ELEVATOR DRIVE CONFIGURATION SHEET
Function Code Parameter Name                       Set Value               Default Setting
                                      Group F0: Basic parameters
    F0-00   Control mode                  1: Closed-loop vector control          1
            Command source
    F0-01                                       1: Distance control              1
            selection
            Running speed under
    F0-02   operational panel                          0.05                     0.05
            control
    F0-03   Maximum running speed                      0.55                      1.6
    F0-04   Rated elevator speed                       0.55                      1.6
    F0-05   Rated elevator load                        500                      1000
    F0-06   Maximum frequency                          50                        50
                                      Group F1: Motor parameters
    F1-00   Encoder type                   2: ABZ incremental encoder            0
    F1-01   Rated motor power                          5.3                 Model dependent
    F1-02   Rated motor voltage                        380                 Model dependent
    F1-03   Rated motor current                        12.1                Model dependent
    F1-04   Rated motor frequency                      25.5                Model dependent
    F1-05   Rated motor speed                           96                 Model dependent
    F1-25   Motor type                      1: Synchronous motor                 1
                                Group F2: Vector control parameters
            Speed loop proportional
    F2-00                                               15                       40
            gain Kp1
            Speed loop integral time
    F2-01                                              0.6                       0.6
            Ti1
            Speed loop proportional
    F2-03                                               35                       35
            gain Kp2
            Speed loop integral time
    F2-04                                              0.8                       0.8
            Ti2
            Torque acceleration
    F2-16                                               1                        1
            time
            Torque deceleration
    F2-17                                              350                      350
            time
                            Group F3: Running control parameters
    F3-02   Acceleration rate                    0.6                             0.6
            Acceleration start jerk
    F3-03                                              2.5                       2.5
            time
            Acceleration end jerk
    F3-04                                              2.5                       2.5
            time
    F3-05   Deceleration rate                          0.6                       0.6
    F3-06   Deceleration end jerk                      2.5                       2.5
    F3-07   Deceleration start jerk                2.5                           2.5
                            Group F5: Terminal function parameters
    F5-01   X1 function selection       33: Up leveling signal NC               33 NC
    F5-02   X2 function selection                   00: Invalid                 35 NC
    F5-03   X3 function selection          34: Down leveling signal NC          34 Nc
    F5-04   X4 function selection         04: Safety circuit feedback N0        4 NO
F5-05   X5 function selection                   00: Invalid                5 NO
F5-06   X6 function selection        38: Run contactor feedback NC         38 NC
F5-07   X7 function selection       39: Brake contactor feedback NC        39 NC
                                      22: Shorting door lock circuit
F5-08   X8 function selection                                              22 NO
                                         contactor feedback NO
F5-09   X9 function selection            40: Inspection signal NC          40 NC
F5-10   X10 function selection         09: Inspection up signal NO         09 NO
F5-11   X11 function selection        10: Inspection down signal NO        10 NO
F5-12   X12 function selection            44: Up limit signal NC           44 NC
F5-13   X13 function selection           45: Down limit signal NC          45 NC
F5-14   X14 function selection        48:Up slow-down 1 signal NC          48 NC
F5-15   X15 function selection      49: Down slow-down 1 signal NC         49 NC
F5-16   X16 function selection                  00: Invalid                50 NC
F5-17   X17 function selection                  00: Invalid                51 NC
F5-18   X18 function selection                  00: Invalid                  0
F5-19   X19 function selection                  00: Invalid                  0
F5-20   X20 function selection        43: Fire emergency signal NC           0
F5-21   X21 function selection                  00: Invalid                  0
F5-22   X22 function selection                  00: Invalid                  0
F5-23   X23 function selection         28: Elevator lock signal NO           0
F5-24   X24 function selection                  00: Invalid                  0
F5-25   CTB input type                             1856                     320
F5-26   Y1 function selection           01: Run contactor control            1
F5-27   Y2 function selection          02: Brake contactor control           2
                                      03: Shorting door lock circuit
F5-28   Y3 function selection                                                3
                                            contactor control
F5-29   Y4 function selection                   00: Invalid
F5-30   Y5 function selection                   00: Invalid
F5-31   Y6 function selection                   00: Invalid
F5-37   X25 function selection            4: Safety circuit signal           0
F5-38   X26 function selection          5: Door lock circuit signal          0
F5-39   X27 function selection             0: Invalid                        0
                         Group F6: Basic elevator parameters
F6-00   Top floor of the elevator                    4                       9
        Bottom floor of the
F6-01                                                1                       1
        elevator
F6-02   Parking floor                                2                       1
F6-03   Fire emergency floor                         2                       1
F6-04   Elevator lock floor                          2                       1
F6-38   Elevator lock start time                   18:30                   00:00
F6-39   Elevator lock end time                     7:00                    00:00
        Program control
F6-40                               Set Bit5 to 1: Timed elevator lock       0
        selection 1
        Program control             Set Bit10 to 1: Elevator lock in the
F6-41                                                                        0
        selection 2                          attendant state
        Fire emergency function
F6-44                                             49224                    16456
        selection
                       Group F8: Enhanced function parameters
F8-01   Pre-torque selection         0: Pre-torque invalid                   0
F8-03   Drive gain                                  0.6                     0.6
F8-04   Brake gain                                  0.6                     0.6
F8-11   Brake apply delay                           0.6                     0.6
                                  Group F9: Time parameters
        Idle time before
F9-00                                             10                     10
        returning to base floor
        Time for fan and lamp to
F9-01                                              2                      2
        be turned off
F9-03   Clock : year                             2023                Current year
F9-04   Clock : month                              7                Current month
F9-05   Clock : day                           Current day            Current day
F9-06   Clock : hour                         Current hour            Current hour
F9-07   Clock : minute                  Current minute              Current minute
                        Group FE: Elevator function parameters
FE-01   Floor 1 display                 1911: display B                 1901
FE-02   Floor 2 display                     1912: display G             1902
FE-03   Floor 3 display                     1901: display 1             1903
FE-04   Floor 4 display                     1902: display 2             1904
                                  Group FP: User parameters
FP-00   User password                       0: No password                0
                                            0: No operation
FP-01   Parameter update               1: Restore default setting         0
                                         2: Clear fault records
Unit
m/s
m/s
m/s
 kg
 Hz
kW
 V
 A
 Hz
RPM
 ms
 ms
m/s²
m/s²
 s
 s
HH:MM
HH:MM
  s
min
min
YYYY
MM
DD
HH
min