CUMMINS CM750 CM850 CM2250 ISB QSK QST
QSX
CATERPILLAR ADEM3 ADEM4
DEUTZ EMR2 EMR3
ECONTROLS GCP
GENERIC J1939 PLUS
GM PSI
ISUZU 4H
IVECO EDC62 EDC7C1 T3
JOHAN DEERE JDEC PUMP
MTU ADEC ECU8 MDEC201 MDEC302 MDEC303 MDEC304
MDEC506
PERKINS 1100 1300 ADEM3 ADEM4
SCANIA S6
SISU EEM3
VOLVO EDC3 EDC4 EMS2 EMS2B
YANMAR ECO
ECU POWER AND ECU STOP
Relay out A & B used configured as CAN Ecu power / CAN Ecu stop via emergency switch. In case of
communication failure between controller and ecu then ECU Stop is an back to stop the engine.
REMOTE SPEED CONTROL
DSE controller have configurable parameter for speed control that can be adjusted during engine is
running.
DSE Control Batt voltage Chrg alt volt No of start
ECM Control coolant Oil fuel air Speed
ECU Wiring
DSE Fuel Output For “CAN ECU Power “use fuel out from control external slave relay may
Relay require. Before connecting check power consumption of ECM, it will be not
exceeded from DSE controller output.
DSE Strat / Crank Connect directly to engine start solenoid. External should be used with
Out put relay compare to start solenoid current rating.
CAN COMM Screened for J1939. Connected ECM Side with some brands and model
CAN H J1939+, Use proper 120-ohm Impedance shielded can cable
CAN L J1939+, Use proper 120-ohm Impedance shielded can cable
CUMMINS ECM
ECM Model Connector ECM On CAN Comm CAN H CAN L
CM750 6 Pin H, Fuel C A B
Connector On
CM850 50 Pin 39 , Fuel E C D
Connector On
CM2250
ISB
QSK
QST
QSX
GCS 6 Pin 5, 8 fuel RS485 A RS485 B 19, 20
Connector on 18 21 LINK FOR