Vanee G3000EE Installation Sheet
Vanee G3000EE Installation Sheet
IMPORTANT NOTES
1. The one and only main wall
control compatible with these
units is the X-Touch (for Venmar
units) or Gold-Touch (for vänEE
units) wall control.
2. These units have a new balancing
procedure, see Section 7.
3. The terminal connectors for
these units are not in the
installation kit; they are already
mounted to their control board.
VB0185
Because of the large amount of models covered in this publication, the illustrations are typical ones. Some details of your unit may be
slightly different than the ones shown.
Please take note that this guide uses the following symbols to emphasize particular information:
! WARNING
Identifies an instruction which, if not followed, might cause serious personal injuries including possibility of death.
CAUTION
Denotes an instruction which, if not followed, may severely damage the unit and/or its components.
NOTE: Indicates supplementary information needed to fully complete an instruction.
We welcome any suggestions you may have concerning this guide and/or the unit, and we would appreciate hearing your comments on
ways to better serve you. Please contact us by phone at 1-800-567-3855.
7. This unit must be grounded. The power supply cord has a 3-prong grounding plug for your personal safety. It must be plugged into a
mating 3-prong grounding receptacle, grounded in accordance with the national electrical code and local codes and ordinances. Do
not remove the ground prong. Do not use an extension cord.
8. Do not install in a cooking area or connect directly to any appliances.
9. Do not use to exhaust hazardous or explosive materials and vapors.
10. When performing installation, servicing or cleaning these units, it is recommended to wear safety glasses and gloves.
11. Due to the weight of the unit, two installers are recommended to perform installation.
12. When applicable local regulations comprise more restrictive installation and/or certification requirements, the aforementioned
requirements prevail on those of this document and the installer agrees to conform to these at his own expenses.
CAUTION
1. To avoid prematurate clogged filters, turn OFF the unit during construction or renovation.
2. Please read specification label on product for further information and requirements.
3. Be sure to duct air outdoors – Do not intake/exhaust air into spaces within walls or ceiling or into attics, crawl spaces, or garage.
4. Intended for residential installation only in accordance with the requirements of NFPA 90B (for a unit installed in USA) or Part 9 of the
National Building Code of Canada (for a unit installed in Canada).
5. Do not run any air ducts directly above or closer than 2 ft (0.61 m) to any furnace or its supply plenum, boiler, or other heat producing
appliance. If a duct has to be connected to the furnace return plenum, it must be connected not closer than 9’ 10” (3 m) from this
plenum connection to the furnace.
6. The ductwork is intended to be installed in compliance with all applicable codes.
7. When leaving the house for a long period of time (more than two weeks), a responsible person should regularly check if the unit
operates adequately.
8. If the ductwork passes through an unconditioned space (e.g.: attic), the ducts must be insulated, and the unit must operate continuously
except when performing maintenance and/or repair. Also, the ambient temperature of the house should never drop below 18°C (65°F).
2
TABLE OF CONTENTS
1. SERVICE PARTS ...............................................................................................................................................................4-5
2. AIR DISTRIBUTION ...............................................................................................................................................................6
3. INSTALLATION .................................................................................................................................................................6-12
3.1 INSPECT THE CONTENT OF THE BOX ............................................................................................................................................... 6
3.2 LOCATING THE UNIT .................................................................................................................................................................. 6-7
3.3 PLANNING OF THE DUCTWORK ....................................................................................................................................................... 8
3.4 DUCT SIZE ................................................................................................................................................................................ 8
3.5 INSTALLING THE DUCTWORK AND REGISTERS ............................................................................................................................... 8-10
3.6 CONNECTING THE DUCTS TO THE UNIT ..........................................................................................................................................11
3.7 INSTALLING TWO EXTERIOR HOODS .............................................................................................................................................. 12
3.8 CONNECTING THE DRAIN ............................................................................................................................................................ 12
4. CONTROLS .................................................................................................................................................................. 13-16
4.1 UNITS BOOTING SEQUENCE ........................................................................................................................................................ 13
4.2 WALL CONTROL(S) ELECTRICAL CONNECTION ........................................................................................................................... 13-15
4.3 SETTING UNIT OPERATION IN THE REMAINING 40 MINUTES ON 20 MIN/H MODE AND SETTING UNIT DEFROST CYCLE TYPE
USING X-TOUCH OR GOLD-TOUCH MAIN WALL CONTROL ................................................................................................................ 16
3
1. SERVICE PARTS
D O
E D
F
4
G
H
L M
I
VL0071
J
1. SERVICE PARTS (CONT’D)
AVS X24 AVS X24 AVS X30 AVS X30 G2400E G2400H G3000E G3000H
NO. DESCRIPTION QTY.
ERV ECM HRV ECM ERV ECM HRV ECM ECM ECM ECM ECM
1 BRACKET KIT 1 63419 63419 63419 63419 63419 63419 63419 63419
DAMPER SYSTEM ASSEMBLY
2 1 63420 63420 63420 63420 63420 63420 63420 63420
(INCLUDING 2 PLASTIC SCREWS)
BLOWER ASSEMBLY
3 2 63421 63421 63421 63421 63421 63421 63421 63421
(INCLUDING 3 PLASTIC SCREWS)
HRV CORE FILTER (PAIR) 1 63426 63426 63426 63426
4
ERV CORE FILTER (PAIR) 1 63433 63433
HEAT RECOVERY CORE 1 63422 63423 63422 63423
5
ENERGY RECOVERY CORE 1 63425 63425
DOOR ASSEMBLY
6 1 63429 63429 63429 63429 63428 63428 63428 63428
(INCLUDING NO. 16)
7 RIGHT PANEL 1 63432 62495 62498 62499 63430 62500 62502 62504
8 ERV CORE FILTER (PAIR) 1 63427 63427
9 ENERGY RECOVERY CORE 1 63424 63424
DAUGHTER BOARD
5
10 1 63437 63437 63437 63437 63437 63437 63437 63437
(INCLUDING INO. 11)
PCB CONNECTOR
11 1 63434 63434 63434 63434 63434 63434 63434 63434
(MAIN CONTROL)
PCB CONNECTOR
12 1 63435 63435 63435 63435 63435 63435 63435 63435
(AUXILIARY CONTROL)
PCB
13 1 63436 63441 63442 63443 63436 63441 63442 63443
(INCLUDING NOS. 10 &12)
14 TRANSFORMER 1 63438 63438 63438 63438 63438 63438 63438 63438
15 WARM SIDE THERMISTOR KIT* 1 62481 62481 62481 62481 62481 62481 62481 62481
16 DOOR MAGNETIC SWITCH* 1 19060 19060 19060 19060 19060 19060 19060 19060
17 PLASTIC SCREW (SET OF 6)* 1 63439 63439 63439 63439 63439 63439 63439 63439
18 HARDWARE KIT* 1 22488 22488 22488 22488 22488 22488 22488 22488
* Not shown.
TO OUTDOORS
FRESH AIR
TO BUILDING
VF0063
3. INSTALLATION
CAUTION
In every case, make sure the unit is level.
6
3. INSTALLATION (CONT’D)
! WARNING
Ensure the wall bracket is attached to all of the
available studs, not into the drywall alone.
LEVEL LINE WALL BRACKET
VD0379
Using 1½” long provided screws, assemble both spacers to left and
right back bottom corner of the unit.
VO0271
Secure the unit to the wall using one 1½” long provided screw
through the small bracket.
VD0380
CAUTION
Never use an electric screwdriver or
drill to screw the brackets to the unit;
use a standard screwdriver.
VR0086
Using 3/8” long provided screws, mount the other bracket (A) to the
back of the unit; start with the 4 back screws, then 2 screws on top
left and right sides, then use the last center one to assemble the VO0272
VD0392
7
3. INSTALLATION (CONT’D)
4" 4"
4" 4"
4"
5" Ø, 86 CFM
6" Ø, 160 CFM 6" Ø, 160 CFM
VI0019
8
3. INSTALLATION (CONT’D)
CAUTION
When performing duct connections to the furnace supply duct, this duct must be sized to support the additional
airflow produced by the unit. Also, the use of metal duct is highly recommended.
• Connect this opening to the Fresh air distribution port of the unit (use metal
duct, see figure at right).
• Make sure the unit duct forms an elbow inside the furnace/air handler ductwork.
• If desired, interlock (synchronize) the furnace/air handler blower operation (see
Section 5 ELECTRICAL CONNECTION TO THE FURNACE).
VJ0128
9
3. INSTALLATION (CONT’D)
CAUTION
When performing duct connections to the furnace supply duct (Method 1), this duct must be sized to support the
additional airflow produced by the unit. Also, the use of metal duct is highly recommended. For a Return-return
installation, the furnace blower must be in operation when the unit is in operation.
There are 2 methods for connecting the unit to the furnace/air handler:
Method 1: Supply-return connection Method 2: Return-return connection
MINIMUM 18"
(0.5 M)
METAL DUCT B
MINIMUM 3'
A+B = NOT LESS
(0.9 M)
THAN 10’ (3.1 M)
B VJ0131
A
A+B = NOT LESS
THAN 10’ (3.1 M)
VJ0130
10
3. INSTALLATION (CONT’D)
3.6 CONNECTING THE DUCTS TO THE UNIT
NOTE: All unit ports are were created to be connected to ducts having a minimum of 6” diameter, but if need be, they can be connected
to bigger sized ducts by using an appropriate transition (e.g.: 6” diameter to 7” diameter transition).
Insulated flexible ducts
Use the following procedure to connect the insulated flexible ducts to the ports of the unit (Exhaust air to outdoors and Fresh air
from outdoors ports).
CAUTION
If ducts have to go through an unconditioned space (e.g.: attic), always use insulated ducts.
Pull back the insulation to expose the flexible duct.
Attach the flexible duct to the port using tie wrap.
Pull the insulation over the joint and tuck in between the inner and outer rings of the double collar.
Pull down the vapor barrier (shaded part in illustrations below) over the outer ring to cover it completely. Fasten in place the vapor
barrier using the port strap (included in unit parts bag). To do so, insert one collar pin through vapor barrier and first strap hole,
then insert the other collar pin through vapor barrier and center strap hole and close the loop by inserting the first collar pin in the
last strap hole.
CAUTION
Make sure the vapor barrier on the insulated ducts does not tear during installation to avoid condensation within the ducts.
1 2 3 COLLAR PINS 4
STRAP
VJ0132
VJ0133
11
3. INSTALLATION (CONT’D)
Make sure the intake hood is at least 6 feet (1.8 m) 6' 18"
(1.8 M) (457 MM)
away from any of the following: 6'
• Dryer exhaust, high efficiency furnace vent, (1.8 M)
central vacuum vent
• Gas meter exhaust, gas barbecue-grill
18"
• Any exhaust from a combustion source
(457 MM)
• Garbage bin and any other source of contamination
TAPE AND DUCT TIE
Refer to figure on the right for connecting insulated ducts
to the exterior hoods. An “Anti-gust intake hood’’ should be
installed in regions where a lot of snow is expected to fall.
VD0028
CAUTION
A drain tubing (included) must be installed for all HRV units. For ERV units, it is not required, however, it is
recommended for climates where the outdoor temperature typically remains below -25°C (-13°F), (over a 24-hour
period) for several days in a row, combined with an indoor humidity of 40% or higher.
TIE WRAP
16" 16"
(406 mm) (406 mm)
VO0273A
± 1”
Cut 2 sections of the plastic tube, at least 16” (406 mm) long, and
attach them to each inner drain fitting, located under the unit.
Join both short sections to the “T” junction and main tube as shown.
VD0337A
Make a water trap loop in the tube to prevent the unit from
DRAIN PLUG LOCATIONS
drawing unpleasant odors from the drain source. Make sure this
loop is located OVER the “T” as shown. Run the tube to the floor
drain or to an alternative drain pipe or pail.
IMPORTANT
If using a pail to collect water, locate the tube end approximately
VD0387 1” from the top of the pail in order to prevent water from being
NOTE: For ERV units installed in cold climate, remove both drain drawn back up into the unit.
plugs inside the unit prior to install tubing.
12
4. CONTROLS
! WARNING
The X-Touch (Venmar units) and Gold-Touch (vänEE units) wall control are the only main wall controls compatible
to your unit. Never attempt to install another wall control model. Always disconnect the unit before making any
connections. Failure to disconnect power could result in electric shock or damage to the wall control or electronic
module inside the unit.
CAUTION
Failure to comply with the following can cause erratic operation of the unit and/or the wall control:
Never install more than one main wall control per unit. Make sure that the wires do not short-circuit between
themselves or by touching any other components on the wall control. Avoid poor wiring connections. To reduce
electrical interference (noise) potential, do not run wall control wiring next to control contactors or near light
dimming circuits, electrical motors, dwelling/building power or lighting wiring, or power distribution panel.
Unplug the unit from power source. Open the side panel to access terminal blocks A B
(A is the one for main control connection only and B is the one for auxiliary controls). Pull
out from the unit board the needed connector(s).
VE0351
Run the end of the control wire(s) through the grommet located on the unit wall. Refer to
illustration at right (side panel removed to ease understanding).
GROMMET
VD0381
13
4. CONTROLS (CONT’D)
VE0352 VE0353
RIGHT WRONG
VE0354
Once the terminal block(s) connections have been made, reinstall it (them) on
the unit PC board. Refer to illustration on the right (side panel removed to ease
understanding). Close the side panel.
NOTE: For information about the operation of the wall controls, refer to their
installation sheet.
VE0355
14
4. CONTROLS (CONT’D)
VE0349
When used, the 20/40/60 minute activation will override the main control operation, as well
as the unit defrost cycle. On example shown on the left, the unit was in CONT mode when
CONT
the auxiliary control was activated; so the actual operation mode stays on X-Touch main wall
control screen, but the chronometer icon appears as long as the 20/40/60 minute is activated.
NOTE: In colder regions, the chronometer icon may stay after the end of the 20/40/60 minute
cycle, due to defrost cycle.
15
4. CONTROLS (CONT’D)
4.3 SETTING UNIT OPERATION IN THE REMAINING 40 MINUTES ON 20 MIN/H MODE AND SETTING UNIT DEFROST CYCLE TYPE
USING X-TOUCH OR GOLD TOUCH MAIN WALL CONTROL
Press and hold the MODE 3 sec.
MODE key for 3 seconds.
The LCD screen will show one of these configurations:
TURBO
CONT
OR OR
Two lines are flashing Recirculation arrows Recirculation arrows
to show Standby are turning, rE are turning, rE
(default configuration flashes and CONT flashes and TURBO
setting). label appears to show label appears to show
RECIRCULATION on RECIRCULATION on
low speed. high speed.
MODE
Use MODE or TURBO key to OR % HUM
see all 3 configurations.
TURBO
Press % HUM key to accept chosen
configuration and go to setting defrost
cycle type.
The LCD screen will show one of these defrost cycle types:
OR OR
Sd (Standard) PL (Plus) dI (Discretion)
(factory defrost cycle setting). Use this cycle in cold region When needed, the defrost cycle
When needed, the unit will (outdoor temperature -27°C will be performed on the same
perform defrost cycle on high [-17°F] and lower). When speed than the unit ventilation
speed. needed, the unit will perform speed. (e.g.: if the unit is set on
NOTE: This is the defrost type defrost cycle on high speed on TURBO, the defrost cycle will
used for the data published by a longer period of time. be done on high speed, and
HVI and ENERGY STAR®. if the unit is set on CONT, the
defrost cycle will be done on
low speed.
MODE
TURBO
Press % HUM key to accept
chosen defrost cycle type and
go to software version display
% HUM
! WARNING
Never connect a 120-volt AC circuit to the terminals of the furnace interlock (standard wiring). Only use the low
voltage class 2 circuit of the furnace blower control.
For a furnace connected to a cooling system:
On some older thermostats, energizing the “R” and “G” terminals at the furnace has the effect of energizing “Y” at the thermostat and
thereby turning on the cooling system. If you identify this type of thermostat, you must use the ALTERNATE FURNACE INTERLOCK WIRING.
STANDARD FURNACE INTERLOCK WIRING ALTERNATE FURNACE INTERLOCK WIRING
NO C NC I OC OL
NO C NC I OC OL
W R G Y THERMOSTAT W R G Y THERMOSTAT
4 WIRES TERMINALS 4 WIRES TERMINAL
R NC
RR
G G
C C C
YY YY
FURNACE FURNACE
24-VOLT 24-VOLT
TERMINAL BLOCK TERMINAL BLOCK
2 WIRES 2 WIRES
COOLING SYSTEM COOLING SYSTEM
VE0350A
17
WIRING DIAGRAM LOGIC DIAGRAM
B
F1
Damper motor Exhaust
K2
B J9-1 K1 fan motor
M3 J3 A2 J9-2 J5-1
B J5-2
12 DAMPER J9-3 J5-3
54321 21
Door interlock switch ELECTRONIC ASSEMBLY
(magnetically actuated S1 J2 J1
J9-4
reed switch)
J7-2 to A1-J17
Defrost
T1 to A1-J12 J7-1
B 120 V temperature sensor
W W Class 2 Supply
24 V t˚ R1
class 2 low voltage K3 fan motor
9.5 V factory wiring J4-1
J4-2
class 2 J4-3
neutral W
From From
supply motor exhaust motor
Y BR
control cable control cable
Y BR J6-2 to A1-J15
BL
BL
Y
W
Y
W
R
R
Power cable Thermistor J6-1
nc
nc
BR 5 4 3 2 1
J5 J11 t˚
J15
J17
G BL R2
1 J8 Override
2 12 1 2 34 5 1 2 34 5
M1 3 2 1
3 switch
JU1
to J12-5 J2-5
18
Exhaust fan motor MED HI 6 (optional; see
J20 5 A2
A2-J2 4 J12-4 J2-4
notes 3 & 4)
1 2 3 4 5
3
Y
BL
R
W
Control cable 12 2 K4 J12-3 J2-3 Damper motor
J9 1 J8-1 J12-2 J2-2 J3-2
J12
120 V
to A1-J17 J14
! WARNING
Y
BL
2
R
W
Control cable 120 V, 60 Hz W1 1 Y remote control J14-1 interlock
A3 J3 K5
(see notes 3 & 4) (optional; see
to A1-J15 J14-2
K1
notes 3 & 5)
K3
G Line voltage factory wiring J15
Class 2 low voltage factory wiring From
Class 2 low voltage field wiring supply motor
1 2 34 5
Critical characteristic. nc
J17
CPU From
NOTES COLOR CODE J2 J16 exhaust motor
A3
1 2 34 5
VE0346A
servicing instructions (refer to wiring diagram for proper fuse rating) and verify the product. If the replaced fuse blows, it may
If the fuse blows, unplug the product and check the polarity and voltage output from the outlet. Replace the fuse as per the
be a short-circuit and the product must be discarded or returned to an authorized service center for examination and/or repair.
• This product is equipped with an overload protection (fuse). A blown fuse indicates an overload or a short-circuit situation.
• Risk of electric shocks. Before performing any maintenance or servicing, always disconnect the unit from its power source.
7. BALANCING THE UNIT
HIGH
LOW
1. Place the magnehelic gauge on a level surface and adjust it to zero. FRESH AIR FLOW
2. According to the airflow to be measured, connect tubing from gauge
to STALE air flow or FRESH air flow pressure taps (see illustration at
right). HIGH
Be sure to connect the tubes to their appropriate high/low fittings. If
the gauge drops below zero, reverse the tubing connections.
LOW
STALE AIR FLOW
VP0027A
The unit balancing chart and the unit preset speed table are affixed on the unit, behind the
right panel (circled area on illustration at right)
VD0388
19
7. BALANCING THE UNIT (CONT’D)
NOTE: The unit is considered balanced even if there is a difference of ± 10 CFM (or ± 5 L/s or 17 m³/h) between the two airflows.
The special design of these units, combined with the X-Touch/Gold-Touch main wall control, offer many preset speeds ranges
according to the unit models. See preset speeds table example below.
UNIT MODEL
TURBO CONT
PRESET
HIGH SPEED LOW SPEED 20/40/60 MIN. RECIRCULATION SPEED
SPEEDS NO.
(CFM@ 0.4 IN. W.G.) (CFM@ 0.2 IN. W.G.) CONTROL STALE AIR (CFM@ 0.4 IN. W.G.)
(CFM@ 0.4 IN. W.G.)
__ From 60 to 250
From 30 CFM to
75% of adjusted
TURBO speed
From 60 to 250 From 60 to 250
20
7. BALANCING THE UNIT (CONT’D)
PROG flashes on screen as long as you This label section shows which speed is
are in Program Mode Setting menus (preset being set (e.g.: TURBO).
speeds or custom speeds). It disappears TURBO
from screen when all settings are done or Arrow shows where to install the
when there is no change after 60 seconds. magnehelic gauge tubing
(e.g.: EXHAUST).
AND % HUM OR
TURBO TURBO OR
Press and hold both PROG start flashing. Press any key to enter
% HUM and TURBO A 10-second program mode. If there
keys for 10 seconds. countdown appears. is no key pressed before
the end of the countdown,
the unit will go back to its
previous mode.
Choose between two options: • 01, 02, etc.: Preset speeds (balance the unit only, faster option)
• _ _: Custom speeds (adjust TURBO speed and balance the unit, then set CONT,
20/40/60 min. control and RECIRC speeds).
Write selected
MODE preset speed
on label affixed
OR % HUM
on the unit for
TURBO
future reference. Press % HUM key
Press on MODE key to to accept chosen
01 speed value preset speed.
(preset value) will raise the value.
appear on screen. Press on TURBO key to
lower the value.
NOTE: From 01 value, pressing on TURBO key will access to custom speed settings (see page 23).
21
7. BALANCING THE UNIT (CONT’D)
I Adjust stale air TURBO speed (or press % HUM key to keep it as is).
NOTE: The following shown values are example. The real values vary according to the preset speed chosen, the unit
installation, etc.
TURBO
MODE
Write selected
TURBO
airflow percentage
22
7. BALANCING THE UNIT (CONT’D)
TURBO
MODE
Write selected
TURBO
airflow percentage
OR on label affixed on % HUM
TURBO TURBO the unit for future
reference. Press % HUM key
Install tubing on fresh Press on MODE key to raise to accept chosen
airflow pressure taps the value. percentage.
and take the reading. Press on TURBO key to lower
the value. Check the magnehelic
Ajust the airflow until the gauge along with the unit
reading on magnehelic gauge balancing chart until the
reaches the stale airflow value. desired airflow is reached.
If you have selected the preset speed balancing at C, the balancing procedure is completed.
If you have selected the custom speed balancing, continue with the following:
CONT
CONT
OR on label affixed on % HUM
TURBO the unit for future
reference. Press % HUM key
CONT
Press on MODE key to raise to accept chosen
the value. percentage.
Press on TURBO key to lower
the value. Check the magnehelic
Ajust the airflow until the gauge along with the unit
reading on magnehelic gauge balancing chart until the
reaches the desired CFM value. desired airflow is reached.
23
7. BALANCING THE UNIT (CONT’D)
TURBO the unit for future
reference. Press % HUM key
Press on MODE key to raise to accept chosen
the value. percentage.
Press on TURBO key to lower
the value. Check the magnehelic
Ajust the airflow until the gauge along with the unit
reading on magnehelic gauge balancing chart until the
reaches the desired CFM value. desired airflow is reached.
OR airflow percentage
on label affixed on % HUM
TURBO
the unit for future
reference. Press % HUM key to
Connect the Press on MODE key to raise accept chosen percentage
magnehelic gauge to the value. and exit the menu OR
FRESH airflow taps. Press on TURBO key to lower wait 60 seconds.
the value.
Ajust the airflow until the Check the magnehelic
reading on magnehelic gauge gauge along with the unit
reaches the desired CFM value. balancing chart until the
desired airflow is reached.
NOTE: The adjusted airflow values are stored within the unit, so, if needed, any X-Touch/Gold-Touch main control can be used to
adjust the unit speeds and balance the unit again. If a power failure occurs, the unit will keep these setting values. To change
the setting values, go to step G and follow the procedure, the new values will replace the previous ones.
24
8. TROUBLESHOOTING
If the unit does not work properly, reset the unit by unplugging and then replug it. If it is still not working properly, refer to the
table below.
If the LED of the unit is flashing, this means the unit sensors have detected a problem. See the table below to know where the problem
occurs on the unit.
LED SIGNAL ERROR CODE ON
ERROR TYPE ACTION UNIT STATUS
ON UNIT CONTROL SCREEN
LED flashes E21 Cold side thermistor • Ensure J12 connector is properly connected Unit works but will
GREEN error. and its wires are not damaged. If they are defrost frequently.
(double blink correct:
every • Replace the damper system assembly.
2 seconds).
LED flashes E22 Warm side • Ensure J20 connector is properly connected Unit does not work.
GREEN thermistor error. and its wires are not damaged. If they are
(2 blinks per correct:
second; faster • Replace the warm side thermistor.
blink).
LED flashes E23 Damper system • Go to point 6 in next table. Unit does not work.
AMBER. error.
E25 and E26 Open door while the • Reset the X-Touch/Gold-Touch wall control
alternately unit is in function or by pressing on MODE and %HUM keys for
magnetic switch bad 10 seconds.
contact. • Check if the unit door is properly closed and for
the door magnet to be properly seated onto the
door. If not, correct the situation, close the door
and reset the X-Touch/Gold-Touch wall control
by pressing on MODE and %HUM keys for
10 seconds.
• Ensure J11 connector is properly connected
LED flashes and its wires are not damaged. If not, correct the
RED situation, close the door and reset the X-Touch/
(one blink Gold-Touch wall control by pressing on MODE Unit does not work.
every and %HUM keys for 10 seconds.
2 seconds). • Using a flat blade screwdriver, jump J11, reset
the X-Touch/Gold-Touch wall control by
pressing on MODE and %HUM keys for
10 seconds and set the unit on CONT.
If the LED is still flashing, go to point 8 in next
table for motor diagnosis.
E25 Cold side motor • Go to point 8 in next table.
error.
E26 Warm side motor • Go to point 8 in next table.
error.
LED flashes Unit is on protection • If outside temperature is colder than -25°C, it Unit perform a special
RED mode. could be normal for the unit to enter in defrost and go back to
(2 blinks per protection mode. There is no action to be taken. its previous mode when
second; faster • If the snowflake icon appears frequently, the completed.
blink). airflows of the unit may be not balanced or the
damper system may be damaged. See point 7
in next table.
25
8. TROUBLESHOOTING (CONT’D)
26
8. TROUBLESHOOTING (CONT’D)
27
NOTES
28