor lighting (for parking areas, street lighting, external building, landscape
& signage).
(i) The lighting design shall provide cohesive and homogeneous
illumination to ensure adequate light levels for safety and uniformity
while avoiding glare, over lighting, light trespass and sky glow.
(ii) Landscape lighting shall be carefully shielded to avoid view of light
source and sky glow where applicable. The design shall be in line with
IESNA design guide.
(iii) The light fixtures shall be appropriate style for architectural design of the
building, reflect the architectural language and enhance the aesthetics
of the building & its context.
c) Specially for guard house, the lighting ratio of outside to inside shall be 7:1 for
clear visibility during night.
7.2.7 Landscaping and Paving Around Buildings
a) Subject to project requirements, the outdoor soft landscape area including
trees and shrubs shall be 25 % of the proposed development area fitted with
water efficient irrigation system around non-process / non-plant / non-
industrial buildings for purpose of enhancing building design, public views and
spaces, providing buffers, transitions and screening. Outdoor landscape shall
be fitted with chairs, lights and walkways whenever applicable. Residential
buildings shall have a minimum of 25 % of the building footprint as front and
rear garden areas.
b) Subject to project requirements, unused areas, within project boundary, not
intended for a specific use or planned for future phases or area which are
neither asphalted nor covered by paving blocks shall be landscaped with
existing natural vegetation, native grasses or 100 mm thickness natural gravel
to be laid evenly and compacted to the required levels as directed by KOC.
7.2.8 Essential Building Services
Following essential services shall be provided, unless specified otherwise in the
contract documents.
a) Water Supply & Distribution, Drainage and Sanitary Services.
All buildings with human occupancy shall have toilets / pantries with both hot
and cold water facilities. Drinking water shall be provided outside and away from
the toilets within an enclosure. Water meters shall be provided for each building
to monitor water usage.
(i) Necessary arrangement shall be made for collection of surface drainage
i.e. from roads, walkways, open yards, car park & roof drainage and can
be discharged directly to storm water system.
(ii) Sanitary sewage from the buildings shall be collected and treated in
accordance with KOC-C-025 “KOC Recommended Practice for Drainage
Systems - Design, Materials and Construction”. All service pipes routed
on the external wall shall be suitably concealed.
DOC. NO. KOC-AR-001 Page 17 of 59 REV. 0
b) Electrical Services
Electrical services for buildings consists of electrical supply, distribution, internal
& external lighting systems, exhaust fans, earthing & lightning protection
systems, including all their accessories, cabling systems etc. shall be in
accordance with relevant KOC Electrical Standards. Electrical meters shall be
fitted to measure and record electricity demand and consumption of electricity
used in specific areas / individual equipment of workshop.
c) Air Conditioning System
f) Other Services
Functional spaces of any building are the space required by the occupants (the
requesting / end user KOC Teams) to perform the required activities to be executed
in that specific building. Various spaces / rooms shall be sized suitably and shall be
integrated logically to generate the overall building layout plan based on the following
considerations:
a) Activities.
d) Safety regulations.
e) Ergonomics.
f) Acoustics.
h) Security.
i) Cost effectiveness.
j) Aesthetics.
DOC. NO. KOC-AR-001 Page 19 of 59 REV. 0
k) Emergency evacuation.
Circulation spaces required for integrating various types of spaces and as means of
access / egress etc. shall be provided as per project requirements for the building
and mainly consisting of:
b) Staircases.
d) Walkways.
f) Emergency exits.
g) Elevators / escalators.
Amenity spaces shall be provided as per project requirements for the building,
depending on gender, designation and number of building users / occupants and
mainly consisting of:
d) Wash room.
e) Pantry.
f) Prayer room.
g) Ablution area.
h) Store room.
DOC. NO. KOC-AR-001 Page 20 of 59 REV. 0
Utility spaces required for utility services like air-conditioning, electrical, telecom etc.
shall be provided as per project requirements for the building and mainly consisting
of:
a) HVAC room.
d) Battery room.
7.3.5 Parking
a) Spaces
(iii) Provide access points and crosswalks from parking areas to facility
entries.
(iv) Parking spaces for a facility shall not be more than 75 m from the facility
entrance.
(v) Parking spaces shall be shaded with cantilever type for offices and
recreational buildings.
(vi) Locate entrances and exits away from busy intersections.
(vii) Locate aisles and rows of parking parallel to the long dimension of the
site with parking on each side of an aisle.
(viii) The minimum setback between parking area curbing and facility walls
is 6.0 m and parking area entrances & exits from roadway intersection
is 15 m - 45 m.
(ix) Parking area pavement slopes shall be in accordance with
KOC-C-002 “KOC Recommended Practice for Engineering Design
Basis of Civil and Structural Work”.
DOC. NO. KOC-AR-001 Page 22 of 59 REV. 0
(x) Storm water collection shall depend on the size of the parking area.
Preferably, shall be collected through circulation aisle in between the
parked areas (stalls).
(xi) The radius of a parking entry or exit should be at least 4 m. The parking
radius should be 13 m when it is expected to use by buses or tractor
trailers. Interior radii for perimeter curbing and islands can be reduced
to 2 m. Inside turning radius of at least 4 m on all internal vehicle
circulation aisles.
In general, finished floor level of buildings shall be determined with respect to top
of approach road or pavement. For more detail on finished floor level KOC-C-002
“KOC Recommended Practice for Engineering Design Basis of Civil and Structural
Work” shall be referred.
The minimum width of platform parallel to the door shall be 1200 mm or maximum
door width + 400 mm and minimum length of platform shall be same as the door
width and shall be provided in between entrance door and steps / ramps. This shall
not be applicable for the main entrance of a building that may require larger width
and length of the platform. The following dimensions for the steps / ramps should
be adhered to:
Sl.
Description Steps and Ramps Sizes
No.
280 mm (minimum) for non-process / non-plant / non-industrial buildings.
1 Tread
For process / plant / industrial buildings, KOC-C-007 shall be referred.
150 mm to 160 mm (maximum) (up to 180 mm for fire stair) for non-process
2 Riser / non-plant / non-industrial buildings. For process / plant / industrial
buildings, KOC-C-007 shall be referred.
Stair or staircase flight 1000 mm (minimum) for non-process / non-plant / non-industrial buildings.
3
width & ramp width For process / plant / industrial buildings, KOC-C-007 shall be referred.
4 Clear width of landing 1200 mm (minimum).
Number of risers per 13 nos. (maximum) for non-process / non-plant / non-industrial buildings.
5
flight For process / plant / industrial buildings, KOC-C-007 shall be referred.
Vehicular ramp slope 7 % in general. However, the slope can be increased up to 12 % in case
6
(maximum) of limitation of available space.
a) For upto 750 mm rise - provide slope / gradient 1 (v):12 (h) (max. length
of ramp not to exceed 9 m - provide intermediate landing (min. 1200
mm to 1500 mm wide) after 9 m length.
Pedestrian ramp slope
7
(maximum) b) For more than 750 mm rise - provide slope / gradient 1 (v):16 (h) (with
max. length of ramp not to exceed 12 m - provide intermediate landing
(min. 1200 mm to 1500 mm wide) after 12 m length.
8 Handrail height Height shall be 1000 mm (minimum) above finish floor level.
DOC. NO. KOC-AR-001 Page 23 of 59 REV. 0
a) In General Buildings:
b) 40 m2 (minimum) up to 15 persons.
Conference room
c) 25 m2 (minimum) up to 10 persons.
b) In residential buildings:
7.3.9 Minimum False Ceiling Heights: (Measured from Finish Floor Level)
All height dimensions are to underside of ceiling or beams, whichever is at the lower
level:
All doors over 2200 mm high can be provided with removable transoms panel of
sufficient size to suit all plant access and removal, subject to KOC approval.
7.3.11 Windows
a) The windows shall be suitably located to provide views to the outdoors for light
& visual relief with 50 %, 75 % & 90 % of external wall area as glazed openings
on suitable facades, where feasible within the constraints of the environment.
Blast resistant buildings shall be typically without windows in line with the
recommendation of KOC-C-030 “KOC Recommended Practice for Blast
Resistant Design of Buildings”.
b) Non-blast resistant buildings which are located inside oil fields in that case all
external windows of the buildings should be fixed closed type because of dust,
safety (H2S and other harmful gas leaks) and security reasons.
DOC. NO. KOC-AR-001 Page 26 of 59 REV. 0
c) Appearance, function, heat gain & loss, maintenance & operation, safety,
structural requirements and stability against environment shall be considered
while designing the size of the window and selecting window glazing. Sill of
windows shall be as per engineering design requirements. Where mullion are
provided for windows, in such cases design of mullion shall be decorative.
Windows shall be designed with suitable sealing to avoid dust ingress into the
room.
a) Workplace amenities (fitness room, recreation rooms, etc.) and facilities shall
be provided for the health, welfare and personal hygiene needs of employees
as per project requirements. They shall include toilets, shelter, seating, dining
rooms, change rooms, drinking water, personal storage and washing facilities.
They shall also include work environment facilities such as workspace,
temperature and air quality, lighting and flooring.
d) The prayer and ablution rooms (Male and Female) shall be provided for the
buildings as per project requirements.
e) The following accessories shall be provided but not limited to the below:
The aesthetics, quality of the interior furnishings and graphics shall be good quality,
commercial design with clean lines, high-tech appearance and shall feature
durability, strength and comfort. This applies to:
c) Upholstered furniture.
d) Laboratory furniture.
f) Miscellaneous furniture.
The building design shall incorporate safety & security measures to meet the design
criteria, relevant codes and project requirements as applicable.
a) Safety
Designs for buildings shall adequately provide life safety features relative to
fire, natural calamities, collapse and aid life safety in similar emergencies. The
designs shall incorporate but not limited to the following:
(v) Appropriate fire rated doors, windows, walls and glazing etc. which shall
be in accordance with KOC-C-001 “KOC Standard for Basic Civil
Engineering Design Data”.
(vii) Appropriate signage and graphics both for building identification and
interiors in both Arabic and English language.
(viii) Fire protection and detection system, fire fighting & safety equipment.
(x) Emergency evacuation arrow sign, emergency alarm button, panic bar
door and AED (Automated External Defibrillator).
b) Security
c) Emergency Exits
(i) Emergency exits shall be provided for all buildings, including individual
functional spaces such as console area and MCC area, etc. Minimum
Two (2) numbers of emergency exits including the entry door at each
floor shall be located in such a manner that escape route is direct,
unobstructed.
(ii) The two emergency exits shall be remote from each other and preferably
not facing any potential blast source. An equipment access door fitted
with a panic bar may act as an emergency exit for personnel.
(iv) Spiral stair, sliding door and revolving doors, lifts, cat ladders etc. shall
not be permitted as emergency exits.
(v) Fire escape routes including staircase, corridors etc. shall be adequately
illuminated and also visible exist sign shall be provided for all fire exits.
(vi) The fire escape routes shall be sufficiently protected from the effects of
fire and shall consider limiting the ingress of smoke from other areas.
(vii) Doors on the emergency escape routes shall open in the direction of the
escape route.
(viii) The need for easy and rapid evacuation during fire may conflict with
security control of entry / exit access doors. Such potential conflicts shall
be identified and resolved in the design to ensure fire rescue services
are not hindered in case of rescuing people trapped in fire.
(ix) All of the above shall be considered while developing the evacuation plan
for the building.
DOC. NO. KOC-AR-001 Page 29 of 59 REV. 0
7.3.15 Miscellaneous
a) Separate service entry shall be provided for service areas such as kitchen, air
conditioned pressurisation plant, electrical room, etc. A common service entry
may be provided depending on spatial arrangement.
b) An air lock lobby shall be provided for one external personnel entrance to each
air conditioned reception area of manned / office buildings, except at external
entrance to small air-conditioned room, like UPS rooms. Air locks shall not be
provided at equipment access doors.
Status Circular Appointed Employees (CAEs) Non Circular Appointed Employees (NCAEs)
Grade / Team Level / 18 &
CEO DCEO Manager 14 / 13 17 / 16 15 / 14 13 & Below
Grade Level Other CAEs Above
Office Space Office Space 70 m2 50 m2 35 m2 25 m2 21 m2 18 m2 15 m2 12 m2 Work Station
Standards
Admin. Asst.
Closed Office / Open Work Station /
(CEO’s Office) /
-- -- -- -- -- -- -- Closed Work Open Areas / Double
Admin. Asst.
Station Occupancy
(DCEO’s Office)
Attached
Secretarial Office
2. Wall paper (for CAEs only) will be in beige / white colour with self-design on.
3. Non-KOC employees will be allocated in workstations for the KOC grade equivalent 15 and below, grade 16-17 will have 12 m 2, grade 18 above will have 15 m 2,
the Project Leaders / Mangers will have 21 m 2 and only PMC Managers will have 25 m 2.
DOC. NO. KOC-AR-001 Page 31 of 59 REV. 0
Team Leader (Option A) Team Leader (Option B) Team Leader Secretary Grade 18
Sl. Sl. Sl. Sl.
Type of Furniture Qty. Type of Furniture Qty. Type of Furniture Qty. Type of Furniture Qty.
No. No. No. No.
Executive Desk Arc Top with Executive Desk Arc Top with Executive U Shaped
1 1 1 1 1 L-Shaped Desk [1] 1 1 1
Extension Extension Desk
Wood Bookcase Executive Ergonomic
2 High Executive Bookcase 1 2 High Executive Bookcase 1 2 1 2 1
Cabinet Chair
3 Executive Ergonomic Chair 1 3 Executive Ergonomic Chair 1 3 Ergonomic Chair 1 3 Wooden Guest Chair 2
4 Executive Wooden Guest Chair 2 4 Executive Wooden Guest Chair 2 4 Wooden Guest Chair 2 4 Small Coffee Table 1
5 Small Coffee Table 1 5 Small Coffee Table 1 5 Small Coffee Table 1 5 Credenza 1
6 Executive Round Meeting Table 1 6 Medium Coffee Table 1 -- -- -- -- -- --
7 Ergonomic Chair 4 7 Large Coffee Table 1 -- -- -- -- -- --
-- -- -- 8 3 Seat Sofa 1 -- -- -- -- -- --
-- -- -- 9 1 Seat Sofa 1 -- -- -- -- -- --
Multiple Occupancy
Grade 16 & 17 Grade 14 & 15 Grade 13 & Below
(Quantities Per Occupant)
Sl. Sl. Sl. Sl.
Type of Furniture Qty. Type of Furniture Qty. Type of Furniture Qty. Type of Furniture Qty.
No. No. No. No.
[1] L Shaped Desk
1 U Shaped Desk 1 1 L Shaped Desk 1 1 Workstation 1 1 1
(160 cm / 140 cm) [1]
Wood Bookcase
2 Wood Bookcase Cabinet 1 2 Wood Bookcase Cabinet 1 2 Ergonomic Chair 1 2 --
Cabinet [2]
3 Ergonomic Chair 1 3 Ergonomic Chair 1 3 Visitor Armchair 1 3 Ergonomic Chair 1
4 Wooden Guest Chair 2 4 Visitor Armchair 2 -- -- -- 4 Visitor Armchair [3] 1
5 Small Coffee Table 1 5 Small Coffee Table 1 -- -- -- 5 Small Coffee Table [3] 1
[1] Desk size subject to office space and available furniture.
[2] One wood bookcase cabinet to every two (2) occupants.
[3] Provision subject to office space and available furniture
DOC. NO. KOC-AR-001 Page 32 of 59 REV. 0
a) Drafting standards shall be applicable for all type of buildings, landscape and
interiors design documents. Drafting shall result in clear, legible and
graphically complete drawing documents incorporating line weight schemes
for readability. Proper pen assignments shall follow while printing. For more
details refer to EG-DO-C-001 “Engineering Drawing Practice Code”.
b) Minimum letter size (height) shall be 2.0 mm high for any scale.
d) Directional arrows shall be provided showing plant north, true north and
prevailing wind direction for the site plans and building floor plans. Grid lines,
bench marks, etc. to be included as appropriate.
8.2 Symbology
All dimensions, quantities and units of measurement used on the drawings and in
calculations shall be in SI units.
8.4 Scale
Description Scale
Site setting out plan for a large buildings 1:200 to 1:500
Building floor plans, elevations & sections 1:100 or 1:150 (As per the size of drawings)
Wall sections 1:25
Door, window and miscellaneous details 1:10 to 1:25
Kitchen / pantry and toilet layout and details 1:10 to 1:25
Staircase & handrail details 1:10 to 1:25
Floor pattern layout & details 1:50
Reflected ceiling plans 1:100
Landscape layout plans 1:100 & details 1:25
Furniture layout 1:50 & details 1:25
DOC. NO. KOC-AR-001 Page 33 of 59 REV. 0
8.6 References
Drawing cross referred with other disciplinary drawing shall be listed such as civil-
structural, HVAC, plumbing, instrumentation, electrical and fire protection, etc. as
applicable.
a) All projects shall adhere to Appendix-1 of this RP for typical finishing schedule
and shall be used as a general guidance.
10.1 General
The designer shall be responsible to verify the space requirements for operation,
service, maintenance and replacement etc. of all mechanical, electrical equipment
as per Manufacturer’s recommendations and shall design all spaces / rooms to
accommodate these requirements. The Contractor shall review all Manufacturer’s
drawings and KOC Standards as well as Government codes requirements to verify
that the drawings of the designer are in compliance.
a) The minimum requirements of the composite roofing system for flat slabs
which consist of different layers above the structural concrete slab shall be
selected from the following types with prior approval from KOC.
a.1) Type-1
a.2) Type-2
c) As a minimum, all the roofs shall be accessible by cage steel ladders. Air
conditioning equipment and / or any other equipment that are installed on the
roof of buildings which requires regular maintenance shall be accessible by
staircase. All roof top equipment shall be adequately set back from the
facades such that these are not visible from the surrounding areas / streets
and adequately enclosed using appropriate building materials, parapet height
and facade treatments.
e) Construction of external solid walls should be provided with sand lime / clay
brick for outer leaf and inner leaf of lightweight block work. The thickness of
the inner leaf shall be minimum 200 mm, subject to project type and design.
For more details KOC-C-008 “KOC Standard for Masonry Works and
Plastering - Materials and Workmanship” shall be referred.
b) All ceiling materials shall have a flame spread index of 25 or less and smoke
developed index of 0-450 when tested in accordance with ASTM E84.
DOC. NO. KOC-AR-001 Page 36 of 59 REV. 0
10.1.6 Doors
a) All entrance doors shall meet the design and architectural requirements and
shall be fire-rated or blast resistant as per project requirements. Doors shall
include hardware and weather-stripping. Vision panels if provided shall be
double paned insulated safety glass to match exterior windows.
b) Exterior steel doors should be insulated hollow metal door and frame, made
of galvanised steel, factory primed & painted.
c) Interior wooden doors shall be solid core wood veneer faced in hollow metal
frame. Plastic lamination shall not be used because of development of
dangerous gases in case of fire. Internal doors to toilets and showers shall
have a minimum 50 mm free opening or undercut from the finished floor.
Doors in corridors of office buildings should not be located directly opposite
each other. Doors should be preferably installed in niches, in order to create
more room in the corridor near the entrance of office rooms. 500 mm height
steel plate covering shall be provided on both sides of wooden door starting
from the bottom of the door leaf in all wet areas.
d) All external doors shall open outwards in the direction of the escape route and
shall be arranged to remain in the normally closed position with suitable self-
closing device. Each door assembly shall include the door, frame, anchors,
hardware and accessories all provided by a single Manufacturer. Panic bars
shall be installed for all emergency exits and the switchgear hall exits, both for
single and double-winged doors with overlapping astragal. Simultaneous
opening of double doors shall be ensured by slight pressure on any part of the
panic bar. The outside operation shall be made by lever handle with a dead
locking mechanism.
e) Subject to project requirements, all door lock hardware keying system shall
be co-ordinated with KOC plant keying system. All cylinders and keys shall be
integrated with the existing master key system.
f) The use of aluminium doors or door made of other materials shall be subjected
to KOC approval.
10.1.7 Windows
a) All internal partition walls constructed with concrete blocks, gypsum board or
any other type shall extend up to the underside of the roof slab or sheeting for
acoustic reasons and to provide specified noise control between the rooms /
spaces.
b) Metal studs and gypsum wall board shall be as specified in the construction
drawings.
c) Private office and other related spaces may be constructed of moveable wall
/ partition system as directed by KOC.
d) Interior masonry walls in all rooms, corridors and lobby to be plastered and
painted as noted in the finishing schedule. Plastering shall be up to the slab
soffit level including the part above false ceiling (if any).
e) Glazed ceramic shall be fixed up to one tile above false ceiling level in toilet
areas and in other rooms as indicated in the finishing schedule.
f) Acid / chemical resistant tiles for laboratories and battery rooms walls shall be
laid to full height of the room.
d) All skirting boards and cover strips shall be snugly fitted and durably fastened.
e) Wooden cover strips shall be mitred at covers and joints. They shall be fixed
at distances not exceeding 600 mm.
a) Minimum 100 mm thick sand cement block walls or modular solid phenolic
plastic, 26 mm thick toilet partitions or Cubicles shall be installed for built-in
ceramic tile toilets and shower rooms including all fixing accessories as
specified in the contract. Ironmongery shall be stainless steel.
b) Urinal screens shall be solid phenolic and wall mounted. For urinals, ceramic
partitions can also be used with prior approval from KOC.
c) Hardware for partition doors and urinal screens shall be stainless steel.
All toilet fixtures and accessories shall be made from brass and exposed parts shall
be stainless steel or chromium plated. Provide flexible hose union tap in a position
adjacent to each water closet. Type and model of all fixtures and accessories shall
be submitted for KOC approval. All the fixtures and accessories shall conform to
the requirements of KOC-AR-002 “KOC Standard for Architectural Finishes”.
Subject to project requirements, fixtures & accessories shall be provided which shall
include, but not limited to the following:
(ii) Hand spray with angle valve, hand trigger and 1000 mm long hose.
(v) 2 hand grips, 250 mm long each only for physically challenged persons.
(i) White ceramic squatting plate (500 mm x 400 mm approx.) with raised
treads for flush installation at floor level.
(ii) Hand spray with angle valve and hand trigger, 1000 mm long hose.
(v) 2 hand grips, 250 mm long each each only for physically challenged
persons.
c) Showers
(ii) Stainless steel towel rail (800 mm long), rope hook, soap tray, foot tray.
(iv) Granite / marble or corian vanity top with integrated ceramic bowl with
complete accessories.
Each rest rooms / Individual toilets shall be equipped with but not limited to
the following accessories:
(i) Water closet shall be western type or Asian squatting type as per KOC
approval. The number of toilet shall be 1 per 25 building occupants.
(iii) Hand spray with angle valve, hand trigger and 1000 mm long hose.
(vi) 2 hand grips, 250 mm long each each only for physically challenged
persons.
(x) Vitreous china shelves below the mirror (length matching to washbasin
and mirror) shall be installed above each washbasin.
(xii) Soap holder / dispenser, paper towel dispenser and hand dryer.
f) Ablution Room
All prayer rooms shall be provided with adjacent ablution facility. Ablution shall
include but not limited to the following:
Safety shower and eye wash shall be located near the exits of laboratories or
other hazardous areas. Safety shower and eye wash shall be in accordance
with KOC-L-009 “KOC Standard for Fire Protection Systems and Safety
Equipment”.
a) Pre-mirror polished, jet black granite or other KOC approved materials shall
be used for the countertops in kitchen, pantry and vanity top. Countertops
shall have a vertical facia of 300 mm from the countertop level to conceal
plumbing underneath countertops with 100 mm high backsplash.
b) Built-in-kitchens, ready to use with furniture (floor cabinets with work tops, sink
and wall cabinets) etc., of a modular system, with an elegant shape, safe and
ergonomic, hard-wearing and easy to clean shall be provided.
d) Sinks shall be stainless steel, generally rectangular in plan and with round
corners including all necessary fittings. The accessories shall be made of rust-
proof high quality stainless steel. For more details KOC-AR-002 “KOC
Standard for Architectural Finishes” shall be referred.
DOC. NO. KOC-AR-001 Page 41 of 59 REV. 0
Heavy-duty steel shelving shall be provided in store rooms and janitor rooms.
a) KOC logo shall be placed at each main entrance for office and recreational
buildings. The size of the logo shall match with the size and height of building.
b) Building name (in Arabic & English) with KOC logo shall be identified in front
of each main entrance. The building name shall be either on ground or wall
mounted.
c) Employee name plate (in Arabic & English) shall be placed in front of all offices
and cubicles identifying employee name and designation.
(i) Zoning and circulation strategy for signage and wayfinding shall be
developed for the building and for the site.
(iii) Signage and wayfinding schedule with specific message and symbols
for each sign.
Layout of shop equipment, cabinets, appliances and heavy duty warehouse racking
shall be provided as per project requirements. Circulation of forklift and trollies shall
be considered during design.
a) Interior design and furniture selection shall provide a high quality, commercial
design which provides a high degree of flexibility, functionality, ergonomic
design, strength, long standing, durability and sustainability.
b) Generally, fabrics (if any) shall be durable and washable. Materials and
finishes used should be easily and locally available. To minimise static
electricity generation in sensitive computer areas, wood or other non-
conductive materials shall be used rather than plastic coated or metal
furniture. For more information regarding furnitures, KOC Office
Administration Team should be contacted.
DOC. NO. KOC-AR-001 Page 42 of 59 REV. 0
All glazed areas which are subject to direct sunlight (if it is not conflicting with
concept and theme of elevations design) at any time of the day throughout the year
may be provided with external shading. Areas of both horizontal and vertical
shading shall be provided to cope with the angle of the sun anywhere on its path.
Solar shading shall be formed by a fixed system.
Refer to KOC-G-001 “KOC Recommended Practice for Green Buildings (New &
Existing)” in regards to usage of adhesives, adhesive bonding primers, adhesive
primers, sealants, sealant primers or any other primer, which have a VOC (Volatile
Organic Compounds) content.
Interior surface area covered by paints and coatings shall be less than the maximum
allowable VOC content limits specified in KOC-G-001 “KOC Recommended
Practice for Green Buildings (New & Existing)”. All paints and coatings shall be fugal
resistant.
a) Mega Complexes:
All projects shall have a dedicated mosque, KOC shall design the mosque
size / capacity according to the number of employees occupying / expected to
occupy inside the building & one female prayer room shall be provided.
b) Other Buildings:
Subject to project requirements, a dedicated male & female prayer room shall
be provided according to the number of employees occupying / expected to
occupy inside the building.
Appendix - 2 provides information and general guidance for each of the process /
plant / industrial buildings and their minimum requirements.
Appendix - 3 provides information and general guidance for each of the non-
process / non-plant / non-industrial buildings and their minimum requirements.
DOC. NO. KOC-AR-001 Page 43 of 59 REV. 0
13.1 Introduction
Life of existing buildings can be extended through the adaptation of their basic forms
to provide a new or updated appearance to the original structure. During
refurbishment of existing buildings below aspects shall be considered but limited to
the following:
a) The location, condition, shape and size of the existing structure / building.
d) Safe work.
e) Feasibility.
There are number of factors that should be included in the evaluation process and
which should be weighed as part of the overall decision process.
In addition to providing pleasant lighting and acoustics, the extension part shall have
an ambience that encourages its use and provides the users with an increased
comfort in building.
Decision to renovate / refurbish or build new should be taken based on the site
location and design implications.
13.2.4 Phasing
Renovation and expansion inevitably involve planning for phasing (especially if the
existing building is equipped during the construction) and possible surge space for
the period of construction. Depending on site conditions and the capacity of the
expansion space, the phasing should be simple, using the new expansion space as
surge space while the renovation work is being carried out.
DOC. NO. KOC-AR-001 Page 44 of 59 REV. 0
Design shall be according to the safety measures and risk management tips and
guidelines as specified. In addition, other site constraints need to be evaluated to
determine the impact on the options for expansion of existing structures.
13.2.7 For extension of any building, the following points shall be considered before
starting the design:
b) Site survey.
c) Re-route plan & drawings of the underground services, which conflict (if any)
with the new extension part.
An assessment study shall be carried out for upgrading the existing buildings
considering the followings but not limited to the below:
Sl.
Building Component Purpose of Assessment
No.
Seismic Resistance Determine what measures are likely to be required to meet current
1
Capacity codes & standards.
Evaluate if the floor loading capacity is adequate for shifting / removal
2 Structural Load Capacity / relocation of equipment etc. throughout the existing structure to
provide maximum flexibility.
Determine what features are particularly inefficient and need to be
3 Energy Efficiency
corrected. Retrofit features should be considered as necessary.
Study the heating / cooling systems and determine if they have
4 HVAC Systems
reached the end of their useful lives.
5 Electrical Systems Determine how extensive an upgrade will be required.
Evaluate the current illumination of existing building and how to make
6 Lighting energy-efficient and also evaluate the possibility of introducing extra
natural lighting.
Telecommunications and Determine the possibility to install new cabling in the existing building
7
Information Systems and how many new data closets needs to be added.
DOC. NO. KOC-AR-001 Page 45 of 59 REV. 0
Sl.
Building Component Purpose of Assessment
No.
Determine if this system needs to be upgraded to meet current
8 Fire Alarm
standards.
Evaluate security needs and assess the requirements of security
9 Security Systems
systems need to be installed.
Determine requirements for additional toilet & facilities and
10 Plumbing Systems
replacement of pipes, fixtures and fittings.
Determine the most feasible fire protection system that can be used
11 Fire Protection
for existing building.
Determine the extent of existing noise problems that need to be
12 Acoustics
addressed.
13 Accessibility Determine upgrades will be required to meet current requirement.
Determine if the existing equipment / machines etc. meets current
14 Equipment Systems standards and other code requirements and evaluate the feasibility
of keeping the existing equipment in place.
Conduct an overall review of the general condition of the existing
15 Architectural Systems building, including features such as roofing, windows, exterior
sheathing and ceilings etc.
Architectural Design Evaluate changes that will be required to improve the overall space
16
Features limits and other architectural features as per current requirements.
17 Interior Design Interior designing shall be based on ergonomic standards.
Determine if there are any special aspects of the existing building that
18 Miscellaneous
may have cost implications in a renovation option.
14.1 The Contractor shall operate a quality system preferably based on ISO 9000 series
of standards to satisfy the requirements of this Recommended Practice. The
Contractor shall demonstrate compliance by providing a copy of the accredited
certificate or the Contractor’s quality manual.
14.2 Verification of the Contractor’s quality system is normally part of the pre-qualification
procedure and therefore not detailed in the core text of this Recommended Practice.
15.0 DOCUMENTATION
15.1 General
15.1.1 All correspondence, instructions, drawings, design calculations or any other written
information shall be in the English language. In the case of dual languages, one
language shall be English.
15.1.2 All dimensions, units of measurement, physical constants etc. shall be in SI units,
unless otherwise specified in the project document.
15.1.3 In addition to the hard copies, all documents (text, specifications, drawings, design
calculations, etc.) shall be provided with electronic (editable & searchable PDF format)
files in the approved and widely used software (MS Word, Excel, Auto Cad etc.). All
calculations shall be submitted in approved and widely used software(s) agreed by
KOC.
DOC. NO. KOC-AR-001 Page 46 of 59 REV. 0
15.2 Reports
When buildings are being designed, depending on the building type / project
requirements, a selection of the following reports shall be submitted to KOC for
review:
15.3 Submittals
The architectural design work for the buildings shall include but not limited to the
following submittals:
d) Shop drawings for doors and windows. Doors & windows schedule including
Ironmongery and hardwares.
j) As-built Drawings.
DOC. NO. KOC-AR-001 Page 48 of 59 REV. 0
HVAC rooms,
firefighting cylinder Plastic acrylic co-polymer
High build, solvent free, hard wearing, 100 mm high Acrylic copolymer base washable
storage room, based washable emulsion
16 abrasion & chemical resistant, dust- epoxy paint emulsion paint system on plastered
generator room, stores, paint system on plastered
proof epoxy resin floor coating system. system. surfaces.
warehouses & surfaces.
workshop
Plastic acrylic co-polymer
Hard wearing, skid-resistant, 100 mm high Acrylic co-polymer base washable
based washable emulsion
17 Garage, fire stations waterproof, flexible, polyurethane epoxy paint emulsion paint system on plastered
paint system on plastered
based, traffic deck system. system. surfaces.
surfaces.
Chemical resistant glazed
Chemical resistant heavy duty non-slip
Chemical stores, ceramic wall tiles full height
vitrified ceramic floor tiles with Chemical resistant epoxy paint
18 battery room, analyser N/A or chemical resistant epoxy
chemically resistant tile adhesives and system on plastered surfaces.
room & sample area paint system on plastered
joint grouting.
surfaces.
Acoustic suspended ceiling of
Acrylic co-polymer base
100 mm high aluminium panels 0.7 mm thick, pre-
washable emulsion paint
19 Security building Non-slip ceramic tiles. matching to finished, powder coated, including
system on plastered
floor finish. 50 mm thick rock wool insulation and
surfaces.
acoustic pads above.
Water resistant and fire rated
gypsum board panels with emulsion
paint.
Kitchen, pantry, food 100 mm high Glazed ceramic wall tiles
20 serve area, washing, Non-slip vitrified floor tiles or quarry tiles. matching to reaching one tile above (or)
dishwashing area etc. floor finish. ceiling level.
600 mm x 600 mm x 1.0 mm thick
metal ceiling with water-proof paint
and fire resistant material.
Oil resistant epoxy coating system on all
concrete surfaces of the pit.
At floor level, GI gratings, covered with Above-ground concrete Concrete roof slab with concrete
21 Transformer areas N/A
crushed gravel layer of at least 150 mm coating system. protection coating system.
thickness or the pit to be fully filled with
the gravel up to floor level.
DOC. NO. KOC-AR-001 Page 52 of 59 REV. 0
Area Finishes
Ramps and loading bays Hard wearing, skid-resistant, waterproof, flexible, polyurethane based, traffic deck system.
External stairs, steps etc. Non-slip UV, dust & water resistant epoxy coating system over hardened concrete or Polished marble / granite 30 mm thick
(Open type) treads and 20 mm thick risers over a cement mortar with 2 or 3 anti-slip grooves based on building services.
Fair faced concrete surfaces High-build epoxy textured, UV, dust & water resistant coating system.
a) All concrete surfaces and soffits of slabs above the false ceiling shall be painted with light coloured, KOC approved concrete protective coating system.
b) All recesses / penetrations inside rooms / buildings shall be closed with KOC approved fire resistant material and at external faces of the rooms / buildings
recesses / penetrations shall be closed with KOC approved fire resistant and weather resistant material.
c) Floor tiles in the wet areas like AC plant room, battery room, laboratory, kitchen / pantry, toilet, ablution etc. shall be constructed with a gradient of at least 1
% slope in order to guarantee a smooth flow of liquids on the floors.
d) Ventilation openings for extract air louvers, fresh air louvers and extract fans shall be equally spaced, equally sized, equally levelled and shall have
symmetrical external finish as far as possible, subject to KOC approval.
e) 30 mm thick machine cut and machine polished granite / Marble threshold over a cement mortar bed shall be provided at all the entrance doors of wet
areas.
f) Anti-termite - A chemical treatment of soils for the protection of buildings from attack by subterranean termites shall be provided while the building is under
construction.
Appendix-2 provides information and general guidance for each building and their design requirements. However, project specific criteria
may be prepared to meet the project requirements.
The building should include various spaces like airlock lobby, console area based
on the ergonomic study and architectural requirements, auxiliary / marshalling
Raised floor with cable cellar
Control Single or Double storey rooms, conference & training rooms, rest rooms, offices, separate toilets (gents &
1 to be provided at all cable laid
Building reinforced concrete ladies), ablution room, shower and lockers rooms, prayer room, pantry, engineering
areas.
room, store rooms, smoking room, rooms for battery, telecom / LAN, HVAC,
firefighting cylinder storage, instrument & electrical etc., parking spaces.
The building should include various spaces like air lock lobby, operator’s room,
Operator Single or Double storey
3 prayer room, full height lockers, separate toilets (Gents & Ladies), showers, rooms
Shelter reinforced concrete
for HVAC, electrical, telecom, storage etc., parking spaces.
DOC. NO. KOC-AR-001 Page 55 of 59 REV. 0
Appendix-3 provides information and general guidance for each building and their design requirements. However, project specific criteria
may be prepared to meet the project requirements.
Sl.
Building Type of Construction Design Requirement Remarks
No.
The building should include various spaces like reception,
lobby area, waiting, airlock lobbies, lifts, staircases, atrium,
Single or multi-storey framed reinforced meeting rooms, open offices, closed offices, conference Ramps, handicapped
concrete along with steel structure (if rooms, separate male and female toilets, cafeteria or dining toilets & underground
Administration / required) as per design requirements. hall or pantry, prayer room, ablution facility, first aid room, parking (if applicable) to
1
Office Building Note: External facade of the building shall general storages for stationery, equipment and instructional be provided and
match with the Ahmadi heritage theme if materials, large filing room, library, rooms for CCTV, HVAC, considered to this type of
building is located in Ahmadi township area. electrical rooms, telecom room, maintenance staff room, building.
smoking room, open and covered parking spaces for
employees, visitors and for physically challenged persons.
Height not less than 5.0 m,
The building should include various spaces like offices,
Single storey or single storey with mezzaine rollup shutter doors shall
covered workshop, material / tool store, toilets, HVAC plant
Maintenance level, framed reinforced concrete or be considered to this type
2 room, machine workshop, electrical workshop, PSV testing
Building / Workshop structural steel with corrugated sandwich of building. The roof shall
room, electrical / data / telephone room and provision for
panel cladding be polyurethane insulated
gantry crane, monorail & forklifts, parking spaces etc.
roof and wall panel.
Single or multi storey framed reinforced The building should include various spaces like offices,
3 Operation Building concrete along with steel structure (if conference rooms, records room, toilets, pantry, HVAC plant
required) as per design requirements room, telecom room and parking spaces etc.
The building should include various spaces like reception,
offices, pantry with dining area, ablution, fireman rest rooms,
separate male and female toilets, library, fire control centre,
Single or multi storey framed reinforced training areas for fire and safety personnel, primary nursing
4 Fire Station concrete along with steel structure (if station, engine hall, foam storage area, workshop cum dry
required) as per design requirements powder filling station, equipment store, room for cylinder
storage, prayer room, showers and lockers, parking for
visitors and employees and training yard as required for the
project.
DOC. NO. KOC-AR-001 Page 56 of 59 REV. 0
Sl.
Building Type of Construction Design Requirement Remarks
No.
The building should include various spaces like reception,
offices, conference room, chemical stores (cold room), locker
Single or multi storey framed reinforced room, room for workers, sample receiving room, retention
concrete along with steel structure (if sample store room, maintenance room for lab, document
5 Laboratory Building required) as per design requirements or control room, lecture and training room, laboratories,
structural steel with corrugated sandwich separate male and female toilets, ablution, prayer room,
panel cladding pantry with dining area, meeting room, HVAC, CCTV,
electrical room, external gas cylinder storage room,
equipment store, chemicals store, parking spaces, etc..
Single or multi storey framed reinforced The building should include various spaces like main
concrete along with steel structure (if workshop, service pits, stores, offices, HVAC, electrical room,
6 Garage & carwash required) as per design requirements or car wash & dry area, toilet with shower, pantry with dining
structural steel with corrugated sandwich area, lockers, vehicle spare parts, tool and general store,
panel cladding parking spaces etc.
Single storey framed reinforced concrete
Acid resistance finishing
along with steel structure (if required) as per The chemical store should include various spaces like
7 Chemical store materials to be considered
design requirements or structural steel with storage / handling areas and store rooms etc.
to this type of building
corrugated sandwich panel cladding
Single storey framed reinforced concrete
The warehouse should include various spaces like offices,
along with steel structure (if required) as per
8 Warehouse reception area, toilets, storage area, parking spaces, pantry
design requirements or structural steel with
with dining area, lockers, parking spaces etc.
corrugated sandwich panel cladding
The building should include various spaces like PABX room,
battery room, rooms for data network & servers, firefighting
cylinder storage room, HVAC room, offices, network
operation centre (NOC) room, pantry, toilets, parking spaces
etc. The following shall be taken into consideration while
Single or multi storey framed reinforced designing the overall building plan: Raised floor with cable
Telecommunication
9 concrete along with steel structure (if cellar to be provided as
building a) Every Floor in the building shall have a Telecom Room.
required) as per design requirements required
Sl.
Building Type of Construction Design Requirement Remarks
No.
c) There shall be direct cable shaft interconnecting the
Telecom Rooms in different floors exclusively for
routing Telecom scope related cables. This shaft shall
be at least 500 mm x 500 mm.
a) Guardhouse buildings shall be raised minimum 500 Large size guard house at
mm from road level to have flood protection. main plant gate and
10 Guard House Single storey reinforced concrete
smaller at the entrance to
b) If the door of the security equipment room is facing the process area
outside the building, the same shall be dust proof to
prevent ingress of duct.
Sl.
Building Type of Construction Design Requirement Remarks
No.
Open area surrounded with louvered
fencing and gate and comprises HVAC The area shall be designed to house the HVAC chillers,
12 Chiller Yard chillers, etc. pumps, room for electrical control panels, transformer and
shaded structures for equipment.
Steel / Reinforced Concrete
The building should include various spaces like dewaniya,
Single storey framed reinforced concrete House area shall be based
Residential master & kids bed rooms, living rooms, dressing rooms,
13 along with steel structure (if required) as per on number of users and
buildings (houses) toilets, pantry, maid room, driver room, store room, kitchen
design requirements the grade of the employee.
and utilities rooms, parking spaces, soft & hard landscape.
The building should include various spaces like tray washing
area, packing area, bakery & pastry area, store areas,
vegetables, salad, meat and fish preparation areas, freezer
rooms for vegetable, fish, meat & chicken, daily freezer
rooms, daily chiller rooms, waiting areas, main cooking area,
wet & dry garbage rooms, receiving office, dry ration, labour
rest room, locker rooms, separate bath rooms for labours, Kitchen area shall be
Single storey framed reinforced concrete /
14 Central Kitchen electrical rooms, engineering workshops, LAN / telecom based on the number of
steel structure
room, security equipment room, dry store, banquet store, meals to be prepared.
delivery office, offices, reception, separate toilets for offices,
gas cylinder room, parking spaces etc.
Gas cylinders shall be provided along all accessories / fittings
to supply gas from the cylinders to the kitchen at designated
places with fire & gas detectors.
DOC. NO. KOC-AR-001 Page 59 of 59 REV. 0
ACKNOWLEDGEMENT
The draft of this document (KOC Recommended Practice for Architectural Design
Basis, Doc. No. KOC-AR-001, Rev. 0) had been circulated to KOC User Teams for
review & comments and responses received were suitably resolved and incorporated
into the document.
The Team Leader Standards - Chairman, ESTC Sub-committee (Technical) would like
to thank the KOC User Teams, ESTC Sub-committee (Technical) Members and Task
Force Members for providing technical inputs and valuable comments for the
successful development of this document.