Harmony GTU,GTUX and iDisplay
ATEX/IECEx Instruction Guide                                            www.se.com
    Concerning the use of Harmony GTU,GTUX and iDisplay for
   applications in potentially explosive atmospheres (Zones 2/22)
Schneider Electric
8ème rue, ZI Carros
06516 Carros cedex – France
         Type examination certificate: INERIS 15ATEX3006X
        IECEx Certificate of Conformity: IECEx INE15.0017X
          Type examination certificate : CML 21UKEX3777X
SAFETY INSTRUCTIONS
Read these instructions carefully, and look at the equipment to become familiar
with the device before trying to install, operate, or maintain it. The following
special messages may appear throughout this documentation or on the
equipment to warn of potential hazards or to call attention to information that
clarifies or simplifies a procedure.
              The addition of this symbol to a “Danger” or “Warning” safety
              label indicates that an electrical hazard exists, which will result
              in personal injury if the instructions are not followed.
             This is the safety alert symbol. It is used to alert you to
             potential personal injury hazards. Obey all safety messages
             that follow this symbol to avoid possible injury or death.
                                   DANGER
 DANGER indicates a hazardous situation which, if not avoided,
 will result in death or serious injury.
*NHA6836007*
The information in this document is subject to change without notice.
Copyright © 10/2021 Schneider Electric
All Rights Reserved.
NHA68360 07
Printed in
                                           1/8
                               WARNING
 WARNING indicates a hazardous situation which, if not avoided,
 could result in death or serious injury.
                               CAUTION
CAUTION indicates a hazardous situation which, if not avoided,
could result in minor or moderate injury.
                              NOTICE
NOTICE is used to address practices not related to physical injury.
PLEASE NOTE
Electrical equipment should be installed, operated, serviced, and maintained
only by qualified personnel. No responsibility is assumed by Schneider Electric
for any consequences arising out of the use of this material. A qualified person
is one who has skills and knowledge related to the construction and operation
of electrical equipment and its installation, and has received safety training to
recognize and avoid the hazards involved.
SCOPE
This present document applies when the Harmony GTU, GTUX and iDisplay
bears      marking and provides important information when used in
hazardous areas. This documentation has to be kept and always refer to those
instructions for installation, operation, maintenance or evolution of your
system.
You can download this instruction guide at www.se.com.
If any translation is needed, you can contact your local Schneider support or
sales center.
The products are only supplied with 12…24 Vdc
                                      2/8
Relevant Standards
These terminals have been manufactured in accordance with:
• Standard EN IEC 60079-0 (2018) and IEC 60079-0 (2017): Explosive
  atmospheres - Part 0: Equipment - General requirements.
• Standard EN IEC 60079-7 (2015) + A1 (2018) and IEC 60079-7 (2015) +
  A1 (2017): Explosive atmospheres - Part 7: Equipment protection by
  increased safety “e”.
• Standard EN 60079-15 (2010) and IEC 60079-15 (2010): Explosive
  atmospheres - Part 15: Equipment protection by type of protection “n”.
• Standard EN 60079-31 (2014) and IEC 60079-31 (2013): Explosive
  atmospheres - Part 31: Equipment dust ignition protection by enclosure “t”.
                              DANGER
POTENTIAL FOR EXPLOSION
Install, use, and maintain these modules in accordance with:
 • Standard IEC 60079-14: Explosive atmospheres - Part 14: Electrical
   installations design, selection and erection.
 • Standard IEC 60079-17: Inspection and maintenance of electrical
   installations in hazardous areas.
 • Edicts, by-laws, laws, directives, circulars, standards, regulations and any
   other document relating to where the apparatus is installed.
Failure to follow these instructions will result in death or serious injury.
Permitted zones of application
Refer to the section "Markings" to get information about the permitted zones of
protection and the types of protection.
• The product installed in zones 2/22 hazardous areas must be certified and
   bear the        marking.
• Ensure with the marking that the terminals are compatible with the
   conditions permitted for the hazardous area at the site where it is being
   used.
                                     3/8
Installation, Operation and Maintenance
Make sure you follow all the recommendations in the user manual for each
product and additionally those listed below.
                                   DANGER
 POTENTIAL FOR EXPLOSION
 • Confirm that the location is free from explosively hazardous gases or dust
   before connecting or disconnecting equipment, replacing or wiring modules.
 • Make sure that the ambient temperature in protective enclose never exceeds
   the temperature marked on the product.
 • Confirm each interface (COM, Ethernet, USB, power line, …) has been
   securely locked.
 • Confirm that any USB cable has been attached with its appropriate clamp.
 • Install the modules in an enclosure EPL Gc insuring a minimal ingress
   protection IP54 for use in zone 2 and in an enclosure EPL Dc insuring a
   minimal ingress protection IP6X for use in zone 22.
 • Make sure the purging test inside the product is performed and validated in
   accordance with IEC 60079-2 when installed in an IP4X pressurized
   enclosure.
 • Do not install the modules in the environment more than Pollution Degree 2
   as defined in IEC 60664-1.
 • Do not open the enclosure when an explosive atmosphere is present.
 • Confirm that the power supply has been turned OFF before disconnecting,
   replacing or wiring modules.
 • Ensure that ground at power supply is properly connected.
 • Do not use equipment that has been damaged.
 • Do not expose the terminal to direct sunlight.
 • Do not allow layers of dust to form on the product: it should be cleaned
   regularly.
 • Implement method to avoid risk of electrostatic discharge at using zone 2
   and 22 areas. See the details at NOTE.
 • Add the warning for potential electrostatic charging hazard in a location
   visible by the operator after installation in order to maintain the required level
   of safety.
 • Take into consideration during the installation, that the product underwent
   only a shock corresponding to an energy of a low risk at 2J.
 • Mount the display in an enclosure according to the installation procedures
   described in the user manual.
 • Use only the identical replacement battery (HMIZGBAT) for the product.
 Failure to follow these instructions will result in death or serious injury.
NOTE: The front surface of the product has risk of electrostatic discharge. If the product is
operating in zone 2/22 areas, the following instructions must be applied:
All models except for HMIDT752 and HMIDT952:
• Use non-conductive gloves (e.g. Electrosoft Latex Gloves by Honeywell Safety) made of
    leather, plastic or rubber whose surface resistance is more than 1 GΩ at 23 ± 2 °C and
    50 ± 5 % relative humidity.
                                            4/8
• Use a non-conductive touch pen (XBTZGPEN by Schneider Electric) made of plastic
  material whose surface resistance is more than 1 GΩ at 23 ± 2 °C and 50 ± 5 % relative
  humidity to all terminals.
HMIDT752 and HMIDT952:
• Install the product away from 1,000 mm distance from a potential electrostatic source
  (e.g. plant process, conveyor belt, pipe, etc). The environmental conditions shall not be
  lower than 25 % relative humidity. If the potential electrostatic source is upper than 30
  kV, it is necessary to call an expert to evaluate the electrostatic risk and the distance
  between the product and the electrostatic source.
Markings
ATEX and IECEx markings, applied to the product are as follows:
  HMIDT351, HMIDT542                            HMIDT752, HMIDT952
  HMIDT551, HMIDT642
  HMIDT643, HMIDT651
  HMIDT732,
  HMIG2U, HMIG3U, HMIG5U, HMIG5U2,
  HMIDID64DTD1, HMIDID73DTD1
  HMIZGPDP, HMIZGCAN,
  HMIZMDARX, HMIZMDAEX
  Schneider Electric                            Schneider Electric
  F-06516 Carros                                F-06516 Carros
  INERIS 15ATEX3006X                            INERIS 15ATEX3006X
  IECEx INE 15.0017X                            IECEx INE 15.0017X
  CML 21UKEX3777X                               CML 21UKEX3777X
  II 3 G D                                      II 3 G D
  Ex ec nC IIC T4 Gc                            Ex ec IIC T4 Gc
  Ex tc IIIC T135°C Dc                          Ex tc IIIC T135°C Dc
  Tamb: 0°C to +60°C                            Tamb: 0°C to +55°C
  WARNING                                       WARNING
  - Do not disconnect when circuit is live      - Do not disconnect when circuit is live
  - Potential electrostatic charging hazard     - Potential electrostatic charging hazard
  (see instructions)                            (see instructions)
  NOTE: Other required elements such as product reference, serial number
  and date code of manufacture are already marked on products.
  All models may be followed by alphanumeric characters and there is no
  impact safety related critical components and constructions.
                                              5/8
HMIDT35X,                   HMIDT65X,                   HMIDT75X,
HMIDT35XFH                  HMIDT65XFH, HMIG3X,         HMIDT75XFH
                            HMIG3FH
Schneider Electric          Schneider Electric          Schneider Electric
F-06516 Carros              F-06516 Carros              F-06516 Carros
INERIS 15ATEX3006X          INERIS 15ATEX3006X          INERIS 15ATEX3006X
IECEx INE 15.0017X          IECEx INE 15.0017X          IECEx INE 15.0017X
CML 21UKEX3777X             CML 21UKEX3777X             CML 21UKEX3777X
II 3 G D                    II 3 G D                    II 3 G D
Ex ec nC IIC T4 Gc          Ex ec IIC T4 Gc             Ex ec IIC T4 Gc
Ex tc IIIC T135°C Dc        Ex tc IIIC T135°C Dc        Ex tc IIIC T135°C Dc
Tamb: -30°C to +65°C        Tamb: -30°C to +70°C        Tamb: -20°C to +60°C
WARNING                     WARNING                     WARNING
- Do not disconnect when    - Do not disconnect when    - Do not disconnect when
circuit is live             circuit is live             circuit is live
- Potential electrostatic   - Potential electrostatic   - Potential electrostatic
charging hazard (see        charging hazard (see        charging hazard (see
instructions)               instructions)               instructions)
NOTE: Other required elements such as product reference, serial number
and date code of manufacture are already marked on products.
All models may be followed by alphanumeric characters and there is no
impact safety related critical components and constructions.
                                      6/8
                 EU DECLARATION OF CONFORMITY
We:   Schneider Electric Industries SAS
      35 rue Joseph Monier
      F - 92506 Rueil Malmaison
Hereby declare under our sole responsibility that the products:
Trademark             Harmony or Magelis
                      Human Machine Interface
                      HMIGTU:
                        HMIDT542, HMIDT642, HMIDT643, HMIDT732, HMIDT351, HMIDT551,
                        HMIDT651, HMIDT752, HMIDT952, HMIG2U, HMIG3U, HMIG5U,
                        HMIG5U2, HMIZGPDP, HMIZGCAN, HMIZMDARX, HMIZMDAEX,
                        HMIZXJ19
Product, Type         HMIGTUX:
                        HMIDT35X, HMIDT65X, HMIDT75X, HMIDT35XFH, HMIDT65XFH,
                        HMIDT75XFH, HMIG3X, HMIG3XFH
                      iDisplay HMIDID:
                        HMIDID64DTD1, HMIDID73DTD1
                      Includes models with additional alphanumeric characters at the end of the
                      model number.
Are in conformity with the requirements of the following directives and conformity was checked in
accordance with the following standards.
Directive            Harmonized standard / Notified body reference
ATEX Directive       EN IEC 60079-0: 2018 + AC: 2020, EN IEC 60079-7: 2015 + A1: 2018,
2014/34/EU           EN 60079-15: 2010, EN 60079-31: 2014
                     Type examination certificate:
                     INERIS 15ATEX3006X and IECEx INE 15.0017X
                                       II 3 G D
                                      Ex ec nC IIC T4 Gc
                                      Ex tc IIIC T135°C Dc
                                                                or II 3 G D
                                      Tamb: 0°C to +60°C or
                                                                     Ex ec IIC T4 Gc
                                      Tamb: -20°C to +60°C or
                                                                     Ex tc IIIC T135°C Dc
                                      Tamb: -30°C to +65°C or
                                                                     Tamb: 0°C to +55°C
                                      Tamb: -30°C to +70°C
                     By INERIS: Parc Technologique ALATA, 60550 Verneuil en Halatte - France
Subject to correct installation, maintenance and use conforming to its intended purpose, to the
applicable regulations and standards, to the supplier's instructions and to accepted rules of the art.
This declaration becomes invalid in the case of any modification to the products not authorized by us.
Compliance with the ATEX Directives will require the application of ATEX guide giving requirements,
details and advices for installation of products used. The guides are available on www.se.com
Issued at Osaka - JAPAN: October 11th, 2021
                                       Name: Hakim GRIB
                                       Digital Plant
                                       Certification Director
                                                7/8
                 UK DECLARATION OF CONFORMITY
We:   Manufacturer                                          UK Representative
      Schneider Electric Industries SAS                     Schneider Electric Limited
      35 rue Joseph Monier                                  Stafford Park
      Rueil Malmaison 92500 - France                        Telford, TF3 3BL - United Kingdom
Hereby declare under our sole responsibility that the products:
Trademark             Harmony or Magelis
                      Human Machine Interface
                      HMIGTU:
                        HMIDT542, HMIDT642, HMIDT643, HMIDT732, HMIDT351, HMIDT551,
                        HMIDT651, HMIDT752, HMIDT952, HMIG2U, HMIG3U, HMIG5U,
                        HMIG5U2, HMIZGPDP, HMIZGCAN, HMIZMDARX, HMIZMDAEX,
                        HMIZXJ19
Product, Type         HMIGTUX:
                        HMIDT35X, HMIDT65X, HMIDT75X, HMIDT35XFH, HMIDT65XFH,
                        HMIDT75XFH, HMIG3X, HMIG3XFH
                      iDisplay HMIDID:
                        HMIDID64DTD1, HMIDID73DTD1
                      Includes models with additional alphanumeric characters at the end of the
                      model number.
Are in conformity with the requirements of the following directives and conformity was checked in
accordance with the following standards.
Regulation           Designated standard / Approved body reference
                     EN IEC 60079-0: 2018 + AC: 2020, EN IEC 60079-7: 2015 + A1: 2018,
SI 2016 No.1107
                     EN 60079-15: 2010, EN 60079-31: 2014
                     Type examination certificate:
                     CML 21UKEX3777X
                                       II 3 G D
                                      Ex ec nC IIC T4 Gc
                                      Ex tc IIIC T135°C Dc        or II 3 G D
                                      Tamb: 0°C to +60°C or           Ex ec IIC T4 Gc
                                      Tamb: -20°C to +60°C or         Ex tc IIIC T135°C Dc
                                      Tamb: -30°C to +65°C or         Tamb: 0°C to +55°C
                                      Tamb: -30°C to +70°C
                     By Eurofins E&E CML Limited: Ellesmere Port CH65 4LZ - UK
Subject to correct installation, maintenance and use conforming to its intended purpose, to the
applicable regulations and standards, to the supplier's instructions and to accepted rules of the art.
This declaration becomes invalid in the case of any modification to the products not authorized by us.
Compliance with the ATEX Regulations will require the application of ATEX guide giving
requirements, details and advices for installation of products used. The guides are available on
www.se.com
Issued at Telford - United Kingdom: October 11th, 2021
                                        Name: David Williams
                                        VP Marketing UK&I
                                        Zone UK & Ireland
                                                8/8